Professional Documents
Culture Documents
Case 1, n = 1
In this case for the sake of simplicity and
without losing the generality, we shall assume that
the pumping well is located at the origin of the
coordinate system. The equation of the dividing
streamlines which separate the capture zone of this
well from the rest of the aquifer is
where = aquifer thickness (m), Q = discharge Fig, 2. The paths of some water particles within the capture
rate (m3/sec), and U = regional flow velocity zone with (Q/BU) = 2000, leading to the pumping well
(m/sec). One may note that the only parameter in located at the origin,
617
the distance between the two wells, again two
stagnation points will appear on the negative x-axis,
one moving toward the origin and the other away
from it, and still no fluid particles could escape
from the space between the wells. ’I‘he following
derivation gives the reason for such behavior.
’1’0 find the position of the stagnation points
one must set the derivative of W to zero:
dW Q 1 1
-- - u+-(-+- )=0 (6)
dz 2nB z - i d ~ + i d
‘I’he roots of equation (6) are given by
618
Obviously, when 2d becomes smaller and smaller,
one of these points tends to the origin and the
other one tends to the point with coordinates of
[-(QInBU), 01. When 2d < Q/nBU, no flow can
pass between the two pumping wells. Therefore, it
is established that the condition for preventing the
escape of contaminated fluid between two pump-
ing wells separated by a distance 2d is
2d
Q
<- (9)
nBU
The optimum condition is achieved a t the
limit when 2d = Q/nBU and the distance of the
stagnation point from the origin is (Q/2nBU). The
equation of the streamlines passing through this
stagnation point is
Q (tan-' y-d Y +d )='
+ tan-' - Q
- (10)
Fig. 5. A set of type curves showing the capture zones of
Y+2nBU X X BU two pumping wells located on the y-axis for various values
of (Q/BU).
One may note that again the only parameter in
equation (10) is (Q/BU). Figure 4 shows the plot
of a pair of these streamlines for (Q/BU) = 800; Case 3, n = 3
some useful distances on this figure are also In this case we shall consider three pumping
identified. Figure 5 gives a set of type curves wells, one at the origin and two on the y-axis at
illustrating the capture zones for two pumping (0, d ) and (0, -d). The regional flow, as before, has
wells and for several values of parameter (Q/BU). a velocity of U and is parallel t o and in the direction
One may note that equation (10) also can be of the negative x-axis. The complex potential repre-
written in nondimensional form as senting flow toward these three wells and the
uniform regional flow is given by
where Y D = BUy/Q, dimensionless; and The velocity potential C#I and the stream function $
X D = BUx/Q, dimensionless. for this flow system are given by
Q
@ = Ux +- {ln(x2 + y z ) +
4nB
l n [ x Z + ( ~ - d ) ~+ l]n [ x 2 + ( ~ + d ) ~ l ) + ( C
13)
Q
$ =Uy+-(tan-'-
Y +tan-' Y
- - d + t a n P - Y) + d (14)
2nR X X X
A A
where A = - (2nBU)/Q. The discriminant of
equation (16) may be written as
d4 d Z 1
D=d2(-- -+-)
27 3A' A4
It can be shown easily that D is positive, except for
the limiting case when d = 0. In that case D
vanishes, too. As a result, when d # 0 equation
(16) has one real root and two other roots which
are complex conjugates of each other.
When d > Q/2nBU we obtain three stagnation
points located at
Fig. 6. A set of type curves showing the capture zones of
three wells all located on the y-axis for various values of
(Q/BU1.
When d becomes smaller and smaller, that is,
the distance between the wells decreases, the
stagnation point on the x-axis moves away from the
origin and the other two tend t o come closer t o the (18) is dependent on one parameter (Q/BU). Figure
y-axis while appraoching the x-axis. Such that for 6 shows a set of type curves illustrating the capture
d = ( 2 "3) QI2nBU the position of stagnation zones for three pumping wells located on the
points are y-axis for several values of parameter (QIBU). Note
that one of the pumping wells is located at the
Q Q Q origin and the other two are on the positive and
~ 1 (-1.54-
: ,O), ZZ : (-0.73 - ,1.9- ),
2nBU 2nBU 2nBU negative y-axis with a distance of '4QInBU from
the origin.
z 3 :(-0.73
Q , -1.9
- Q
->. Here, one can also write equation (18) in a
2nBU 2nBU nondimensional form as
The value of d = (2 ' ~ 5Q/2nBU
) is the
maximum distance between two pumping wells
where n o fluid could escape between the wells. One
may note that this distance is approximately 1.2
times the optimum distance between two wells for
the case of n = 2 .
Eventually, when d becomes zero, that is, where XD and y u are dimensionless coordinates as
when the outer two wells coincide with the middle defined before,
one, three roots of equation (16) correspond t o one
stagnation point on the negative x-axis with a General Case
distance of 3Q/2nBU from the origin and the other We shall now attempt t o extend the solution
two collapse at the origin. At the optimum condi- for a larger number of pumping wells. Table 1
tion, the equation for the streamlines passing shows some characteristic distances for the cases
through the stagnation point on the negative that we have already discussed. There are two
x-axis becomes generalizations that one can infer from Table 1.
(1) The distance between dividing streamlines far
Q Y Y-d Y+d 3Q upstream from the wells is equal t o (nQ/BU) and
(tan-' -+tan" - +tan-l---)=& -
y + 2nBU X X X 2BU it is twice the distance between these streamlines
at the line of wells. ( 2 ) The equation of the dividing
. . . . . (18) streamlines for the case of n pumping wells can be
where d = 34 QI(nBU). Since d is only a function written down by comparing the corresponding
of (Q/BU), it is apparent that once again equation equations for one, two, and three pumping wells:
620
Table 1. Some Characteristic Distances in Flow Regimes parameter (Q/BU). Note that two of the wells are
for One, Two, and Three Pumping Wells Under a on the positive and the other two are on the
Uniform Regional Ground-Water Flow
negative y-axis. 'The distance between each pair of
wells depends on the type curve (i,e., Q/BU value)
chosen. Once the type curve is selected, the optimum
distance between each pair is d = 1.2 Q/(nBU).
62 1
on the map matches the one in Figure 1. Move the contour map becomes parallel and opposite to the
contour line of the plume toward the tip of the direction of regional flow on the type curves. By so
capture curve and read the value of Q/I3U from the doing, we ensure that all the particles of the injected
particular curve which completely encompasses the water stay within the present position of the
contour line of the plume. contour line of the plume and force the contami-
3 . Calculate the value of Q by multiplying nated water toward the extraction wells. The only
(Q/HU) obtained in step 2 by (HU), the product of shortcoming of this technique is that a small
the aquifer thickness, B, and the magnitude of volume of the contaminated water currently located
regional velocity U. at the tail of the plume will fall within a zone of
4. If the well is able to produce the required relatively very small velocity and may stay there
discharge rate Q obtained in step 3 , we have for a long time. This also can be overcome by
reached the answer. That is, one is the optimum moving the recharge well( s) upstream as much as
number of pumping wells. Its optimum location is half of the distance between the calculated
copied directly from the position of the well on location and the tail of the plume.
the type curves to the contour map at the
matching position. EXAMPLE
5. If the well is not able to produce at such a This example is designed to illustrate the use
rate, then one has to follow the above procedure of this technique for aquifer cleanup. It is assumed
using the type curves for two pumping wells given that leakage from a faulty injection well has
in Figure 5 . After identifying the appropriate type contaminated a confined aquifer with trichloro-
curve and calculating the rate of discharge for each ethylene (TCE). A thorough investigation of the site
well, one has to investigate the capability of the has identified the 1'CE concentration distribution
aquifer to deliver such discharges to both pumping as given in Figure 8. Hydrologic studies have
wells. An important point to note is that because revealed the following data: aquifer thickness, 10 m ;
the zones of influence of two wells have some regional hydraulic gradient, 0.002 ; aquifer hydraulic
overlap, one may not be able to pump the same conductivity, m/s; effective porosity, 0 . 2 ;
amount of flow rate from each individual well as storage coefficient, 3 X ; and permissible draw-
one could from a single well, for the same down at each well, 7 m.
allowable drawdown. Suppose we want t o clean the aquifer such
If the aquifer is capable of delivering such that maximum remaining 'I'CE concentration after
flow rates t o both pumping wells, then the the cleanup operation does not exceed 10 ppb. To
optimum number of pumping wells is two, and optimize the aquifer cleanup operation cost we
their position can be traced directly from the type want t o minimize the cost of pumping the contam-
curves at the matching position. Note that the inated water and treating it a t the surface. Reinjec-
exact distance between each pair of wells depends tion of the treated water is an option which should
o n the choice of the type curve and should be not be ignored.
calculated from the equations given before. The first step is t o choose the optimum
However, if thc aquifer is not able to deliver that number of pumping wells, their location, and
rate of discharge required for each well, then one
has to use the type curves for the three-well case as
given in Figure 6. This procedure could be carried
out until the optimum number of wells are found.
If one decides to reinject the treated water
back into the aquifer, then one strategy could be
to d o this at the upper end of the plume, 'This
would substantially shorten the total cleanup time
of the aquifer.
To find the appropriate location for the
reinjection well(s), one can use the same technique
which we introduced for siting the extraction wells,
neglecting the interference between the recharge
and extraction wells. Here, one should match the
contour line of the plume with the type curves in a
way that the direction of regional flow o n the Fig. 8. Observed TCE concentration distribution.
622
calculate their rate of discharge, using the procedure contour on the double-well capture-zone type
given above. Figure 8 includes the contour line of curves given in Figure 5 . Matching the direction
10 ppb. The area within this curve identifies the of the regional flow and moving the contour line t o
zone where the ‘TCE concentration is above 10 ppb the left, we see that the capture curve with
that should be captured and treated, Direction of Q/BU = 1200 completely encornpasses the 10 ppb
the regional flow is also shown in this figure. l‘he contour. The corresponding rate of discharge for
scale of this map is identical to that of Figure 1. each of the two wells now becomes Q = 0.0024
Superposition of this map on Figure 1 and match- m3/sec.
ing the direction of flow indicate that the size of To check the drawdown at each of these two
the area within the 10 ppb contour is larger than wells, we should add the drawdowns of both wells
all of the type curves presented in Figure 1. at the position of each well. The optimum distance
Although one could easily prepare other type between these two wells is obtained from
curves with larger values of (Q/BU), extrapolation equation ( 9 ) :
suggests that a type curve with Q/BU = 2500 will
encompass the 10 ppb contour line. Now we
should first calculate the regional velocity U:
and drawdown at each of these two wells is obtained
U = Ki = m/s)(0.002) = 2.0 X loF7m/sec (21) from
2.3Q 2.2 5KBt 2.25KBt
Therefore, the corresponding discharge rate of the Ah =- {log + log 1 (25)
well is 4nKB r& S (2d)’S
Q ) BU= Substituting for 2d, the drawdown after one year
Q=( - becomes 6.57 m. Generally, the well losses for
BU
small discharge rates such as 0.0024 m3/sec are
(2500 m)(10m)(2 X m/sec) = 5 X m3/sec small. However, if the amount of well losses
together with the calculated drawdown 6.57 m
become larger than the assumed maximum allow-
Since cleanup operation usually lasts for several able drawdown of 7 meters, we have to examine
years, corresponding drawdown at the well bore the possibility of using three pumping wells.
may be calculated using either the equilibrium or Superposition of the 10 ppb contour line with
nonequilibrium equation for large values of time the three-well capture-zone type curves (Figure 6)
such as a year or so: gives a matching parameter of Q/RU = 800. Figure
2.3Q 2.25KBt 9 shows the 10 ppb contour line of ‘ICE on the
Ahz-log
4nKB rf S
where Ah = drawdown in the aquifer (m);
Q = pumping rate (m3/sec); K = hydraulic conduc-
tivity (m/sec); B = aquifer thickness (m); t = time
elapsed since the start of pumping (sec);
rw = effective well radius (m); and S = storage
coefficient,
Substituting for variables in equation ( 2 3 ) ,
the value of drawdown after one year and for
rw = 0.2 m becomes 9.85 m. Note that this calcula-
tion gives drawdown only in the aquifer. To obtain
total drawdown in the well, one has to add to it
the well losses. These losses are a function of the
well design, and the best way t o obtain the total
drawdown in a well is to find the specific capacity
of the well and its variation with the rate of dis-
charge and time. In the above case, since the
drawdown in the well is more than the permissible
drawdown, we will have t o use more than one Fig, 9. The 10-ppb contour line of TCE at the matching
pumping well. Thus, we superimpose the 10 ppb posltion wirh the capture-zone type curve of (Q/BU) = 800.
62 3
three-well capture-zone type curves at the matching assumption that no water with Concentration
position. The area within the contour line has been below 10 ppb is extracted by the wells. Our investi-
crosshatched for clarity. gation using RESSQ (Javandel et al., 1984) shows
The rate of discharge for each pumping well is that it takes about 48 years to extract the total
volume of contaminated water presently located
Q = 800(10)(2 X lo-') = 0.0016 m3/sec within the 10 ppb contour. This period could be
Drawdown in the middle well is the sum of the shortened substantially if we reinject the treated
drawdowns of the two lateral wells in that well water back into the aquifer at an appropriate
plus its own drawdown, which amounts to 5.7 m. location upstream from the extraction wells.
If we are convinced that the total drawdown is less To avoid mixing the highly contaminated
than 7 m or field tests indicate that, then our water with the surrounding water, it is often
optimum number of wells is three and the rate of beneficial to consider one or more extraction wells
discharge from each one is 0.0016 m3/sec. One of in the high concentration zone of the plume. The
these wells is on the origin and the other two are technique described here could be used to site
at (0, k 320) as shown in Figure 9 . these wells.
Extraction wells are assumed to penetrate and
D ISC USSI0N be open over the total thickness of the aquifer. If
The method introduced in this paper is the wells are partially penetrating the aquifer, the
intended to provide guidance to proper siting of cleanup is effective at elevations corresponding t o
extraction wells and to determine their appropriate the screened zone and is subject to error in the
rates of discharge for cleaning aquifers contaminated elevations corresponding to the nonpenetrated
with hazardous chemicals. It is important to note zone of the aquifer. In other words, contaminants
that the theory was developed based on the located in the nonpenetrated zone may not be
assumption that the aquifer is confined, homoge- totally captured if the extraction wells are only
neous, and isotropic. Obviously, for aquifers partially penetrating. Obviously, if the plume is
consisting of impermeable clay lenses and high con- located only at the upper or lower part of the
ducting flow channels, this technique may give aquifer, then partially penetrating extracting wells
erroneous results. For example, in some fluvial are beneficial.
aquifers, highly permeable channels can easily The method is based on two-dimensional flow
carry away the contaminants at a much faster rate systems which implies that the aquifer is confined.
than the general average regional flow. If the field For unconfined aquifers the solution is more
investigation has clearly identified such a channel complex. However, if the amount of drawdown
system, one can easily adapt this method to take it relative to the total saturated thickness of the
into consideration, However, these features can be aquifer is small, the error is not expected to be
missed during typical site investigations. Therefore, large.
it is recommended that some array of monitoring
wells be constructed downstream and beyond the SUMMARY
capture zone of the extraction wells. These wells Optimum design of the cleanup operation for
should be continuously monitored during the a contaminated aquifer is an important task for the
cleanup operation to insure that such channeling people in charge of such activities as well as for the
does not exist. regulatory agencies responsible for enforcing the
Although this technique minimizes the cost of requirements set by law and the National Con-
aquifer cleanup, it does not necessarily minimize tingency Plan. An important part of such task is
the operation time. Once we choose the minimum capturing the contaminated water and pumping it
pumping rate, it takes a long time to extract all of to surface. Rigorous analytical soltuions have been
the contaminated ground water. In the example presented which give the position of stagnation
described above, the total volume of contaminated points and optimum distances between pumping
water within the 10 ppb contour is about 5.16 wells t o avoid any escape of contaminated water
million cubic meters (MCM). The rate of discharge between tlie wells. Equations for the dividing
from all three wells is 0.0048 m3/sec which is about streamlines defining the capture zone of the
4 14.7 m 3/day.Therefore, ignoring biodegradation pumping wells from the rest of the aquifer are also
and adsorption, the total period required to remove presented. A series of capture-zone type curves for
5.16 MCM of Contaminated water at the above rate one, two, three, and four pumping wells are given.
is about 34 years. 'This is, of course, based on the A procedure is recommended t o facilitate selection
624
of the optimum number, location, and discharge Under the Comprehensive Environmental Response,
rate for the pumping wells. The criteria for such Compensation and Liability Act of 1980 40CFR300.
Amended by 48 FR 40669, September 1983. ’rhc
recommendations include minimizing the cost,
Bureau of National Affairs, Inc. S-672,101:1001-1043.
avoiding degradation of the water quality beyond Javandel, I., C. Doughty, and C. F. Tsang. 1984. Ground-
the selected zone, and achieving the goal that the water Transport: Handbook of Mathematical Models.
maximum concentration of a contaminant in the American Geophysical Union, Water Kesources
aquifer at the end of operation does not exceed a Monograph 10, Washington, D.C. 228 pp.
given value. In case that the treated water needs to Milne-Thomson, L. M. 1968. Theoretical Hydrodynamics.
Macmillan Company, New York. 743 pp.
be returned t o the aquifer, a procedure is suggested U.S. Environmental Protection Agency. 1984. National
for siting recharge wells. This is based on the Priorities List, 786 Current and Proposed Sites in
capture-zone technique which avoids mixing of the Order of Ranking and State, October 1984. HW-7.2,
treated water with fresh water while reducing the 75 PP.
aquifer cleanup time.
* * * * *
ACKNOWLEDGMENTS
This work was supported by the U.S. Environ- Iraj Javandel received his 1%. 11. in Civil Engineering,
,majoring in Geohydrology, f r o m t h e University of
mental Protection Agency (EPA), Kobert s. Kerr
California, Berkeley, in 1968. In 1 9 6 9 he joined t h e Pahlavi
Environmental Research Laboratory (RSKERI,), University faculty in Shiraz, Iran, where b e was a n Associate
in part pursuant t o Interagency Agreement l-’rofessor and Chairman o f t h e Civil Engineering Depart-
DW 89930722-01-0 between the U.S. EPA and m e n t . Ile has also taught courses in fluid mechanics and
the U.S. Department of Energy and in part flow in porous media at t h e University of California,
Ilerkeley. Iie bas been a staff scientist in t h e 1:’arth Sciences
under U.S. Department of Energy Contract
Division of‘the Lawrence Berkeley Laboratory since 1980.
DE-ACO3-76SF00098. The authors would like to I-Iis current principal intevest is in hydraulics o f wells,
thank Jack W . Keeley and Joseph F. Keely of mathematical modeling of ground-water Contamination,
RSKERL for their technical guidance, encourage- aquifer restoration, and underground injection.
ment, and review of this manuscript. We would Chin-Fu-Tsang received his Ph.D. in Physics frorn the
also like to thank Marcel0 Lippmann for reviewing University o f California, Berkeley in 1 9 6 9 , and is currently
a Senior Staff Scientist and D e p u t y Group Leader of t h e
this manuscript.
Ifydrogeology and Reservoir Engineering Group in t h e liartb
Sciences Division o f t h e Lawrence Rerkeley Laboratory. Iiis
REFERENCES research interests range f r o m advanced well test methods t o
Comprehensive Environmental Response, Compensation, flow o f fluids and contaminant transport through porous
and Liability Act of 1980. Public Law 96-510. The and fractured media. I1e bas been the Editor of the Inter-
Bureau of National Affairs, Inc. S-632, 71-0701-0716. national Seasonal Thermal Energy Storage Quarterly News-
Environmental Protection Agency National Oil and letter and was one o f t h e Editors f o r t h e Journal of
Hazardous Substances Pollution Contingency Plan Environmental Geology.
625