(MCPs): UL 508 and UL 489, and provided as shown. Provide MSCPs that
consist of an adjustable instantaneous trip circuit breaker used only in
conjunction with a combination motor controller which provides coordinated
motor branch-circuit overload and short-circuit protection. Rate MSCPs in
accordance with the requirements of NFPA 70.
2.17 TRANSFORMERS
(2) 180 degrees C insulation for transformers rated 10 kVA and less,
with temperature rise not exceeding 115 degrees C under full-rated
load in maximum ambient of 40 degrees C.
2.18 MOTORS
SECTION 26 20 00 Page 21