1. GENERAL DATA
Piping Class GRE GRE
Diameter 4”/6”/8”/10” GRE 6”/8”GRE
Pipe Length ( Refer Note-3)
Fluid Water Water
Service Fire Water Fire Water
2. DESIGN DATA
Min – 18 barg
Max – shall be selected to
Design pressure Min / Max, 18 bar g
accommodate surge pressure of
19 barg (Refer Note -5)
Design temperature Min / Max, C 0
5/82 C 5/82 C
Fluid normal operating pressure min/Max 2.5 / 12.5 barg
Fluid operating Temperature 0C - min/Nor/Max 20/40/60 20/40/60
Average Fluid Velocity (m/s) 3.0 m/s
Construction philosophy Under ground for 4”/6”/8”/10”” Under ground for 6”/8”
20450 m3 /day
Note:
1. Value will be finalized after final hydraulics calculation performed.
2. As pigging is envisaged only during hydro-testing, commissioning and decommissioning stages by using
soft pigs and not during the normal operation. Provision for temporary pigging shall be considered.
3. The pipe length shall be estimated by VENDOR based on Conceptual layout and Underground Piping
layout drawings & Site survey.
4. Pressure class shall be selected considering the surge pressure of 19 barg.
5. Fire water network design pressure is 18 barg, However the maximum surge of 19 barg, shall be
considered for thickness calculation and select GRE pipe accordingly