You are on page 1of 4

M

embrane roof systems installed

Construction
a
on steel roof decks traditionally
result in a uniform transfer of
wind (uplift) loads from the roof

Issues membrane to the steel roof deck and underly-


ing supporting structure (e.g., steel joists). For
example, in a built-up membrane roof system
Deck
N

– which has been used commonly in the U.S.


discussion of construction Fastener Lines
roofing industry for more than 125 years – the
issues and techniques built-up membrane is continuously adhered to
rigid board insulation. The rigid board insulation,
which is used to span the steel deck’s flutes, is Figure 1. Typical membrane layout by roofers.
mechanically attached to the steel roof deck in a
closely-spaced pattern (e.g., 1 fastener per every 3
square feet), resulting in a near uniform uplift load

+
path. Polymer-modified bitumen roof systems ®

+
E
and adhered single-ply membrane roof systems

+ +

+ +
are installed in similar configurations and result

R
in a similar uniform uplift load path.
+ + + + + + + + + + + +
In the 1960s, single-ply membrane roof sys-

U
tems were first introduced hinto the U.S. roofing

+ +

+ +
t
yrig

T
Cop
market. By the late 1970s,
the seam-fastened, mechani-

C
+ + + + + + + + + + + +
Are Your Roof Members cally attached method of

+ +

+ +
e
U
installation was first intro-
Overstressed? duced. With this installation
n
i
R
method, the single-ply mem-
z
Figure 2. Typical fastener layout at corner zones.

T
brane sheet is mechanically
By James M. Fisher, Ph.D., a
attached along its outer edges into the roof
g
S
P.E., Dist. M.ASCE and deck, which results in a larger tributary uplift
Thomas Sputo, Ph.D., P.E., a
load per fastener and placement of fasteners in
S.E., F.ASCE
m
linear, non-uniform loading configurations of the
roof deck and underlying supporting structure.
When first introduced, membrane sheet widths in
seam-fastened single-ply membrane roof systems
typically were five feet wide, resulting in rows of
mechanical fasteners spaced at five feet on-center. Figure 3. Line attached membrane under uplift.
Since the early 2000s, single-ply membrane sheet Courtesy of the Steel Deck Institute.
widths have become wider, with 10-foot-wide
James M. Fisher is Vice President sheets now commonplace – resulting in rows of severely overstress the steel deck and may also
Emeritus, Computerized Structural mechanical fasteners spaced at 10 feet on-center. cause the steel joist below the deck to be over-
Design, Milwaukee, WI, and Currently, single-ply membrane roof systems stressed under uplift loading. The behavior of such
Consulting Engineer to the Steel have clearly overtaken conventional built-up and fastening systems, when the roof system is sub-
Joist Institute. He may be reached polymer-modified bitumen membrane systems in jected to uplift loadings, is shown in Figure 3. The
at jfisher.florida@gmail.com. market share. The seam-fastened, mechanically- current trend in securement is for the membrane
attached method of installation also has overtaken installer to mechanically fasten the membrane to
Thomas Sputo is President of
traditionally adhered methods of application. The the deck only along the edge of the sheet rolls to
Sputo and Lammert Engineering,
National Roofing Contractors Association (NRCA) speed up the roof installation, thereby lowering
LLC, Gainesville, FL, and
annual market survey shows seam-fastened, mechan- installation costs. Unfortunately, the Structural
Technical Director of the Steel
ically attached single-ply membrane roof systems Engineer of Record, and the steel deck and joist
Deck Institute. He may be reached
make up the majority of all membrane roof systems suppliers, are usually unaware of the concentrated
at tsputo50@gmail.com.
currently installed. load pattern of the roof membrane attachment.
With the present emphasis on wind resistance In fact, the architect of record may not be aware
in design, a closer look at how seam-fastened of the ramifications of such attachments. The
mechanically attached single-ply membrane roof Architectural roofing specifications may simply
systems interact with steel roof deck and joist state that the roof membrane shall be installed
construction is in order. per manufacturers recommendations. The roofing
A common method of single-ply membrane installers foreman is the one who generally decides
sheet layout is shown in Figure 1. A common on the exact layout of the membrane sheets on the
placement of mechanical fasteners is shown roof. That decision is made based on what layout
in Figure 2. These concentrated line loads can can be installed in the fastest and least expensive

30 March 2017
manner. Roofing suppliers and FM Global Assume that, at some location in the field of the
North-South Perimeters (Attachments
recommend the fastener line loads not be roof, the fastener line will be located at the center
Parallel to Deck Span)
installed parallel to the deck ribs, but rather of a deck end span. From a structural analysis
perpendicular to the deck flutes. Placing the of a three span deck, the maximum moment Note: Fasteners running parallel to the deck
lines of attachment parallel to the deck ribs occurs in the end span (positive moment); Mr flutes is a severe condition and not recom-
will only load a one-foot width of the steel = 4.85 kip-inches. For a uniformly loaded deck, mended. If used, the following loading
deck. This recommendation helps but may the maximum moment occurs over the two sup- conditions occur.
not eliminate potential severe overstress of ports (negative moment); Mr = 1.24 kip-inches. Line Load: Parallel to Deck Flutes
the deck. The uplift pressure is 55.8 psf.
East-West Perimeters (Attachments
Currently, the Steel Deck Institute’s (SDI) The membrane area for the line load = (5
Perpendicular to Deck Span)
position paper, Attachment of Roofing feet) = 5 square foot.
Membranes to Steel Deck (sdi.org), states: The first line load is 5 feet from the building Line Load on 1.0 foot of deck width = (5.0
“SDI does not recommend the use of roof- edge and the second is 10 feet from the edge. feet)(55.8 psf )- 4.5 plf = 275 pounds per foot
ing membranes attached to the steel deck The third is 20 feet from the edge. Positive moment = Mw = (0.08)wL2 = (0.08)
using line patterns with large spacing unless a First Line Load: The membrane area for the (0.275 kips per foot)(6.0 foot)2 = 0.79 kip-feet
structural engineer has reviewed the adequacy first line load = (5 foot) = 5.0 square feet. = 9.50 kip-inches.
®

E
of the steel deck and the structural supports Second Line Load: The membrane area for Negative moment: Mw = (0.10)wL2 = (0.10)
to resist the wind uplift loads transmitted the second line load = (2.5 feet + 5 feet)(1.0 (.275 kips per foot)(6.0 foot)2 = 0.99 kip-feet

R
along the lines of attachment. Those lines of feet) = 7.5 square feet. = 11.9 kip-inches.
attachment shall only be perpendicular to the Third Line Load: The membrane area for the For a uniformly loaded deck, the maximum

U
flutes of the deck.” third line load = (5rigfeet
ht + 5 feet)(1.0 feet) = 10.0 negative moment is 2.22 kip-inches.

T
y
square feet. TheCop uplift pressure is 55.8 psf for
Corner Condition Zone
the first 10 feet from the building edge and 33.3

C
Deck Strength Example psf for the remainder of the three span deck. The uplift pressure is 84.0 psf for the first 10

e
U
To illustrate the potential effect of the The maximum moment is 4.32 kip-in feet from the building edge, and 55.8 for the
attachment pattern, determine the deck and occurs in the second span as a positive
i n remainder of the three span deck.

R
strength for the following conditions illus- moment. For a uniformly loaded deck, the Line load on 1.0 foot of deck width = [(5
z
T
trated by Figures 1 and 2. Use Load and maximum moment is 2.31 kip-inches (nega- feet)(84 psf )]/2-4.5 plf = 206 pounds per
Resistance Factor Design (LRFD) Load a
tive) and is located over the first support from
g
foot for first 10 feet. The division by 2 is to

S
Combinations and American Society of the building edge. account for load distribution between fastener
Civil Engineers’ ASCE 7-1. Thus, the a
controlling ASCE Load Combination
is 0.9D + 1.0W. (Wind calculations are m
not shown for brevity.)
Given: A roof system located in Kansas LEED
City, MO. Category II Building. Exposure
C per ASCE 26.7.3. The building is an
CERTIFIED
Enclosed Building with a flat roof (¼-inch
per foot). The building is 100 feet by 100
feet in plan and has an eave height equal
GOLD

ADVERTISEMENT–For Advertiser Information, visit www.STRUCTUREmag.org


to 30 feet.
The metal deck is 1.5-inch 22-gage, wide
rib (WR) deck on joists 6 feet on-center.
Fy = 33 ksi. The roof dead load on the
metal deck = 5 psf. The membrane is 10 Seattle Pasadena
feet wide in the interior zones and 5 feet Tacoma Irvine
Lacey San Diego
wide in the perimeter zones. Portland Boise
From the SDI Roof Deck Design Manual Eugene St. Louis
(RDDM), φMn (negative moment capac- Sacramento Chicago
ity) = 5.358 kip-inches, and φMp (positive San Francisco Louisville
Los Angeles New York
moment capacity) = 5.088 kip-inches. Long Beach

Interior Zone (Field of Roof)


Uplift line loads are determined
using Component and Cladding ASCE KPFF is an
Requirements (ASCE Chapter 30). Equal Opportunity
Employer.
The fasteners are placed perpendicular
to the deck span and are spaced 1-foot www.kpff.com

on-center. Therefore, the membrane area The Ardea


is 10 square feet (1-foot x 10-foot-wide Portland, OR
sheet). The uplift pressure is 33.3 psf.

STRUCTURE magazine 31 March 2017


Summary table of required deck strength to actual deck strength.
Zone Moment Mr /φMp Moment Mr /φMp Clarification
Line Load, Mr or Uniform Load, Mr or
This article refers to FM Approval
(kip-inches) Mr /φMn (kip-inches) Mr /φMn
Standard 4470 regarding steel decks and
Interior 4.851 0.95 1.242 0.23 a Factor of Safety of 2. In fact, the FM
East-West Perimeter 4.32 1
0.85 2.31 2
0.43 Global requirements for steel deck is
covered in FM Approval Standard 4451,
North-South Perimeter 11.92 2.22 2.222 0.41
Approval Standard for Profiled Steel Panels
Corner 11.55 2
2.16 3.48 2
0.65 for Use as Decking in Class 1 Insulated Roof
1
Positive moment, Negative moment.
2 Construction and FM Global Property Loss
φMp = 5.088 kip-inches, φMn = 5.358 kip-inches Prevention Data Sheet 1-29. FM Approval
Standard 4451, Section 4.3.1.6 states,
lines. Then (5 feet)(55.8 psf )-4.5 plf = 275 installed every year is re-roofing of existing “Stresses induced to steel roof decking
pounds per foot beyond. buildings. Buildings that are 20 to 30 years shall be determined by rational analysis
Based on a continuous beam analysis, the maxi- old are unlikely to have higher yield strength using Allowable® Strength Design (ASD)
mum negative moment equals 11.55 kip-inches steel deck. Therefore, caution is required when principles and shall not exceed the allow-

E
and occurs over the second interior support from evaluating roof deck when re-roofing. able stresses per the latest edition of the

R
the corner. The maximum positive moment North American Specification for the Design
occurs within the third span and equals 9.64 of Cold-Formed Steel Structural Members,
Higher Wind Regions

U
kip-inches. For a uniform load, the maximum AISI S100-2007.” FM Global Property
t h
negative moment equals 3.48 kip-inches and The analysis described
yrig above was performed Loss Prevention Data Sheet 1-29, Section

T
Cop
occurs over the first interior support. The maxi- on a building located within the basic wind 2.2.3.2 includes tables that are based on

C
mum positive moment occurs in the first span velocity zone of 115 mph per ASCE 7-10. ASD principles and the allowable stresses
and equals 2.73 kip-inches. See Table for a sum- Particular attention must be paid to the design per AISI S100-2012. This section also
e
U
mary of the conditions. of the deck for regions where the wind veloc- allows for “a performance-based approach”

i n
ity is higher. At higher design wind speeds, a with the required assumption (Subsection

R
Conclusions
z
deck which is adequate to support an adhered C), “Assume maximum allowable stresses

T a
North-South Perimeters and Corner Zone fail- membrane roof with uniform uplift deck are determined using allowable strength

g
S
ures occurred. It is interesting to note that, with loading may not be structurally adequate design (ASD) in accordance with AISI
the amounts of overload shown in these calcu-
a
to support widely spaced line loads from a S100-2012, or comparable standard out-
lations, there are not more reported deck and
joist failures. There may be a number of reasons
for fewer reported failures. For example:
m
mechanically attached membrane roof. side the United States.” Therefore, the FM
Global requirements are no more stringent
than AISI S100 for steel deck spans and
1) The design uplift anchorage of the
FM Global Requirements thicknesses.
deck to the joists, while increased for Often times, FM Approval Standard 4470, This confusion may have been the result
mechanical attachment as compared to Single-Ply, Polymer-Modified Bitumen Sheet, of interpretation of the definition of
adhered membranes, does not exceed Built-Up Roof (BUR) and Liquid Applied Service Wind Load within FM Approval
the factors of safety in the design of the Roof Assemblies for use in Class 1 and Standard 4470 which states, “The uplift
deck attachment fasteners. Noncombustible Roof Deck Construction, is load resulting from a windstorm that a
2) The majority of roofs have not seen required for roof systems. These requirements roof assembly must resist. The service load
roof uplift loads of those predicted are more stringent with respect to deck spans is equal to one-half of the rated load in psf
by ASCE 7 because the U.S. has not and thicknesses because the FM Standard (kPa).” As part of the FM Approval process
been impacted by a major hurricane uses a Factor of Safety of 2 (see sidebar for covered by this Standard, Simulated Wind
in over 10 years. updated information), whereas the AISI S100 Uplift Pressure Testing is performed on
3) The decks may have higher yield Standard mandates an ASD Factor of Safety roof assemblies. The rated load achieved
strengths than those used in the of 1.67 for flexure. These requirements can by a particular roof assembly in uplift pres-
design example. The SDI RDDM be found on their RoofNav website. Go to sure testing is equivalent to two times the
tabulates roof deck capacity based on www.roofnav.com and select Reference uplift pressure from a windstorm the roof
a lower bound yield stress of 33 ksi. Materials followed by Approval Standards. assembly is required to resist. Therefore,
Many manufacturers provide decks The FM Standard provides wind ratings based the factor of safety of 2 applies only to the
with yield stresses of 40, 50, or 80 ksi on fastener row spacing, deck spans, deck performance of a roof assembly during
(limited to a 60 ksi design stress by the thicknesses, and deck yield strengths. uplift pressure testing. It does not apply
AISI S100 Standard). A design stress For the above example, for a 33 ksi, 1.5-inch. to deck span calculations.
of 60 ksi versus 33 ksi will increase the WR deck spanning 6 feet, a 20-gage deck is
deck flexural strength by about 70%. required to obtain a 60 rating (30 psf ASD). Anthony Longabard
Staff Engineering Specialist
FM Global
Application When Re-Roofing Recommendations www.fmglobal.com
An important point to note is that, per NRCA, Design recommendations for single-ply roofing
approximately two-thirds of the roofing when concentrated line securements are used to

STRUCTURE magazine 32 March 2017


connect the membrane to steel roof deck instead perform a structural analysis of the entire roofing team (specifier,
of uniformly distributed securements include: the deck as a 3-span beam, placing manufacturer, and installer).
1) When FM Global requirements are the first concentrated load at the e) Determine the net uplift
to be followed, maximum deck spans, mid-span of the first deck span. requirement for all joists based on
deck thicknesses, and deck yield The subsequent loads are placed the final selected line securement
strengths as required by FM Global according to their spacing. This spacing and forces.
must be used. analysis will produce a moment f ) S pecify these requirements to the
a) Based on the maximum diagram that is close to the joist manufacturer.
concentrated line loads determined maximum that would be achieved g) Coordinate your design
from FM Global, specify the from an influence line analysis. requirements with the general
required joist net uplift. c) From this analysis, specify a deck contractor and the architect.
b) Coordinate your design that has a flexural capacity that
requirements with the general exceeds the maximum positive and
contractor and the architect. negative design moments.
Economics
2) When FM Global requirements are d) If no deck is found that will Based on experience, using the wide attachment
not required: work, change the spacing of spacing may not®be economical when one con-

E
a) Determine the uniform net uplift the supports (joists) or alter the siders the increase in deck costs and joist costs
forces based on the building code spacing of membrane fastening. as compared to the labor savings using the wide

R
in force. Changing the spacing of the securement spacing. For any given project, these
b) Using the spacing between the lines membrane fastening is something cost comparisons should be made.▪

U
of fasteners for the membrane, that requires
righ
t coordination with

T
y
Cop

U C i n e

S T R m
a g a z

STRUCTURE magazine 33 March 2017

You might also like