You are on page 1of 35

NAME LT PANEL-1

FED FROM 630 KVA TRANSFORMER


LOCATION TRANSFORMER YARD
CIRCUIT
FEEDER SPN/ TPN
DB NO.
INCOMER : TPN
OUTGOING :

DISTRIBUTION PANEL-1(ST STAND) TPN

DISTRIBUTION PANEL-2(OFFICES AND


TPN
SHOPS)
APFCR TPN
TPN
TPN

MAX. DEMAND (3 PH) 815.384 KW AT 0.8 DIVERS


Consultant :
Type of Meter (Rating of Incomer):
MER
D
RATING-AMPS FAULT
PVC/XLPE
MCCB DUTY Voltage Drop Length
MCB
ACB KA XLPE/SWA/LSF
1000 35 XLPE

315 35 XLPE 0.18 120

630 35 XLPE 0.09 80


250 35 XLPE 0.30 100
160 35 XLPE 0.45 100
250 35 XLPE 0.21 100

W AT 0.8 DIVERSITY TOTAL CONNECTED LOAD


+
(1) Upto 60 A (2) Upto 100 A
(1 Phase) (3 Phase)

#N/A
CABLE SIZE
CURRENT
2/4 X 2/3/4C CONNECTED DIVERSIFIED AFTER
LOAD LOAD DERATING
1C mm2 mm2
3x240 1019.23 815.38 1402.46

300 214.44 171.55 295.07

2x300 384.00 307.20 528.38


150 135.90 108.72 187.00
95 108.90 87.12 149.85
240 175.99 140.79 242.16

D LOAD 1019.23

(3) 125 - 160 A


PROPOSED TYPE & NO. OF KWH METERS
CALCULATED
VOLTAGE Permissable 1-PH 3-PH 3-PH LV/HV
Voltage Drop CT
DROP
-1 -2 -3 -4 REMARKS
0.00 10.38

6.42 10.38

3.83 10.38
5.66 10.38
6.68 10.38
5.04 10.38

….KW
DISTRIBUTION PANEL - 1 Rev : 00

CIRCUIT RATING-AMPS

SPN/ TPN
FEEDER F/S MCCB

DB NO. ISO ACB


INCOMER : TPN 315
OUTGOING :
GND FLOOR VTPN VB TPN 160
FIRST FLOOR VTPN VB TPN 125
KITCHEN PANEL TPN 40
PARCEL OFFICE DB SPN 32

LVP-ESS
fed from : TRANSFORMER

MAX. DEMAND (3 PH) KW. AT………..


Consultant :
Type of Meter (Rating of Incomer):
ATING-AMPS FAULT Voltage Drop CABLE SIZE
PVC/XLPE
Length
DUTY 2/4 X
MCB
KA XLPE/SWA/LSF 1C mm2
35 XLPE 0.18 120

35 XLPE 0.45 20
35 XLPE 0.87 20
35 XLPE 4.05 25
16 XLPE 0.87 25

Total Connected Load

KW. AT……….. 0.80 …….DIVERSITY 171.552


+
(1) Upto 60 A (2) Upto 100 A (3) 125 - 160 A
(1 Phase) (3 Phase)
CABLE SIZE
CURRENT CALCULATED
CONNECTED DIVERSIFIED AFTER VOLTAGE
LOAD LOAD DERATING DROP
2/3/4C

mm2
300 214.44 171.55 295.07

95 111.67 89.34 153.66 1.37


50 72.77 58.22 100.13 1.74
10 25.00 20.00 34.40 3.48
10 5.00 4.00 6.88 0.15

214.44 171.55 295.07

TOTAL CONENCTED LOAD (3 PH)…… 214.44


TEL:
) 125 - 160 A
PROPOSED TYPE & NO. OF KWH METERS
Permissable
Voltage Drop LV/HV
1-PH 3-PH 3-PH CT
-1 -2 -3 -4 REMARKS

10.38
10.38
10.38
10.38

TOTAL

….KW
FAX :
DISTRIBUTION PANEL - 1 Rev : 00

CIRCUIT RATING-AMPS

SPN/ TPN
FEEDER F/S MCCB

DB NO. ISO ACB


INCOMER : TPN 630
OUTGOING :
METER PANEL-1 TPN 250
METER PANEL-2 TPN 315
METER PANEL-3 TPN 20

LVP-ESS
fed from : TRANSFORMER

MAX. DEMAND (3 PH) KW. AT………..


Consultant :
Type of Meter (Rating of Incomer):
ATING-AMPS FAULT Voltage Drop CABLE SIZE
PVC/XLPE
Length
DUTY 2/4 X
MCB
KA XLPE/SWA/LSF 1C mm2
35 XLPE 0.09 20

35 XLPE 0.25 30
35 XLPE 0.18 150
35 XLPE 4.05 25

Total Connected Load

KW. AT……….. 0.80 …….DIVERSITY 307.84


+
(1) Upto 60 A (2) Upto 100 A (3) 125 - 160 A
(1 Phase) (3 Phase)
CABLE SIZE
CURRENT CALCULATED
CONNECTED DIVERSIFIED AFTER VOLTAGE
LOAD LOAD DERATING DROP
2/3/4C

mm2
2x300 384.80 307.84 529.48 0.96

185 165.00 132.00 227.04 1.72


300 205.48 164.38 282.74 7.68
10 14.32 11.46 19.70 2.00

384.80 307.84 529.48

TOTAL CONENCTED LOAD (3 PH)…… 384.80


TEL:
) 125 - 160 A
PROPOSED TYPE & NO. OF KWH METERS
Permissable
Voltage Drop LV/HV
1-PH 3-PH 3-PH CT
-1 -2 -3 -4 REMARKS
10.38

10.38
10.38
10.38

TOTAL

….KW
FAX :
MINI FEEDER PILLAR - 1 Rev : 00

CIRCUIT RATING-AMPS

SPN/ TPN
FEEDER F/S MCCB

DB NO. ISO ACB


INCOMER : TPN 125
OUTGOING :
WORKSHOP VTPN DB TPN 63
DIESEL PUMP PANEL TPN 32
QUARTERS DB TPN 40

LVP-ESS
fed from : TRANSFORMER

MAX. DEMAND (3 PH) KW. AT………..


Consultant :
Type of Meter (Rating of Incomer):
ATING-AMPS FAULT Voltage Drop CABLE SIZE
PVC/XLPE
Length
DUTY 2/4 X
MCB
KA XLPE/SWA/LSF 1C mm2
35 0.61 100

35 XLPE 2.55 25
35 XLPE 2.55 20
35 XLPE 1.62 120

Total Connected Load

KW. AT……….. 1.00 …….DIVERSITY


+
(1) Upto 60 A (2) Upto 100 A (3) 125 - 160 A
(1 Phase) (3 Phase)

70
CABLE SIZE
CURRENT CALCULATED
CONNECTED DIVERSIFIED AFTER VOLTAGE
LOAD LOAD DERATING DROP
2/3/4C

mm2
70 82.70 66.16 113.80 6.91

16 37.70 30.16 51.88 3.30


16 20.00 16.00 27.52 1.40
25 25.00 20.00 34.40 6.67

82.70 66.16 113.80

TOTAL CONENCTED LOAD (3 PH)…………………………..


TEL:
) 125 - 160 A
PROPOSED TYPE & NO. OF KWH METERS
Permissable
Voltage Drop LV/HV
1-PH 3-PH 3-PH CT
-1 -2 -3 -4 REMARKS
10.38

10.38
10.38
10.38

TOTAL

….KW
FAX :
MINI FEEDER PILLAR - 1 Rev : 00

CIRCUIT RATING-AMPS

SPN/ TPN
FEEDER F/S MCCB

DB NO. ISO ACB


INCOMER : TPN
OUTGOING :
GROUND FLOOR TPN 25
FIRST FLOOR TPN 32

LVP-ESS
fed from : TRANSFORMER

MAX. DEMAND (3 PH) KW. AT………..


Consultant :
Type of Meter (Rating of Incomer):
ATING-AMPS FAULT Voltage Drop CABLE SIZE
PVC/XLPE
Length
DUTY 2/4 X
MCB
KA XLPE/SWA/LSF 1C mm2
35

35 XLPE 4.05 10
35 XLPE 4.05 20

Total Connected Load

KW. AT……….. 1.00 …….DIVERSITY


+
(1) Upto 60 A (2) Upto 100 A (3) 125 - 160 A
(1 Phase) (3 Phase)
CABLE SIZE
CURRENT CALCULATED
CONNECTED DIVERSIFIED AFTER VOLTAGE
LOAD LOAD DERATING DROP
2/3/4C

mm2
#N/A

10 16.43 13.14 22.61 0.92


10 21.27 17.02 29.27 2.37

TOTAL CONENCTED LOAD (3 PH)…………………………..


TEL:
) 125 - 160 A
PROPOSED TYPE & NO. OF KWH METERS
Permissable
Voltage Drop LV/HV
1-PH 3-PH 3-PH CT
-1 -2 -3 -4 REMARKS

10.38
10.38

TOTAL

….KW
FAX :
Planned Completion Date : 2020
COMMON LOAD PANEL Rev : 00

CIRCUIT FAULT

SPN/ TPN
FEEDER MCCB DUTY

DB NO. ACB KA
INCOMER : TPN 500 35
OUTGOING :
UTILITY PANEL(STP,WTP,OWC,PUMP
TPN 20 35
PANEL)
STP TPN 32
WTP
CLUBHOUSE DB TPN 35
EXTERNAL DB TPN 63 35
BASEMENT PANEL TPN 16 35
STACK PARKING TPN 100 35
LVP-ESS
fed from : TRANSFORMER
Client
DETAILS: MINISTRY OF OILLOAD/MAX.
OF CONNECTED AND GAS DEMAND

Consultant :

Voltage Drop CABLE SIZE


PVC/XLPE
Length
2/4 X 2/3/4C

XLPE/SWA/LSF 1C mm2 mm2


XLPE 2x185

XLPE 4.05 50 10
XLPE 4.05 50 10.0

XLPE 2.55 20 16
XLPE 1.17 20 35.0
XLPE 4.05 60 10.0
XLPE 1.17 50 35
Total Connected Load
CURRENT CALCULATED
CONNECTED DIVERSIFIED AFTER VOLTAGE Permissable
LOAD LOAD DERATING DROP Voltage Drop

248.00 248.00 429.54

14.40 11.52 19.81 4.01 10.38


15.00 15.00 25.80 5.23 10.38

7.33 5.86 10.09 0.51 10.38


38.00 34.20 58.82 1.38 10.38
8.00 8.00 13.76 3.34 10.38
80.00 48.00 82.56 4.83 10.38
PROPOSED TYPE & NO. OF KWH METERS

1-PH 3-PH 3-PH LV/HV


CT
-1 -2 -3 -4 REMARKS

TOTAL
Planned Completion Date : 2020
COMMON LOAD PANEL Rev : 00

CIRCUIT FAULT

SPN/ TPN
FEEDER MCCB DUTY

DB NO. ACB KA
INCOMER : TPN 35
OUTGOING :
STP TPN 20 25
DOMESTIC TPN 20 25
FLUSHING TPN 20 25
DEWATERING PUMP TPN 20 25
FIRE PUMP PANEL TPN 200 25

LVP-ESS
fed from : TRANSFORMER

MAX. DEMAND (3 PH) #REF! KW. AT 1.00


Consultant :
Type of Meter (Rating of Incomer):
Client
DETAILS: MINISTRY OF OILLOAD/MAX.
OF CONNECTED AND GAS DEMAND

Consultant :

Voltage Drop CABLE SIZE


PVC/XLPE
Length
2/4 X 2/3/4C

XLPE/SWA/LSF 1C mm2 mm2


4C 185

XLPE 2.55 50 16
XLPE 4.05 30 10
XLPE 4.05 30 10
XLPE 4.05 30 10
XLPE 0.36 30 120

Total Connected Load

…….DIVERSITY TOTAL CONENCTED LOA


+ TEL:
(2) Upto 100 A (3) 125 - 160 A
(3 Phase)
CURRENT CALCULATED
CONNECTED DIVERSIFIED AFTER VOLTAGE Permissable
LOAD LOAD DERATING DROP Voltage Drop

22.39 17.91 30.81 0.00 10.38

11.19 11.19 19.25 2.45 10.38


4.48 2.69 4.62 0.56 10.38
4.48 2.69 4.62 0.56 10.38
2.24 1.34 2.31 0.28 10.38
50.00 50.00 172.00 1.87 10.38
72.39

AL CONENCTED LOAD (3 PH)…………………………..


PROPOSED TYPE & NO. OF KWH METERS

1-PH 3-PH 3-PH LV/HV


CT
-1 -2 -3 -4 REMARKS

TOTAL

….KW
FAX :
Meter Panel 1
Type Working Load in kw Quantity Total Load in KW
2BHK Type 1
2BHK Type 1
2BHK Type 2
2BHK Type 2
3BHK Type 2
Total Load in Kw 0

Meter Panel 2
Type Working Load in kw Quantity Total Load in KW
2BHK Type 1
2BHK Type 1
2BHK Type 2
2BHK Type 2
3BHK Type 2
Total Load in Kw 0

Meter Panel 3
Type Working Load in kw Quantity Total Load in KW
2BHK Type 1
2BHK Type 1
2BHK Type 2
2BHK Type 2
3BHK Type 2
Total Load in Kw 0

Meter Panel 4
Type Working Load in kw Quantity Total Load in KW
2BHK Type 1
2BHK Type 1
2BHK Type 2
2BHK Type 2
3BHK Type 2
Total Load in Kw 0

Meter Panel 5
Type Working Load in kw Quantity Total Load in KW
2BHK Type 1
2BHK Type 1
2BHK Type 2
2BHK Type 2
3BHK Type 2
Total Load in Kw 0
Meter Panel 6
Type Working Load in kw Quantity Total Load in KW
2BHK Type 1
2BHK Type 1
2BHK Type 2
2BHK Type 2
3BHK Type 2
Total Load in Kw 0
Load Current

Load Current

Load Current

Load Current

Load Current
Load Current
1BHK Type 1 Cable Current
1BHK Type 2 Capacity
2BHK Type 1 CABLE SIZE Armoured

2BHK Type 2 1.50 31.0009 - 20

3BHK Type 1 2.50 18.9614 - 27

3BHK Type 2 4 11.8020 - 34

3BHK Type 1 6 7.8827 - 43

3BHK Type 2 10 4.6841 - 57

16 2.9461 2.9469 73

25 1.8696 1.8706 96

35 1.3546 1.3559 115

50 1.0070 1.0083 134

70 0.7083 0.7097 165

95 0.5234 0.5250 198

120 0.4279 0.4296 225

150 0.3618 0.3640 252

185 0.3065 0.3085 285

240 0.2573 0.2593 330

300 0.2282 0.2302 371

2x95

2x120

2x1150

2x185

2x240

2x300

3x95

3x120

3x150

3x185

3x240

3x300

Voltage
CABLE SIZE Drop MCCB
1.50 26.82 16
2.50 16.40 20
4 10.21 25
6 6.82 32
10 4.05 40
16 2.55 63
25 1.62 100
35 1.17 125
50 0.87 160
70 0.61 200
95 0.45 250
120 0.36 315
150 0.30 400
185 0.25 500
240 0.21 630
300 0.18 800
2x95 0.22 1000
2x120 0.18 1250
2x1150 0.15 1600
2x185 0.13 2000
2x240 0.10 3200
2x300 0.09 4000
500 0.15

630 0.14

800 -

1000 -
PVC
Current after
derating 3 Phase @
Single Phase @ 70 deg. C
3 Phase @
90 deg. C 70 deg. C
Unarmoured Armoured

0.8 16.0 26.8156 29.0011 - 25.0857

0.8 21.6 16.4013 17.8016 - 15.3981

0.8 27.2 10.2083 11.0424 - 9.5513

0.8 34.4 6.8180 7.3833 - 6.3860

0.8 45.6 4.0509 4.3850 - 3.7920

0.8 58.4 2.5470 2.7672 2.7681 2.3922

0.8 76.8 1.6151 1.7512 1.7523 1.5125

0.8 92.0 1.1689 1.2746 1.2759 1.0994

0.8 107.2 0.8673 0.9479 0.9492 0.8157

0.8 132.0 0.6075 0.6673 0.6688 0.5715

0.8 158.4 0.4458 0.4981 0.4997 0.4232

0.8 180.0 0.3616 0.4084 0.4102 0.3441

0.8 201.6 0.3028 0.3487 0.3510 0.2908

0.8 228.0 0.2532 0.2994 0.3014 0.2463

0.8 264.0 0.2082 0.2555 0.2576 0.2061

0.8 296.8 0.1812 0.2297 0.2319 0.1823

316.8

360.0

403.2

456.0

528.0

593.6

633.6

720.0 0.1524

806.4 0.1438

912.0 -

1056.0 -

1187.2

Voltage
Drop

You might also like