You are on page 1of 2

VOLTAGE DROP CALCULATION (STAFF BUILDING)

PHASE WIRE
CKT NO. DESCRIPTION K L I VD %VD
1Ø 3Ø CM SET
1 SERVICE ENTRANCE TO MAIN PANEL / 12 52 127.7 167800 1 0.95 0.41
2 MAIN PANEL TO PP1 / 12 23 93.50 66360 1 0.78 0.34
3 PP1 TO THE FARTHEST C.O. / 12 48.0 6.26 6530 1 1.10 0.48

TOTAL 2.83 V 1.23 %

VOLTAGE DROP CALCULATION (ADMIN BUILDING)


PHASE WIRE
CKT NO. DESCRIPTION K L I VD %VD
1Ø 3Ø CM SET
1 SERVICE ENTRANCE TO PP1 (ADMIN BLDG) / 12 38 84 66360 1 1.15 0.50
2 PP1 TO FARTHEST ACU / 12 32 14.50 10380 1 1.07 0.47
3 PP1 TO THE FARTHEST C.O. / 12 62.0 5.48 6530 1 1.25 0.54

TOTAL 3.48 V 1.51 %

VOLTAGE DROP CALCULATION (WORKSHOP BUILDING)


PHASE WIRE
CKT NO. DESCRIPTION K L I VD %VD
1Ø 3Ø CM SET
1 SERVICE ENTRANCE TO PP1 (WORKSHOP BLDG) / 12 43 61.4 52620 1 1.20 0.52
2 PP1 TO FARTHEST ACU / 12 39 14.50 10380 1 1.31 0.57
3 PP1 TO THE FARTHEST C.O. / 12 53.0 6.26 6530 1 1.22 0.53

TOTAL 3.73 V 1.62 %


VOLTAGE DROP CALCULATION (WAREOUSE, MRF BUILDING)
PHASE WIRE
CKT NO. DESCRIPTION K L I VD %VD
1Ø 3Ø CM SET
1 SERVICE ENTRANCE TO PP1 (WORKSHOP BLDG) / 12 26 61.4 16210 1 2.36 1.03
2 PP1 TO L.O. / 12 39 1.57 6530 1 0.23 0.10
3 PP1 TO THE FARTHEST C.O. / 12 46.0 5.48 6530 1 0.93 0.40

TOTAL 3.52 V 1.53 %

VOLTAGE DROP CALCULATION (DG HOUSE & BOP MCC)


PHASE WIRE
CKT NO. DESCRIPTION K L I VD %VD
1Ø 3Ø CM SET
1 SERVICE ENTRANCE TO PANEL (DG HOUSE) / 12 32 139.71 167800 1 0.55 0.24
2 PANEL (DG HOUSE) TO BOP MCC / 12 42 41.02 26240 1 1.36 0.59
3 BOP MCC TO FARTHESR OUTLET / 12 33.0 5.48 6530 1 0.58 0.25

TOTAL 2.49 V 1.08 %

Prepared by:
Engr. ISIDRO C. RABACCA
PRC ID No: 0066621
PTR No: 1943592