Danfoss FC Control Profile The control word is used to send commands from a
master (PLC or PC) to a slave (frequency converter).
Control Word according to FC Profile (CTW)
To select FC protocol in the control word, par. 8-10
Control word profile must be set to FC protocol [0].
Please refer to Application Examples for an example of a control word telegram using PPO type 3.
NB!:
In par. 8-56 Preset reference select a selection is made to define how Bit 00/01 gates with the
corresponding function on the digital inputs.
NB!:
In par. 8-50 Coasting select a selection is made to define how Bit 03 gates with the corresponding
function on a digital input.
NB!:
If Freeze output is active, the frequency converter can only be stopped by the following:
NB!:
In par. 8-53 Start select a selection is made to define how Bit 06 Ramp stop/start gates with the
corresponding function on a digital input.
NB!:
In par. 8-55 Set-up select a selection is made to define how Bit 13/14 gates with the corresponding
function on the digital inputs.
Bit 15 Reverse
Bit 15 = "0" causes no reversing.
Bit 15 = "1" causes reversing.