You are on page 1of 4

VENTUS AIRCONDITIONING PVT. LTD.

1/1, DJ Park, Opp. Holaram Colony, Sadhu Waswani Road, Nashik 422 002
Tel. : + 91 253 2314403, 2314404, 2314400, email : sachin@vapl.co

JOB NAME : Annexure VII PROP. No. : People Ventilation 1125


SPACE : Floor DATE : Area Ventilation 193.74
Total 1319
AREA in SQFT 3229 No. OF PEOPLE 150.0 Volume 51664
HT OF AREA in FEET 16.00 CFM PER PERSON 7.50 1 ACPH 861
AIR CHANGE REQD. 1.53 Ventilation Reqd. 1.53
CFM VENTILATION ( AREA ) 1319 CFM VENTILATION ( PEOPLE ) 1125

CFM VENTILATION FOR FURTHER CALCULATION 1319

DESIGN CONDITIONS DR. BULB WT. BULB RH SP. HUMIDITY


OUTSIDE CONDITIONS 104.000 0 F 75.599 0 F 28 % 97.619 GR./ LB
INSIDE CONDITIONS 77.000 0 F 65.378 No Strict Control 81.968 GR./ LB
DIFFERENCE 27.000 0 F 15.651 GR./ LB

SOLAR GAIN THROUGH GLASSES OUTSIDE AIR LOAD


AREA BTU/SQFTFACTOR BTU/HR CFM GR. DIFF.BYPASSFACTOR BTU/HR
North 0 11 0.56 0 1319 15.651 0.12 0.68 1684 Dining Gym
South 0 11 0.56 0 PEOPLE 150.0 205 30750 People 270 525
East 0 11 0.56 0 ROOM LATENT HEAT WITH SAF 5 % 34056
West 0 165 0.56 0 ROOM TOTAL HEAT 137260
SOLAR & TRANSMISSION GAIN - WALLS OUTSIDE AIR HEAT
North 780 24 0.34 6365 SENSIBLE 1319 27.000 0.88 1.08 33840
South 780 36 0.34 9547 LATENT 1319 15.651 0.88 0.68 12351
East 986 38 0.34 12739 SUB TOTAL 46191
West 986 32 0.34 10728
ROOF 3229 47 0.48 0 0
OTHER TRANSMISSION GAIN TOTAL HEAT 183451
ALL GLS. 0 27.000 1.13 0
PARTI. 0 22.000 0.34 0 SENSIBLE HEAT FACTOR 0.75
CEILING 3229 22.000 0.40 0 0 SELECTED A.D.P. 54.0
FLOOR 3229 22.000 0.52 0 0 DEHUMIDIFIED RISE 20.24
OUTSIDE AIR LOAD
CFM TP. DIFF FACTOR
1318.7 27.000 0.12 1.08 4615
INTERNAL HEAT Dining Gym
RESULTS
PEOPLE 150.0 245 36750 People 280 325
EQUIP. 5 3.4 17 GRAND TOTAL HEAT 18.11 TR 188954
LIGHTS 3229 3.4 1.00 1 10979 DEHUMIDIFIED AIR CFM 4721
SUB TOTAL 91739 LOAD AS PER CFM 11.80

TOTAL SENSIBLE HEAT + SAF 12.5 % 103204 MINIMUM REQUIRED TONNAGE ( TR ) 18.11

Note : 1 West side glasses brings in lot of heat. Kindly use reflector film + curtains/blinds on windows.

Location Area Tonnage Air Qty CFM VENTILATION FOR FURTHER CALCU
Results (Sqft) (TR) (CFM)
0 3229 18.11 4721 1319
FOR FURTHER CALCULATION