You are on page 1of 2

November 1998

TM
CARBON DIOXIDE SENSORS
SOLUTIONS MODEL 4GS

t
DESCRIPTION
The Texas Instruments 4GS Series carbon dioxide sen-

n
sors are dependable, economical devices designed to be
used as inputs to building automation systems for effi-

e
cient control of ventilation. Using ambient CO2 levels to
adjust ventilation based on demand is recognized by
ASHRAE as one of the few ways to comply with both the
ventilation and energy standards. The 4GS Series pro-

m
vides an analog output of CO 2 concentration from a
small, attractive wall mount package. An optional relay

u
output is available for direct control of equipment, and an
optional LCD display may be used for local indication.

c
For duct applications, the 4GS may be combined with an
optional aspiration box. If the duct pressure is positive or

o
neutral and air velocity exceeds 200 ft/min (1.0 m/s), a
less expensive impact sampling tube may be used.

D
FEATURES

• Analog output: 4-20 mA standard • Optional LCD display

d
• Field selectable 0-10 VDC or 0-5 VDC output • No initial calibration required
• 24 VAC or DC power • Small, attractive wall mount enclosure
• 3-year calibration interval • Optional duct aspiration box or sampling tube kit

e
• Optional relay (programmable setpoint)

iv
SPECIFICATIONS

h
Power 18-28 VAC 50/60 Hz or 18-40 Analog output 4-20 mA into 500 ohm maximum

c
VDC, less than 3 VA load (standard), field convertible
to 0-5 VDC or 0-10 VDC with

r
Sensing method NDIR – Non Dispersive Infrared 1000 ohm output impedance

Measuring range 0 to 2000 ppm standard, field Optional relay Normally open, 10 mA to 500 mA

A
adjustable from 0 to 300 ppm at 24 VAC or 30 VDC
to 0 to 5000 ppm Field adjustable setpoint 300 ppm
to 5000 ppm,100 ppm hysteresis
Accuracy ±75 ppm from 0 to 1500 ppm below setpoint
±5% above 1500 ppm
Storage condition -4° to 158°F (-20° to 70°C)
Pressure effect 0.19% of reading per mm Hg 5% to 95% RH, non condensing

Repeatability ±8 ppm Case ABS plastic, UL 94V-0

Calibration interval 3 years recommended Weight 13 oz (0.37 kg)

Operating condition 32° to 122°F (0° to 50°C) Agency approval FCC part 15 Class A, CE
5% to 95% RH, non condensing

KELE • www.kele.com • FAX 901-372-2531 USA 901-937-4900 • International 901-382-6084


rev. 11/98
DIMENSIONS WIRING

in
(cm) (I) (V) (R) (M)
Current Voltage Run or Menu Display Models ONLY
Output Select Mode Select
3.84˝ Jumper Jumper
(9.8) V M

t
I R
Enter

n
CO2 COMMON
CO2 OUT
RELAY
RELAY
24 VAC/DC COMMON
24 VAC/DC IN
Select
3.84˝ 1.1˝
(9.8) (2.8)

e
4GS Sensor
0.62
(1.58)

m
1.25
1.12 (3.17)
(0.62) 2.5 18-30 VAC or
(6.35) - + 18-40 VDC (No Polarity)
5.12

u
(13.01) Analog
8 Output Control Relay (Optional)
(20.3) Contacts make on rise in CO2

c
5.12 1.75
(13.01) (4.44)
Note: CO2 Common and 24 VAC/DC Common

o
3
(7.62) are connected internally.

Duct Aspiration Box (Optional)

MOUNTING

D
d
The 4GS sensor should be mounted in an area that is representative of the conditioned space to be monitored.

e
Avoid drafty windows and doorways that might tend to dilute the atmosphere being controlled. Mounting height of
4 1/2 to 5 feet (1.2 to 1.5 m) is recommended but is not critical since carbon dioxide diffuses rapidly in air.

iv
The 4GS comes factory configured for 4-20 mA analog output. If voltage output is required, moving the jumper on
the back of the unit from “I” to “V” will change the output to 0-10 VDC. The voltage output may in turn be changed to
0-5 VDC, the sensing range adjusted, and the (optional) relay setpoint changed by use of the programming keys on

h
the back of the 4GS and its optional LCD display. Units with no display will require the CAL-B-KEY calibration key-
pad for adjustment. Refer to the programming manual supplied with the 4GS for configuration and calibration

c
instructions.

A r 4GS-22C-06
4GS-22CD-06
4GS-22CR-06
4GS-22CDR-06
ORDERING INFORMATION

Sensor with Analog Output Only


Sensor with Analog Output and Display
Sensor with Analog Output and Relay
Sensor with Analog Output, Display and Relay

4GS-DM-KIT Duct Mount Kit for 4GS Sensor (order sensor separately)
4GS-PT-KIT Impact Sampling Tube Kit for 4GS Sensor (order sensor
separately)

CAL-B-KEY Calibration Keypad with Cable and Connector for 4GS Sensor

KELE • www.kele.com • FAX 901-372-2531 USA 901-937-4900 • International 901-382-6084