CONTRACTOR: SEPCOIII OWNER: LUCKY ELECTRIC CONSULTANT: FICHTNER

ELECTRIC POWER POWER COMPANY LIMITED GMBH & CO KG


CONSTRUCTION
CO.,LTD.

BOP control logic test card

NAME LEPCL660MWCFPP,Karachi PHASE TRIAL-RUN

PROFESSION I&C NAME system logic Test card

NO. CONTENT Conclusion

1 _______________pump/fan

2 _______________valve

3 ____________ standby/back-up drive start

4 _______________ start sequence

5 _______________ stop sequence

Issued By SEPCOIII COMM Consultant/Owner

Signature

Date
CONTENT : pump/fan
NO. CONTENT Conclusion
Start Permissive

1 or
and

Stop Permissive

2
and

Auto start

and
3
or

Auto stop

and
4
or

Emergency start
5
and or
Emergency stop

and
6
or

Issued By SEPCOIII COMM Consultant/Owner


Signature
Date
CONTENT : valve
NO. CONTENT Conclusion
Open Permissive

1 or
and

Close Permissive

2
and

Auto open

and
3
or

Auto close

and
4
or

Emergency open

5 and
or
Emergency close

and
6
or

Issued By SEPCOIII COMM Consultant/Owner


Signature
Date
CONTENT : Standby/back-up pump/fan
NO. CONTENT Conclusion
Start Permissive

1 or
and

Stop Permissive

2
and

Auto start

and
3
or

Auto stop

and
4
or

Emergency start

5 and
or
Emergency stop

and
6
or

Issued By SEPCOIII COMM Consultant/Owner


Signature
Date
CONTENT : SWRO B start Permissive

NO. CONTENT Conclusion

Start Permissive

SWRO cartridge filter B intake on-off valve In auto(10GCF11AA001)

SWRO HP pump B outlet on-off valve in auto (10GCF21AA101)

SWRO device B permeate discharge on-off valve in auto(10GCF31AA011)

SWRO device B reject valve in auto (10GCF34AA027)

SWRO reinforcing pump B in auto(10GCF37AP001)

SWRO HP pump B in auto (10GCF21AP001)

SWRO device B flushing intake ON-OFF valve in auto (10GCF10AA013)

SWRO low pressure brushing pump in auto (10GCP06AP001)

SWRO SEL REDUCTANT METER PUMP A (10GCQ22AP001)


and
REDUCTANT METER PUMP A IN AUTO (10GCQ22AP001)
OR
SWRO SEL REDUCTANT METER PUMP B (10GCQ23AP001)
1 and
and
METER PUMP B IN AUTO (10GCQ23AP001)

SWRO2 SEL UF WTR PMP A (10GCB60AP001)


and OR
UF CPER BST PMP A IN AUTO (10GCB60AP001)

SWRO 2 SEL UF WTR PMP B (10GCB61AP001)


and
UF CPER BST PMP B IN AUTO (10GCB61AP001)

SWRO 2 SEL UF WTR PMP C (10GCB62AP001)


and
UF CPER BST PMP C IN AUTO (10GCB62AP001)

SWRO SEL INHIBIT METER PUMP A (10GCQ26AP001)


and
INHIBIT METER PMP A IN AUTO (10GCQ26AP001)

SWRO SEL INHIBIT METER PUMP B (10GCQ27AP001) OR


and
INHIBIT METER PMP B IN AUTO (10GCQ27AP001)

Step n

n+1 action

condition

Issued By SEPCOIII COMM Consultant/Owner

Signature

Date
CONTENT : SWRO B RUN SEQUENCE
Step 1

SWRO FILTER B INTAKE VALVE(10GCF11AA001)

SWRO HP PUMP B OUTLET VALVE OP (10GCF21AA101)

SWRO2 DRN DIR OP(SWRO2-DRN-DIR)


action
SWRO B PERMATE DISCHARGE VALVE (10GCF31AA011)

SWRO B REJECT VALVE OP (10GCF34AA027)

3 SWRO B TANK INL VALVE OP (SWRO2-TANK-INL)

SWRO FILTER B INTAKE VALVE(10GCF11AA001XB01) OPEND

SWRO HP PUMP B OUTLET VALVE (10GCF21AA101XB01) OPEND

SWRO2 DRN DIR OP


condition
SWRO B PERMATE DISCHARGE VALVE (10GCF31AA011XB01) OPEND

SWRO B REJECT VALVE (10GCF34AA027YQ01) OPEND

SWRO B TANK INL VALVE(SWRO2-TANK-INL)

Step 2

REDUCTANT METER PUMP A START (10GCQ22AP001)


action

condition REDUCTANT METER PUMP (10GCQ22AP001XB01) START

Step 3
4
action UF PERMIATE BOOST PUMP A START (10GCB60AP001)

condition UF PERMIATE BOOST PUMP A(10GCB60AP001XB01) RUN

STEP 4

action SWRO REINFORC PUMP B START(10GCF37AP001)

SWRO BOOST PUMP B OUTLET VALVE OP(10GCF37AA026)

SWRO REINFORC PUMP B (10GCF37AP001XB01) RUN


condition
SWRO BOOST PUMP B OUTLET VALVE(10GCF37AA026XB01) OPEND

STEP5

SWRO2 DRN DIR OP(SWRO2-DRN-DIR)


action
5 INHIBITER METER PUMPA START(10GCQ26AP001)

SWRO B HP PUMP B OP (10GCF21AP001)

SWRO2 DRN DIR CL (SWRO2-DRN-DIR-SCL) CLOSED

condition INHIBITER METER PUMPA RUN (10GCQ26AP001XB01)

SWRO B HP PUMP B RUN (10GCF21AP001XB01)

STEP6
action
SWRO B PERMATE DISCHARGE VALVE(10GCF31AA011)

condition SWRO B PERMATE DISCHARGE VALV (10GCF31AA011XB02)CLOSED

Step n

n+1 action

condition

Issued By SEPCOIII COMM Consultant/Owner

Signature
Date
CONTENT : SWRO B STOP SEQUENCE
Step 1

SWRO FILTER B INTAKE VALVE (10GCF11AA001)

SWRO HP PUMP B OUTLET VALVE OP (10GCF21AA101)

SWRO B REJECT VALVE OP (10GCF34AA027)

SWRO B TANK INL VALVE OP (SWRO2-TANK-INL)

action REDUCTANT METER PUMP A START (10GCQ22AP001)

UF PERMIATE BOOST PUMP START (10GCB60AP001)

SWRO REINFORC PUMP B START(10GCF37AP001)

INHIBITOR METER PUMP A START(10GCQ26AP001)


1 SWRO BOOST PUMP B OUTLET VALVE OP(10GCF37AA026)

SWRO FILTER B INTAKE VALVE(10GCF11AA001XB01) OPEND

SWRO HP PUMP B OUTLET VALVE (10GCF21AA101XB01) OPEND

SWRO B REJECT VALVE OP(10GCF34AA027YQ01) OPEND

SWRO B TANK INL VALVE (SWRO2-TANK-INL)

condition REDUCTANT METER PUMP A START (10GCQ22AP001XB01)

UF PERMIATE BOOST PUMP (10GCB60AP001XB01) RUN

SWRO REINFORC PUMP B (10GCF37AP001XB01) RUN

INHIBITOR METER PUMP A RUN (10GCQ26AP001XB01)

SWRO BOOST PUMP B OUTLET VALVE(10GCF37AA026XB01) OPEND

Step 2

SWRO REINFORC PUMP B(10GCF37AP001)


2
action SWRO BOOST PUMP B OUTLET VALVE OP(10GCF37AA026)

SWRO REINFORC PUMP B STOP (10GCF37AP001XB02)


condition
SWRO BOOST PUMP B OUTLET VALVE(10GCF37AA026XB02) CLOSED

Step 3

3 action UF PERMIATE BOOST PUMP (10GCB60AP001)

condition UF PERMIATE BOOST PUMP (10GCB60AP001XB02) STOP

STEP 4

4 action INHIBITOR METER PUMP A (10GCQ26AP001)

condition INHIBITOR METER PUMP A STOP (10GCQ26AP001XB02)

action STEP5

5 action REDUCTANT METER PUMP A (10GCQ22AP001)

condition REDUCTANT METER PUMP A (10GCQ22AP001XB02) STOP

STEP6

6 action SWRO FILTER B INTAKE VALVE (10GCF11AA001)

condition SWRO FILTER B INTAKE VALVE (10GCF11AA001XB02) CLOSED

STEP7

SWRO B PERMATE DISCHARGE VALVE (10GCF31AA011)


action
7 SWRO B FLUSH INTAKE VALVE (10GCF10AA013)

SWRO B PERMATE DISCHARGE VALVE (10GCF31AA011XB01)OPEND


condition
SWRO B FLUSH INTAKE VALVE (10GCF10AA013XB01)OPEND
STEP8

8 action SWRO L PRESS BRUSH PUMP(10GCP06AP001)

condition SWRO L PRESS BRUSH PUMP(10GCP06AP001XB01) RUN

STEP9

SWRO REINFORC PUMP B START(10GCF37AP001)


action
9 SWRO BOOST PUMP B OUTLET VALVE OP(10GCF37AA026)

SWRO REINFORC PUMP B (10GCF37AP001XB01) RUN


condition
SWRO BOOST PUMP B OUTLET VALVE(10GCF37AA026XB01) OPEND

STEP10

SWRO REINFORC PUMP B (10GCF37AP001)

action SWRO L PRESS BRUSH PUMP(10GCP06AP001)

10 SWRO BOOST PUMP B OUTLET VALVE OP(10GCF37AA026)

SWRO REINFORC PUMP B (10GCF37AP001XB02) STOP

condition SWRO L PRESS BRUSH PUMP(10GCP06AP001XB02) STOP

SWRO BOOST PUMP B OUTLET VALVE(10GCF37AA026XB02) CLOSED

STEP11

SWRO HP PUMP B OUTLET VALVE OP (10GCF21AA101)

SWRO B PERMATE DISCHARGE VALVE (10GCF31AA011)

action SWRO B REJECT VALVE OP (10GCF34AA027)


11
SWRO B TANK INL VALVE OP (SWRO2-TANK-INL)

SWRO B FLUSH INTAKE VALVE (10GCF10AA013)

SWRO HP PUMP B OUTLET VALVE (10GCF21AA101XB02) CLOSED


condition
SWRO B PERMATE DISCHARGE VALVE (10GCF31AA011XB02)

SWRO B REJECT VALVE OP(10GCF34AA027YQ01) CLOSED

SWRO B TANK INL VALVE CLOSED

SWRO B FLUSH INTAKE VALVE (10GCF10AA013XB02)CLOSED

Step n

n+1 action

condition

Issued By SEPCOIII COMM Consultant/Owner

Signature

Date
CONTENT : SWRO B FLUSH SEQUENCE
Step 1

SWRO B PERMATE DISCHARGE VALVE (10GCF31AA011)

action SWRO B REJECT VALVE OP (10GCF34AA027)

1 SWRO B FLUSH INTAKE VALVE (10GCF10AA013)

SWRO B PERMATE DISCHARGE VALVE (10GCF31AA011XB01) OPEND

condition SWRO B REJECT VALVE OP(10GCF34AA027YQ01) OPEND

SWRO B FLUSH INTAKE VALVE (10GCF10AA013XB01) OPEND

Step 2
2
SWRO L PRESS BRUSH PUMP(10GCP06AP001)
action

condition SWRO L PRESS BRUSH PUMP(10GCP06AP001XB01) RUN

Step 3

SWRO REINFORC PUMP B START(10GCF37AP001)


3 action
SWRO BOOST PUMP B OUTLET VALVE OP(10GCF37AA026)

SWRO REINFORC PUMP B (10GCF37AP001XB01) RUN


condition
SWRO BOOST PUMP B OUTLET VALVE(10GCF37AA026XB01) OPEND

STEP 4

SWRO REINFORC PUMP B START(10GCF37AP001)


action
SWRO L PRESS BRUSH PUMP(10GCP06AP001)
4
SWRO BOOST PUMP B OUTLET VALVE OP(10GCF37AA026)

SWRO REINFORC PUMP B (10GCF37AP001XB02) STOP

condition SWRO L PRESS BRUSH PUMP(10GCP06AP001XB02) STOP

SWRO BOOST PUMP B OUTLET VALVE(10GCF37AA026XB02) CLOSED

STEP5

SWRO B PERMATE DISCHARGE VALVE (10GCF31AA011)


action
SWRO B REJECT VALVE OP (10GCF34AA027)

5 SWRO B FLUSH INTAKE VALVE (10GCF10AA013)

SWRO B PERMATE DISCHARGE VALVE (10GCF31AA011XB02) CLOSE

condition SWRO B REJECT VALVE OP(10GCF34AA027YQ01) CLOSED

SWRO B FLUSH INTAKE VALVE (10GCF10AA013XB02) CLOSED

Step n

n+1 action

condition

Issued By SEPCOIII COMM Consultant/Owner

Signature

Date
CONTENT : SWRO B EMERGINCY STOP
NO. CONTENT Conclusion

Start Permissive

SWRO ALL EMG STOP ( SWRO-ALL-EMG-STOP) OR

SWRO2 SEL UF PMP STOP (SWRO2-SEL-UF-PMP-SP)

SWRO REINFORCING PUMP B STOP (10GCF37AP001XB02)

SWRO HP PUMP B TRIP (10GCF21AP001-TRIP)


1
SWRO BST PUMP B O. PRESS 0-100 BAR(10GCF37CP104) OR AND
OR
SWRO INTAKE HEADER PRS 0-6 BAR(10GCB60CP101)

SWRO H PRS PMP B INL LOW PRS (10GCF21CP001)

ENER REC B H PRS REJECT IN FLOW 0-35t/h 10GCF31CF101) OR

SWRO H PRS B PMPO FLOW 0-250t/h (10GCF21CF101)

SWRO1 ST RUN (SWRO1-ST-RUNNING)

Step n

n+1 action

condition

Issued By SEPCOIII COMM Consultant/Owner

Signature

Date