ProSafe-RS/ProSafe-RS Lite
General RS4E5000, RS4E5100
Specifications Automation Design Suite (AD Suite)
Engineering Server Function
GS 32P04C10-01EN Safety System Engineering and Maintenance Function

 GENERAL
Automation Design Suite (AD Suite) provides an integrated engineering environment for configuring and maintaining
overall instrumentation including plant instrumentation, safety instrumentation, and maintenance management.
This software is available for ProSafe-RS and ProSafe-RS Lite (*1).
*1: When used for ProSafe-RS Lite engineering, it has been supported since ProSafe-RS R4.06.

 FUNCTIONAL SPECIFICATIONS
 Overview of AD Suite
The AD Suite for implementing ProSafe-RS/ProSafe-RS Lite engineering consists of Engineering Server Function
to manage project data and Safety System Engineering and Maintenance Function to configure and manage the
ProSafe-RS/ProSafe-RS Lite system. The Engineering Server Function and the Safety System Engineering and
Maintenance Function can run on a single computer.

AD Suite

Safety System Engineering Engineering Server Function


and Maintenance Function (Automation Design Server)
(Safety Engineering Station)

Automation
Automation
Design Server
Design organizer
Management Tool

Automation
SCS Manager Design Master
Database

F01E.ai

Figure Software Configuration of AD Suite


The AD Suite manages the histories of engineering changes done by a user in the form of a database. Change
information contains a change set ID, user name, date/time , details, and comment.

 ENGINEERING SERVER FUNCTION


RS4E5000 Engineering Server Function is a software license to use the AD Server.
The Engineering Server Function has the following functions.

 Automation Design Master Database (ADMDB)


All RS project data is stored in the ADMDB. Information on change histories of the project data is also stored in this
database.

 Automation Design Server Management Tool (ADS Management Tool)


This software manages the AD Server.

Yokogawa Electric Corporation GS 32P04C10-01EN


2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan ©Copyright Nov. 2015 (YK)
2nd Edition Jan. 22, 2021 (YK)
<<Contents>> <<Index>> 2
 SAFETY SYSTEM ENGINEERING AND MAINTENANCE FUNCTION
RS4E5100 Safety System Engineering and Maintenance Function is a software license to use the safety engineering
station (SENG).
The Safety System Engineering and Maintenance Function has the following functions.

 Automation Design Organizer (AD Organizer)


The AD Organizer implements engineering in the AD Suite. The AD Organizer provides an interface to each tool
necessary for ProSafe-RS/ProSafe-RS Lite engineering and maintenance.
The AD Organizer also displays information on change histories of the project data stored in the ADMDB.

 SCS Manager
The SCS Manager contains basic functions to configure and manage the ProSafe-RS/ProSafe-RS Lite. The table
below shows the functions of the SCS Manager.

Table The Functions of SCS Manager (1/2)

Category Function Description


Creates an SCS (Safety Control Station) project (*1)
Project creation function that contains an SCS database.
Database generation function Constructs databases that run on the SCS.
Database
Controls a history of changes by backing up databases
Version control function on an SCS project basis.
Self-document function Prints a document defined an SCS project.
SCS definition Defines SCS parameters.
Defines parameters and the configuration of I/O
I/O definition modules.
Defines variables, parameters and the like, which are
Variable definition used by the application logic.
Defines the application logic using the FBD, LD and ST
POU(*2) definition language.
Application
Sequence-of-events recorder (SOER) Defines parameters and conditions for collecting event
function definition information (such as trip signals).
Defines function blocks to override SCS data from the
Override definition CENTUM VP HIS.
Inter-SCS safety communication Defines inter-SCS safety communication.
definition
SCS Link Transmission Definition Defines inter-SCS data transmission.
Modbus Defines parameters for operating the communication
Communication module definition
communication module as Modbus master and Modbus slave.
Downloads all of the SCS project definitions to the
Off-line download function SCS.
Downloads online to the SCS only the differential
Online change download function (*3) data between the SCS project definition data last
downloaded and the most updated data.
Download When a CPU module is replaced, the master database
Master database off-line download that was last downloaded is downloaded to the SCS
function again. (*4)
When an I/O module is replaced, the I/O module
I/O module definition download function definition information that was last downloaded is
downloaded to the SCS again. (*4)
*1: An application for an SCS unit is called as an SCS project. A group of SCS projects to implement an application is called as
an RS project.
*2: POU (Program Organization Unit): A generic term indicating programs, function blocks, and functions.
*3: Depending on the changes to be made, the online change download function cannot be executed.
*4: Used for hardware replacement.

All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 32P04C10-01EN Jan. 22, 2021-00
<<Contents>> <<Index>> 3
Table The Functions of SCS Manager (2/2)

Category Function Description


Limits changes in SCS projects by restricting
Database access control function unauthorized users' access.
Misoperation prevention function Prevents users from misoperating the SCS.
Security
Permits only authorized users to change the security
SCS access control management level of the SCS.
function Generates SCS tag lists.
Forcing Forcing function Externally locks or changes SCS data in use, from outside.
Supports a test to check whether the application logic is
Test Test function (*5)
designed correctly.
Safety-related check function Inspects the application logic in terms of safety.
Engineering support
Help function Displays help documents.
Displays the status of I/O modules and SCS operation on the
SCS status display function SCS Operation Status Display window and the SCS Status
Management window.
Displays diagnostic information messages, which are
produced from the results of SCS’s self-diagnosis, in
chronological order in the Diagnostic Information window.
Maintenance support Diagnostic information display function
These messages can be re-displayed for confirmation, or
deleted. A help dialog can be displayed for each diagnostic
information message.
Allows monitoring of the application logic being executed on
Online monitoring function
the SCS.
SOE viewer function Displays event information (such as trip signals).
*5: Refer to the “Test Function” of the GS “Safety Control Functions Package” (GS 32P03B10-01EN, GS 32P03B20-01EN, GS
32P03B25-01EN, GS 32P03B30-01EN, or GS 32P53B30-01EN).

 SYSTEM REQUIREMENTS
Refer to the GS “ProSafe-RS Safety Instrumented System Overview (for Vnet/IP)” (GS 32P01B10-01EN),
“ProSafe-RS Safety Instrumented System Overview (for Vnet/IP-Upstream)” (GS 32P01B30-01EN), or “ProSafe-RS
Lite Safety Instrumented System Overview” (GS 32P51B10-01EN).

 MODEL AND SUFFIX CODES


RS4E5000 Engineering Server Function

Description
Model RS4E5000 Engineering Server Function
-V Software license
Suffix
1 Always 1
Codes
1 English version

Note: Place an order of this package using the suffix codes of “RS4E5100 Safety System Engineering and Maintenance
Function.” This package cannot be purchased independently.

RS4E5100 Safety System Engineering and Maintenance Function

Description
Model RS4E5100 Safety System Engineering and Maintenance Function
-V Software license

Suffix 1 For Engineering and Maintenance Function & Engineering Server Function
Codes 2 Engineering and Maintenance Function
1 English version

Note: A license of “RS4E5000 Engineering Server Function” per RS project is mandatory. Place an order of this package by
specifying the model code of “RS4E5100-V11”.

All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 32P04C10-01EN Jan. 22, 2021-00
<<Contents>> <<Index>> 4
 ORDERING INFORMATION
Specify the model and suffix code(s).

 TRADEMARK ACKNOWLEDGMENT
The names of corporations, organizations, products and logos herein are either registered trademarks or trademarks
of Yokogawa Electric Corporation and their respective holders.

All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 32P04C10-01EN Jan. 22, 2021-00
Subject to change without notice.