[Reference Design 11]

Equipment List - Facility Cooling

Equipment Architecture Product Description Quantity


Type
Designation Location
Uniflair packaged air
Standard air cooled cooled chiller 245kW
ROOF-CH-01A Roof terrace 1
chiller (selected according to
location)
Uniflair packaged air
cooled chiller 245kW
ROOF-CH-02A Free cooling chiller Roof terrace with free cooling 1
(selected according to
location)
ROOF-PCHWP- Chilled water pump 45 m3/hr constant
Roof terrace 1
01A (fitted to chiller) volume pump - DN100
ROOF-PCHWP- Chilled water pump 45 m3/hr constant
Roof terrace 1
02A (fitted to chiller) volume pump - DN100
Isolating valve 2-way butterfly valve -
ROOF-IV-01 Roof terrace 8
primary loop DN100
Balancing valve Static balancing valve -
ROOF-BL-01 Roof terrace 2
primary loop DN100
DN 15 differential
Differential pressure gauge,
ROOF-DPG-01 pressure gauge Roof terrace switches and 2
primary loop transmitters (max 10
bar)
Thermometer For DN100 pipe (scale
ROOF-TH-01 Roof terrace 4
primary loop 0C to 50C)
Vibration eliminator DN100 pipe vibration
ROOF-VE-01 Roof terrace 4
for chillers isolator
Flow meter Bi-directional insertion
ME-FB-01 primary/secondary Mechanical room turbine flow meter with 2
decoupler analog output
1m3 vertical internal
ME-ST-01 Thermal storage Mechanical room 2
buffer tank
Centrifugal pump on
© 2013 Schneider Electric. All rights reserved.
ME-SCHWP- Chilled water pump
Mechanical room VFD 45m3/hr, 3kW, 2
01A (VFD) on UPS
base-mounted pump
Centrifugal pump on
ME-SCHWP- Chilled water pump
Mechanical room VFD 45m3/hr, 3kW, 2
02A (VFD) on UPS
base-mounted pump
Check valve for
ME-CV-01 Mechanical room DN100 check valve 4
chilled water pump
Strainer for pump SS "Y" strainer DN100
ME-STR-01 Mechanical room 4
loop with flanges

Schneider Electric www.schneider-electric.com


Document Number RD11_3.3_Facility_Cooling_EquipmentList_EN_R0 Revision 0 / June 2013
[Reference Design 11]

ME-PG-01 DN15 pressure gauge,


Pumps pressure switches and
Mechanical room 8
gauge transmiters (max 10
bar)
DN15 differential
Differential pressure gauge,
ME-DPG-01 pressure gauge Mechanical room switches and 2
secondary loop transmiters (max 10
bar)
Thermometer For DN100 pipe (scale
ME-TH-01 Mechanical room 8
secondary loop 0C to 50C)
Single insertion turbine
Chilled water
ME-F-01 Mechanical room flow meter isolated 2
flowmeter
analog output
25 liters closed
ME-ET-01 Expansion tank Mechanical room 2
expansion tank
Ethylene glycol (%
ME-GL-01 Glycol feeder Mechanical room according to external 2
conditions)
Dirt and air DN100 dirt and air
ME-DAS-01 Mechanical room 2
separator separator, flange type
Isolating valve 2-way butterfly valve -
ME-IV-01 Mechanical room 26
secondary loop DN100
Isolating valve 2-way butterfly valve -
ME-IV-02 Mechanical room 4
secondary loop DN65
2-way valve
2-way motorized
ME-MW-01 secondary loop Mechanical room 4
butterfly valve
bypass
300 cfm combined
supply and exhaust
WS-AHU-01A Air handling unit Roof terrace 2
AHU cooling and
heating coils
2-way butterfly valve -
WS-IV-01 Isolating valve IT Space 4
DN100
Isolating valve for
WS-IV-02 IT Space SS ball valve - DN25 15
TDCV4000G
Balancing valve for Static balancing valve -
WS-BL-01 IT Space 3
TDCV4000G DN25 © 2013 Schneider Electric. All rights reserved.

Strainer for SS "Y" strainer DN25


WS-STR-01 IT Space 6
TDCV4000G with thread connection
Computer room air TDCV700A (chilled
UPS-CRAH-
handling unit UPS/Battery room water inRoom cooling 4
01/02/A
(chilled water type) unit)
2-way motorized 2-way NPT ball valve,
UPS-MCV-01 UPS room 4
control valve SS, DN40, CCV

UPS-IV-01 Isolating valve UPS/Battery room SS ball valve DN32 20

Schneider Electric www.schneider-electric.com


Document Number RD11_3.3_Facility_Cooling_EquipmentList_EN_R0 Revision 0 / June 2013
[Reference Design 11]

Static balancing valve -


UPS-BL-01 Balancing valve UPS/Battery room 4
DN32
"Y" strainer with 20
UPS-STR-01 Strainer UPS/Battery room mesh screen - DN32 8
with thread connection
For DN32 pipe (scale
UPS-TH-01 Thermometer UPS/Battery room 8
0C to 50C)
DN15 pressure gauge,
switches and
UPS-PG-01 Pressure gauge UPS/Battery room 8
transmiters (max 10
bar)
Fitted to AHU, 3kg/hr,
pressure = 0,3 to 3 bar,
WS-H-01A/B Humidifier Roof terrace 2
room condition (24C,
HR 50%)
Indoor automatic
Humidifier control humidifier control -
WS-HC-01 IT Space 2
panel control range HR 40%
to 55%
Water treatment Softener type: PERMO
ME-WTR-01 Mechanical room 1
system 5016
DN20 backflow
ME-BP-01 Backflow preventer Mechanical room 1
preventer

ME-IV-03 Isolating valve Mechanical room SS ball valve - DN20 7

ME-WM-01 Water meter Mechanical room DN20 water meter 1

Check valve for


ME-CV-02 Mechanical room DN20 check valve 1
water pipe

© 2013 Schneider Electric. All rights reserved.

Schneider Electric www.schneider-electric.com


Document Number RD11_3.3_Facility_Cooling_EquipmentList_EN_R0 Revision 0 / June 2013