You are on page 1of 2

Scott Miller, TBE

Thomas-Young Associates
Stairwell/Elevator Pressurization Checklist
Project Name: _____________________________________ Date: __________

Stairwell Pressurization Checklist Address: ________________________________________________________

______________________________________________________

O
ur company is involved in Life Safety Testing in encounter are architecturally incomplete stairwells (wall
many of the cities and towns in our area and as penetrations not sealed, doors or door hardware not Contact: ____________________________________________________
is probably typical throughout the country, we installed, door sweeps not installed or finished floors not
find different requirements for each city. As a result of complete), volume dampers not installed, controls or
this, we have developed a checklist over time that has been control sequences not complete and fans not wired. ❏ Are stairwells / elevator shafts architecturally complete?
useful to not only our company but also to all of the other
contractors involved.
The requirement for trained and certified technicians ❏ Are all wall penetrations properly sealed?
to perform this testing also cannot be overstated. It is
We use this checklist as a tool to save time and headaches imperative that the technician performing the testing ❏ Are all doors and door hardware installed?
for all contractors involved. Our experience has shown us completely understands not only the balancing requirements
that there is nothing worse than scheduling the local fire but also the requirements of the local inspectors and testing ❏ Are door sweeps installed and set to the correct height?
department for an inspection only to find out that all the criteria. The technician needs to be intimately familiar with
items are not ready. As is typical for most jobs, life safety the contract drawings as well as the sequence of operation ❏ Are thresholds and finished floors complete?
gets pushed off to the last minute and does not become for the equipment.
a priority until the general contractor is trying to get the ❏ Are the correct fans installed and are they wired?
Prior to starting any testing the technician must completely
certificate of occupancy. ❏ Are all volume dampers installed?
review the drawings for the following:
To complicate matters, we have found that on most jobs, Are all of the registers installed?
the general contractors are not always sure what exactly

❏ Are all motorized dampers installed and are the motors wired and powered?
■ Are the correct damper types installed? (manual,
is required to pass a life safety inspection. It is for this
reason that we find it extremely important to stress the Life
motorized, weighted barometric etc.) ❏ Are all relief dampers installed?
■ Are all control dampers including damper motors
Safety (Stairwell Pressurization) requirements to the general
installed?
❏ Are the correct type of relief dampers installed and have they been tested for
contractor as early as possible during the construction proper operation?
process in order to ensure a smooth and successful ■ Are the correct fans installed?
inspection.
Once the above is verified, the sequence of operation
❏ Has the ATC contractor completed and commissioned all of the control
components?
Our checklist concentrates on the stairwell and elevator for the stairwells needs to be reviewed with the controls
pressurization portions of Life Safety and includes items contractor so that the correct procedure for balancing ❏ Has the ATC contractor downloaded the correct sequence of operation?
which need to be complete before starting any stairwell or can be formulated. The final step is to perform the actual
elevator pressurization testing. The checklist also includes balancing of the stairwells and vestibules. As the balancing ❏ Have all pressure sensors been calibrated?
some procedures which need to be followed during the starts, coordination between all contractors is essential.
actual testing. Our experience has been that if the first
inspection does not pass, each additional inspection All systems must be running and all stairwell and vestibule
becomes more difficult and this checklist can help to make doors must remain closed during the setting of airflows and
the general contractor aware of what is involved in the individual floor pressurizations. Remarks: _________________________________________________________
testing process. In summary, we have found that the most important
items of a successful stairwell or elevator pressurization _________________________________________________________
Our checklist places stress on the items that we find to be
the most critical in completing both stairwell and elevator test are planning, coordination and trained and certified
personnel. _________________________________________________________

pressurization testing. Some of the items that we commonly

20 TAB Journal 21
Scott Miller, TBE
Thomas-Young Associates
Stairwell/Elevator Pressurization Checklist
Project Name: _____________________________________ Date: __________

Stairwell Pressurization Checklist Address: ________________________________________________________

______________________________________________________

O
ur company is involved in Life Safety Testing in encounter are architecturally incomplete stairwells (wall
many of the cities and towns in our area and as penetrations not sealed, doors or door hardware not Contact: ____________________________________________________
is probably typical throughout the country, we installed, door sweeps not installed or finished floors not
find different requirements for each city. As a result of complete), volume dampers not installed, controls or
this, we have developed a checklist over time that has been control sequences not complete and fans not wired. ❏ Are stairwells / elevator shafts architecturally complete?
useful to not only our company but also to all of the other
contractors involved.
The requirement for trained and certified technicians ❏ Are all wall penetrations properly sealed?
to perform this testing also cannot be overstated. It is
We use this checklist as a tool to save time and headaches imperative that the technician performing the testing ❏ Are all doors and door hardware installed?
for all contractors involved. Our experience has shown us completely understands not only the balancing requirements
that there is nothing worse than scheduling the local fire but also the requirements of the local inspectors and testing ❏ Are door sweeps installed and set to the correct height?
department for an inspection only to find out that all the criteria. The technician needs to be intimately familiar with
items are not ready. As is typical for most jobs, life safety the contract drawings as well as the sequence of operation ❏ Are thresholds and finished floors complete?
gets pushed off to the last minute and does not become for the equipment.
a priority until the general contractor is trying to get the ❏ Are the correct fans installed and are they wired?
Prior to starting any testing the technician must completely
certificate of occupancy. ❏ Are all volume dampers installed?
review the drawings for the following:
To complicate matters, we have found that on most jobs, Are all of the registers installed?
the general contractors are not always sure what exactly

❏ Are all motorized dampers installed and are the motors wired and powered?
■ Are the correct damper types installed? (manual,
is required to pass a life safety inspection. It is for this
reason that we find it extremely important to stress the Life
motorized, weighted barometric etc.) ❏ Are all relief dampers installed?
■ Are all control dampers including damper motors
Safety (Stairwell Pressurization) requirements to the general
installed?
❏ Are the correct type of relief dampers installed and have they been tested for
contractor as early as possible during the construction proper operation?
process in order to ensure a smooth and successful ■ Are the correct fans installed?
inspection.
Once the above is verified, the sequence of operation
❏ Has the ATC contractor completed and commissioned all of the control
components?
Our checklist concentrates on the stairwell and elevator for the stairwells needs to be reviewed with the controls
pressurization portions of Life Safety and includes items contractor so that the correct procedure for balancing ❏ Has the ATC contractor downloaded the correct sequence of operation?
which need to be complete before starting any stairwell or can be formulated. The final step is to perform the actual
elevator pressurization testing. The checklist also includes balancing of the stairwells and vestibules. As the balancing ❏ Have all pressure sensors been calibrated?
some procedures which need to be followed during the starts, coordination between all contractors is essential.
actual testing. Our experience has been that if the first
inspection does not pass, each additional inspection All systems must be running and all stairwell and vestibule
becomes more difficult and this checklist can help to make doors must remain closed during the setting of airflows and
the general contractor aware of what is involved in the individual floor pressurizations. Remarks: _________________________________________________________
testing process. In summary, we have found that the most important
items of a successful stairwell or elevator pressurization _________________________________________________________
Our checklist places stress on the items that we find to be
the most critical in completing both stairwell and elevator test are planning, coordination and trained and certified
personnel. _________________________________________________________

pressurization testing. Some of the items that we commonly

20 TAB Journal 21

You might also like