Water Cooled Manual IOM120229 1.10

You might also like

You are on page 1of 76

 

Installation, Operation & Maintenance Manual


Standard Water Cooled Range

 
 


SCWIOMM0001.10 
Installation Manual

 
This page is intentionally blank.


SCWIOMM0001.10 
Installation Manual

Proprietary Notice 
 
This  publication  contains  information  proprietary  and  confidential  to  Smardt  Chillers  Pty  Ltd  trading  as 
PowerPax‐Smardt  (hereafter  referred  to  as  PowerPax‐Smardt).  Any  reproduction,  disclosure  or 
unauthorized  use  of  this  publication  is  expressly  prohibited  without  written  approval  from  PowerPax‐
Smardt.  PowerPax‐Smardt  reserves  the  right  to  make  changes  without  notice  in  product  or  component 
design as warranted by evolution in user needs or progress in engineering or manufacturing technology.  
   
PowerPax‐Smardt has exercised its best efforts to ensure that the information contained in the manual is 
correct.  However,  no  warranty  of  reliability  or  accuracy  is  given  with  respect  to  the  information  and 
PowerPax‐Smardt  is  not  and  shall  not  be  responsible  or  liable  for  the  correctness  or  suitability  of  the 
information or for any error or omission.  
 
All brand names and product names used in the manual are trademarks, registered trademarks, or trade 
names of their respective holders.  
 
© 2011, PowerPax & Smardt Chillers & Smardt Inc. All rights reserved.  
 
 
 

For product support issues, corrections, or enquiries contact: 
 
Product Support 
service.admin@powerpax.com.au 
 
PowerPax‐Smardt 
144 Colchester Road 
PO Box 2021 
Bayswater North, Vic, 3153 
Australia 
+61 3 9761 5055
www.powerpax.com.au 

Smardt Chillers – Singapore 
1 Maritime Square 
11‐19A Harbourfront Centre 
Singapore, 099253 
+65 6273 1120


SCWIOMM0001.10 
Installation Manual

Table of Contents 
Installation, Operation & Maintenance Manual ....................................................................... 1 
Proprietary Notice ....................................................................................................................... 3 
List of Acronyms / Definitions .................................................................................................. 7 
Installation ............................................................................................................................ 10 
General ...................................................................................................................................... 10 
Safety Precautions ..................................................................................................................... 10 
Safety Guidelines ....................................................................................................................... 10 
Warranty, Commissioning & Maintenance ............................................................................... 11 
Spare Parts ................................................................................................................................. 11 
Training ...................................................................................................................................... 11 
General Description ................................................................................................................... 12 
Customer Service ....................................................................................................................... 12 
Heat Exchangers ........................................................................................................................ 13 
Evaporator .............................................................................................................. 13 

Water Cooled Condenser ....................................................................................... 13 

Refrigeration Components ..................................................................................... 13 

Controls ................................................................................................................... 13 

Safeties .................................................................................................................... 14 

Information on Welding ............................................................................................................ 14 
Foundation ................................................................................................................................ 14 
Clearance and Maintenance Access .......................................................................................... 14 
Nameplates ............................................................................................................................... 15 
Unpacking and Inspection ......................................................................................................... 16 
Unit Placement .......................................................................................................................... 17 
Rigging Requirements ................................................................................................................ 19 
Dimensional Drawings ............................................................................................................... 20 
Piping Configurations and Flow Connections ............................................................................ 32 
Minimum Water Loop Volumes ................................................................................................ 33 
Evaporator Water Circuits ......................................................................................................... 33 
Flow Detection Devices ............................................................................................................. 33 


SCWIOMM0001.10 
Installation Manual

Relief Valves .............................................................................................................................. 34 
Control Field Wiring ................................................................................................................... 34 
Power Wiring ............................................................................................................................. 35 
Disconnects and Power Wiring .................................................................................................. 36 
Circuit Breakers ......................................................................................................................... 38 
Line Reactor / RFI Filters ............................................................................................................ 38 
Wiring Diagram & Schematic..................................................................................................... 38 
Pre‐Commissioning .................................................................................................................... 39 
Operation .............................................................................................................................. 44 
System Checks Before Start Up ................................................................................................. 44 
Powering up Compressors ......................................................................................................... 46 
PowerPax‐Smardt Controller ................................................................................. 47 

Inputs, Outputs, & Interlocks ................................................................................. 48 

Head Pressure Control Option ............................................................................... 50 

Summary of Status Contacts .................................................................................. 50 

High Level Options .................................................................................................. 51 

Operating the Controller ........................................................................................................... 52 
Password Access ..................................................................................................... 52 

Navigating the Controller ....................................................................................... 52 

Data Entry ............................................................................................................... 52 

Alarm Button ........................................................................................................... 52 

Carel Controller User Level Screens .......................................................................................... 53 
Front User Screen ................................................................................................... 53 

Main Menu ............................................................................................................. 54 

Operational Data .................................................................................................... 54 

User Settings ........................................................................................................... 56 

Compressor MB Data ............................................................................................. 57 

Clock ........................................................................................................................ 58 

History ..................................................................................................................... 59 


SCWIOMM0001.10 
Installation Manual

Information ............................................................................................................. 60 

Maintenance ......................................................................................................................... 63 
Water Cooled Maintenance Form ............................................................................................. 65 
Appendix 1 – Recommended Spare Parts List ........................................................................... 71 
Appendix 2 – Wiring Schematic ................................................................................................. 73 


SCWIOMM0001.10 
Installation Manual

List of Acronyms / Definitions

BACnet  Proprietary High Level Protocol 
BMCC  Bearing Motor Compressor Controller 
COM  Communications (RS232) Serial Port 
EXV  Electronic Expansion Valve 
HLI  High Level Interface
IGBT  Insulated Gate Bipolar Transistor (Inverter) 
IGV  Inlet Guide Vane 
I/O Board  Compressor Interface Module 
LBV  Load Balancing Valve 
LED  Light Emitting Diode
ModBus  Proprietary High Level Protocol 
PCB  Printed Circuit Board 
PCO3  Carel Controller with PowerPax‐Smardt Software 
PGD3  Color Touchscreen Display 
PWM  Pulse Width Modulation – Bearing Amplifier 
RFI  Radio Frequency Interference 
SCR  Silicon Controlled Rectifier 


SCWIOMM0001.10 
Installation

 
 
This page is intentionally blank. 


SCWIOMM0001.10 
Installation

 
PowerPax‐Smardt 
Installation Manual 


SCWIOMM0001.10 
Installation

Installation 

General 
 
This manual is intended to inform contractors, building owners, and engineers of the installation, commissioning, 
operation,  and  maintenance  requirements  for  the  PowerPax‐Smardt  air  cooled  centrifugal  chiller  range.  It  is 
intended  that  this  document  be  used  alongside  the  applicable  chiller  general  assembly  drawing  and  wiring 
diagrams, supplied with the chiller.  
 
Prior to installation and set‐up of this chiller, it is intended that those involved in the installation, set‐up, operation 
and  maintenance  of this  chiller familiarize  themselves  with  the procedures  in  this  manual.  This  manual  contains 
the information necessary to become familiar with the controls system prior to working on this system.  

Safety Precautions 
 
Access  to  the  PowerPax‐Smardt  chiller  must  be  reserved  for  authorized  personnel.  Only  those  trained  in 
maintenance and service are authorized to access the unit.  
 
Safety precautions must be observed during installation, start‐up and all service of the chiller due to the presence 
of high pressure refrigerant charge and high voltage hazards. Only qualified personnel should install, start‐up and 
service this equipment. Failure to use qualified personnel to work on PowerPax‐Smardt equipment will affect the 
equipment warranty and may result in serious injury. 
 
Always ensure that all required safety measures are followed such as: 
 
 Wearing protective clothing (gloves, shoes etc) 
 Wearing safety glasses 
 Wearing a grounding wrist strap 
 Using appropriate tools 
 Employing qualified electricians 
 Employing PowerPax‐Smardt trained and certified refrigeration technicians 
 Following local regulations and codes 
 

Safety Guidelines 
 
Never cover or obstruct any safety device, including the relief valves in the refrigerant circuits. Ensure that all relief 
valves are vented outside the building/plant area in accordance with safety regulations. High concentration levels 
of  refrigerant  in  enclosed  spaces  can  displace  oxygen  and  cause  asphyxiation  and  lead  to  heart  irregularities, 
unconsciousness, or death. Do not disable any safety devices.  
 
 

10 
SCWIOMM0001.10 
Installation

 
WARNING! 
High  voltage  electrical  equipment  is  potentially  lethal!  Isolate  incoming  electrical  power  before  attempting 
installation  of  the  equipment.  If  work  is  interrupted,  ensure  that  all  circuits  are  de‐energized  and  power  is  still 
isolated before continuing work. Only a qualified electrician should work on high‐voltage electrical equipment.  
 
 
 
  Wait a minimum of 15 minutes after isolating power before removing compressor access covers
as capacitors can store sufficient charge to cause electrocution within this time frame.

Warranty, Commissioning & Maintenance 
 
Commissioning  and  maintenance  of  all  PowerPax‐Smardt  chillers  is  to  be  undertaken  by  PowerPax‐Smardt  or  a 
PowerPax‐Smardt certified service provider. Failure to comply with this requirement will void the chiller warranty. 
PowerPax‐Smardt  chillers  come  with  a  unit  parts  and  labour  warranty  in  respect  to  all  non‐consumable  parts 
(when  installed  within  Australia,  International  warranty  may  vary),  for  a  period  of  12  months  from  the  date  of 
commissioning or 18 months from the date of dispatch from PowerPax‐Smardt – whichever is sooner.  
 
Warranty is not a substitute for maintenance. Warranty cover is conditional upon maintenance being carried out 
according to the PowerPax‐Smardt recommendations during the warranty period. Failure to follow the designated 
maintenance  procedures  and  schedules  will  void  the  chiller  warranty  and  remove  any  liability  from  PowerPax‐
Smardt. Please consult the PowerPax‐Smardt Terms and Conditions for a warranty statement.  
 

Spare Parts 
 
PowerPax‐Smardt has a recommended spare parts list. Stocking the recommended spare parts can reduce service 
response times. See Appendix 1 for the recommended spare parts list. For the recommended spare parts price list 
please contact the PowerPax‐Smardt service department.  
 

Training 
 
PowerPax‐Smardt  offers  a  range  of  training  courses  on  the  complete  range  of  PowerPax‐Smardt  products.  For 
further information on the training courses available please see the PowerPax website (www.powerpax.com.au) or 
contact PowerPax‐Smardt directly.  
 
 
 

11 
SCWIOMM0001.10 
Installation

General Description 
 
PowerPax‐Smardt make a range of water cooled chillers from 200 to 3500kWr. The PowerPax‐Smardt water cooled 
chiller range consists of Danfoss Turbocor centrifugal compressor(s), a flooded R134a shell and tube evaporator, 
and a water cooled condenser. Liquid control is via a PowerPax‐Smardt Electronic Expansion Valve (EXV).  
 
The  compressors  are  semi‐hermetic,  two  stage,  direct  drive,  variable  speed  centrifugals.  This  is  a  high  speed 
centrifugal machine which employs advanced magnetic bearing technology and direct drive to eliminate the need 
for oil within the system.  
 
Capacity  control  is  provided  by  variable  speed  drive  and  inlet  guide  vanes,  capable  of  reducing  compressor 
capacity to 25% of full load (at ARI550/590 standard part load conditions).  
 
To accommodate loads below 25% there is a provision for discharge gas to be injected into the evaporator. This 
provision is implemented by the controller only after the maximum turn down has been achieved by compressor 
speed  reduction.  This  ensures  that  the  maximum  efficiency  is  maintained  at  all  times.  This  load  balancing  valve 
feature can be disabled by the user through the chiller controller. 
 
The compressor starts unloaded and current is limited to less than 2 amps per compressor. The maximum amps 
are  also  limited  to  a  preset  value  by  the  compressors  inbuilt  control  software.  Motor  cooling  is  provided  by  an 
integrated  liquid  refrigerant  injection  system  controlled  by  the  compressor.  The  compressor  is  equipped  with 
discharge and suction shutoff (isolating) valves, and fitted check valves to prevent reverse spin on shutdown.  
 
As a guide, a number of units from 200 to 2800kWr at nominal conditions have been pre‐selected and used 
throughout the manual for information purposes only. 
 
Please contact PowerPax with your specific requirements or specific technical data. 

Customer Service 
 
For additional product support please contact the PowerPax‐Smardt service department at: 
service.admin@powerpax.com.au or call +61 3 9761 5055.  
 
For additional sales support please contact the PowerPax sales department at: sales@powerpax.com.au or call +61 
3 9761 7905.  
 
For additional product support, or Sales Support throughout Asia‐Pacific, please contact the Singapore Office at: 
sales.asia@smardt.com or call +65 6273 1120 
 
Or visit the PowerPax website at: www.powerpax.com.au 
 

12 
SCWIOMM0001.10 
Installation

Heat Exchangers 

Evaporator 
The evaporator is a flooded shell and tube design using enhanced surface finned copper tubes. It is constructed in 
accordance  with  ASME  code  for  a  refrigerant  side  working  pressure  of  1320kPa  and  is  tested  for  a  maximum 
water‐side pressure of 1000 kPa.  
 
The evaporator shell is insulated with 19mm closed‐cell foam (max k factor of 0.038W/mK) with a vapor barrier 
skin as standard. Further insulation is available as an optional extra.  
 

Water Cooled Condenser 
The  condenser  is  a  flooded  shell  and  tube  design  using  enhanced  surface  copper  tubes.  It  is  constructed  in 
accordance  with  ASME  code  for  a  refrigerant  side  working  pressure  of  1320  kPa  and  is  tested  for  a  maximum 
water‐side pressure of 1000 kPa. 
 
Correct  operating  refrigerant  level  is  maintained  by  a  control  feedback  loop  which  uses  a  resistance  type  level 
sensor. This control function is built into the chiller controller which maintains the levels in the heat exchangers by 
modulating the position of a stepper motor driven EXV. Similarly, the hot gas injection is controlled by the chiller 
controller  via  a  stepper  motor  driven  valve.  The  set  points  and  control  terms  for  these  functions  are  set  at 
commissioning via the chiller controller interface. 
 

Refrigeration Components 
Refrigerant  circuit  components  include  pressure  relief  valves,  combination  discharge  check  and  isolation  valves, 
suction  line  valves,  motor  cooling  line  filter  drier,  liquid  line,  condenser  level  float  chamber,  sight  glasses, 
electronic expansion and load balancing valves and motor cooling isolation valves. The refrigeration system does 
not contain oil.  
 

Controls 
The chiller controller utilizes a microprocessor based controller running on PowerPax‐Smardt proprietary software. 
It  handles  the  basic  functions  of  chilled  water  temperature  control,  and  condenser  head  pressure  control.  The 
controller  incorporates  a  function  to  trip  the  circuit  breaker  in  the  event  of  a  compressor  controls  failure.  The 
controls  protect  the  chiller  against  freezing  by  monitoring  for  low  leaving  water  temperature  and  loss  of  water 
flow  (via  the  external  interlocks).  The  controller  also  monitors  the  compressor  status  signal  which  indicates  the 
state of various production functions built into the compressor controller.  
 
In‐built compressor control functions protect against high head pressure, low suction pressure, power supply faults 
(voltage  and  imbalance),  excess  power  input,  excess  amps  input,  excess  motor  temperature,  and  excessive 
electronics temperature.  
 
The  controller  fitted  to  the  PowerPax‐Smardt  water  cooled  chiller  is  a  PLC  based  device  manufactured  by  Carel 
utilizing  imbedded  control  software  written  specifically  by  PowerPax‐Smardt  for  PowerPax‐Smardt  chiller 
applications. It utilizes a color touch screen interface and provides access to  settings via a combination  of touch 
screen and button controls.  
The various applications are selectable through user interface screens to the touch screen interface. The status of 
the compressors and various systems parameters can be viewed on these screens as can the log of up to 20 past 
alarm events. The program is stored in non‐volatile memory and can be upgraded in the field.  

13 
SCWIOMM0001.10 
Installation

 
The compressor controller also ensures compressor operation is between the limits (eg. surge) of its operational 
envelope at all times.  
 

Safeties 
PowerPax‐Smardt water cooled units are equipped to provide the following protection: 
 
 Low chilled water temperature 
 Power supply errors 
 Compressor motor thermal or electrical overload 
 Phase loss 
 High pressure  
 Low pressure 
 Loss of chiller water flow via an interlock to an external flow switch 
 Loss of condenser water flow to an external flow switch

Information on Welding 
 
PowerPax‐Smardt vessels are either ASME or AS1210 certified. Please note that welding should never be 
performed on the vessels or tube sheets. Such a practice will void the ASME certification. Do not weld on any part 
of the chiller under any circumstances as current can travel through the chiller earth if the welder earth is not 
satisfactory, unnecessarily damaging chiller and/or compressor electronics and voiding the unit warranty.

Foundation 
 
Before installing the chiller set, ensure that the supporting floor meets the load bearing requirements. Consult the 
Dimensions and Weight Table on page 17 to determine the load bearing requirements. Four point supports must 
be installed, two at each end of the chiller.   
 
PowerPax‐Smardt is not responsible for the load bearing capacity of the floor.  
 

Clearance and Maintenance Access 
 
Adequate  clearance  around  the  chiller  set  is  essential  to  facilitate  maintenance  and  service.  Required  minimum 
clearances are tabulated under “Water Cooled Chiller Clearances” on page 18, please ensure that adequate space 
for  all  installation  and  service  operations  is  allowed.  Check  that  the  minimum  clearance  complies  with  all  local 
electrical codes.  
 
Each compressor weighs approximately 140 kilograms. It is advised that sufficient access be provided  for rigging 
equipment  and  also  is  allowed  for  a  small  trolley  to  easily  be  brought  alongside  the  chiller,  to  allow  for  future 
service and maintenance needs.  
 

14 
SCWIOMM0001.10 
Installation

Nameplates 
 
Nameplates are located in various locations on the chiller.  
Figure 1: Chiller Nameplate
The  chiller  unit  nameplate  is  located  inside  the  control 
cabinet  door and  contains  both  a  model  and  serial  number. 
Both  of  these  numbers  are  unique  to  the  particular  chiller 
and  help  identify  it.  These  numbers  should  be  used  to 
identify the chiller for service, parts and warranty enquiries. 
Check  that  the  information  on  the  chiller  nameplate  is 
consistent with the chiller ordered.
Figure 2: Evaporator/Condenser Nameplate
Both the evaporator and condenser have nameplates. These 
plates  have  serial  numbers  which  identifies  the  individual 
vessels, but not the entire unit. These plates also provide the 
year  of  manufacture,  the  rated  pressures,  and  operating 
temperature ranges of the vessels.     
 
Each  compressor  also  has  a  nameplate.  These  nameplates 
help  identify  the  individual  compressors.  The  serial  number 
on  these  plates  should  be  used  when  identifying  the 
compressor in question for any service, parts or warranty   Figure 3: Compressor Nameplate
enquiries.  
 
To  obtain  some  replacement  parts  it  may  be  necessary  to 
quote  the  Model  Number,  Serial  Number,  and  Part  Number 
which are found on the above plates.  
                             

15 
SCWIOMM0001.10 
Installation

Unpacking and Inspection 
 
Upon receipt of the chiller it should be inspected immediately for any possible damage and checked thoroughly to 
ensure  that  everything  is  complete.  The  unit  should  be  carefully  inspected  for  damage  to  the  evaporator 
insulation, broken wires, and loose piping and bolts. If damage is suspected immediately perform a leak test, and 
repair any leaks if found. If damage is detected, or the shipment is incomplete, immediately file a claim with the 
shipping company and notify PowerPax‐Smardt.  
 
Upon receipt confirm that the unit received is the unit that was ordered. Compare the chiller nameplate with the 
specifications on the order.  
 
Do  not  remove  any  packing  materials  until  the  chiller  is  in  its  final  position  as  moving  the  unit  without  the 
packaging may result in damage, which will not be covered by the PowerPax‐Smardt warranty. 
 
Confirm  that  all  accessories  ordered  with  the  chiller  have  been  supplied.  Report  any  shortages  to  PowerPax‐
Smardt immediately.  
 
 
Figure 4: Major Components Diagram
 

16 
SCWIOMM0001.10 
Installation

Unit Placement 
 
Before  placing  the  unit,  consult  the  Chiller  Dimensions  and  Weight  Table  (Table  1)  and  Chiller  Clearances  Table 
(Table 2) to confirm that there is adequate room for all connections and to service the chiller. Install the chiller on 
approved  anti‐vibration  mounts.  Each  corner  should  be  supported  on  vibration  eliminators  and  steel  plates  or 
suitably isolated from the plant room floor. Generally waffle pads are considered suitable as the PowerPax‐Smardt 
chiller  is  virtually  vibration  free.  PowerPax‐Smardt  does  not  recommend  the  use  of  spring  isolators.  The  chiller 
should be protected from excessive ground or pipe borne vibration from external sources such as pumps.  
 
Once installed, remove the rigging equipment and check for longitudinal and transverse alignment. Add shims, if 
necessary, to level the unit along both axis. Obtaining a 0 incline along the x and y axis is important. The following 
tables  contain  the  dimensions  and  clearances  required  for  the  standard  PowerPax‐Smardt  Water  Cooled  range. 
Please confirm these for each specific job, even if the model number matches as dimensions are subject to change 
in accordance with our continuous development policy.  
 
Table 1: Water Cooled Dimensions and Weights

Model  Height (mm)  Width (mm)  Length (mm)  Weight (kg) 


WA027.1BHX.44N  2070  1265  2525  2455 

WA031.1BHX.44N  2100  1265  2505  2680 


WA040.1HHX.44N  2370  1360  2535  3530 
WA044.2BHX.22N  2100  1265  3775  3615 
WA044.2BHX.33N  2100  1265  3775  3615 
WA050.2BHX.22N  2100  1265  3775  3660 
WA050.2BHX.23N  2100  1265  3775  3660 

WA052.2BHX.22N  2100  1265  3775  3710 

WA059.2BHX.44N  2390  1335  2585  4270 

WA062.2BHX.22N  2100  1265  3775  3990 

WA062.2BHX.33N  2100  1265  3775  3980 

WA074.3BHX.22N  2100  1265  4175  4500 

WA084.3BHX.22N  2100  1265  4175  4680 

WA088.2HHX.44N  2420  1360  3030  5410 

WA092.3BHX.22N  2340  1335  4175  5240 

WA095.2HHX.22N   2390  1360  3735  5070 

WA096.2HHX.22N   2390  1360  4185  5070 

WA105.4BHX.32N  2340  1335  4535  6115 

WA120.4BHX.22N   2360  1335  4535  6320 

WA125.3AHX.22N  2390  1360  4535  5965 

WA140.3HHX.22N   2420  1360  5030  7240 

WA150.5BHX.22F  2390  1565  5030  7955 

WA180.4HHX.22NS  2420  1360  5030  9560 

WA190.4HHX.22S  1975  2140  5030  9010 

WA240.5HHX.22S  1975  2140  5530  10675 

WA260.6HHX.22S  1975  2140  6530  12785 

17 
SCWIOMM0001.10 
Installation

Table 2: Water Cooled Chiller Clearances

Minimum Clearances (mm) 
Model  Tube Clean  Non‐Tube  Front & Back  Centre of Gravity (mm from left 
Above Chiller 
End of Chiller*  Clean End  of Chiller  hand rigging point) 
WA027.1BHX.44N  2525  1200  1300  400  971 

WA031.1BHX.44N  2505  1200  1300  400  974 

WA040.1HHX.44N  2535  1200  1300  400  974 

WA044.2BHX.22N  3775  1200  1300  400  1569 

WA044.2BHX.33N  3775  1200  1300  400  1569 

WA050.2BHX.22N  3775  1200  1300  400  1570 

WA050.2BHX.23N  3775  1200  1300  400  1570 

WA052.2BHX.22N  3775  1200  1300  400  1570 

WA059.2BHX.44F  2585  1200  1300  400  970 

WA062.2BHX.22N  3775  1200  1300  400  1572 

WA062.2BHX.33N  3775  1200  1300  400  1572 

WA074.3BHX.22N  4175  1200  1300  400  1780 

WA084.3BHX.22N  4175  1200  1300  400  1781 

WA088.2HHX.44F  3030  1200  1300  400  1228 

WA092.3BHX.22N  4175  1200  1300  400  1783 

WA095.2HHX.22N   3735  1200  1300  400  1587 

WA096.2HHX.22N   4185  1200  1300  400  1785 

WA105.4BHX.32N  4535  1200  1300  400  1975 

WA120.4BHX.22N   4535  1200  1300  400  1976 

WA125.3AHX.22N  4535  1200  1300  400  1976 

WA140.3HHX.22N   5030  1200  1300  400  2234 

WA150.5BHX.22F  5030  1200  1300  400  226 

WA180.4HHX.22N S  5030  1200  1300  400  2510 

WA190.4HHX.22S  5030  1200  1300  400  2258 

WA240.5HHX.22S  5530  1200  1300  400  2506 

WA260.6HHX.22S  6530  1200  1300  400  3007 


* Right or left is determined by facing the chiller in front of the control panel.   
**Centre of Gravity measurements are mm from left hand rigging points.  
NOTE: Centre of Gravity measurements are applicable for rigging and chillers directly mounted on a concrete plinth. Spring isolators are not recommended by 
PowerPax‐Smardt and cannot be used in conjunction with the above centre of gravity measurements.    

18 
SCWIOMM0001.10 
Installation

Rigging Requirements 
 
Care  must  be  exercised  at  all  times  when  rigging  or  handling  the  new  chiller  to  protect  it  from  damage.  Where 
possible, all packaging and protection should be left in place until the chiller is in its final position. Care should be 
taken to ensure that slings do not damage the compressors or control cabinets.  
 
Four rigging  points (two at  each end) are  provided on the evaporator tube sheet corners. The chiller’s centre of 
gravity  must  be  considered  when  rigging  to  ensure  that  the  chiller  is  secure  and  balanced  when  suspended.  A 
spreader bar / I‐beam combination should be used to safely position the chiller into its final location. When lifting 
the unit always ensure that the slings are of the correct lifting capacity. The PowerPax‐Smardt units should not be 
lifted from any points other than the lifting points on the tube sheet corners. 
 
PowerPax‐Smardt  is  not  responsible  for  the  rigging  and  placement  of  the  unit.  PowerPax‐Smardt  strongly 
recommends that a specialized company unloads the machine.  
 
Local codes and regulations regarding the lifting of this equipment may apply. Always ensure that these codes are 
adhered to.  
 
The  rigging  details  are  shown  below  in  Figure  5:  Rigging  Diagram.  Refer  to  Table  2:  Water  Cooled  Chiller 
Clearances on page 18 for the Centre of Gravity information.  
 
 
Figure 5: Rigging Diagram

19 
SCWIOMM0001.10 
Installation

Dimensional Drawings 

Figure 6: Dimensional Drawing WA027.1BHX.44N.

 
 
Figure 7: Dimensional Drawing WA031.1BHX.44N

20 
SCWIOMM0001.10 
Installation

Figure 8: Dimensional Drawing WA040.1HHX.44N

 
 
 
Figure 9: Dimensional Drawing WA044.2BHX.22N & WA044.2BHX.33N

21 
SCWIOMM0001.10 
Installation

Figure 10: Dimensional Drawing WA050.2BHX.22N & WA050.2BHX.23N

 
 
 
Figure 11 Dimensional Drawing WA052.2BHX.22N

 
 
 
 

22 
SCWIOMM0001.10 
Installation

Figure 12: Dimensional Drawing WA059.2BHX.44N

 
 
 
 
 
Figure 13: Dimensional Drawing WA062.2BHX.22N & WA062.2BHX.23N

23 
SCWIOMM0001.10 
Installation

Figure 14: Dimensional Drawing WA074.3BHX.22N

 
 
 
 
Figure 15: Dimensional Drawing WA084.3BHX.22N

 
 
 

24 
SCWIOMM0001.10 
Installation

Figure 16: Dimensional Drawing WA088.2HHX.44N

 
 
 
 
Figure 17: Dimensional Drawing WA092.3BHX.22N

 
 

25 
SCWIOMM0001.10 
Installation

Figure 18: Dimensional Drawing WA095.2HHX.22N

 
 
 
 
 
Figure 19: Dimensional Drawing WA096.2HHX.22N

 
 
 
 
 
 

26 
SCWIOMM0001.10 
Installation

Figure 20: Dimensional Drawing WA105.4BHX.32N

 
 
 
 
 
Figure 21: Dimensional Drawing WA120.4BHX.22N

 
 
 
 
 
 

27 
SCWIOMM0001.10 
Installation

Figure 22: Dimensional Drawing WA125.3AHX.22N

 
 
 
 
Figure 23: Dimensional Drawing WA140.3HHX.22N

 
 
 
 
 
 

28 
SCWIOMM0001.10 
Installation

Figure 24: Dimensional Drawing WA150.5BHX.22F

 
 
 
 
 
Figure 25: Dimensional Drawing WA180.4HHX.22NS

 
 
 
 
 

29 
SCWIOMM0001.10 
Installation

Figure 26: Dimensional Drawing WA190.4HHX.22S

 
 
 
 
 
Figure 27: Dimensional Drawing WA240.5HHX.22S

 
 
 
 
 
 

30 
SCWIOMM0001.10 
Installation

Figure 28: Dimensional Drawing WA260.6HHX.22S

 
 
Note: Above are the typical dimensional drawings for PowerPax‐Smardt chillers. Due to PowerPax‐Smardt policy of continuous development dimensions are subject 
to change without notice. Please contact PowerPax‐Smardt for specific dimensions.  

31 
SCWIOMM0001.10 
Installation

Piping Configurations and Flow Connections 
 
The  evaporator  and  condenser  have  Victaulic  Type  stubs  (unless  specified  as  flanged)  for  connection  to  the 
external water circuits.  
 
All  external  piping  must  be  adequately  supported  and  aligned  to  prevent  strain  and  distortion  on  the  chiller 
headers  and  couplings.  See  Table 3  for  piping  connections  and  typical  flow  configurations.  Please  consult  the 
specific chillers specification sheet for exact Flows and Pressure Drops.  
 
Table 3: Evaporator Piping Connections and Flow Configurations

Nominal  Evaporator  Condenser


Model  Capacity 
(kWr) No. of Passes  Flow Rate (l/s)*  Size (inch vict.) No. of Passes  Flow Rate (l/s)*  Size (inch vict.)
WA027.1BHX.44N  270  4  11.6  4  4  14.6  4 
WA031.1BHX.44N  280  4  12  4  4  15.1  4 
WA040.1HHX.44N  400  4  17.2  5  4  21.6  5 
WA044.2BHX.22N  440  2  18.9  5  2  23.8  5 
WA044.2BHX.33N  440  3  18.9  5  3  23.8  5 
WA050.2BHX.22N  500  2  21.5  5  2  27  5 
WA050.2BHX.23N  470  2  20.2  5  3  25.4  5 
WA052.2BHX.22N  520  2  22.4  5  2  28.1  5 
WA059.2BHX.44F  590  4  25.4  5  4  31.9  5 
WA062.2BHX.22N  619  2  26.6  6  2  33.4  6 
WA062.2BHX.33N  610  3  26.2  6  3  32.9  6 
WA074.3BHX.22N  740  2  31.8  6  2  40.0  6 
WA084.3BHX.22N  840  2  36.1  6  2  45.4  6 
WA088.2HHX.44F  880  4  37.8  8  4  47.5  8 
WA092.3BHX.22N  860  2  37.0  6  2  46.4  6 
WA095.2HHX.22N   950  2  40.7  6  2  51.3  6 
WA096.2HHX.22N   960  2  41.3  8  2  51.8  6 
WA105.4BHX.32N  990  2  42.6  6  2  53.5  6 
WA120.4BHX.22N   999  2  43  8  2  53.9  6 
WA125.3AHX.22N  1245  2  53.5  8  2  67.2  6 
WA140.3HHX.22N   1400  2  60.2  8  2  75.6  6 
WA150.5BHX.22F  1200  2  51.6  8  2  64.8  6 
WA180.4HHX.22NS  1800  2  77.4  8  2  97.2  8 
WA190.4HHX.22S  1840  2  50.9  8  2  99.4  8 
WA240.5HHX.22S  2400  2  103.2  8  2  129.6  8 
WA260.6HHX.22S  2600  2  111.8  10  2  140.4  8 
*Based on ARI Standard Temperature Design 

32 
SCWIOMM0001.10 
Installation

Minimum Water Loop Volumes 
 
In  the  evaporator  and  condenser  water  circuits  there  is  a  minimum  water  volume  requirement  of  3.5  litres  per 
cooling  kilowatt  (kWr)  for  all  air  conditioning  applications  and  7  litres  per  cooling  kilowatt  (kWr)  for  all  process 
cooling  applications.  Non‐comfort  cooling  applications  should  be  checked  for  recommended  loop  volume  with 
sales@powerpax.com.au.  Recommendations  are  available  from  our  office  for  placement  of  peripheral  items 
including chilled water bypass and inertia tank systems.  

Evaporator Water Circuits 
 
The  chiller  performance  and  efficiency  can  be  adversely  affected  by  contaminants  in  the  water  circuit.  Such 
contaminants may impede or block the flow of water 
through  the  circuit  or  reduce  heat  exchanger 
performance.    
   
Strainers  should  be  located  on  the  inlet  side  of  the 
evaporator.  Return  water  to  the  chiller  must  be 
connected to the lower connection of the evaporator. 
All external  water  piping  must  be  cleaned  or  flushed 
before being connected to the chiller set.  
 
The  water  circuits  should  be  arranged  so  that  the 
pumps discharge through the evaporator, and should 
be  controlled  as  necessary  to  maintain  essentially 
constant  chiller  water  flows  through  the  unit  at  all 
load conditions.   Figure 29: Water Circuits
 

Flow Detection Devices 
 
Flow switches  or  pressure  differential  switches are  required to  be  fitted  in  the evaporator and  condenser water 
piping. These switches must be wired into the chiller controller in order to shut down the chiller in the event of 
reduced  or  no  flow  to  guard  the  evaporator  from  the  potential  of  freezing.  If  flow  detection  devices  are  not 
installed, warranty on the chiller will be void. An interlock from a pump is not sufficient as a safety device. These 
switches should be adjusted to open and therefore shut down the chiller when the flow decreases to below 70% of 
design flow (l/s) or 50% of the design pressure drop (KPa).  
If the chiller has been designed for Variable Chilled Water flow, or variable condenser water flow, please confirm 
the appropriate cut off point with PowerPax‐Smardt. 
 
 
 
 

33 
SCWIOMM0001.10 
Installation

Relief Valves 
 
As  a  precaution  and  to  meet  safety  code  requirements  each  PowerPax‐Smardt  water  cooled  chiller  comes  with 
pressure relief valves fitted to both the evaporator and condenser vessels to relieve excess refrigerant pressure to 
the atmosphere in case of equipment malfunction. Most codes require that pressure relief valves be vented to the 
outside of a building to prevent oxygen displacement which can lead to asphyxiation. At least two valves on each 
vessel are provided, with a change over manifold for service.  
 
Control Field Wiring 
  Figure 30: PowerPax Controller
The primary chiller control functions are implemented via a Carel ® 
PLC with PowerPax‐Smardt proprietary software, which controls the 
chiller  water  temperature,  interlocks,  and  provides  an  interface  to 
the  building  system.  These  connections  are  made  via  a  24  volt 
terminal strip inside the control cabinet.  
 
Control  wiring  connections  for  the  Carel  controller  only  are 
tabulated in Table 4. 

Consult Figure 31 for wiring diagram (page 38).  

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

34 
SCWIOMM0001.10 
Installation

 
Table 4: Wiring Connections for the Carel Controller

Field Terminal  Reference  Signal  Function 

T3  24VAC Supply     Supply for X2 – X8 

X2  Close to run  Start/Stop 

Chilled Water Flow 
X4  Close to run 
Interlock 
Use voltage free contacts to switch the 24 
VAC at T3 to these inputs **DO NOT USE 
OTHER VOLTAGES**  Condenser Water Flow 
X6  Close to run 
Interlock 

Open to initiate 
Refrigerant Reclaim.  Refrigerant Leak Detector 
X8 
(Not in use unless selected  Interlock 
within the Software)

X10  Run Signal ‐ Reference to X11  Closed to signal run  

Voltage free relay contacts 
X11  Common Reference for X10 & X12  switched by the chiller  Reference for X10 & X12 
controller 

X12  Fault Signal ‐ Reference to X11  Closed to signal fault 

X14  External Set Point Offset  0 – 10 VCD  SP offset from BAS 

X16  Ground    Ground for X14 

External demand limit 
X18   External Demand Limit Signal Signal  0 – 10 VDC 
signal 

X20  Ground    Ground for X18 

Power Wiring  Note: Control wiring must be run separately to power wiring


 
 

35 
SCWIOMM0001.10 
Installation

Disconnects and Power Wiring 
Mains wiring is brought to a single connection point. All power wiring upstream of this point is the responsibility of 
the installing contractor. Ensure that a qualified electrician is used at all times.  
 
 
WARNING! 
To  prevent  injury  or  death,  disconnect  and  isolate  all  electrical  power  sources  before  completing  wiring 
connections  to  the  unit.  Wait  at  least  15  minutes  after  isolating  power  before  removing  compressor  access 
covers.  
 
The mains power supply is brought into the power cabinet from either the top or the bottom of the cabinet and is 
connected  to the  mains  bus  bars.  Correct  Phase  rotation  should  be  observed.  A  dedicated Earth  /  Ground must 
also be connected to the ground bus bar inside this same cabinet.  
 
All  wiring must  be  installed in  accordance  with appropriate local and  national electrical  codes and  will  require a 
circuit breaker or fuses to protect main wiring from the final distribution sub board to the unit. 
 
It is important that the voltage to the PowerPax‐Smardt units is within +/‐10% of the nameplate voltage, and the 
voltage unbalance between phases must not exceed 2%. Any imbalance between phase voltage of more than 2% 
or more than 10% of the current will be considered neglect and will void the PowerPax‐Smardt chiller warranty. If 
this  occurs,  contact  your  local  electricity  supplier  and  ensure  that  the  chiller  is  turned  off  until  this  has  been 
rectified.  
 
To prevent control malfunctions, do not run low voltage wiring (<30V) in conduit with conductors carrying more 
than  30  volts.  It is  recommended  that  the  control wiring  is  run  in  screened  cable  and grounded  as it  enters  the 
control panel. The supply wiring should carry 3 phase + earth + neutral (for control purposes.)  
 
Table 5: Chiller Electrical Data on the following page contains the PowerPax‐Smardt chiller electrical data. Table 6 
outlines the lug sizes.  
 

36 
SCWIOMM0001.10 
Installation

Table 5: Chiller Electrical Data

Model  Voltage  Hz  kW Input  FLA**  LRA*** 


WA027.1BHX.44N  400  50  47  100  110 
WA031.1BHX.44N  400  50  51  100  110 
WA040.1HHX.44N  400  50  68  135  145 
WA044.2BHX.22N  400  50  75  200  210 
WA044.2BHX.33N  400  50  73  200  210 
WA050.2BHX.22N  400  50  87  200  210 
WA050.2BHX.23N  400  50  80  200  210 
WA052.2BHX.22N  400  50  92  200  210 
WA059.2BHX.44F  400  50  108  200  210 
WA062.2BHX.22N  400  50  116  200  210 
WA062.2BHX.33N  400  50  111  200  210 
WA074.3BHX.22N  400  50  129  300  320 
WA084.3BHX.22N  400  50  151  300  320 
WA088.2HHX.44F  400  50  146  270  280 
WA092.3BHX.22N  400  50  155  300  320 
WA095.2HHX.22N   400  50  163  300  315 
WA096.2HHX.22N   400  50  164  300  315 
WA105.4BHX.32N  400  50  164  400  420 
WA120.4BHX.22N   400  50  171  400  420 
WA125.3AHX.22N  400  50  204  405  425 
WA140.3HHX.22N   400  50  231  405  425 
WA150.5BHX.22F  400  50  201  500  520 
WA180.4HHX.22NS  400  50  301  540  560 
WA190.4HHX.22S  400  50  313  540  560 
WA240.5HHX.22S  400  50  406  750  780 
WA260.6HHX.22S  400  50  412  810  830 
 
**FLA: Nominal Full Load Amps 
***LRA: Locked Rotor Amps  
 
 
 
Note: Amp values shown above are the maximum. Refer to PowerPax for specific product values.
Compressor motors are designed to operate satisfactorily over a range of +/- 10% of the design voltage.

Table 6: Lug Sizes

Actives  Neutral  Earth 


Main Lug Size  10mm  10mm  8mm 
 

  Note: A neutral is required for control purposes. The load is essentially a balanced 3 phase load and the
neutral may be run in the minimum allowable cable size relative to the 3 phase mains.

37 
SCWIOMM0001.10 
Installation

Circuit Breakers 
 
The chiller is equipped with a circuit breaker for each compressor. Isolating these circuit breakers does not isolate 
the incoming power supplied to the chiller. To conduct any work involving accessing the circuit breakers or the 
incoming power connections to the chiller, power must be isolated and tagged as per local regulations and safe 
work practices at the Mechanical Services board supplying the chiller.  

Line Reactor / RFI Filters 
 
PowerPax‐Smardt supply each chiller with a line reactor and RFI filter per compressor as standard. These come 
pre‐wired from the factory. They are located in the separate panel on the chiller electrically between the circuit 
breakers and the compressor. The use of the line reactor and RFI filter help improve the power quality going to the 
compressors. 

Wiring Diagram & Schematic 
Figure 31: Wiring Diagram

 
 
 

38 
SCWIOMM0001.10 
Installation

 
 
 
Figure 32: Wiring Schematic
  

Note: To see Figure 32 in more detail please refer to Appendix 2.  

Pre‐Commissioning 
 
PowerPax‐Smardt requires equipment to be commissioned according to a detailed procedure and by a PowerPax‐
Smardt  trained  and  certified  technician.  In  order  to  activate  the  warranty,  the  commissioning  form  must  be 
completed and submitted to PowerPax‐Smardt.  
 
Prior to commissioning, obtain the current pre‐commissioning form (example shown on the following pages) either 
by  contacting  the  PowerPax‐Smardt  service  department  or  by  downloading  the  form  at  www.powerpax.com.au 
and  ensure  that  all  requirements  have  been  met  to  commission  the  Chiller.  Please  allow  7  days  for  the 
coordination of commissioning from the date the pre‐commissioning form is submitted. Forms can be submitted 
to: service.admin@powerpax.com.au or by faxing +61 3 9761 6707.  
 

39 
SCWIOMM0001.10 
Installation

40 
SCWIOMM0001.10 
Installation

 
41 
SCWIOMM0001.10 
Maintenance
 

 
 
This page is intentionally blank. 

42 
SCGWCIOMM0001.10 
Maintenance

 
 
 
 
PowerPax‐Smardt 
Operation Manual 
 
 
 

43 
SCGWCIOMM0001.10 
Maintenance

Operation  

System Checks Before Start Up 
 
Chiller Checks 

Before powering up the PowerPax‐Smardt chiller, check for any signs of damage. If damage is discovered, contact 
PowerPax‐Smardt immediately to report it.  
 
Ensure that all refrigerant valves are open including suction, discharge, motor cooling and liquid line valves.  
 
 
Electrical Checks: 

Note: Below checks must be performed with the power OFF. Removal of covers with power applied
will result in exposure to high voltages. Failure to have power off may result in electrocution.

 
Check all control connections in control cabinet. Check the wiring diagram for control wiring.  
 
Check  all  mains  electrical  connections.  Ensure  that  there  is  a  neutral  and  an  earth  present  and  both  have  been 
connected to the appropriate bus bar in the electrical cabinet as these are essential for correct operation of the 
unit. Tighten terminals if needed.  
 
Remove  the  line  reactor  enclosure  covers  and  check  electrical  connections  for  tightness.  Replace  line  reactor 
enclosure covers. 
 
Compressor Checks: 

 
  Note: The below checks must be performed with the power OFF. Removal of covers with power
applied will result in exposure to high voltages. Failure to have power off may result in electrocution.
 
 
Remove  the  top  cover  from  the  compressor,  remove  the  four  screws,  near  the  motor  bus  bars,  holding  the 
softstart board in place. Turn the softstart over and check the four fuses are securely in place and in good working 
order (See Figure 33 on the following page for softstart fuse locations).  
 

44 
SCGWCIOMM0001.10 
Maintenance
Figure 33: Softstart Fuse Locations

 
 
Check all screws for tightness and check all electrical plugs are fitted correctly. Refit top cover when all checks have 
been completed.  
 
Remove the side covers from the compressors and check the Serial Driver and BMCC boards are firmly seated onto 
the backplane board (see Figure 34), check all electrical plugs are fitted correctly. Refit the compressor side covers 
once the compressor tests have been completed.  

Figure 34: Backplane Board

 
 

45 
SCGWCIOMM0001.10 
Maintenance

Powering up Compressors 
 
Check with the electrical contractor and request that power be turned on to the chiller. Once all the covers have 
been replaced on the compressor, and the electrician  has turned  on the power,  power  can  be  turned  on to the 
compressors.  
 
 
 
WARNING: Risk of Electrocution. Do NOT power up compressors with the compressor top covers
  removed.
 
Compressors should be powered up one at a time. Compressors are turned on by switching the allocated circuit 
breaker.  
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

46 
SCGWCIOMM0001.10 
Maintenance

PowerPax‐Smardt Controller 

Data on the Color Touch Screen Display 
Information: 
 Entering and Leaving Chilled water temperature 
 Entering and Leaving Condenser water temperature 
 Compressor RPM 
 Demand percentage for each compressor 
 Common system low and high pressure 
 System status (various descriptions) 
 Current alarms (announce and manual reset provision) Settings: 
 Chiller water setpoint 
 Time (real time clock) – set to time stamp alarm events 
 PID terms 
 Low load offset settings 
 HP and LP Fault Settings 
 Head pressure control settings  
 
Figure 35: Carel Controller Screen Diagram

47 
SCGWCIOMM0001.10 
Maintenance
Inputs, Outputs, & Interlocks 

Controller BAS Interface 
 
Table 7: Wiring Connections for the Carel Controller 2

Field Terminal  Reference  Signal  Function 

T3  24VAC Supply     Supply for X2 – X8 

X2  Close to run  Start/stop 

Chilled Water Flow 
X4  Close to run 
Interlock 
Use voltage free contacts to switch the 24 
VAC at T3 to these inputs **DO NOT USE 
OTHER VOLTAGES**  Condenser Water Flow 
X6  Close to run 
Interlock 

Open to initiate 
Refrigerant Reclaim.  Refrigerant Leak Detector 
X8 
(Not in use unless selected  Interlock 
within the Software) 

X10  Run Signal ‐ Reference to X11  Closed to signal run  

Voltage free relay contacts 
X11  Common Reference for X10 & X12  switched by the chiller  Reference for X10 & X12 
controller 

X12  Fault Signal ‐ Reference to X11  Closed to signal fault 

X14  External Set Point Offset  0 – 10 VCD  SP offset from BAS 

X16  Ground    Ground for X14 

External demand limit 
X18   External Demand Limit Signal  0 – 10 VDC 
signal 

X20  Ground    Ground for X18 

48 
SCGWCIOMM0001.10 
Maintenance
Figure 36: Wiring Diagram 2

 
Note:  Because  of  PowerPax‐Smardt’s  continual  development  policy  and  the  variances  in  chiller  models  wiring  schematics  are  likely  to  change.  Please  contact 
PowerPax‐Smardt for job‐specific wiring schematics.  
 
The PowerPax‐Smardt controller has the following inputs: 
 Remote on/off switch (Cooling call) 
 Evaporator water flow switch 
 Condenser water flow switch 
 Refrigerant Leak Detector Interlock (activated by software) 
 
  All of the above inputs will enable/disable the controller. Refer to the electrical schematics for correct
  input configuration. Digital inputs that are not used should be bridged.
 
 Analog chiller water set‐point offset (0 – 10 vdc at B6) 
 Analog demand from BAS (0 – 10 vdc at B6) – external demand should must be selected in lieu of input PI 
(configurable within software but not recommended) 
 Digital input to hold compressor N and higher offline (N is selectable) 
 Analog (0 ~ 10 vdc) input to set maximum demand from the BAS 

49 
SCGWCIOMM0001.10 
Maintenance
 
The PowerPax‐Smardt controller has the following inbuilt outputs: 
 Chilled water pump contacts (close if ON and cooling cool _ID‐1&ID‐4). Output contacts are (J22‐NO 17) 
 Condenser water pump contacts (closed with compressor run) 
 Alarm changeover contacts announce alarm state not reset or loss of control power 
 Analog (0~10 VDC) = 0 ~100% demand (at Y5) 
 Analog (0 ~ 10 VDC) for head pressure control by VSD (at Y6) 
 

Head Pressure Control Option 
 
The  PowerPax‐Smardt  Carel  Controller  is  equipped  with  built  in  Head  Pressure  control,  available  via  High  Level 
Interface, or via an analogue output (0 ‐ 10 VDC) connected to Y5 or Y6 (configured during commissioning). 
The analogue output is only available providing there are four or less compressors on the chiller; however the high 
level output (BAS Communications) is always available. 
 
This control is not designed to optimise the plant efficiency, and should not be utilised as such, as the chiller is not 
monitoring sufficient data points such as the relative humidity to make such decisions. 
The  primary  purpose  of  this  output  is  to  optimise  the  condenser  water  temperatures  to  be  suitable  for  the 
demands  of  the  chiller,  such  as  in  startup,  and  low  load  conditions.    This  is  achieved  through  the  proportional 
control of a valve or similar mechanism to affecting the head pressure. 
 
The following items could be controlled by this output. 
Variable Speed Cooling Tower Fan 
Cooling Tower Bypass Valve 
Variable Speed Condenser Water Pump 
 
This  should  be  configured  during  chiller  commissioning  by  a  PowerPax‐Smardt  technician,  or  by  a  PowerPax‐
Smardt certified Service Provider..  

Summary of Status Contacts 
 
The PowerPax‐Smardt controller provides a set of change over contacts which sends a signal to the external BAS 
indicating that either a fault  condition is in existence (X12‐X11)  or that the chiller is running (X10‐X11), however 
only one condition can be indicated at any one time. The X12 contact is closed to indicate the power is off (there is 
no control power to the Carel controller) or that there is a fault requiring a manual reset. These contacts close on 
shunt  trip,  high  pressure  or  low  pressure  trip  (both  of  which  require  the  fault  to  be  manually  reset).    The  Fault 
contact will also close if the auto‐reset alarm count has been reached, or if a compressor fault has not auto‐reset 
within the designated time, which therefore could result in the available compressors on the chiller continuing to 
run despite the run status contact opening.  E.g. On a 3 compressor chiller, if one compressor cannot be reset, the 
fault  signal  will  close,  opening  the  run  status,  however  the  other  2  compressors  will  continue  to  run  until  the 
cooling call is removed from the chiller.  
 

50 
SCGWCIOMM0001.10 
Maintenance
High Level Options 

ModBUS** 
A  ModBUS  interface  is  available  with  the  controller,  acting  as  a  slave.  This  interface  is  a  Modicon  standard  RTU 
protocol and has access to all basic controller information and settings. 
 

BACnet** 
BACnet over IP is available. This interface is BACnet Test Laboratory certified for BACnet protocol communications.  

Remote Monitoring** 
A  remote  access  capability  is  available  for  the  PowerPax‐Smardt  chillers’  which  enables  users  to  access  a  chiller 
operation summary screen utilizing a standard PC web browser.  
 
** All of the above high level options do not come as standard on the chiller but are available for purchase at the 
time the chiller is ordered. Some conditions apply to availability. Contact PowerPax‐Smardt for high level interface 
options and availability. 
 

51 
SCGWCIOMM0001.10 
Maintenance

Operating the Controller 

Power Button 
 
Press the Power button to display the systems ON/OFF screen. Touch the icon on the screen or press the ON/OFF 
key again to locally switch the chiller either on or off.  
 

Password Access 
 
The controller has different levels of access that are password protected: 
 
Open (user) Level Access 
This level of access is not password protected. It provides basic information on the chillers operation and enables 
the user to access basic control settings. 
Level 1 – Service Access 
This level of access required a level 1 password. This password allows access to more detailed chiller settings.  
Level 2 – Advanced Service Access 
The level of access requires a level 2 password. It allows basic unit settings such as the number of compressors and 
type of unit to be changed. It is only applicable to people who have received PowerPax‐Smardt Certified Training. 

Navigating the Controller 
 
The touch screen interface uses a combination of touch features and the keys at the right hand side of the screen 
to move around the controller and enter values.  
 
Each touch screen has navigation buttons in the top corners. The following are used to move between screens: 
 
NEXT – Go to the next screen 
BACK – Return to the front screen 
MENU – Go to menu options 
OEM – Same as NEXT if OEM access is granted 
HELP – Instructions on use 

Data Entry 
 
To navigate to the desired value, touch on the screen location or use the ENTER key. The values are changed on 
the controller by using the UP or DOWN arrows (keys) to the right hand side of the screen. To make a selection 
press the ENTER key to confirm a selection or exit the screen.   
 

Alarm Button 
 
An alarm condition brings up the red LED on the left hand side of the display and sounds the alarm that something 
is in fault. The alarm key accesses the alarm screens to display the detail of the alarms and allows a manual reset. It 
also switches the alarm sound off but the LED remains illuminated until the alarm reset is complete.  
 

52 
SCGWCIOMM0001.10 
Maintenance

Carel Controller User Level Screens 

Front User Screen


 
Figure 37: Front User Screen
 

 
 
Figure  37  shows  the  front  user  screen  of  the  Carel  Controller.  This  main  screen  can  be  viewed  at  any  time  by 
pressing the ESC key. This is an overview of the systems main parameters, such as the Setpoint, the Return Chilled 
Water Temperature, Leaving Chilled Water Temperature, the Return Condenser Water Temperature, and Leaving 
Condenser Water Temperature in addition to the System Demand and the Suction and Discharge Pressures.  
 
The  top  line  (displayed  as  “System  on  Auto”)  provides  further  information.  It  may  display  one  of  the  following 
messages, however only one message is possible at any time: 
 
 “System On Auto” – The chiller is in its normal operating state. (“‐ALARM” if there is an alarm present) 
 “Remote OFF (or Internal time clock)” ‐  No input on X2 detected or the time clock has the chiller OFF 
 “Refrigerant  Leak”  –  This  is  a  response  to  an  optional  external  signal  which  Initiates  a  refrigerant  leak 
response if the chiller is configured for pump‐out. 
 “No Evaporator Flow” – the interlock from the evaporator flow switch is open, or the flow rate is too high. 
 “No Condenser Flow” – the interlock from the condenser flow switch is open, or the flow rate is too high. 
 “Keypad  OFF  (or  Hi  Water  Temp  Al)”  –  the  chiller  has  been  turned  off  using  this  screen,  (or  the  water 
temperatures are above 50C) 
 “OFF Cycle Delay”  ‐ Minimum off timer is running (default of 180seconds) 
 “Manual Demand” ‐  Service intervention ‐ manual control 
 “Auto Reset Delay” – the controller is counting down to automatically reset the compressor fault. 
 “Below Restart Temp or Ambient T lockout” ‐  Return chilled water or ambient temperature too low 
 “Stage Delay” ‐ Inter‐stage timer delaying the next compressor start. 
 “HP Fault” – Condenser Pressure too high (system 1 if twin system) 
 “LP Fault” – Evaporator Pressure too low (system 1 if twin system) 
 “Freeze Alarm” ‐  Leaving Chilled Water Temperature was below the anti‐freeze set point 
 “LCWT Sensor Fault” ‐  Controller has detected a bad reading in the Leaving Chilled Water Temp Sensor 
 “Assisting Start” ‐  A compressor is about to start after the system has done a Pressure Ratio adjustment 
 “Bad MB Compressors” ‐ If using the optional ModBus control of compressors, and the data is interrupted 
between the compressors and controller this will cause a resettable fault. 
 “Wait Compressors” ‐  Waiting at start for compressors to be ready (normally seen after power off) 

53 
SCGWCIOMM0001.10 
Maintenance
Main Menu
 
 
Figure 38: Main Menu Screen
 
Users have access to screens/sub menus under 
the  heading  shown  on  the  screen  in  white. 
Figure  38  below  shows  the  screens  that  users 
have access to under User Level Settings.  
 
For  details  on  the  access  screens  see  the 
following.  
 

Operational Data
 
This screen provides the current set point information being utilized by the controller (see Figure 39).  
  Figure 39: Operational Summary Screen
 Ent ChWT – this is the current entering 
Chilled Water Temp. 
 Start Temp – the temperature of 
leaving chilled water needed to restart 
system. 
 Low Load Offset – this is the effect on 
the setpoint during low load conditions. 
 External Offset – this shows any offset 
to the setpoint from the BAS signal. 
 Actual SP – the user defined setpoint. 
 Act controller value – the setpoint that 
includes the current external and low 
load offsets. 
 PID Out % ‐ the current demand being 
generated based on the setpoint and 
current conditions. 
 Demand % ‐ the actual demand, based 
on all limits, timers, staging etc. 
 Limited by ramp to – reflects the maximum system demand during start‐up due to the ramp settings. 
 Reset due to HP – the demand is reduced by this amount if discharge/condenser pressure exceeds pre‐
determined values. 
 Reset due to Power – the reduction in demand limit due to excessively high current draw. 
 Min. Off time – time remaining to restart compressors after chiller has shut down. 
 Stage delay – time remaining in stage delay before next compressor loads. 
 
 

54 
SCGWCIOMM0001.10 
Maintenance
Figure 40 and Figure 41 display information for each individual compressors  on the chiller such as hours, starts, 
and any delays or timers. This screen is repeated for each compressor present.  
 
Figure 40: Compressor 1 Data Screen
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Figure 41: Compressor 2 Data Screen
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

55 
SCGWCIOMM0001.10 
Maintenance
  Figure 42: Data System Electrical Screen
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
The Data System Electrical Screen, shown above in Figure 42, provides the information being read and calculated 
by the compressors only. As such it should be used as a guide only, as it is a calculated value not a measured value.  

User Settings
 
The user settings menu screen, shown below in Figure 43 allows the user to start or stop the chiller and adjust the 
current setpoint.  
 
 
Figure 43: User Settings Menu
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

56 
SCGWCIOMM0001.10 
Maintenance
Compressor MB Data
 
The following screens are for information purposes only. They reflect the high level data that is being obtained 
from the individual compressors.  
 
 
Figure 44: Compressor Alarms and Faults Screen
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
The compressor alarms and faults screen (Figure 44) shows any alarms or fault codes recorded by the compressors.  
 
  Figure 45: MB Data Summary Screen

 
 
 

Figure  45  shows  data  from  the  compressors  such  as  pressures,  operational  data,  and  compressor  operating 
speeds.  

57 
SCGWCIOMM0001.10 
Maintenance
 
Figure 46: Compressor Status Codes Screen

 
 
The Compressor Status Codes Screen in Figure 46 indicates the compressor status. Note: “Calibration Mode” as 
seen above, indicates no compressor communications. 
 

Clock
 
The Clock Menu Screen shown in Figure 47 displays the current time and date at the top of the screen. They can be 
adjusted at this screen. For installations without the building system capability to run the chiller at preset times on 
selected days, a basic start/stop 7 day time clock is available for this function.  
 
 
 
Figure 47: Clock Menu

58 
SCGWCIOMM0001.10 
Maintenance
History

Figure 48: Evaporator Temperatures Screen

 
 
 
 
 
Figure 49: Condenser Temperature History Screen

59 
SCGWCIOMM0001.10 
Maintenance
Figure 50: Graphs Help Screen

The graphs above may need to be rescaled to the appropriate range. If so, press   which will change the buttons 
displayed along the bottom of the screen. Select the appropriate button to scale either the temperature or time 
axis, then touch the screen on the graph area. Once you have adjusted the scale, press   to return to the PAN 
menu, which will then allow you, using the buttons, to adjust the graph to the desired location.  

Information
 
This screen displays the Basic system setup and the software version. To access a higher user level, enter the 
password at this screen.  
 
Figure 51: Information Menu

 
 
 
 

60 
SCGWCIOMM0001.10 
Maintenance

 
 
This page is intentionally blank. 

61 
SCGWCIOMM0001.10 
Maintenance

PowerPax‐Smardt 
Maintenance Manual 

62 
SCGWCIOMM0001.10 
Maintenance

Maintenance
 
The following PowerPax‐Smardt maintenance schedule is outlined on the following pages in table 8. It should be 
noted however, that PowerPax‐Smardt require quarterly maintenances only, however this table provides the 
checks based on a monthly schedule should that be your requirement.  Please note that maintenance should only 
be carried out by a PowerPax‐Smardt certified technician. Warranty is not an excuse for not maintaining the 
system. Chiller warranty will only be valid if the service schedule has been adhered to. Once a scheduled 
maintenance has been completed PowerPax‐Smardt requires the PowerPax‐Smardt service form be returned to 
the service department. The PowerPax‐Smardt maintenance form can be found on pages 55 – 60 of the 
Maintenance Manual. For the latest maintenance form please contact the PowerPax‐Smardt service department.  

Note: Maintenance should only be carried out by a PowerPax certified technician. Failure to comply will
void chiller warranty.

63 
SCGWCIOMM0001.10 
Maintenance

Table 8: PowerPax Maintenance Schedule

Item  Task Frequency


  M  Q  A
Check main power supply voltages       

Check electrical terminals are tight       
Electrical Checks 
Check there are no hot spots / discoloration on power cables       

Check Amperages are as per design       

Check communication cables are secure       

Check pressure and temperature sensor connections are secure       

Electronic 
Inspections 
Check PCB’s (printed circuit boards) are free of dust       

Check there are no signs of damage / hot spots on Printed Circuit 
Boards 
     

Check EXV winding resistance (do NOT disturb unless repair 
required)  
     

Check IGV Assembly operating correctly       

Check compressor fault log       

Compressor 
Checks 
Check calibration of pressure and temperature sensors       

Check Backplane voltage test points       

Check all modules and connections are secure       

Check all mounting bolts are secure       

Check for refrigerant leaks       
Compressor 
Refrigeration  Check for mechanical damage       
Circuit Inspections 
Check operating temperatures and pressures       

Check that the compressor motor cooling line sight glass is full 
during operation 
     

64 
SCGWCIOMM0001.10 
Maintenance

Check for insulation damage       

Check chilled water sensors are secure and installed with adequate 
heat transfer medium 
     

Check water flows and pressure drops are as per design conditions       
Chilled Water 
Circuit Inspection 
Check flow switch operation       

Check for leaks       

Check water strainers       
Check chilled water sensors are secure and installed with adequate 
heat transfer medium 
     

Check water flows and pressure drops are as per design conditions       
Condenser Water 
Circuit Inspection 
Check flow switch operation       

Check for leaks       

Check water strainers       

Water Cooled Maintenance Form 
The Water Cooled Maintenance form found in this manual is for demonstration purposes only and is an example of 
the form issued in Excel format. When completing the scheduled maintenance on a PowerPax‐Smardt chiller 
please contact the PowerPax‐Smardt service department for the latest copy of the maintenance form.  

65 
SCGWCIOMM0001.10 
Maintenance

66 
SCGWCIOMM0001.10 
Maintenance

67 
SCGWCIOMM0001.10 
Maintenance

68 
SCGWCIOMM0001.10 
Maintenance

This page is intentionally blank. 

69 
SCGWCIOMM0001.10 
Appendix

Appendix 
 
 
 
 
 
 
 
 

70 
SCGWCIOMM0001.10 
Appendix

Appendix 1 – Recommended Spare Parts List 

TT300  TT400  Recommendation 


Item  Part Description  Part No.  No.  
R134a  R134a  for Stocking 

Compressor Components   

KIT – MODULE – SOFT START 
1.1  100020‐3      Recommended  1 
(400V) 

1.2  KIT – MODULE – BACKPLANE  100021‐1      Beneficial  1 

1.3  KIT – MODULE – BEARING PWM  100022      Recommended  1 

KIT‐SENSOR‐ASSEMBLY‐
1.4  100034      Beneficial  1 
TEMPERATURE‐MOTOR ROTOR 

KIT ‐SENSOR‐
1.5  PRESSURE/TEMPERATURE ‐ 100036      Recommended  1 
SUCTION 

KIT‐SENSOR‐
1.6  PRESSURE/TEMPERATURE‐ 100037      Recommended   1 
DISCHARGE & ECR 

KIT ‐DC/DC CONVERTER 
1.7  100040‐5      Recommended  1 
ASSEMBLY 

KIT‐IGBT 370032, MANIFOLD 
1.8  100043‐3      Beneficial – TT300  1 
COOLING 

KIT ‐IGBT 340032 MANIFOLD 
1.9  100043‐4      Beneficial – TT400  1 
COOLING ‐ TT400 

1.10  KIT‐DIODE RECTIFIERS TT300  100047‐1      Not Required  0 

1.11  KIT‐DIODE RECTIFIERS TT400  100047‐2      Not Required  0 

71 
SCGWCIOMM0001.10 
Appendix

KIT ‐IGV HOUSING ASSEMBLY ‐
1.12  TT‐300 EXTENDED RANGE  100050‐2      Beneficial – TT300  1 
(R134a) 

KIT‐IGV ‐HOUSING ASSEMBLY 
1.13  100050‐7      Beneficial – TT400  1 
AND O' RING‐TT‐400C 

1.14  KIT – MODULE – SERIAL DRIVER  100292      Beneficial  1 

KIT –COOLING VALVE  Beneficial – Model 
1.15  100150‐2      1 
ASSEMBLY – TT300  Specific 

KIT –COOLING VALVE  Beneficial – Model 
1.16  100150‐4      1 
ASSEMBLY – TT400C  Specific 

KIT‐FUSES (FIE) ASIC SOFT 
1.17  100317‐1      Recommended  1 
START TT300,TT400 

KIT ‐ FUSE CLASS T‐FAST 
1.18  100344      Recommended  1 
ACTING A6T 175 TT300,TT400 
KIT –BEARING MOTOR 
Beneficial – Model 
1.19  COMPRESSOR CONTROL  100296      1 
Specific 
(BMCC) 

Chiller Components 

2.1  Pressure Sensor  SPKT0031CO      Recommended  2 

2.2  Temperature Sensor  NTCO30WPOO      Recommended  2 

2.3  PCO3 Controller  PCO3000AL0      Beneficial  1 

2.4  EXV Controller  EXV‐Control      Recommended  1 

Other Components 

3.1  EXV Head  EXV–Head      Recommended  1 

72 
SCGWCIOMM0001.10 
Appendix

Appendix 2 – Wiring Schematic 

73 
SCGWCIOMM0001.10 
Appendix

This page is intentionally blank.

74 
SCGWCIOMM0001.10 
Appendix

This page is intentionally blank.


 

75 
SCGWCIOMM0001.10 
 

144 Colchester Road


PO Box 2021
Bayswater North, VIC
Australia, 3775
www.powerpax.com.au
Phone: +61 3 9761 7905 Fax: +61 3 9761 6707

76 
SCGWCIOMM0001.10 

You might also like