3Bases Expansion Project - Tabuk W912ER-16-C-0004

(MCPs): UL 508 and UL 489, and provided as shown. Provide MSCPs that
consist of an adjustable instantaneous trip circuit breaker used only in
conjunction with a combination motor controller which provides coordinated
motor branch-circuit overload and short-circuit protection. Rate MSCPs in
accordance with the requirements of NFPA 70.

2.17 TRANSFORMERS

Provide transformers in accordance with the following:

a. NEMA ST 20, general purpose, oil-type, self-cooled, ventilated sealed.

b. Provide transformers in NEMA 3R enclosure.

c. Transformer insulation system:

(1) 220 degrees C insulation system for transformers 15 kVA and


greater, with temperature rise not exceeding 115degrees C under
full-rated load in maximum ambient of 40 degrees C.

(2) 180 degrees C insulation for transformers rated 10 kVA and less,
with temperature rise not exceeding 115 degrees C under full-rated
load in maximum ambient of 40 degrees C.

d. Transformer of 150 degrees C temperature rise: capable of carrying


continuously 100 percent of nameplate kVA without exceeding insulation
rating.

e. Transformer of 115 degrees C temperature rise: capable of carrying


continuously 115 percent of nameplate kVA without exceeding insulation
rating.

f. Transformer of 80 degrees C temperature rise: capable of carrying


continuously 130 percent of nameplate kVA without exceeding insulation
rating.

g. Transformers: quiet type with maximum sound level at least 3 decibels


less than NEMA standard level for transformer ratings indicated.

2.17.1 Specified Transformer Efficiency

Transformers, indicated and specified with: 13.8kV primary, 80 degrees C


or 115 degrees C temperature rise, kVA ratings of 37.5 to 100 for single
phase or 30 to 500 for three phase, energy efficient type. Minimum
efficiency, based on factory test results: not be less than NEMA Class 1
efficiency as defined by NEMA TP 1.

2.18 MOTORS

Provide motors in accordance with the following:

a. NEMA MG 1 except provide fire pump motors as specified in Section


21 30 00 FIRE PUMPS.

b. Hermetic-type sealed motor compressors: Also comply with UL 984.

c. Provide the size in terms of kW, or kVA, or full-load current, or a


combination of these characteristics, and other characteristics, of

SECTION 26 20 00 Page 21