dependent upon the magnitude of the current, which is D. Short Circuit Breaking Value
dependent on the time from fault inception. This is done for The short-circuit breaking current is the r.m.s.-value of
various types of faults (three phase, phase-to-phase, double- the short-circuit current at switching instant such as at
phase-to-ground, and phase-to-ground) at different locations circuit breaker operating time. While opening the contacts
throughout the system. The information is used to select of the circuit breaker, the arc inside the breaker will heat up
fuses, breakers, and switchgear ratings in addition to setting the installation, which also depends on the breaking time.
protective relays [4].
Despite careful planning and design, excellent
maintenance and thorough operation of the system, faults
for example short circuits in power system are still
unavoidable. It is vital that short circuit conditions be taken
seriously as short circuit currents are usually many times
greater than its rated currents, high dynamic and thermal
stress and in certain cases, unacceptable voltages which may
cause danger must be expected. Short circuit currents,
according to IEC 60 909 results from a short circuit within
an electrical network. The causes and effects of short circuit
as listed in Table I
TABLE I
CAUSES AND EFFECTS OF SHORT CIRCUITS
Causes Effects
1. Over temperatures due to 1. Power supply
excessively high interruptions
overcurrent 2. System component
2. Disruptive changes damage or destruction Fig 1. Importance of short-circuit currents and definition of tasks as per IEC
causes by overvoltage 3. Development of 60781, IEC 60865, IEC 60909 and IEC 61660
3. Arcing caused by unacceptable mechanical
moisture together with and thermal stresses in III. SHORT CIRCUIT ANALYSIS AND TECHNIQUES
impure air especially on electrical operational A balanced 3-phase also known as symmetrical or
insulators equipment balanced fault implies that all three phases of the power
system are simultaneously short-circuited to each other
The typical time course of a short-circuit current shown through a direct or "bolted" connection [6]. Although the
in the Fig 1. can be measured at high-voltage installations in probability of this happening is small, relative to the
the vicinity of power stations with synchronous generators, probability of other types of unbalanced faults occurring
characterized by decaying ac and dc components of the (phase-to-ground and phase-to-phase faults), nevertheless
current. It is assumed that the short-circuit is switched-off the balanced 3-phase fault calculation method is used for the
approximately 14 periods after its initiation which seems a short-circuit study for the following reason [7]:
rather long duration but was chosen for reason of a better i. 3-phase fault produces the largest short-circuit current
visibility in the figure. The four parameters of the short- magnitude. Hence, this worst-case result is then used
circuit current which would be focused on are as listed as the basis to select the short-circuit capabilities of
below [5]. switchgear from manufacturers' tables.
A. Total Time Duration ii. The simplest short-circuit calculations method because
symmetry of the fault connection permits us to
The total time duration of the short-circuit current consider only one of the three phases.
consists of the operating time of the protection devices and
the total switchgear breaking time The other types of unbalanced short-circuit faults are
B. Peak Short Circuit Current important in selecting the time-current characteristics and
The peak short-circuit time current, which is the maximal settings of phase-overcurrent and ground-fault protective
instantaneous value of the short-circuit current, occurs devices to provide selective coordination. This coordination
approximately a quarter period after the initiation of the assures service continuity and minimizes damage to
short-circuit. As electromagnetic forces are proportional to switchgear and load equipment. However, unbalanced fault
the instantaneous current value, the peak short-circuit calculations are more difficult to perform for industrial and
current is necessary to know in order to calculate the forces commercial power systems and require knowledge of the
on conductors and construction parts affected by the short- method of symmetrical components.
circuit current. The 3-phase fault current calculation basically uses the
normal circuit theory methods which are very simple and
C. r.m.s Value easy to use. Basically, two methods of 3-phase fault
The r.m.s.-value of the short-circuit current combined calculation will be employed; MVAF method and Inominal.
with the total time duration is a measure of the thermal However, the availability of computer based power system
effects of the short-circuit. analysis programs have enabled easier and simpler short
3
circuit analysis procedures and it is more widely used in IV. ESTIMATION OF TRANSFORMER FAULT CURRENT
complex networks as it is less time consuming. The transformer fault current was calculated both
A. MVAF Method manually and using the Transformer Fault Current
The MVAF method is a modification of the Ohmic Calculator. Samples of the calculations for Transformer T1
method where the impedance of a circuit equals the sum of are as shown below based on its rated values of:
the impedances of components constituting the circuit [8]. S = 2.0 MVA
Using the admittances, it follows that the reciprocal of the V = 11k / 433V
system impedance is the sum of the reciprocals of the I = 104.97 / 2666.8 A
admittances of the components. By very definition, the Z = 5.93%
circuit component admittance is the maximum current or A. MVAF Method
KVA at unit voltage which would flow through the circuit Using Equation (2),
or component to a short circuit or fault when supplied from MVAB 2.0M
a source of infinite capacity. MVAF(T 1 ) = = = 33.726 MVA
Z pu 0.0593
The calculation of the MVA fault, MVAF and fault
current, IF can performed with the following equations [9 & Using Equation (3),
10]. MVAF 33.726 M
I F,primary(T 1 ) = = = 1770.16 A
MVAF = 3 × Vline × I F (1) 3 Vp 3 × 11k
MVAB MVAF 33.726 M
or MVAF = (2) I F ,sec ondary (T 1) = = = 44970.4 A
Z pu 3 Vp 3 × 433
Where MVAB is the MVA base and Zpu is the impedance
between the supply source and the fault location in per unit. B. Inominal Method
Hence, the three-phase fault current can be determined Using Equation (4),
using equation (3). I 104.97
I F , primary (T 1) = no min al = = 1770.15 A
MVAF Z pu 0.0593
IF = (3)
3V I 2666.8
I F ,sec ndary (T 1) = no min al = = 44971.33 A
B. Inominal Method Z pu 0.0593
This method is employed when the magnitudes of the
nominal current and total impedance in per unit are known C. Transformer Fault Current Calculator
and it is very straight forward and simple. Hence, the fault After analyzing the Transformer Fault Current Calculator
current can be determined by dividing the magnitude of the [11], it was discovered that the secondary fault current was
nominal current with the total impedance in per unit as calculated using equation (6) below:
given in equation (4).
I no min al Secondary Transformer Fault Current,
IF = (4) aI PF
Z pu I Fault = + 4 I FL ,in + 5 I FL, sync (6)
⎛ ⎞
Where, Inominal = Rated current in ampere, and ⎜1 + 3 V P I PF Z ⎟
⎜ 100 S ⎟
Zpu = Total impedance in per unit ⎝ ⎠
VS
Or; IF = (5) Where,
3 Z pu a = Ratio (Vp / Vs)
IPF = Available primary fault current
Total Impedance, Z pu = Z S + Z R (3.11)
VP = Primary voltage
Z = Transformer impedance in %
Where, VS = Source voltage S = Transformer Rating (MVA)
ZS = Source impedance in per unit IFL, in = Full load current of induction machines
ZR = Impedance of protected element in per unit IFL, sync = Full load current of synchronous machines
C. Computer Aided Short Circuit Analysis
The results of the secondary transformer fault currents are
There are many computer aided power system analysis as shown in Fig 1.. A sample calculation of the secondary
programs that are equipped with comprehensive analysis transformer fault current based on Transformer T1 is as
platform for the design, simulation and operation of shown below.
industrial power system. The short circuit analysis function Transformer T1 parameters;
is the fundamental or basic functions that are available in IPF = 20kA V = 11k/433V
almost all computer aided power system analysis programs. S = 2.0 MVA Z = 5.93%
These programs are available in the market and are utilized IFL, induction = IFL, synchronous = 0A
by engineers to conduct in house analyses in the comfort of
their own workplace either at home or in the office using a
personal computer.
4
VS
IF = (11)
3 Z total
Where Ztotal = Summation of source impedance and
protected element impedance
TABLE II
FAULT LEVEL RESULTS (MANUAL CALCULATIONS)
System
Fig 3. Single line diagram showing T1 connections Fault Location
Voltage Fault Level / IShort-Circuit (A)
(Busbar)
Level
11kV 1 20 kA
1.626 kA (referred to 11kV)
433V 2
41.314 kA (referred to 433V)
1.634 kA (referred to 11kV)
433V 3
41.506 kA (referred to 433V)
11kV 4 20 kA
1.251 kA (referred to 11kV)
480V 5
11k 28.668 kA (referred to 480V)
3 851.716 A (referred to 11kV)
208V 6
45.043 kA (referred to 208V)
851.716 A (referred to 11kV)
433V 7
Fig 4. Illustration showing the fault levels based on Fig 3. 21.637 kA (referred to 433V)
11kV 8 20 kA
1.634 kA (referred to 11kV)
Using Equation (11), 433V 9
41.507 kA (referred to 433V)
11k
Fault current at busbar 1, I F 1 = = 20 kA 11kV 10 20 kA
3 × 0.31754 208V 11
1.263 kA (referred to 11kV)
66.793 kA (referred to 208V)
846.223 A (referred to 11kV)
433V 12
Fault current at busbar 2, 21.498 kA (referred to 433V)
11k 845.765 A (referred to 11kV)
IF2 = = 1.626 kA @ 11kV, 480V 13
19.840 kA (referred to 480V)
3 × (0.31754 + 3.58765 ) 846.223 A (referred to 11kV)
433V 14
11000 21.495 kA (referred to 433V)
= 1.626k × = 41.314kA @ 433V. 1.251 kA (referred to 11kV)
433 433V 15
28.667 kA (referred to 480V)
1.634 kA (referred to 11kV)
433V 16
SESCO Incomer 41.507 kA (referred to 433V)
No. 1
B. Simulation Results
T8 T2
2.0MVA 2.0MVA Fault analysis was also conducted using the ETAP 5.5.5
11k/433V 4 11k/433V
5.90% 5.90% Demo Version’s Short-Circuit Analysis function. A sample
of T1’s short circuit analysis results are as shown below:
3 2
T11 T10 T9
1.0MVA 1.0MVA 1.5MVA
11k/208V 11k/433V 11k/480V
L8 5.90% 5.90% 5.90% L1
7 6 5
L11 L10 L9
VII. CONCLUSION
Fig 7. ETAP Simulations (From Feeder 1 Sesco Incomer 1 to L1)
The fault analysis plays a vital role in a power system
analysis as it used in determining the appropriate protection
scheme for a power system. The calculated fault current or
short circuit current based on the rated equipment values are
used in determining the minimum protection requirement as
the obtained fault current is the maximum fault current that
may occur within the system. Hence, this would enable
sufficient protection. After all, short circuit currents are
normally quite excessively high and potentially deadly and
hazardous to both equipments and personnel. Thus, the
obtained fault levels in this paper acts as the prerequisite to
protection coordination studies in KSO.
REFERENCES
[1] Kho, H. PowerPoint Slides: KSO Overview, 2007.
[2] J., L. Yong, KSO Contingency Plan Rev. IV, 2007, p. 1-107.
[3] I. Kasikci, Short Circuit in Power Systems: A Practical Guide to IEC
60 909 Germany: Wiley VCH, 2002, p. 1-102.
[4] IEEE Recommended Pracrice for Industrial and Commercial Power
System Analysis (IEEE Brown Book), IEEE Standard 399-1997.
[5] J. Schlabbach, Short Circuit Currents: IEE Power & Energy Series
51.UK: IEE, 2005, p.67-94.
[6] J. D. Glover and M. S. Sarma, Power System Analysis and Design.
Third Edition. USA: Brooks/Cole Thomson Learning, 2002, p. 608-
610.
[7] Chu & Gassman Consulting Engineers, “Short-Circuit Calculation
Methods”,EC & M. [Online]. Available: http://ecmweb.com/mag/el-
ectric_shortcircuit_calculation_methods/
Fig 8. Short circuit analysis results for circuit Sesco Incomer No.1 to L1
[8] J. Frank, “ How to Perforn Short-Circuit Calculations”, EC & M
[Online]. Available: http://ecmweb.com/mag/electric_perform_s-
VI. DISCUSSION hortcircuit_calculations_3/
[9] Rahim Bin Hj. Selamat, “Menganalisa Pembezalayanan dan
From the analysis and simulations made above, the Penatahan Perlindungan Arus Lampau dan Kerosakan Ke Bumi Pada
following conclusions can be made: Rangkaian Sistem Pengagihan Voltan Rendah”, Malacca: UTeM,
1) The maximum fault current can be predicted and 2005, p. 10-46.
calculated based on the rated values of the connected [10] K. S. Wong, Power Distribution and Protection. Second Edition.
Singapore: Pearson Prentice Hall, 2003, p. 14-31.
equipments and loadings [11] Electrical Engineering Programs [Online]. Available:
2) The obtained fault current values are deemed to be http://newcalc.com/engineering-software.htm
accurate as the manual calculation results are almost [12] Duncan Lee Chian Kok, Facalities Engineer Komag Sarawak
equivalent to the simulated results. The differences in values Operation.
are mainly due to the impedance factor.
3) The obtained fault level at the busbars (Busbar 1-16 –
refer to Fig. 5 and 6. connected to the transformer’s
secondary side are approximately similar to the calculated
transformer fault currents at the secondary windings as they
are basically located at the same locations. This is because
the fault level at busbar 2 and the secondary winding
transformer fault current are located at the same location.
4) Furthermore, it was observed that the simulated fault
levels at the transformer’s also differs but with a slight
difference. The differences in the results are due to the fact
that in the simulation analyses, the program takes the
impedances of the entire circuit into the account. Hence, the
load impedances are also accounted for in the analyses
unlike the two other calculation methods.
5) The simulated results of fault current were observed to
be generally higher than the calculated values. Basically, the
difference in results was caused by the impedance
consideration factor. In the simulation, the ETAP program
takes the load impedance into account causing a difference
in the short circuit analysis results. Furthermore, the type of
load selected for the system was the lumped load where the
power factor and the efficiency of the system are also
considered by the program.