Introduction
1. Thanks for using TECO AP-ENBD expansion card. To learn more about the product, please
carefully read the manual before using it.
Function Introduction
Auto detection of 10/100Mbps transmission rate
Support MODBUS TCP protocol
Point-to-point data exchange function(The maximum for data exchange is 256 Bytes)
Function Specification
Network interface
Item Specification
UI RJ-45
Port number 1 PORT
Transmission method IEEE802.3
Cable Category 5e
Transmission rate 10/100Mbps Auto/Defect
Network protocol ICMP,IP,TCP,UDP,DHCP,MODBUS TCP
Indicator Description
Name Indicator color Function
100M indicator Orange Shows the network connection condition
LINK indicator Green Shows the network communication condition
Connection Configuration
Power off the AP Basic unit, remove the cover of the AP expansion card and plug in ENBD
expansion card. Connect the ENBD expansion card and the router or HUB with the cable, and
then connect the PC and the router. Power on, if the indicator of ENBD network interface is ON,
it indicates the connection is correct.
You could also connect AP-ENBD and the network interface on PC with a cable.
Network Configuration on PC
Set the local IP address in the segment of 192.168.0.XXX, which must be different from
the IP address of ENBD.
Please check whether it is connected with the network connection interface.
Network Configuration on PC is finished.
Configuration on ENBD
The default IP address of ENBD is 192.168.0.3. Please confirm it by inputting 192.168.0.3 in the
browser on PC.
Key in the default user name admin and password admin to log in.
Please set the baud rate as 19200,DATA BITS=8,Data Parity = None, Stop Bits =2, all others
shall keep the default value.
MODBUS TCP protocol *Note, make sure Server Listening Port = 502;
MODBUS protocol, make sure Server Listening Port = 5000;
To modify the IP address, please do remember it and make sure it is within the same segment with
the PC IP address.
Apply the modification and reboot.
Configuration on ENBD is finished.
Use AP-LINK
*Note: For MODBUS TCP protocol, the BUFF sent by MASTER shall be 256BYTE in
maximum, and BUFF received by MASTER shall be 171BYTE in maximum.