Inverter compressors

Operating conditions for A/C systems in Europe

Fixed-speed solution
• The cooling system with the compressor is
Bin hours Ambient °C
dimensioned to meet peak load demand
250

• Peak load demand happens rarely during 40

the operation time 200


35

• Depending on country, a fixed speed 150


30
compressor (FS) operates at either 50 or 60
rps (revolutions per second) 100
25

• The FS will cycle to adjust to the cooling 50 20

demand at any given time


0

10 20 15 20 25 30 35 40 45 50 55 60 65 70 75 80 90 95 100 105 110 115 120 125


Part load ratio %
Bin hours Ambient temp

Source: EN14825

Cooling demand vs capacity


VS frequency % as data label
Variable speed solution

120,00

• The variable speed (VS) compressor


100,00
100% system is also dimensioned for peak load
Cooling demand/capacity [kW]

demand
80,00

60,00
64%
• The VS will lower the speed and thereby
the capacity yield to meet the required
40,00 25%
37%
demand at any given time
25%

20,00 • Because the VS operates at up to twice the


speed of an FS only the half swept volume is
0,00
15 20 25 30 35 40
requied
Ambient temperature [*C]

Cooling demand (setpoint) [kW] Cooling capacity FS [kW] Cooling capacity VS [kW]

Source: Danfoss Advanced System Simulation Services, A3S

Example of Piping

• Pipe dimensions ensuring correct velocities 0.5%


0.5%
0.5%
for oil return must be carefully calculated for Velocity = > 4 m/s

the whole speed range to enable sufficient


13 ft/s
System design

lubrication at all operating conditions


25 - 40 ft/s
Velocity = 8 - 12 m/s

• Oil return can be managed by a boost


feature in the controller/compressor drive.
25 - 40 ft/s
Velocity = 8 - 12 m/s

Active oil management systems and/or oil


separator are optionable 0.5%

• Together with a Danfoss micro channel heat


exchanger (MCHE) the VSC system can
reduce the system charge significantly

• Adapts and adjusts the speed to the


required capacity at any time.

• Prevents cycling with repeated energy


EER (Energy Efficiency Ratio) on a Chiller
consuming start-stops
Comparison between FS and VS

8.00 • Significant noise reduction


7.00
• No need for soft-start or star-delta switches
Benefits

6.00

5.00 • Low inrush current with variable speed


4.00
• Safe operation even with unstable power
3.00 grids
2.00
• Reduced temperature fluctuations
1.00

0,00
15 20 25 30 35 40 • Reduced refrigerant flow ensures optimal
Ambient temperature [*C] operating conditions for the evaporator and
Fixed-speed scroll compressors Variable-speed scroll compressors condenser

• When commissioning an inverter


compressor or condensing unit, please
follow instructions when connecting, setting,
Support

and adjusting the electronics.

For assistance, please refer to the manuals


found here.

• The Danfoss Compressor Drive (CDS) can


communicate via RS 485 to other control
units

Click to view
Discover how we can help you with our simulation services A3S

Scroll inverter compressors Turbocor inverter compressors Reciprocating inverter compressors