You are on page 1of 8

COMMERCIAL BUILDING SERVICES

GRUNDFOS DISTRIBUTED PUMPING

PUMP SIZING

HYDRONIC FULLY SPECIFIED


CORRECT SIZING = SCHEMATIC MATCHING PUMP EQUIPMENT
EFFICIENCY YOUR PROJECT SCHEDULE READY

Introduction Table of contents


Distributed pumping can help improve the efficiency of Pump sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
chilled water systems. This paper explores how to correctly What is distributed pumping? . . . . . . . . . . . . . . . . . . . . . . . 2
size pumps in a distributed network, addresses common
Why use distributed pumps? . . . . . . . . . . . . . . . . . . . . . . . . . 3
questions related to distributed pumping and provides
insight on benefits, including lower pressure and Primary pumps in distributed pumping systems . . . . . . 3
horsepower requirements. The focus is on chilled water, Secondary pumps in distributed pumping systems. . . . 5
but the theories contained are applicable to hydronic
Conclusion. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
heating as well.

Prepared by Pavel Mirchev


2

PUMP SIZING WHAT IS DISTRIBUTED PUMPING?


Chilled water hydronic applications have traditionally Distributed pumping is a hybrid pumping arrangement
been arranged two ways: primary with variable secondary that combines variable primary and variable secondary
or variable primary pumps. Distributed pumping is an systems. Distributed simply means that the secondary
introduction of a third style of hydronic pumping. pumps are distributed through the piping network so as
to be located next to each zone (coil pumps) – specifically
This paper will provide insight on how to properly size the air handling unit (AHU) or bank of fan-coil units. These
pumps in a distributed network and address some of the distributed pumps are installed in place of control valves
most common questions and selection pitfalls. The paper and balancing valves. Primary pumps can provide for the
will focus on chilled water, but the same theories apply to full system flow and circulation through the bypass line if
hydronic heating. necessary. Figure 1A shows a traditional variable primary
design and Figure 1B illustrates the same application but
In order to understand the subject matter of this paper it is with distributed pumps.
necessary to understand pump and hydraulic performance,
friction loss in piping networks and across chilling
equipment, and the general curves and data associated
with hydronic equipment. For the purposes of this
conversation, it is assumed that the standard systems
utilise control valves and circuit setters, and that piping is
set up in a two-pipe configuration.

DN125 DN125 DN125 DN100 DN100 DN80


Flow 23.88 L/s Flow 23.88 L/s Flow 19.1 L/s Flow 14.3L/s Flow 9.55 L/s Flow 4.78 L/s
30 m 25 m 10 m 10 m 10 m 10 m

1 2 3 4 5 6
CHILLER
CHILLER

PD 60 KPA
PD 24.5 kPa

Variable
primary design
M

CV PD 20 KPA
Figure 1A. Traditional variable primary arrangement
3

DN125 DN125 DN125 DN100 DN100 DN80


Flow 23.88 L/s Flow 23.88 L/s Flow 19.1 L/s Flow 14.3L/s Flow 9.55 L/s Flow 4.78 L/s
30 m 25 m 10 m 10 m 10 m 10 m

1 2 3 4 5 6
CHILLER
CHILLER

PD 60 kPa

Grundfos distributed
Pumping design PD 24.5 kPa

Figure 1B. Distributed pump arrangement

WHY USE DISTRIBUTED PUMPS? PRIMARY PUMPS IN DISTRIBUTED PUMPING SYSTEMS


In conventional systems, pumps are used to create the In traditional chilled water systems, pumps can be sized in
maximum pressure needed for the system’s most distant two ways. Either the primary pumps are sized for the full
consumer. Balancing and control valves are then used to system flow and maximum pressure loss in variable
restrict the flow that is delivered to the rest of the primary systems or they are sized for the full system flow
consumers that do not require the maximum head. If this and pressure loss out to the bypass in a primary/secondary
is not done, it will result in overflow. The pump duty point arrangement. Here the secondary pumps are sized for
will move to the right and the consumer that needs the full flow and the maximum pressure drop through the
maximum head will not receive it. Distributed pumping secondary loop. In distributed pumping, the primary
eliminates the flow-restricting balancing and control pumps are only sized for pressure loss through the bypass
valves and replaces them with pumps that produce only in the mechanical room and along with full system flow.
the locally required flow and head. This reduces the See Figure 2 for flow path of the primary pump.
pressure requirements for the entire system, thereby
reducing the pumping energy required to move the rated
flow throughout the chilled water network. The reduction
in pump energy also results in significant energy savings.
The chilled water systems will also operate closer to the
designed delta temperature of the system, increasing
chiller performance efficiency.
4

DN125 DN125
Flow 23.88 L/s Flow 23.88 L/s
30 m 25 m

1 2
CHILLER
CHILLER

PD 60 kPa

Grundfos distributed
Pumping design PD 24.5 kPa

Figure 2. Flow path of the primary pumps

What happens if the full system pressure is removed What about minimum flows through the chillers?
from the primary pumps? The first responsibility for the primary pumps in a
If the pressure loss for the full system is not required when distributed pumping arrangements is to ensure there is
selecting the primary pumps, pump size can be drastically minimum flow back to the chiller. The system utilises an
reduced compared to a variable primary arrangement. open, free-flowing de-coupler, so the primary pumps
In the case of primary variable secondary pumping simply bypass flow to maintain minimum flows. If the
arrangements, the primary pumps are sized for full system minimum flows are satisfied, the primary pumps will then
flow at constant speed. However, they only pump against work to balance themselves with the secondary pumps.
the pressure to reach the bypass line at the variable
secondary. The sizing of the primary pumps in distributed
pumping is done similarly with the exception of variable
speed. These pumps can operate at constant speed like
traditional primary pumps in a primary/secondary
arrangement, but to maximize energy savings and delta
temperature improvements, these pumps should be
variable speed.
5

SECONDARY PUMPS IN DISTRIBUTED PUMPING SYSTEMS What happens when the secondary pumps are
For systems utilising variable primary pumps, no secondary distributed?
pumps are required. In primary/secondary arrangements, When the pumps are distributed into the piping networks
the secondary pumps are sized for full system flow and in place of valves, a flow inhibitor is replaced by a flow
maximum pressure loss throughout the entire secondary initiator, which makes the system as “free-flowing” as
network. Balance valves are then used to set the flow possible. This process greatly reduces friction losses in the
requirements for each zone or AHU. Since valves are flow piping network, which means less horsepower is required
inhibitors, the pressure requirements for the secondary to pump the secondary side of the system.
pumping system increases each time this process takes
place in a network. This also increases pump horsepower Are the distributed pumps sized the same way as
requirements. traditional secondary pumps?
The secondary pumps in a distributed pump network are
located at each zone, specific to an AHU or a bank of fan-
coil units. If the system has multiple zones, it will require
multiple distributed pumps. See Figure 3 for the location
of the distributed pumps.

CHILLER

Figure 3. Locations of the distributed pumps


6

Since each zone requires its own pump, each pump should Will the pumps cross-flow into other zones?
be sized for the flow in its zone, taking into account friction Distributing the pumps in a chilled water network requires
loss through that AHU and the piping loop tracing back to removing the control valves and the balancing valves and
the de-coupler. See Figure 4. replacing them with a pump. Without a control valve in
place, the pump will be exposed to back-flow when it is not
What are the key points to consider when determining the operating. Because of this, a low resistance check valve is
flow and head for the pump? required for discharge on the sides of each distributed
The flow for the distributed pump is determined by the pump. This check valve will prevent back-flow in the
flow required for the specific zone it is supplying. The head system. See Figure 4 for the location of each check valve.
calculation should include loss through the AHU, check
valve, and the friction loss of the supply and return piping How is the distributed pumping system balanced if there
loop from the de-coupler to the pump. The piping’s friction are no balancing valves?
loss should be determined for the worst-case scenario – The pumps auto-balance the system. All that is required
maximum system flow. This means that friction loss in the during commissioning is to set maximum pump flow for
common supply and return line should be determined by each of the distributed pumps based on the maximum
using the total flow of all the distributed pumps if there is flow for the AHU/zone being serviced. Doing this ensures
more than one zone connected to the system. the system never runs out of balance and will not need
rebalancing after years of operation. The pumps will
continuously readjust to changes as equipment ages,
ensuring optimal operation throughout the entire lifetime
of the equipment.

DN125 DN125 DN125


Flow 23.88 L/s Flow 23.88 L/s Flow 19.1 L/s
30 m 25 m 10 m

1 2 3
CHILLER
CHILLER

PD 60 kPa

Grundfos distributed
Pumping design
PD 24.5 kPa

Figure 4. Piping loop for distributed pump.


7

What additional input is needed to size a distributed CONCLUSION


pumping system? Distributed pumping is an excellent way to improve the
Because distributed pumping delves further into overall efficiency of your chilled water system. By removing the
system design, more information is needed than for valves from the system and installing pumps in their place,
traditional pump selections. For these applications, a “free-flowing” system is created, reducing the overall
Grundfos requires schematic layouts and equipment system pressure. This pressure reduction also means less
schedules. The information needed in a schematic includes system horsepower is needed to operate the system,
pipe details (diameter and length), fitting details, and simultaneously addressing low delta temperature
number of risers. This information can be estimated but syndrome.
the more exact it is at the design stage, the more efficient
the system will operate. The flow and pressure drop for the
scheduled equipment (chillers, AHU, fan-coil units, etc.) is
also needed.

Key information:
1. Building schematic
2. P ipe schematic including pipe diameter and length.
As .dwg or pdf file.
3. Equipment schedule of: Chillers, Airhandling units,
Fan coil units, Conventional pumps
www.grundfos.com
Tel: +45 87 50 14 00
DK-8850 Bjerringbro
Poul Due Jensens Vej 7
GRUNDFOS Holding A/S
Trademarks displayed in this material, including but not limited to Grundfos and the Grundfos logo are registered trademarks owned by The Grundfos Group. All rights reserved. © 2022 Grundfos Holding A/S, all rights reserved.

You might also like