You are on page 1of 2

Wednesday, September 25, 2019

OTDR Trace Report:


Fiber Number: 5 End 1: PLC
Wavelength: 850 nm End 2: MOTOR
Cable ID: A1 OTDR Located At: PLC
Fiber Type: OM3 50/125um Operator 1: --
Company Name: Proctek Operator 2: Operator2
Test Date: 9/23/2019 9:45:32 AM
File name: \...\FO PISCILAGO\PISCILOCA.job\PLC_MOTOR.rte\A1.cbl\PLC-MOTOR-A1_005_M85.sor
Trace Comment:
OTDR Model: M700-25 Backscatter Coef. (BC): -68.0 dB Cursor A: 15.22 m
Port: MM Loss Threshold: 0.10 dB Cursor B: 35.34 m
Range: 250.50 m Reflection Threshold: -65.00 dB B-A Distance: 20.13 m
Pulse Width: 30 ns End Threshold: 3.00 dB B-A Loss: 1.51 dB
Averages: 2304 Group Index of Refr. (GIR): 1.49600 B-A Loss per km: 60.81 dB/km

A B
0 dB

5 dB

10 dB

15 dB

20 dB

25 dB

30 dB

35 dB

40 dB

45 dB

50 dB

55 dB

60 dB

65 dB 1
0 20 40 60 80 100 120 140 160 180 200 220 240 m
Event Table
Number of Events: 1 -- -- Link Length: 0.0 m
Fiber Before Event Link Events
Atten. Loss Location Refl. Loss
# Source Type
(dB / km) (dB) (Meters) (dB) (dB)
1 -- -- Auto Reflective End 35.59 -30.44 --
: Failing value.
* Does not include loss of first or last connector.

Page: 1
Wednesday, September 25, 2019
OTDR Trace Report:
Fiber Number: 5 End 1: PLC
Wavelength: 1300 nm End 2: MOTOR
Cable ID: A1 OTDR Located At: PLC
Fiber Type: OM3 50/125um Operator 1: --
Company Name: Proctek Operator 2: Operator2
Test Date: 9/23/2019 9:45:47 AM
File name: \...\FO PISCILAGO\PISCILOCA.job\PLC_MOTOR.rte\A1.cbl\PLC-MOTOR-A1_005_M13.sor
Trace Comment:
OTDR Model: M700-25 Backscatter Coef. (BC): -76.0 dB Cursor A: 15.22 m
Port: MM Loss Threshold: 0.10 dB Cursor B: 35.34 m
Range: 251.34 m Reflection Threshold: -65.00 dB B-A Distance: 20.13 m
Pulse Width: 30 ns End Threshold: 3.00 dB B-A Loss: 0.85 dB
Averages: 2304 Group Index of Refr. (GIR): 1.49100 B-A Loss per km: 94.40 dB/km

A B
0 dB

5 dB

10 dB

15 dB

20 dB

25 dB

30 dB

35 dB

40 dB

45 dB

50 dB

55 dB

60 dB

65 dB 1
0 20 40 60 80 100 120 140 160 180 200 220 240 m
Event Table
Number of Events: 1 -- -- Link Length: 0.0 m
Fiber Before Event Link Events
Atten. Loss Location Refl. Loss
# Source Type
(dB / km) (dB) (Meters) (dB) (dB)
1 7.93 -- Auto Reflective End 35.21 -38.09 --
: Failing value.
* Does not include loss of first or last connector.

Page: 2