Professional Documents
Culture Documents
(4.1) External Faults Three-phase kVA 100 1000 10 000 100 000
(4.1.1) Internal Axial Compression.
The tendency of flux lines to contract like elastic bands pro-
duces a tension along these lines. The lines of force around a Reactance ex, % • • 3-75 5-5 8 10
Effective width of duct d,
current-carrying conductor of any cross-sectional shape thus inches 1 2 3 6
exeit a pressure on that conductor, tending to squeeze it into a Crest radial force Ps, tons 44-6 152 697 2 783
section of minimum perimeter, i.e. into a circular shape. This
internal compression is quite independent of the currents flowing In absolute units, dynes/cm«
BILLIG: MECHANICAL STRESSES IN TRANSFORMER WINDINGS 229
sizes of typical 3-phase 50-c/s transformers with simple con- (4.2) Internal Faults
centric windings. The force varies approximately as the |th Excessive currents can also be caused by internal faults or by
power of the rating. electrical or mechanical faults in the tap-changing gear. These
This value is the theoretical maximum, which under practical faults involve only parts of a winding. Owing to the heavy con-
conditions will never be reached. Even in the largest supply centration of current within a small space, the forces and stresses
systems there will always be some voltage drop at the primary produced are usually much more severe than in the cases pre-
terminals of a transformer if its secondary winding is short- viously considered, and are likely to result in permanent deforma-
circuited. Furthermore, the resistance of the windings will cause tion, decrease of clearances, and further breakdowns. Once
damping of the d.c. component of the short-circuit current. The started, internal faults thus have a tendency to spread pro-
combined effect will be a reduction of the first current peak and gressively unless the supply is quickly interrupted. This is not
of the corresponding value of the forces. Fig. 2 gives the factors always easy to achieve, because the high fault reactance limits
iO the current drawn from the line to only a fraction of the full-load
1 111111 1 current, and protective relays would have to be set rather fine.
0-9 \ 1 JJ 1 LU Effective protection of transformers against internal faults should
\ not, therefore, rely exclusively upon the direct action of electrical
0-8 --- stance dan
s •s, > ^« t L quantities. Buchholz relays or similar devices responsive to dis-
07 \ s -«* integration products of the insulation are found to be more
\ K^
reliable.
06 /\ \ > x«.
/ s ~\ An accidental short-circuit across part of a winding may occur
•=.05
owing to one of the following causes:—
j
04 / Drop m supply wttage (a) Breakdown of the insulation between turns, coils or wind-
/ Scale I
/ •»•».
;
ings, or from any live part to the frame or to the iron core
03 ^. (earth), caused by high dielectric stress, by overheating, or by
02 mechanical damage to the insulation produced by slackness in
the winding, etc.
o-i (b) Faulty operation of the tap-changing gear.
(c) Accidental short-circuit between tapping leads or across
01 02 03 0-4 0-5 075 10 NJCO/N, Scale!
the terminals to which these are connected.
0 1 2 3 4 5 lOX/R ScaleD 15 A common occurrence is the sticking of a contactor in the
Fig. 2.—Damping factors for current, c due to winding resistance closed position. The closing of the next contactor in the normal
and k due to drop in supply voltage. sequence of events during a tap-changing operation may then
R •-= resistance of transformer.
X =» reactance of transformer. result in the portion of the winding connected between the two
NT<X> =• short-circuit capacity of transformer with unlimited supply. contactors being short-circuited through them. Another likely
Ni -- short-circuit capacity of supply system on primary side of transformer.
cause is a diverter switch the contacts of which have become
c2 and k2 by which the value of the forces according to the above welded together or which fails to open for some other reason.
formula should be multiplied to allow for damping due to finite This leaves the selector switch to break the full-load current, a
resistance and limited power of the supply circuit. duty for which it has not been designed. The arc drawn on
breaking this current is likely to bridge the gap between adjacent
(4.1.3) Axial Forces. contactors and thus short-circuit part of the winding.
The primary and secondary windings are in a state of unstable A typical example of an internal fault in a transformer winding
equilibrium in the axial direction: if the magnetic centre of one is the flashover across an end-coil or a tapping coil subsequent
winding is displaced axially against the other, an axial force to the arrival of a steep-fronted high-voltage surge at the terminals
comes into play which tends to increase the displacement, of the transformer. Such surges create high voltage stresses
and which, in turn, grows with it. For a small displace- across parts of the winding adjacent to points where the surge
ment the force is approximately proportional to it. Fig. 22 impedance changes abruptly, i.e. especially across end-coils or
shows that a displacement equal to even less than 1 % of the tapping coils. Tapping coils at either side of a junction are in
axial height of the windings gives rise to a force which is danger whether actually in circuit (Fig. 4a) or "tapped out"
an appreciable fraction of the tremendous radial force Ps. This
state of unstable equilibrium is illustrated in Fig. 3, where the
4
s
f
the radial force P$ given in Section 4.1.2 and, for both windings T-30%
s
together, is given by \
Ph:Ps~S:H s, \
4/ii
o-
where 8 = the radial width of the duct and H = the axial height 25% \
of each winding. The residual pull on the end coils is somewhat Tapped
s ^c
if-.
\
reduced by the proximity of the core yokes, which tend to attract V £2 -.
f
\/
these coils. 1 /
\ b
The proximity of the iron core also results in an increase in \
axial pressure in the winding nearer the core and a decrease in •'
> \\ |
the outer winding. The sum of these pressures is, however, not
appreciably altered. 7 K
1
i
y
\ Inner winding
'' The uniform distribution of turns in the windings is often dis-
(ne ther windm? taDDed)//L-
turbed by tappings or by some reinforcement of the insulation. c
This local reduction in ampere-turn density in one winding, with \
no corresponding reduction in the other, gives rise to a "cross- I0X y
\\ /
V 1 A
field" which is mainly radial in direction. As shown in Fig. 12, 8% Outer or inner winding
i (ne ther winding tapped)
\r -/
1/ 6%
j
/
p
A
/-
1
Ocite r w 1 \ j
2% 1 •>-
( H-
vi rid apped)
—
\
~ 0 10 h/H 20 30 40
t 50 60%
/ H -100% -
nil
iiV
1
iJl Without core
+ 1*5
11 ith core
- w esidual
D
-met hoc with and
AT-
U.
K\ without core
\
+ 10
1.1
\t ,4 y <soer/
1°*'
\
1
\ •*&< X'
lkiA
ntre
u
+05
\\ \\
Ir.Ml \ \ ^1 ^ <>^ •sh % H
AI
1! towards
V
\\. . .o'
4^ r"
•
r— oed )
i k 10
—«•
i2^
——-
i
TTT*-*' wind in? (neither winding Capped
EBE
T
•iMi
50
%
1 o -0-5
*^ ^ v
'V
j
n
in 1
\ !
i*-
-^
\ ^ ,
-i-o \
\
\\ \
-1-5 \ V
\
\J \
\ +
-ao
H —j
h-a
1 1
l'V5Z
^/////V7//////777//////y/////////7////////////////
I
14. Distribution of axial force Fh in the two windings of a transformer, with and without iron core, with and without tapping at the
centre of the outer winding for:
Width of duct 4 = 5%
ti
Clearance to core — = 2 • 5 %
ti
Centre tap ^ =10%
ti
234 BILLIG: MECHANICAL STRESSES IN TRANSFORMER WINDINGS
however, the l.v. winding is made up of a number of separate
"barrel-type" coils having rather thin walls. There is a danger
that, under high external pressure, such coils may collapse like
a thin-walled cylinder. If such a coil is wound over axial runners
it is likely to collapse owing to the polygonal, rather than circular,
shape.
If the h.v. and l.v. windings are not exactly concentric, a
restoring force will appear which tends to pull their axes into
coincidence.
3, In a balanced double-concentric arrangement, the leakage flux
density in both ducts is nearly equal and radial forces on the centre
TVs winding nearly cancel out leaving only a tension in the outermost
1
"4 and a compression in the innermost winding. Similarly, in a
• • • » "
4 4 properly-balanced sandwich arrangement, where the leakage flux
o a density is constant in all main ducts between h.v. and l.v. groups,
( a \ "4 there will be an axial repulsion only on the end groups, as the
a pressures acting on both sides of any other group will cancel out.
11 Proceeding in a radial direction through the windings of con-
(J) centric arrangements, the pressure rises with the leakage-flux den-
Fig. 15.—Distribution of residual ampere-turns for tapping arrange- sity from zero at the outside to a maximum value at the surface of
ments according to Fig. 1. the duct. If the turns are wound solidly on top of each other, the
that may occur in any position. It is 137 500 — 29 500 = 108 000 total stress will be taken up more or less uniformly over the whole
ampere-turns, or 5 • 72 % of the total ampere-turns in the winding, radial depth. If, however, the winding is made up of several
occurring at level V, i.e. near the centre of the winding, on layers separated from each other by a cooling duct, the inner
tapping 4.* layers, i.e. those nearer the duct, will be stressed to double the
previous value, while the layers more remote from the duct will
take progressively less stress. A special tapping coil of the outer
(6) MECHANICAL STRESSES IN WINDINGS winding, for instance, should therefore never be placed near the
All the various forces described in the previous Section depend main duct, but always on the outside of the outer winding.
on the magnitude of the instantaneous currents flowing in the
windings, and under normal operating conditions are not very The axial forces are transmitted through the whole length of
large. They vary as the square of the current, are unidirectional, the winding, compressing the copper conductors and also the
and pulsate at twice the operating frequency. Under short- insulation and supports between them. Where conductors are
circuit conditions, however, the forces reach excessive values; wound solidly side by side, the turns are well supported over
they must be overcome by the mechanical strength of the con- their whole length. If the individual conductors are wound "on
ductors themselves and of the supporting structures between the flat," in order to minimize eddy-currents losses, there is,
turns, coils, windings and the core. As the slightest asym- however, always a tendency for the wires to slip over each other
metry in the windings gives rise to forces which increase rapidly unless they are very tightly wound, especially where thicker
with the displacement, the whole structure should be so designed insulation is used or where the corners of the rectangular wire
as to avoid any movement whatever, even under extreme con- are rounded. This applies especially to coils wound with round
ditions. wire, as there is always a tendency for the turns to squeeze in
between neighbouring turns until the whole coil assumes a
The stresses produced by the rapidly varying mechanical forces
may greatly exceed the corresponding static stresses, f If the circular cross-section. This effect can be prevented by running
structure is fully elastic, the maximum stress due to a suddenly the wire through a special paste when winding the coil, so filling
applied load may reach double the static value. If resonance the interstices between the turns. After baking, the coils as-
occurs between the rate of loading and one of the free modes of sume a hard cement-like consistency which effectively prevents
oscillation of the structure, the amplitudes of movement and any movement of the wire.
stress may exceed double the static values and might well become In "disc" windings, the axial forces, acting uniformly over the
excessive. whole length of each turn, exert a bending moment on that part
The radial forces, even for the worst conditions of short- of the conductor which is not supported. The full axial pressure
circuit, can usually be withstood by the conductors, in which is transmitted over the supporting pieces in a cumulative way,
they produce a static tensile stress of approximately each turn contributing its own share. These supports must not
be too far apart, as this would result in an excessive bending
a ~ >—K X V/turn x A/cm-, in kg/cm2 stress in the conductors, and their supporting area must be large
enough to prevent any excessive compression of their own or
This stress remains well below the yield pointj for copper (about of the conductor insulation. On the other hand, sufficient clear
1 000 kg/cm2 at 100° C), even in the largest transformers so far space between the supports must be allowed so as to avoid inter-
built. Thus there is usually no need to brace or bandage the ference with the cooling of the coils. The bending stress at the
outer winding, provided that it is of circular shape. ends of the windings or adjacent to tappings should always be
The same formula applies to the inner winding, with the only checked, and, if necessary, the axial dimensions of the conductors
difference that a here is a compressive stress which the copper should be increased to give greater strength.
will more readily withstand. This latter statement applies only
to windings with fairly large radial thickness. Quite frequently, (7) SHRINKAGE OF WINDINGS
• According to Fig. 15(i), a maximum field of a/4 = 5% would be expected for Whilst the effect of the internal forces on the metallic con-
this type of winding with a tapping range of ± 10%, or a = 20%.
t A "static" stress is produced in a structure by a force which is applied to it ductors can be predicted with reasonable accuracy, the effect on
rather slowly so as to prevent any vibration.
1 It is realized that copper yields even under very small stress. The figure cited
the insulating materials used in the supports of the coils is less
indicates the stress beyond which the strain would become excessive. certain, as the behaviour of these materials under such special
BILLIG: MECHANICAL STRESSES IN TRANSFORMER WINDINGS 235
10 I? tons
50*IOOOAT/inch
. -i 1 1 1 r .
-100-90-80-70-60-5(M0-30-20 -10 0 10 20 30 40 50 60 70 80 30 IOOXIOOOAT.
Fig. 16.—Distribution of ampere-turns for external short-circuit |of a 45-MVA transformer with h.v. winding on tapping 7 (r.m.s. values are
given for the a.c. component of the short-circuit current).
conditions is still under investigation. Although no precise in- former. Although considerably below the short-circuit peak
formation is at present available, it has been found that with value, the current may amount to several times the full-load value.
pressures of the order of 1 ton/in2, which may well arise in large As there is no relief from opposing ampere-turns, the contractive
transformers, the insulating material will take a considerable per- effects will be relatively large. Integrated over the whole life of
manent set. Conductors which had moved slightly under the the transformer, the shrinkage produced by frequent switching
action of the electromagnetic forces whilst the fault lasted, would may be considerable, and may lead to serious trouble when a
return to their original positions only if all the deformations pro- short-circuit occurs. The h.v. winding, which is usually me-
duced were entirely elastic. Owing to the permanent character chanically weaker, is normally the outer winding, and fortunately
of part of the deformation, some portions of the windings will switching currents in the outer winding are lower, owing to the
be left in a slightly shifted position. Quite apart from any larger area available to the flux.
thermal or other ageing effects, there is thus a certain amount Particularly heavy stresses can be experienced when a trans-
of shrinkage produced by every short-circuit. former is switched on whilst short-circuited on the secondary
Excessive currents, too, may appear on energizing a trans- side, especially when the primary winding is adjacent to the core.
236 BILLIG: MECHANICAL STRESSES IN TRANSFORMER WINDINGS
conductor insulation and to lead ultimately to complete break-
down.
(8) CLAMPING OF WINDINGS
To avoid trouble from shrinkage, every care must be exercised,
not only to balance the forces by proper design, but to use only
suitable insulating materials in the construction of the windings
and in such a way that shrinkage in service is reduced to a
minimum. An instance where particular difficulties are likely
to be met is the support of windings with a small radial depth
such as cylindrical tapping coils, especially if located in a strong
magnetic field. The practice of using end-rings cut from
Bakelized paper cylinders or similar materials is not to be recom-
mended unless suitable types are chosen, as there is a likelihood
of deterioration in time under the combined influence of hot oil
and mechanical pressure applied in an axial direction, i.e. edge-
wise to the paper laminations. Materials for the supports
should be pre-shrunk for a prolonged period until no more
settling will occur.
(8.1) Design of Clamping Structure
The purpose of a well-designed clamping structure is to prevent
any movement within the windings. This can be achieved by
any clamping device which puts the coils permanently under a
higher pressure than any produced by the short-circuit forces,
thus ensuring a constant pressure within the coils at all times.
The maximum stress produced in the clamping gear consists of
three components:—
(a) The clamping pressure applied when tightening down.
(b) The end thrust created by electromagnetic forces in the
winding due to an unbalance of ampere-turns and especially on
the occurrence of internal short-circuits.
(c) The differential thermal expansion of windings and
clamping gear.
0 10 2 0 3 0 4 0 5 0 6 0 70 8 0 ? 0 ICO 110 120 130 I 4 0 X ! C 0 0 A T ( To obtain a rigid construction, the clamping structure should
Fig. 17. Superposition of ampere-turns in the 45-MVA transformer tie the windings together, preferably without transmitting stress
of Fig. 16 for any tapping position. through any other part of the transformer. Thus the practice
Distribution tor "full winding" position. of clamping coils from the core yoke transmits the clamping
— — Additional distribution for any other position. pressure through the core, and this fact must be taken into
In this event the primary winding may draw current correspond- account in designing the core structure, and particularly the core-
ing to the sum of the short-circuit and switching current peaks, bolt insulation if it is subject to mechanical stress due to the
whereas the secondary carries only the normal short-circuit clamping pressure.
current. Having regard to the lack of balance between primary It is possible to effect the clamping of the coils in two essen-
and secondary ampere-turns and the fact that the forces are tially different ways: each winding may be clamped separately,
approximately proportional to the square of the currents, the or all the windings on one limb may be clamped together. Each
severity of such a fault will be readily appreciated. arrangement has its special difficulties if shrinkage does take
A large power transformer has about one-third to one-half of place. In the former case adjusting screws are usually provided
its axial winding length occupied by various insulating materials which compress each winding separately from the top yoke.
such as paper, cotton, pressboard, etc. With a total winding These screws can be tightened by hand or by means of a non-
length, including end-clearances, of about 80 in, it can be seen return spring device which takes up any shrinkage automatically.
that considerable shrinkage of the coils can take place, even if As, however, one winding may shrink more than the other, the
the insulation were to shrink by only a fraction of 1 %. The effect of clamping each winding tightly will be to push that
amount of shrinkage will be different for the various windings, winding which has shrunk more further down the core limb than
according to the amount and nature of the insulating materials the other, so producing magnetic asymmetry.* In the other
used in their construction. Under the same pressure the h.v. type of design, a common clamping ring for both windings is
winding will shrink more than the l.v. winding. Fortunately, usually provided at each end of the winding and the two are
this effect is largely offset by the proximity of the iron core, clamped together by means of tie-rods; alternatively the top ring
which tends to decrease appreciably the pressure in the outer— only may be depressed from the yoke. Tightening of the tic-
high-voltage—winding. There is, however, no doubt that short- rods or of the adjusting screws following unequal shrinkage then
circuit shrinkage will differ in the various windings. Under the results in restoring the pressure on one winding only, whilst the
influence of their own weight or of clamping springs, the coils other remains more or less slack, unless it is packed up again as
then drop by a corresponding amount, so causing an axial dis- * The opinion is sometimes expressed by maintenance engineers that any asym-
placement of the two windings, the very condition which must be ismetry so produced could be detected by an increase in the reactance. Although this
true in principle, the measurements would have to be taken with great care, as
avoided, as it results in increased forces, further shrinkage and (see Fig.relativelyeven a large displacement would produce only a small increase in reactance
7). Quantitatively, the increase is larger for windings with a small ratio of dis-
greater displacement on the occurrence of the next short-circuit. tance between windings to axial height of windings; e.g. with a ratio of 1 : IS,
The vicious circle so started is likely to cause damage to the axial unbalances of 1, 2and 5% would produce increases in reactance of 0-15.0-60
and 3 • 75 % respectively of the original value.
BILUG: MECHANICAL STRESSES IN TRANSFORMER WINDINGS 237
in the original assembly. This, of course, can only be done after
lifting the transformer out of its tank. Another method that
has been suggested involves the introduction of springs at the Tie reds
centre of the "softer" winding; these springs take up any
shrinkage symmetrically from the centre, so maintaining the
balance between the h.v. and l.v. windings. It is important that Clamping
the springs should be strong enough to withstand such clamping arrangement
pressures as may be necessary to prevent appreciable coil
movement.
It should be possible, however, to build a clamping structure
in which the pressure applied to a common clamp is distributed
evenly over both windings, even after they have shrunk by
different amounts. Care must be taken, however, that the
shrinkage is taken up without altering the relative positions of Clamping
the magnetic centres of the two windings affected. v~' diagram
Another method that has been suggested concerns the "cage
Strain
type" or "pressure-free" coil assembly (Fig. 18), where the force
4
w r ~Ph2
CI ci m p i n g d legra q\ (f)
(enlarged)
grammes. The restoring force of all the tie-rods together is (9) CONCLUSIONS
/C' = 2-32 x 1012 dynes/cm extension of each half length, cor- (a) The clamping structure should keep all the windings con-
responding to an elastic modulus E = 2 • 1 X 1012 dynes/cm. tinually under a pressure which is strong enough to prevent even
Hence the slightest movement in any circumstances which might arise
2-32 x in the operation of the transformer during the whole of its useful
life.
(b) All the methods of clamping which have been used up to
This value for the frequency is obviously too low, as the masses the present effect a compromise between various factors, and
are not concentrated but distributed over the axial height of the none of them fully solves the problems arising out of shrinkage.
coil. Therefore consider another extreme case, i.e. an elastic (c) High-voltage windings should preferably be arranged on the
body, with masses and restoring forces uniformly distributed outside from the point of view of mechanical strength.
over the height H. This is the mechanical equivalent of an {d) Tapping coils should be removed as far as possible from
electric transmission line with distributed capacitance and in- strong magnetic fields.
ductance. Phenomena analogous to electrical waves arise in the (e) There is scope for more detailed investigation of the be-
elastic body: any mechanical disturbance is propagated along the haviour of the materials now used as inter-turn, inter-coil, and
body as an elastic wave, progressing at a constant speed end insulation of transformer windings, and possibly for the
v — V(Slm), where stiffness S = AE, with cross-section A, development of a new material better suited to the purpose.
Young's modulus E, and m = mass per unit length. If left to The main property required of such a material, apart from the
itself, such a body may execute free vibrations, the frequency of usual electrical and mechanical requirements, would be freedom
which depends on its length. The lowest mode of vibration from appreciable yield even after extended operation over many
corresponds to a wavelength A equal to half the length of the years when immersed in oil at temperatures up to 100° C under
body if both ends are free to move. Hence, the fundamental a high continuous pressure of the order of 1 ton/in2, on which
frequency is given by is superposed a lower pressure pulsating at 100 c/s.
(J) Proper use should be made of the experience to be gained
f=s = from the performance of transformers under short-circuit.
i" 2flrV(m) Tiija' Records should be kept of the frequency and severity of faults
where M — total mass and H — total height of insulation. in the system and of the state of windings as found by occasional
Compared with the formula found above for 2 masses concen- inspection. The development of slackness and signs of move-
trated at the ends, the frequency for a system with the masses ment in the windings should be carefully recorded. Quantitative
uniformly distributed is higher in the ratio TT : 2, i.e. in the records of any loss in clamping pressure could readily be obtained
example given it comes to 600 c/s. by fitting a simple strain indicator to the clamping gear and by
taking readings at certain intervals.
(8.5) Loss of Clamping Pressure
An immediate effect of the loss in clamping pressure would be
a certain slackness in the windings. Any slight movement of (10) BIBLIOGRAPHY
conductors subsequent to a fault will produce small gaps at (1) SEARLE, G. F. C.: "On the Magnetic Field Due to a Current
certain points.* At the occurrence of the next fault an electro- in a Wire Placed Parallel to the Axis of a Cylinder of
mechanical force of large magnitude will again tend to com- Iron," Electrician, 1898, 40, pp. 453, 510.
press the winding. Owing to the slackness between adjacent (2) ROGOWSKI, W.: "Uber das Streufeld und den Streuinduk-
coils, however, these will start to close up and will gather con- tionskoeffizienten eines Transformators mit Scheiben-
siderable momentum before being restrained from further wicklung und geteilten Endspulen," Mitteilungen iiber
movement by the insulating spacers. The compressive stresses Forschungs-Arbeiten des V.D.I., 1909, No. 71.
are therefore considerably increased by the impact nature of the (3) STEINMETZ, C. P.: " Mechanical Forces in Magnetic Fields,"
forces (see Fig. 20c). Transactions of the American I.E.E., 1911, 30, p. 367.
If the force remains constant over the whole travel and the (4) ELLIS, A. G., and J. L. THOMPSON: "Large Power Trans-
material is fully elastic, with Young's modulus E, the maximum formers," Journal I.E.E., 1919, 57, p. 547.
stress is given by—• (5) BIERMANNS, J.: "Kursschlusskrafte an Transformatoren,"
Bulletin, Schweizer Elektrotechnischer Verein, 1923, 14,
pp. 212, 245.
(6) HAK, J.: "Mechanische Beanspruchungen in Reaktanz-
where <r0 is the corresponding static stress and h/H is the gap spulen,"Elektrotechnik und Maschinenbau, 1924, 42, p. 17.
expressed as a fraction of the overall height of the winding. (7) MtiLLNER, F.: "Stromkrafte in Transformator-Wicklun-
If there is no gap (Ji — 0) and thus no impact, the maximum gen," ibid., 1924, 42, p. 679.
dynamic stress is just double the static value. For a gap (8) HAGUE, B.: "The Electromagnetic Forces on Conductors
of h/H = 1 % with modulus E = 12 000 kg/cm2 and static near Iron," World Power, 1926, 5, pp. 124, 205.
stress (T0 — 100 kg/cm2 the maximum stress would, owing to the (9) "Mechanical Stresses in the Windings of Core-Type Trans-
impact, rise to 2 • 85 times the value cr0. formers," A.S.E.A. Journal, 1925, 2, p. 158.
Various processes have been described in this Section which (10) CLEM, J. E.: "Mechanical Forces in Transformers," Trans-
may give rise to some axial movement of a cylindrical winding actions of the American I.E.E., 1927, 46, p. 577.
or parts of it. Such movement, if continued for any length of (11) MOODY, W. S., and BOYAJIAN, A.: "Mechanical Forces in
time or repeated every time the transformer is energized, is Transformers," General Electric Review, 1927, 30, p. 420.
likely to chafe the turn insulation where it rides on the runners (12) VIDMAR, M.: "Der Transformator im Betrieb" (Springer,
along the insulating cylinder or the iron core, and would eventually Berlin, 1927).
lead to abrasion and electrical breakdown of the turn insulation. (13) STEroiNGER, W.: "Induktivitat, Energie und Stromkraft
* The possibility of the formation of slackness at the tapping point in a tapping
von Sammelschienen," Archiv fur Elektrotechnik, 1929,
coil has been discussed in more detail in Section S. 23, p. 153.
240 BILLIG: MECHANICAL STRESSES IN TRANSFORMER WINDINGS
<14) RICHTER, R.: "Elektrische Maschinen": 3, "Transforma-
toren," pp. 83-90 (Springer, Berlin, 1932).
(15) KORB, A.: "Stromkrafte bei Transformatoren mit Rohren-
Spulen," Elektrotechnik und Maschinenbuu, 1932, 50, pp.
489, 505.
(16) KORB, A.: "Radiale Druck- und Sprengkrafte in Rohren-
spulen," Archiv fitr Elektrotechnik, 1933, 27, p. 454.
(17) KORB, A.:" Axiale Stromkrafte zwischen koaxialen Rd'hren-
Wicklungen mit Abschaltspulen," Bulletin, Schweizer
Elektrotcchnischer Verein, 1933, 24, p. 333.
(18) BIHRMANNS, J.: "Die Aufgaben des heutigen Transforma-
toren-Baues," Elektrotechnische Zeitschrift, 1933, 54 (II),
pp. 717, 767.
(19) KORB, A.: "Der Einfluss des Eisens auf die radialen Strcm-
krafte bei Transformator-Rohrenspulen," Archiv fiir
Elektrotechnik, 1934, 28, p. 625. (a)
(20) STEPHENS, H. O.: "Transformer Reactance and Losses with
Non-Uniform Windings," Transactions of the American Fig. 21.—Arrangement of two parallel current conductors.
I.E.E., 1934, 53, p. 346. (a) Line conductor and current sheet.
(21) NORRIS, E. T.: "The Mechanical Strength of Large Power (b) Two current sheets.
Transformers," World Power, 1935, 24, p. 292.
r 'V(M
(H 821
<22) FISCHER, E.: "Einfluss des Eisenkernes auf die Stromkrafte where the factor <f)h = log-f ^ log../ -——- (3)
von Transformator-Wicklungen," Elektrotechnische /'i \ L h"
Zeitschrift, 1938, 59 (II), p. 1059. /•j, r2 = distances from the wire to the two edges of the
(23) MoRLtY, A.: "Strength of Materials," 7th ed., p. 326 sheet.
(Longmans, Green, London, 1928). h, H— /z = their axial projections.
(24) HAK, J.: "Eisenlose Drosselspulen" (K. F. Koehler, S — radial distance.
Leipzig, 1938). (Note: Natural logarithms are employed throughout.)
(25) BILMG, E.: "Mechanical Stresses in Transformer Wind- It is worth noting that the direction of the resulting force,
ings. Critical Resume," E.R.A. Report Ref. Q/T101, given by tan a = F/JFs ~ </>/,/</»rt, is not towards the centre of
1943. the bar but towards a point nearer the wire [see Fig. 2\(a)], i.e. the
(26) BILLIG, £\: "Electrical and Mechanical Effects of Internal axial component is always smaller than would be expected from
Faults in Transformers," E.R.A Report Ref. Q/T103. the radial force F8 if the resultant force F were assumed to pass
(27) BILLIG, E.: "Displacements in the Windings of a 45-MVA through the centre of the bar.
Transformer," E.R.A. Report Ref. Q/T105.
(28) BILLIG, E.: "The Calculation of the Magnetic Field of (11.1.2) Two Parallel Current Sheets.
Rectangular Conductors in a Closed Slot, and Its Appli- With axial heights H and H2, and linear current densities
cation to the Reactance of Transformer Windings," Ax = nxiJH, A2 — n2i2IH2 respectively (Fig. 216).
l.R.A. Report Ref. Q/T106, 1945.
Radial component offorce P6 = Pif/$ (4)
where force constant P — l A ^ J l l (5)f
(11) APPENDIX
(11.1) Formulae for Electro-Mechanical Forces in Transformer and factor 0 S - y -{- B - / a -\- ^ log °P (6)
ti
ti nn n i{s
Windings The various dimensions and angles occurring in equations (6)
The following extract from item 25 of the Bibliography and (8) are marked in Fig. 21(6). For two sheets with flush ends
might be found useful when calculating the forces likely to arise (c = 0) and of equal heights (H2 — H), the factor for the radial
in the windings of normal transformers. Two concentric wind- component may be simplified to
ings are assumed which may be approximated by parallel current
sheets, i.e. straight, thin bars of axial height H corresponding to • (fin)
the height of the windings which are separated by a distance S
according to the effective width of the leakage duct, and of
Axial component of force P/t • - Ptfi/, • (7)
length / corresponding to the mean length of turn in all the
windings concerned. For a winding with n turns, carrying p c s b q 8 (
current i*, the linear current density is A ~ ni/H. where factor xjjh = log - 4- ->> log - f — log - a) (8)
(11.1.1) Line Conductor Parallel to Current Sheet. For two sheets with flush ends (c = 0) and equal heights
(// = 0) the axial component disappears tyh ~ 0). For two
Radial component of force Fs = 2A1i2l^>s . . (l)f sheets, flush at one end but of unequal heights (H2 — H -- /;),
where the factor (f>$ is equal to the angle in radians subtended equation (8) may be simplified to
by two straight lines from the conductor wire to the edges of the
current sheet (Fig. 21a). w H-
Width of duct
0 5 10 15 35 40 45 Scale IH 50?.
100 95 90 &5 80 h
65 60 - 55 Scale IZ ,
Axial distance of end turn /n
Fig. 22.—Axial push between two windings of different height but with flush ends.
(11.2.5) Force on End-Turns in H.V. Winding. are 5-15 and 62-1 in respectively; hence the outward thrust
With 588 turns in the full h.v. winding, the force constant per towards the clamps is
turn is
700 1-19 x log-—- = 2-98 tons
F — — — 119 tons
588
The distances from the centre of the end coil to the two ends of Therefore resultant inward pull =1-94 tons towards the body
the remaining body of the h.v. winding are 1 in and 62 in of the winding. This is reduced by the presence of the core to
respectively; hence the inward pull towards the body of the 1 • 5 tons per turn.
winding, according to equations (2) and (3), is A knowledge of the forces and pressures enables the windings
and mechanical details of the winding structure such as cross-
119 x log?? = 4-92 tons section of wires, spacing and size of coil spacers and axial
runners, number and cross-section of tie-rods and end clamps,
The distances to the top and bottom edges of the l.v. winding etc., to be properly designed.