ABSTRACT
This article deals with inter-turn fault Detection
of winding
detection in the transformer winding,
inter-turn fault which occurs due to insu-
lation degradation between one or more
sequential turns of the winding. If the
inter-turn
fault is not detected at the earliest stage,
it propagates to the nearby turns of the
winding during certain period of time
and it causes irreversible damage to the
faults
winding. Therefore, it is necessary to
detect inter-turn fault to save the trans-
former from catastrophic failure.
KEYWORDS
detection, fault factor, inter-turn, Detection based on frequency response
SFRA, transformer analysis - Part III
100 TRANSFORMERS MAGAZINE | Volume 7, Issue 3 | 2020
Manojmohan SUBRAMANIAN
1. Case studies – Detection of which corresponds to a short circuit of winding and a schematic diagram of sing
fault in layer windings using 50 turns. Fig. 1a and 1b show single-layer le-layer winding.
SFRA
Frequency response analysis can be extend
ed to single and multi-layer windings. At
the same time, the fault factor characteris
tics are obtained for different fault percent
ages.
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 101
DIAGNOSTICS
Figure 2. Impedance characteristics for healthy winding and 5 %, 10 % and 20 % faults at different locations along the single-layer winding
Sweep frequency response analysis is in the winding. The curve shifts upwards
as the percentage of fault decreases. This
performed from 10 Hz to 25 MHz curve is symmetrical with respect to
the centre of the winding section and
provides reliable information about fault
Fig. 2 shows the measured impedance teristic shows a reduction in the impe detection.
characteristics for healthy winding and dance at this frequency depending on the
5 %, 10 % and 20 % faults at different lo location of the fault. 1.2. Detection of fault in multi-layer
cations along the winding. The first reso winding - measurement results
nant frequency of the healthy winding is Fig. 3 shows the fault factor characteristics
frh1= 40.738 kHz. The impedance charac for 5 %, 10 % and 20 % of inter-turn fault SFRA is performed on the multi-layer
WINDING SECTIONS
Figure 3. Fault factor for 5 %, 10 %, 20 % faults vs layer sections for different percentage of faults at different locations
Figure 5. Impedance characteristics for healthy and percentage of faults along the multi-layer winding
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 103
DIAGNOSTICS
SFRA method can be used for detecting the length, may lead to changes in resonant
frequencies [2]. The magnitude of the
inter-turn faults for both single-layer and series capacitance of the windings has an
important effect on the impulse voltage
multi-layer winding distribution and the stresses along
the windings. By increasing the series
capacitances of the windings, the impulse
Change in the fault factor values for Transformer winding resistance, self and voltage distribution α becomes more
10 %, 20 %, 30 % of inter-layer faults at mutual inductance as well as the series and linear, and the stress on the winding is
different locations along the winding is shunt capacitances, have their own impacts reduced.
shown in Fig. 6. It is clear from the fi on the spectrum response. From a physical
α = Cg
gure that the location and extent of fault
changes when there is a corresponding
point of view, winding inductances, as
well as capacitances, play a major role in √ Cs
(1)
change in the fault factor values. As the the formation of the frequency response Where:
percentage of fault increases, the fault trace. At low frequencies, transformer α - Voltage distribution parameter
factor curve shifts downwards. Thus, winding inductances are more dominant Cg - Capacitance between winding and tank
it can be noted that the 20 % fault cur as inductive reactance of the transformer Cs - Series capacitance of winding
ve lies within the 10 % fault curve and winding is considerably greater than
the 30 % fault curve. This factor value capacitive reactance. As the frequency To improve the transient voltage distri
is symmetrical for each percentage of increases, inductive reactance will take the bution along the transformer winding,
faults, and this property is used for de values high enough to be neglected. At the it is necessary to make the initial voltage
tection of an inter-layer fault in the layer same time, capacitive reactance becomes distribution constant α as low as possi
winding. gradually a major player in the formation ble. One way of accomplishing this is to
of the frequency response trace. This study increase Cs [3]. The static end ring (SER)
2. Effect of static end ring, concentrates on the shunt capacitance is placed over the top of the winding and
influences on the frequency response connected to the line terminal of the
grounded inner core and alu-
spectrum oscillations and explores the winding. A spacer is inserted in-between
minium grounded tank on de- shunt capacitance contribution in the FRA the SER and the top of the winding to pro
tection of the inter-turn fault spectrum. The contribution of this study vide proper clearance. In practical cases, a
in continuous disc winding is generally focused on the transformer SER is placed over the top of the winding,
model winding with an isolated tank, which reduces the stress locally during the
The objective of this section is to check grounded tank on LV and HV windings initial voltage distribution.
the influence of the shunt capacitance, in order to check any influence on the
as well as the series capacitance, on the frequency response fluctuations [1]. By providing a large equipotential surface
frequency response trace of the winding, with a good corner radius, the SER re
and thus on the detection of the inter- Any changes in the values of inductance duces the stress concentration at the line
turn fault. or capacitances, as well as winding end. The SER changes the series capacitance
WINDING SECTIONS
Figure 6. Fault factor vs layer sections in multi-layer winding with 10 layers for 10 %, 20 % and 30 % inter-layer fault
Case I: Continuous disc winding with a Presence of the static end ring has an
grounded tank, grounded inner core, and
SER on top of the winding. influence on the resonant frequencies in
the frequency response trace which comes
Case II: Continuous disc winding with
the grounded inner core, and SER on top from changes in the series capacitances
of the winding.
Deviated frequencies provided in Table A fault factor is calculated for continuous surement on the continuous disc winding
1 show the first two resonant frequency disc winding in the presence and absence and layer windings and can be summa
variations. In the case of the frequency re of a grounded aluminium tank and SER. rized as follows:
sponse trace of the winding, C1 is due to the Fig. 8 - 10 show the fault factor variation • Detection of fault with respect to
presence of the grounded tank, grounded in the presence and absence of the groun the centre of the winding can be
inner core and SER, and C2 is due to the ded tank and SER where the difference found by using fault factor charac
presence of the grounded inner core and between the fault factor characteristics is teristics.
SER. According to the data shown in Table very minimal. • Fault factor characteristics are obtained
1, it is estimated that the shift in the reso for the detection of inter-turn faults in
nant frequencies in the presence and ab Detection of inter-turn fault in the continuous disc winding and the
sence of the static grounded tank and SER, same methodology is extended for lay
transformer winding using SFRA
the series and shunt capacitance variation er windings for a different percentage
is found to be 9.6 %, while the second re – measurement summary of faults in the winding. The efficacy of
sonant frequency reports 4.7 % variation Methods for detection of the fault have the methodology is checked in the lay
in the capacitance. been developed by the SFRA-based mea er winding.
Table 1. Capacitance ratio and resonant frequencies for continuous disc winding in the presence and absence of a grounded aluminium tank and SER
Winding with the
Winding with the
grounded inner
grounded tank,
()
core, SER on top of 2
grounded inner C 2 = f1
Resonant frequency Hz the winding
core, SER on top of C1 f2
(grounded tank is
the winding
excluded)
f1 [Hz]
f2 [Hz]
fr1
794329 758578 1.096
(anti-resonance)
fr2
1258930 1230270 1.047
(resonance)
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 105
DIAGNOSTICS
ZFaulty / ZHealthy
Figure 8. Fault factor vs winding disc or sections for 8.33 % inter-turn fault in continuous disc winding in the presence and absence of SER and tank
ZFaulty / ZHealthy
Figure 9. Fault factor vs winding disc or sections for 4.44 % inter-turn fault in continuous disc winding in the presence and absence of SER and tank
To improve the transient voltage distribution fault factor characteristics in the pres
ence and absence of the SER and tank
along the winding, it is necessary to make the is around 0.013 for different percentage
of faults.
initial voltage distribution constant (α) as
low as possible; one way of accomplishing Efficacy of the developed methodology is
validated under practical cases which in
this is to increase the series capacitance volve the SER, grounded inner core and
by providing SER at the line terminal of the grounded tank.
the influence of the winding distributed Conclusion ing and layer windings are developed by
parameters on the detection of the fault. using sweep frequency response anal
The corresponding flow chart for detec The methods for the detection of the in ysis through the transformer winding
tion of fault is shown in Fig. 11. ter-turn fault in a continuous disc wind circuit modelling and impedance mea
SFRA
Presence of Grounded inner core Presence of Static End Ring, Grounded tank,
(Case A) grounded inner core (Case B)
Comparison between fault factors (A), (B) and calculation of absolute difference
Figure 11. Flow chart for detection of a fault in the presence and absence of grounded tank grounded inner core and SER
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 107
DIAGNOSTICS
surement over a wide frequency range. [3] M. Bagheri et al., Influence of Elec- transformer windings using frequency
trostatic shielding of disc winding on response analysis, CIGRE Guide 2008
The proposed methodology provides a increasing series capacitance in trans- working group A2.26.
better insight into the detection of the former, Power Tech, 2007
fault in the winding through fault fac [5] Frequency Response Analyzer, Meg
tor characteristics. Also, the effect of the [4] Mechanical condition assessment of ger User Manual
grounded inner core, grounded tank and
SER on top of the winding is included in
the existing measurement setup to check
the influence of the winding distributed Author
parameters, such as shunt and series capa Manojmohan Subramanian completed M.Eng. in
citances, on the detection of the fault. High Voltage Engineering from College of Engineering
Guindy, Anna University Chennai, India, B.Eng. in
Bibliography Electrical and Electronics Engineering from Thiagarajar
College of Engineering, Madurai, and Diploma in
[1] M. Bagheri, B. T. Phung et al., Shunt Electronics and Communication Engineering. Presently
capacitance influences on single phase he is working as an Energy and Utilities Consultant.
transformer FRA spectrum, Electrical He has also been working as a Systems Engineer at
Insulation Conference, Ottawa, Ontario, Tata Consultancy Services and British Telecommunication, UK. Today he
Canada, June 2nd to 5th 2013 is an active member of IAENG Hong Kong, IRED NewYork, ITEEA, and
NASSCOM. His research interests include transformer fault diagnosis
[2] M. Bagheri et al., Transformer fre- and condition monitoring, frequency response analysis of transformers,
quency response analysis: Mathemati- characterization of transformer insulation, power transmission and
cal and practical approach to interpret distribution, smart grid, deregulated energy market, advanced metering
mid-frequency oscillations, IEEE Trans infrastructure, energy data management, applications of artificial
actions on Dielectrics and Electrical Insu intelligence, and data analytics for utilities.
lation, Volume 20, Issue 6, 2013