HEATLOAD SUMMARY SHE

PROJECT NAME MEDTRONICS


LOCATION MUMBAI
SOLAR GAIN U FACTOR 0.54
TRANSMISSION GAINS 1.13
ADP 54
STANDARD SGU PARAMERTERS
AREA DETAILS ELECTRICAL PO

AREA NAME OCCUPANCY AREA SQ.MM. AREA SQ.FT. HEIGHT IN FT.

CABIN-2 3 12619000 135.8 12


CABIN-3 3 13930741 149.9 12
CABIN-4 3 13285734 143.0 12
CABIN-5 3 14183569 152.7 12
AD SUMMARY SHEET - STANDARD SGU ADP 54

CONDITIONS - OFFICE AREA


DEG F. DBT WBT
OUTSIDE 104 76
ROOM 74 55
DIFFERENCE 30 21.00

ELECTRICAL POWER HEAT LOAD

VENTILATION
NUMBER OF EQUIPEMENT CFM FOR LOAD IN TR DEHUM. CFM / SQ.FT AREA
PC LOAD(WATTS) CFM
CALCULATION

1 80 27.12 1.05 572 4.21


1 80 29.93 1.15 625 4.17
1 80 28.55 1.06 573 4.01
1 80 30.47 1.20 660 4.32
- OFFICE AREA PROJECT NAME MEDTRONICS
GR/LB RH% LOCATION MUMBAI
90 62.2 SOLAR GAIN U FACTOR 1
70 50 TRANSMISSION GAINS 1.13
20 ADP 60.2

LOAD AREA DETAILS

SQ.FT / TR CFM / TR Additional Additional TR AREA NAME OCCUPANCY


CFM

129 543 612 0.39 CABIN-2 5


131 545 673 0.43 CABIN-3 5
135 541 613 0.39 CABIN-4 5
127 548 713 0.46 CABIN-5 5
HEATLOAD SUMMARY SHEET - STANDARD CLEAR GLASS ADP 60.2

AREA DETAILS ELECTRICAL POWER

VENTILATION
AREA SQ.MM. AREA SQ.FT. HEIGHT IN FT. NUMBER OF EQUIPEMENT CFM FOR
PC LOAD(WATTS)
CALCULATION

12619000 136 12.0 1 80 27.12


13930741 150 12.0 1 80 29.93
13285734 143 12.0 1 80 28.55
14183569 153 12.0 1 80 30.47
GLASS ADP 60.2

CONDITIONS - OFFICE AREA


DEG F. DBT WBT GR/LB RH%
OUTSIDE 104 76 90 62.2
ROOM 74 55 70 50
DIFFERENCE 30 21.00 20

HEAT LOAD

LOAD IN TR DEHUM. CFM / SQ.FT AREA SQ.FT / TR CFM / TR


CFM

1.44 1184 8.72 94 821


1.58 1298 8.66 95 824
1.45 1186 8.30 99 819
1.66 1373 8.99 92 827