You are on page 1of 7

Title Drawing n° Rev.

AL SHABAB POWER STATION PHASE II


2x750 MW COMBINED CYCLE PROJECT
30610-G-G1101 0 3 4 5
Description Office Issued by Date

HRSG ELECTRICAL LOAD LIST IEE A. Poto 19/01/2017

LEGEND
N NORMAL SOURCE
POWER SOURCE

U U.P.S.

DC DIRECT CURRENT

E EMERGENCY SOURCE (DIESEL)

CS CONTINUOUS SERVICE

SS STAND-BY SERVICE
DUTY

IS INTERMITTENT SERVICE

DS DISCONTINUOUS SERVICE

D CONTROL DRIVE

MO MOTOR

EA ELECTRICAL ON-OFF ACTUATOR


TYPE

EAI ELECTRICAL ACTUATOR WITH INTERMEDIATE POSITION

L LINE FEEDER

EH ELECTRICAL HEATER

CMA ELECTRICAL CONTROL ACTUATOR

SBE EMERGENCY SOURCE (DIESEL) LOW VOLTAGE LOCAL MCC (SUBDISTRIBUTION BOARD)
IDENTIFICATION

SBL LOW VOLTAGE LOCAL COMBINED POWER & LOGIC SUBDISTRIBUTION BOARD
MCC

SBU LOW VOLTAGE UNINTERRUPTIBLE POWER SUBDISTRIBUTION BOARD

SBT DIRECT CURRENT SUBDISTRIBUTION BOARD

NOTES

- The List is issued for HRSG Unit 1A


- Unit tag shall change to 1B, 1C, 1D, 2A, 2B, 2C, 2D for Units 1B, 1C, 1D, 2A, 2B, 2C, 2D.

- Equipment that are common to two HRSGs shall have prefix 1AX, 1CX, 2BX, 2DX for Units 1A-1B, 1C-1D, 2A-
2B, 2C-2D and shall be fed from Unit 1A, 1C, 2B, 2D distribution boards.

Page 2 of 7
AL SHABAB POWER STATION PHASE II 10066A-9-V05-MOOZ-00001 Prepared A. Poto
DOC. No.
2 x 750 MW COMBINED CYCLE PROJECT 3061 0 - G - G1 101 Approved L. Bini
Checked R. Filipponi
HRSG ELECTRICAL LOAD LIST REVISION 5 DATE 19 Jan 2017
ACTUATOR
RATED RATED REQUIRED NOMINAL START-UP
TYPE OF POWER MAX POWER
TAG NUMBER DESCRIPTION P&ID Q'ty VOLTAGE POWER POWER CURRENT CURRENT DUTY TYPE FEEDED FROM NOTE Rev
VOLTAGE SOURCE CURRENT FACTOR
[kV] [kW] [kW] [A] [A]
[A]

REQUIRED POWER FOR


1B/1D/2A/2C-ECEC-01
BOARDS = 140 kW
OWNER LV SWGR
1A-EC-EC-01 L.V. SUB DISTRIBUTION BOARD 1 0,4 3 ph 50 Hz + N N 370,6 170 307,1 / / / CS / 4
1X-EK-EK-01A
REQUIRED POWER FOR
1C/2B/2D-ECEC-01 BOARDS
= 170 kW
FED BY L.V. SUB
REFER TO DOC. 30610-I-
LOCAL MOTOR STARTER OF CONDENSATE PREHEATER DISTRIBUTION BOARD
1A-EC-EC-03 30610-G-G0004 1 0,4 3 ph 50 Hz + N N 30 22 52 N.A. 332 0,89 CS L4 L0301 SINGLE LINE 3
RECIRCULATION PUMP A 1A-EC-EC-01 FROM UNIT
DIAGRAM
1A

FED BY L.V. SUB


REFER TO DOC. 30610-I-
LOCAL MOTOR STARTER CONDENSATE PREHEATER DISTRIBUTION BOARD
1A-EC-EC-04 30610-G-G0004 1 0,4 3 ph 50 Hz + N N 30 22 52 N.A. 332 0,89 SS L4 L0301 SINGLE LINE 3
RECIRCULATION PUMP B 1B-EC-EC-01 FROM UNIT
DIAGRAM
1B

FED BY LOCAL MOTOR COMPLETE OF SPACE


1A-AD-MP-001A CONDENSATE PREHEATER RECIRCULATION PUMP A 30610-G-G0004 1 0,4 3 ph 50 Hz N 30 22 52 N.A. 332 0,89 CS MO 3
STARTER 1A-EC-EC-03 HEATER

FED BY LOCAL MOTOR COMPLETE OF SPACE


1A-AD-MP-001B CONDENSATE PREHEATER RECIRCULATION PUMP B 30610-G-G0004 1 0,4 3 ph 50 Hz N 30 22 52 N.A. 332 0,89 SS MO 3
STARTER 1A-EC-EC-04 HEATER

1A-AD-HV-701 CONDENSATE PREHEATER INLET SHUT-OFF VALVE 30610-G-G0004 1 0,4 3 ph 50 Hz N 2,9 1,5 4,2 7,5 23 0,55 DS EA 3

1A-AA-HV-711 LP FEEDWATER INLET SHUT-OFF VALVE 30610-G-G0003 1 0,4 3 ph 50 Hz N 1,2 0,4 1,8 2,5 7,5 0,67 DS EA 3

1A-AA-HV-712 LP DRUM VENT SHUT-OFF VALVE 30610-G-G0003 1 0,4 3 ph 50 Hz N 0,6 0,3 1,45 1,89 4,6 0,46 DS EA 3

1A-AA-HV-713 LP SH DRAIN SHUT-OFF VALVE 30610-G-G0003 1 0,4 3 ph 50 Hz N 0,6 0,3 1,45 1,9 4,6 0,46 DS EAI 3

1A-AB-HV-503 LP SH MAIN STEAM SHUT-OFF VALVE 30610-G-G0003 1 0,4 3 ph 50 Hz N 3,0 1,7 4,5 6,5 30 0,67 DS EA 3

1A-AB-HV-504 LP SH MAIN STEAM BY-PASS SHUT-OFF VALVE 30610-G-G0003 1 0,4 3 ph 50 Hz N 0,5 0,2 0,86 1,2 3,3 0,56 DS EA 3

1A-AA-HV-718 LP SH STEAM TO DEAERATOR SHUT-OFF VALVE 30610-G-G0003 1 0,4 3 ph 50 Hz N 1,8 0,8 2,84 4,3 12 0,61 DS EA 3

1A-AA-HV-719 LP SH STEAM DRAIN SHUT-OFF VALVE 30610-G-G0003 1 0,4 3 ph 50 Hz N 1,0 0,4 1,25 2,1 6 0,71 DS EA 3

1A-AA-HV-731 HP ECONOMIZER INLET SHUT-OFF VALVE 30610-G-G0001 1 0,4 3 ph 50 Hz N 4,9 1,9 8 13 25 0,55 DS EA 3

1A-AA-HV-730 HP STEAM SPRAY WATER SHUT-OFF VALVE 30610-G-G0001 1 0,4 3 ph 50 Hz N 0,8 0,4 1,7 2,5 7,5 0,49 DS EA 3

1A-AA-HV-733 HP DRUM VENT SHUT-OFF VALVE 30610-G-G0001 1 0,4 3 ph 50 Hz N 1,2 0,5 3,1 3,9 9,8 0,43 DS EA 3

1A-AA-HV-734 HP SH-2 DRAIN SHUT-OFF VALVE 30610-G-G0001 1 0,4 3 ph 50 Hz N 0,6 0,1 1,45 2 4,6 0,46 DS EAI 3

1A-AA-HV-735 HP SH-3 DRAIN SHUT-OFF VALVE 30610-G-G0001 1 0,4 3 ph 50 Hz N 0,6 0,1 1,45 2 4,6 0,46 DS EAI 3

1A-AB-HV-501 HP SH MAIN STOP&CHECK SHUT-OFF VALVE 30610-G-G0001 1 0,4 3 ph 50 Hz N 28,8 11,6 27,5 57 130 0,73 DS EA 3

1A-AB-HV-502 HP SH MAIN STEAM STOP&CHECK VALVE BY-PASS 30610-G-G0001 1 0,4 3 ph 50 Hz N 1,0 0,4 1,8 2,5 7,5 0,55 DS EA 3

1A-AA-HV-737 HP SH MAIN STEAM DRAIN SHUT-OFF VALVE 30610-G-G0001 1 0,4 3 ph 50 Hz N 1,0 0,4 1,25 2,1 6 0,71 DS EA 3

1A-AA-HV-716 LP CONTINUOUS BLOW-DOWN VALVE 30610-G-G0006 1 0,4 3 ph 50 Hz N 0,6 0,1 1,45 2 4,6 0,46 DS EAI 3

1A-AA-HV-717 LP INTERMITTENT BLOW-OFF VALVE 30610-G-G0006 1 0,4 3 ph 50 Hz N 0,6 0,3 1,45 1,89 4,6 0,46 DS EAI 3

1A-AA-HV-739 HP CONTINUOUS BLOW-DOWN VALVE (TO LP DRUM) 30610-G-G0002 1 0,4 3 ph 50 Hz N 0,6 0,1 1,68 1,3 4 0,7 DS EAI 3

1A-AA-HV-740 HP INTERMITTENT BLOW-OFF VALVE 30610-G-G0006 1 0,4 3 ph 50 Hz N 3,6 0,16 5,6 12,1 19,5 0,43 DS EAI 3

1A-BA-HV-763 HRSG STACK DAMPER 30610-G-G0007 1 0,4 3 ph 50 Hz N 1,0 1 5,2 0,64 DS EA 3

Page 3 of 7
AL SHABAB POWER STATION PHASE II 10066A-9-V05-MOOZ-00001 Prepared A. Poto
DOC. No.
2 x 750 MW COMBINED CYCLE PROJECT 3061 0 - G - G1 101 Approved L. Bini
Checked R. Filipponi
HRSG ELECTRICAL LOAD LIST REVISION 5 DATE 19 Jan 2017
ACTUATOR
RATED RATED REQUIRED NOMINAL START-UP
TYPE OF POWER MAX POWER
TAG NUMBER DESCRIPTION P&ID Q'ty VOLTAGE POWER POWER CURRENT CURRENT DUTY TYPE FEEDED FROM NOTE Rev
VOLTAGE SOURCE CURRENT FACTOR
[kV] [kW] [kW] [A] [A]
[A]

COMMON DEAERATOR.
1AX-AE-HV-752 DEAERATOR VENT SHUT-OFF VALVE 30610-G-G0005 1 0,4 3 ph 50 Hz N 0,6 0,3 1,45 1,89 4,6 0,46 DS EAI AVAILABLE ONLY ON UNIT 1A , 3
IC, 2B AND 2D
COMMON DEAERATOR.
1AX-AE-HV-753 DEAERATOR DRAIN SHUT-OFF VALVE 30610-G-G0005 1 0,4 3 ph 50 Hz N 1,8 0,8 2,8 4,3 12 0,61 DS EA AVAILABLE ONLY ON UNIT 1A , 3
IC, 2B AND 2D
1A-BA-MS-101 HOIST FOR BLANKING PLATE HV-762 1 0,4 3 ph 50 Hz + N N 2,5 DS L4 3

HOIST FOR HRSG MAINTENANCE / 1 0,4 3 ph 50 Hz N 2,3 2,7 7 N.A. 30 0,84 DS L4 4


1A-HA-MS-100
TROLLEY MOTOR / 1 0,4 3 ph 50 Hz N 0,37 1 0,97 N.A. 4 0,79 DS L4 4
COMMON ELEVATOR.
1AX-EE-EAA-04 ELEVATOR BOARD / 1 0,4 3 ph 50 Hz + N N 55 30 55 N.A. N.A. 0,8 DS L4 AVAILABLE ONLY ON UNIT 1A , 4
IC, 2B AND 2D
1A-EE-EAA-01 FEEDING TO CEMS SHELTER 30610-I-I7006 1 0,4 3 ph 50 Hz N 24,3 9,8 N.A. N.A. N.A. N.A CS L4 3

1A-EE-EAA-02 FEEDING TO SWAS SHELTER 30610-I-I3022 1 0,4 3 ph 50 Hz N 21,1 10,2 N.A. N.A. N.A. N.A CS L4 3

1A EL-EAL-01 LIGHTING DISTRIBUTION PANEL / 1 0,4 3 ph 50 Hz + N N 25 18 N.A. N.A. N.A. N.A DS 3

1A-EC-EC-02 DIVERTER DAMPER SYSTEM DISTRIBUTION BOARD 30610-G-G2310 1 0,4 3 ph 50 Hz + N N 67,4 33,9 N.A. N.A. N.A. N.A CS L4 3

1B-EC-EC-02 DIVERTER DAMPER SYSTEM DISTRIBUTION BOARD 30610-G-G2310 1 0,4 3 ph 50 Hz + N N 67,4 33,9 N.A. N.A. N.A. N.A DS L4 4

1A-EE-EAA-05 MCC SHELTER / 1 0,4 3 ph 50 Hz + N N 10,5 5,5 N.A. N.A. N.A. N.A CS L4 3

DCS SYSTEM & MARSHALLING CABINET HRSG1A + GTC1A -


1A-HRSG-S-001 / 1 0,23 1 ph 50 Hz + N N 1 1 N.A. N.A. N.A. N.A CS L3 3
NORMAL POWER
DCS SYSTEM & MARSHALLING CABINET HRSG1A + GTC1A -
1A-HRSG-S-001 / 1 0,23 1 ph 50 Hz + N N 1 1 N.A. N.A. N.A. N.A DS L3 3
AUXILIARY POWER
DCS SYSTEM & MARSHALLING CABINET BOP-1XA - NORMAL FEEDER VALID ONLY FOR
1XA-BOP-S-001 / 1 0,23 1 ph 50 Hz + N N 1 1 N.A. N.A. N.A. N.A CS L3 3
POWER UNIT 1B
DCS SYSTEM & MARSHALLING CABINET BOP-1XA - AUX. FEEDER VALID ONLY FOR
1XA-BOP-S-001 / 1 0,23 1 ph 50 Hz + N N 1 1 N.A. N.A. N.A. N.A CS L3 3
POWER UNIT 1B
DCS SYSTEM & MARSHALLING CABINET BOP-2XA - NORMAL FEEDER VALID ONLY FOR
2XA-BOP-S-001 / 1 0,23 1 ph 50 Hz + N N 1 1 N.A. N.A. N.A. N.A CS L3 3
POWER UNIT 2B
DCS SYSTEM & MARSHALLING CABINET BOP-2XA - AUX. FEEDER VALID ONLY FOR
2XA-BOP-S-001 / 1 0,23 1 ph 50 Hz + N N 1 1 N.A. N.A. N.A. N.A CS L3 3
POWER UNIT 2B
DIVERTER DAMPER HYDRAULIC SYSTEM CONTROL PANEL
1A-EE-EAA-03 30610-G-G0007 1 0,23 1 ph 50 Hz N 0,5 0,5 N.A. N.A. N.A. N.A CS L3 3
(normal supply)

Page 4 of 7
AL SHABAB POWER STATION PHASE II 10066A-9-V05-MOOZ-00001 Prepared A. Poto
DOC. No.
2 x 750 MW COMBINED CYCLE PROJECT 3061 0 - G - G1 101 Approved L. Bini
Checked R. Filipponi
HRSG ELECTRICAL LOAD LIST REVISION 5 DATE 19 Jan 2017
ACTUATOR
RATED RATED REQUIRED NOMINAL START-UP
TYPE OF POWER MAX POWER
TAG NUMBER DESCRIPTION P&ID Q'ty VOLTAGE POWER POWER CURRENT CURRENT DUTY TYPE FEEDED FROM NOTE Rev
VOLTAGE SOURCE CURRENT FACTOR
[kV] [kW] [kW] [A] [A]
[A]

FED BY L.V. SUB


REFER TO DOC. 30610-I-
DISTRIBUTION BOARD
30610-G-G2310 1 0,4 3 ph 50 Hz + N N 67,4 33,9 61,2 / / / CS / L0301 SINGLE LINE 3
1A-EC-EC-01 FROM UNIT
DIAGRAM
1A
1A-EC-EC-02 DIVERTER DAMPER SYSTEM DISTRIBUTION BOARD
FED BY L.V. SUB
REFER TO DOC. 30610-I-
DISTRIBUTION BOARD
30610-G-G2310 1 0,4 3 ph 50 Hz + N N 67,4 33,9 61,2 / / / SS / L0301 SINGLE LINE 3
1B-EC-EC-01 FROM UNIT
DIAGRAM
1B

1A-BA-MA-001A DIVERTER DAMPER SEALING AIR FAN A 30610-G-G2310 1 0,4 3 ph 50 Hz N 18,5 18,5 32,8 N.A. 0,87 CS MO 4

1A-BA-MA-001B DIVERTER DAMPER SEALING AIR FAN B 30610-G-G2310 1 0,4 3 ph 50 Hz N 18,5 18,5 32,8 N.A. 0,87 SS MO 4

1A-BA-HV-765 DIVERTER DAMPER SEALING AIR SHUT-OFF DAMPER 30610-G-G2310 1 0,4 3 ph 50 Hz N 0,03 0,03 0,4 N.A. 0,43 DS EA 3

1A-BA-HV-766 DIVERTER DAMPER SEALING AIR SHUT-OFF DAMPER 30610-G-G2310 1 0,4 3 ph 50 Hz N 0,03 0,03 0,4 N.A. 0,43 DS EA 3

1A-BA-MP-002A DIVERTER DAMPER HYDRAULIC UNIT PUMP A 30610-G-G2310 1 0,4 3 ph 50 Hz N 15 15 26,7 N.A. 0,8 CS L4 3

1A-BA-MP-002B DIVERTER DAMPER HYDRAULIC UNIT PUMP B 30610-G-G2310 1 0,4 3 ph 50 Hz N 15 15 26,7 N.A. 0,8 SS L4 3
DIVERTER DAMPER DISTRIBUTION BOARD
-- 30610-G-G2310 0,23 1 ph 50 Hz N 0,3 0,3 0,2 N.A. 1 CS L3 5
ANTICONDENSATION HEATER AND ENCLOSURE LIGHTING
DIVERTER DAMPER HYDRAULIC SYSTEM CONTROL PANEL
1A-EE-EAA-03 30610-G-G0007 1 0,23 1 ph 50 Hz N 0,5 SS L3 3
(normal supply)

230 VAC UPS OWNER


1A-EU-EAU-01 UPS DISTRIBUTION BOARD 1 0,23 1 ph 50 Hz + N U 5 4,5 19,6 / / / CS / 3
DISTRIB. BOARD

1A-AA-PV-117 LP SH SAFETY VALVE (POWER ACTUATED) 30610-G-G0003 1 0,23 1 ph 50 Hz U 0,1 0,1 N.A. N.A N.A N.A DS L5 3

1A-AA-PV-321 HP SH SAFETY VALVE (POWER ACTUATED) 30610-G-G0001 1 0,23 1 ph 50 Hz U 0,1 0,1 N.A. N.A N.A N.A DS L5 3

1A-AA-LG-108 LP DRUM LOCAL LEVEL (GAUGE) - RIGHT SIDE 30610-G-G0003 1 0,23 1 ph 50 Hz U 0,3 CS L5 1

1A-AA-LG-109 LP DRUM LOCAL LEVEL (GAUGE) - LEFT SIDE 30610-G-G0003 1 0,23 1 ph 50 Hz U 0,3 CS L5 1

1A-AA-LI-112 LP DRUM LOCAL LEVEL (CONDUCTIVE) - RIGHT SIDE 30610-G-G0003 1 0,23 1 ph 50 Hz U 0,1 0,1 N.A. N.A N.A N.A CS L5 3

1A-AA-LG-308 HP DRUM LOCAL LEVEL (GAUGE) - RIGHT SIDE 30610-G-G0001 1 0,23 1 ph 50 Hz U 0,3 0,3 N.A. N.A N.A N.A CS L5 3

1A-AA-LG-309 HP DRUM LOCAL LEVEL (GAUGE) - LEFT SIDE 30610-G-G0001 1 0,23 1 ph 50 Hz U 0,3 0,3 N.A. N.A N.A N.A CS L5 3

1A-AA-LI-312 HP DRUM LOCAL LEVEL (CONDUCTIVE) - RIGHT SIDE 30610-G-G0001 1 0,23 1 ph 50 Hz U 0,1 0,1 N.A. N.A N.A N.A CS L5 3
COMMON DEAERATOR. THIS
LEVEL INDICATOR IS FED
1AX-AE-LG-400 DEAERATOR LOCAL LEVEL (GAUGE) 30610-G-G0005 1 0,23 1 ph 50 Hz U 0,5 CS L5 1
FROM 1A-EUEAU-01 BOARD
ONLY.

1A-EE-EAA-03 DIVERTER DAMPER HYDRAULIC SYSTEM CONTROL PANEL 30610-G-G0007 1 0,23 1 ph 50 Hz U 0,5 0,2 N.A N.A N.A N.A CS L5 3

1A-EE-EAA-03 DIVERTER DAMPER HYDRAULIC SYSTEM CONTROL PANEL 30610-G-G0007 1 0,23 1 ph 50 Hz U 0,5 DS L5 3

1A-EL-EAL-03 FEEDING TO STACK AVIATION WARNING LIGHT PANEL / 1 0,23 1 ph 50 Hz + N U 1,3 1,3 N.A. N.A N.A N.A CS L5 3

1A-HRSG-S-001 DCS SYSTEM & MARSHALLING CABINET HRSG1A + GTC1A / 1 0,23 1 ph 50 Hz + N U 1 1 N.A. N.A N.A N.A CS L5 3

FEEDER VALID ONLY FOR


1XA-BOP-S-001 DCS SYSTEM & MARSHALLING CABINET BOP-1XA / 1 0,23 1 ph 50 Hz + N U 1 1 N.A. N.A N.A N.A CS L5 3
UNITS 1B
FEEDER VALID ONLY FOR
2XA-BOP-S-001 DCS SYSTEM & MARSHALLING CABINET BOP-2XA / 1 0,23 1 ph 50 Hz + N U 1 1 N.A. N.A N.A N.A CS L5 3
UNITS 2B

Page 5 of 7
AL SHABAB POWER STATION PHASE II 10066A-9-V05-MOOZ-00001 Prepared A. Poto
DOC. No.
2 x 750 MW COMBINED CYCLE PROJECT 3061 0 - G - G1 101 Approved L. Bini
Checked R. Filipponi
HRSG ELECTRICAL LOAD LIST REVISION 5 DATE 19 Jan 2017
ACTUATOR
RATED RATED REQUIRED NOMINAL START-UP
TYPE OF POWER MAX POWER
TAG NUMBER DESCRIPTION P&ID Q'ty VOLTAGE POWER POWER CURRENT CURRENT DUTY TYPE FEEDED FROM NOTE Rev
VOLTAGE SOURCE CURRENT FACTOR
[kV] [kW] [kW] [A] [A]
[A]

FED BY L.V. SUB


DISTRIBUTION BOARD
1A-EE-EAA-01 CEMS SHELTER 1 0,4 3 ph 50 Hz + N N 24,3 9,8 17,7 / / / CS / 3
1A-EC-EC-01 FROM UNIT
1A
1A-BA-AT-521 CO CONTENT ANALYZER INTO FLUE GASES AT CHIMNEY 30610-I-I7006 1 0,23 1 ph 50 Hz N 0,06 0,06 N.A. N.A N.A N.A CS L3 3

1A-BA-AT-522 O2 % CONTENT ANALYZER INTO FLUE GASES AT CHIMNEY 30610-I-I7006 1 0,23 1 ph 50 Hz N 0,06 0,06 N.A. N.A N.A N.A CS L3 3

1A-BA-AT-523 SO2 CONTENT ANALYZER INTO FLUE GASES AT CHIMNEY 30610-I-I7006 1 0,23 1 ph 50 Hz N 0,06 0,06 N.A. N.A N.A N.A CS L3 3

1A-BA-AT-524 NOx CONTENT ANALYZER INTO FLUE GASES AT CHIMNEY 30610-I-I7006 1 0,23 1 ph 50 Hz N 0,15 0,15 N.A. N.A N.A N.A CS L3 3

/ ANALYZER LINE HEATING 30610-I-I7006 1 0,4 3 ph 50 Hz N 2,1 2,1 N.A. N.A N.A N.A CS L4 3
/ AUXILIARIES (LIGHTING, SOCKET, FANS, COOLER) 30610-I-I7006 1 0,23 1 ph 50 Hz N 11,2 3,8 N.A. N.A N.A N.A DS L3 3
SP-AL CEMS SAMPLE PROBE 30610-I-I7006 1 230 1 ph 50 Hz N 0,44 0,44 N.A. N.A N.A N.A CS L3 3
SC1.1 CEMS SAMPLE COOLER 30610-I-I7006 1 230 1 ph 50 Hz N 0,3 0,3 N.A. N.A N.A N.A CS L3 3
P1.1 CEMS SAMPLE PUMP 30610-I-I7006 1 230 1 ph 50 Hz N 0,2 0,2 N.A. N.A N.A N.A CS L3 3

/ CEMS SHELTER CONDITIONING SYSTEM A 30610-I-I7006 1 0,23 1 ph 50 Hz N 2,6 2,6 N.A. N.A N.A N.A CS L3 3

/ CEMS SHELTER CONDITIONING SYSTEM B 30610-I-I7006 1 0,23 1 ph 50 Hz N 2,6 2,6 N.A. N.A N.A N.A SS L3 3

/ AVAILABLE SPARE 30610-I-I7006 1 0,23 1 ph 50 Hz N 4,6 4,6 N.A. N.A N.A N.A SS L3 3

FED BY L.V. SUB


DISTRIBUTION BOARD
1A-EE-EAA-02 SWAS SHELTER 30610-G-G0008 1 0,4 3 ph 50 Hz + N N 21,1 10,2 18,4 / / / CS 3
1A-EC-EC-01 FROM UNIT
1A
1A-AA-AT-361 H.P. DRUM WATER pH 30610-I-I3022 1 0,23 1 ph 50 Hz N 0,015 0,015 N.A. N.A N.A N.A CS L3 3

1A-AA-AT-362 H.P. DRUM WATER SPECIFIC CONDUCTIVITY 30610-I-I3022 1 0,23 1 ph 50 Hz N 0,015 0,015 N.A. N.A N.A N.A CS L3 3

1A-AA-AT-363 H.P. MAIN STEAM SILICA 30610-I-I3022 1 0,23 1 ph 50 Hz N 0,1 0,1 N.A. N.A N.A N.A CS L3 3

1A-AA-AT-364 H.P. MAIN STEAM CATION CONDUCTIVITY 30610-I-I3022 1 0,23 1 ph 50 Hz N 0,015 0,015 N.A. N.A N.A N.A CS L3 3

1A-AA-AT-161 L.P. DRUM WATER pH 30610-I-I3022 1 0,23 1 ph 50 Hz N 0,015 0,015 N.A. N.A N.A N.A CS L3 3

1A-AA-AT-162 L.P. DRUM WATER SPECIFIC CONDUCTIVITY 30610-I-I3022 1 0,23 1 ph 50 Hz N 0,015 0,015 N.A. N.A N.A N.A CS L3 3

1A-AA-AT-163 L.P. MAIN STEAM SILICA 30610-I-I3022 1 0,23 1 ph 50 Hz N 0,1 0,1 N.A. N.A N.A N.A CS L3 3

1A-AA-AT-164 L.P. MAIN STEAM CATION CONDUCTIVITY 30610-I-I3022 1 0,23 1 ph 50 Hz N 0,015 0,015 N.A. N.A N.A N.A CS L3 3

1A-AD-AT-165 CONDENSATE PREHEATER OUTLET DISSOLVED OXYGEN 30610-I-I3022 1 0,23 1 ph 50 Hz N 0,015 0,015 N.A. N.A N.A N.A CS L3 3
COMMON DEAERATOR. SAMPLE
DEAERATOR OUTLET (BFW PUMP SUCTION) DISSOLVED
1AX-AE-AT-461 30610-I-I3022 1 0,23 1 ph 50 Hz N 0,015 0,015 N.A. N.A N.A N.A CS L3 AVAILABLE ONLY ON UNIT 1A , IC, 2B 3
OXYGEN AND 2D
COMMON DEAERATOR. SAMPLE
1AX-AE-AT-462 DEAERATOR OUTLET (BFW PUMP SUCTION) pH 30610-I-I3022 1 0,23 1 ph 50 Hz N 0,015 0,015 N.A. N.A N.A N.A CS L3 AVAILABLE ONLY ON UNIT 1A , IC, 2B 3
AND 2D
COMMON DEAERATOR. SAMPLE
DEAERATOR OUTLET (BFW PUMP SUCTION) SPECIFIC
1AX-AE-AT-463 30610-I-I3022 1 0,23 1 ph 50 Hz N 0,015 0,015 N.A. N.A N.A N.A CS L3 AVAILABLE ONLY ON UNIT 1A , IC, 2B 3
CONDUCTIVITY AND 2D
COMMON DEAERATOR. SAMPLE
DEAERATOR OUTLET (BFW PUMP SUCTION) CATION
1AX-AE-AT-464 30610-I-I3022 1 0,23 1 ph 50 Hz N 0,015 0,015 N.A. N.A N.A N.A CS L3 AVAILABLE ONLY ON UNIT 1A , IC, 2B 3
CONDUCTIVITY AND 2D

Page 6 of 7
AL SHABAB POWER STATION PHASE II 10066A-9-V05-MOOZ-00001 Prepared A. Poto
DOC. No.
2 x 750 MW COMBINED CYCLE PROJECT 3061 0 - G - G1 101 Approved L. Bini
Checked R. Filipponi
HRSG ELECTRICAL LOAD LIST REVISION 5 DATE 19 Jan 2017
ACTUATOR
RATED RATED REQUIRED NOMINAL START-UP
TYPE OF POWER MAX POWER
TAG NUMBER DESCRIPTION P&ID Q'ty VOLTAGE POWER POWER CURRENT CURRENT DUTY TYPE FEEDED FROM NOTE Rev
VOLTAGE SOURCE CURRENT FACTOR
[kV] [kW] [kW] [A] [A]
[A]

1A-AA-XY-581 HP DRUM WATER SAMPLE SOLENOID VALVE 30610-G-G0008 1 0,23 1 ph 50 Hz N DS 3

1A-AA-XY-582 HP SATURATED STEAM SAMPLE SOLENOID VALVE 30610-G-G0008 1 0,23 1 ph 50 Hz N DS 3

1A-AA-XY-583 HP SH MAIN STEAM SAMPLE SOLENOID VALVE 30610-G-G0008 1 0,23 1 ph 50 Hz N DS 3

1A-AA-XY-587 LP DRUM WATER SAMPLE SOLENOID VALVE 30610-G-G0008 1 0,23 1 ph 50 Hz N DS 3

1A-AA-XY-588 LP SATURATED STEAM SAMPLE SOLENOID VALVE 30610-G-G0008 1 0,23 1 ph 50 Hz N DS 3

1A-AA-XY-589 LP SH MAIN STEAM SAMPLE SOLENOID VALVE 30610-G-G0008 1 0,23 1 ph 50 Hz N DS 3

1A-AD-XY-591 CONDENSATE PREHEATER OUTLET SAMPLE SOLENOID VALVE 30610-G-G0008 1 0,23 1 ph 50 Hz N DS 3

1AX-AA-XY-592 DEAERATOR OUTELT SAMPLE SOLENOID VALVE 30610-G-G0008 1 0,23 1 ph 50 Hz N DS 3

/ AUXILIARIES (LIGHTING, SOCKET, FANS, COOLER) 30610-I-I3022 1 0,23 1 ph 50 Hz N 7,69 4,01 N.A. N.A N.A N.A DS L3 3
CH1.1 WATER COOLED WATER CHILLER 30610-I-I3022 1 0,23 1 ph 50 Hz N 3,25 3,25 N.A. N.A N.A N.A CS L3 3

/ SWAS SHELTER CONDITIONING SYSTEM A 30610-I-I3022 1 0,23 1 ph 50 Hz N 2,6 2,6 N.A. N.A N.A N.A CS L3 3

/ SWAS SHELTER CONDITIONING SYSTEM B 30610-I-I3022 1 0,23 1 ph 50 Hz N 2,6 2,6 N.A. N.A N.A N.A SS L3 3

/ AVAILABLE SPARE 30610-I-I3022 1 0,23 1 ph 50 Hz N 4,6 4,6 N.A. N.A N.A N.A SS L3 3

OWNER EMERGENCY
1 0,4 3 ph 50 Hz + N E 6,5 5,6 8,1 / / 1 DS / 4
DIESEL DISTRIB. BOARD

1A-EL-EAL-01 LIGHTING DISTRIBUTION PANEL Required power calculated


FED BY L.V. SUB
considering Lighting Fixtures,
DISTRIBUTION BOARD
1 0,4 3 ph 50 Hz + N N 25 18 26,2 / / 1 DS / Nr. 1 Receptacle 230V-16A 4
1A-EC-EC-01 FROM UNIT
and Nr. 1 Receptacle 400V-
1A
16A

ESSENTIAL LIGHTING 1 0,23 1 ph 50 Hz E 5 DS 1


FOR DETAIL REFER TO
NORMAL/EMERGENCY LIGHTING 1 0,4 3 ph 50 Hz + N N 10 DS L4 1
DOCUMENT 30610-I-L0304
FEEDING TO POWER SOCKET 16 A DISTRIBUTION 1 0,4 3 ph 50 Hz + N N 15 DS L4 1

FROM OWNER CENTRAL


CONTROL ROOM
CEMS DAHS OPERATOR INTERFACE - COMMON TO BOTH
1 0,23 1 ph 50 Hz N CS L5 DISTRIBUTION PANEL (ONE
HRSG's
STATION COMMON TO 8
HRSG's)

REFERENCE DOCUMENTS:
- 10066A-9-V05-MBPR-00090 (30610-I-L0301) - HRSG SINGLE LINE DIAGRAM
- 10066A-9-V05-MBPR-00078 (30610-I-L0304) - LIGHTING SINGLE LINE DIAGRAM

Page 7 of 7