Professional Documents
Culture Documents
GP 12-25
Applicability Group
Date 14 November 2003
GP 12-25
BP GROUP
ENGINEERING TECHNICAL PRACTICES
14 November 2003 GP 12-25
Guidance on Practice for Earthing/Grounding
Foreword
This is the first issue of Engineering Technical Practice (ETP) GP 12-25. This Guidance on Practice
(GP) is based on the following heritage documents from merged BP companies:
Amoco ACES
EL-GR-00-G Electrical—Grounding—Guide
EL-GR-00-E Electrical—Grounding—Engineering Specification
EL-GR-00-C Electrical—Grounding—Installation Specification
ARCO APCES
ES 401-90 Electrical Grounding
BP GOMDW
EL-SP-4056 Neutral Grounding Resistor
BP Chemical-US
CP 17-10-1 Neutral Grounding Resistor
CP 17-15-1 Equipment Grounding Details
BP RPSE
RP 12-16 Electrical Systems and Installations Earthing and Bonding
Copyright 2003, BP Group. All rights reserved. The information contained in this
document is subject to the terms and conditions of the agreement or contract under which
the document was supplied to the recipient’s organization. None of the information
contained in this document shall be disclosed outside the recipient’s own organization
without the prior written permission of Manager, Standards, BP Group, unless the terms of
such agreement or contract expressly allow.
Page 2 of 38
14 November 2003 GP 12-25
Guidance on Practice for Earthing/Grounding
Table of Contents
Page
Foreword.......................................................................................................................................... 2
1. Scope...................................................................................................................................... 5
2. Normative references.............................................................................................................. 5
3. Power system earthing/grounding philosophy.........................................................................5
3.1. General........................................................................................................................ 5
3.2. Un-earthed/grounded (isolated) neutral........................................................................7
3.3. Solidly earthed/grounded neutrals (for systems below 1000 V)....................................7
3.4. Impedance earthed/grounded neutrals (for systems rated 1000 V and above)............7
3.5. Earthing/grounding resistors.........................................................................................8
3.6. Generators................................................................................................................... 8
3.7. Substations.................................................................................................................. 9
3.8. High-voltage motors...................................................................................................11
3.9. Low-voltage equipment..............................................................................................11
3.10. Offshore installations..................................................................................................11
4. Earthing/Grounding methodology..........................................................................................12
4.1. General...................................................................................................................... 12
4.2. Common earthing/grounding system..........................................................................13
4.3. Steel structures (onshore)..........................................................................................14
4.4. Vessels...................................................................................................................... 14
4.5. Storage tanks.............................................................................................................14
4.6. Floating roof tanks without rolling ladders..................................................................15
4.7. Metallic stacks and towers (not applicable to flare stacks).........................................16
4.8. Non-metallic structures...............................................................................................16
4.9. Metallic guy ropes......................................................................................................16
4.10. Pipelines and valves...................................................................................................16
4.11. Machine sets with non-electric drive...........................................................................17
4.12. Machine sets with electric drive..................................................................................17
4.13. Road tanker loading bays...........................................................................................17
4.14. Rail car loading bays..................................................................................................18
4.15. Sea tanker loading jetties...........................................................................................18
4.16. Portable container filling.............................................................................................18
5. Earthing system design......................................................................................................... 19
5.1. Soil resistivity.............................................................................................................19
5.2. Earth electrodes.........................................................................................................19
6. Earthing/grounding when cathodic protection is applied........................................................20
FIGURE 1A.................................................................................................................................... 22
Typical Methods of Earthing Electrical Equipment Onshore...........................................................22
Page 3 of 38
14 November 2003 GP 12-25
Guidance on Practice for Earthing/Grounding
FIGURE 1B.................................................................................................................................... 23
Earthing Principles Onshore...........................................................................................................23
FIGURE 2A (1 of 2)........................................................................................................................ 24
Typical Methods of Earthing Electrical Equipment Offshore...........................................................24
FIGURE 2B (1 of 2)........................................................................................................................ 26
Earthing Principles Offshore...........................................................................................................26
FIGURE 3....................................................................................................................................... 28
Bonding Principles Cable Glands...................................................................................................28
FIGURE 4....................................................................................................................................... 29
Static and Lightning Earthing Systems (Onshore) General Principles............................................29
FIGURE 5 (1 of 2).......................................................................................................................... 30
Typical Earth Rod and Earth Bar Details........................................................................................30
FIGURE 6....................................................................................................................................... 32
Typical Connections for Double Roof Tank with 4" Outlet..............................................................32
FIGURE 7....................................................................................................................................... 33
Typical Connections for Double Roof Tank with 6" Outlet..............................................................33
FIGURE 8....................................................................................................................................... 34
Typical Roof Connection for Double Roof Tank..............................................................................34
FIGURE 9....................................................................................................................................... 35
Typical Connections for Single Roof Tank......................................................................................35
FIGURE 10..................................................................................................................................... 36
Typical Roof Connection for Single Roof Tank...............................................................................36
Bibliography................................................................................................................................... 38
Page 4 of 38
14 November 2003 GP 12-25
Guidance on Practice for Earthing/Grounding
1. Scope
This GP document provides guidance for design, application, and installation of earthing/grounding.
2. Normative references
The following normative documents contain requirements that, through reference in this text,
constitute requirements of this technical practice. For dated references, subsequent amendments to, or
revisions of, any of these publications do not apply. However, parties to agreements based on this
technical practice are encouraged to investigate the possibility of applying the most recent editions of
the normative documents indicated below. For undated references, the latest edition of the normative
document referred to applies.
3.1. General
a. Earthing/grounding and/or bonding for electric power distribution systems should be
designed and installed in accordance with relevant parts of IEC 60364-5-54, IEC 61892,
API RP2003, NFPA 70, IEEE Standards 80, 141, and 142 or BS 7430.
Additional earthing/grounding details are given in PIP ELIGD000 and Appendix A
of this GP. Typical earthing and bonding installations for both onshore and offshore
are shown in Fig 1A, 1B, 2A, and 2B.
Page 5 of 38
14 November 2003 GP 12-25
Guidance on Practice for Earthing/Grounding
Page 6 of 38
14 November 2003 GP 12-25
Guidance on Practice for Earthing/Grounding
3.4. Impedance earthed/grounded neutrals (for systems rated 1000 V and above)
a. Neutral earthing/grounding equipment to limit earth fault currents should be provided in
the neutral connection to the plant earth system on all high-voltage power systems.
Such provision limits the overall transient system disturbance caused by earth faults
and also limits the amount of damage caused by this most common type of fault.
b. If the power system at the specific voltage contains no direct connected generators under
any mode of operation, the provision of the earthing/grounding resistor and its
earth/ground connection should consider the following possibilities:
1. At the source star connected transformers.
2. At other star connected power transformers.
3. At earthing/grounding transformers.
c. Neutral earthing/grounding equipment should comprise a resistor with a minimum
10-second fault rating selected to reduce the fault current to the full load rating of the
Page 7 of 38
14 November 2003 GP 12-25
Guidance on Practice for Earthing/Grounding
power source transformer. The use of reactors to earth/ground neutral systems should only
be used subject to design approval
Systems employing reactor earths are uncommon but have been used in some
countries or under special circumstances. One special circumstance is if a
'Petersen Coil' is used to avoid a circuit trip due to a transient earth fault e.g.
lightning induced flashover in overhead lines. Such special circumstances are
unlikely in industrial installations.
If reactance earthing/grounding is considered, its use should be tested against the
cost/benefit compared with resistance earthing/grounding. Special attention should
be taken of the possible tuning effects between the earthing/grounding reactor and
the power system.
d. If direct connected generators may be operated in parallel with source transformers, the
neutral earthing/grounding arrangements should provide for either system operating
independently. Neutral earthing/grounding equipment should be identically rated for all
power sources. If resistors are provided, these should comprise 10-second fault rated, solid
resistors. Resistors should reduce the fault current to a convenient level one half to full
load rating of the lowest rated power source, provided this fault current is sufficient to
operate the distribution system earthing/grounding protection and provide suitable
discrimination. If normal ratings of the source transformer and parallel running generators
are significantly different, the resistor rating selection should be dictated by the
requirement to ensure that the most insensitive earth/ground fault protection on any
incoming or outgoing circuit operates positively with the smallest possible source of
earth/ground fault current connected to the system.
If there is a 4-wire supply system, solid earthing/grounding will be provided in
order to keep neutral voltages as close to earth as possible. In this case the neutral
earthing/grounding arrangement should be simplified by arranging for the neutral
to be earthed at the switchboard.
3.6. Generators
a. Neutrals of generators directly connected to the distribution switchgear in 3-wire systems
(i.e. HV systems or special LV systems) may be solidly or resistance earthed/grounded.
However, solid earthing/grounding should be limited to generators if the earth/ground fault
capacity of the generator is approximately equal to the current level required to operate the
distribution system protection.
If solid earthing/grounding of the neutral is applied to a system with a (relatively)
low capacity generator in parallel with a larger power source, which has resistance
earthing/grounding, the generator should have a neutral circuit breaker, which
should be automatically controlled. However, where the influence of the fault on
other equipment is not unduly compromised by too high an earth/ground fault
current, the generator neutral could be allowed to remain solidly connected.
Page 8 of 38
14 November 2003 GP 12-25
Guidance on Practice for Earthing/Grounding
3.7. Substations
a. Substation safety criteria are different in different countries, with two main approaches.
American and European methods assess “step” and “touch” voltages, while the UK, focus
is given to evaluating the Rise of Earth Potential.
UK method is based on the fact that if the rise of earth potential is within specific
safety limits, then the maximum ‘step’ and ‘touch’ voltages are also sufficiently low
not to yield any hazard.
UK maximum permissible substation potential rise is 430 V. On systems protected
by high-speed protection (typically transmission lines), this limit may be increased
Page 9 of 38
14 November 2003 GP 12-25
Guidance on Practice for Earthing/Grounding
Page 10 of 38
14 November 2003 GP 12-25
Guidance on Practice for Earthing/Grounding
In single-core cable installations, the terminating gland plate surrounds each of the
three cable cores. The load current in each of the three phases generates a magnetic
field which extends into the volume external to the cable core and therefore into the
gland plate. If a ferrous material is used alternating magnetic field induces
hysteresis and eddy current effects, which heat the gland plate, with possible
insulation stress. Insulation stress effects are reduced by introducing an air gap
between adjacent cables (or other means of producing high magnetic reluctance).
This reduces the magnetic field intensity and the magnitude of eddy currents.
Alternatively, a non-ferrous gland plate could be employed, however, corrosion due
to dissimilar metals and the method of sheath earth bonding/grounding need to be
carefully considered.
Problems associated with eddy currents and hysteresis in single core cables also
affect ferrous armour. Therefore single core cables should always have a
non-ferrous armour applied.
m. If single point (or cross) bonding is required, unearthed/ungrounded terminations must be
insulated and shrouded. Earthed/grounded end should be at the hazardous area end (when
applicable). Maximum permissible sheath voltages to earth/ground are specified in
referenced industry standards for both sealing ends and joint positions.
Page 11 of 38
14 November 2003 GP 12-25
Guidance on Practice for Earthing/Grounding
4. Earthing/Grounding methodology
4.1. General
a. Earthing/grounding conductors may consist of one or a parallel combination of:
1. Dedicated earthing/grounding conductor
2. Cable armouring or metallic sheath
3. Rigid screwed conduit
4. Earth core within a multi-core cable
5. Structural steelwork.
b. Sole reliance on cable armouring and/or metallic sheathing should only be made if it is
adequately fault rated as a protective conductor.
This is a fundamental requirement, which should be met in case of faults within
electrical equipment. In the case of faults within cable, it may not be possible to
have armour which is fully fault-rated, particularly if armour is steel braid type.
However, the advantages of steel braid armour over steel wire armour on cables
used offshore are considered to outweigh this possible disadvantage.
c. Structural steelwork may be considered as a protective conductor provided it is part of the
common static and lightning earthing/grounding system and there is a permanent metallic
path for fault current via such steelwork and other earthing/grounding conductors back to
the power supply.
Use of structural steelwork as part of earthing/grounding system and as a path for
fault current is acceptable practice, particularly offshore where welded steel
structure of platform is regarded as 'earth'. The term only applies to permanent
structures such as an offshore platform or an onshore process plant. Connection
points should be made available for periodic testing of electrical integrity and
current carrying capacity of steelwork alone.
When a complex structure is used as (one of) the protective conductors, its
impedance cannot be readily calculated. However, it can be assumed that a very
large structure such as an offshore platform has negligible impedance compared
with that of cable armouring. For the purpose of calculations, the impedance of the
return path through such a structure can be assumed to be zero.
A consistency in choice of protective conductors for a particular plant should be
maintained when extensions to the plant are designed.
d. Cross sectional area of earthing/grounding conductors and bonding connections between
exposed and extraneous conductive parts should be capable of carrying earth fault current,
or an appropriate fraction of total fault current, for the duration of the fault without
damaging conductor or associated insulation.
Page 12 of 38
14 November 2003 GP 12-25
Guidance on Practice for Earthing/Grounding
e. The cross sectional area of protective conductors should comply with the minimum
requirements determined by methods given in clause 543.1of IEC 60364-5-54.
If 'protective conductor' consists of a large steel structure such as an offshore
platform, or an extensive mesh of interconnected copper earthing/grounding
conductors, its earth impedance may be ignored for fault current calculation.
However, for short cable circuits, earth impedance may be of comparable
magnitude to that of the cable sheath and should be considered. Also, if evaluating
its earth potential rise under fault conditions, the voltage rise across such
impedances should be accounted for.
Minimum sizes without mechanical protection are prescribed.
Use of multi-stranded protective conductors should be considered (e.g. 2.5mm 2,
7/0.67).
In practice, it may be desirable for any one project, to limit the number of sizes of
protective/bonding conductors to make purchasing more economical and/or to
simplify design and installation.
f. Buried earthing/grounding conductors should normally be bare copper cable. However,
when there is a likelihood of corrosion (for example particularly acidic soil), an overall
protective covering, e.g. green/yellow PVC, should be provided.
Note: When conductor is used as (part of) an earth/ground electrode, its
earthing/grounding performance will be reduced by the protective covering (no
transverse current leakage).
g. Joints in protective conductors should be avoided.
h. Design of high voltage cable glands or terminations should incorporate a lug for bonding
the cable armour to earth, or to equipment enclosure.
i. If a low-voltage cable enters a metallic enclosure, a bonding connection between the gland
and enclosure is not required, provided there is no electrical discontinuity of the enclosure.
j. If non-metallic enclosures are used, means shall be provided to preserve the electrical
continuity of the armouring and/or metallic sheaths of cables.
k. Enclosures, of any type, should be maintained at ground potential or be protected by a
system of double insulation.
Page 13 of 38
14 November 2003 GP 12-25
Guidance on Practice for Earthing/Grounding
4.4. Vessels
a. When vessels are mounted directly on, and in metallic contact with, an earthed steel
structure, no further bonding is necessary. However, additional earthing/grounding may be
required for lightning protection or to reduce overall earth/ground impedance.
b. When vessel mounting is insulated from steelwork by materials of poor conductivity such
as wood, concrete, rubber etc., two earthing/grounding connections should be taken from
vessel to common earthing/grounding system. If vessel is remote from plant and
connection to the common earthing/grounding system is impractical, two connections
should be taken from vessel to separate earth/ground electrodes and the resistance to earth
of each electrode should be less than 10 ohms.
c. Looping earthing/grounding conductors between vessels is permitted provided a
connection is taken from each end of 'looped' system to general earthing/grounding system
or earth electrodes.
d. Direct earthing/grounding for lightning should be applied when necessary.
e. Earthing/grounding connections should be copper conductor and sized as specified in
section 4.1.
f. If a vessel has insulation and an outer metal cladding or wire reinforcement, the metal
cladding or reinforcement should be electrically continuous and bonded to the vessel.
g. Armouring of armoured cables, which enter the vessel should be bonded to shell at point of
entry.
Page 14 of 38
14 November 2003 GP 12-25
Guidance on Practice for Earthing/Grounding
Bonding can preferably be achieved by direct bolting. Care should be taken to avoid
the formation of re-entrant loops.
e. On floating roof tanks, multiple shunt connections comprising stainless steel strips (e.g.
50x0.6x400 mm long), should be provided between the floating roof and the tubbing shoe
at adequate intervals around the roof periphery or one per pantograph if these are fitted.
a. If high winds prevail shunt strips may be replaced with cables bolted in position. Shunts
should be fitted above the sealing arrangement.
b. Spacing of shunt connections should avoid risk of discharge from roof to tank wall directly
across the gap rather than via a shunt, due to formation of re-entrant loops.
The risk is increased when path length of the loop exceeds eight times the width of
the open side. In this case the maximum loop length is half the peripheral distance
of the closed path between adjacent shunts.
Although hanger linkages on the pantograph offer an earthing/grounding path from
the floating roof to the shell, they can be a source of arcs during a lightning strike if
placed too close together (accepted minimum separation on an empirical basis is
1m). The arcs occur from sharp points or joints, but may be avoided installing short
insulated jumpers around each pinned hanger joint and covering sharp points of
hangers with insulating material.
c. When a rolling ladder is installed, a flexible copper-bonding conductor [e.g. 35 mm2
(No. 2 AWG)] should be applied across the ladder hinges, between ladder and tank top,
and between ladder and floating roof. (This is in addition to shunt connections.)
The earthing/grounding provisions assume that the ladder is articulated in the
centre in a manner, which allows continuity of earthing/grounding. If there may be
appreciable movement of the ladder at either the roof or rim, which makes
earth/ground bonding non-feasible, another approach may be necessary. No
specific advice is available for this eventuality, but past instances have led to
arrangements, which stowed ladders away from the roof when not in use.
d. When a rolling ladder is not installed, a flexible earth/ground cable [e.g. 70 mm2
(No. 2/0 AWG)] should be installed along roof drain of tank.
Previously, fitting of flexible earthing/grounding cable between the floating roof and
tank shell was practised as a supplement to the pantograph earthing/grounding
system. However, experience showed that these cables frequently became entangled
and broke with the movement of the roof. Also, the tangling of the cable produced
re-entrant loops. Thus, this practice is no longer recommended.
As an alternative to the provisions of this section, lightning protection may be
achieved by using an air termination network. A suitable system is described in
BS6651.
Page 15 of 38
14 November 2003 GP 12-25
Guidance on Practice for Earthing/Grounding
d. A detensioner should be installed if the earth/ground cable exits the roof connection. The
earth/ground cable should be fixed to the roof drain using suitable clips (e.g. stainless steel
cable ties) with due allowance for movement of all swivels.
e. When earthing/grounding cables have been installed, tests should be undertaken to ensure
a low resistance (less than 0.1 ohm) between roof and wall.
Page 16 of 38
14 November 2003 GP 12-25
Guidance on Practice for Earthing/Grounding
Page 17 of 38
14 November 2003 GP 12-25
Guidance on Practice for Earthing/Grounding
Page 18 of 38
14 November 2003 GP 12-25
Guidance on Practice for Earthing/Grounding
2. Conveyor tracks
3. Other ancillary equipment.
b. Filling hoses should be electrically continuous. A separate flexible earthing/grounding lead
with a robust clip or clamp should be provided for connecting to drum during filling. This
arrangement is not necessary for filling of pressure containers.
c. An earthing/grounding unit, interlocked with product delivery pumps should be installed.
Page 19 of 38
14 November 2003 GP 12-25
Guidance on Practice for Earthing/Grounding
d. Due to galvanic coupling between copper and steel, an extensive copper grounding system
grid may accelerate corrosion of steel piping and other buried structures that are connected
to the system. Under this condition, galvanized steel ground rods and insulated or coated
copper conductors may be used. However, earth electrodes should not be allowed to
corrode or rust and reduce their effectiveness, and use of insulated or coated conductors
should not compromise overall system safety by increasing its overall earth impedance.
e. Earth/ground rods may be of the following materials providing that they are entirely
suitable for the application and ground conditions:
1. Solid hard drawn copper
2. Phosphor bronze
3. Copper clad steel
4. Stainless steel
5. Galvanised steel
6. Cast iron pipe.
f. Earth rods are generally available in standard lengths. Copper is commonly used for
grounding system grids because of resistance to corrosion as well as high conductivity.
Copper clad steel rods are available in specific lengths. An appropriate minimum diameter
should be considered.
g. Copper clad steel rods should be of molecularly bonded type. Minimum thickness of
copper recommended in relevant standards should be respected and coatings should be
maintained over entire length of rod, including threaded portion. Couplings should be
made of silicone aluminium bronze and should be of sufficient length to enclose
completely threads with rods in end-to-end contact.
h. Each earth/ground rod should be protected against corrosion and terminated in an
inspection pit.
a. Bonding between a cathodically protected pipeline and/or storage tank and any
earthing/grounding system can reduce efficiency of an impressed current cathodic
protection system by diverting flow of impressed current. Cathodically protected sections
of pipeline should be isolated from unprotected sections and from any earthing/grounding
systems. Presence of electrically operated valves may make complete isolation impractical.
b. Isolation can be achieved when electrically operated valves or other devices are installed
by inserting insulating bushings between cable gland and device. Device should be bonded
to pipeline. It should be established that a return earth/ground path via the pipeline is
sufficient to ensure correct operation of protective devices on supply to equipment.
c. Sometimes it is necessary to earth/ground buried pipelines which are impressed current
cathodically protected, e.g. to alleviate the effects of local overhead power lines. In such
cases pipeline should be earthed/grounded by polarisation cells or alternatively by use of
earthing/ground rod materials of a suitable galvanic potential.
d. When plant is cathodically protected, either by sacrificial anodes or by an impressed
current system, the design of earthing/grounding systems should be agreed with suppliers
and designers of cathodic protection system.
Page 20 of 38
14 November 2003 GP 12-25
Guidance on Practice for Earthing/Grounding
Annex A
(Informative)
Earthing/grounding details
Note: Some details forming part of this Annex contain references to heritage BP
RP 12-16. It is intended that these details will be revised in a future update of this
GP 12-25, but until then, if required, it will be possible to check the references with
the heritage document.
Page 21 of 38
14 November 2003 GP 12-25
Guidance on Practice for Earthing/Grounding
NOTES:
1. Numbers shown thus 2.2.1 indicate the relevant clause of RP 12-16.
2. For earthing details see figure 5.
FIGURE 1A
Page 22 of 38
14 November 2003 GP 12-25
Guidance on Practice for Earthing/Grounding
NOTES:
1. Apparatus which is bonded to an earthed steel structure by means of its holding down bolts or by
welding requires no additional bonding connection.
2. Apparatus which is otherwise isolated from the earthing system should be bonded as shown. The cross
section of the earth bond should be in accordance with sub-section 2.1.5 or 2.1.6 of RP 12-16.
3. If the plant/apparatus is remote from the sub-station the earthing systems need not be interconnected.
In this case earth fault current will return via the cable armour or earth core. Account should be taken of
parallel earth paths via the armour of other cables.
FIGURE 1B
Page 23 of 38
14 November 2003 GP 12-25
Guidance on Practice for Earthing/Grounding
FIGURE 2A (1 of 2)
Page 24 of 38
14 November 2003 GP 12-25
Guidance on Practice for Earthing/Grounding
NOTES
1. Fixed off shore installations are grounded or earthed into the seabed by steel pipes, well conductors etc.
Mobile units are earthed by the conductivity of the seawater
2. All topsides metalwork is either bolted or welded onto the structural support steelwork to extend the earth
continuity to the extremities of the installation.
3. All tanks, vessels, pipe, duct , and traywork, handling and access ways are bolted or welded to the
structural steelwork to ensure that any static potential build up will be avoided by continuous drain to
‘earth’
4. All live conductors are protected against touching by personnel, corrosion and possible mechanical
damage
5. All metallic enclosures, gland plates and cables glands have earth continuity by physical connection.
6. All insulated enclosures have earth continuity facility for internal metal work, via cable armouring
system.
7. Neutrals of low voltage systems are earthed at the switchboard
8. Exposed metallic parts of electrical equipment are in electrical contact with the structure by holding down
bolts, bedplates etc, but additional bonding connections are required where indicated
9. Numbers shown thus :- 2.2.1 indicate the relevant clause of RP 12-16.
10. This drawing is based on fig 2.1 of the IEE recommendations for the electrical and electronic
equipment of mobile and fixed offshore installations.
FIGURE 2A (2 of 2)
Page 25 of 38
14 November 2003 GP 12-25
Guidance on Practice for Earthing/Grounding
FIGURE 2B (1 of 2)
Page 26 of 38
14 November 2003 GP 12-25
Guidance on Practice for Earthing/Grounding
NOTES
1. The steel structure of the platform jacket and modules forms the earthing system and the principle
protective conductor
2. Exposed metallic parts of electrical (and non-electrical ) apparatus are normally effectively
bonded to the steel structure by holding down bolts, bedplates welds etc
But additional bonding connections are required where indicated
3. All tanks, vessels . pipes, ducts, traywork, handrails, etc. are bolted or welded to the steel
structure ensuring electrical continuity throughout installation and preventing any build up of
static.
4. Arrows indicate route of current for earth fault at point ‘F’ in addition fault current will return via
pipe work and the armouring of other cables.
FIGURE 2B (2 of 2)
Page 27 of 38
14 November 2003 GP 12-25
Guidance on Practice for Earthing/Grounding
NOTES
1. Where cables enter a metallic enclosure it is not necessary to install additional bonding connections
between glands or between glands and the equipment, provided that the entry is tapped or a ‘ star ‘ washer
is fitted under the backnut to ensure good electricity
2. Where cables enter a non-metallic enclosure means should be provided for bonding the cable armour to
each other and to earth. ( normally achieved with an earth continuity plate located inside the enclosure ).
FIGURE 3
Page 28 of 38
14 November 2003 GP 12-25
Guidance on Practice for Earthing/Grounding
Notes
1. Numbers shown thus 3.4.1 refer to relevant clause of RP 12-16
2. For earthing details refer figure 5
3. This diagram is intended to illustrate a typical static and lightning earthing scheme. In practice the design
of the earthing system will depend on site conditions, soil resistivity, plant layout, need for lightning
protection, etc
FIGURE 4
Page 29 of 38
14 November 2003 GP 12-25
Guidance on Practice for Earthing/Grounding
FIGURE 5 (1 of 2)
Page 30 of 38
14 November 2003 GP 12-25
Guidance on Practice for Earthing/Grounding
NOTES
1. Minimum size and type or earth conductor for general use shall be 25 x 3 copper tape or 70mm 2 bare
copper cable. Minimum size and type of flexible earth conductor should be 35mm 2 276/0 single core
600/1000 volt grade. Whilst copper conductors are preferred other equivalent materials may be used
subject to approval. For mechanical protection or where corrosive conditions may exist an overall
covering, e.g. pvc, shall be provided
2. If rods cannot be driven to a suitable depth their installation must be preceded by drilling. Care must be
taken to ensure the satisfactory consolidation of the backfill soil. Resistivity can be reduced by the use of
a suitable soil conditioning agent. Salt agents should be avoided as they encourage corrosion.
3. The use of cad weld jointing technique is permitted for earth conductor joints, and is the preferred method
for underground joints.
4. Earthing bosses welded to pressurised vessels shall be of the same material quality as the vessel
FIGURE 5 (2 of 2)
Page 31 of 38
14 November 2003 GP 12-25
Guidance on Practice for Earthing/Grounding
FIGURE 6
Page 32 of 38
14 November 2003 GP 12-25
Guidance on Practice for Earthing/Grounding
FIGURE 7
Page 33 of 38
14 November 2003 GP 12-25
Guidance on Practice for Earthing/Grounding
FIGURE 8
Page 34 of 38
14 November 2003 GP 12-25
Guidance on Practice for Earthing/Grounding
FIGURE 9
Page 35 of 38
14 November 2003 GP 12-25
Guidance on Practice for Earthing/Grounding
FIGURE 10
Page 36 of 38
14 November 2003 GP 12-25
Guidance on Practice for Earthing/Grounding
FIGURE 11
Page 37 of 38
14 November 2003 GP 12-25
Guidance on Practice for Earthing/Grounding
Bibliography
[1] BS 5958 Code of Practice for the control of undesirable static electricity
[3] BS 7671 Requirements for electrical installations. IEE Wiring Regulations. Sixteenth edition
[4] EA TS 41-24 Guidelines for the design, installation, testing and maintenance of main earthing
systems in substations
[5] EA S.34 A guide for assessing the rise of earth potential at substation sites
[6] IEE Recommendations for the electrical and electronic equipment of mobile and fixed offshore
installations
Page 38 of 38