TITLE:

I&C functions test during commissioning – CWS 69


ECCN: N
AL: N

DOCUMENT KIND : DCC : CONFIDENTIALITY :

Technical report EBB RESTRICTED

AREVA NP FGF PEPS-G/2015/en/1050


Name of the issuing company COMPANY CODE DOCUMENT NUMBER

The reproduction, transmission or use of this document or its contents is not permitted without express written authority. Offenders will be liable for damages. All
rights, including rights created by patent grant or registration of a utility model or design, are reserved.
Goods labeled with "AL not equal to N" are subject to European or German export authorization when being exported out of the EU. Goods labeled with "ECCN not
equal to N" are subject to US reexport authorization. Even without a label, or with label "AL:N" or "ECCN:N", authorization may be required due to the final
whereabouts and purpose for which the goods are to be used.
The original version of this document is stored in electronic form in the AREVA NP-EDM system. The current status of this document can be viewed only in the EDM
system.
2006.04 ANP 2268
Document type

Technical report
Class Number of pages 191
RESTRICTED Number of appendices 1

Document Title

I&C functions test during commissioning – CWS 69


CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

Short Title

I&C function test - CWS 69

GIRAUD Mathieu KISSICH Sven MARTIN Henri


A 2016-06-15 KREINHOEFNER
Ulrich
First issue FIN
ECCN: N
AL: N

Rev Date Author Checked by Modifications / Observations Status Approved by

Contract :
Project FIN005
PEPS-G/2015/en/1050
File code -
No EOTP:

Subdivision INTERNAL IDENTIFICATION NUMBER

This document is the property of AREVA NP.


It must not be used reproduced, transmitted or disclosed without the prior written permission of AREVA NP.
2006.04 ANP 0313
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 3 / 50

REVISIONS

IND STATUS
PARAGRAPH SCOPE OF THE REVISION
REV DATE

A 2016-06-15 First issue


CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract
ECCN: N
AL: N
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 4 / 50

SUMMARY

The purposes of this document is to provide:


- an overview of the I&C functions test coverage strategy,
- a guideline in order to create the commissioning instructions which aim at testing I&C
functions (or part of I&C functions) which are not already tested previously on Test Bay,
or in the frame of process system or pseudo system commissioning programs (SCP).
During commissioning of the process systems including the related I&C functions, signal
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

simulation is required in order to allow the testing of the functions mainly in phase A and B,
or to simulate plant situations which cannot be reached without unnecessary loads for the
equipment or damaging it.

KEY WORDS

Commissioning, I&C, Function test, signal simulation, CWS 69, I&C Functions Level Test
Plan

ABBREVIATIONS

AIH Anti Ice Heating


ATWS Anticipated Transient Without Scram
CLT Closed Loop Test
CWS Commissioning Work Sheet
ECCN: N

DBC Design Basis Condition / Category


DEC Design Extended Condition / Category
DLS Diesel Load Sequence
AL: N

EDG Emergency Diesel Generator


EDGSIC Emergency Diesel Generator Safety I&C
EFWS Emergency Feedwater System
ERBUS Simulation tool for stimulating and monitoring inputs and outputs of a
TELEPERM XS I&C application for testing purposes
ESFAS Engineered Safety Features Actuation System
ESWS Essential Service Water System
FAR Function Allocation Report
FAT Factory Acceptance Test
FD Functional Diagram
FGC Function Group Complex
FUM Function Module
HBS Hardwired Backup System
HMI Human-Machine Interface
HVAC Heating Ventilating and Air Conditioning
I&C Information & Control
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 5 / 50

IRD Intermediate Range Detector


LCO Limiting Condition for Operation
LCP Local Control Panel
LHSI Low-Head Safety Injection
LIM Limitation
MHSI Medium-Head Safety Injection
NI Nuclear Island
OAF Operator Aid Function
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

PACS Priority and Actuator Control System


PCP Phase Commissioning Program
PICS Process Information and Control System
PRD Power Range Detector
PS Protection System
RCSL Reactor Control, Surveillance and Limitation system
RPMU Rod Position Measuring Unit
RRS Result Record Sheet
RT Reactor Trip
SAT Site Acceptance Test
SBO Station Blackout
SCI Standard Commissioning Instruction
SCP System Commissioning Program
SCPSSA Signal Conditioning for PS and SA-I&C
ECCN: N

SG Steam Generator
SICS Safety Information and Control System
SIMIT I/O simulation test bench from SIEMENS
AL: N

SIS Safety Injection System


SIVAT SImulation-based VAlidation Tool
SPND Self-Powered Neutron Detector
SRD Source Range Detector
SU Service Unit
SWGR Switchgear
TGI Turbine Generator Instrumentation and control
TI Turbine Island
TUM Maximal Undervoltage Time
TWS Timed sequence for delayed restart
TXP TELEPERM XP (Process)
TXS TELEPERM XS (Safety)
UVP Undervoltage Protection
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 6 / 50

TABLE OF CONTENTS

0. REFERENCES 10

1. INTRODUCTION 12
1.1. Objective 12
1.2. Test scope during commissioning 12
1.3. Applicability 13
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

1.4. Strategy for testing I&C functions. 13

2. I&C FUNCTIONS TO BE TESTED DURING COMMISSIONING 14


2.1. Assignment of I&C Functions to the related Process or Pseudo
System Commissioning Program 14
2.2. Basic boundary conditions for commissioning test. 14
2.3. Test Sequence – Time Schedule 15
2.4. Re-Testing of Function after Hard- and Software Modification 15

3. TEST COVERAGE ANALYSIS AND DOCUMENTATION 16


3.1. Assignment of I&C Functions to SCPs and I&C Architecture Level
Test Coverage 16
3.2. Definition of tests related to I&C functions in relation to the CIs and
SCPs 18
3.3. Coverage Documentation / Highlighting of Functional Diagrams 18
ECCN: N

4. I&C FUNCTION TEST TYPES 27


4.1. I&C Function Test at I&C System Level 27
4.2. Field Equipment Interface Tests 28
AL: N

4.3. Function Tests 30


4.4. Test of Functions with Interlocks or Permissives 33
4.5. Test coverage of function with signal voting or several triggering
parameters 33
4.6. Allocation of I&C Functions to Test Types. 36
4.7. Specific Function Tests 37
4.8. I&C System test coverage 39

5. SIGNAL SIMULATION 44
5.1. Field instrumentation Simulation 44
5.2. Automation System Simulation 48
5.3. Deactivation of actuators 49
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 7 / 50

LIST OF APPENDICES

Appendix A: Preliminary I&C Functions SCP Assignment A1


CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract
ECCN: N
AL: N
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 8 / 50

LIST OF TABLES

Table 1: Test Types 27

Table 2: Allocation of I&C functions to I&C Systems 39

Table 3: TXS I&C Systems (computer based) 40

Table 4: TXS I&C Systems (Non-computer based) 41


CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

Table 5: TXP I&C Systems 42

Table 6: SICS Functions 43

Table 7: SSS Systems 43

Table 8: List of pseudo SCP for I&C Funciton Testing A2

Table 9: Preliminary I&C Functions Assignment A2

LIST OF FIGURES

Figure 1: Time Schedule – Principle 15

Figure 2: Assigenment of I&C functionS to SCPs 17


ECCN: N

Figure 3: Coverage documentation elaboration 19

Figure 4: Example for highlighting FD 22


AL: N

Figure 5: Example of stamp for FD highlighting 23

Figure 6: Example of stamp for SCI52 and SCI53 23

Figure 7: Template for an I&C function coverage review sheet 24

Figure 8: Level 1Function test 28

Figure 9: Test Coverage – Instrumentation Channels (TT1) 29

Figure 10: Test Coverage – Actuation Channels (TT2) 30

Figure 11: Test Coverage –Function without Sensors (TT3) 31

Figure 12: Test Coverage –Function without Actuators (TT4) 31

Figure 13: Test Coverage – complete Function (TT5) 32

Figure 14: Test Coverage – Function without Field (TT6) 33

Figure 15: Test Coverage for Functions with Voter 34


Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 9 / 50

Figure 16: Example Test of ESFAS Functions 34

Figure 17: Test coverage for Function with several triggering paramters 35

Figure 18: Example Test of Component Protection Function 35

Figure 19: Flow digagram – Function assignment 36

Figure 20: Reactor Trip Function Test 37


CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

Figure 21: Sensor Simulation – Analog (4..20mA) 44

Figure 22: Sensor Simulation – Temperature 45

Figure 23: Sensor Simulation – Frequency 45

Figure 24: Sensor Simulation – Binary 46

Figure 25: Sensor Simulation – Rod Position 46

Figure 26: Sensor Simulation – EXCORE / INCORE Flux 47

Figure 27: Sensor Simulation – N16 47

Figure 28: Sensor Simulation – Activity 47

Figure 29: Simulation in TXS (computer-Based) 48

Figure 30: Simulation in TXS (non-computer-based) 49

Figure 31: Simulation in TXP 49


ECCN: N

Figure 32: Deactivation of actuators at SWGR 50


AL: N

Figure 33: Disable all output commands to SWGR 50


Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 10 / 50

0. REFERENCES

[1] YVL 2.5, September 29th 2003


The Commissioning of a Nuclear Power Plant
[2] YVL 5.5, September 13th 2002
Instrumentation Systems and Components at Nuclear Facilities
[3] PELLN-G/2010/en/1054 rev. E
I&C Architecture Master Test Plan [AD-02.03b]
[4] NLN-G/2009/en/1001 rev F
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

I&C Architecture Quality Plan [AD-01.01]


[5] NLP-G/2008/en/1111 rev. N
Plant Level I&C Architecture [AD-02.01a]
[6] NLE-F DC 94 rev. L
Allocation of I&C Functions [AD-02.01b]
[7] PEAV-F DC 1006 rev. N
Protection System Master Test Report
[8] PELV-F DC 311 rev. A
HBS Master Test Report
[9] PELV-F DC 293 rev. A
SA I&C Master Test Report
[10] PELV-G/2013/en/1011 rev. A
RCSL Master Test Report
[11] PEAV-F DC 1001 rev. B
SAS/PAS Master Test Report
[12] NFLE DC 1039 rev.L
ECCN: N

Protection System Concept for I&C failure handling


[13] DN0042 rev. D
TXP-Module parameter according to DN042
AL: N

[14] NL-G/2007/en/1004 rev. L


Standard Commissioning Instruction: Commissioning of the control section of the
switchgear feeders, motors, actuators and control valves
(SCI 52 NI)
[15] NL-G/2007/en/1005 rev. D
Standard Commissioning Instruction for Measuring Circuits (binary & analog)
(SCI 53 NI)
[16] NLNL-G/2009/en/1020 rev. F
Standard Commissioning Instruction for Closed Loop Controllers
SCI 54
[17] NECC DC 123 rev. B
Commissioning Manual - Temporary Modification Control during Commissioning
CP 7.2
[18] FSS DC 0357 rev. C
PI 20.02 - Management of Temporary Modifications before TOTO
[19] FSM DC 2689 rev. A
PI 20.19 Project Instruction Simulation in I&C
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 11 / 50

[20] NECC DC 3 rev. G


Overall Plant Commissioning Program
[21] 420783170 rev. D
CWS No. 4 TI Process Interlock Test
[22] FSM DC 2539 rev. B
PI 6.10 - I&C Technical Change and Configuration Management Procedure during
Commissioning Phases
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract
ECCN: N
AL: N
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 12 / 50

1. INTRODUCTION

1.1. Objective
According to YVL guide [1], [2] the final testing shall demonstrate that the I&C system or
equipment fulfill the functional and performance requirements specified for it. The testing can
be partially based on simulation. The final testing shall, however, be performed in the final
operational environment.
The purpose of this document is to provide:
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

- an overview of the I&C functions test coverage strategy,


- a guideline in order to create the commissioning instructions which aim at testing I&C
functions (or part of I&C functions) which are not already tested previously on Test Bay,
or in the frame of the process system or pseudo system commissioning programs
(SCP).
The tests are performed in the final I&C systems environment installed on site. Nevertheless
tests performed on Test Bay are also credited in the coverage analysis.
During commissioning of the process systems including the related I&C functions, signal
simulation is required in order to allow the testing of the functions, or to simulate plant
situations which cannot be reached without unnecessary loads for the equipment or
damaging the equipment in the different phases of the commissioning program.
This document gives is a guideline to:
– ensure that all I&C functions are tested in the frame of a process or pseudo SCP,
– prepare I&C functional tests per process or pseudo system,
– define documentation to allow the tracing of test coverage.
ECCN: N

– define for each function test if signal simulation is required, and how it can be done.

1.2. Test scope during commissioning


AL: N

According to I&C Architecture Master Test Plan [1], tests and verifications shall be performed
with the process SCP (e.g. mechanical, HVAC or electrical systems).
During process system commissioning the designed functionality of each unique process
system is validated and tested. During the testing of the process function the designed sub-
functionalities as e.g. mechanical component design or I&C design is activated and in this
frame tested in an overall manner. Therefore the control via the different I&C functions is
tested integrally for the single function. This activation allows the demonstration of the
correctness of I&C application function requirements by observing the result of the I&C
control on the process.
Testing the I&C Functions from sensors to actuators can be performed as a full chain test or
in an overlapping way.
I&C Functions involved in normal operation DBC1 and abnormal operation DBC2 events of
the plant shall be tested in the scope of Commissioning Program written by using the OL3
Operating Manual. The correct operational behavior of the I&C Functions and the fulfillment
of their intended use can be demonstrated when controlling process systems involved in the
normal operation of the plant. The plant level tests which are based on the operational
manual will be credited to determine the suitability of the I&C Functions, they are performed
according to the PCP which will contain the item-pass criteria based on plant requirements.
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 13 / 50

I&C Functions designed to cope with DBC2 to DBC4, DEC-A and DEC-B events shall be
tested as far as possible tested from sensor to actuator at Commissioning Phases A to B.
If triggering parameter setpoint(s) cannot be reached with the plant process especially
without damaging equipment or endangering equipment lifetime, the triggering signal shall be
simulated. Actuation of field equipment shall only be performed if a damage of the equipment
can be excluded. In addition I&C Functions controlling this same process function i.e. the
same set of actuators or system functionality do not need to activate these actuators several
times in order not to endanger equipment lifetime.
During Commissioning the behavior of each function needs to be checked against functional,
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

and safety requirements.

1.3. Applicability
I&C Functions defined in the Allocation of I&C Functions [AD-02.01b] [6] shall be tested
during Commissioning. I&C Functions involved in the control of several process systems or
involving regulations is attributed to either one process SCP or to pseudo SCP.
This document is a guideline aiming at creating and gathering evidences which will ensure
that all functions are tested. The SCP allocated in Appendix A as a baseline should define
the tests done to verify the related I&C function.
The SCP of the main process system triggered by the I&C function coordinates the test
condition with the support process systems.

1.4. Strategy for testing I&C functions.


This guideline provides the necessary background information how I&C functions can be
tested in principle and the strategy how to assign the different I&C function to one SCP and
define the necessary tests.
ECCN: N

– Chapter 2 provides the strategies for testing of the different I&C functions;
– Chapter 3 defines the strategy for I&C function test coverage and documentation;
AL: N

– Chapter 4 defines the I&C function test types;


– Chapter 5 provides the technical basis for signal simulation.
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 14 / 50

2. I&C FUNCTIONS TO BE TESTED DURING COMMISSIONING

During commissioning all process systems including related I&C need to be tested in order to
demonstrate a correct operation of the plant in normal, abnormal and accident conditions. In
order to demonstrate this, all process systems including related I&C need to be tested in as a
first step at system level according to the process SCP or pseudo SCP. As a second step,
the correct operation of all systems together at plant level needs to be tested in the different
phase commissioning programs.
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

2.1. Assignment of I&C Functions to the related Process or Pseudo


System Commissioning Program
All I&C functions required to operate the different process systems and all I&C functions
defined to operate the plant in normal, abnormal and accident conditions are defined in each
process system description and collected in the report Allocation of I&C Functions [6].
As a first step, all I&C functions need to be assigned to a process system or pseudo system
commissioning program, in order to secure that all functions are covered by commissioning
activities.
In the second step it needs to be decided whether the function can be fully tested with the
process system(s) including subfunctions or if signal simulation is required to test the
function. As far as reasonable the I&C functions shall be tested within the final process
environment during process tests. If this is not possible it shall be checked if the function can
be tested in a simulated system or plant condition. This can be done by simulating interlocks
or permissives. If the triggering plant parameters cannot be reached with the plant or system
process the instrumentation channels can be simulated. In some cases the function can only
be tested without field response in order not to damage the equipment or stress the
equipment unnecessarily. In exceptional cases the I&C function can only be tested with
simulation and monitoring of the output signal because the plant or system conditions cannot
ECCN: N

be reached and the field response would lead to damages of the equipment. For this type of
function adequate overlapping tests needs to be applied to test the whole function. Chapter 4
describes different application test types.
AL: N

2.2. Basic boundary conditions for commissioning test.


Following basic boundary conditions needs to be fulfilled:
– HMI interfaces PICS, SICS and LCP needs to be operable for control and monitoring
of the I&C functions.
– Each I&C automation system including service unit needs to be operable and
successfully tested according to the I&C SCP.
– For the test planning all I&C functions triggered by the same process parameters
need to be considered and if possible tested at the same time. Otherwise unwanted
triggering can occur. In order to avoid this either the test conditions need to be
prepared for all (sub)functions which can be actuated during the test sequence or the
actuation of the other (sub)functions not part of the test need to be blocked by an
adequate method, e.g. putting SWGR in test position.
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 15 / 50

– If simulation is required for the function testing the modified parts need to be restored
to normal conditions. That means for example instrumentation channels or actuation
channels have to be restored to normal configuration following the nuclear testing
manual or modifications of parameters, setpoint, etc. need to be tracked and put to
normal configuration after the test. A check of the complete restoration of all changes
required for simulation need to be done latest before fuel loading (see [17], [18]).

2.3. Test Sequence – Time Schedule


CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

The leading principle is to get all I&C functions fully qualified during commissioning phases A
and B including actuation of all actuators involved (through test) with exception of all
functions involving nuclear flux, control rod position, nuclear and generator power and
associated parameters.
For those functions or sub-functions, a pre-qualification in full simulation mode shall be
performed prior to phase C in order to get all functions and sub-functions declared operable
for fuel loading, the once through test with actuator activation and feedback being postponed
in phase C or D.
ECCN: N

FIGURE 1: TIME SCHEDULE – PRINCIPLE


AL: N

2.4. Re-Testing of Function after Hard- and Software Modification


During Test Bay test the application software (I&C functions) were tested in the final
environment (I&C cabinets). If during commissioning, an I&C system needs to be modified,
the function or parts of the function which are affected by the change need to be re-tested.
The change process including the retesting shall follow the applicable technical change
management process (refer to [22]).
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 16 / 50

3. TEST COVERAGE ANALYSIS AND DOCUMENTATION

3.1. Assignment of I&C Functions to SCPs and I&C Architecture Level


Test Coverage
During Commissioning all I&C functions defined in the process system description and
collected in the report Allocation of I&C Functions [6] need to be tested.
Figure 2 defines the process how all I&C functions are assigned to at least one process or
pseudo SCP and how the test coverage at I&C architecture level is ensured.
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

– Step 1) All I&C functions are assigned to at least one process or pseudo SCP with the
Preliminary I&C Function SCP assignment as provided in Appendix A as a baseline.
In the first step, the I&C functions defined in the different process system descriptions
(e.g. 3 0PE) are assigned to the process SCP which tests the I&C function related to
the process functions (e.g. SCP PE).
– Step 2) All I&C functions assigned to the SCP shall be listed and assigned to the final
SCP which takes care of the complete check of the I&C function. If the preliminary
assignment is modified and the assignment is shifted to another SCP, the function will
be kept in the table of the preliminary assigned SCP with the link to the final SCP and
will also be listed in the final SCP.
– Inside the SCP each I&C function shall be assigned to an Activity Code and the
related Commissioning Instruction(s) which defines the test in detail. The SCP states
with which activity codes of the SCP which I&C is tested. If the preliminary assignment
is not followed, the link to the SCP where the function is tested is given. A commonly
formatted table is extracted for each function detailing the tests defined. (see chapter
3.3.3)
– Step 3) A completeness check is performed whether all I&C functions are assigned or
ECCN: N

re-assigned to the final process or pseudo SCP. If inconsistencies or gaps are


identified, the overall commissioning team decides about the final allocation of the I&C
function test. Inconsistencies in the input documentation need to be clarified with the
responsible system engineer (step3a). This completeness check is based on
AL: N

Allocation of I&C Functions table (refer to [6]) and will be updated regularly, in parallel
of SCP issuance.
– Step 4) The final verification that all functions are covered via test programs is
documented on I&C architecture level in the I&C Functions Level Test Plan by V&V
[4].
– Step 5) The test coverage analysis on I&C architecture level is recorded in the I&C
Functions Level Test Report by V&V [4].
At the end the SCP leads the test coverage of the complete I&C function to which the I&C
function is originally assigned to. There can be several commissioning steps /instructions
involved in the test but only one SCP.
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 17 / 50
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract
ECCN: N
AL: N

FIGURE 2: ASSIGENMENT OF I&C FUNCTIONS TO SCPS


Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 18 / 50

3.2. Definition of tests related to I&C functions in relation to the CIs and
SCPs
The I&C Functions shall be tested in the frame of the process SCP; they are assigned to like
defined in section 3.1.
All logics which are not covered by Test Bay Tests shall be tested during the commissioning
of the process system.
The author of the SCP is responsible to define tests covering the full functionality of I&C
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

functions.
As an input what has to be tested during commissioning the author can use:
– The description of the functions in the System Description related to the SCP;
– The Functional Diagrams (e.g. DD4);
– The documentation of allocation of I&C Functions to Logics (DD4 Bubbling);
– The documentation of Test Bay testing (test reports).
I&C tests are carried out in the frame of the corresponding process tests. If it appears that an
I&C function is not fully tested during process tests (as it is e.g. too complex), a dedicated
test procedure called CI-69 have to be created in order to fill the gap.
All functions are covered by one SCP. Together with the test description in the
commissioning documentation (SCP / CI) a full coverage of tests is ensured.

3.3. Coverage Documentation / Highlighting of Functional Diagrams


ECCN: N

3.3.1. Overview
The following diagram provides an overview of the process aiming at collecting evidences of
I&C function test coverage.
AL: N
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 19 / 50
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract
ECCN: N
AL: N

FIGURE 3: COVERAGE DOCUMENTATION ELABORATION


Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 20 / 50

3.3.2. Highlighting of Functional Diagrams


The Functional Diagrams show the logic in the corresponding I&C and contain the
connections to the field via input and outputs modules. Therefore it is appropriate to
document the test coverage of the I&C function test by using the Functional Diagrams.
During or after the test execution, the Functional Diagrams are stamped and highlighted in
color to give proof in which frame the logic is tested.
The logic is tested in several steps at several dates. To show the reference to each test it
might be necessary to use different colors. It must be clear which test reference belongs to
which highlighting. Usually each page is printed only once. If it is necessary to use two pages
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

for clarity reasons, there shall be one main page and references to the following pages as
attachment.
For the test coverage analysis and documentation on I&C function level, the Functional
Diagrams of the Commissioning master documentation in reference configuration RC 2.1DP
is used. The highlighting is performed for all I&C systems for:
– TXP based System in the DD4 Functional Diagram Documentation per Functional
group complex (FGC), and for
– TXS based Systems in the level 3 Functional Diagrams per I&C System:
– PS NFLE DC 1018
– RCSL NGLP/2005/en/1008
– HBS NFLE DC 1070
– SA I&C NFLE DC 1164
– EDGSIC NLP-G/2006/en/1115 – Appendix A
Note: Any other I&C function embedded on another I&C platform (e.g. Self Standing
ECCN: N

Systems) are out of scope of highlighting.


As far as possible, highlighting is performed in two steps:
1. First one is performed before commissioning test execution. The purpose of this first
AL: N

step is to detect as early as possible the potential gaps, which will require extension
of an existing CI or creation of a dedicated test procedure (so called CI-69).
Preferably this highlighting step is organized as a sequence:
i. Firstly, I&C commissioning team pre-highlights scope covered by
SCI52/53, using thin colored lines
ii. Secondly, process commissioning engineer pre-highlights the scope
covered by the remaining part of SCP, using thin colored lines (pre-
highlighting)
iii. Thirdly, V&V team fill the gaps thanks to Test Bay activities, using thick
colored lines
2. Second one is performed while executing each relevant commissioning test, by
overlining the existing thin lines with thick ones.

3.3.2.1. Highlighting rules


During or immediately after the test execution, it is validated that the logic is tested via the
test instructions by highlighting the test scope in different colors and adding the test
reference in the Functional Diagrams.
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 21 / 50

If a part of a function is tested several times in various tests, it must only be highlighted once.
Nevertheless, it might be needed to highlight some parts twice in order to show the “Once
through Test”.
If a logic block is highlighted, it means signal path through that block has been checked
during test execution.
In the same way, if a parameter appearing on the Functional Diagrams is highlighted, it
means that this parameter has been directly checked during test execution (i.e. the range of
a sensor during SCI53 execution).
Links (between several diagrams or within a diagram) are highlighted as follow:
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

· In case it has been checked during tests execution that the signal path is reaching the
“transmitter” part of the link, only the “transmitter” block is highlighted
· In case the signal path has also been checked after the “receiver” part of the link,
then both “transmitter” and “receiver” block are highlighted
Regarding field components, if there is connection to a transmitter or switchgear, the
respective block module will be highlighted only if the test is done with the field up to
switchgear or component.
Following color code will be used:
· Green : SCI52 and SCI53
· Yellow : Once Through Test
· Blue : CI69
· Orange : other commissioning steps
· Pink : V&V
Figure 4 shows an example of a highlighted DD4 Functional Diagram.
ECCN: N
AL: N
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 22 / 50
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract
ECCN: N
AL: N

FIGURE 4: EXAMPLE FOR HIGHLIGHTING FD

3.3.2.2. Stamp
3.3.2.2.1. Usual case
Figure 5 shows an example of a stamp used for the documentation of the test execution in
the Functional Diagrams. This stamp is used for each test that can be used to cover some
logics on a functional diagram, except for SCI52 and SCI53.
Note: If a test does not cover any additional logic compared to what is already highlighted,
there is no need to make a dedicated stamp for it.
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 23 / 50

FIGURE 5: EXAMPLE OF STAMP FOR FD HIGHLIGHTING


– Date: date of the test performance (not necessary date of highlighting)
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

– Test Ref: the test reference (e.g. Test Bay Test Protocol or Commissioning Step)
– Color in which the tested logic is highlighted.
– Name: Test executer name or the one who takes the responsibility that the test is
done e.g. by checking
• the existing Result Record Sheet (RRS) or
• the test report of Test Bay or
• the highlighted superseded Functional Diagrams of former tests
(without modification to the tested logic).
– Signature: Signature of the test executer, or the one who takes the responsibility that
the test is done, to validate that the test was performed
Note: For pre-highlighting, those stamps have to be filled without Date, Name, and Signature,
those will be filled only during final highlighting.
3.3.2.2.2. SCI52/53 case
In case of SCI52 and SCI53, to avoid overloading the Functional Diagrams, a small stamp
ECCN: N

will be used, closed to the related highlighted part, with the date and the signature.
AL: N

FIGURE 6: EXAMPLE OF STAMP FOR SCI52 AND SCI53


Note: For SCI52/53 pre-highlighting, there is no need of stamping; Stamp, Date and
Signature will be done only for final highlighting.

3.3.3. I&C Function Coverage Review Sheet


For each I&C function, a coverage review sheet will be created according to the following
template (see Figure 7). Those sheets aim at building a standardized overview of the test
coverage on a single page per I&C function.
They will be generated from a database collecting all relevant data. This database (called
I&C functions coverage database) is :
· created, managed and initialized by I&C commissioning team,
· filled by process commissioning and V&V teams.
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 24 / 50
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract
ECCN: N
AL: N

FIGURE 7: TEMPLATE FOR AN I&C FUNCTION COVERAGE REVIEW SHEET


Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 25 / 50

“Status” of the sheet will be mentioned, in the top right corner, using the two following steps:
· PREL: From the sheet initialization, and during execution of related tests
· FIN: Once all tests mentioned in the sheets are successfully executed and the sheet
is ready to be signed.
Each “I&C function coverage review sheet” is filled by the process commissioning engineer in
charge of the SCP to which the I&C function is allocated, and then, if needed, by the V&V
team for Test Bay activities, and by I&C commissioning team for CI69. Each sheet will be in
the end signed when all commissioning steps listed in the sheet are successfully executed.
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

For each SCP or pseudo SCP, relevant coverage review sheets are collected and gathered
in a dedicated appendix of the System Commissioning Report. In case a commissioning step
required for the coverage of an I&C function is planned to be executed in the frame of Phase
B, C or D, related System Commissioning Report will have to be updated after TOTO
milestone to include the finalized coverage review sheets.

3.3.4. Commissioning Instruction 69 (CI-69)


In case the highlighting of Functional Diagrams reveals that a part of an I&C function is not
covered by a commissioning step or a Test Bay activity, this will have to be filled by:
· either extending an existing commissioning instruction in the frame of the RFA
process (e.g. adding one check during an already planned commissioning
sequence).
· or creating a dedicated commissioning test procedure, which will be named CI-69. As
a consequence, each SCP (or pseudo SCP) may need to be updated in order to add
reference to such a CI-69.

3.3.5. Roles and Responsibilities


Master Functional Diagrams are located in the Main Control Room, to be available for
ECCN: N

highlighting during commissioning tests execution. Folders gathering Functional Diagrams


are under responsibilities of I&C commissioning as part of I&C systems master
documentation. Nevertheless, process commissioning and V&V team can have access to
AL: N

those folders for their own highlighting scope directly in the MCR, or in TSC (Technical
Service Center).
3.3.5.1. I&C commissioning
I&C commissioning teams are in charge of the following activities:
· Building, updating and managing I&C systems master documentation, including
Functional Diagrams to be highlighted
· Creation and management of the I&C functions coverage database.
· Pre-highlighting and highlighting of Functional Diagrams scope covered by SCI52,
SCI53 and CI69
· Elaboration and execution of CI69
3.3.5.2. Process commissioning
Process commissioning teams are in charge of the following activities:
· Elaboration of System Commissioning Program and related System Commissioning
Report
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 26 / 50

· Filling the I&C coverage review sheets for the part related to commissioning, including
check of data previously imported in the database by I&C commissioning (ex: list of
Functional Diagrams related to each function)
· Pre-highlighting and highlighting of Functional Diagrams scope related to the SCP
(expect scope already covered by SCI52, SCI53 and CI69)
· Review of CI69
Each process commissioning engineer is responsible of the I&C function coverage database
filling for the function related to its SCP.
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

3.3.5.3. V&V
V&V team is in charge of the following activities
· Highlighting of Functional Diagrams according to activities performed on Test Bay
· Filling the I&C coverage review sheets for the part related to V&V.
ECCN: N
AL: N
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 27 / 50

4. I&C FUNCTION TEST TYPES

Depending on the test purpose and test environment conditions a function needs be tested
as a whole chain or needs to be tested in overlapping manner.
As far as reasonable, the I&C functions test shall be performed with the process system
tests. These allows monitoring the correct behavior of the process function as whole and also
reduces the number of retest for the different aspects (process, I&C, plant, etc. aspect).
Depending on the test purpose and boundary conditions, signal simulation is required to
reach the required test conditions for each I&C function. The following sections describe
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

typical tests which are used for the I&C function tests.
TABLE 1: TEST TYPES
Test Type Description
TT1 Instrumentation Channel Test (according to SCI 53)
TT2 Actuation Channel Test (according to SCI 52)
Function test with process system actuation and
TT3
triggering signal simulation
Function test with signal triggering by the process and
TT4
without process system actuation
Function test in open or closed loop control with process
TT5
system
TT6 Function test without field equipment

4.1. I&C Function Test at I&C System Level


ECCN: N

4.1.1. I&C System Tests


I&C systems tests are performed on Test Bay. The aim of these tests is to check :
· the application software and all functionalities of I&C system, hardware and software.
AL: N

· HMI interface and general operation of the system (alarm appearing, actuator/sensor
operation).
These tests ensure that the implementation and correct operation of the main functionalities
related to the logics modules are correct on a full coverage basis (for software).
Further details are in the I&C system Master Test Reports, [3] and [7] - [11].

4.1.2. I&C Functions and related Tests


The aim of I&C functional tests on Test Bay is to validate the implementation of I&C
functions, in the application software. This validation phase on final I&C cabinets is
necessary, to detect potential problems in safety related functions before commissioning
phase.
The I&C function logics are tested in the Test Bay from I&C system input module to output
module. One I&C function can be allocated in one or more process systems, and from I&C
system point of view, in one or more cabinets. Therefore groups of cabinets are tested
together to allow the full functional test of the I&C function. The cabinets which are tested
together are recorded in the test documentation.
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 28 / 50

Different tools like SIMIT, ERBUS, etc. are used to simulate and monitor input and output
channel of the I&C functions processed in the final system environment (I&C cabinets).
Tools like SIVAT are used for application software testing.
Further details see I&C system Master Test Reports, [3] and [7] - [11].
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

FIGURE 8: LEVEL 1FUNCTION TEST

4.2. Field Equipment Interface Tests

4.2.1. Instrumentation Channel Test (TT1)


ECCN: N

The purpose of the instrumentation channel test is to assure that binary and analog
measuring circuits are ready for use when the associated process systems are put into
operation.
AL: N

Each sensor signal shall be monitored in each connected I&C automation system. The
correct triggering of the setpoints and the correct assignment of the output signal of the
threshold module to all connected voting modules (2oo4, OR…) shall be checked against the
I&C function specification. Indications of analog and binary values shall be checked on SICS
and PICS.
It shall be ensured that with the instrumentation channel check no unwanted actuator actions
occurs (e.g. by interlocks or disconnection from the field at PACS level and/or switchgear
level).
Further details are specified in SCI 53 NI [15].
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 29 / 50
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

FIGURE 9: TEST COVERAGE – INSTRUMENTATION CHANNELS (TT1)

4.2.2. Actuation Channel Test (TT2)


The purpose of the actuation channel test is to ensure the commissioning of individual drives,
heaters, actuators, valves, etc. and their associative feeders and so permits their correct
operation together within a process system.
The manual individual actuation channel test shall be performed with the actuator equipment
commissioning of the process system. The related manual individual actuator control
functions including check-back signals are tested with the remote actuator control from PICS,
SICS and LCP.
ECCN: N

For I&C validation it is sufficient to operate the actuator itself only one time, for all other
actuator channel test the signal can be disconnected at switchgear level.
Standard Commissioning Instruction SCI 52 NI [14] provides the detail for the actuation
AL: N

channel test.
Note: Actuator controls from each connected automation system are tested with dedicated
test instructions defined by each I&C system SCP.
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 30 / 50
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

FIGURE 10: TEST COVERAGE – ACTUATION CHANNELS (TT2)

4.3. Function Tests

4.3.1. Function Test with Process System Actuation and Triggering Signal
Simulation (TT3)
The purpose of this function test is to ensure the commissioning of startup/shutdown or
operation of the process system(s) as a functional unit. The triggering parameter setpoints
are simulated.
ECCN: N

The I&C function shall be tested in the frame of the related process function test. This test
type is applied for I&C function for which the triggering parameter setpoint cannot be reached
with the plant process (e.g. without damaging equipment or endangering equipment lifetime).
AL: N

For I&C validation, it is sufficient to operate the actuator itself only one time. For all other I&C
functions with the same actuator processing in other I&C systems, the signal to the field
equipment can be disconnected at switchgear level.
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 31 / 50
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

FIGURE 11: TEST COVERAGE –FUNCTION WITHOUT SENSORS (TT3)

4.3.2. Function Test with Signal Triggering by the Process and without Process
System Actuation (TT4)
The purpose of this function test is to ensure the commissioning of startup/shutdown or
operation of the process system(s) without field response. This test type is applied for
function for which an actuation of the field equipment leads to a damage, an unwanted
system configuration or endanger equipment lifetime.
The I&C function shall be tested in the frame of the related process function test.
ECCN: N

It shall be ensured that the I&C function test does not lead to an unwanted actuator action
(e.g. by interlocks or disconnection from the field at PACS level and/or switchgear level).
AL: N

FIGURE 12: TEST COVERAGE –FUNCTION WITHOUT ACTUATORS (TT4)


Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 32 / 50

4.3.3. Function Test in Open or Closed Loop Control with Process System (TT5)
The purpose of this function test is to ensure the commissioning of startup/shutdown or
operation of the process system(s) in an open or closed loop control configuration.
This type of test is performed with the process system in an open or closed loop control
configuration. The process parameter setpoints can be reached and related actuation can be
performed without endangering or damaging plant equipment.
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

FIGURE 13: TEST COVERAGE – COMPLETE FUNCTION (TT5)

4.3.4. Function Test without Field Equipment (TT6)


ECCN: N

This type of function test is only foreseen for functions which cannot be reasonable tested
with 4.3.1 or 4.3.2 and for function which requiring a pre-testing for safety reasons before
4.3.1, 4.3.2 or 4.3.3 test.
AL: N

This test type is applied for I&C Function for which the triggering parameter setpoint cannot
be reached with the plant process (e.g. without damaging equipment or endangering
equipment lifetime) and for function for which an actuation of the field equipment leads to a
damage or endanger equipment lifetime.
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 33 / 50
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

FIGURE 14: TEST COVERAGE – FUNCTION WITHOUT FIELD (TT6)

4.4. Test of Functions with Interlocks or Permissives


Depending on the plant conditions, I&C functions are activated or deactivated with interlocks
or permissives. During commissioning phase A and phase B (partly) all plant conditions
cannot be reached with the plant process in order to activate or de-activate I&C functions
under commissioning test. Therefore Interlocks and Permissives need to be simulated in the
I&C to allow a proper testing of the process / I&C functions.
Depending on the test purpose and test complexity the level of signal simulation can be
ECCN: N

selected. It needs to be ensured that with the simulation of the Interlock or Permissive no
other functions resulting from the I&C function under test are activated and an unwanted
actuation occurs. The interlock or permissive function itself needs to be tested at least once
as a complete chain.
AL: N

Similar approach can be performed for I&C function actuated signals like ATWS signal or SIS
signal in order to perform a proper testing of the related I&C function.
Simulation methods are further described in chapter 5.

4.5. Test coverage of function with signal voting or several triggering


parameters
For each I&C function test type TT3 – TT6 all instrumentation channels of a function need to
be tested at least once. This is done for each I&C automation system with test type TT1
which check the signal transfer from the sensor via signal conditioning to the I&C automation
system input. Inside the I&C automation system the signal is checked at the threshold
module and in addition at the connected voters modules (see also section 4.2.1).As far as
the function is not overlapping between I&C systems and has no connection to the field I&C
System Level Tests and I&C Functions tests at Test Bay can be credited.

4.5.1. Test Coverage of Function with Signal Voting


For an I&C function containing 2 out of 4 voting(s) at least two input channels have to be
triggered at the same time to get the required function response. The two other channels of
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 34 / 50

the 2 out of 4 voting are tested with the instrumentation channel test TT1. The different
combinations of the 4 channels do not need to be tested during the commissioning test on
site again because the voting logic test is already performed in the Test Bay.
Figure 15 shows a function test with a voter in the logic (example ESFAS function processed
in PS). For the functional chain test, two channels need to be triggered in order to get an
actuation and the field response. The two other channels are tested with test type TT1. With
this approach all input and output channels are tested. Figure 16 shows the logic of the
example of Figure 15 with signal voters in the 4 divisions. The outputs of the 4 voters are
triggered with the input of 2 instrumentation channels. With the instrumentation channel
checks all other inputs are tested down to the voter module.
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract
ECCN: N

FIGURE 15: TEST COVERAGE FOR FUNCTIONS WITH VOTER


AL: N

FIGURE 16: EXAMPLE TEST OF ESFAS FUNCTIONS

4.5.2. Test Coverage of Function Dedicated to Sensor Failure Handling


In general sensor failures are handled according to the Concept for I&C failure handling
corresponding to the I&C System [12] and [13]. All default behaviors and values are tested in
Test-bay. If there is a deviation of this behavior defined by Process Engineering dedicated
tests are performed either during Test Bay or need to be done during commissioning.
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 35 / 50

4.5.3. Test Coverage of Function with Several Triggering Parameters


For an I&C function containing an OR-gate combining several triggering parameters at least
one input channel has to be triggered to get the required function response. The other
triggering channels are tested with the instrumentation channel test TT1. The different
combinations of the channels connected to the OR-gate do not need to be tested during the
commissioning test on site again because the logic test is already performed in the Test Bay.
Figure 17 shows a function test with an OR-gate in the logic (example component protection
function in SAS). For the functional chain test at least one channel needs to be triggered in
order to get an actuation and the field response. The other channels are tested with test type
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

TT1. With this approach all input and output channels are tested. Figure 18 shows the logic
of the example of Figure 17 with an OR-gate combining several triggering parameters. The
outputs of the OR-gate are triggered with the input of at least one instrumentation channel.
With the instrumentation channel checks all other inputs are tested down to the voter
module.
ECCN: N
AL: N

FIGURE 17: TEST COVERAGE FOR FUNCTION WITH SEVERAL TRIGGERING


PARAMTERS

FIGURE 18: EXAMPLE TEST OF COMPONENT PROTECTION FUNCTION


Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 36 / 50

4.6. Allocation of I&C Functions to Test Types.


Figure 19 shows the decision tree which shall be applied for each function to define the test
type.
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

FIGURE 19: FLOW DIGAGRAM – FUNCTION ASSIGNMENT


I&C is required to get process systems in operation. With the instrumentation channel test
(TT1, see section4.2.1) and actuation channel test (TT2, see section 4.2.2) the basic I&C
functions needed for each process function is tested. Manual or automatic startup and
shutdown sequences and closed loop controls used during normal operation are fully tested
ECCN: N

with the interaction of the I&C functions with the process system(s) during the process
system test. Direct indications of process parameters on PICS and SICS are tested with
instrumentation channel test (TT1). The individual control of actuators from PICS and SICS
are tested with the actuation channel test (TT2).
AL: N

Process functions including the related I&C functions which are in standby during normal
plant or system operation requires to be tested in dedicated steps with either bringing the
plant or process system in the required condition or by simulation the process conditions.
In the first step of the flow diagram in Figure 19, it needs to be decided whether the function
can be fully tested with the plant process including all subfunctions or if signal simulation is
required to test the function. As described in section 4.3 different test types can be applied.
As far as possible the I&C functions shall be tested within the final process environment. If
this is not possible, it shall be checked if the function can be tested in a simulated system or
plant condition. This can be done by simulating interlocks or permissives. If the triggering
plant parameters cannot be reached with the plant process, the instrumentation channels
can be simulated. In some cases the function can only be tested without field response in
order not to damage the equipment or stress the equipment unnecessarily. In exceptional
cases, the I&C function can only be tested with simulation and monitoring of the output signal
because the plant conditions cannot be reached and the field response would lead to
damages of the plant equipment. For this type of function adequate overlapping tests needs
to be applied to test the whole function.
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 37 / 50

4.7. Specific Function Tests


This chapter describes for some specific function types how the I&C need to be tested.
Depending on the process system specific boundary conditions may be required. Also these
types of functions are tested as far as possible and reasonable with the process. If not,
specific tests need to be defined.

4.7.1. Reactor Trip Functions


Reactor Trip functions shall be tested within the process SCP related of the main sensors
triggering the reactor trip function. Reactor Trip functions based on in-core and ex-core
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

instrumentation are tested within related instrumentation SCP.


For each I&C system at least one complete RT function chain, from sensor (conditioning) to
trip breaker/contactor, shall be tested. All other RT function processed in the same I&C
system can be tested without actuation of the trip breaker, trip contactors and rod pilots in
order not to endanger equipment lifetime unnecessarily. All initiation channels shall be tested
as described in section 4.5.1.
For PS, one RT function per subsystem (A/B) shall be tested from sensor input down to the
actuation of the trip breaker undervoltage coil, trip contactors and rod pilot. With this test the
RT checkback signal including signal transfer to TGI (turbine trip signal) and MFW full load
isolation valves. All other RT functions in PS can be tested without active opening of the
main trip breakers, contactor and rod pilots.
For HBS, one RT function shall be tested from sensor input down to the actuation of the trip
breaker shunt-trip coil. All other RT functions in HBS can be tested without active opening of
the main trip breakers.
For SAS, one RT function shall be tested from sensor input down to the actuation of the trip
breaker shunt-trip coil. All other RT functions in SAS can be tested without active opening of
the main trip breakers.
ECCN: N

Correct indication of the reactor trip actuation shall be checked on SICS and PICS.
AL: N

FIGURE 20: REACTOR TRIP FUNCTION TEST

4.7.2. ESFAS Functions


ESFAS functions shall be tested within the process SCP related to the main actuators
triggered by the ESFAS function. For different ESFAS function acting on the same actuator
processed in the same I&C system, the full function chain from sensor (conditioning) to
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 38 / 50

actuator shall be tested at least once. All other ESFAS function processed in the same I&C
system can be tested without actuation of the actuator in order not to endanger equipment
lifetime unnecessarily. The initiation channels shall be tested as described in section 4.5.
ESFAS backup functions in HBS and SAS (DEC-A functions) shall be tested at least once
down to the switchgear level. As the process response is tested with the PS function, it is not
necessary to repeat the test for the backup functions. For example the backup SIS function
in SAS can only be tested to the PAC/SWGR level w/o real actuation of the actuators. MHSI
and LHSI water injection in the primary circuit is done one time with the PS I&C function.

4.7.3. LCO Functions


CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

LCO functions shall be tested within the process SCP related to the main sensors triggering
the LCO alarm function.
LCO functions monitoring process parameters controlled by a closed loop control shall be
tested when possible and reasonable with the closed loop control test.

4.7.4. Control Functions


Control functions shall be tested within the process SCP related to the main control actuator.
Checks of setpoint adjuster, control deviation, controller and actuator shall be tested as
described in SCI 54 [16].
The control behavior shall be checked by introducing a disturbance in the closed loop control
and if required optimized. If possible and reasonable the introduced disturbance can be
selected in such a way so that response of the LCO functions and maybe of the limitation
function is required.

4.7.5. Limitation and Operator Aid Functions


Limitation and Operator Aid Functions shall be tested within the process SCP related to the
main actuators triggered by the LIM or OAF function. If possible and reasonable the LIM or
ECCN: N

OAF function shall be tested with the closed loop control test. Otherwise dedicated tests
need to be defined.
AL: N

4.7.6. Component Protection Functions


Component Protection Functions are in general functions with a big number of input
channels combined with a “big OR-gate” triggering the component protection action. At least
one channel chain needs to be tested from sensor (conditioning) to actuator. For all other
channels of the component protection function, it is sufficient to test from sensor
(conditioning) up to threshold and the “big” OR-gate according to section 4.5. If reasonable
the signal can also be monitored at the I&C system output without actuation of the
switchgear in order not to endanger equipment lifetime unnecessarily (see also Figure 17).

4.7.7. EDG/SBO DLS Consumer Trip


EDG/SBO DLS consumer trip functions are manual switch-off commands from SICS for large
consumers required for manual startup and diesel loading. These set of function are tested
with the manual actuator control channel test from SICS (see TT2) of the corresponding
process SCP. No dedicated tests are required for this type of I&C functions.

4.7.8. Manual Containment Isolation


Manual containment isolation stage 1, stage 2 and manual outer containment isolation
functions are manual individual closure commands from SICS for containment isolation
valves. These set of function are tested with the manual actuator control channel test from
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 39 / 50

SICS (see TT2) of the corresponding process SCP. No dedicated tests are required for this
type of I&C functions.

4.7.9. Hazard Alarms


Hazard alarm functions shall be tested within the process SCP related to the main sensors
triggering the alarm function.
Hazard alarm H0 shall be tested within the I&C architecture SCP.
Hazard alarm H1 (PS, HBS and SSA) shall be tested with the related RT and ESFAS
function test.
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

4.7.10. Restart after Loss of Power: Undervoltage Monitoring


Regarding undervoltage monitoring for process functions which do not require a restart after
voltage recovery (TUM = 0s and TWS = 0s), the switch-off functionality shall be tested in the
frame of electrical system commissioning. If an automatic restart of motors and heaters after
an undervoltage event is required (TUM > 0s and TWS > 0s), the function shall be tested
with the process system, especially if specific boundary conditions of the process system are
required (opening or closing of valves or dampers to secure proper restart of the pump or
fan).

4.7.11. Automatic Evacuation Alarm


Automatic Evacuation Alarm functions shall be tested within the process SCP related to the
main sensors triggering the alarm function.

4.8. I&C System test coverage


The Plant Level I&C Architecture document [5] defines the main tasks of each I&C system
and in the document Allocation of I&C Functions [6] all I&C functions were assigned to one
ECCN: N

I&C system. Table 2 summarize the allocation of the different I&C functions according to the
flow chart in FAR.
TABLE 2: ALLOCATION OF I&C FUNCTIONS TO I&C SYSTEMS
AL: N

I&C Functional
Main function types
System SC
SC2 FA.0002
PS SC3 FA.0009, FA.0012, FA.DEV
SC4 FA.DEV
SC2 FA.0001
EDGSIC
SC3 FA.DEV
SICS SC3 FA.0004, FA.0017, FA.DEV
HBS SC3 FA.0006, FA.0008, FA.0009
SC3 FA.0005, FA.DEV
RCSL
SC4 FA.DEV
SC3 FA.0007, FA.0013, FA.0014
SA I&C
SC4 FA.DEV
SC3 FA.0009, FA.0010, FA.0011, FA.0015, FA.0016, FA.0022, FA.DEV
SAS SC4 FA.0022, FA.DEV
EYT FA.0022, FA.DEV
PAS1 SC4 FA.0019, FA.DEV
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 40 / 50

I&C Functional
Main function types
System SC
EYT FA.0019
SC4 FA.0021
PAS2
EYT FA.0021
SC4 FA.0020
TGI
EYT FA.0020
SC2 FA.DEV
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

SC3 FA.0003
SSS
SC4 FA.0018
EYT FA.0018

Table 3 to Table 7 provides for each I&C platforms (TXS, TXP, SICS (hardwired) and SSS)
general information how the related I&C functions need to be tested.

TABLE 3: TXS I&C SYSTEMS (COMPUTER BASED)


I&C systems (Safety class / Function Allocation)
PS (SC2 / FA.0002), PS (SC3 / FA.DEV)
PS H-Alarms H1, H4 (SC3 / FA.009. FA.0012) RCSL (SC3 / FA.0005, FA.DEV)

, SA I&C (SC3 / FA.0007, FA.DEV) RCSL (SC4 / FA.DEV)

SA I&C H-Alarms H5, H6 (SC3 / FA.0013,


FA.0014)

– All here above I&C systems were tested on Test Bay in order to validate the implementation
of I&C functions in the application software.
ECCN: N

– All here above I&C systems were fully tested in Test Bay from input modules to output
modules (island mode).
AL: N

– Interfaces between field and between I&C systems were not tested in Test Bay.
General – All voting modules input combinations were tested in Test Bay.

– PS: All calculation sub-modules were fully tested in Test Bay

– RCSL: All calculation / algorithms sub-modules were fully tested in Platform Simulator or
Test Bay from inputs to outputs
As per SCI53 all triggering sub functions outputs are checked down to the voting modules in all 4
divisions or to the concentration OR gate depending on the configuration.
All RT and ESFAS to be tested ONCE from the All functions to be tested with the here above
input (triggering device) of the triggering sub- restrictions:
function to outputs of the ESFAS (actuators). All
other sub-functions triggering the ESFAS to be Calculations and Algorithms modules need not
tested from input (sensor or conditioning module) to be retested on site in term of correctness of
to input of the ESFAS (Voting module, OR gate) the results.
Scope in order not to jeopardize any actuator lifetime by Only capability of functions to react on operator
of test numerous unnecessary actuations. requests and/or parameter measure / setpoint
All HBS & SA I&C functions to be tested ONCE deviation and right actuator motion way to be
from the input (triggering device) of the sub- checked.
function to outputs of the HBS or SA I&C See also section 4.7.3, 4.7.4 and 4.7.9.
function. In case of multiple initiators, only ONE
test from sensor to actuators, the other ones up
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 41 / 50

until output modules in order not to jeopardize


any actuator lifetime by numerous unnecessary
actuations.
See also section 4.7.1 4.7.2 and 4.7.9.
From 100% during process tests with additional From 100% during normal operation or CLT
simulated inputs up to 100% of simulated inputs. procedures with additional disruption to exceed
How to the normal operating zone then to enter in the
The ONCE THROUGH test is ideally performed extended operating zone.
do it? during a process test. The additional tests to
qualify all other triggering sub-functions are
mostly done in full simulation.
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

TABLE 4: TXS I&C SYSTEMS (NON-COMPUTER BASED)


I&C systems (Safety class / Function Allocation)
EDGSIC (SC2 / FA.0001), EDGSIC (SC3 / FA.DEV)
HBS (SC3 / FA.0006), HBS H-Alarms H0, H1 (SC3 / FA.0008, FA.009)

– HBS and EDGSIC cabinets were fully tested on Test Bay in order to validate the
implementation of I&C functions.

– With the HBS and EDGSIC tester the I&C functions processed in the I&C system are tested
General on site with the SCP JQ HBS and SCP XYA EDG. The tester devices are also used for the
periodic test of the I&C systems.
As per SCI53 all triggering sub functions outputs are checked down to the voting modules in all
4 divisions or to the concentration OR gate depending on the configuration.
All functions to be tested from the input (sensor or conditioning module) of the triggering sub-function
to outputs of the functions. Actuators switchgears being racked out or in test position in order to get
the output modules fed back (simulation of checkback signals in SWGR).
Scope
of test Per function, at least ONCE from the input (sensor or conditioning module) of the triggering sub-
ECCN: N

function to actuators with switchgears racked in.


See also section 4.7.1 4.7.2 and 4.7.9.
From 100% during process tests with additional simulated inputs up to 100% of simulated inputs.
How to
AL: N

do it? The ONCE THROUGH test is ideally performed during a process test. The additional tests to qualify
all other triggering sub-functions are mostly done in full simulation.
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 42 / 50

TABLE 5: TXP I&C SYSTEMS


I&C systems (Safety class / Function Allocation)
SAS (SC4, EYT / FA.0022, FA.DEV)

SAS (SC3 / FA.0016, FA.0022, FA.DEV) PAS1 (SC4, EYT /, FA.0019, FA.DEV)

SAS H-Alarms H1, H2, H3,H7 (SC3 / FA.0009, PAS1 (SC4, EYT /, FA.0021)
FA.0010, FA.0011, FA.0015) TGI (SC4, EYT /, FA.020)
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

– System Integration tests are performed to verify the correct installation and operability of the
SAS and PAS systems. System tests are executed to validate the technological features on
both SAS and PAS with differences of scope and coverage. The objective of the Application
SW tests is to check the proper communication between Automation System (AS) and
OM690, to verify that the design guidelines have been applied as defined and that their
proper functionality within the installed I&C environment is ensured. The Application
Software tests cover all I&C functions of the Automation System

General – SAS: I&C functions tests are performed to validate all SC3 I&C functions. During these SAS
Functional Tests on Test Bay, the functional requirements established by the process
engineers are validated in order to confirm that the requirements are implemented without
errors into the system. (further details see [7])
As per SCI53 all triggering sub functions outputs are checked down to the voting modules (in all 4
divisions) or to the concentration OR gate depending on the configuration.
As per SCI52 all TXP output channels are tested from the drive macros down FUM or PAC, SWGR
to the field equipment.
All functions to be tested from the input (sensor
or conditioning module) of the triggering sub-
function to outputs of the functions. Actuators
switchgears being racked out or in test position All functions to be tested 100% on site.
in order to get the output modules fed back
All functions to be tested from the input (sensor
Scope (simulation of checkback signals in SWGR).
ECCN: N

or conditioning module) of the triggering sub-


of test Per function, at least ONCE from the input function to outputs of the functions.
(sensor or conditioning module) of the triggering
sub-function to actuators with switchgears See also section 4.7.5 and 4.7.10.
racked in.
AL: N

See also section 4.7.5, 4.7.9 and4.7.10.


Ideally during process test for at least the ONCE Ideally during process test for at least the ONCE
THROUGH test. THROUGH test.
How to
do it? From 100% during process test with additional From 100% during process test with additional
simulated inputs when required to 100% by simulated inputs when required to 100% by
inputs simulation. inputs simulation.
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 43 / 50

TABLE 6: SICS FUNCTIONS


I&C systems (Safety class / Function Allocation)

SICS, (SC3 / FA.0004, FA.0017, FA.DEV)

General – Hardwired interfaces between SCPSSA/SICS and SICS/PACS are not tested in Test Bay.

All indications on SICS shall be tested with TT1 (SCI 53).


CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

All indications can be re-checked after startup/stop or operation test of the related process systems.
Scope All individual manual control on SICS shall be tested with TT2 (SCI 52).
of test All individual manual control can be used for system startup/stop or operation tests of the related
process systems instead of PICS controls.
See also section 4.7.7 and 4.7.8.

How to From 100% during SCI 52 / SCI 53 tests.


do it? Ideally during a process test for at least the ONCE THROUGH test.

TABLE 7: SSS SYSTEMS


I&C systems (Safety class / Function Allocation)

SSS, (SC2/FA.DEV; SC3/FA.0003; SC4/FA.0018; EYT/FA.0018)

– SSS functions were tested during the factory acceptance tests and site acceptance tests
General
– Interfaces between I&C systems were not tested.

Scope SSS functions shall be tested with the process system startup/stop or operation test.
ECCN: N

of test
Ideally during process test for at least the ONCE THROUGH test.
How to
AL: N

do it? From 100% during process test with additional simulated inputs when required to 100% by inputs
simulation.
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 44 / 50

5. SIGNAL SIMULATION

For the commissioning of the I&C functions signals need to be simulated in order to allow
testing of the process system independent from other functions or plant state or if the
triggering conditions cannot be reached without endangering of damaging plant equipment.
How signal can be simulated in principle is described in the following sections. More details
can be found in [19].

5.1. Field instrumentation Simulation


CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

5.1.1. Analog Sensors (4..20mA)


Analog sensors providing a 4 to 20mA signal (p-, Dp sensors…) can be simulated as follow:
– Simulation by a physical calibrator for level (dP), pressure (P) and flow (dP)
measurements. The physical calibrator is mounted on request at the valve manifold
connected to the sensor.
– Simulation by an electrical calibrator can be done for standard measurements which
are connected to the I&C cables by a plug of company Harting. By disconnecting and
injection of a current (in general 4 to 20 mA) the sensor signal is simulated.
– Simulation using an electrical calibrator can be done if measurement is connected to
TXS signal conditioning (SCPSSA or TXS signal conditioning cabinets RCSL) and
TXS card SAA1. Connected measurement will be short-circuited on SAA1 (special
designed socket). Then signal can be simulated externally.
ECCN: N
AL: N

FIGURE 21: SENSOR SIMULATION – ANALOG (4..20MA)

5.1.2. Temperature Sensors


Simulation for temperature measurements PT100 or thermocouple is possible. Following
location for simulation is possible:
– Simulation by a resistor decade or thermocouple simulator at the sensor which is
connected to the I&C cables by a plug.
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 45 / 50

– Simulation using a resistor decade or thermocouple simulator can be done if


temperature measurement is connected to TXS signal conditioning (SCPSSA or TXS
signal conditioning cabinets RCSL) and TXS card STT1.
– Information: After connection of simulator or later the measurement the TXS card
STT1 must be reset.
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

FIGURE 22: SENSOR SIMULATION – TEMPERATURE

5.1.3. Frequency Sensors


Simulation for frequency measurement is possible. Following location for simulation is
possible:
ECCN: N

– Simulation by a frequency generator at the sensor which is connected to the I&C


cables by a plug.
– Simulation by using a frequency generator if speed measurement is connected to TXS
AL: N

signal conditioning (SCPSSA or TXS signal conditioning cabinets RCSL) and TXS
card SSC1. The simulation will be enabled by an external release signal (hardwired to
SSC1).

FIGURE 23: SENSOR SIMULATION – FREQUENCY

5.1.4. Binary Sensors


Binary sensors can be simulated in different locations:
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 46 / 50

– Simulation by a physical calibrator for level (dP), pressure (P) and flow (dP)
measurements. The physical calibrator is mounted on request at the valve manifold
connected to the sensor.
– Simulation by a binary simulator (jumper / bridge) at the sensor which is connected to
the I&C cables by a plug.
– Simulation by using a binary simulator (jumper / bridge) or TDI1 interface if binary
sensor is connected to TXS signal conditioning (SCPSSA or TXS signal conditioning
cabinets RCSL) and TXS card SBC1.
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

FIGURE 24: SENSOR SIMULATION – BINARY


ECCN: N

5.1.5. Rod Position Sensors


The control rods position measurement can be simulated in the RPMU cabinets by means of
a programmed and built-in feature dedicated to periodic testing purposes.
AL: N

FIGURE 25: SENSOR SIMULATION – ROD POSITION

5.1.6. Neutron Flux Measurement (SRD, IRD, PRD and SPND) sensors
The neutron flux sensors simulation can be performed in the SCPSSA of the neutron flux
measurements by means of the built-in simulation modules for neutron flux measurements.
However, in order to simulate a flux level a dedicated coding device describing (12 digits) all
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 47 / 50

necessary parameters must be designed and fit at the interface of the TXS signal
conditioning cabinet to get the right simulation done. The simulated flux level is validated by
means of a key switch located in the TXS conditioning cabinet.
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

FIGURE 26: SENSOR SIMULATION – EXCORE / INCORE FLUX

5.1.7. N16 Activity Sensors


The N16 activity measurements can be simulated in the SCPSSA by means of the built-In
simulation modules in the SCPSSA. The simulation is done using the HMI module NZ21 and
validation by a key switch
ECCN: N
AL: N

FIGURE 27: SENSOR SIMULATION – N16


The N16 activity measurements can be simulated from the field

FIGURE 28: SENSOR SIMULATION – ACTIVITY


Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 48 / 50

5.2. Automation System Simulation

5.2.1. TXS Systems (computer-based)


Simulations in TXS can be performed in normal operation mode only by modifying
parameters.
All changeable parameters can be modified in operational mode. Thereby, the parameters
inside of the automation system (in the memory of the CPUs, located in the cabinets) are
modified, only. The TXS database on the service unit is not affected by such kind of
modification.
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

Following features in TXS for PS, SA I&C and RCSL are available:
– Release to perform a parameter modification must be available
– Parameter modification can be done parameter by parameter
– Modifications of parameters are also possible by a script where many parameters are
modified temporary by a batch. However, the script must be prepared. Therefore,
information regarding parameters to be modified should be available. The script can
be prepared and tested prio to testing by means of the TXS real-time simulator
RTSIM, which is located on the test server in the I&C commissioning department.
– Parameters change can be performed and restored easily
ECCN: N
AL: N

FIGURE 29: SIMULATION IN TXS (COMPUTER-BASED)

5.2.2. TXS Systems (non-computer-based)


In general, input signals from the field are connected in HBS and EDGSIC either to the
SPAM1 (analog signals) or to the SBC1 (binary signals) card. Therefore, following
simulations are possible for incoming external signals:
– SPAM1: Simulation of analog signals by using TDI1 interface
– SBC1: Simulation of binary signals using TDI1 interface
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 49 / 50
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

FIGURE 30: SIMULATION IN TXS (NON-COMPUTER-BASED)

5.2.3. TXP System


There are several possibilities to perform simulations without modifying the software code:
– For TXP this is possible at the entrance of dedicated input cards as long as the
software input module is not labeled with ANC. The simulated signal is indicated with
the letter S and corresponding information is transferred to PICS.
Signals received in TXP via the module labeled with ANC are in general signals,
which are safety related signals (plant) provided by PS.
– Additional to this it is also possible to simulate status signals for drives, actuators and
feeders in TXP as long as the drive, actuator or feeder is not connected to PACS. The
simulated signal is indicated with the letter S and information is transferred to PICS.
ECCN: N

FIGURE 31: SIMULATION IN TXP


AL: N

It is also possible to simulate signals by implementing simulation blocks. However this


requires a modification in the software. The simulation block can be enabled and disabled as
long it is available in the software. The simulation block shall be removed after its use.

5.3. Deactivation of actuators

5.3.1. Switchgear
If needed the electrical switchgears for medium and low voltage can be switched into test
mode. By this feature following control is still available:
– Commands by I&C systems
– Feedbacks to I&C systems
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE 50 / 50

FIGURE 32: DEACTIVATION OF ACTUATORS AT SWGR


CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

5.3.2. PACS
It is possible to block all commands to the electrical switchgear without suppression of
command signals of connected I&C systems. It is done by a coding plug used for TXS
module AV42.
Important information: This blocking of outgoing commands is not applicable for PAC-B
modules. There safety related commands have higher priority than the coding plug.

FIGURE 33: DISABLE ALL OUTPUT COMMANDS TO SWGR


ECCN: N

5.3.3. TXS automation system


All outputs can be disabled for TXS systems PS, SA I&C and RCSL by setting the SVE2-
AL: N

CPUs into test mode. The precondition is the permission to put the system into test mode
(“Permission Test / Diagnosis) is available. Following aspects need to be considered:
– Each SVE2 can be set into test mode individually
– One complete division can be set into test mode
– Complete system can be set into test mode
– All emitting signals by a SVE2 set into test mode are indicated as invalid by a SVE2
which is still in operation mode
– By setting the complete system into test mode the output cards can be set individual
into operation or out of operation
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A1 / A141
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

APPENDIX A: PRELIMINARY I&C FUNCTIONS SCP ASSIGNMENT


ECCN: N
AL: N
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A2 / A141

With the preliminary I&C functions assignment each I&C function listed in FAR [6] is
assigned to one process or pseudo SCP. If an I&C functions involves more than one process
system the function is listed in several lines with the related process system and SCP
assignment.
Subfunctions of for example automatic functions (e.g. RFFR00493) or group commands
(RFFR00006) shall be tested as far as reasonable with the main subfunctions and their
related SCP. For this then the subfunctions are assigned to the process SCP of the main
subfunctions.
According to [20] functions which are not specific to any given mechanical, electrical or I&C
system, are put together in so-called "pseudo-systems", for which a specific test program is
defined and described in a SCP. In the Preliminary I&C Functions Assignment all I&C
functions for which a pseudo system SCP exist are pre-assigned to this specific SCP.
Following pseudo SCPs have an assignment of I&C functions:
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

TABLE 8: LIST OF PSEUDO SCP FOR I&C FUNCITON TESTING


SCP Name
SCP AIH Anti-Icing Heating
SCP CIT Containment Isolation Tests
SCP CLT Control Tests
SCP LOOP Loss Of Offsite Power Tests
SCP PST Power Source Transfer Tests
SCP UVP Under Voltage Protection of medium voltage and low voltage switchgears 1
I&C functions which are assigned to Turbine Island like some SSS (Siemens), TGI (Siemens)
and PAS2 (Siemens) are in the scope of Siemens commissioning activities. Detailed
assignment to SCPs is in the scope of Siemens. These I&C functions are tested according to
CWS 4 TI [21].
TABLE 9: PRELIMINARY I&C FUNCTIONS ASSIGNMENT
Function Safety I&C Preliminary
Function Name System
Label Class System SCP
ECCN: N

JNA; JND;
RFFR00000 SIS switch-off MHSI (train by train) SC4 SAS SCP JN
JNG, JNK
JNA; JND;
RFFR00001 SIS switch-off LHSI (train by train) SC4 SAS SCP JN
AL: N

JNG, JNK
JNA; JND;
RFFR00002 SIS switch-off MHSI (train by train) SC4 SAS SCP JN
JNG, JNK
JNA; JND;
RFFR00003 SIS switch-off LHSI (train by train) SC4 SAS SCP JN
JNG, JNK
JNA; JND;
RFFR00004 SIS switch-off MHSI (train by train) SC3 SICS SCP JN
JNG, JNK
JNA; JND;
RFFR00005 SIS switch-off LHSI (train by train) SC3 SICS SCP JN
JNG, JNK
JNA; JND;
RFFR00006 SIS actuation MHSI (train by train) SC4 SAS SCP JN
JNG, JNK
RFFR00006 SIS actuation MHSI (train by train) KAA, KAB SC4 SAS SCP JN

1
The functions Restart after loss of power: Undervoltage monitoring are assigned first to the related process
SCP because some of these functions contain also a process related function. Functions which have no process
related function can be directly re-assigned to SCP UVP.
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A3 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
RFFR00006 SIS actuation MHSI (train by train) PEB/PEH SC4 SAS SCP JN
JNA; JND;
RFFR00007 SIS actuation LHSI (train by train) SC4 SAS SCP JN
JNG, JNK
RFFR00007 SIS actuation LHSI (train by train) KAA, KAB SC4 SAS SCP JN
RFFR00007 SIS actuation LHSI (train by train) PEB/PEH SC4 SAS SCP JN
RFFR00007 SIS actuation LHSI (train by train) QKA-QKC SC4 SAS SCP JN
JNA; JND;
RFFR00008 SIS actuation MHSI (train by train) SC4 SAS SCP JN
JNG, JNK
JNA; JND;
RFFR00009 SIS actuation LHSI (train by train) SC4 SAS SCP JN
JNG, JNK
JNA; JND;
RFFR00010 SIS LHSI actuation (train by train) SC3 SICS SCP JN
JNG, JNK
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

JNA; JND;
RFFR00011 SIS MHSI actuation (train by train) SC3 SICS SCP JN
JNG, JNK
RFFR00013 CCWS actuation from SICS KAA, KAB SC3 SICS SCP KAA/KAB
RFFR00014 ESWS actuation from SICS PEB/PEH SC3 SICS SCP PE
LHSI switch-over from cold leg injection to JNA; JND;
RFFR00015 SC4 SAS SCP JN
hot leg injection (train by train) JNG, JNK
LHSI switch-over from cold leg injection to JNA; JND;
RFFR00016 SC4 SAS SCP JN
hot leg injection (train by train) JNG, JNK
LHSI switch-over from cold leg injection to JNA; JND;
RFFR00017 SC3 SICS SCP JN
hot leg injection (train by train) JNG, JNK
Connection of LHSI in RHR mode train by JNA; JND;
RFFR00018 SC4 SAS SCP JN
train JNG, JNK
Connection of LHSI in RHR mode train by
RFFR00018 KAA, KAB SC4 SAS SCP JN
train
Connection of LHSI in RHR mode train by
RFFR00018 QKA-QKC SC4 SAS SCP JN
train
Connection of LHSI in RHR mode train by JNA; JND;
RFFR00019 SC4 SAS SCP JN
train JNG, JNK
Connection of LHSI in RHR mode train by JNA; JND;
RFFR00020 SC3 SICS SCP JN
train JNG, JNK
Isolation of LHSI in RHR mode train by JNA; JND;
RFFR00021 SC4 SAS SCP JN
ECCN: N

train JNG, JNK


Isolation of LHSI in RHR mode train by JNA; JND;
RFFR00022 SC4 SAS SCP JN
train JNG, JNK
Isolation of LHSI in RHR mode train by JNA; JND;
AL: N

RFFR00023 SC3 SICS SCP JN


train JNG, JNK
JNA; JND;
RFFR00024 SIS back-flushing SC4 SAS SCP JN
JNG, JNK
SIS accumulators isolation / opening (train JNA; JND;
RFFR00025 SC4 SAS SCP JN
by train) JNG, JNK
SIS accumulators isolation / opening (train JNA; JND;
RFFR00026 SC3 SICS SCP JN
by train) JNG, JNK
Manual control of LHSI heat exchanger
JNA; JND;
RFFR00027 valves after automatic actuation of safety SC4 SAS SCP JN
JNG, JNK
injection
Manual control of LHSI heat exchanger
JNA; JND;
RFFR00028 valves after automatic actuation of safety SC3 SICS SCP JN
JNG, JNK
injection
RFFR00029 RCP trip (RCP by RCP) BB SC4 SAS SCP JA-JE
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A4 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
JAA
JAC
JEA
RFFR00029 RCP trip (RCP by RCP) SC4 SAS SCP JA-JE
JEB
JEC
JEF, JEG
RFFR00030 RCP stop BB SC3 SICS SCP JA-JE
JAA
JAC
JEA
RFFR00031 RCP stop SC3 SICS SCP JA-JE
JEB
JEC
JEF, JEG
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

KBA, KBD, SCP KBA-KBD-


RFFR00032 CVCS charging flow isolation SC4 SAS
JEW JEW
KBA, KBD, SCP KBA-KBD-
RFFR00033 CVCS charging flow isolation SC3 SICS
JEW JEW
KBA, KBD, SCP KBA-KBD-
RFFR00034 Seal injection line isolation SC4 SAS
JEW JEW
KBA, KBD, SCP KBA-KBD-
RFFR00035 Seal injection line isolation SC3 SICS
JEW JEW
KBA, KBD, SCP KBA-KBD-
RFFR00036 CVCS letdown isolation SC4 SAS
JEW JEW
KBA, KBD, SCP KBA-KBD-
RFFR00037 CVCS HP letdown isolation SC3 SICS
JEW JEW
JNA; JND;
RFFR00038 CVCS LP letdown isolation SC3 SICS SCP JN
JNG, JNK
RFFR00039 EBS isolation (train by train) JDH SC4 SAS SCP JDH
JNA; JND;
RFFR00039 EBS isolation (train by train) SC4 SAS SCP JDH
JNG, JNK
RFFR00042 EBS actuation (train by train) JDH SC4 SAS SCP JDH
JNA; JND;
RFFR00042 EBS actuation (train by train) SC4 SAS SCP JDH
JNG, JNK
ECCN: N

Manual local opening/closing of the


RFFR00045 JDH SC4 SAS SCP JDH
header upstream EBS pumps
EBS header upstream EBS pumps
RFFR00046 JDH SC3 SICS SCP JDH
opening closure
AL: N

JAA
JAC
PSV opening / closing (PSV by PSV) JEA
RFFR00047 SC4 SAS SCP JA-JE
monitoring JEB
JEC
JEF, JEG

JAA
JAC
JEA
RFFR00048 PSV opening / closing (PSV by PSV) SC3 SICS SCP JA-JE
JEB
JEC
JEF, JEG
BFJ
RFFR00049 PZR heaters switch off SC4 RCSL SCP JA-JE
BFK
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A5 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
JAA
JAC
JEA
RFFR00049 PZR heaters switch off SC4 RCSL SCP JA-JE
JEB
JEC
JEF, JEG
BFJ
RFFR00050 PZR heaters switch off SC3 SICS SCP JA-JE
BFK
JAA
JAC
JEA
RFFR00050 PZR heaters switch off SC3 SICS SCP JA-JE
JEB
JEC
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

JEF, JEG
FAK
RFFR00051 Manual Containment isolation stage 1 SC3 PS SCP CIT
FAL
RFFR00051 Manual Containment isolation stage 1 GHC SC3 PS SCP CIT
RFFR00051 Manual Containment isolation stage 1 JDH SC3 PS SCP CIT
RFFR00051 Manual Containment isolation stage 1 JMM SC3 PS SCP CIT
RFFR00051 Manual Containment isolation stage 1 JMQ SC3 PS SCP CIT
RFFR00051 Manual Containment isolation stage 1 KAA, KAB SC3 PS SCP CIT
KBA, KBD,
RFFR00051 Manual Containment isolation stage 1 SC3 PS SCP CIT
JEW
RFFR00051 Manual Containment isolation stage 1 KLA SC3 PS SCP CIT
RFFR00051 Manual Containment isolation stage 1 KPL SC3 PS SCP CIT
RFFR00051 Manual Containment isolation stage 1 KTA-KTE SC3 PS SCP CIT
KUA, KUB,
RFFR00051 Manual Containment isolation stage 1 SC3 PS SCP CIT
KUF
LCA90
RFFR00051 Manual Containment isolation stage 1 SC3 PS SCP CIT
LCQ
RFFR00051 Manual Containment isolation stage 1 QJA-QJE SC3 PS SCP CIT
RFFR00051 Manual Containment isolation stage 1 QN SC3 PS SCP CIT
ECCN: N

SCB
RFFR00051 Manual Containment isolation stage 1 QFB SC3 PS SCP CIT
SCA
RFFR00051 Manual Containment isolation stage 1 SGB SC3 PS SCP CIT
AL: N

RFFR00052 Manual Containment isolation stage 2 BB SC3 PS SCP CIT


FAK
RFFR00052 Manual Containment isolation stage 2 SC3 PS SCP CIT
FAL
RFFR00052 Manual Containment isolation stage 2 GHC SC3 PS SCP CIT
JAA
JAC
JEA
RFFR00052 Manual Containment isolation stage 2 SC3 PS SCP CIT
JEB
JEC
JEF, JEG
RFFR00052 Manual Containment isolation stage 2 JDH SC3 PS SCP CIT
RFFR00052 Manual Containment isolation stage 2 JMM SC3 PS SCP CIT
RFFR00052 Manual Containment isolation stage 2 JMQ SC3 PS SCP CIT
RFFR00052 Manual Containment isolation stage 2 KAA, KAB SC3 PS SCP CIT
KBA, KBD,
RFFR00052 Manual Containment isolation stage 2 SC3 PS SCP CIT
JEW
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A6 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
RFFR00052 Manual Containment isolation stage 2 KLA SC3 PS SCP CIT
RFFR00052 Manual Containment isolation stage 2 KPL SC3 PS SCP CIT
RFFR00052 Manual Containment isolation stage 2 KTA-KTE SC3 PS SCP CIT
KUA, KUB,
RFFR00052 Manual Containment isolation stage 2 SC3 PS SCP CIT
KUF
RFFR00052 Manual Containment isolation stage 2 KUL SC3 PS SCP CIT
LCA90
RFFR00052 Manual Containment isolation stage 2 SC3 PS SCP CIT
LCQ
RFFR00052 Manual Containment isolation stage 2 QJA-QJE SC3 PS SCP CIT
RFFR00052 Manual Containment isolation stage 2 QN SC3 PS SCP CIT
RFFR00052 Manual Containment isolation stage 2 QUC SC3 PS SCP CIT
SCB
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

RFFR00052 Manual Containment isolation stage 2 QFB SC3 PS SCP CIT


SCA
RFFR00052 Manual Containment isolation stage 2 SGB SC3 PS SCP CIT
RFFR00053 Manual Containment isolation stage 1 GHC SC4 PAS 1 SCP GHC NI
RFFR00054 Manual Containment isolation stage 1 JDH SC4 SAS SCP JDH
RFFR00056 Manual Containment isolation stage 1 JMM SC4 PAS 1 SCP JMM
RFFR00057 Manual Containment isolation stage 1 JMQ SC4 SAS SCP JMQ
RFFR00058 Manual Containment isolation stage 1 KAA, KAB SC4 SAS SCP KAA/KAB
KBA, KBD, SCP KBA-KBD-
RFFR00059 Manual Containment isolation stage 1 SC4 SAS
JEW JEW
FAK
RFFR00060 Manual Containment isolation stage 1 SC4 SAS SCP FAK/FAL
FAL
RFFR00061 Manual Containment isolation stage 1 KPL SC4 PAS 1 SCP KPL
KUA, KUB, SCP KUA-KUB-
RFFR00063 Manual Containment isolation stage 1 SC4 SAS
KUF KUF
LCA90 SCP LCQ-
RFFR00064 Manual Containment isolation stage 1 SC4 PAS 1
LCQ LCA90
RFFR00065 Manual Containment isolation stage 1 QJA-QJE SC4 PAS 1 SCP QJ NI
RFFR00066 Manual Containment isolation stage 1 QN SC4 PAS 1 SCP QN
SCB
ECCN: N

RFFR00067 Manual Containment isolation stage 1 QFB SC4 PAS 1 SCP SCB1 NI
SCA
RFFR00068 Manual Containment isolation stage 1 SGB SC4 PAS 1 SCP SG
KBA, KBD, SCP KBA-KBD-
AL: N

RFFR00069 Manual Containment isolation stage 2 SC4 SAS


JEW JEW
RFFR00070 Manual Containment isolation stage 2 KAA, KAB SC4 SAS SCP KAA/KAB
RFFR00071 Manual Containment isolation stage 2 KUL SC4 SAS SCP KUL
RFFR00072 Manual Containment isolation stage 2 QUC SC4 PAS 1 SCP QUC NI
RFFR00073 Manual Containment isolation stage 1 KLA SC4 SAS SCP KLA
FAK
RFFR00074 Manual Containment isolation stage 1 SC3 SICS SCP FAK/FAL
FAL
RFFR00075 Manual Containment isolation stage 1 GHC SC3 SICS SCP GHC NI
RFFR00076 Manual Containment isolation stage 1 JDH SC3 SICS SCP JDH
RFFR00078 Manual Containment isolation stage 1 JMM SC3 SICS SCP JMM
RFFR00079 Manual Containment isolation stage 1 JMQ SC3 SICS SCP JMQ
RFFR00080 Manual Containment isolation stage 1 KAA, KAB SC3 SICS SCP KAA/KAB
KBA, KBD, SCP KBA-KBD-
RFFR00081 Manual Containment isolation stage 1 SC3 SICS
JEW JEW
RFFR00082 Manual Containment isolation stage 1 KPL SC3 SICS SCP KPL
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A7 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
RFFR00083 Manual Containment isolation stage 1 KTA-KTE SC3 SICS SCP KT10/11
KUA, KUB, SCP KUA-KUB-
RFFR00084 Manual Containment isolation stage 1 SC3 SICS
KUF KUF
LCA90 SCP LCQ-
RFFR00085 Manual Containment isolation stage 1 SC3 SICS
LCQ LCA90
RFFR00086 Manual Containment isolation stage 1 QJA-QJE SC3 SICS SCP QJ NI
RFFR00087 Manual Containment isolation stage 1 QN SC3 SICS SCP QN
SCB
RFFR00088 Manual Containment isolation stage 1 QFB SC3 SICS SCP SB NI
SCA
RFFR00089 Manual Containment isolation stage 1 SGB SC3 SICS SCP SG
RFFR00090 Manual Containment isolation stage 1 KLA SC3 SICS SCP KLA
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

KBA, KBD, SCP KBA-KBD-


RFFR00091 Manual Containment isolation stage 2 SC3 SICS
JEW JEW
RFFR00092 Manual Containment isolation stage 2 KAA, KAB SC3 SICS SCP KAA/KAB
RFFR00093 Manual Containment isolation stage 2 KUL SC3 SICS SCP KUL
RFFR00094 Manual Containment isolation stage 2 QUC SC3 SICS SCP QUC NI
RFFR00095 Containment filtered venting monitoring JMA30 SC4 SAS SCP JMA30
RFFR00096 Containment filtered venting monitoring JMA30 SC3 SICS SCP JMA30
RFFR00097 Containment isolation valve reopening JDH SC4 SAS SCP JDH
RFFR00098 Containment isolation valve reopening KAA, KAB SC4 SAS SCP KAA/KAB
KBA, KBD, SCP KBA-KBD-
RFFR00099 Containment isolation valve reopening SC4 SAS
JEW JEW
KUA, KUB, SCP KUA-KUB-
RFFR00100 Containment isolation valve reopening SC4 SAS
KUF KUF
RFFR00101 Containment isolation valve reopening KUL SC4 SAS SCP KUL
RFFR00102 Containment isolation valve reopening QUC SC4 PAS 1 SCP QUC NI
RFFR00103 Containment isolation valve reopening SGB SC4 PAS 1 SCP SG
RFFR00104 Containment isolation valve reopening JDH SC3 SICS SCP JDH
RFFR00105 Containment isolation valve reopening KAA, KAB SC3 SICS SCP KAA/KAB
KBA, KBD, SCP KBA-KBD-
RFFR00106 Containment isolation valve reopening SC3 SICS
JEW JEW
ECCN: N

KUA, KUB, SCP KUA-KUB-


RFFR00107 Containment isolation valve reopening SC3 SICS
KUF KUF
RFFR00108 Containment isolation valve reopening KUL SC3 SICS SCP KUL
AL: N

RFFR00109 Containment isolation valve reopening QUC SC3 SICS SCP QUC NI
RFFR00110 Containment isolation valve reopening SGB SC3 SICS SCP SG
Manual MSRT opening / closing (train by
RFFR00111 LBA SC4 SAS SCP LBA NI
train)
Manual MSRT opening / closing (train by
RFFR00112 LBA SC3 SICS SCP LBA NI
train)
Manual actuation of automatic cooldown
RFFR00113 LBA SC3 SAS SCP CLT
via MSRT (train by train)
Manual MSRCV setpoint increase (train
RFFR00114 LBA SC3 SAS SCP CLT
by train)
RFFR00116 Manual MSIV closure (train by train) LBA SC4 SAS SCP LBA NI
RFFR00117 Manual MSIV closure (train by train) LBA SC4 SAS SCP LBA NI
RFFR00118 Manual MSIV closure (train by train) LBA SC3 SICS SCP LBA NI
Manual MSIV bypass opening / closing
RFFR00119 LBA SC4 SAS SCP LBA NI
(train by train)
Manual MSIV bypass opening / closing
RFFR00120 LBA SC3 SICS SCP LBA NI
(train by train)
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A8 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Manual EFWS actuation / isolation (train
RFFR00121 LAR, LAS SC4 SAS SCP LAR-LAS
by train)
Manual EFWS actuation / isolation (train
RFFR00122 LAR, LAS SC3 SICS SCP LAR-LAS
by train)
Manual local opening/closure of header
RFFR00123 LAR, LAS SC3 SAS SCP LAR-LAS
downstream of EFWS pumps
Manual local opening/closure of header
RFFR00124 LAR, LAS SC3 SAS SCP LAR-LAS
upstream of EFWS pumps
RFFR00125 Manual MFW/SSS isolation (SG per SG) LAB SC4 SAS SCP LAB NI
RFFR00126 Manual MFW/SSS isolation (SG per SG) LAB SC3 SICS SCP LAB NI
Manual opening/closure of transfer LCA90 SCP LCQ-
RFFR00127 SC4 SAS
blowdown lines between SGs LCQ LCA90
Manual opening/closure of transfer LCA90 SCP LCQ-
RFFR00128 SC3 SICS
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

blowdown lines between SGs LCQ LCA90


Manual closure of SG blowdown (SG per LCA90 SCP LCQ-
RFFR00129 SC4 PAS 1
SG) LCQ LCA90
Manual closure of SG blowdown (SG per LCA90 SCP LCQ-
RFFR00130 SC3 SICS
SG) LCQ LCA90
Automatic closure of LHSI suction line and
miniflow lines isolation valves when hot JNA; JND;
RFFR00131 SC3 SAS SCP JN
leg suction line is not closed (train by JNG, JNK
train)
Manual RT (inducing TT, MFW-FL
RFFR00132 BU SC3 HBS SCP CLT
isolation)
Manual RT (inducing TT, MFW-FL
RFFR00132 JDA SC3 HBS SCP CLT
isolation)
Manual RT (inducing TT, MFW-FL
RFFR00132 LAB SC3 HBS SCP CLT
isolation)
JAA
JAC
JEA
RFFR00134 RCP seal No 1 leak-off line isolation SC3 SICS SCP JA-JE
JEB
JEC
JEF, JEG

EDG
ECCN: N

SAD
RFFR00136 Manual diesel startup in case of LOOP SC3 Safety SCP LOOP
SAL
I&C
EDG
XJA10-40 SCP XJA-XKA
RFFR00136 Manual diesel startup in case of LOOP SC3 Safety
AL: N

XKA10-40 10-20-30-40
I&C
XJA50/80,
RFFR00137 Manual diesel startup in case of LOOP SC3 SICS SCP LOOP
XKA50/80
EDG
RFFR00138 Manual diesel startup in case of LOOP SC3 safety SCP LOOP
I&C
BM, BN, BL,
RFFR00139 Manual diesel startup in case of LOOP SC3 SICS SCP LOOP
BR
RFFR00140 Manual diesel startup in case of LOOP BD SC3 SICS SCP LOOP
RFFR00141 Manual diesel startup in case of LOOP SC3 SICS SCP LOOP
RFFR00142 EDG DLS consumer trip PEB/PEH SC3 SICS SCP PE
KBA, KBD, SCP KBA-KBD-
RFFR00143 EDG DLS consumer trip SC3 SICS
JEW JEW
EDG DLS consumer trip
RFFR00144 QN SC3 SICS SCP QN
SBO DLS consumer trip
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A9 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
EDG DLS consumer trip
RFFR00145 JDH SC3 SICS SCP JDH
SBO DLS consumer trip
RFFR00146 EDG DLS consumer trip KLA SC3 SICS SCP KLA
FAK
RFFR00147 EDG DLS consumer trip SC3 SICS SCP FAK/FAL
FAL
RFFR00148 EDG DLS consumer trip KAA, KAB SC3 SICS SCP KAA/KAB
EDG DLS consumer trip
RFFR00149 LAR, LAS SC3 SICS SCP LAR-LAS
SBO DLS consumer trip
EDG DLS consumer trip JNA; JND;
RFFR00150 SC3 SICS SCP JN
SBO DLS consumer trip JNG, JNK
RFFR00151 EDG DLS consumer trip SAC SC3 SICS SCP SAC
RFFR00153 CCWS actuation from PICS KAA, KAB SC4 SAS SCP KAA/KAB
Actuation of Safety Chilled Water System
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

RFFR00154 QKA-QKC SC4 SAS SCP QK


(for SIS)
RFFR00155 ESWS actuation from PICS PEB/PEH SC4 SAS SCP PE
RFFR00157 PICS Sign-Of-Life signal SC3 SAS SCP I&C ARCH
FAK
RFFR00158 Fuel pool temperature SC3 SAS SCP FAK/FAL
FAL
FAK
RFFR00159 Fuel pool temperature SC3 SICS SCP FAK/FAL
FAL
FAK
RFFR00160 Fuel pool level SC3 SAS SCP FAK/FAL
FAL
FAK
RFFR00161 Fuel pool level SC3 SICS SCP FAK/FAL
FAL
RFFR00162 EBS flow JDH SC4 SAS SCP JDH
RFFR00163 EBS flow JDH SC3 SICS SCP JDH
RFFR00164 EBS tank level JDH SC4 SAS SCP JDH
RFFR00165 EBS tank level JDH SC3 SICS SCP JDH
JAA
JAC
JEA
RFFR00166 SG level (WR) SC4 SAS SCP JA-JE
JEB
JEC
ECCN: N

JEF, JEG

JAA
JAC
AL: N

JEA
RFFR00167 SG level (WR) SC3 PS SCP JA-JE
JEB
JEC
JEF, JEG

JAA
JAC
JEA
RFFR00168 SG level (WR) SC3 SICS SCP JA-JE
JEB
JEC
JEF, JEG

JAA
JAC
JEA
RFFR00169 SSSS position SC3 SAS SCP JA-JE
JEB
JEC
JEF, JEG
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A10 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
JAA
JAC
JEA
RFFR00170 HLEG temperature (WR) SC4 SAS SCP JA-JE
JEB
JEC
JEF, JEG

JAA
JAC
JEA
RFFR00171 HLEG temperature (WR) SC3 PS SCP JA-JE
JEB
JEC
JEF, JEG

JAA
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

JAC
JEA
RFFR00172 HLEG temperature (WR) SC3 SICS SCP JA-JE
JEB
JEC
JEF, JEG

JAA
JAC
JEA
RFFR00173 CLEG temperature (WR) SC4 SAS SCP JA-JE
JEB
JEC
JEF, JEG

JAA
JAC
JEA
RFFR00174 CLEG temperature (WR) SC3 PS SCP JA-JE
JEB
JEC
JEF, JEG

JAA
JAC
JEA
RFFR00175 HLEG loop level SC4 SAS SCP JA-JE
JEB
ECCN: N

JEC
JEF, JEG

JAA
AL: N

JAC
JEA
RFFR00176 HLEG loop level SC3 PS SCP JA-JE
JEB
JEC
JEF, JEG

JAA
JAC
JEA
RFFR00177 HLEG loop level SC3 SICS SCP JA-JE
JEB
JEC
JEF, JEG

JAA
JAC
JEA
RFFR00178 PZR level (NR) SC4 SAS SCP JA-JE
JEB
JEC
JEF, JEG
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A11 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
JAA
JAC
JEA
RFFR00179 PZR level (NR) SC3 PS SCP JA-JE
JEB
JEC
JEF, JEG

JAA
JAC
JEA
RFFR00180 PZR level (NR) SC3 SICS SCP JA-JE
JEB
JEC
JEF, JEG
SCP JKS
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

RFFR00181 RPVL top JKS SC3 SAS


RPVL/RPVDT
SCP JKS
RFFR00182 RPVL middle JKS SC3 SAS
RPVL/RPVDT
SCP JKS
RFFR00183 RPVL bottom JKS SC3 SAS
RPVL/RPVDT
SCP JKS
RFFR00184 core outlet temperature (2nd MAX) JKS SC3 PS
SPND/COT
SCP JKS
RFFR00185 MIN DELTA T SATN JKS SC3 PS
SPND/COT
RFFR00186 Neutron flux (IR) JKT SC4 SAS SCP JKT
RFFR00187 Neutron flux (IR) JKT SC3 PS SCP JKT
RFFR00188 Neutron flux (IR) JKT SC3 SICS SCP JKT
RFFR00189 Neutron flux (IR) JKT SC3 SA I&C SCP JKT
RFFR00190 Neutron flux (PR) JKT SC3 SICS SCP JKT
RFFR00191 hydrogen concentration JMU SC3 SAS SCP JMU
JNA; JND;
RFFR00192 HLEG pressure (NR) SC4 SAS SCP JN
JNG, JNK
JNA; JND;
RFFR00193 HLEG pressure (NR) SC3 SICS SCP JN
JNG, JNK
JNA; JND;
RFFR00194 HLEG pressure (WR) SC3 PS SCP JN
ECCN: N

JNG, JNK
JNA; JND;
RFFR00195 HLEG pressure (WR) SC4 SAS SCP JN
JNG, JNK
JNA; JND;
RFFR00196 HLEG pressure (WR) SC3 SICS SCP JN
AL: N

JNG, JNK
JNA; JND;
RFFR00197 SAB sump level SC4 SAS SCP JN
JNG, JNK
JNA; JND;
RFFR00198 SAB sump level SC3 PS SCP JN
JNG, JNK
JNA; JND;
RFFR00199 LHSI/RHR flow SC4 SAS SCP JN
JNG, JNK
JNA; JND;
RFFR00200 LHSI/RHR flow SC3 SICS SCP JN
JNG, JNK
JNA; JND;
RFFR00201 LHSI HLEG injection flow SC3 SAS SCP JN
JNG, JNK
JNA; JND;
RFFR00202 MHSI flow SC4 SAS SCP JN
JNG, JNK
JNA; JND;
RFFR00203 MHSI flow SC3 SICS SCP JN
JNG, JNK
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A12 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
JNA; JND;
RFFR00204 DP SIS sump strainer SC3 SAS SCP JN
JNG, JNK
JNA; JND;
RFFR00205 IRWST level SC4 SAS SCP JN
JNG, JNK
JNA; JND;
RFFR00206 IRWST level SC3 SICS SCP JN
JNG, JNK
JNA; JND;
RFFR00207 IRWST level SC3 SA I&C SCP JN
JNG, JNK
JNA; JND;
RFFR00208 IRWST temperature SC4 SAS SCP JN
JNG, JNK
JNA; JND;
RFFR00209 IRWST temperature SC3 SICS SCP JN
JNG, JNK
JNA; JND;
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

RFFR00210 IRWST temperature SC3 SA I&C SCP JN


JNG, JNK
RFFR00211 CONT dose rate JYK, KLK SC4 SAS SCP JYK - KLK
RFFR00212 CONT dose rate JYK, KLK SC3 SA I&C SCP JYK - KLK
RFFR00213 CONT dose rate JYK, KLK SC3 SICS SCP JYK - KLK
RFFR00214 CCWS pump flow KAA, KAB SC4 SAS SCP KAA/KAB
RFFR00215 CCWS pump flow KAA, KAB SC3 SICS SCP KAA/KAB
RFFR00216 CCWS temperature KAA, KAB SC4 SAS SCP KAA/KAB
RFFR00217 CCWS temperature KAA, KAB SC3 SICS SCP KAA/KAB
KBA, KBD,
RFFR00219 CVCS charging line boron concentration SC3 PS SCP CPF
JEW
RFFR00220 Containment pressure KLA SC4 SAS SCP CIT
RFFR00221 Containment pressure KLA SC3 PS SCP CIT
RFFR00222 Containment pressure KLA SC3 SICS SCP CIT
RFFR00223 EFWS flow downstream LAS pump LAR, LAS SC4 SAS SCP LAR-LAS
RFFR00224 EFWS flow downstream LAS pump LAR, LAS SC3 PS SCP LAR-LAS
RFFR00225 EFWS flow downstream LAS pump LAR, LAS SC3 SICS SCP LAR-LAS
RFFR00226 EFWS tank level LAR, LAS SC3 SAS SCP LAR-LAS
RFFR00227 EFWS tank level LAR, LAS SC3 SICS SCP LAR-LAS
RFFR00228 MS pressure LBA SC4 SAS SCP LBA NI
ECCN: N

RFFR00229 MS pressure LBA SC3 PS SCP LBA NI


RFFR00230 MS pressure LBA SC3 SICS SCP LBA NI
RFFR00231 MS activity JYK, KLK SC4 SAS SCP JYK - KLK
AL: N

RFFR00231 MS activity LBA SC4 SAS SCP JYK - KLK


RFFR00232 MS activity JYK, KLK SC3 PS SCP JYK - KLK
RFFR00232 MS activity LBA SC3 PS SCP JYK - KLK
RFFR00233 MS activity JYK, KLK SC3 SICS SCP JYK - KLK
RFFR00233 MS activity LBA SC3 SICS SCP JYK - KLK
RFFR00234 SG blowdown activity JYK, KLK SC3 SAS SCP JYK - KLK
RFFR00234 SG blowdown activity QUC SC3 SAS SCP JYK - KLK
JAA
JAC
JEA
RFFR00235 DP RCP SC3 SICS SCP JA-JE
JEB
JEC
JEF, JEG
RFFR00236 Emergency busbar voltage BD SC4 SAS SCP BB-BD
RFFR00237 Emergency busbar voltage BD SC3 SICS SCP BB-BD
RFFR00238 Emergency busbar frequency BD SC4 SAS SCP BB-BD
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A13 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
RFFR00239 Emergency busbar frequency BD SC3 SICS SCP BB-BD
KUA, KUB, SCP KUA-KUB-
RFFR00240 RCS boron concentration SC3 SAS
KUF KUF

BTD, BRU,
RFFR00241 12h UPS voltage BTP, BUE- SC4 SAS SCP BATT
BUH; BR; BTW

BTD, BRU,
RFFR00242 12h UPS current BTP, BUE- SC3 SA I&C SCP BATT
BUH; BR; BTW

JAA
JAC
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

JEA
RFFR00243 PDS valve opening monitoring SC4 SAS SCP JA-JE
JEB
JEC
JEF, JEG

JAA
JAC
JEA
RFFR00244 PDS valve opening SC3 SICS SCP JA-JE
JEB
JEC
JEF, JEG
SCP JKS
RFFR00245 core outlet temperature (WR) JKS SC4 PS
SPND/COT
SCP JKS
RFFR00246 Core outlet temperature (WR) JKS SC3 SA I&C
SPND/COT
SCP JKS
RFFR00247 core outlet temperature (WR) JKS SC3 SICS
SPND/COT
RFFR00250 Venturi scrubber level JMA30 SC4 SAS SCP JMA30
RFFR00251 Venturi scrubber level JMA30 SC3 SA I&C SCP JMA30
RFFR00252 RPV lower head outside wall temperature JMB SC4 SAS SCP JMB
RFFR00253 RPV lower head outside wall temperature JMB SC3 SA I&C SCP JMB
RFFR00254 Central cooling channel temperature JMB SC4 SAS SCP JMB
ECCN: N

RFFR00255 Central cooling channel temperature JMB SC3 SA I&C SCP JMB
RFFR00256 venting chimney temperature JMB SC4 SAS SCP JMB
RFFR00257 venting chimney temperature JMB SC3 SA I&C SCP JMB
AL: N

RFFR00258 CHRS sump level JMQ SC4 SAS SCP JMQ


RFFR00259 CHRS sump level JMQ SC3 SA I&C SCP JMQ
RFFR00260 Tank level downstream flooding valve JMQ SC4 SAS SCP JMQ
RFFR00261 Tank level downstream flooding valve JMQ SC3 SA I&C SCP JMQ
RFFR00262 Containment pressure SA JMQ SC4 SAS SCP JMQ
RFFR00263 Containment pressure SA JMQ SC3 SA I&C SCP JMQ
RFFR00264 CHRS inlet temperature JMQ SC4 SAS SCP JMQ
RFFR00265 CHRS inlet temperature JMQ SC3 SA I&C SCP JMQ
RFFR00266 CHRS outlet temperature JMQ SC4 SAS SCP JMQ
RFFR00267 CHRS outlet temperature JMQ SC3 SA I&C SCP JMQ
RFFR00268 CHRS pump pressure JMQ SC4 SAS SCP JMQ
RFFR00269 CHRS pump pressure JMQ SC3 SA I&C SCP JMQ
RFFR00270 CHRS flow rate JMQ SC4 SAS SCP JMQ
RFFR00271 CHRS flow rate JMQ SC3 SA I&C SCP JMQ
RFFR00272 flooding valve position JMQ SC4 SAS SCP JMQ
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A14 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
RFFR00273 flooding valve position JMQ SC3 SA I&C SCP JMQ
RFFR00274 CHRS containment spray actuation JMQ SC4 SAS SCP JMQ
RFFR00275 CHRS containment spray actuation JMQ SC3 SICS SCP JMQ
RFFR00276 CHRS base-mat cooling actuation JMQ SC4 SAS SCP JMQ
RFFR00277 CHRS base-mat cooling actuation JMQ SC3 SICS SCP JMQ
RFFR00278 CHRS sump backflushing JMQ SC4 SAS SCP JMQ
RFFR00279 CHRS sump backflushing JMQ SC3 SICS SCP JMQ
JNA; JND;
RFFR00280 CHRS sump backflushing SC3 SICS SCP JN
JNG, JNK
RFFR00281 Post accident sampling JMQ SC4 SAS SCP JMQ
RFFR00282 Post accident sampling JMQ SC3 SICS SCP JMQ
RFFR00283 Hydrogen mixing damper opening JMQ SC4 SAS SCP JMT
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

RFFR00283 Hydrogen mixing damper opening JMT SC4 SAS SCP JMT
RFFR00284 Hydrogen mixing damper opening JMT SC3 SA I&C SCP JMT
RFFR00285 hydrogen concentration JMU SC4 SAS SCP JMU
RFFR00286 hydrogen concentration JMU SC3 SA I&C SCP JMU
RFFR00287 moisture concentration JMU SC4 SAS SCP JMU
RFFR00288 moisture concentration JMU SC3 SA I&C SCP JMU
RFFR00290 BB *JMU ON/OFF JMU SC3 SA I&C SCP JMU
JNA; JND;
RFFR00291 HLEG pressure SA (WR) SC4 SAS SCP JN
JNG, JNK
JNA; JND;
RFFR00292 HLEG pressure SA (WR) SC3 SA I&C SCP JN
JNG, JNK
JNA; JND;
RFFR00293 HLEG pressure SA (NR) SC4 SAS SCP JN
JNG, JNK
JNA; JND;
RFFR00294 HLEG pressure SA (NR) SC3 SA I&C SCP JN
JNG, JNK
JNA; JND;
RFFR00295 DP CHRS sump strainer SC4 SAS SCP JN
JNG, JNK
JNA; JND;
RFFR00296 DP CHRS sump strainer SC3 SA I&C SCP JN
JNG, JNK
RFFR00297 Dedicated CCWS pump flow rate KAA50/80 SC4 SAS SCP KAA50/80
ECCN: N

RFFR00298 Dedicated CCWS pump flow rate KAA50/80 SC3 SA I&C SCP KAA50/80
RFFR00299 Dedicated CCWS JMQ HX flow rate KAA50/80 SC4 SAS SCP KAA50/80
RFFR00300 Dedicated CCWS JMQ HX flow rate KAA50/80 SC3 SA I&C SCP KAA50/80
AL: N

Dedicated CCWS ESWS HX inlet


RFFR00301 KAA50/80 SC4 SAS SCP KAA50/80
temperature
Dedicated CCWS ESWS HX inlet
RFFR00302 KAA50/80 SC3 SA I&C SCP KAA50/80
temperature
Dedicated CCWS ESWS HX outlet
RFFR00303 KAA50/80 SC4 SAS SCP KAA50/80
temperature
Dedicated CCWS ESWS HX outlet
RFFR00304 KAA50/80 SC3 SA I&C SCP KAA50/80
temperature
Dedicated CCWS CHRS HX inlet
RFFR00305 KAA50/80 SC4 SAS SCP KAA50/80
temperature
Dedicated CCWS CHRS HX inlet
RFFR00306 KAA50/80 SC3 SA I&C SCP KAA50/80
temperature
Dedicated CCWS CHRS HX outlet
RFFR00307 KAA50/80 SC4 SAS SCP KAA50/80
temperature
Dedicated CCWS CHRS HX outlet
RFFR00308 KAA50/80 SC3 SA I&C SCP KAA50/80
temperature
Dedicated CCWS surge tank safety valve
RFFR00309 KAA50/80 SC4 SAS SCP KAA50/80
position
RFFR00310 Dedicated CCWS surge tank safety valve KAA50/80 SC3 SA I&C SCP KAA50/80
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A15 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
position
RFFR00311 Dedicated CCWS surge tank level KAA50/80 SC4 SAS SCP KAA50/80
RFFR00312 Dedicated CCWS surge tank level KAA50/80 SC3 SA I&C SCP KAA50/80
RFFR00313 Dedicated CCWS surge tank pressure KAA50/80 SC4 SAS SCP KAA50/80
RFFR00314 Dedicated CCWS surge tank pressure KAA50/80 SC3 SA I&C SCP KAA50/80
RFFR00315 Dedicated CCWS actuation KAA50/80 SC4 SAS SCP KAA50/80
RFFR00316 Dedicated CCWS actuation KAA50/80 SC3 SICS SCP KAA50/80
RFFR00317 annulus ventilation flow rate KLB SC4 SAS SCP KLB
RFFR00318 annulus ventilation flow rate KLB SC3 SA I&C SCP KLB
RFFR00319 annulus pressure KLB SC4 SAS SCP KLB
RFFR00320 annulus pressure KLB SC3 SA I&C SCP KLB
RFFR00321 CHRS room ventilation closing KLC SC4 SAS SCP KLC
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

RFFR00322 CHRS room ventilation closing KLC SC3 SICS SCP KLC
RFFR00323 volume flow rate stack KLE SC4 SAS SCP KLE
RFFR00324 volume flow rate stack KLE SC3 SA I&C SCP KLE
RFFR00325 SAB ventilation volume flow rate KLC SC4 SAS SCP KLC
RFFR00326 SAB ventilation volume flow rate KLC SC3 SA I&C SCP KLC
RFFR00327 annulus ventilation dose rate JYK, KLK SC4 SAS SCP JYK - KLK
RFFR00328 annulus ventilation dose rate JYK, KLK SC3 SA I&C SCP JYK - KLK
RFFR00329 SAB ventilation dose rate JYK, KLK SC4 SAS SCP JYK - KLK
RFFR00330 SAB ventilation dose rate JYK, KLK SC3 SA I&C SCP JYK - KLK
RFFR00331 dose rate stack JYK, KLK SC4 SAS SCP JYK - KLK
RFFR00332 dose rate stack JYK, KLK SC3 SA I&C SCP JYK - KLK
RFFR00335 CHRS sample. Line pressure KUL SC4 SAS SCP KUL
RFFR00336 CHRS sample. Line pressure KUL SC3 SA I&C SCP KUL
RFFR00338 IRWST atmosphere sampling (BB *KUL) KUL SC3 SA I&C SCP KUL
RFFR00339 MSIV position LBA SC4 SAS SCP LBA NI
RFFR00340 MSIV position LBA SC3 SA I&C SCP LBA NI
RFFR00341 MSRIV position LBA SC4 SAS SCP LBA NI
RFFR00342 MSRIV position LBA SC3 SA I&C SCP LBA NI
RFFR00343 Dedicated ESWS flow rate PEB/PEH SC4 SAS SCP PE
ECCN: N

RFFR00344 Dedicated ESWS flow rate PEB/PEH SC3 SA I&C SCP PE


RFFR00345 Dedicated ESWS actuation PEB/PEH SC4 SAS SCP PE
RFFR00346 Dedicated ESWS actuation PEB/PEH SC3 SICS SCP PE
AL: N

FAK
RFFR00347 Outer Containment Isolation stage 1 & 2 SC3 SA I&C SCP CIT
FAL
RFFR00347 Outer Containment Isolation stage 1 & 2 GHC SC3 SA I&C SCP CIT
RFFR00347 Outer Containment Isolation stage 1 & 2 JDH SC3 SA I&C SCP CIT
RFFR00347 Outer Containment Isolation stage 1 & 2 JMM SC3 SA I&C SCP CIT
RFFR00347 Outer Containment Isolation stage 1 & 2 JMQ SC3 SA I&C SCP CIT
RFFR00347 Outer Containment Isolation stage 1 & 2 KAA, KAB SC3 SA I&C SCP CIT
KBA, KBD,
RFFR00347 Outer Containment Isolation stage 1 & 2 SC3 SA I&C SCP CIT
JEW
RFFR00347 Outer Containment Isolation stage 1 & 2 KLA SC3 SA I&C SCP CIT
RFFR00347 Outer Containment Isolation stage 1 & 2 KPL SC3 SA I&C SCP CIT
RFFR00347 Outer Containment Isolation stage 1 & 2 KTA-KTE SC3 SA I&C SCP CIT
KUA, KUB,
RFFR00347 Outer Containment Isolation stage 1 & 2 SC3 SA I&C SCP CIT
KUF
RFFR00347 Outer Containment Isolation stage 1 & 2 KUL SC3 SA I&C SCP CIT
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A16 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
LCA90
RFFR00347 Outer Containment Isolation stage 1 & 2 SC3 SA I&C SCP CIT
LCQ
RFFR00347 Outer Containment Isolation stage 1 & 2 QJA-QJE SC3 SA I&C SCP CIT
RFFR00347 Outer Containment Isolation stage 1 & 2 QN SC3 SA I&C SCP CIT
RFFR00347 Outer Containment Isolation stage 1 & 2 QUC SC3 SA I&C SCP CIT
SCB
RFFR00347 Outer Containment Isolation stage 1 & 2 QFB SC3 SA I&C SCP CIT
SCA
RFFR00347 Outer Containment Isolation stage 1 & 2 SGB SC3 SA I&C SCP CIT
JNA; JND;
RFFR00348 Manual Outer Containment isolation SC3 SICS SCP JN
JNG, JNK
RFFR00349 Manual Outer Containment isolation LAB SC3 SICS SCP LAB NI
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

RFFR00350 Manual Outer Containment isolation LAR, LAS SC3 SICS SCP LAR-LAS
RFFR00351 Manual Outer Containment isolation LBA SC3 SICS SCP LBA NI
Automatic Reactor Trip (RT) on Low SG
RFFR00352 BU SC3 HBS SCP JA-JE
level
JAA
JAC
Automatic Reactor Trip (RT) on Low SG JEA
RFFR00352 SC3 HBS SCP JA-JE
level JEB
JEC
JEF, JEG
Automatic Reactor Trip (RT) on Low SG
RFFR00352 JDA SC3 HBS SCP JA-JE
level
MFW-FL isolation triggered by hardwired
RFFR00353 LAB SC3 HBS SCP LAB NI
Reactor Trip
Turbine Trip triggered by hardwired
RFFR00354 SC3 HBS SCP CLT
Reactor Trip (on reactor trip check back)
Automatic Reactor Trip (RT) on High SG
RFFR00355 BU SC3 HBS SCP JA-JE
level
JAA
JAC
Automatic Reactor Trip (RT) on High SG JEA
RFFR00355 SC3 HBS SCP JA-JE
level JEB
ECCN: N

JEC
JEF, JEG
Automatic Reactor Trip (RT) on High SG
RFFR00355 JDA SC3 HBS SCP JA-JE
level
AL: N

Automatic Reactor Trip (RT) on high


RFFR00356 BU SC3 HBS SCP JA-JE
excore flux, power range
Automatic Reactor Trip (RT) on high
RFFR00356 JDA SC3 HBS SCP JA-JE
excore flux, power range
Automatic Reactor Trip (RT) on high
RFFR00356 JKT SC3 HBS SCP JA-JE
excore flux, power range
Automatic Reactor Trip (RT) on low SG
RFFR00357 BU SC3 HBS SCP LBA NI
pressure
Automatic Reactor Trip (RT) on low SG
RFFR00357 JDA SC3 HBS SCP LBA NI
pressure
Automatic Reactor Trip (RT) on low SG
RFFR00357 LBA SC3 HBS SCP LBA NI
pressure
Automatic Reactor Trip (RT) on low HL
RFFR00358 BU SC3 HBS SCP JN
pressure
Automatic Reactor Trip (RT) on low HL
RFFR00358 JDA SC3 HBS SCP JN
pressure
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A17 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Automatic Reactor Trip (RT) on low HL JNA; JND;
RFFR00358 SC3 HBS SCP JN
pressure JNG, JNK
Automatic Reactor Trip (RT) on high HL
RFFR00359 BU SC3 HBS SCP JN
pressure
Automatic Reactor Trip (RT) on high HL
RFFR00359 JDA SC3 HBS SCP JN
pressure
Automatic Reactor Trip (RT) on high HL JNA; JND;
RFFR00359 SC3 HBS SCP JN
pressure JNG, JNK
Automatic Reactor Trip (RT) on high SG
RFFR00360 BU SC3 HBS SCP LBA NI
pressure
Automatic Reactor Trip (RT) on high SG
RFFR00360 JDA SC3 HBS SCP LBA NI
pressure
Automatic Reactor Trip (RT) on high SG
RFFR00360 LBA SC3 HBS SCP LBA NI
pressure
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

Automatic Reactor Trip (RT) on low deltaP


RFFR00361 BU SC3 HBS SCP JA-JE
over RCP
JAA
JAC
Automatic Reactor Trip (RT) on low deltaP JEA
RFFR00361 SC3 HBS SCP JA-JE
over RCP JEB
JEC
JEF, JEG
Automatic Reactor Trip (RT) on low deltaP
RFFR00361 JDA SC3 HBS SCP JA-JE
over RCP
JAA
JAC
MFW Low Load isolation on High WR SG JEA
RFFR00362 SC3 HBS SCP JA-JE
level (SG related) JEB
JEC
JEF, JEG
MFW Low Load isolation on High WR SG
RFFR00362 LAB SC3 HBS SCPJA-JE
level (SG related)
JAA
JAC
Automatic CVCS HP & LP letdown JEA SCP KBA-KBD-
RFFR00363 SC3 HBS
ECCN: N

isolation on low RCS loop level JEB JEW


JEC
JEF, JEG
Automatic CVCS HP & LP letdown JNA; JND; SCP KBA-KBD-
RFFR00363 SC3 HBS
AL: N

isolation on low RCS loop level JNG, JNK JEW


Automatic CVCS HP & LP letdown KBA, KBD, SCP KBA-KBD-
RFFR00363 SC3 HBS
isolation on low RCS loop level JEW JEW
JAA
JAC
JEA
RFFR00364 Permissive P12 SC3 HBS SCP JA-JE
JEB
JEC
JEF, JEG

JAA
JAC
Automatic CVCS HP & LP letdown JEA
RFFR00365 SC3 HBS SCP JA-JE
isolation on low PZR pressure JEB
JEC
JEF, JEG
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A18 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Automatic CVCS HP & LP letdown JNA; JND;
RFFR00365 SC3 HBS SCP JA-JE
isolation on low PZR pressure JNG, JNK
Automatic CVCS HP & LP letdown KBA, KBD,
RFFR00365 SC3 HBS SCP JA-JE
isolation on low PZR pressure JEW
RFFR00366 RCP trip on low SG level (WR) BB SC3 HBS SCP JA-JE
JAA
JAC
JEA
RFFR00366 RCP trip on low SG level (WR) SC3 HBS SCP JA-JE
JEB
JEC
JEF, JEG
RCP trip on low DP over RCP and low
RFFR00367 BB SC3 HBS SCP JA-JE
PZR pressure
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

JAA
JAC
RCP trip on low DP over RCP and low JEA
RFFR00367 SC3 HBS SCP JA-JE
PZR pressure JEB
JEC
JEF, JEG
RFFR00368 RCP trip on high bearing temperature BB SC3 HBS SCP JA-JE
JAA
JAC
JEA
RFFR00368 RCP trip on high bearing temperature SC3 HBS SCP JA-JE
JEB
JEC
JEF, JEG
RFFR00369 Containment ventilation system isolation KLA SC3 HBS SCP CIT
Closure of CVCS HP letdown line on high
KBA, KBD, SCP KBA-KBD-
RFFR00370 temperature downstream the non- SC3 HBS
JEW JEW
regenerative heat exchanger

JAA
JAC
Closure of RCP seal N°1 leak-off line on
JEA
RFFR00371 Loss of RCP thermal barrier and seal SC3 HBS SCP JA-JE
ECCN: N

JEB
injection
JEC
JEF, JEG
Closure of RCP seal N°1 leak-off line on
KBA, KBD,
AL: N

RFFR00371 Loss of RCP thermal barrier and seal SC3 HBS SCP JA-JE
JEW
injection
JAA
JAC
Closure of gaseous waste processing
JEA
RFFR00372 system containment isolation valves on SC3 HBS SCP JA-JE
JEB
high PZR relief tank pressure
JEC
JEF, JEG

Closure of gaseous waste processing


RFFR00372 system containment isolation valves on KPL SC3 HBS SCP JA-JE
high PZR relief tank pressure
RFFR00373 Permissive P21 JKT SC3 HBS SCP JKT
MFW-FL isolation triggered by Reactor
RFFR00375 LAB SC3 SAS SCP LAB NI
Trip signal (SAS)
Turbine Trip triggered by hardwired
RFFR00376 SC3 SAS SCP CLT
Reactor Trip (on reactor trip check back)
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A19 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Manual isolation of VCT and switchover of FAK SCP KBA-KBD-
RFFR00377 SC4 SAS
the suction from VCT to IRWST FAL JEW
Manual isolation of VCT and switchover of SCP KBA-KBD-
RFFR00377 JMQ SC4 SAS
the suction from VCT to IRWST JEW
Manual isolation of VCT and switchover of JNA; JND; SCP KBA-KBD-
RFFR00377 SC4 SAS
the suction from VCT to IRWST JNG, JNK JEW
Manual isolation of VCT and switchover of KBA, KBD, SCP KBA-KBD-
RFFR00377 SC4 SAS
the suction from VCT to IRWST JEW JEW
Automatic SIS and PC actuations on hot
RFFR00379 BU SC3 SAS SCP CIT
leg pressure < min3
JAA
JAC
Automatic SIS and PC actuations on hot JEA
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

RFFR00379 SC3 SAS SCP CIT


leg pressure < min3 JEB
JEC
JEF, JEG
Automatic SIS and PC actuations on hot
RFFR00379 JDA SC3 SAS SCP CIT
leg pressure < min3
Automatic SIS and PC actuations on hot JNA; JND;
RFFR00379 SC3 SAS SCP CIT
leg pressure < min3 JNG, JNK
Automatic SIS and PC actuations on hot
RFFR00379 KAA, KAB SC3 SAS SCP CIT
leg pressure < min3
Automatic SIS and PC actuations on hot
RFFR00379 KLC SC3 SAS SCP CIT
leg pressure < min3
Automatic SIS and PC actuations on hot
RFFR00379 MAN SC3 SAS SCP CIT
leg pressure < min3
Automatic SIS and PC actuations on hot
RFFR00379 PEB/PEH SC3 SAS SCP CIT
leg pressure < min3
Automatic SIS and PC actuations on hot
RFFR00379 QKA-QKC SC3 SAS SCP CIT
leg pressure < min3
Automatic SIS and PC actuations on hot
RFFR00379 SAC SC3 SAS SCP CIT
leg pressure < min3
Automatic SIS and PC actuations on hot
RFFR00379 SAQ SC3 SAS SCP CIT
ECCN: N

leg pressure < min3


JNA; JND;
RFFR00382 Manual CHRS actuation SC4 SAS SCP JN
JNG, JNK
JNA; JND;
AL: N

RFFR00383 Manual CHRS actuation SC3 SICS SCP JN


JNG, JNK
JAA
JAC
JEA
RFFR00384 RCPB isolation SC3 SAS SCP CIT
JEB
JEC
JEF, JEG
RFFR00384 RCPB isolation JDH SC3 SAS SCP CIT
JNA; JND;
RFFR00384 RCPB isolation SC3 SAS SCP CIT
JNG, JNK
KBA, KBD,
RFFR00384 RCPB isolation SC3 SAS SCP CIT
JEW
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A20 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
JAA
JAC
Automatic SIS actuation on diversified JEA
RFFR00385 SC3 SAS SCP CIT
RCS loop level < min1 JEB
JEC
JEF, JEG
Automatic SIS actuation on diversified JNA; JND;
RFFR00385 SC3 SAS SCP CIT
RCS loop level < min1 JNG, JNK
Automatic SIS actuation on diversified
RFFR00385 KAA, KAB SC3 SAS SCP CIT
RCS loop level < min1
Automatic SIS actuation on diversified
RFFR00385 KLC SC3 SAS SCP CIT
RCS loop level < min1
Automatic SIS actuation on diversified
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

RFFR00385 PEB/PEH SC3 SAS SCP CIT


RCS loop level < min1
Automatic SIS actuation on diversified
RFFR00385 QKA-QKC SC3 SAS SCP CIT
RCS loop level < min1
Automatic SIS actuation on diversified
RFFR00385 SAC SC3 SAS SCP CIT
RCS loop level < min1
Automatic SIS actuation on diversified
RFFR00385 SAQ SC3 SAS SCP CIT
RCS loop level < min1
RFFR00386 Automatic RCP trip for SSSS actuation BB SC3 PS SCP JA-JE
JAA
JAC
JEA
RFFR00386 Automatic RCP trip for SSSS actuation SC3 PS SCP JA-JE
JEB
JEC
JEF, JEG
RFFR00386 Automatic RCP trip for SSSS actuation KAA, KAB SC3 PS SCP JA-JE
KBA, KBD,
RFFR00386 Automatic RCP trip for SSSS actuation SC3 PS SCP JA-JE
JEW
Automatic drop of all rods on loss of main
RFFR00387 BU SC3 RCSL SCP LAB NI
feedwater
Automatic drop of all rods on loss of main
RFFR00387 JDA SC3 RCSL SCP LAB NI
ECCN: N

feedwater
Automatic drop of all rods on loss of main
RFFR00387 LAB SC3 RCSL SCP LAB NI
feedwater
JAA
AL: N

JAC
JEA
RFFR00388 Permissive P12 SC3 SAS SCP JA-JE
JEB
JEC
JEF, JEG

JAA
JAC
Permissive P20 for activation of automatic
JEA
RFFR00389 SIS actuation on diversified RCS loop SC3 SAS SCP JA-JE
JEB
level < min1
JEC
JEF, JEG
Automatic RHR pump trip on low CCWS
JNA; JND;
RFFR00390 flowrate or high CCWS temperature (on SC3 SAS SCP JN
JNG, JNK
LHSI trains 1&4)
Automatic RHR pump trip on low CCWS
RFFR00390 flowrate or high CCWS temperature (on KAA, KAB SC3 SAS SCP JN
LHSI trains 1&4)
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A21 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Ensure the extraction of heat generated
by the SIS/RHR, KAA/LAR and JMU/KUL
RFFR00391 (Div 1 and 4 only) systems equipment to KLC SC4 SAS SCP KLC
maintain ambient temperatures below the
maximum limits
Maintain ambient temperature conditions
RFFR00392 below maximum limits for EFWS (30LAS) LAR, LAS SC4 SAS SCP SAC
pumps and 30KAA system components
Maintain ambient temperature conditions
RFFR00392 below maximum limits for EFWS (30LAS) SAC SC4 SAS SCP SAC
pumps and 30KAA system components
Service water pump building ventilation
(recirculation for pump rooms; Start of the
RFFR00393 SAQ SC4 SAS SCP SAQ
fans of the 30SAQ circulation cooling
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

units)
SCP JKS
RFFR00394 Dome temperature measurement JKS EYT PAS 1
RPVL/RPVDT
RFFR00395 Entry in Emergency Operation (H1) SC3 PS SCP LOOP
Entry in symptom based EOP (H2).
Reactor power greater than 0.1% and
RFFR00396 JKT SC3 SAS SCP JKT
time after reactor trip is greater than 60
min
Entry in symptom based EOP (H2). : RCS JNA; JND;
RFFR00397 SC3 SAS SCP JN
pressure > 180 barg JNG, JNK
JAA
JAC
Entry in symptom based EOP (H2). : RPV JEA
RFFR00398 SC3 SAS SCP JA-JE
brittle fracture JEB
JEC
JEF, JEG
Entry in symptom based EOP (H2). : RPV JNA; JND;
RFFR00398 SC3 SAS SCP JA-JE
brittle fracture JNG, JNK
JAA
JAC
Entry in symptom based EOP (H2). : Loss JEA
RFFR00399 SC3 SAS SCP LBA NI
ECCN: N

of all four steam generators JEB


JEC
JEF, JEG
Entry in symptom based EOP (H2). : Loss JNA; JND;
AL: N

RFFR00399 SC3 SAS SCP LBA NI


of all four steam generators JNG, JNK
Entry in symptom based EOP (H2). : Loss
RFFR00399 LBA SC3 SAS SCP LBA NI
of all four steam generators
Entry in symptom based EOP (H2). : JNA; JND;
RFFR00400 SC3 SAS SCP JN
IRWST temperature high JNG, JNK
Entry in symptom based EOP (H2). : Low JNA; JND;
RFFR00401 SC3 SAS SCP JN
level of the IRWST JNG, JNK
Entry in symptom based EOP (H2). :
RFFR00402 KLA SC3 SAS SCP KLA
Containment pressure over allowed value
Entry in symptom based EOP (H2). : High
RFFR00403 JMU SC3 SAS SCP JMU
hydrogen concentration inside *UJA*
Entry in symptom based EOP (H2). : High
RFFR00404 JYK, KLK SC3 SAS SCP JYK - KLK
dose rate containment
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A22 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
JAA
JAC
JEA
RFFR00405 Level RCS < MIN (H3) SC3 SAS SCP JA-JE
JEB
JEC
JEF, JEG
RFFR00405 Level RCS < MIN (H3) JKS SC3 SAS SCP JA-JE
JAA
JAC
JEA
RFFR00406 Superheating at RPV outlet > 40°C (H4) SC3 PS SCP JA-JE
JEB
JEC
JEF, JEG
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

RFFR00406 Superheating at RPV outlet > 40°C (H4) JKS SC3 PS SCP JA-JE
JAA
Entry into emergency operation after JAC
excessive core heatup when core outlet JEA
RFFR00407 SC3 SA I&C SCP JA-JE
temperature > 550°C or HLEG JEB
temperature > 390°C (H5) JEC
JEF, JEG
Entry into emergency operation after
excessive core heatup when core outlet
RFFR00407 JKS SC3 SA I&C SCP JA-JE
temperature > 550°C or HLEG
temperature > 390°C (H5)
SCP JKS
RFFR00408 Temperature core outlet > 650°C (H6) JKS SC3 SA I&C
SPND/COT
Entry in Fuel Pool EOP (H7): Logic for fuel FAK
RFFR00409 SC3 SAS SCP FAK/FAL
pool temperature FAL
Entry in Fuel Pool EOP (H7): Logic for fuel FAK
RFFR00410 SC3 SAS SCP FAK/FAL
pool level FAL
Safeguard building controlled area
RFFR00411 KLC SC3 SICS SCP KLC
ventilation
Non controlled mechanical area of
RFFR00412 SAC SC3 SICS SCP SAC
Safeguard building ventilation
ECCN: N

Electrical division of Safeguard building


RFFR00413 SAC SC3 SICS SCP SAC
ventilation
RFFR00414 Service water pump building ventilation SAQ SC3 SICS SCP SAQ
Process Radioactivity Monitoring:
RFFR00415 Component Cooling Water System JYK, KLK SC3 SAS SCP JYK - KLK
AL: N

(System KAA) monitoring


Process Radioactivity Monitoring:
RFFR00415 Component Cooling Water System KAA, KAB SC3 SAS SCP JYK - KLK
(System KAA) monitoring
Process Radioactivity Monitoring:
RFFR00416 Gaseous Waste Processing System JYK, KLK SC4 SAS SCP JYK - KLK
(System KPL) monitoring
Process Radioactivity Monitoring:
RFFR00416 Gaseous Waste Processing System KPL SC4 SAS SCP JYK - KLK
(System KPL) monitoring
Process Radioactivity Monitoring: Reactor
RFFR00417 Coolant System (System JEA, JEB, JEC) JYK, KLK SC4 SAS SCP JYK - KLK
monitoring
Process Radioactivity Monitoring: Reactor
KUA, KUB,
RFFR00417 Coolant System (System JEA, JEB, JEC) SC4 SAS SCP JYK - KLK
KUF
monitoring
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A23 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Process Radioactivity Monitoring:
Secondary System Monitoring: Steam
Generator Tube Leakage during Normal
RFFR00418 JYK, KLK SC4 SAS SCP JYK - KLK
Operation or Anticipated Operational
Occurrences: Condenser Air Removal
System (System MAJ))
Process Radioactivity Monitoring:
Secondary System Monitoring: Steam
Generator Tube Leakage during Normal MAJ
RFFR00418 SC4 SAS SCP JYK - KLK
Operation or Anticipated Operational MAQ
Occurrences: Condenser Air Removal
System (System MAJ))
Area Radiation and Airborne Radioactivity
JNA; JND;
RFFR00419 Monitoring: Airborne Radioactivity SC4 SAS SCP JYK - KLK
JNG, JNK
Monitoring
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

Area Radiation and Airborne Radioactivity


RFFR00419 Monitoring: Airborne Radioactivity JYK, KLK SC4 SAS SCP JYK - KLK
Monitoring
Area Radiation and Airborne Radioactivity
RFFR00420 JYK, KLK SC4 SAS SCP JYK - KLK
Monitoring: Local Dose Rate Monitoring
Effluent Radioactivity Monitoring:
RFFR00421 JYK, KLK SC4 SAS SCP JYK - KLK
Gaseous Effluent Monitoring
Effluent Radioactivity Monitoring: Liquid
RFFR00422 Effluent Monitoring System: Nuclear liquid JYK, KLK SC3 SAS SCP JYK - KLK
waste
Effluent Radioactivity Monitoring: Liquid
RFFR00422 Effluent Monitoring System: Nuclear liquid QUC SC3 SAS SCP JYK - KLK
waste
Personnel radiation monitoring: Dose
RFFR00424 JYC SC4 SSS SCP JYC
monitoring
Personnel radiation monitoring: Personnel
RFFR00425 JYC SC4 SSS SCP JYC
contamination monitors
Personnel radiation monitoring: Small
RFFR00426 JYC SC4 SSS SCP JYC
items contamination monitors
Personnel radiation monitoring: Laundry
RFFR00427 EYT SSS SCP JYC
contamination monitors
Personnel radiation monitoring: Portable
ECCN: N

RFFR00428 - - SCP JYK - KLK


and Mobile Instrumentation
Environmental Gamma Dose Rate
RFFR00429 SC4 PAS 1 SCP JYK - KLK
Monitoring
RFFR00430 Environmental Monitoring SC4 PAS 1 SCP JYK - KLK
AL: N

Measurements of gamma ray emitting


RFFR00431 KPC SC4 SSS SCP JYK - KLK
isotopes in waste drums
RFFR00432 Radiation Monitoring of Waste Packages - - SCP KPC
Assessing the radiation and activity
measurements of the plant to calculate
RFFR00433 the radiological consequences of activity CKG SC4 SSS SCP CKG
releases into the environment and to
assess allocated activity inside the plant.
RFFR00434 Launch boration KBC SC3 RCSL SCP KBC
Stabilization of the turbine load at fixed
RFFR00435 SC4 TGI TGI (Siemens)
setpoint

RFFR00436 Decrease of power down to 25% NP SC4 RCSL SCP CLT


Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A24 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
JAA
JAC
JEA
RFFR00437 MS pressure control by MSB I&C function SC4 RCSL SCP CLT
JEB
JEC
JEF, JEG
JNA; JND;
RFFR00437 MS pressure control by MSB I&C function SC4 RCSL SCP CLT
JNG, JNK
RFFR00437 MS pressure control by MSB I&C function LBA* SC4 RCSL SCP CLT
RFFR00437 MS pressure control by MSB I&C function MAN SC4 RCSL SCP CLT
RFFR00437 MS pressure control by MSB I&C function SC4 RCSL SCP CLT
KBA, KBD, SCP KBA-KBD-
RFFR00438 Manual Control of CVCS charging flow SC3 SAS
JEW JEW
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

RFFR00439 Monitoring of generator breaker ACA SC4 PAS 2 PAS 2 Siemens


SCP
BM, BN, BL,
RFFR00440 LV Switchgear voltage monitoring SC4 SAS BF/BH/BK/BL/B
BR
M/BN/BR
RFFR00441 Time after reactor trip SC4 PS SCP CLT
RFFR00442 Test of Protection System SC4 PS SCP JR PS
RFFR00443 Test of Severe accident I&C system SC4 SA I&C SCP JZ SA I&C
Test of Reactor Control and Surveillance
RFFR00444 SC4 RCSL SCP JS RCSL
System
RFFR00446 PS Sign-Of-Life signal SC3 PS SCP I&C ARCH
RFFR00447 RCSL Sign-Of-Life signal SC3 RCSL SCP I&C ARCH
RFFR00448 SAS Sign-Of-Life signal SC3 SAS SCP I&C ARCH
RFFR00450 ACT LCO P MSH abs > MAX S1 LBA* SC4 RCSL SCP LBA NI
RFFR00451 MSRV regulation “stand-by position” LBA SC3 SAS SCP LBA NI
RFFR00452 MSRV regulation “stand-by position” LCO LBA SC4 SAS SCP LBA NI
JAA
JAC
JEA
RFFR00453 Pressurizer Level Control SC3 RCSL SCP CLT
JEB
JEC
ECCN: N

JEF, JEG

JNA; JND;
RFFR00453 Pressurizer Level Control SC3 RCSL SCP CLT
JNG, JNK
AL: N

KBA, KBD,
RFFR00453 Pressurizer Level Control SC3 RCSL SCP CLT
JEW

BFJ
RFFR00454 MIN3 level function: PZR level SC3 RCSL SCP JA-JE
BFK
JAA
JAC
JEA
RFFR00454 MIN3 level function: PZR level SC3 RCSL SCP JA-JE
JEB
JEC
JEF, JEG
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A25 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
JAA
JAC
JEA
RFFR00455 MAX2 level function: PZR level SC3 RCSL SCP JA-JE
JEB
JEC
JEF, JEG
KBA, KBD,
RFFR00455 MAX2 level function: PZR level SC3 RCSL SCPJA-JE
JEW
JAA
JAC
JEA
RFFR00456 MIN2 level function: PZR level SC3 RCSL SCP JA-JE
JEB
JEC
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

JEF, JEG
KBA, KBD,
RFFR00456 MIN2 level function: PZR level SC3 RCSL SCP JA-JE
JEW
JAA
JAC
JEA
RFFR00457 SC3 RCPB isolation SC3 RCSL SCP CIT
JEB
JEC
JEF, JEG
JNA; JND;
RFFR00457 SC3 RCPB isolation SC3 RCSL SCP JN
JNG, JNK
KBA, KBD,
RFFR00457 SC3 RCPB isolation SC3 RCSL SCP JN
JEW
JAA
JAC
JEA
RFFR00459 ΔMAX function: Pressurizer level SC3 RCSL SCP CLT
JEB
JEC
JEF, JEG
KBA, KBD,
RFFR00459 ΔMAX function: Pressurizer level SC3 RCSL SCP CLT
JEW
ECCN: N

KBA, KBD, SCP KBA-KBD-


RFFR00460 SGTR level function SC3 RCSL
JEW JEW
JAA
AL: N

JAC
JEA
RFFR00461 Pressurizer level LCO SC4 RCSL SCP CLT
JEB
JEC
JEF, JEG

JAA
JAC
JEA
RFFR00462 High SG level operator aid function SC3 RCSL SCP CLT
JEB
JEC
JEF, JEG
RFFR00462 High SG level operator aid function LAB SC3 RCSL SCP CLT
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A26 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
JAA
JAC
JEA
RFFR00463 Low SG level operator aid function SC3 RCSL SCP CLT
JEB
JEC
JEF, JEG
RFFR00463 Low SG level operator aid function LAB SC3 RCSL SCP CLT
JAA
JAC
Very low flow SG level operator aid JEA
RFFR00464 SC3 RCSL SCP CLT
function JEB
JEC
JEF, JEG
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

Very low flow SG level operator aid


RFFR00464 LAB SC3 RCSL SCP CLT
function
JAA
JAC
JEA
RFFR00465 Steam Generator Level Control SC3 RCSL SCP CLT
JEB
JEC
JEF, JEG
RFFR00465 Steam Generator Level Control LAB SC3 RCSL SCP CLT
JAA
JAC
JEA
RFFR00466 High SG level LCO SC4 RCSL SCP CLT
JEB
JEC
JEF, JEG
JAA
JAC
JEA
RFFR00467 Low SG level LCO SC4 RCSL SCP CLT
JEB
JEC
JEF, JEG
ECCN: N

BFJ
RFFR00468 RCS pressure control function SC3 RCSL SCP CLT
BFK
JAA
JAC
AL: N

JEA
RFFR00468 RCS pressure control function SC3 RCSL SCP CLT
JEB
JEC
JEF, JEG
JNA; JND;
RFFR00468 RCS pressure control function SC3 RCSL SCP CLT
JNG, JNK
KBA, KBD,
RFFR00468 RCS pressure control function SC3 RCSL SCP CLT
JEW
JAA
JAC
JEA
RFFR00469 RCS pressure LCO SC4 RCSL SCP CLT
JEB
JEC
JEF, JEG
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A27 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP

JNA; JND;
RFFR00469 RCS pressure LCO SC4 RCSL SCP CLT
JNG, JNK

BFJ
RFFR00470 RCS Pressure Control SC3 RCSL SCP JA-JE
BFK
JAA
JAC
JEA
RFFR00470 RCS Pressure Control SC3 RCSL SCP JA-JE
JEB
JEC
JEF, JEG
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

JNA; JND;
RFFR00470 RCS Pressure Control SC3 RCSL SCP JA-JE
JNG, JNK
BFJ
RFFR00471 OAF Max2 / Max2 sliding / RHRS SC3 RCSL SCP CLT
BFK
JAA
JAC
JEA
RFFR00471 OAF Max2 / Max2 sliding / RHRS SC3 RCSL SCP CLT
JEB
JEC
JEF, JEG
JNA; JND;
RFFR00471 OAF Max2 / Max2 sliding / RHRS SC3 RCSL SCP CLT
JNG, JNK
KBA, KBD,
RFFR00471 OAF Max2 / Max2 sliding / RHRS SC3 RCSL SCP CLT
JEW
BFJ
RFFR00472 OAF RCP function SC3 RCSL SCP CLT
BFK
JAA
JAC
JEA
RFFR00472 OAF RCP function SC3 RCSL SCP CLT
JEB
JEC
ECCN: N

JEF, JEG
JNA; JND;
RFFR00472 OAF RCP function SC3 RCSL SCP CLT
JNG, JNK
KBA, KBD,
AL: N

RFFR00472 OAF RCP function SC3 RCSL SCP CLT


JEW
BFJ
RFFR00473 OAF Brittle fracture function SC3 RCSL SCP JA-JE
BFK
JAA
JAC
JEA
RFFR00473 OAF Brittle fracture function SC3 RCSL SCP JA-JE
JEB
JEC
JEF, JEG
RFFR00473 OAF Brittle fracture function JDH SC3 RCSL SCP JA-JE
JNA; JND;
RFFR00473 OAF Brittle fracture function SC3 RCSL SCP JA-JE
JNG, JNK
KBA, KBD,
RFFR00473 OAF Brittle fracture function SC3 RCSL SCP JA-JE
JEW
BFJ
RFFR00474 OAF SGTR pressure function SC3 RCSL SCP JA-JE
BFK
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A28 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
JAA
JAC
JEA
RFFR00474 OAF SGTR pressure function SC3 RCSL SCP JA-JE
JEB
JEC
JEF, JEG
JNA; JND;
RFFR00474 OAF SGTR pressure function SC3 RCSL SCP JA-JE
JNG, JNK
KBA, KBD,
RFFR00474 OAF SGTR pressure function SC3 RCSL SCP JA-JE
JEW
LAB*
LAC
RFFR00475 Request Main FW Pumps SC4 RCSL SCP CLT
LAH
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

LAJ
Limitation of reactor power with respect to
RFFR00476 BU SC3 RCSL SCP LAB NI
feedwater flowrate - Start-up phase
Limitation of reactor power with respect to
RFFR00476 JDA SC3 RCSL SCP LAB NI
feedwater flowrate - Start-up phase
Limitation of reactor power with respect to
RFFR00476 LAB SC3 RCSL SCP LAB NI
feedwater flowrate - Start-up phase
Limitation of reactor power with respect to
RFFR00477 feedwater flowrate - Loss of one Main BU SC3 RCSL SCP CLT
Feedwater Pump
Limitation of reactor power with respect to
RFFR00477 feedwater flowrate - Loss of one Main JDA SC3 RCSL SCP CLT
Feedwater Pump
Limitation of reactor power with respect to
RFFR00477 feedwater flowrate - Loss of one Main LAB SC3 RCSL SCP CLT
Feedwater Pump
Limitation of reactor power with respect to
RFFR00478 BU SC4 RCSL SCP CLT
generator power

Limitation of reactor power with respect to


RFFR00478 JDA SC4 RCSL SCP CLT
generator power
ECCN: N

Limitation of reactor power with respect to


RFFR00478 SC4 RCSL SCP CLT
generator power
Limitation of reactor power with respect to
RFFR00479 BU SC3 RCSL SCP JA-JE
heat removal
AL: N

JAA
JAC
Limitation of reactor power with respect to JEA
RFFR00479 SC3 RCSL SCP JA-JE
heat removal JEB
JEC
JEF, JEG
Limitation of reactor power with respect to
RFFR00479 JDA SC3 RCSL SCP JA-JE
heat removal
Limitation function: Closure of turbine inlet
RFFR00480 valves on MIN MSH pressure (setpoint SC4 RCSL SCP LBA NI
only)
RFFR00481 Reactor trip on PZR pressure < MIN2p BU SC2 PS SCP JA-JE
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A29 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
JAA
JAC
JEA
RFFR00481 Reactor trip on PZR pressure < MIN2p SC2 PS SCP JA-JE
JEB
JEC
JEF, JEG
RFFR00481 Reactor trip on PZR pressure < MIN2p JDA SC2 PS SCP JA-JE
RFFR00482 Reactor trip on PZR pressure > MAX2p BU SC2 PS SCP JA-JE
JAA
JAC
JEA
RFFR00482 Reactor trip on PZR pressure > MAX2p SC2 PS SCP JA-JE
JEB
JEC
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

JEF, JEG
RFFR00482 Reactor trip on PZR pressure > MAX2p JDA SC2 PS SCP JA-JE
RFFR00483 Reactor trip on PZR level > MAX1p BU SC2 PS SCP JA-JE
JAA
JAC
JEA
RFFR00483 Reactor trip on PZR level > MAX1p SC2 PS SCP JA-JE
JEB
JEC
JEF, JEG
RFFR00483 Reactor trip on PZR level > MAX1p JDA SC2 PS SCP JA-JE
Reactor trip on hot leg pressure (WR) <
RFFR00484 BU SC2 PS SCP JN
MIN1p
Reactor trip on hot leg pressure (WR) <
RFFR00484 JDA SC2 PS SCP JN
MIN1p
Reactor trip on hot leg pressure (WR) < JNA; JND;
RFFR00484 SC2 PS SCP JN
MIN1p JNG, JNK
Reactor trip on SG pressure drop >
RFFR00485 BU SC2 PS SCP LBA NI
MAX1p
Reactor trip on SG pressure drop >
RFFR00485 JDA SC2 PS SCP LBA NI
MAX1p
Reactor trip on SG pressure drop >
RFFR00485 LBA SC2 PS SCP LBA NI
ECCN: N

MAX1p
RFFR00486 Reactor trip on SG pressure < MIN1p BU SC2 PS SCP LBA NI
RFFR00486 Reactor trip on SG pressure < MIN1p JDA SC2 PS SCP LBA NI
RFFR00486 Reactor trip on SG pressure < MIN1p LBA SC2 PS SCP LBA NI
AL: N

RFFR00487 Reactor trip on SG pressure > MAX1p BU SC2 PS SCP LBA NI


RFFR00487 Reactor trip on SG pressure > MAX1p JDA SC2 PS SCP LBA NI
RFFR00487 Reactor trip on SG pressure > MAX1p LBA SC2 PS SCP LBA NI
RFFR00488 Reactor trip on SG level (NR) < MIN1p BU SC2 PS SCP JA-JE
JAA
JAC
JEA
RFFR00488 Reactor trip on SG level (NR) < MIN1p SC2 PS SCP JA-JE
JEB
JEC
JEF, JEG
RFFR00488 Reactor trip on SG level (NR) < MIN1p JDA SC2 PS SCP JA-JE
RFFR00489 Reactor trip on SG level (NR) > MAX1p BU SC2 PS SCP JA-JE
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A30 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
JAA
JAC
JEA
RFFR00489 Reactor trip on SG level (NR) > MAX1p SC2 PS SCP JA-JE
JEB
JEC
JEF, JEG
RFFR00489 Reactor trip on SG level (NR) > MAX1p JDA SC2 PS SCP JA-JE
RFFR00490 Reactor trip on MS activity > MAX1p BU SC2 PS SCP JYK - KLK
RFFR00490 Reactor trip on MS activity > MAX1p JDA SC2 PS SCP JYK - KLK
RFFR00490 Reactor trip on MS activity > MAX1p JYK, KLK SC2 PS SCP JYK - KLK
RFFR00490 Reactor trip on MS activity > MAX1p LBA SC2 PS SCP JYK - KLK
Reactor trip on containment pressure >
RFFR00491 BU SC2 PS SCP KLA
MAX1p
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

Reactor trip on containment pressure >


RFFR00491 JDA SC2 PS SCP KLA
MAX1p
Reactor trip on containment pressure >
RFFR00491 KLA SC2 PS SCP KLA
MAX1p
RFFR00492 Turbine trip on reactor trip checkback SC2 PS SCP CLT
RFFR00493 SIS actuation on PZR pressure < MIN3p BU SC2 PS SCP JN
JAA
JAC
JEA
RFFR00493 SIS actuation on PZR pressure < MIN3p SC2 PS SCP JN
JEB
JEC
JEF, JEG
RFFR00493 SIS actuation on PZR pressure < MIN3p JDA SC2 PS SCP JN
RFFR00493 SIS actuation on PZR pressure < MIN3p JDH SC2 PS SCP JN
JNA; JND;
RFFR00493 SIS actuation on PZR pressure < MIN3p SC2 PS SCP JN
JNG, JNK
RFFR00493 SIS actuation on PZR pressure < MIN3p KAA, KAB SC2 PS SCP JN
KBA, KBD,
RFFR00493 SIS actuation on PZR pressure < MIN3p SC2 PS SCP JN
JEW
RFFR00493 SIS actuation on PZR pressure < MIN3p KLC SC2 PS SCP JN
ECCN: N

RFFR00493 SIS actuation on PZR pressure < MIN3p PEB/PEH SC2 PS SCP JN
RFFR00493 SIS actuation on PZR pressure < MIN3p QKA-QKC SC2 PS SCP JN
RFFR00493 SIS actuation on PZR pressure < MIN3p SAC SC2 PS SCP JN
RFFR00493 SIS actuation on PZR pressure < MIN3p SAQ SC2 PS SCP JN
AL: N

RFFR00494 SIS actuation on Δ Psat < MIN1p BU SC2 PS SCP JN


JAA
JAC
JEA
RFFR00494 SIS actuation on Δ Psat < MIN1p SC2 PS SCP JN
JEB
JEC
JEF, JEG
RFFR00494 SIS actuation on Δ Psat < MIN1p JDA SC2 PS SCP JN
RFFR00494 SIS actuation on Δ Psat < MIN1p JDH SC2 PS SCP JN
JNA; JND;
RFFR00494 SIS actuation on Δ Psat < MIN1p SC2 PS SCP JN
JNG, JNK
RFFR00494 SIS actuation on Δ Psat < MIN1p KAA, KAB SC2 PS SCP JN
KBA, KBD,
RFFR00494 SIS actuation on Δ Psat < MIN1p SC2 PS SCP JN
JEW
RFFR00494 SIS actuation on Δ Psat < MIN1p KLC SC2 PS SCP JN
RFFR00494 SIS actuation on Δ Psat < MIN1p PEB/PEH SC2 PS SCP JN
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A31 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
RFFR00494 SIS actuation on Δ Psat < MIN1p QKA-QKC SC2 PS SCP JN
RFFR00494 SIS actuation on Δ Psat < MIN1p SAC SC2 PS SCP JN
RFFR00494 SIS actuation on Δ Psat < MIN1p SAQ SC2 PS SCP JN
RFFR00495 SIS actuation on RCS loop level < MIN1p BU SC2 PS SCP JN
JAA
JAC
JEA
RFFR00495 SIS actuation on RCS loop level < MIN1p SC2 PS SCP JN
JEB
JEC
JEF, JEG
RFFR00495 SIS actuation on RCS loop level < MIN1p JDA SC2 PS SCP JN
RFFR00495 SIS actuation on RCS loop level < MIN1p JDH SC2 PS SCP JN
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

JNA; JND;
RFFR00495 SIS actuation on RCS loop level < MIN1p SC2 PS SCP JN
JNG, JNK
RFFR00495 SIS actuation on RCS loop level < MIN1p KAA, KAB SC2 PS SCP JN
KBA, KBD,
RFFR00495 SIS actuation on RCS loop level < MIN1p SC2 PS SCP JN
JEW
RFFR00495 SIS actuation on RCS loop level < MIN1p KLC SC2 PS SCP JN
RFFR00495 SIS actuation on RCS loop level < MIN1p PEB/PEH SC2 PS SCP JN
RFFR00495 SIS actuation on RCS loop level < MIN1p QKA-QKC SC2 PS SCP JN
RFFR00495 SIS actuation on RCS loop level < MIN1p SAC SC2 PS SCP JN
RFFR00495 SIS actuation on RCS loop level < MIN1p SAQ SC2 PS SCP JN
RCP trip on ΔP over RCP < MIN1p and
RFFR00496 BB SC2 PS SCP JA-JE
SIS signal
JAA
JAC
RCP trip on ΔP over RCP < MIN1p and JEA
RFFR00496 SC2 PS SCP JA-JE
SIS signal JEB
JEC
JEF, JEG
LHSI/RHR train isolation on SAB sump
JNA; JND;
RFFR00497 level > MAX1p or SABpressure rise > SC2 PS SCP JN
JNG, JNK
MAX1p
ECCN: N

RFFR00498 Minimum CCWS temperature control KAA, KAB SC2 PS SCP KAA/KAB
JAA
JAC
JEA
AL: N

RFFR00499 RHR pump trip on ΔPsat < MIN2p SC2 PS SCP JN


JEB
JEC
JEF, JEG
JNA; JND;
RFFR00499 RHR pump trip on ΔPsat < MIN2p SC2 PS SCP JN
JNG, JNK
JAA
JAC
RHR pump trip on RCS loop level < JEA
RFFR00500 SC2 PS SCP JN
MIN2p JEB
JEC
JEF, JEG
RHR pump trip on RCS loop level < JNA; JND;
RFFR00500 SC2 PS SCP JN
MIN2p JNG, JNK
RFFR00501 Partial cooldown actuation on SIS signal LBA SC2 PS SCP JA-JE
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A32 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
JAA
JAC
Partial cooldown actuation on SG level JEA
RFFR00502 SC2 PS SCP JA-JE
(NR) > MAX2p JEB
JEC
JEF, JEG

LAB*
Partial cooldown actuation on SG level LAC
RFFR00502 SC2 PS SCP LBA NI
(NR) > MAX2p LAH
LAJ
Partial cooldown actuation on SG level
RFFR00502 LBA SC2 PS SCP LBA NI
(NR) > MAX2p
Partial cooldown actuation on SGTR and
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

RFFR00503 LBA SC2 PS SCP LBA NI


MSRT response signals
JAA
JAC
EFWS actuation on SG level (WR) < JEA
RFFR00504 SC2 PS SCP LAR-LAS
MIN2p JEB
JEC
JEF, JEG
EFWS actuation on SG level (WR) <
RFFR00504 KAA, KAB SC2 PS SCP LAR-LAS
MIN2p
EFWS actuation on SG level (WR) <
RFFR00504 KLC SC2 PS SCP LAR-LAS
MIN2p
EFWS actuation on SG level (WR) <
RFFR00504 LAR, LAS SC2 PS SCP LAR-LAS
MIN2p
EFWS actuation on SG level (WR) < LCA90
RFFR00504 SC2 PS SCP LAR-LAS
MIN2p LCQ
EFWS actuation on SG level (WR) <
RFFR00504 PEB/PEH SC2 PS SCP LAR-LAS
MIN2p
EFWS actuation on SG level (WR) <
RFFR00504 SAC SC2 PS SCP LAR-LAS
MIN2p
EFWS actuation on SG level (WR) <
RFFR00504 SAQ SC2 PS SCP LAR-LAS
MIN2p
RFFR00505 EFWS pump overflow protection LAR, LAS SC2 PS SCP LAR-LAS
ECCN: N

EFWS actuation on LOOP signal and SIS


RFFR00506 KAA, KAB SC2 PS SCP LOOP
signal
EFWS actuation on LOOP signal and SIS
RFFR00506 KLC SC2 PS SCP LOOP
signal
AL: N

EFWS actuation on LOOP signal and SIS


RFFR00506 LAR, LAS SC2 PS SCP LOOP
signal
EFWS actuation on LOOP signal and SIS LCA90
RFFR00506 SC2 PS SCP LOOP
signal LCQ
EFWS actuation on LOOP signal and SIS
RFFR00506 PEB/PEH SC2 PS SCP LOOP
signal
EFWS actuation on LOOP signal and SIS
RFFR00506 SAC SC2 PS SCP LOOP
signal
EFWS actuation on LOOP signal and SIS
RFFR00506 SAQ SC2 PS SCP LOOP
signal
JAA
JAC
EFWS isolation on SG level (WR)> JEA
RFFR00507 SC2 PS SCP LAR-LAS
MAX1p JEB
JEC
JEF, JEG
EFWS isolation on SG level (WR)>
RFFR00507 LAR, LAS SC2 PS SCP LAR-LAS
MAX1p
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A33 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
RFFR00508 MSRT opening on SG pressure > MAXp LBA SC2 PS SCP CLT
RFFR00509 MSRT isolation on SG pressure < MIN3p LBA SC2 PS SCP LBA NI
JAA
JAC
MSRT setpoint increase in SGi on SG
JEA
RFFR00560 level (NR) > MAX2p, if partial cooldown is SC2 PS SCP LBA NI
JEB
finished
JEC
JEF, JEG
MSRT setpoint increase in SGi on SG
RFFR00560 level (NR) > MAX2p, if partial cooldown is LBA SC2 PS SCP JA-JE
finished
MSRT setpoint increase in SGi on activity
RFFR00561 JYK, KLK SC2 PS SCP LBA NI
signal, if partial cooldown is finished
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

MSRT setpoint increase in SGi on activity


RFFR00561 LBA SC2 PS SCP LBA NI
signal, if partial cooldown is finished
MSIV closure on SG pressure drop >
RFFR00562 LBA SC2 PS SCP LBA NI
MAX1p
RFFR00563 MSIV closure on SG pressure < MIN1p LBA SC2 PS SCP LBA NI
JAA
JAC
MSIV closure in SGi on SG level (NR) > JEA
RFFR00564 SC2 PS SCP JA-JE
MAX2p, if partial cooldown is finished JEB
JEC
JEF, JEG
MSIV closure in SGi on SG level (NR) >
RFFR00564 LBA SC2 PS SCP JA-JE
MAX2p, if partial cooldown is finished
MSIV closure in SGi on activity signal, if
RFFR00565 JYK, KLK SC2 PS SCP LBA NI
partial cooldown is finished
MSIV closure in SGi on activity signal, if
RFFR00565 LBA SC2 PS SCP LBA NI
partial cooldown is finished
MFW full load closure on reactor trip
RFFR00566 LAB SC2 PS SCP CLT
checkback
MFW/SSS isolation on SG pressure drop
RFFR00567 LAB SC2 PS SCP LBA NI
> MAX2p
ECCN: N

MFW/SSS isolation on SG pressure drop


RFFR00567 LBA SC2 PS SCP LBA NI
> MAX2p
MFW/SSS isolation on SG pressure <
RFFR00568 LAB SC2 PS SCP LBA NI
MIN2p
MFW/SSS isolation on SG pressure <
AL: N

RFFR00568 LBA SC2 PS SCP LBA NI


MIN2p
JAA
JAC
MFW/SSS isolation on SG level (NR) > JEA
RFFR00569 SC2 PS SCP JA-JE
MAX1p JEB
JEC
JEF, JEG
MFW/SSS isolation on SG level (NR) >
RFFR00569 LAB SC2 PS SCP JA-JE
MAX1p
LAB*
MFW/SSS isolation on SG level (NR) > LAC
RFFR00569 SC2 PS SCP JA-JE
MAX1p LAH
LAJ
Containment isolation stage 1 on
FAK
RFFR00570 containment pressure > MAX1p or SIS SC2 PS SCP CIT
FAL
signal
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A34 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Containment isolation stage 1 on
RFFR00570 containment pressure > MAX1p or SIS GHC SC2 PS SCP CIT
signal
Containment isolation stage 1 on
RFFR00570 containment pressure > MAX1p or SIS JDH SC2 PS SCP CIT
signal
Containment isolation stage 1 on
RFFR00570 containment pressure > MAX1p or SIS JMM SC2 PS SCP CIT
signal
Containment isolation stage 1 on
RFFR00570 containment pressure > MAX1p or SIS JMQ SC2 PS SCP CIT
signal
Containment isolation stage 1 on
RFFR00570 containment pressure > MAX1p or SIS KAA, KAB SC2 PS SCP CIT
signal
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

Containment isolation stage 1 on


KBA, KBD,
RFFR00570 containment pressure > MAX1p or SIS SC2 PS SCP CIT
JEW
signal
Containment isolation stage 1 on
RFFR00570 containment pressure > MAX1p or SIS KLA SC2 PS SCP CIT
signal
Containment isolation stage 1 on
RFFR00570 containment pressure > MAX1p or SIS KPL SC2 PS SCP CIT
signal
Containment isolation stage 1 on
RFFR00570 containment pressure > MAX1p or SIS KTA-KTE SC2 PS SCP CIT
signal
Containment isolation stage 1 on
KUA, KUB,
RFFR00570 containment pressure > MAX1p or SIS SC2 PS SCP CIT
KUF
signal
Containment isolation stage 1 on
LCA90
RFFR00570 containment pressure > MAX1p or SIS SC2 PS SCP CIT
LCQ
signal
Containment isolation stage 1 on
RFFR00570 containment pressure > MAX1p or SIS QJA-QJE SC2 PS SCP CIT
signal
Containment isolation stage 1 on
RFFR00570 containment pressure > MAX1p or SIS QN SC2 PS SCP CIT
signal
ECCN: N

Containment isolation stage 1 on SCB


RFFR00570 containment pressure > MAX1p or SIS QFB SC2 PS SCP CIT
signal SCA
Containment isolation stage 1 on
AL: N

RFFR00570 containment pressure > MAX1p or SIS SGB SC2 PS SCP CIT
signal
Containment isolation stage 2 on
RFFR00571 BB SC2 PS SCP CIT
containment pressure > MAX2p
Containment isolation stage 2 on FAK
RFFR00571 SC2 PS SCP CIT
containment pressure > MAX2p FAL
Containment isolation stage 2 on
RFFR00571 GHC SC2 PS SCP CIT
containment pressure > MAX2p
JAA
JAC
Containment isolation stage 2 on JEA
RFFR00571 SC2 PS SCP CIT
containment pressure > MAX2p JEB
JEC
JEF, JEG
Containment isolation stage 2 on
RFFR00571 JDH SC2 PS SCP CIT
containment pressure > MAX2p
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A35 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Containment isolation stage 2 on
RFFR00571 JMM SC2 PS SCP CIT
containment pressure > MAX2p
Containment isolation stage 2 on
RFFR00571 JMQ SC2 PS SCP CIT
containment pressure > MAX2p
Containment isolation stage 2 on
RFFR00571 KAA, KAB SC2 PS SCP CIT
containment pressure > MAX2p
Containment isolation stage 2 on KBA, KBD,
RFFR00571 SC2 PS SCP CIT
containment pressure > MAX2p JEW
Containment isolation stage 2 on
RFFR00571 KLA SC2 PS SCP CIT
containment pressure > MAX2p
Containment isolation stage 2 on
RFFR00571 KPL SC2 PS SCP CIT
containment pressure > MAX2p
Containment isolation stage 2 on
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

RFFR00571 KTA-KTE SC2 PS SCP CIT


containment pressure > MAX2p
Containment isolation stage 2 on KUA, KUB,
RFFR00571 SC2 PS SCP CIT
containment pressure > MAX2p KUF
Containment isolation stage 2 on
RFFR00571 KUL SC2 PS SCP CIT
containment pressure > MAX2p
Containment isolation stage 2 on LCA90
RFFR00571 SC2 PS SCP CIT
containment pressure > MAX2p LCQ
Containment isolation stage 2 on
RFFR00571 QJA-QJE SC2 PS SCP CIT
containment pressure > MAX2p
Containment isolation stage 2 on
RFFR00571 QN SC2 PS SCP CIT
containment pressure > MAX2p
Containment isolation stage 2 on
RFFR00571 QUC SC2 PS SCP CIT
containment pressure > MAX2p
SCB
Containment isolation stage 2 on
RFFR00571 QFB SC2 PS SCP CIT
containment pressure > MAX2p
SCA
Containment isolation stage 2 on
RFFR00571 SGB SC2 PS SCP CIT
containment pressure > MAX2p
JAA
JAC
ECCN: N

PSV opening for brittle fracture protection JEA


RFFR00572 SC2 PS SCP JA-JE
of RPV JEB
JEC
JEF, JEG
AL: N

PSV opening for brittle fracture protection JNA; JND;


RFFR00572 SC2 PS SCP JA-JE
of RPV JNG, JNK
ATWS signal due to mechanical blockage
RFFR00573 JDA SC2 PS SCP JDA/BU NI
of the rods
ATWS signal due to mechanical blockage
RFFR00573 JDA1 SC2 PS SCP JDA/BU NI
of the rods
JAA
JAC
Shutdown of CVCS charging line on PZR JEA
RFFR00574 SC2 PS SCP JA-JE
level > MAX2p JEB
JEC
JEF, JEG
Shutdown of CVCS charging line on PZR KBA, KBD,
RFFR00574 SC2 PS SCP JA-JE
level > MAX2p JEW
Shutdown of CVCS charging line on hot JNA; JND; SCP KBA-KBD-
RFFR00575 SC2 PS
leg pressure (WR)> MAX0p JNG, JNK JEW
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A36 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Shutdown of CVCS charging line on hot KBA, KBD, SCP KBA-KBD-
RFFR00575 SC2 PS
leg pressure (WR)> MAX0p JEW JEW
JAA
JAC
Shutdown of CVCS charging line on SG
JEA
RFFR00576 level (NR) > MAX2p, if partial cooldown is SC2 PS SCP JA-JE
JEB
finished
JEC
JEF, JEG
Shutdown of CVCS charging line on SG
KBA, KBD,
RFFR00576 level (NR) > MAX2p, if partial cooldown is SC2 PS SCP JA-JE
JEW
finished
Shutdown of CVCS charging line on SG KBA, KBD, SCP KBA-KBD-
RFFR00577 SC2 PS
pressure < MIN4p and SIS signal JEW JEW
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

Shutdown of CVCS charging line on SG SCP KBA-KBD-


RFFR00577 LBA SC2 PS
pressure < MIN4p and SIS signal JEW
RFFR00578 EBS actuation on SG pressure < MIN4p JDH SC2 PS SCP JDH
JNA; JND;
RFFR00578 EBS actuation on SG pressure < MIN4p SC2 PS SCP JDH
JNG, JNK
RFFR00578 EBS actuation on SG pressure < MIN4p LBA SC2 PS SCP JDH
RFFR00579 Automatic EBS actuation on ATWS signal JDH SC2 PS SCP JDH
JNA; JND;
RFFR00579 Automatic EBS actuation on ATWS signal SC2 PS SCP JDH
JNG, JNK
Automatic RCP trip on ATWS signal and
RFFR00580 BB SC2 PS SCP JA-JE
SG level (NR) < MIN1p
JAA
JAC
Automatic RCP trip on ATWS signal and JEA
RFFR00580 SC2 PS SCP JA-JE
SG level (NR) < MIN1p JEB
JEC
JEF, JEG
Reactor trip on diversified SG pressure >
RFFR00581 BU SC2 PS SCP LBA NI
MAX2p
Reactor trip on diversified SG pressure >
RFFR00581 JDA SC2 PS SCP LBA NI
MAX2p
ECCN: N

Reactor trip on diversified SG pressure >


RFFR00581 LBA SC2 PS SCP LBA NI
MAX2p
Closure of SG transfer blowdown lines SCP LCQ-
RFFR00582 KLA SC2 PS
when RT checkback signal is not present LCA90
AL: N

Closure of SG transfer blowdown lines LCA90 SCP LCQ-


RFFR00582 SC2 PS
when RT checkback signal is not present LCQ LCA90
Closure of RHRS hot leg suction lines JNA; JND;
RFFR00583 SC2 PS SCP JN
when P14 and P16 are not activated JNG, JNK
JAA
JAC
Closure of SSSS on loss of RCP thermal JEA
RFFR00584 SC2 PS SCP JA-JE
barrier and RCP seal injection JEB
JEC
JEF, JEG
Closure of SSSS on loss of RCP thermal JNA; JND;
RFFR00584 SC2 PS SCP JA-JE
barrier and RCP seal injection JNG, JNK
Closure of SSSS on loss of RCP thermal
RFFR00584 KAA, KAB SC2 PS SCP JA-JE
barrier and RCP seal injection
Closure of SSSS on loss of RCP thermal KBA, KBD,
RFFR00584 SC2 PS SCP JA-JE
barrier and RCP seal injection JEW
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A37 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
JAA
JAC
JEA
RFFR00585 Permissives P 12 SC2 PS SCP JA-JE
JEB
JEC
JEF, JEG

JAA
JAC
JEA
RFFR00586 Permissives P 13 SC2 PS SCP JA-JE
JEB
JEC
JEF, JEG

JAA
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

JAC
JEA
RFFR00587 Permissives P 14 SC2 PS SCP JN
JEB
JEC
JEF, JEG
JNA; JND;
RFFR00587 Permissives P 14 SC2 PS SCP JN
JNG, JNK
JAA
JAC
JEA
RFFR00588 Permissives P 15 SC2 PS SCP JA-JE
JEB
JEC
JEF, JEG

JAA
JAC
JEA
RFFR00589 Permissives P 16 SC2 PS SCP JA-JE
JEB
JEC
JEF, JEG
JNA; JND;
RFFR00589 Permissives P 16 SC2 PS SCP JA-JE
JNG, JNK
ECCN: N

JAA
JAC
JEA
RFFR00590 Permissives P 17 SC2 PS SCP JA-JE
AL: N

JEB
JEC
JEF, JEG
RFFR00591 Permissives P 19 SC2 PS SCP LBA NI
SCP JKS
RFFR00592 High linear power density channel BU SC2 PS
SPND/COT
SCP JKS
RFFR00592 High linear power density channel JDA SC2 PS
SPND/COT
SCP JKS
RFFR00592 High linear power density channel JKS SC2 PS
SPND/COT
RFFR00593 Low DNBR channel BU SC2 PS SCP JA-JE
JAA
JAC
JEA
RFFR00593 Low DNBR channel SC2 PS SCP JA-JE
JEB
JEC
JEF, JEG
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A38 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
RFFR00593 Low DNBR channel JDA SC2 PS SCP JA-JE
RFFR00593 Low DNBR channel JKT SC2 PS SCP JA-JE
Excore high neutron flux rate of change
RFFR00594 BU SC2 PS SCP JKT
channel
Excore high neutron flux rate of change
RFFR00594 JDA SC2 PS SCP JKT
channel
Excore high neutron flux rate of change
RFFR00594 JKT SC2 PS SCP JKT
channel
RFFR00595 High core power level (HCPL) channel BU SC2 PS SCP JA-JE
JAA
JAC
JEA
RFFR00595 High core power level (HCPL) channel SC2 PS SCP JA-JE
JEB
JEC
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

JEF, JEG
RFFR00595 High core power level (HCPL) channel JDA SC2 PS SCP JA-JE
JNA; JND;
RFFR00595 High core power level (HCPL) channel SC2 PS SCP JA-JE
JNG, JNK
RFFR00596 Low and low-low loop flow rate channels BU SC2 PS SCP JA-JE
JAA
JAC
JEA
RFFR00596 Low and low-low loop flow rate channels SC2 PS SCP JA-JE
JEB
JEC
JEF, JEG
RFFR00596 Low and low-low loop flow rate channels JDA SC2 PS SCP JA-JE
RFFR00597 Low RCP speed (four RCPs) channel BU SC2 PS SCP JA-JE
JAA
JAC
JEA
RFFR00597 Low RCP speed (four RCPs) channel SC2 PS SCP JA-JE
JEB
JEC
JEF, JEG
RFFR00597 Low RCP speed (four RCPs) channel JDA SC2 PS SCP JA-JE
ECCN: N

RFFR00598 High neutron flux (source range) channel BU SC2 PS SCP JDH
RFFR00598 High neutron flux (source range) channel JDA SC2 PS SCP JDH
RFFR00598 High neutron flux (source range) channel JDH SC2 PS SCP JDH
AL: N

RFFR00598 High neutron flux (source range) channel JKT SC2 PS SCP JDH
JNA; JND;
RFFR00598 High neutron flux (source range) channel SC2 PS SCP JDH
JNG, JNK
High neutron flux (intermediate range)
RFFR00599 BU SC2 PS SCP JKT
channel
High neutron flux (intermediate range)
RFFR00599 JDA SC2 PS SCP JKT
channel
High neutron flux (intermediate range)
RFFR00599 JKT SC2 PS SCP JKT
channel
RFFR00600 Low doubling time (intermediate range) BU SC2 PS SCP JKT
RFFR00600 Low doubling time (intermediate range) JDA SC2 PS SCP JKT
RFFR00600 Low doubling time (intermediate range) JKT SC2 PS SCP JKT
Anti-dilution in shutdown conditions with SCP KBA-KBD-
RFFR00601 CPF SC2 PS
RCP not in operation channel JEW
Anti-dilution in shutdown conditions with JNA; JND; SCP KBA-KBD-
RFFR00601 SC2 PS
RCP not in operation channel JNG, JNK JEW
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A39 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Anti-dilution in shutdown conditions with KBA, KBD, SCP KBA-KBD-
RFFR00601 SC2 PS
RCP not in operation channel JEW JEW
Anti-dilution in standard shutdown states SCP KBA-KBD-
RFFR00602 CPF SC2 PS
conditions channel JEW
JAA
JAC
Anti-dilution in standard shutdown states JEA SCP KBA-KBD-
RFFR00602 SC2 PS
conditions channel JEB JEW
JEC
JEF, JEG
Anti-dilution in standard shutdown states KBA, KBD, SCP KBA-KBD-
RFFR00602 SC2 PS
conditions channel JEW JEW
SCP KBA-KBD-
RFFR00603 Anti-dilution in power conditions channel CPF SC2 PS
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

JEW
KBA, KBD, SCP KBA-KBD-
RFFR00603 Anti-dilution in power conditions channel SC2 PS
JEW JEW
RFFR00604 Permissive P2 JKT SC2 PS SCP JKT
RFFR00605 Permissive P3 JKT SC2 PS SCP JKT
RFFR00606 Permissive P5 JKT SC2 PS SCP JKT
JAA
JAC
JEA
RFFR00607 Permissive P6 SC2 PS SCP JA-JE
JEB
JEC
JEF, JEG
JNA; JND;
RFFR00607 Permissive P6 SC2 PS SCP JA-JE
JNG, JNK
JAA
JAC
JEA
RFFR00608 Permissive P7 SC2 PS SCP JA-JE
JEB
JEC
JEF, JEG
ECCN: N

RFFR00609 Permissive P8 JDA SC2 PS SCP JDA/BU NI


RFFR00609 Permissive P8 JDA1 SC2 PS SCP JDA/BU NI
Limitation function: High linear power
RFFR00610 BU SC3 RCSL SCP CLT
density
AL: N

Limitation function: High linear power


RFFR00610 JDA SC3 RCSL SCP CLT
density
RFFR00611 Limitation function: Low DNBR BU SC3 RCSL SCP CLT
RFFR00611 Limitation function: Low DNBR JDA SC3 RCSL SCP CLT
Limitation function: Loss of one reactor
RFFR00612 BU SC3 RCSL SCP CLT
coolant pump
JAA
JAC
Limitation function: Loss of one reactor JEA
RFFR00612 SC3 RCSL SCP CLT
coolant pump JEB
JEC
JEF, JEG
Limitation function: Loss of one reactor
RFFR00612 JDA SC3 RCSL SCP CLT
coolant pump
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A40 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP

RFFR00613 Limitation function: Rod drop BU SC3 RCSL SCP JDA/BU NI

RFFR00613 Limitation function: Rod drop JDA SC3 RCSL SCP JDA/BU NI

RFFR00613 Limitation function: Rod drop JKT SC3 RCSL SCP JDA/BU NI

Limitation function: High neutron flux (&


RFFR00614 JDA SC3 RCSL SCP CLT
low doubling time) - Intermediate range
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

Limitation function: High neutron flux (&


RFFR00614 JDA1 SC3 RCSL SCP CLT
low doubling time) - Intermediate range
Limitation function: Pellet clad interaction
RFFR00616 BU SC3 RCSL SCP KBC
(PCI)
Limitation function: Pellet clad interaction
RFFR00616 JDA SC3 RCSL SCP KBC
(PCI)
Limitation function: Pellet clad interaction
RFFR00616 KBC SC3 RCSL SCP KBC
(PCI)

RFFR00617 LCO function: Linear Power Density (LPD) BU SC3 RCSL SCP KBC

RFFR00617 LCO function: Linear Power Density (LPD) JDA SC3 RCSL SCP KBC

RFFR00617 LCO function: Linear Power Density (LPD) KBC SC3 RCSL SCP KBC

RFFR00618 LCO function: DNBR BU SC3 RCSL SCP JA-JE


JAA
JAC
JEA
RFFR00618 LCO function: DNBR SC3 RCSL SCP JA-JE
JEB
JEC
ECCN: N

JEF, JEG
RFFR00618 LCO function: DNBR JDA SC3 RCSL SCP JA-JE
RFFR00618 LCO function: DNBR SC3 RCSL SCP JA-JE
RFFR00619 LCO function: Reactor Thermal Power BU SC3 RCSL SCP JA-JE
AL: N

JAA
JAC
JEA
RFFR00619 LCO function: Reactor Thermal Power SC3 RCSL SCP JA-JE
JEB
JEC
JEF, JEG
RFFR00619 LCO function: Reactor Thermal Power JDA SC3 RCSL SCP JA-JE
RFFR00619 LCO function: Reactor Thermal Power KBC SC3 RCSL SCP JA-JE
SCP JKS
RFFR00620 LCO function: Axial power shape JKS SC4 RCSL
SPND/COT
RFFR00622 LCO function: Azimuthal power imbalance JKT SC4 RCSL SCP JKT
RFFR00623 LCO function: RCCA misalignment JDA SC4 RCSL SCP JDA/BU NI
RFFR00623 LCO function: RCCA misalignment JDA1 SC4 RCSL SCP JDA/BU NI
Automatic isolation of CVCS
KBA, KBD,
RFFR00624 demineralized water and start up of the SC3 RCSL SCP KBC
JEW
boric acid pumps on ATWS signal
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A41 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Automatic isolation of CVCS
RFFR00624 demineralized water and start up of the KBC SC3 RCSL SCP KBC
boric acid pumps on ATWS signal
RFFR00626 Axial Offset control BU SC3 RCSL SCP CLT
RFFR00626 Axial Offset control JDA SC3 RCSL SCP CLT
RFFR00626 Axial Offset control KBC SC3 RCSL SCP CLT

RFFR00627 Bank Position Control BU SC3 RCSL SCP CLT

RFFR00627 Bank Position Control JDA SC3 RCSL SCP CLT

RFFR00627 Bank Position Control KBC SC3 RCSL SCP CLT


CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

RFFR00628 Neutron Flux Control BU SC3 RCSL SCP CLT


RFFR00628 Neutron Flux Control JDA SC3 RCSL SCP CLT

RFFR00629 Rod Return Control BU SC3 RCSL SCP CLT

RFFR00629 Rod Return Control JDA SC3 RCSL SCP CLT

RFFR00630 Pi bank sequence interchange BU SC3 RCSL SCP CLT


RFFR00630 Pi bank sequence interchange JDA SC3 RCSL SCP CLT
Manual control and shutdown RCCA
RFFR00631 BU SC4 RCSL SCP JDA/BU NI
movements
Manual control and shutdown RCCA
RFFR00631 JDA SC4 RCSL SCP JDA/BU NI
movements
EDG
XJA10-40 SCP XJA-
RFFR00632 EDG Safety Preheating SC3 Safety
XKA10-40 XKA10-20-30-40
I&C
EDG
XJA10-40 SCP XJA-
RFFR00633 Safety EDG component Protection SC2 Safety
ECCN: N

XKA10-40 XKA10-20-30-40
I&C
Diesel actuation on 10kV busbar voltage <
RFFR00634 BD SC2 PS SCP LOOP
MIN1p or 10kV busbar frequency < MIN1p
AL: N

Diesel actuation on 10kV busbar voltage < BM, BN, BL,


RFFR00634 SC2 PS SCP LOOP
MIN1p or 10kV busbar frequency < MIN1p BR
Diesel actuation on 10kV busbar voltage < FAK
RFFR00634 SC2 PS SCP LOOP
MIN1p or 10kV busbar frequency < MIN1p FAL
Diesel actuation on 10kV busbar voltage <
RFFR00634 JDH SC2 PS SCP LOOP
MIN1p or 10kV busbar frequency < MIN1p
Diesel actuation on 10kV busbar voltage < JNA; JND;
RFFR00634 SC2 PS SCP LOOP
MIN1p or 10kV busbar frequency < MIN1p JNG, JNK
Diesel actuation on 10kV busbar voltage <
RFFR00634 KAA, KAB SC2 PS SCP LOOP
MIN1p or 10kV busbar frequency < MIN1p
Diesel actuation on 10kV busbar voltage < KBA, KBD,
RFFR00634 SC2 PS SCP LOOP
MIN1p or 10kV busbar frequency < MIN1p JEW
Diesel actuation on 10kV busbar voltage <
RFFR00634 KLA SC2 PS SCP LOOP
MIN1p or 10kV busbar frequency < MIN1p
Diesel actuation on 10kV busbar voltage <
RFFR00634 LAR, LAS SC2 PS SCP LOOP
MIN1p or 10kV busbar frequency < MIN1p
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A42 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Diesel actuation on 10kV busbar voltage <
RFFR00634 PEB/PEH SC2 PS SCP LOOP
MIN1p or 10kV busbar frequency < MIN1p
Diesel actuation on 10kV busbar voltage <
RFFR00634 QKA-QKC SC2 PS SCP LOOP
MIN1p or 10kV busbar frequency < MIN1p
Diesel actuation on 10kV busbar voltage <
RFFR00634 QN SC2 PS SCP LOOP
MIN1p or 10kV busbar frequency < MIN1p
Diesel actuation on 10kV busbar voltage <
RFFR00634 SAC SC2 PS SCP LOOP
MIN1p or 10kV busbar frequency < MIN1p
Diesel actuation on 10kV busbar voltage < SAD
RFFR00634 SC2 PS SCP LOOP
MIN1p or 10kV busbar frequency < MIN1p SAL
Diesel actuation on 10kV busbar voltage < XJA10-40
RFFR00634 SC2 PS SCP LOOP
MIN1p or 10kV busbar frequency < MIN1p XKA10-40
Diesel actuation on 10kV busbar voltage < XJA50/80,
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

RFFR00634 SC2 PS SCP LOOP


MIN1p or 10kV busbar frequency < MIN1p XKA50/80
RFFR00636 LOOP Alarm HBS BD SC3 HBS SCP LOOP
XJA50/80, SCP XJA-XKA
RFFR00637 Start SBO diesel SC3 SSS
XKA50/80 50/80
Actuation of "SBO-Switch" in PS to
actuate Generator Breaker and to avoid JNA; JND;
RFFR00638 SC3 PS SCP LOOP
automatic restart of LAS, JNG and QKA JNG, JNK
during recovery of TXS
RFFR00640 All rods in signal JDA SC3 PS SCP JDA/BU NI
RFFR00640 All rods in signal JDA1 SC3 PS SCP JDA/BU NI
LAA
RFFR00642 Feedwater water tank water level LBS SC4 PAS 2 PAS 2 Siemens
LBS50
LAB*
LAC
RFFR00643 Feedwater pump status SC4 PAS 2 PAS 2 Siemens
LAH
LAJ
LCA
LCB
RFFR00644 Condensate pump status SC4 PAS 2 PAS 2 Siemens
LCR
LCW
ECCN: N

LCA
LCB
RFFR00645 Condensator monitoring SC4 PAS 2 PAS 2 Siemens
LCR
LCW
AL: N

PAB
PAC
RFFR00646 Circulation water pump monitoring PAH SC4 PAS 2 PAS 2 Siemens
PUE
PUR
RFFR00647 MCR air conditioning Building ISOL KLC SC4 SAS SCP SAB
RFFR00647 MCR air conditioning Building ISOL SAB SC4 SAS SCP SAB
RFFR00647 MCR air conditioning Building ISOL SAC SC4 SAS SCP SAB
SAD
RFFR00648 Diesel Building ventilation operation SC3 SICS SCP SAD-SAL
SAL
SAD
RFFR00649 Diesel Building ventilation operation SC3 SICS SCP SAD-SAL
SAL

RFFR00650 Averaged Coolant Temperature Control BU SC3 RCSL SCP CLT


Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A43 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP

RFFR00650 Averaged Coolant Temperature Control JDA SC3 RCSL SCP CLT

RFFR00650 Averaged Coolant Temperature Control JKT SC3 RCSL SCP CLT

RFFR00651 RCS Temperature Control - ACT LCO SC4 RCSL SCP CLT
JAA
JAC
JEA
RFFR00652 RCS temperature surveillance SC3 RCSL SCP JA-JE
JEB
JEC
JEF, JEG

JAA
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

JAC
JEA
RFFR00653 RHR Control SC3 RCSL SCP JN
JEB
JEC
JEF, JEG
JNA; JND;
RFFR00653 RHR Control SC3 RCSL SCP JN
JNG, JNK
JNA; JND;
RFFR00654 RHR Control SC3 RCSL SCP JN
JNG, JNK
RFFR00654 RHR Control KAA, KAB SC3 RCSL SCP JN
JAA
JAC
JEA
RFFR00655 RCS Loop Level Control SC3 RCSL SCP CLT
JEB
JEC
JEF, JEG
KBA, KBD,
RFFR00655 RCS Loop Level Control SC3 RCSL SCP CLT
JEW

JAA
JAC
RCS loop level limitation I&C function: JEA
RFFR00656 SC3 RCSL SCP CIT
ECCN: N

RCPB isolation function JEB


JEC
JEF, JEG
RCS loop level limitation I&C function: JNA; JND;
AL: N

RFFR00656 SC3 RCSL SCP CIT


RCPB isolation function JNG, JNK
RCS loop level limitation I&C function: KBA, KBD,
RFFR00656 SC3 RCSL SCP CIT
RCPB isolation function JEW
JAA
JAC
RCS loop level limitation above control JEA
RFFR00657 SC3 RCSL SCP CLT
range JEB
JEC
JEF, JEG
RCS loop level limitation above control KBA, KBD,
RFFR00657 SC3 RCSL SCP CLT
range JEW
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A44 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
JAA
JAC
RCS loop level limitation below control JEA
RFFR00658 SC3 RCSL SCP CLT
range JEB
JEC
JEF, JEG
RCS loop level limitation below control KBA, KBD,
RFFR00658 SC3 RCSL SCP CLT
range JEW
JAA
JAC
JEA
RFFR00659 RCS Loop Level Control SC3 RCSL SCP CLT
JEB
JEC
JEF, JEG
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

Operator aid function: stop depressurizing KBA, KBD, SCP KBA-KBD-


RFFR00660 SC3 RCSL
sources JEW JEW
Operator aid function: stop charging KBA, KBD, SCP KBA-KBD-
RFFR00661 SC3 RCSL
injection in case of SI signal JEW JEW
JAA
JAC
JEA
RFFR00662 Interlockings for solid PZR operation SC3 RCSL SCP CLT
JEB
JEC
JEF, JEG
RFFR00663 Inhibition of the low RCS pressure LCO SC4 RCSL SCP CLT
KBA, KBD,
RFFR00664 Solid PZR Pressure Control SC3 RCSL SCP CLT
JEW
Pressurize PZR at constant PZR water
BFJ
RFFR00665 temperature - Automatic end of the SC3 RCSL SCP CLT
BFK
manual phase
JAA
JAC
Pressurize PZR at constant PZR water
JEA
RFFR00665 temperature - Automatic end of the SC3 RCSL SCP CLT
JEB
manual phase
JEC
ECCN: N

JEF, JEG
Pressurize PZR at constant PZR water
KBA, KBD,
RFFR00665 temperature - Automatic end of the SC3 RCSL SCP CLT
JEW
manual phase
AL: N

Inhibition of RCS pressure operator aid


RFFR00666 SC3 RCSL SCP CLT
functions

JAA
JAC
JEA
RFFR00667 Alarm depressurization SC3 RCSL SCP JA-JE
JEB
JEC
JEF, JEG
RFFR00668 EFWS flow upstream SG LAR, LAS SC3 SAS SCP LAR-LAS
RFFR00670 Manual MFW/SSS isolation (SG per SG) LAB SC4 SAS SCP LAB NI
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A45 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
JAA
JAC
Automatic opening control of EFWS JEA
RFFR00671 SC3 SAS SCP LAR-LAS
control valve (train by train) JEB
JEC
JEF, JEG
Automatic opening control of EFWS
RFFR00671 LAR, LAS SC3 SAS SCP LAR-LAS
control valve (train by train)
RFFR00672 Switchover sequence order KAA, KAB SC4 SAS SCP KAA/KAB
RFFR00672 Switchover sequence order PEB/PEH SC4 SAS SCP KAA/KAB
Control of SAB fans over Hard-wired
RFFR00673 SAB SC3 SICS SCP SAB
Backup system
Manual RT (including TT, MFW-FL
RFFR00674 BU SC3 PS SCP LAB NI
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

isolation)
Manual RT (including TT, MFW-FL
RFFR00674 JDA SC3 PS SCP LAB NI
isolation)
Manual RT (including TT, MFW-FL
RFFR00674 LAB SC3 PS SCP LAB NI
isolation)
EDG DLS consumer trip
RFFR00675 QKA-QKC SC3 SICS SCP LOOP
SBO DLS consumer trip
FAK
RFFR00677 Fuel pool cooling system operation SC3 SICS SCP FAK/FAL
FAL
Pressure difference over the
RFFR00678 CCWS/ESWS Heat exchanger control KAA, KAB SC3 SICS SCP KAA/KAB
valve
Position of control valve downstream the
RFFR00679 CCWS/ESWS heat exchanger and of KAA, KAB SC3 SICS SCP KAA/KAB
control valve on its bypass
RHR heat exchanger control valve and JNA; JND;
RFFR00680 SC3 SICS SCP JN
bypass control valve position JNG, JNK
RFFR00681 EFWS SG level control valve position LAR, LAS SC3 SICS SCP LAR-LAS
RFFR00682 EFWS overflow limitation valve position LAR, LAS SC3 SICS SCP LAR-LAS
RFFR00683 MSRCV position LBA SC3 SICS SCP LBA NI
RFFR00684 Loss of digital automation systems (H0) SC3 HBS SCP I&C ARCH
ECCN: N

RFFR00685 Entry in Emergency Operation (H1) SC3 HBS SCP LOOP


RFFR00686 Entry in Emergency Operation (H1) KAA, KAB SC3 SAS SCP PE
RFFR00686 Entry in Emergency Operation (H1) PEB/PEH SC3 SAS SCP PE
Limitation function: Anti-dilution in
AL: N

RFFR00688 standard shutdown states - Maximum KBC SC3 RCSL SCP KBC
Boration Part

LCO function: Shutdown margin (insertion


RFFR00689 KBC SC3 RCSL SCP KBC
limit) - Maximum Boration Part

Automatic boration following a loss of 2 or JNA; JND;


RFFR00691 SC3 RCSL SCP KBC
more RCPs JNG, JNK
Automatic boration following a loss of 2 or KBA, KBD,
RFFR00691 SC3 RCSL SCP KBC
more RCPs JEW
Automatic boration following a loss of 2 or
RFFR00691 KBC SC3 RCSL SCP KBC
more RCPs
JNA; JND;
RFFR00692 Manual Outer Containment isolation SC4 SAS SCP JN
JNG, JNK
RFFR00693 Manual Outer Containment isolation LAB SC4 SAS SCP LAB NI
RFFR00694 Manual Outer Containment isolation LAR, LAS SC4 SAS SCP LAR-LAS
RFFR00695 Manual Outer Containment isolation LBA SC4 SAS SCP LBA NI
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A46 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
JNA; JND;
RFFR00696 SIS back-flushing SC3 SICS SCP JN
JNG, JNK
SCP JKS
RFFR00697 RPVL top JKS SC3 SICS
RPVL/RPVDT
SCP JKS
RFFR00698 RPVL middle JKS SC3 SICS
RPVL/RPVDT
SCP JKS
RFFR00699 RPVL bottom JKS SC3 SICS
RPVL/RPVDT
RFFR00700 MCR air conditioning Building ISOL SAB SC3 SICS SCP SAB
RFFR00701 Fuel handling hall isolation KLL SC3 SICS SCP KLL
RFFR00702 Room in front of the hatch isolation KLL SC3 SICS SCP KLL
Room in front of the emergency airlock
RFFR00703 KLL SC3 SICS SCP KLL
isolation
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

Isolate the volume of mechanical divisions


RFFR00704 of Safeguard Buildings when the SIS KLC SC3 SICS SCP KLC
system is used after an accident in the RB
Maintain subpressure in the affected area
and remove iodine released in the RB or
RFFR00705 KLC SC3 SICS SCP KLC
fuel handling hall in the event of a fuel
handling accident
JAA
JAC
ΔMIN function: Pressurizer level - Adjust JEA
RFFR00706 SC3 RCSL SCP CLT
letdown flow rate to minimum JEB
JEC
JEF, JEG
ΔMIN function: Pressurizer level - Adjust KBA, KBD,
RFFR00706 SC3 RCSL SCP CLT
letdown flow rate to minimum JEW
JAA
JAC
ΔMIN function: Pressurizer level - Start JEA SCP KBA-KBD-
RFFR00707 SC3 RCSL
2nd HP charging pump JEB JEW
JEC
JEF, JEG
ECCN: N

ΔMIN function: Pressurizer level - Start KBA, KBD, SCP KBA-KBD-


RFFR00707 SC3 RCSL
2nd HP charging pump JEW JEW
Limitation function: Anti-dilution in
RFFR00708 standard shutdown states - Block Dilution KBC SC3 RCSL SCP KBC
AL: N

Source Part

LCO function: Shutdown margin (insertion


RFFR00709 KBC SC3 RCSL SCP KBC
limit) - Block Dilution Source Part

Block Demineralized Water following a JNA; JND;


RFFR00710 SC3 RCSL SCP KBC
loss of two or more RCPs JNG, JNK
Block Demineralized Water following a
RFFR00710 KBC SC3 RCSL SCP KBC
loss of two or more RCPs
Closing of the air supply in front of the
RFFR00711 KLA SC3 SICS SCP KLA
hatch and of KLA2 filter isolation dampers
Closure of QUC containment isolation LCA90
RFFR00712 SC3 SICS SCP QUC NI
valves LCQ
Closure of QUC containment isolation
RFFR00712 QUC SC3 SICS SCP QUC NI
valves
RFFR00713 Neutron flux (SR) JKT SC3 PS SCP JKT
RFFR00715 Dose rate RB Lock JYK, KLK SC4 SAS SCP JYK - KLK
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A47 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
RFFR00716 Dose rate RB Lock JYK, KLK SC3 SICS SCP JYK - KLK
RFFR00717 Dose rate RB hatch JYK, KLK SC4 SAS SCP JYK - KLK
RFFR00718 Dose rate RB hatch JYK, KLK SC3 SICS SCP JYK - KLK
JNA; JND;
RFFR00719 CHRS sump backflushing SC4 SAS SCP JN
JNG, JNK
RFFR00720 H2 H20 INDICATION JMU SC4 SAS SCP JMU
RFFR00721 H2 H20 INDICATION JMU SC3 SA I&C SCP JMU
RFFR00722 H2 INDICATION 6% JMU SC4 SAS SCP JMU
RFFR00723 H2 INDICATION 6% JMU SC3 SA I&C SCP JMU
RFFR00726 ESWS flow rate PEB/PEH SC3 SAS SCP PE
Automatic MSIV closure and Reactor trip
RFFR00727 BU SC3 SAS SCP LBA NI
on diversified SG pressure < min1
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

Automatic MSIV closure and Reactor trip


RFFR00727 JDA SC3 SAS SCP LBA NI
on diversified SG pressure < min1
Automatic MSIV closure and Reactor trip
RFFR00727 LBA SC3 SAS SCP LBA NI
on diversified SG pressure < min1
Manual isolation of VCT and switchover of KBA, KBD, SCP KBA-KBD-
RFFR00728 SC3 SICS
the suction from VCT to IRWST JEW JEW
Manual isolation of VCT and switchover of FAK
RFFR00729 SC3 SICS SCP FAK/FAL
the suction from VCT to IRWST FAL
Manual isolation of VCT and switchover of
RFFR00730 JMQ SC3 SICS SCP JMQ
the suction from VCT to IRWST
Manual isolation of VCT and switchover of JNA; JND;
RFFR00731 SC3 SICS SCP JN
the suction from VCT to IRWST JNG, JNK
RFFR00732 Post accident signal actuation SC3 RCSL SCP CLT
RFFR00733 Block Demineralized Water Injection KBC SC3 RCSL SCP KBC
RFFR00734 EFWS Alignment monitoring LAR, LAS SC3 SAS SCP LAR-LAS

BTD, BRU,
RFFR00735 12h UPS voltage BTP, BUE- SC3 SA I&C SCP BATT
BUH; BR; BTW

BTD, BRU,
ECCN: N

RFFR00736 12h UPS current BTP, BUE- SC4 SAS SCP BATT
BUH; BR; BTW

LAA
AL: N

RFFR00737 Feedwater water tank pressure LBS SC4 PAS 2 PAS 2 Siemens
LBS50
Manual Outer Containment isolation for CI
RFFR00738 valves not actuated by stage 1&2 KAA, KAB SC3 SICS SCP KAA/KAB
(Thermal Barrier)
Manual Outer Containment isolation for CI
RFFR00739 valves not actuated by stage 1&2 KAA, KAB SC4 SAS SCP KAA/KAB
(Thermal Barrier)
Manual Inner Containment isolation for CI
RFFR00740 valves not actuated by stage 1&2 KAA, KAB SC4 SAS SCP KAA/KAB
(Thermal Barrier)
Manual Inner Containment isolation for CI
RFFR00741 valves not actuated by stage 1&2 KAA, KAB SC3 SICS SCP KAA/KAB
(Thermal Barrier)
RFFR00742 Automatic escape alarm in UJA CYC SC4 SAS SCP CYC
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A48 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
JAA
JAC
JEA
RFFR00742 Automatic escape alarm in UJA SC4 SAS SCP CYC
JEB
JEC
JEF, JEG
JNA; JND;
RFFR00742 Automatic escape alarm in UJA SC4 SAS SCP CYC
JNG, JNK
RFFR00742 Automatic escape alarm in UJA KLA SC4 SAS SCP CYC
RFFR00743 Automatic evacuation alarm in UJA CYC SC4 SAS SCP CYC
JAA
JAC
JEA
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

RFFR00743 Automatic evacuation alarm in UJA SC4 SAS SCP CYC


JEB
JEC
JEF, JEG
JNA; JND;
RFFR00743 Automatic evacuation alarm in UJA SC4 SAS SCP CYC
JNG, JNK
RFFR00743 Automatic evacuation alarm in UJA JYK, KLK SC4 SAS SCP CYC
RFFR00743 Automatic evacuation alarm in UJA KLA SC4 SAS SCP CYC
RFFR00743 Automatic evacuation alarm in UJA QJA-QJE SC4 SAS SCP CYC
Manual actuation of evacuation alarm in
RFFR00744 CYC SC4 SAS SCP CYC
UJA
Manual actuation of evacuation alarm in
RFFR00744 KLA SC4 SAS SCP CYC
UJA
RFFR00745 Automatic evacuation alarm in UFA CYC SC4 SAS SCP CYC
RFFR00745 Automatic evacuation alarm in UFA QJA-QJE SC4 SAS SCP CYC
Manual actuation of evacuation alarm in
RFFR00746 CYC SC4 SAS SCP CYC
UFA
Manual actuation of evacuation alarm in
RFFR00746 KLL SC4 SAS SCP CYC
UFA
RFFR00747 Automatic evacuation alarm in UKA CYC SC4 SAS SCP CYC
RFFR00747 Automatic evacuation alarm in UKA KLE SC4 SAS SCP CYC
RFFR00747 Automatic evacuation alarm in UKA QJA-QJE SC4 SAS SCP CYC
ECCN: N

RFFR00748 Automatic evacuation alarm in 31UJH CYC SC4 SAS SCP CYC
RFFR00748 Automatic evacuation alarm in 31UJH KLC SC4 SAS SCP CYC
RFFR00748 Automatic evacuation alarm in 31UJH KLE SC4 SAS SCP CYC
AL: N

RFFR00748 Automatic evacuation alarm in 31UJH QJA-QJE SC4 SAS SCP CYC
RFFR00749 Automatic evacuation alarm in 34UJH CYC SC4 SAS SCP CYC
RFFR00749 Automatic evacuation alarm in 34UJH KLC SC4 SAS SCP CYC
RFFR00749 Automatic evacuation alarm in 34UJH KLE SC4 SAS SCP CYC
RFFR00749 Automatic evacuation alarm in 34UJH QJA-QJE SC4 SAS SCP CYC
RFFR00750 Dose rate RB Refueling machine trolley JYK, KLK SC4 SAS SCP JYK - KLK
XJA10-40 SCP XJA-
RFFR00751 Excitation Control SC2 SSS
XKA10-40 XKA10-20-30-40
XJA10-40 SCP XJA-
RFFR00752 Speed Control SC2 SSS
XKA10-40 XKA10-20-30-40
XJA50/80, SCP XJA-XKA
RFFR00753 SBO Busbar Active Power SC3 SICS
XKA50/80 50/80
XJA10-40 SCP XJA-
RFFR00754 Emergency Busbar Active Power SC3 SICS
XKA10-40 XKA10-20-30-40
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A49 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
EDG
XJA10-40 SCP XJA-
RFFR00755 EDG Safety Excitation Control Actuation SC2 Safety
XKA10-40 XKA10-20-30-40
I&C
XJA10-40 SCP XJA-
RFFR00756 Safety Generator Protection SC2 SSS
XKA10-40 XKA10-20-30-40
XJA50/80, SCP XJA-XKA
RFFR00757 Engine controller over-speed SC3 SSS
XKA50/80 50/80
XJA50/80, SCP XJA-XKA
RFFR00758 Lubrication oil, low pressure SC3 SSS
XKA50/80 50/80
XJA50/80, SCP XJA-XKA
RFFR00759 Water HT cooling, Very High temperature SC3 SSS
XKA50/80 50/80
XJA50/80, SCP XJA-XKA
RFFR00760 Time over-current SC3 SSS
XKA50/80 50/80
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

RFFR00761 Manual Containment isolation stage 1 KTA-KTE SC4 PAS 1 SCP KT10/11
RFFR00762 Manual Containment isolation stage 1 KTA-KTE SC4 SAS SCP KT10/11
RFFR00763 Test of SA I&C functions in SAS SC4 SAS SCP I&C ARCH
RFFR00764 EBS actuation (train by train) JDH SC4 SAS SCP JDH
JNA; JND;
RFFR00765 EBS actuation (train by train) SC4 SAS SCP JN
JNG, JNK
RFFR00766 EBS actuation (train by train) JDH SC3 SICS SCP JDH
JNA; JND;
RFFR00767 EBS actuation (train by train) SC3 SICS SCP JN
JNG, JNK
KBA, KBD, SCP KBA-KBD-
RFFR00768 RCPB isolation SC4 SAS
JEW JEW
JNA; JND;
RFFR00769 RCPB isolation SC4 SAS SCP JN
JNG, JNK
RFFR00770 EBS isolation (train by train) JDH SC4 SAS SCP JDH
JNA; JND;
RFFR00771 EBS isolation (train by train) SC4 SAS SCP JN
JNG, JNK
RFFR00772 EBS isolation (train by train) JDH SC3 SICS SCP JDH
JNA; JND;
RFFR00773 EBS isolation (train by train) SC3 SICS SCP JN
JNG, JNK
RFFR00774 Secondary heat balance measurement LAB SC4 SSS SCP CPB
ECCN: N

RFFR00774 Secondary heat balance measurement LBA SC4 SSS SCP CPB
RFFR00775 EFWS SG level control valve position LAR, LAS SC4 SAS SCP LAR-LAS
RFFR00776 EFWS overflow limitation valve position LAR, LAS SC4 SAS SCP LAR-LAS
AL: N

RFFR00777 MS activity alarm JYK, KLK SC3 HBS SCP JYK - KLK
RFFR00777 MS activity alarm LBA SC3 HBS SCP JYK - KLK
Process Radioactivity Monitoring:
RFFR00778 Component Cooling Water System JYK, KLK SC4 SAS SCP JYK - KLK
(System KAB) monitoring
Process Radioactivity Monitoring:
RFFR00778 Component Cooling Water System KAA, KAB SC4 SAS SCP JYK - KLK
(System KAB) monitoring
Area Radiation and Airborne Radioactivity
RFFR00779 Monitoring: Airborne Radioactivity JYK, KLK SC3 SAS SCP JYK - KLK
Monitoring
Area Radiation and Airborne Radioactivity
RFFR00780 Monitoring: Local Dose Rate Monitoring: JYK, KLK SC3 SAS SCP JYK - KLK
dose rate fuel pool
Effluent Radioactivity Monitoring:
RFFR00781 Gaseous Effluent Monitoring: Stack JYK, KLK SC3 SAS SCP JYK - KLK
activity monitoring
RFFR00782 Failure of Iodine sampler stack Monitoring JYK, KLK SC4 SAS SCP JYK - KLK
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A50 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
RFFR00783 Failure of Aerosol sampler stack JYK, KLK SC4 SAS SCP JYK - KLK
RFFR00784 Failure of Iodine sampler stack JYK, KLK SC3 SAS SCP JYK - KLK
RFFR00785 Failure of Aerosol sampler stack JYK, KLK SC3 SAS SCP JYK - KLK
RFFR00786 Building isolation- Opening SGB SC4 PAS 1 SCP SG
RFFR00787 Building isolation- Stand by SGB SC4 PAS 1 SCP SG
RFFR00788 High neutron flux (source range) channel CYC SC4 PS SCP JKT
RFFR00788 High neutron flux (source range) channel JKT SC4 PS SCP JKT
Average of core outlet temperature SCP JKS
RFFR00789 JKS SC3 PS
(WR/NR) SPND/COT
SCP JKS
RFFR00790 core outlet temperature gradient JKS SC3 PS
SPND/COT
RFFR00791 MSIV position LBA SC3 SICS SCP LBA NI
RFFR00792 MSRIV position LBA SC3 SICS SCP LBA NI
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

RFFR00793 MCR air conditioning Building ISOL SAB SC4 SAS SCP SAB
RFFR00794 Actuation of Safety Chilled Water System QKA-QKC SC3 SICS SCP QK
XJA50/80, SCP XJA-XKA
RFFR00795 Start SBO diesel SC3 SSS
XKA50/80 50/80
SAD
RFFR00796 Start SBO diesel SC3 SAS SCP SAD-SAL
SAL
XJA50/80, SCP XJA-XKA
RFFR00797 SBO diesel monitoring SC3 SSS
XKA50/80 50/80
EDG
XJA10-40 SCP XJA-
RFFR00798 EDG Safety Speed Control Actuation SC2 Safety
XKA10-40 XKA10-20-30-40
I&C
RFFR00799
3 Automatic evacuation alarm in UKE CYC SC4 SAS SCP CYC
*
RFFR00799
Automatic evacuation alarm in UKE KLD SC4 SAS SCP CYC
*3
RFFR00799
Automatic evacuation alarm in UKE QJA-QJE SC4 SAS SCP CYC
*3
RFFR00800
3 Monitoring of BB *JMU JMU SC4 SAS SCP JMU
*
RFFR00801 monitoring of IRWST atmosphere
3 KUL SC4 SAS SCP KUL
ECCN: N

* sampling (BB *KUL)


Manual closure of the motor operated
RFFR00802 isolation valve 30JMQ12/42AA004 in the
3 JMQ SC4 SAS SCP JMQ
* flooding line (in case of leaking flooding
valve)
AL: N

Manual closure of the motor operated


RFFR00803 isolation valve 30JMQ12/42AA004 in the
3 JMQ SC3 SICS SCP JMQ
* flooding line (in case of leaking flooding
valve)
QHA
QHE
xFSD00001 Start boiler EYT SSS SSS Siemens
QHG
QHX
QHA
QHE
xFSD00002 Stop boiler EYT SSS SSS Siemens
QHG
QHX
QHA
QHE
xFSD00004 Circulation pump control EYT SSS SSS Siemens
QHG
QHX
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A51 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
QHA
QHE
xFSD00005 Volume control of boiler EYT SSS SSS Siemens
QHG
QHX
QHA
QHE
xFSD00006 Feedwater pump control EYT SSS SSS Siemens
QHG
QHX
QHA
Maintaining the boiler’s pressure and QHE
xFSD00007 EYT SSS SSS Siemens
reducing the boiler’s pressure QHG
QHX
QHA
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

QHE
xFSD00008 Boiler water’s conductivity control EYT SSS SSS Siemens
QHG
QHX
QHA
QHE
xFSD00009 Bottom blowdown EYT SSS SSS Siemens
QHG
QHX
QHA
QHE
xFSD00010 Deaerating the boiler EYT SSS SSS Siemens
QHG
QHX
QHA
QHE
xFSD00011 Cooling the protective cage EYT SSS SSS Siemens
QHG
QHX
QHA
QHE
xFSD00012 Heating of boiler during standby operation EYT SSS SSS Siemens
QHG
QHX
QHA
ECCN: N

QHE
xFSD00013 Pressure control of feedwater tank EYT SSS SSS Siemens
QHG
QHX
QHA
AL: N

QHE
xFSD00014 Level control of feedwater tank EYT SSS SSS Siemens
QHG
QHX
QHA
Overflow valve (30QHE03 AA404)
QHE
xFSD00015 opening on High water level (level switch EYT SSS SSS Siemens
QHG
30QHA03 CL001)
QHX
QHA
Keeping the feedwater tank “warm” and QHE
xFSD00016 EYT SSS SSS Siemens
pressurized during standby operation QHG
QHX
QHA
QHE
xFSD00017 Deaeration the feedwater tank EYT SSS SSS Siemens
QHG
QHX
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A52 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
QHA
Shut-off valve at terminal point to the QHE
xFSD00019 EYT SSS SSS Siemens
auxiliary steam system (LBG) QHG
QHX
QHA
QHE
xFSD00020 Flash tank cooling EYT SSS SSS Siemens
QHG
QHX
QHA
QHE
xFSD00021 Freeze protection of silencers EYT SSS SSS Siemens
QHG
QHX
Monitoring of QU (Sampling system water
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

xFSD00022 QUA-QUC SC4 SSS SSS Siemens


/steam cycle) system
Monitoring the water and steam quality of
xFSD00023 the conventional steamwater cycle, QUA-QUC EYT SSS SSS Siemens
cooling water system and auxiliary steams
Dry running protection in sample water
xFSD00024 QUA-QUC SC4 SSS SSS Siemens
tank
Dry running protection in the inlet of the
xFSD00025 QUA-QUC SC4 SSS SSS Siemens
condensate sampling system
Overheating protection of sampling
xFSD00026 QUA-QUC SC4 SSS SSS Siemens
system equipments through pump control
Overheating protection of sampling
xFSD00027 QUA-QUC SC4 SSS SSS Siemens
system equipments through valve control
xFSD00028 Dosing pumps control QCA EYT SSS SSS Siemens
Protections of the pumping equipment
xFSD00029 against dry running through level switch QCA EYT SSS SSS Siemens
(30QCA01CL102)
Monitoring of QCA (dosing system for
xFSD00030 QCA EYT SSS SSS Siemens
hydrazine)
Differential Pressure measurements (2/3
xFSD00031 logic for low pressure) to determine when SC4 TGI TGI (Siemens)
hydrogen pressure is in an abnormal state
ECCN: N

Turbine trip incase of hydrogen pressure


xFSD00032 SC4 TGI TGI (Siemens)
is in an abnormal state
Control and Monitoring of the exhaust gaz
xFSD00033 SC4 TGI TGI (Siemens)
system
AL: N

Convert torque from the steam turbines to


xFSD00034 SC4 TGI TGI (Siemens)
electrical power: Monitor temperature
CHY
CHY10/ACA/A
xFSD00035 Monitoring of the generator functions SC4 TGI TGI (Siemens)
CB/BAT/BBT/B
CT/MKA
xFSD00035 Monitoring of the generator functions SC4 TGI TGI (Siemens)
xFSD00036 Closing solenoid valve MKG29AA011 SC4 TGI TGI (Siemens)
xFSD00037 Flow monitoring with 30MKG29CF001 SC4 TGI TGI (Siemens)
Measuring Range Limiter
xFSD00038 SC4 TGI TGI (Siemens)
(30MKG29AA141)
Pressure mesurement 30MKG10CP001 to
xFSD00039 monitor if low hydrogen supply pressure SC4 TGI TGI (Siemens)
exists and Alarm
xFSD00040 Control of the rotating exciter set MKC EYT TGI TGI (Siemens)
xFSD00041 Monitoring of MKC - Exciter set MKC EYT TGI TGI (Siemens)
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A53 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Step Criteria for Gas Turbine Startup
xFSD00042 Program: signal "SEAL OIL PUMP N- MKW SC4 TGI TGI (Siemens)
FAUL T
Control of Seal Oil Pump 3
xFSD00043 MKW SC4 TGI TGI (Siemens)
(MKW13AP001)
Control of Seal Oil Pumps 1 and 2
xFSD00044 MKW SC4 TGI TGI (Siemens)
(MKW11AP001 and MKW12AP001)
Indication of pressure of Stator winding
xFSD00045 MKF EYT TGI TGI (Siemens)
cooling system
Control of Stator water pump skids and
xFSD00046 MKF EYT TGI TGI (Siemens)
treatment skid
Control of Stator water pump skids and
xFSD00046 MKF EYT TGI TGI (Siemens)
treatment skid
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

xFSD00047 Monitoring of the generator stator MKA SC4 TGI TGI (Siemens)
Provide a status condition of any liquid
that has entered the generator frame or
xFSD00048 MKA SC4 TGI TGI (Siemens)
lead box: liquid level sensors to detect any
leaks and provide an Alarm
Turbine trip by opening of the Fire
Protection Valve 30 MKG19AA025 or low
xFSD00050 generator pressure from 2/3 signals of MKG SC4 TGI TGI (Siemens)
30MKG18CP001, 30MKG18CP002,
30MKG18CP003
xFSD00051 Control of the gas cooling system MKG SC4 TGI TGI (Siemens)
Protection of the gas cooling system
xFSD00052 MKG SC4 TGI TGI (Siemens)
valves
Monitoring of the exhaust gas system:
xFSD00053 Initiation of 30MKQ81AN001 fan upon MKQ EYT TGI TGI (Siemens)
low low pressure of 30MKQ82CP001
Monitoring of the exhaust gas system:
xFSD00054 Initiation of 30MKQ82AN001 fan upon MKQ EYT TGI TGI (Siemens)
low low pressure of 30MKQ81CP001
Provide a purge gas for the changing of
xFSD00055 MKG SC4 TGI TGI (Siemens)
generator gas.
Monitoring of the gas changing system:
xFSD00056 Monitor the argon supply pressure MKG SC4 TGI TGI (Siemens)
ECCN: N

30MKG82CP001
LAA
Supplying of steam from the moisture
xFSD00057 LBS EYT PAS 2 PAS 2 Siemens
separator to feedwater tank
LBS50
AL: N

LAA
Monitoring of the extraction steam piping
xFSD00058 LBS EYT PAS 2 PAS 2 Siemens
system
LBS50
Stop protection condensate extraction
pumps30LCB11/12/13AP001 on
LAA
Feedwater storage tank Level 30LAA10
xFSD00060 LBS SC4 PAS 2 PAS 2 Siemens
CL001/002/003 >= HIGH 4 (incl. Alarm on
LBS50
Feedwater storage tank Level 30LAA10
CL001/002/003 >= HIGH 4)
Stop protection condensate extraction
pumps30LCB11/12/13AP001 on LCA
Feedwater storage tank Level 30LAA10 LCB
xFSD00060 SC4 PAS 2 PAS 2 Siemens
CL001/002/003 >= HIGH 4 (incl. Alarm on LCR
Feedwater storage tank Level 30LAA10 LCW
CL001/002/003 >= HIGH 4)
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A54 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Close protection condensate extraction
pump discharge valves LAA
xFSD00061 30LCA11/12/13AA003 on Feedwater LBS SC4 PAS 2 PAS 2 Siemens
storage tank Level 30LAA10 LBS50
CL001/002/003 >= HIGH 4
Close protection condensate extraction
LCA
pump discharge valves
LCB
xFSD00061 30LCA11/12/13AA003 on Feedwater SC4 PAS 2 PAS 2 Siemens
LCR
storage tank Level 30LAA10
LCW
CL001/002/003 >= HIGH 4
Close protection condensate control
LAA
valves 30LCA30AA101/102/111on
xFSD00062 LBS SC4 PAS 2 PAS 2 Siemens
Feedwater storage tank Level 30LAA10
LBS50
CL001/002/003 >= HIGH 4
Close protection condensate control LCA
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

valves 30LCA30AA101/102/111on LCB


xFSD00062 SC4 PAS 2 PAS 2 Siemens
Feedwater storage tank Level 30LAA10 LCR
CL001/002/003 >= HIGH 4 LCW
Close protection MSR drain valves
30LCT11/21AA101/004; LAA
xFSD00063 30LCS21/22AA121) on Feedwater LBS SC4 PAS 2 PAS 2 Siemens
storage tank Level 30LAA10 LBS50
CL001/002/003 >= HIGH 3
Close protection MSR drain valves
30LCT11/21AA101/004;
xFSD00063 30LCS21/22AA121) on Feedwater LCS SC4 PAS 2 PAS 2 Siemens
storage tank Level 30LAA10
CL001/002/003 >= HIGH 3
Close protection MSR drain valves
30LCT11/21AA101/004;
xFSD00063 30LCS21/22AA121) on Feedwater LCT SC4 PAS 2 PAS 2 Siemens
storage tank Level 30LAA10
CL001/002/003 >= HIGH 3
Stop protection MSR drain pump
LAA
30LCT11/21AP001 on Feedwater storage
xFSD00064 LBS SC4 PAS 2 PAS 2 Siemens
tank Level 30LAA10 CL001/002/003 >=
LBS50
HIGH 3
Stop protection MSR drain pump
ECCN: N

30LCT11/21AP001 on Feedwater storage


xFSD00064 LCT SC4 PAS 2 PAS 2 Siemens
tank Level 30LAA10 CL001/002/003 >=
HIGH 3
Close protection HP heater drains valves
LAA
30LCH61/62AA101 on Feedwater storage
AL: N

xFSD00065 LBS SC4 PAS 2 PAS 2 Siemens


tank Level 30LAA10 CL001/002/003 >=
LBS50
HIGH 3
Close protection HP heater drains valves
LAD
30LCH61/62AA101 on Feedwater storage
xFSD00065 LBQ SC4 PAS 2 PAS 2 Siemens
tank Level 30LAA10 CL001/002/003 >=
LCH
HIGH 3
Close protection main steam supply
LAA
control valves 30LBA81/82AA101on
xFSD00066 LBS SC4 PAS 2 PAS 2 Siemens
Feedwater storage tank Level 30LAA10
LBS50
CL001/002/003 >= HIGH 3
Close protection main steam supply
LAD
control valves 30LBA81/82AA101on
xFSD00066 LBQ SC4 PAS 2 PAS 2 Siemens
Feedwater storage tank Level 30LAA10
LCH
CL001/002/003 >= HIGH 3
Stop protection LP heater drains pump
LAA
30LCJ30AP001 on Feedwater storage
xFSD00067 LBS SC4 PAS 2 PAS 2 Siemens
tank Level 30LAA10 CL001/002/003 >=
LBS50
HIGH 2
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A55 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Stop protection LP heater drains pump
30LCJ30AP001 on Feedwater storage LCC
xFSD00067 SC4 PAS 2 PAS 2 Siemens
tank Level 30LAA10 CL001/002/003 >= LCJ
HIGH 2
Close protection LP heater A3 control
LAA
valve 30LCJ30AA101 on Feedwater
xFSD00068 LBS SC4 PAS 2 PAS 2 Siemens
storage tank Level 30LAA10
LBS50
CL001/002/003 >= HIGH 2
Close protection LP heater A3 control
valve 30LCJ30AA101 on Feedwater LCC
xFSD00068 SC4 PAS 2 PAS 2 Siemens
storage tank Level 30LAA10 LCJ
CL001/002/003 >= HIGH 2
Close protection aux. Steam CV
LAA
30LBG50AA101 on Feedwater storage
xFSD00069 LBS SC4 PAS 2 PAS 2 Siemens
tank Level 30LAA10 CL001/002/003 >=
LBS50
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

HIGH 2
Close protection aux. Steam CV
30LBG50AA101 on Feedwater storage LBG
xFSD00069 SC4 PAS 2 PAS 2 Siemens
tank Level 30LAA10 CL001/002/003 >= LCN
HIGH 2
Open emergency drain valve to
LAA
condenser 30LAA10AA405 on Feedwater
xFSD00070 LBS SC4 PAS 2 PAS 2 Siemens
storage tank Level 30LAA10
LBS50
CL001/002/003 >= HIGH 2
Close emergency drain valve to
LAA
condenser 30LAA10AA405 on Feedwater
xFSD00071 LBS SC4 PAS 2 PAS 2 Siemens
storage tank Level 30LAA10
LBS50
CL001/002/003 =< HIGH 1
Level control with 30LCA30AA101,
LAA
30LCA30AA102, 30LCA30AA111during
xFSD00072 LBS SC4 PAS 2 PAS 2 Siemens
Feedwater storage tank Level 30LAA10
LBS50
CL001/002/003 is within limits
Level control with 30LCA30AA101, LCA
30LCA30AA102, 30LCA30AA111during LCB
xFSD00072 SC4 PAS 2 PAS 2 Siemens
Feedwater storage tank Level 30LAA10 LCR
CL001/002/003 is within limits LCW
Enable start of feedwater pumps
LAA
30LAC11/12/13/14AP001 on Feedwater
xFSD00073 LBS SC4 PAS 2 PAS 2 Siemens
ECCN: N

storage tank Level 30LAA10


LBS50
CL001/002/003 >= LOW 1
Enable start of feedwater pumps LAB*
30LAC11/12/13/14AP001 on Feedwater LAC
xFSD00073 SC4 PAS 2 PAS 2 Siemens
AL: N

storage tank Level 30LAA10 LAH


CL001/002/003 >= LOW 1 LAJ
Close protection emergency drain valve
LAA
30LAA10AA405 to condenser on
xFSD00074 LBS SC4 PAS 2 PAS 2 Siemens
Feedwater storage tank Level 30LAA10
LBS50
CL001/002/003 =< LOW 1
Stop protection feedwater pumps
LAA
30LAC11/12/13/14AP001on Feedwater
xFSD00075 LBS SC4 PAS 2 PAS 2 Siemens
storage tank Level 30LAA10
LBS50
CL001/002/003 =< LOW 2
Stop protection feedwater pumps LAB*
30LAC11/12/13/14AP001on Feedwater LAC
xFSD00075 SC4 PAS 2 PAS 2 Siemens
storage tank Level 30LAA10 LAH
CL001/002/003 =< LOW 2 LAJ
Activation of feedwater storage tank
LAA
emergency level control 30LAA10DL902
xFSD00076 LBS SC4 PAS 2 PAS 2 Siemens
on Feedwater storage tank Level
LBS50
30LAA10 CL001/002/003 =< LOW 2
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A56 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Activation of feedwater storage tank LAB*
emergency level control 30LAA10DL902 LAC
xFSD00076 SC4 PAS 2 PAS 2 Siemens
on Feedwater storage tank Level LAH
30LAA10 CL001/002/003 =< LOW 2 LAJ
Enable start of feedwater startup/ shut-
LAA
down pump 30LAJ10AP001 on Feedwater
xFSD00077 LBS SC4 PAS 2 PAS 2 Siemens
storage tank Level 30LAA10
LBS50
CL001/002/003 > LOW 3
Enable start of feedwater startup/ shut- LAB*
down pump 30LAJ10AP001 on Feedwater LAC
xFSD00077 SC4 PAS 2 PAS 2 Siemens
storage tank Level 30LAA10 LAH
CL001/002/003 > LOW 3 LAJ
Stop protection feedwater startup/ shut-
LAA
down pump 30LAJ10AP001 on Feedwater
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

xFSD00078 LBS SC4 PAS 2 PAS 2 Siemens


storage tank Level 30LAA10
LBS50
CL001/002/003 =< LOW 4
Stop protection feedwater startup/ shut- LAB*
down pump 30LAJ10AP001 on Feedwater LAC
xFSD00078 SC4 PAS 2 PAS 2 Siemens
storage tank Level 30LAA10 LAH
CL001/002/003 =< LOW 4 LAJ
Feedwater tank emergency level control
xFSD00079 GHC SC4 PAS 2 PAS 2 Siemens
activation
LAA
Feedwater tank emergency level control
xFSD00079 LBS SC4 PAS 2 PAS 2 Siemens
activation
LBS50
xFSD00080 Feedwater Tank Emergency level control GHC SC4 PAS 2 PAS 2 Siemens
LAA
xFSD00080 Feedwater Tank Emergency level control LBS SC4 PAS 2 PAS 2 Siemens
LBS50
Opening the feedwater tank emergency
level control valve (3 0GHC60 AA101)
xFSD00081 supplying demineralised water from the GHC SC4 PAS 2 PAS 2 Siemens
demineralised water storage tanks (3
0GHC01/02 BB001)
Opening the feedwater tank emergency
level control valve (3 0GHC60 AA101) LAA
ECCN: N

xFSD00081 supplying demineralised water from the LBS SC4 PAS 2 PAS 2 Siemens
demineralised water storage tanks (3 LBS50
0GHC01/02 BB001)
Warming up feedwater tank maintaining
AL: N

LAA
pressure at 2 bar (a) by the auxiliary
xFSD00082 LBS SC4 PAS 2 PAS 2 Siemens
steam control valve (3 0LBG50 AA101) by
LBS50
a temperature gradient of 1 K/min
Warming up feedwater tank maintaining
pressure at 2 bar (a) by the auxiliary LBG
xFSD00082 SC4 PAS 2 PAS 2 Siemens
steam control valve (3 0LBG50 AA101) by LCN
a temperature gradient of 1 K/min
Limiting the opening of the auxiliary steam
LAA
control valve in case of the auxiliary steam
xFSD00083 LBS SC4 PAS 2 PAS 2 Siemens
header pressure (3 0LBG10 CP901)
LBS50
drops below 5 bar(a)
Limiting the opening of the auxiliary steam
control valve in case of the auxiliary steam LBG
xFSD00083 SC4 PAS 2 PAS 2 Siemens
header pressure (3 0LBG10 CP901) LCN
drops below 5 bar(a)
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A57 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Closing the control valve through LAA
xFSD00084 protection command in case of too high LBS SC4 PAS 2 PAS 2 Siemens
level in feedwater tank. LBS50
Closing the control valve through
LBG
xFSD00084 protection command in case of too high SC4 PAS 2 PAS 2 Siemens
LCN
level in feedwater tank.
Closing pegging steam controls valves (3
LAA
0LBA81/82 AA101) when the steam
xFSD00086 LBS SC4 PAS 2 PAS 2 Siemens
pressure in the moisture separator
LBS50
extraction rises above 2.2 bar (a)
Closing pegging steam controls valves (3
0LBA81/82 AA101) when the steam
xFSD00086 LBA* SC4 PAS 2 PAS 2 Siemens
pressure in the moisture separator
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

extraction rises above 2.2 bar (a)


LAA
Feedwater storage tank overpressure
xFSD00087 LBS SC4 PAS 2 PAS 2 Siemens
protection
LBS50
Opening of the pegging steam control
LAA
valves in case of a rapid pressure drop
xFSD00088 LBS SC4 PAS 2 PAS 2 Siemens
(>=0,4bar/min) and feedwater tank level is
LBS50
above the minimum level
Heater pressure protection : Indication in LAD
xFSD00089 main control room of HP heater A6 LBQ SC4 PAS 2 PAS 2 Siemens
pressure LCH
Heater pressure protection : Indication in LAD
xFSD00090 main control room of HP heater A7 LBQ SC4 PAS 2 PAS 2 Siemens
pressure LCH
Stop protective Feedwater pumps
30LAC11/12/13/14 AP001;
LAB*
30LAJ10AP001 on HP Heater A6 Level
LAC
xFSD00092 30LAD61/62CL001/002/003 (CL901)>= SC4 PAS 2 PAS 2 Siemens
LAH
HIGH 4 (inclu Alarm on HP Heater A6
LAJ
Level 30LAD61/62CL001/002/003
(CL901)>= HIGH 4)
Stop protective Feedwater pumps
ECCN: N

30LAC11/12/13/14 AP001;
30LAJ10AP001 on HP Heater A6 Level LAD
xFSD00092 30LAD61/62CL001/002/003 (CL901)>= LBQ SC4 PAS 2 PAS 2 Siemens
HIGH 4 (inclu Alarm on HP Heater A6 LCH
Level 30LAD61/62CL001/002/003
AL: N

(CL901)>= HIGH 4)
Heater bypass operation on HP Heater A6
Level 30LAD61/62CL001/002/003 LAB*
(CL901)>= HIGH 3 (inlu. Alarm on HP LAC
xFSD00094 SC4 PAS 2 PAS 2 Siemens
Heater A6 Level LAH
30LAD61/62CL001/002/003 (CL901)>= LAJ
HIGH 3)
Heater bypass operation on HP Heater A6
Level 30LAD61/62CL001/002/003
LAD
(CL901)>= HIGH 3 (inlu. Alarm on HP
xFSD00094 LBQ SC4 PAS 2 PAS 2 Siemens
Heater A6 Level
LCH
30LAD61/62CL001/002/003 (CL901)>=
HIGH 3)
Close protective MSR stage 1 normal
drains control valve 30LCS11/12 AA101
LAD
on HP Heater A6 Level
xFSD00096 LBQ EYT PAS 2 PAS 2 Siemens
30LAD61/62CL001/002/003 (CL901)>=
LCH
HIGH 2 (incl. Alarm on HP Heater A6
Level 30LAD61/62CL001/002/003
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A58 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
(CL901)>= HIGH 2)

Close protective MSR stage 1 normal


drains control valve 30LCS11/12 AA101
on HP Heater A6 Level
xFSD00096 30LAD61/62CL001/002/003 (CL901)>= LCS EYT PAS 2 PAS 2 Siemens
HIGH 2 (incl. Alarm on HP Heater A6
Level 30LAD61/62CL001/002/003
(CL901)>= HIGH 2)
Close protective HP heater A7 normal
LAD
drains control valve on HP Heater A6
xFSD00097 LBQ EYT PAS 2 PAS 2 Siemens
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

Level 30LAD61/62CL001/002/003
LCH
(CL901)>= HIGH 2
Start-up drains level control 30LCH61/62
LAD
AA111 on HP Heater A6 Level
xFSD00098 LBQ EYT PAS 2 PAS 2 Siemens
30LAD61/62CL001/002/003 (CL901)>=
LCH
HIGH 1
Normal drains level control with
LAD
30LCH61/62 AA101on HP Heater A6
xFSD00099 LBQ EYT PAS 2 PAS 2 Siemens
Level 30LAD61/62CL001/002/003
LCH
(CL901) within limits
Close protective normal drains valve on
HP Heater A6 Level
30LAD61/62CL001/002/003 (CL901)
=<LOW 2 (incl. Warning on HP Heater A6 LAD
xFSD00102 Level 30LAD61/62CL001/002/003 LBQ EYT PAS 2 PAS 2 Siemens
(CL901) =<LOW 1 and Alarm on HP LCH
Heater A6 Level
30LAD61/62CL001/002/003 (CL901)
=<LOW 2)
Close protective start-up drains valve on
LAD
HP Heater A6 Level
xFSD00103 LBQ EYT PAS 2 PAS 2 Siemens
30LAD61/62CL001/002/003 (CL901)
LCH
=<LOW 2
Stop protective Feedwater pumps
ECCN: N

30LAC11/12/13/14 AP001,
LAB*
30LAJ10AP001on HP Heater A7 Level
LAC
xFSD00105 30LAD71/72 CL001/002/003 (CL901) >= SC4 PAS 2 PAS 2 Siemens
LAH
HIGH 4 (incl. Alarm on HP Heater A7
LAJ
Level 30LAD71/72 CL001/002/003
AL: N

(CL901) >= HIGH 4)


Stop protective Feedwater pumps
30LAC11/12/13/14 AP001,
30LAJ10AP001on HP Heater A7 Level LAD
xFSD00105 30LAD71/72 CL001/002/003 (CL901) >= LBQ SC4 PAS 2 PAS 2 Siemens
HIGH 4 (incl. Alarm on HP Heater A7 LCH
Level 30LAD71/72 CL001/002/003
(CL901) >= HIGH 4)
Heater bypass operation 30LAB31/32
AA404/406 on HP Heater A7 Level LAB*
30LAD71/72 CL001/002/003 (CL901) >= LAC
xFSD00107 SC4 PAS 2 PAS 2 Siemens
HIGH 3 (incl Alarm on HP Heater A7 LAH
Level 30LAD71/72 CL001/002/003 LAJ
(CL901) >= HIGH 3)
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A59 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Heater bypass operation 30LAB31/32
AA404/406 on HP Heater A7 Level
LAD
30LAD71/72 CL001/002/003 (CL901) >=
xFSD00107 LBQ SC4 PAS 2 PAS 2 Siemens
HIGH 3 (incl Alarm on HP Heater A7
LCH
Level 30LAD71/72 CL001/002/003
(CL901) >= HIGH 3)
Close protective MSR stage 2 normal
drain control valve 30LCS21/22 AA101 on
HP Heater A7 Level 30LAD71/72 LAD
xFSD00109 CL001/002/003 (CL901) >= HIGH 2 (incl. LBQ EYT PAS 2 PAS 2 Siemens
Alarm on HP Heater A7 Level LCH
30LAD71/72 CL001/002/003 (CL901) >=
HIGH 2)
Close protective MSR stage 2 normal
drain control valve 30LCS21/22 AA101 on
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

HP Heater A7 Level 30LAD71/72


xFSD00109 CL001/002/003 (CL901) >= HIGH 2 (incl. LCS EYT PAS 2 PAS 2 Siemens
Alarm on HP Heater A7 Level
30LAD71/72 CL001/002/003 (CL901) >=
HIGH 2)
Close protective MSR stage 2 normal
LAD
drain isolation valve 30LCS21/22AA002
xFSD00110 LBQ EYT PAS 2 PAS 2 Siemens
on HP Heater A7 Level 30LAD71/72
LCH
CL001/002/003 (CL901) >= HIGH 2
Close protective MSR stage 2 normal
drain isolation valve 30LCS21/22AA002
xFSD00110 LCS EYT PAS 2 PAS 2 Siemens
on HP Heater A7 Level 30LAD71/72
CL001/002/003 (CL901) >= HIGH 2
Close protective bypass valve reheater
LAD
stage 2 drain on HP Heater A7 Level
xFSD00111 LBQ EYT PAS 2 PAS 2 Siemens
30LAD71/72 CL001/002/003 (CL901) >=
LCH
HIGH 2
Close protective bypass valve reheater
stage 2 drain on HP Heater A7 Level
xFSD00111 LCS EYT PAS 2 PAS 2 Siemens
30LAD71/72 CL001/002/003 (CL901) >=
HIGH 2
Start-up drains level control on HP Heater LAD
ECCN: N

xFSD00112 A7 Level 30LAD71/72 CL001/002/003 LBQ EYT PAS 2 PAS 2 Siemens


(CL901) >= HIGH 1 LCH
Normal drains level control with
LAD
30LCH71/72 AA101on HP Heater A7
xFSD00113 LBQ EYT PAS 2 PAS 2 Siemens
Level 30LAD71/72CL001/002/003
AL: N

LCH
(CL901) within limits
Close protective normal drains valve
30LCH71/72 AA101 on HP Heater A7
Level 30LAD71/72 CL001/002/003
(CL901) =< LOW 2 (incl. Warning on HP LAD
xFSD00116 Heater A7 Level 30LAD71/72 LBQ EYT PAS 2 PAS 2 Siemens
CL001/002/003 (CL901) =< LOW 1 and LCH
Alarm on HP Heater A7 Level
30LAD71/72 CL001/002/003 (CL901) =<
LOW 2 )
Close protective start-up drains valve
LAD
30LCH71/72 AA111 on HP Heater A7
xFSD00117 LBQ EYT PAS 2 PAS 2 Siemens
Level 30LAD71/72 CL001/002/003
LCH
(CL901) =< LOW 2
LAD
Indication in main control room of HP
xFSD00118 LBQ EYT PAS 2 PAS 2 Siemens
heater A6 drains flow
LCH
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A60 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
LAD
Indication in main control room of HP
xFSD00119 LBQ EYT PAS 2 PAS 2 Siemens
heater A6 drains temperature
LCH
LAD
Indication in main control room of HP
xFSD00120 LBQ EYT PAS 2 PAS 2 Siemens
heater A7 drains flow
LCH
LAD
Indication in main control room of HP
xFSD00121 LBQ EYT PAS 2 PAS 2 Siemens
heater A7 drains temperature
LCH
Indication in main control room of the LAD
xFSD00122 extraction steam temperature upstream LBQ EYT PAS 2 PAS 2 Siemens
heater A6 LCH
Indication in main control room of the LAD
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

xFSD00123 extraction steam temperature upstream LBQ EYT PAS 2 PAS 2 Siemens
heater A7 LCH
LAB*
Feedwater pump minimum flow control LAC
xFSD00128 SC4 PAS 2 PAS 2 Siemens
(30 LAB11/12/13/14 DF121) LAH
LAJ
LAB*
Start-up/shutdown feedwater pump LAC
xFSD00129 SC4 PAS 2 PAS 2 Siemens
pressure control (3 0LAH10 DP901) LAH
LAJ
Automatic switch off of the second and LAB*
third feedwater pump during reactor trip or LAC
xFSD00130 SC4 PAS 2 SCP CLT
turbine trip, when signal 30LAC00EZ001 LAH
XV51 is not present LAJ
Automatic switch on of the second
LAB*
feedwater pump via signal
LAC
xFSD00131 30JSC00DF251AY XR20, switch off of the SC4 PAS 2 SCP CLT
LAH
second running pump when the signal is
LAJ
not present
Automatic switch on of the third feedwater LAB*
pump via signal 30JSC00DF251BY XR30, LAC
xFSD00132 SC4 PAS 2 SCP CLT
ECCN: N

switch off of the third running pump when LAH


the signal is not present LAJ
LAB*
Manual start of the subgroup control start-
LAC
AL: N

xFSD00133 up/shutdown feedwater pump SC4 PAS 2 PAS 2 Siemens


LAH
30LAJ10EC001
LAJ
LAB*
Shutdown of the last running feedwater LAC
xFSD00134 SC4 PAS 2 PAS 2 Siemens
pump LAH
LAJ
Protection OFF command of the
LAB*
feedwater pumps (30LAC11/12/13/14
LAC
xFSD00135 AP001) in case of high bearing SC4 PAS 2 PAS 2 Siemens
LAH
temperature (30LAC11/12/13/14 CT
LAJ
911/913/915/977/979)
Protection OFF command of the LAB*
feedwater pumps (30LAC11/12/13/14 LAC
xFSD00136 SC4 PAS 2 PAS 2 Siemens
AP001) in case of high feedwater flow LAH
(30LAB11/12/13/14 CF901) LAJ
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A61 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Protection OFF command of the
LAB*
feedwater pumps (30LAC11/12/13/14
LAC
xFSD00137 AP001) in case of high motor winding SC4 PAS 2 PAS 2 Siemens
LAH
temperature (30LAC11/12/13/14
LAJ
CT971/973/975)
Protection OFF command of the LAB*
feedwater pumps (30LAC11/12/13/14 LAC
xFSD00138 SC4 PAS 2 PAS 2 Siemens
AP001) in case of low level in lube oil LAH
tank (30LAC11/12/13/14 CL933) LAJ
Protection OFF command of the LAB*
feedwater pumps (30LAC11/12/13/14 LAC
xFSD00139 SC4 PAS 2 PAS 2 Siemens
AP001) in case of low minimum flow LAH
(30LAB11/12/13/14 CF901) LAJ
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

Protection OFF command of the LAB*


feedwater pumps (30LAC11/12/13/14 LAC
xFSD00140 SC4 PAS 2 PAS 2 Siemens
AP001) in case of low lube oil pressure LAH
(30LAC11/12/13/14 CP931) LAJ
Protection OFF command of the Start- LAB*
up/shutdown feedwater pumps (30LAJ10 LAC
xFSD00142 SC4 PAS 2 PAS 2 Siemens
AP001) in case of high bearing LAH
temperature (30LAJ10 CT 903/977/979) LAJ
Protection OFF command of the Start- LAB*
up/shutdown feedwater pumps (30LAJ10 LAC
xFSD00143 SC4 PAS 2 PAS 2 Siemens
AP001) in case of high feedwater flow LAH
(30LAH10 CF901) LAJ
Protection OFF command of the Start- LAB*
up/shutdown feedwater pumps (30LAJ10 LAC
xFSD00144 SC4 PAS 2 PAS 2 Siemens
AP001) in case of high motor winding LAH
temperature (30LAJ10 CT971/973/975) LAJ
Protection OFF command of the Start- LAB*
up/shutdown feedwater pumps (30LAJ10 LAC
xFSD00145 SC4 PAS 2 PAS 2 Siemens
AP001) in case of low level in lube oil LAH
tank (30LAJ10 CL933) LAJ
Protection OFF command of the Start- LAB*
ECCN: N

up/shutdown feedwater pumps (30LAJ10 LAC


xFSD00146 SC4 PAS 2 PAS 2 Siemens
AP001) in case of low lube oil pressure LAH
(30LAJ10 CP931) LAJ
LAB*
AL: N

LAC
xFSD00147 Monitoring of the feedwater system SC4 PAS 2 PAS 2 Siemens
LAH
LAJ
LBG
xFSD00148 Monitoring of the auxiliary steam system EYT PAS 2 PAS 2 Siemens
LCN
Monitoring of collection and discharge of
xFSD00151 LCS EYT PAS 2 PAS 2 Siemens
drains
Close protective heating steam valve on
reheater Stage 1 Condensate Tank Level
LBB
30LCS11/12 CL001/002/003 (CL901) >=
xFSD00153 LBC EYT PAS 2 PAS 2 Siemens
HIGH 2 (inlu. Alarm on reheater Stage 1
LBJ
Condensate Tank Level 30LCS11/12
CL001/002/003 (CL901) >= HIGH 2)
Close protective heating steam valve on
reheater Stage 1 Condensate Tank Level
xFSD00153 30LCS11/12 CL001/002/003 (CL901) >= LCS EYT PAS 2 PAS 2 Siemens
HIGH 2 (inlu. Alarm on reheater Stage 1
Condensate Tank Level 30LCS11/12
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A62 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
CL001/002/003 (CL901) >= HIGH 2)

Start-Up / Emergency drains level control


(incl. Warning on reheater Stage 1
xFSD00155 LCS EYT PAS 2 PAS 2 Siemens
Condensate Tank Level 30LCS11/12
CL001/002/003 (CL901) >= HIGH 1)
Normal drains level control on reheater
Stage 1 Condensate Tank Level
xFSD00156 LCS EYT PAS 2 PAS 2 Siemens
30LCS11/12 CL001/002/003 (CL901)
within range
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

Close protective normal drains valve on


reheater Stage 1 Condensate Tank Level
30LCS11/12 CL001/002/003 (CL901) =<
LOW 2 (inclu. Warning on reheater Stage
xFSD00159 1 Condensate Tank Level 30LCS11/12 LCS EYT PAS 2 PAS 2 Siemens
CL001/002/003 (CL901) =< LOW 1 and
Alarm on reheater Stage 1 Condensate
Tank Level 30LCS11/12 CL001/002/003
(CL901) =< LOW 2)
Close protective Start-Up / emergency
drains valve on reheater Stage 1
xFSD00160 LCS EYT PAS 2 PAS 2 Siemens
Condensate Tank Level 30LCS11/12
CL001/002/003 (CL901) =< LOW 2
Injection water control of the reheater
xFSD00161 stage 1 drains piping (3 0LCS11/12 LCS EYT PAS 2 PAS 2 Siemens
DT131)
Close protective steam valves on reheater
Stage 2 Condensate Tank Level
LBB
30LCS21/22 CL001/002/003 (CL901) >=
xFSD00163 LBC EYT PAS 2 PAS 2 Siemens
HIGH 2 (incl. Alarm on reheater Stage 2
LBJ
Condensate Tank Level 30LCS21/22
CL001/002/003 (CL901) >= HIGH 2)
Close protective steam valves on reheater
Stage 2 Condensate Tank Level
ECCN: N

30LCS21/22 CL001/002/003 (CL901) >=


xFSD00163 LCS EYT PAS 2 PAS 2 Siemens
HIGH 2 (incl. Alarm on reheater Stage 2
Condensate Tank Level 30LCS21/22
CL001/002/003 (CL901) >= HIGH 2)
Start-up drains level control on reheater
AL: N

Stage 2 Condensate Tank Level


30LCS21/22 CL001/002/003 (CL901) =
xFSD00165 SET POINT 2 (incl. Warning on reheater LCS EYT PAS 2 PAS 2 Siemens
Stage 2 Condensate Tank Level
30LCS21/22 CL001/002/003 (CL901) >=
HIGH 1)
Emergency drains level control on
reheater Stage 2 Condensate Tank Level
xFSD00166 LCS EYT PAS 2 PAS 2 Siemens
30LCS21/22 CL001/002/003 (CL901) =
SET POINT 1
Normal drains level control when reheater
xFSD00167 Stage 2 Condensate Tank Level is within LCS EYT PAS 2 PAS 2 Siemens
limits
Enable opening of steam valves on
reheater Stage 2 Condensate Tank Level
LBB
30LCS21/22 CL001/002/003 (CL901) =<
xFSD00169 LBC EYT PAS 2 PAS 2 Siemens
LOW 2 (incl. Warning on reheater Stage 2
LBJ
Condensate Tank Level 30LCS21/22
CL001/002/003 (CL901) =< LOW 1)
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A63 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Enable opening of steam valves on
reheater Stage 2 Condensate Tank Level
30LCS21/22 CL001/002/003 (CL901) =<
xFSD00169 LCS EYT PAS 2 PAS 2 Siemens
LOW 2 (incl. Warning on reheater Stage 2
Condensate Tank Level 30LCS21/22
CL001/002/003 (CL901) =< LOW 1)
Close protective normal drains valve on
reheater Stage 2 Condensate Tank Level
30LCS21/22 CL001/002/003 (CL901) too
xFSD00171 LCS EYT PAS 2 PAS 2 Siemens
low (incl. Alarm on reheater Stage 2
Condensate Tank Level 30LCS21/22
CL001/002/003 (CL901) too low)
Close protective emergency drains valve
on reheater Stage 2 Condensate Tank
xFSD00172 LCS EYT PAS 2 PAS 2 Siemens
Level 30LCS21/22 CL001/002/003
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

(CL901) too low


Close protective start-up drains valve on
reheater Stage 2 Condensate Tank Level
xFSD00173 LCS EYT PAS 2 PAS 2 Siemens
30LCS21/22 CL001/002/003 (CL901) too
low
Injection water control of the reheater
xFSD00174 stage 2 emergency drains piping (3 LCS EYT PAS 2 PAS 2 Siemens
0LCS21/22 DT141)
xFSD00175 Control of wash water pump PAA SC4 SSS SSS Siemens
Control of circulating water screening
equipment : Screening the circulating
water and essential service water required
xFSD00176 PAA SC4 SSS SSS Siemens
for the plant and to keep the circulating
water and essential service water free of
fouling.
xFSD00177 Control of chopper pumps PAA EYT SSS SSS Siemens
Manual control (PAA - Circulating water
xFSD00178 screening plant) of equipment for repair PAA EYT SSS SSS Siemens
and maintenance
xFSD00179 Control of electrical inline heater PAA SC4 SSS SSS Siemens
xFSD00180 Control of heating pump PAA SC4 SSS SSS Siemens
xFSD00181 Control of stationary raking machines PAA SC4 SSS SSS Siemens
ECCN: N

xFSD00182 Control of traveling band screens PAA SC4 SSS SSS Siemens
Supply of the turbine valves with SCB
xFSD00183 compressed air: Indication of the system QFB EYT PAS 2 PAS 2 Siemens
pressure SCA
AL: N

SCB
xFSD00184 Monitoring of the compressor units QFB EYT SSS SCP SB NI
SCA
SCB
Supply of the plant with compressed air:
xFSD00185 QFB EYT SSS SCP SB NI
Black Box I&C
SCA
Isolation of non-protected system part SCB
xFSD00186 inside containment and pressure QFB EYT PAS 1 SCP SCB1 NI
monitoring SCA
Control of Nitrogen (N2) Gas Distribution
xFSD00188 QJA-QJE EYT SSS SCP QJ NI
System
Control of Nitrogen (N2) Gas supply to the
xFSD00189 reactor pressure vessel head 30JAA and QJA-QJE EYT PAS 1 SCP QJ NI
the primary coolant pumps 30JEB.
Control of Oxygen (O2) Gas Distribution
xFSD00190 QJA-QJE EYT SSS SCP QJ NI
System
xFSD00193 Control of Hydrogen (H2) Gas Distribution QJA-QJE EYT SSS SCP QJ NI
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A64 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
System
Control of Argon-Methane (Ar/CH4) Gas
xFSD00194 QJA-QJE EYT SSS SCP QJ NI
Distribution System
Control of Argon (Ar) Gas Distribution
xFSD00195 QJA-QJE EYT SSS SCP QJ NI
System
Monitoring of sump levels, collecting,
xFSD00196 GM EYT SSS SCP GM NI
treatment and discharge of drainages
Automatic protective action: Shut down of
the corresponding ESWS pump
xFSD00198 GM SC3 SAS SCP GM NI
(PEB10/20/30/40 AP001) if flooding is
detected
Automatic protective action: Shut down of
the corresponding ESWS pump
xFSD00198 PEB/PEH SC3 SAS SCP GM NI
(PEB10/20/30/40 AP001) if flooding is
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

detected
Automatic protective action: Protective
close of the corresponding ESWS
xFSD00199 GM SC3 SAS SCP GM NI
isolation valve (30PEB10/20/30/40
AA005) if flooding is detected
Automatic protective action: Protective
close of the corresponding ESWS
xFSD00199 PEB/PEH SC3 SAS SCP GM NI
isolation valve (30PEB10/20/30/40
AA005) if flooding is detected
Automatic protective action: Shut down of
the Anti Icing Pumps (30PAC41/42/43
AP001) if flooding is detected (incl. Alarm
xFSD00201 in case water level >0.1m in the room GM SC3 SAS SCP GM NI
(30GMQ11/13/21/23/31/32/41/42
CL003/004 and 30GMQ35/45/46
CL001/002))
Automatic protective action: Shut down of
the Anti Icing Pumps (30PAC41/42/43 PAB
AP001) if flooding is detected (incl. Alarm PAC
xFSD00201 in case water level >0.1m in the room PAH SC3 SAS SCP GM NI
(30GMQ11/13/21/23/31/32/41/42 PUE
CL003/004 and 30GMQ35/45/46 PUR
CL001/002))
EYT manual sump draining I&C function
ECCN: N

xFSD00204 GM EYT SSS SCP GM NI


(TI related)
EYT automatic sump draining I&C
function of the Emergency Diesel
xFSD00205 Buildings, Essential Service Water GM EYT SSS SCP GM NI
AL: N

Buildings, Access Buildings and Channels


(TI related)
PROTECTION CLOSE signal for the
isolation valves 30GKB10 AA001/002 in
case GKB level measurements >=MAX at
xFSD00208 GKB SC4 PAS 1 SCP GKB NI
each level measurement (incl. Alarm in
case GKB level measurements >=MAX at
each level measurement)
PROTECTION CLOSE signal for the
isolation valves 30GKB10 AA001/002 in
case GKB level measurements >=MAX at
xFSD00208 KTA-KTE SC4 PAS 1 SCP GKB NI
each level measurement (incl. Alarm in
case GKB level measurements >=MAX at
each level measurement)
Supply of drinking water to the different
consumers in Access Building UKE: hot
xFSD00209 water supply temperature measurements GKB EYT PAS 1 SCP GKB NI
30GKB13CT001/CT002 for control of the
valve 30SBE22AA101
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A65 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Supply of drinking water to the different
consumers in Access Building UKE: hot
xFSD00209 water supply temperature measurements SBA EYT PAS 1 SCP GKB NI
30GKB13CT001/CT002 for control of the
valve 30SBE22AA101
Closed loop control of the heating water
xFSD00212 supply temperature and heating capacity SBA EYT SSS SSS Siemens
from heat exchangers 30SBA10/20AC001
Open valve in 30GHC demineralized
xFSD00213 water system when heating water level in SBA EYT SSS SSS Siemens
expansion tank 30SBA40CL001 is low
Close valve in 30GHC demineralized
water system when control of heating
xFSD00214 SBA EYT SSS SSS Siemens
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

water level in expansion tank


30SBA40CL001 is high
Switch ON of the re circulation air heaters
30SBZ70AH001 – 30SBZ70AH010 in 4
xFSD00215 groups when the room temperature in SBA EYT SSS SSS Siemens
30UMY Pipe bridge 30SBZ70
CT001/2/3/4 is low
Switch OFF of the re circulation air
heaters 30SBZ70AH001 –
xFSD00216 30SBZ70AH010 in 4 groups when the SBA EYT SSS SSS Siemens
room temperature in 30UMY Pipe bridge
30SBZ70 CT001/2/3/4 is high
Switch ON re circulation air heaters in 4
groups when the room temperature in
xFSD00217 SBA EYT SSS SSS Siemens
30UMA building 30SBM03/06/11/14
CT001 is low
Switch OFF re circulation air heaters in 4
groups when the room temperature in
xFSD00218 SBA EYT SSS SSS Siemens
30UMA building 30SBM03/06/11/14
CT001 is High
xFSD00221 Protection of condensate system 30LCN SBA EYT SSS SSS Siemens
Protection of heating water system from
xFSD00222 LOW heating water level in expansion SBA EYT SSS SSS Siemens
tank 30SBA40BB001
ECCN: N

Protection of heating water system from


xFSD00223 SBA EYT SSS SSS Siemens
LOW pressure
Protection of heating water system from
xFSD00224 SBA EYT SSS SSS Siemens
AL: N

over temperature
Protection of heating water system from
xFSD00225 SBA EYT SSS SSS Siemens
overpressure
Control of chilled water supply
xFSD00227 QNM EYT SSS SSS Siemens
temperature of chilled water machines
Chilled water machine and relevant chilled
water re circulation pump switched ON on
xFSD00228 QNM EYT SSS SSS Siemens
water flow measurement 30QNM04CF001
high
Chilled water machine and relevant chilled
water re circulation pump switched OFF
xFSD00229 QNM EYT SSS SSS Siemens
on water flow measurement
30QNM04CF001 low
Freeze protection chilled water machines
30QNM01/02/03 through the Protection
xFSD00230 OFF command of the chilled water QNM EYT SSS SSS Siemens
machines in case of LOW temperature in
evaporator inside the chilled water
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A66 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
machine

Protection of chilled water machines


30QNM01/02/03 through the Protection
OFF command of chilled water machines
xFSD00231 in case of failure in cooling water 30PGB QNM EYT SSS SSS Siemens
supply or failure in chilled water supply
from the relevant re circulation pumps
30QNM01/02/03AP001
Protection of re circulation chilled water
pumps 30QNM01/02/03,
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

30QNM04AP001/2 through the protection


xFSD00232 QNM EYT SSS SSS Siemens
OFF command of the pumps in case of
LOW pressure in chilled water system
30QNM04CP002
Closed loop control of de mineralized
QMA, QME,
xFSD00233 water level in steam evaporator EYT SSS SCP QM NI
QMK, QMS
30QMA01AC001
Closed loop control of the condensate QMA, QME,
xFSD00234 EYT SSS SCP QM NI
level in hot well tank 30QMA02BB001 QMK, QMS
Closed loop control of the air
QMA, QME,
xFSD00235 humidification steam pressure in steam EYT SSS SCP QM NI
QMK, QMS
supply line to NI
Desalting of the steam evaporator
30QMA01AC001: OPEN / CLOSURE of QMA, QME,
xFSD00236 EYT SSS SCP QM NI
de salting valve in determined time QMK, QMS
intervals
Protection of components in 30QMA QMA, QME,
xFSD00237 EYT SSS SCP QM NI
system QMK, QMS
Control of outside air and return air flow
dampers 30SAM11AA001/2/3/5/6/7,
xFSD00238 SAM1 EYT SSS SSS Siemens
30SAM12AA001/2/3/5/6/7 in supply air
units
Air intake openings 30SAM10AA001-24
ECCN: N

xFSD00239 OPENED in stages on room temperature SAM1 EYT SSS SSS Siemens
sensors value 30SAM19CT001/2/3 high
Exhaust air roof fans 30SAM19AN001-12
Switched ON in stages on room
xFSD00240 SAM1 EYT SSS SSS Siemens
AL: N

temperature sensors value


30SAM19CT001/2/3 high
Air intake openings 30SAM10AA001-24
xFSD00241 CLOSED in stages on room temperature SAM1 EYT SSS SSS Siemens
sensors value 30SAM19CT001/2/3 low
Exhaust air roof fans 30SAM19AN001-12
Switched OFF in stages on room
xFSD00242 SAM1 EYT SSS SSS Siemens
temperature sensors value
30SAM19CT001/2/3 low
Control of heating water valves
30SBM21/22/23/24AA101 to supply air
xFSD00243 SAM1 EYT SSS SSS Siemens
heaters 30SAM11/12AC001/2 in supply
air to turbine hall
Switch ON roof top cooling unit
SAM13AH001/2 in stages on HVAC
xFSD00244 SAM1 EYT SSS SSS Siemens
cubicle room temperature
30SAM13CT001 high
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A67 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Switch OFF roof top cooling unit
SAM13AH001/2 in stages on HVAC
xFSD00245 SAM1 EYT SSS SSS Siemens
cubicle room temperature
30SAM13CT001 low
Air intake opening 30SAM10AA025 or
30SAM10AA026 OPENED on room
xFSD00246 SAM1 EYT SSS SSS Siemens
temperature 30SAM18CT002 in lift
machine room in UMA building high
Exhaust air fan 30SAM18AN004 lift
machine room switched ON on room
xFSD00247 SAM1 EYT SSS SSS Siemens
temperature 30SAM18CT002 in lift
machine room in UMA building high
Air intake opening 30SAM10AA025 or
30SAM10AA026 CLOSED on room
xFSD00248 SAM1 EYT SSS SSS Siemens
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

temperature 30SAM18CT002 in lift


machine room in UMA building low
Exhaust air fan 30SAM18AN004 lift
machine room switched OFF on room
xFSD00249 SAM1 EYT SSS SSS Siemens
temperature 30SAM18CT002 in lift
machine room in UMA building low
Protection ON command of the heating
water pumps 30SBM21-24AP001 on
xFSD00250 SAM1 EYT SSS SSS Siemens
LOW2 supply air temperature
30SAM11CT002/3, 30SAM12CT001/2
Protection OPEN command of the heating
water valves 30SBM21-24AA101 on low
xFSD00251 SAM1 EYT SSS SSS Siemens
LOW2 supply air temperature
30SAM11CT002/3, 30SAM12CT001/2
Protection CLOSE command of outside
air multi leaf damper
xFSD00252 30SAM11/12AA001/2/5/6 in case of SAM1 EYT SSS SSS Siemens
LOW3 supply air temperature
30SAM11CT002/3, 30SAM12CT001/2
Monitoring of 30SAM1 (Ventilation system
xFSD00253 for turbine building): Fault, Alarm SAM1 EYT SSS SSS Siemens
indication
Control of outside-, return and exhaust air
ECCN: N

xFSD00254 flow dampers 30SAC70AA001/2/3/4; SAC70 EYT SSS SSS Siemens


30SAC72AA021/22
Control of heating water valve to pre
xFSD00255 SAC70 EYT SSS SSS Siemens
heaters 30SAC70AC001/2
AL: N

Control of heating water valves to pre


heaters 30SAC70AC001/2, coolers
xFSD00256 SAC70 EYT SSS SSS Siemens
30SAC70AC003/4 and heaters
30SAC70AC005/6 in sequence
Control of heating water valve to heaters
xFSD00257 SAC70 EYT SSS SSS Siemens
30SAC74AC001
Control of electrical supply air humidifier
xFSD00258 SAC70 EYT SSS SSS Siemens
30SAC70AH001/2; 30SAC70AH003/4
Electrical air heater 30SAC71AH001 in
supply air to battery room Switched on
xFSD00259 SAC70 EYT SSS SSS Siemens
room temperature in battery rooms
30SAC71CT003 low
Electrical air heater 30SAC71AH001 in
supply air to battery room Switched OFF
xFSD00260 SAC70 EYT SSS SSS Siemens
on room temperature in battery rooms
30SAC71CT003 high
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A68 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Electrical air heater 30SAC71AH002 in
supply air to battery room Switched OFF
xFSD00261 SAC70 EYT SSS SSS Siemens
on room temperature in battery rooms
30SAC71CT006 low
Electrical air heater 30SAC71AH002 in
supply air to battery room Switched on
xFSD00262 SAC70 EYT SSS SSS Siemens
room temperature in battery rooms
30SAC71CT006 low
Protection of components in 30SAC70
xFSD00263 SAC70 EYT SSS SSS Siemens
system
Control of heating water valve
xFSD00264 (30SBH01AA101) for supply air SAH EYT SSS SSS Siemens
temperature
Outside air temperature 30SAH11CT006
for control of supply air temperature to
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

xFSD00265 switchgear rooms (also for boiler room, if SAH EYT SSS SSS Siemens
auxiliary boiler is not in operation) with
30SAH11AA001/2 and 30SAH12AA004
Control of supply air temperature to
switchgear rooms (also for boiler room, if
xFSD00266 auxiliary boiler is not in operation) with SAH EYT SSS SSS Siemens
valves 30SAH11AA001/2 and
30SAH12AA004
Switch ON Re circulation air heater
xFSD00267 30SBH02/03AH001 on room temperature SAH EYT SSS SSS Siemens
in boiler room 30SAH11CT002 low1
Switch OFF Re circulation air heater
xFSD00268 30SBH02/03AH001 on room temperature SAH EYT SSS SSS Siemens
in boiler room 30SAH11CT002 high
OPEN air intake openings on room
xFSD00269 temperature in boiler room SAH EYT SSS SSS Siemens
30SAH11CT008 high
Switch ON Exhaust air fans in stages on
xFSD00270 room temperature in boiler room SAH EYT SSS SSS Siemens
30SAH11CT008 high
Close air intake openings on room
xFSD00271 SAH EYT SSS SSS Siemens
temperature in boiler room low
ECCN: N

Switch OFF Exhaust air fans in stages on


xFSD00272 SAH EYT SSS SSS Siemens
room temperature in boiler room low
Protection OFF command of motors of
fans 30SAH11/12AN001 in case of low
difference pressure at the supply air fans
AL: N

xFSD00273 SAH EYT SSS SSS Siemens


30SAH11CP003 or low difference
pressure at exhaust air fan
30SAH12CP001
Protection CLOSE command of outside
air multi leaf dampers 30SAH10AA001/2
xFSD00274 and 30SAH11 AA001 in case of low room SAH EYT SSS SSS Siemens
temperature in boiler building
30SAH11CT001
Protection ON command of the heating
water pump 30SBH01AP001 and
protection OPEN command of the heating
xFSD00275 SAH EYT SSS SSS Siemens
water valve 30SBH01AA101 in case of
low supply air temperature
30SAH11CT001
Monitoring of SAH Ventilation system for
xFSD00276 SAH EYT SSS SSS Siemens
auxiliary boiler building: Fault indication
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A69 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Control of heating water valve
30SBQ50AA101 to supply air heater
xFSD00277 30SAQ51/52AC001 based on the room SAQ50 EYT SSS SSS Siemens
temperature 30SAQ51CT001 in
switchgear rooms
Control of outside air / return air multi leaf
dampers 30SAQ50AA001/2,
xFSD00278 30SAQ53AA001 in supply air unit based SAQ50 EYT SSS SSS Siemens
on the room temperature
30SAQ50/51CT001 in switchgear rooms
Switch ON stage 2 air flow of supply air
fans 30SAQ51/52 AN001 on room
xFSD00279 SAQ50 EYT SSS SSS Siemens
temperature in switchgear rooms
30SAQ52CT001/2/3 high
Switch ON stage 2 air flow of supply air
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

fans 30SAQ56/57AN001 on room


xFSD00280 SAQ50 EYT SSS SSS Siemens
temperature in switchgear rooms
30SAQ52CT001/2/3 high
Switch OFF stage 2 air flow of supply air
fans 30SAQ51/52 AN001 on room
xFSD00281 SAQ50 EYT SSS SSS Siemens
temperature in switchgear rooms
30SAQ52CT001/2/3 low
Switch OFF stage 2 air flow of supply air
fans 30SAQ56/57AN001 on room
xFSD00282 SAQ50 EYT SSS SSS Siemens
temperature in switchgear rooms
30SAQ52CT001/2/3 low
Protection CLOSE command of outside
air multi leaf dampers 30SAQ50AA001/2
xFSD00283 SAQ50 EYT SSS SSS Siemens
in case of low room temperature in
30UQA building 30SAQ52CT001/2/3
Protection ON command of the heating
water pump 30SBQ50AP001 and on
xFSD00284 SAQ50 EYT SSS SSS Siemens
LOW2 supply air temperature
30SAQ51CT002 / 30SAQ52CT004
Protection OPEN command of the heating
water valve 30SBQ50AA101 on LOW2
xFSD00285 SAQ50 EYT SSS SSS Siemens
supply air temperature 30SAQ51CT002 /
30SAQ52CT004
ECCN: N

Protection CLOSE command of outside


air multi leaf damper 30SAQ50AA001/2 in
xFSD00286 SAQ50 EYT SSS SSS Siemens
case of LOW3 supply air temperature
30SAQ51CT002 / 30SAQ52CT004
Monitoring of Ventilation System for
AL: N

xFSD00287 Circulating Water Building: Fault, Alarm SAQ50 EYT SSS SSS Siemens
indication
Position control of multi leaf dampers
xFSD00288 30SAJ10/11AA001/2, 30SAJ20AA001 (in SAJ EYT SSS SSS Siemens
outside air, return air and exhaust air)
Switch ON supply air heater
30SAJ10/11AH001 on room temperature
xFSD00289 SAJ EYT SSS SSS Siemens
(30SAJ10CT002) in anti-icing pump room
low.
Switch OFF supply air heater
30SAJ10/11AH001 on room temperature
xFSD00290 SAJ EYT SSS SSS Siemens
(30SAJ10CT002) in anti-icing pump room
high.
Protection OFF command of electrical air
heaters 30SAJ10/11 AH001 in case of
xFSD00291 SAJ EYT SSS SSS Siemens
high supply air temperature behind
electrical air heater 30SAJ10/11 CT001
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A70 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Protection OFF command of electrical air
xFSD00292 heaters 30SAJ10/11 AH001 in case of low SAJ EYT SSS SSS Siemens
supply air flow 30SAJ10/11 CF001
Protection CLOSE command of outside
air damper 30SAJ10/11AA001 in case of
xFSD00293 SAJ EYT SSS SSS Siemens
low room temperature in anti-icing pump
room 30SAJ10CT002
Monitoring of SAJ Circulating water seal
xFSD00294 SAJ EYT SSS SSS Siemens
pit building ventilation: Fault indication
OPEN relevant air intake openings
30SAZ70AA001-10 on room temperature
xFSD00295 SAZ* EYT SSS SCP SAZ
(30SAZ70CT001-CT006) in pipe bridge
30UMY high
Switch ON relevant Exhaust air fans
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

30SAZ70AN001-6 on room temperature


xFSD00296 SAZ* EYT SSS SCP SAZ
(30SAZ70CT001-CT006) in pipe bridge
30UMY high
Close relevant air intake openings
30SAZ70AA001-10 on room temperature
xFSD00297 SAZ* EYT SSS SCP SAZ
(30SAZ70CT001-CT006) in pipe bridge
30UMY low
Switch OFF relevant Exhaust air fans
30SAZ70AN001-6 on room temperature
xFSD00298 SAZ* EYT SSS SCP SAZ
(30SAZ70CT001-CT006) in pipe bridge
30UMY low
Switch ON relevant Re circulation air
heaters on room temperature
xFSD00299 SAZ* EYT SSS SCP SAZ
(30SAZ70CT001-CT006) in pipe bridge
30UMY low
Switch OFF relevant Re circulation air
heaters on room temperature
xFSD00300 SAZ* EYT SSS SCP SAZ
(30SAZ70CT001-CT006) in pipe bridge
30UMY high
Monitoring of the System BCT ( Auxiliary
xFSD00304 BCT SC4 PAS 2 PAS 2 Siemens
Standby Transformers)
CHY
Monitoring of the System BCT ( Auxiliary CHY10/ACA/A
xFSD00304 SC4 PAS 2 PAS 2 Siemens
ECCN: N

Standby Transformers) CB/BAT/BBT/B


CT/MKA
Control of power supply of the electrical
xFSD00305 auxiliaries after failure of the power supply BCT SC4 PAS 2 PAS 2 Siemens
AL: N

via the auxiliary normal transformers ANT


Control of power supply of the electrical
xFSD00306 BCT SC4 PAS 2 PAS 2 Siemens
auxiliary boiler
Control and Monitoring of the System AEA AEA/BUM/BUN
xFSD00307 SC4 PAS 2 PAS 2 Siemens
(110kV standby grid connection) /BUP
Control of connection of the generator to
xFSD00308 BA SC4 PAS 2 PAS 2 Siemens
the generator transformer
Control of transfer of the generated power
xFSD00309 ACA SC4 PAS 2 PAS 2 Siemens
into the HV Grid
Control of transfer of the generated power
xFSD00309 BA SC4 PAS 2 PAS 2 Siemens
into the HV Grid
Control of transfer of the generated power
xFSD00309 CHA SC4 PAS 2 PAS 2 Siemens
into the HV Grid
Control of power supply of the unit
xFSD00310 BA SC4 PAS 2 PAS 2 Siemens
electrical auxiliaries
Monitoring of the power transmission
xFSD00311 BA SC4 PAS 2 PAS 2 Siemens
systems
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A71 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Control of power supply of NI and big
xFSD00312 BB SC4 PAS 2 PAS 2 Siemens
loads and LV transformers in TI
Control of power supply of NI
xFSD00313 BB SC4 PAS 2 PAS 2 Siemens
maintenance power system
Control of power supply of the auxiliary
xFSD00314 BB SC4 PAS 2 PAS 2 Siemens
boilers
Control and monitoring of power supply of
xFSD00315 BB SC4 PAS 2 PAS 2 Siemens
the unit el. auxiliaries
CHY
Control and monitoring of power supply of CHY10/ACA/A
xFSD00315 SC4 PAS 2 PAS 2 Siemens
the unit el. auxiliaries CB/BAT/BBT/B
CT/MKA
Monitoring of TI MV Distribution Boards
xFSD00316 BB SC4 PAS 2 PAS 2 Siemens
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

and Transformers
Indication of BB measurements and
xFSD00317 BB SC4 PAS 1 SCP BB-BD
system status
Indication of BD, BMT, BBA-BBD, XKA,
xFSD00318 TVA-TVD measurements and system BD SC3 SAS SCP BB-BD
status
xFSD00319 Monitoring of the LV Distribution System BF, BH, BJ SC4 PAS 2 PAS 2 Siemens
Control of switchgear for power supply of
TI LV loads 690V (safety class acc. to the
xFSD00320 BF, BH, BJ SC4 PAS 2 PAS 2 Siemens
class for the operation of the connected
loads)
Control of Distribution boards for power
supply of smaller TI LV loads 400V (safety
xFSD00321 BF, BH, BJ SC4 PAS 2 PAS 2 Siemens
class acc. to the class for the operation of
the connected loads)
Control of transformers for power supply
of TI switchgear BFA-BFD (safety class
xFSD00322 BF, BH, BJ SC4 PAS 2 PAS 2 Siemens
acc. to the class for the operation of the
connected loads)
Control of transformers for power supply
of switchgear BHA-BHF (safety class acc.
xFSD00323 BF, BH, BJ SC4 PAS 2 PAS 2 Siemens
to the class for the operation of the
connected loads)
ECCN: N

Control of transformers for power supply


of TI LV Distributions BJC/BJD (safety
xFSD00324 BF, BH, BJ SC4 PAS 2 PAS 2 Siemens
class acc. to the class for the operation of
the connected loads)
SCP
AL: N

Indication of BF, BH measurements and


xFSD00325 BF, BH, BK SC4 PAS 1 BF/BH/BK/BL/B
system status
M/BN/BR
SCP
Indication of BK measurements and
xFSD00326 BF, BH, BK SC4 PAS 1 BF/BH/BK/BL/B
system status
M/BN/BR
Control of power supply of TI emergency
xFSD00327 LV loads (safety class acc. to the class for BM SC4 PAS 2 PAS 2 Siemens
the operation of the connected loads)
Monitoring of the System BM (Non-Safety
xFSD00328 Emergency Power LV Distribution System BM SC4 PAS 2 PAS 2 Siemens
of Turbine Island)
SCP
Indication of BM, BN, BL, BR BM, BN, BL,
xFSD00329 SC3 SAS BF/BH/BK/BL/B
measurements and system status BR
M/BN/BR
Measurement and indication of the UPS
xFSD00330 BR SC4 PAS 2 PAS 2 Siemens
distribution system
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A72 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Control of power supply of TI UPS loads
xFSD00331 (safety class acc. to the class for the BR SC4 PAS 2 PAS 2 Siemens
operation of the connected loads)
Measurement and indications of the
xFSD00332 BT SC4 PAS 2 PAS 2 Siemens
battery and DC distribution system
Control of power supply of TI DC loads
xFSD00333 BT SC4 PAS 2 PAS 2 Siemens
after failure of AC power supply
Control of power supply of TI DC loads
xFSD00334 and the reactor control rods as well as BT SC4 PAS 2 PAS 2 Siemens
battery charging during normal operation
Control of power supply of TI 24V DC
xFSD00335 BT SC4 PAS 2 PAS 2 Siemens
loads
Control of power supply of TI 220V DC
xFSD00336 BT SC4 PAS 2 PAS 2 Siemens
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

loads and NI reactor control rods

BTD, BRU,
Indication of BT, BR, BU measurements
xFSD00337 BTP, BUE- SC3 SAS SCP BATT
and system status
BUH; BR, BTW

BTD, BRU,
Indication of BN, BT, BR measurements
xFSD00338 BTP, BUE- SC3 SAS SCP BATT
and system status
BUH; BR; BTW

Indication of BU measurements and


xFSD00339 BU SC4 SAS SCP JDA/BU NI
system status
Measurement and indications of the High-
xFSD00340 CBQ SC4 PAS 2 PAS 2 Siemens
Speed Busbar Transfer System
Control of change over between the two
xFSD00341 infeeds (30BBT-30BCT) in the TI 10kV CBQ SC4 SSS SCP PST
switchgear 30BBA-BBD

JAA
JAC
Control of change over between the two
JEA
xFSD00341 infeeds (30BBT-30BCT) in the TI 10kV SC4 SSS SCP PST
JEB
switchgear 30BBA-BBD
JEC
ECCN: N

JEF, JEG

Control of change over between the two


XJA10-40
xFSD00341 infeeds (30BBT-30BCT) in the TI 10kV SC4 SSS SCP PST
XKA10-40
switchgear 30BBA-BBD
AL: N

Control of change over between the two


XJA50/80,
xFSD00341 infeeds (30BBT-30BCT) in the TI 10kV SC4 SSS SCP PST
XKA50/80
switchgear 30BBA-BBD
Monitoring of the system CHA ( Generator
and Transformer Protection,
xFSD00342 CHA SC4 PAS 2 PAS 2 Siemens
Synchronization, Transformer Voltage
Regulator)
Control and protection of unit generator
xFSD00343 and HV Transformers (BBT/BLT) CHA SC4 PAS 2 PAS 2 Siemens
secondary voltage acc. to a preset value
CHY
Monitoring of the system CHY (Measuring CHY10/ACA/A
xFSD00344 SC4 PAS 2 PAS 2 Siemens
and Metering System) CB/BAT/BBT/B
CT/MKA
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A73 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
CHY
Metering and measuring of the unit energy CHY10/ACA/A
xFSD00345 SC4 SSS SSS Siemens
production and consumption CB/BAT/BBT/B
CT/MKA
CHY
Control and Monitoring of the System CHY10/ACA/A
xFSD00346 SC4 PAS 2 PAS 2 Siemens
ACB ( 400 kV switchyard (off site)) CB/BAT/BBT/B
CT/MKA
Control of generation of electrical power
xFSD00347 XKA SC4 PAS 2 PAS 2 Siemens
for TI emergency loads
Measurements and status indication of
xFSD00348 Non safety Emergency Diesel Generator XKA SC4 PAS 2 PAS 2 Siemens
Set of Turbine Island
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

Control of connection/ disconnection of


xFSD00350 ACA SC4 PAS 2 PAS 2 Siemens
the main generator to/from the grid
Control of transfer of auxiliary power at
xFSD00351 ACA SC4 PAS 2 PAS 2 Siemens
400 kV level
PAB
Control of cooling water to the turbine PAC
xFSD00356 condenser with the aid of circulating water PAH SC4 PAS 2 PAS 2 Siemens
pump PUE
PUR

PAB
Intermediate positions of check valves PAC
xFSD00357 30PAB11/12/13/14AA001 on the PAH SC4 PAS 2 PAS 2 Siemens
discharge site of Circulating water pump PUE
PUR

PAB
PAC
Monitoring of the circulating/recirculation
xFSD00358 PAH EYT PAS 2 PAS 2 Siemens
water pump
PUE
PUR

PAB
PAC
Monitoring of the circulating/recirculation
ECCN: N

xFSD00359 PAH SC4 PAS 2 PAS 2 Siemens


water pump motor
PUE
PUR

PAB
AL: N

PAC
Pumping of the circulating water trough
xFSD00360 PAH SC4 PAS 2 PAS 2 Siemens
the condense back to the sea
PUE
PUR

PAB
PAC
Monitoring of the evacuation system for
xFSD00361 PAH EYT PAS 2 PAS 2 Siemens
cooling water
PUE
PUR

PAB
PAC
Control of cleaning of the condenser tubes
xFSD00362 PAH EYT PAS 2 PAS 2 Siemens
by rubber balls
PUE
PUR
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A74 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
PAB
PAC
Monitoring of the condenser cleaning
xFSD00363 PAH EYT SSS SSS Siemens
system
PUE
PUR

PAB
PAC
Control of Evacuating of the circulating
xFSD00364 PAH EYT PAS 2 PAS 2 Siemens
water system
PUE
PUR

PAB
Control of recirculation of heated cooling
PAC
water to the cooling water inlet culvert via
xFSD00365 PAH SC4 PAS 2 PAS 2 Siemens
the cooling water recirculation pumps
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

PUE
during cold weather conditions
PUR

PAB
Control of corrosion protection of the PAC
xFSD00366 components in the circulating water PAH EYT SSS SCP PUR NI
system PUE
PUR

PAB
PAC
Monitoring of the Cathodic protection
xFSD00367 PAH EYT SSS SCP PUR NI
system
PUE
PUR
Monitoring of the Cathodic protection
xFSD00367 30PUR, 30UPx EYT SSS SCP PUR NI
system
Protect through the protection OFF
command of the Circulating water pump ( PAB
30PAC11/12/13/14 AP001 ) if the PAC
xFSD00368 combined isolation and check valve has PAH SC4 PAS 2 PAS 2 Siemens
not reached an monitored aperture angle ( PUE
two applications ) in an required time ( PUR
30PAB11/12/13/14 CG001 )
ECCN: N

Protect through the protection OFF PAB


command of the Circulating water pump ( PAC
xFSD00369 30PAC11/12/13/14 AP001 ) in case of low PAH SC4 PAS 2 PAS 2 Siemens
level in the pump intake pit ( 30PAB11/14 PUE
CL901 ) PUR
AL: N

Protect through the protection OFF PAB


command of the Circulating water pump ( PAC
xFSD00370 30PAC11/12/13/14 AP001 ) in case of too PAH SC4 PAS 2 PAS 2 Siemens
low pressure of the lube oil pump ( PUE
30PAC11/12/13/14 CP153/154 ) PUR
Protect through the protection OFF
PAB
command of the Circulating water pump (
PAC
30PAC11/12/13/14 AP001 ) in case of
xFSD00371 PAH SC4 PAS 2 PAS 2 Siemens
high motor- or pump bearing temperature
PUE
( 30PAC11/12/13/14 CT001-
PUR
006/077A/077B/79A/79B )
Protect through the protection OFF PAB
command of the Circulating water pump ( PAC
xFSD00372 30PAC11/12/13/14 AP001 ) in case of PAH SC4 PAS 2 PAS 2 Siemens
high motor winding temperature ( PUE
30PAC11/12/13/14 CT971/973/975 ) PUR
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A75 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Protect through the protection OFF
command of the Circulating water pump (
30PAC11/12/13/14 AP001 ) in case of too
high differential pressure circulating water PAB
pump ( 30PAB11/12/13/14 CP001 and PAC
xFSD00373 PAB11/14 CL901 (incl Alarm in case of PAH SC4 PAS 2 PAS 2 Siemens
difference pressure ( 30PAB11/12/13/14 PUE
CP001 and PAB11/14 CL901 ) >= MAX2 PUR
and Warning in case of difference
pressure ( 30PAB11/12/13/14 CP001 and
PAB11/14 CL901 ) >= MAX1)
Protect through the protection OFF
command of the Circulating water pump (
30PAC11/12/13/14 AP001 ) in case of too
low differential pressure circulating water PAB
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

pump ( 30PAB11/12/13/14 CP001 and PAC


xFSD00374 PAB11/14 CL901 ) (incl. Warning in case PAH SC4 PAS 2 PAS 2 Siemens
of difference pressure ( PUE
30PAB11/12/13/14 CP001 and PAB11/14 PUR
CL901 ) =< MIN1 and Alarm in case of
difference pressure ( 30PAB11/12/13/14
CP001 and PAB11/14 CL901 ) =< MIN2)
Protect through the protection OFF
PAB
command of the Circulating water pump (
PAC
30PAC11/12/13/14 AP001 ) in case of
xFSD00375 PAH SC4 PAS 2 PAS 2 Siemens
too high average differential pressure
PUE
band screens 30PAA10 CP901 (all
PUR
CIWP´s)
Protect through the protection OFF PAB
command of the Circulating water pump ( PAC
xFSD00376 30PAC11/12/13/14 AP001 ) in case of PAH SC4 PAS 2 PAS 2 Siemens
high average differential pressure band PUE
screens (only one CWIP) PUR

Protect through the protection OFF PAB


command of the recirculating water pump PAC
xFSD00377 ( 30PAC41/42/43 AP001) in case of low PAH SC4 PAS 2 PAS 2 Siemens
level in the pump chambers ( PUE
30PAB41/42/43 CL001 ) PUR
ECCN: N

Protect through the protection OFF PAB


command of the recirculating water pump PAC
xFSD00378 ( 30PAC41/42/43 AP001) in case of high PAH SC4 PAS 2 PAS 2 Siemens
AL: N

motor winding temperature ( PUE


30PAC41/42/43 CT071/72/73/74/75/76 ) PUR

Protect through the protection OFF PAB


command of the recirculating water pump PAC
xFSD00379 ( 30PAC41/42/43 AP001) in case of too PAH SC4 PAS 2 PAS 2 Siemens
high pressure discharge line ( PUE
30PAB41/42/43 CP001 ) PUR
Close protection demineralized water
supply valve 30GHC01 AA010 on
demineralized water storage tank level
xFSD00381 GHC SC4 PAS 2 PAS 2 Siemens
30GHC01/02CL001 > HIGH 2 (incl. Alarm
on demineralized water storage tank level
30GHC01/02CL001 >HIGH 2)
Close demineralized water supply valve
30GHC01 AA010 on demineralized water
xFSD00382 GHC SC4 PAS 2 PAS 2 Siemens
storage tank level 30GHC01/02CL001 >
HIGH 1
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A76 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Normal level control on demineralized
xFSD00383 water storage tank level GHC SC4 PAS 2 PAS 2 Siemens
30GHC01/02CL001 within range
Enable Open demineralized water supply
(30LCA00 EC001, 30GHC50 AA101) on
xFSD00384 GHC SC4 PAS 2 PAS 2 Siemens
demineralized water storage tank level
30GHC01/02CL001 > LOW 1
Release demineralized water pumps
30GHC11/12 AP001 on demineralized
xFSD00385 GHC SC4 PAS 2 PAS 2 Siemens
water storage tank level
30GHC01/02CL001 > LOW 2
Release sealing water supply pumps on
xFSD00386 demineralized water storage tank level GHC SC4 PAS 2 SCP GHC NI
30GHC01/02CL001 > LOW 2
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

Stop protection Sealing water supply


pumps 30GHW11/12 AP001 on
demineralized water storage tank level
30GHC01/02CL001 < LOW 3 (incl.
Warning on demineralized water storage
xFSD00390 GHC SC4 PAS 2 SCP GHC NI
tank level 30GHC01/02CL001 < LOW2
and Alarm on demineralized water storage
tank level 30GHC01/02CL001 < LOW 3
and Alarm on demineralized water storage
tank level 30GHC01/02CL001 < LOW 4)
Stop protection Sealing water supply
pumps 30GHW11/12 AP001 on
demineralized water storage tank level
30GHC01/02CL001 < LOW 3 (incl.
Warning on demineralized water storage
xFSD00390 GHW SC4 PAS 2 SCP GHC NI
tank level 30GHC01/02CL001 < LOW2
and Alarm on demineralized water storage
tank level 30GHC01/02CL001 < LOW 3
and Alarm on demineralized water storage
tank level 30GHC01/02CL001 < LOW 4)
Release emergency demineralized water
pump 30GHC60 AP001 on demineralized
xFSD00392 GHC SC4 PAS 2 PAS 2 Siemens
water storage tank level
30GHC01/02CL001 > LOW4
ECCN: N

Stop protection emergency demineralized


water pump 30GHC60 AP001 on
demineralized water storage tank level
xFSD00394 GHC SC4 PAS 2 PAS 2 Siemens
30GHC01/02CL001 < LOW 5 (incl. Alarm
AL: N

on demineralized water storage tank level


30GHC01/02CL001 < LOW 5)
Stop protection demineralized water
pumps 30GHC11/12 AP001 in case of low
xFSD00397 water level in the demineralized water GHC SC4 PAS 2 PAS 2 Siemens
storage tank and the valves 30GHC60
AA031/032 are not open
Stop protection demineralized water
pumps 30GHC11/12 AP001 in case of low
xFSD00398 water level in the demineralized water GHC SC4 PAS 2 PAS 2 Siemens
storage tank and one of the valves
30GHC60 AA031/032 opened
Stop protection demineralized water
pumps 30GHC11/12 AP001 in case of the
xFSD00399 GHC SC4 PAS 2 PAS 2 Siemens
level measurements are not in operation
or are not valid
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A77 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Protection OFF command of emergency
demineralized water pump
xFSD00401 (30GHC60AP001) in case of the level GHC SC4 PAS 2 PAS 2 Siemens
measurements are not in operation or
fault
Protection OFF command of emergency
demineralized water pump
xFSD00402 GHC SC4 PAS 2 PAS 2 Siemens
(30GHC60AP001) in case of the motor
winding temperature is too high
Monitoring of the demineralized water flow
xFSD00403 GHC SC4 PAS 2 PAS 2 Siemens
30GHC20CF001, 30GHC60 CF001
Monitoring and control of the
xFSD00404 demineralized water pressure GHC SC4 PAS 2 PAS 2 Siemens
30GHC10/20/60 CP001
Demineralized water pump 30GHC11
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

AP001/ 30GHC12 AP001switch over on


xFSD00405 GHC SC4 PAS 2 PAS 2 Siemens
demineralized water differential pressure
30GHC10 CP001< low
Monitoring of the demineralized water
xFSD00406 temperature 30GHC01 CT001, 30GHC02 GHC SC4 PAS 2 PAS 2 Siemens
CT001
Monitoring of the emergency
xFSD00407 demineralized water pump 30GHC60 GHC SC4 PAS 2 PAS 2 Siemens
AP001
Isolation of the supply of the safeguard
xFSD00408 buildings for flooding protection with GHC SC4 PAS 1 SCP KTC/D/E
valves 30GHC78 AA001/AA002
Isolation of the supply of the safeguard
xFSD00408 buildings for flooding protection with KTA-KTE SC4 PAS 1 SCP KTC/D/E
valves 30GHC78 AA001/AA002
Isolation of the supply of nuclear island
xFSD00409 GHC SC4 PAS 1 SCP GHC NI
with valves 30GHC70 AA001/AA002
Isolation of the supply of UFA building for
FAK
xFSD00410 flooding protection with valves 30GHC73 SC4 PAS 1 SCP GHC NI
FAL
AA001/AA002
Isolation of the supply of UFA building for
xFSD00410 flooding protection with valves 30GHC73 GHC SC4 PAS 1 SCP GHC NI
ECCN: N

AA001/AA002
Isolation of the supply of UFA building for
xFSD00410 flooding protection with valves 30GHC73 KTA-KTE SC4 PAS 1 SCP GHC NI
AA001/AA002
AL: N

Control of Pumping of closed cooling


water to the component coolers and back PGB
xFSD00411 SC4 PAS 2 PAS 2 Siemens
to the closed cooling water heat PGC
exchangers
Opening of bypass valve 30PGB15AA001
will open on low closed cooling water
temperature. (incl Alarm on closed cooling
PGB
xFSD00413 water temperature too high, Warning on SC4 PAS 2 PAS 2 Siemens
PGC
closed cooling water temperature high,
Warning on closed cooling water
temperature low )
Switch off closed cooling water pumps on
differential pressure measurement PGB
xFSD00416 SC4 PAS 2 PAS 2 Siemens
30PGB10CP904 of the closed cooling PGC
water pumps low
Control of 30PGC11/12/13 AP001 on
differential pressure measurement PGB
xFSD00417 SC4 PAS 2 PAS 2 Siemens
30PGB10CP904 of the closed cooling PGC
water pumps within range
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A78 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Protective shut-off closed cooling water
pumps on differential pressure
(30PGB10CP904) of the closed cooling PGB
xFSD00418 SC4 PAS 2 PAS 2 Siemens
water pumps too high (incl. Warning on PGC
differential pressure (30PGB10CP904)
too high)
Start of standby pump on differential
PGB
xFSD00419 pressure measurement 30PGB10CP904 SC4 PAS 2 PAS 2 Siemens
PGC
of the closed cooling water pumps low
Closing of valve 30PGB01AA003 on
pressure measurement PGB
xFSD00422 SC4 PAS 2 PAS 2 Siemens
(30PGB10CP001/002/003) of the closed PGC
cooling water system high
Enabling of the pumps 30PGC11/12/13
PGB
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

xFSD00423 AP001 when PGB (Closed cooling water SC4 PAS 2 PAS 2 Siemens
PGC
piping system) is in operation
Opening of valve 30PGB01AA003 on
pressure measurement
(30PGB10CP001/002/003) of the closed
PGB
xFSD00424 cooling water system low (incl. Warning SC4 PAS 2 PAS 2 Siemens
PGC
on pressure measurement
(30PGB10CP001/002/003) of the closed
cooling water system low)
Protective close of valve 30PGB01AA003
on pressure measurement
(30PGB10CP001/002/003) of the closed
PGB
xFSD00425 cooling water system too high (incl SC4 PAS 2 PAS 2 Siemens
PGC
Warning on pressure measurement
(30PGB10CP001/002/003) of the closed
cooling water system too high)
Alarm, Shut off closed cooling water
pumps on pressure measurement PGB
xFSD00426 SC4 PAS 2 PAS 2 Siemens
(30PGB10CP001/002/003) of the closed PGC
cooling water system very low
Protection OFF command of closed
cooling water pump (PGC11/12/13
PGB
xFSD00428 AP001) in case of difference pressure SC4 PAS 2 PAS 2 Siemens
PGC
closed cooling water pumps too high (
ECCN: N

30PGB10 CP904 )
Protection OFF command of closed
cooling water pump (PGC11/12/13
PGB
xFSD00429 AP001) in case of difference pressure SC4 PAS 2 PAS 2 Siemens
PGC
AL: N

closed cooling water pumps too low (


30PGB10 CP904 )
Protection OFF command of closed
cooling water pump (PGC11/12/13 PGB
xFSD00430 SC4 PAS 2 PAS 2 Siemens
AP001) in case of pressure closed cooling PGC
water system too low ( 30PGB10 CP901 )
Protection OFF command of closed
cooling water pump (PGC11/12/13
PGB
xFSD00431 AP001) in case of high motor winding SC4 PAS 2 PAS 2 Siemens
PGC
temperature ( 30PGC11/12/13
CT971/973/975 )
Protection OFF command of closed
cooling water pump (PGC11/12/13
PGB
xFSD00432 AP001) in case of too low aperture angle SC4 PAS 2 PAS 2 Siemens
PGC
of bypass valve CCWHX ( 30PGB15
AA001 )
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A79 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Protection OFF command of closed
cooling water pump (PGC11/12/13
PGB
xFSD00433 AP001) in case of too low aperture angle SC4 PAS 2 PAS 2 Siemens
PGC
of isolation valve downstream CCWHX (
30PGB16/17/18AA002 )
Monitoring of the closed cooling water PGB
xFSD00434 SC4 PAS 2 PAS 2 Siemens
pump system PGC
Close protection normal drains C-V
30LCJ40 AA101 on LP heater 4 level
30LCC40 CL001/CL002/CL003 (CL901) LCC
xFSD00438 EYT PAS 2 PAS 2 Siemens
=< LOW 2 (incl. Alarm on LP heater 4 LCJ
level 30LCC40 CL001/CL002/CL003
(CL901) =< LOW 2)
Closing protection emergency drains C-V
30LCJ40 AA111 on LP heater 4 level LCC
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

xFSD00439 EYT PAS 2 PAS 2 Siemens


30LCC40 CL001/CL002/CL003 (CL901) LCJ
=< LOW 2
Emergency drains level control (incl.
LCC
xFSD00440 Warning on LP heater 4 level 30LCC40 EYT PAS 2 PAS 2 Siemens
LCJ
CL001/CL002/CL003 (CL901) >= HIGH 2)
Heater bypass operation on LP heater 4
LCA
level 30LCC40 CL001/CL002/CL003
LCB
xFSD00441 (CL901) >= HIGH 3 (incl. Warning on LP EYT PAS 2 PAS 2 Siemens
LCR
heater 4 level 30LCC40
LCW
CL001/CL002/CL003 (CL901) >= HIGH 3)
Heater bypass operation on LP heater 4
level 30LCC40 CL001/CL002/CL003
LCC
xFSD00441 (CL901) >= HIGH 3 (incl. Warning on LP EYT PAS 2 PAS 2 Siemens
LCJ
heater 4 level 30LCC40
CL001/CL002/CL003 (CL901) >= HIGH 3)
Normal drains level control on LP heater
4 level 30LCC40 CL001/CL002/CL003
(CL901) within range (incl. Warning on LP
heater 4 level 30LCC40 LCC
xFSD00442 EYT PAS 2 PAS 2 Siemens
CL001/CL002/CL003 (CL901) =< LOW 1 LCJ
and Warning on LP heater 4 level
30LCC40 CL001/CL002/CL003 (CL901)
>= HIGH 1)
ECCN: N

Stop protection condensate extraction


pumps 30LCB11/12/13AP001 on LP LCA
heater 4 level 30LCC40 LCB
xFSD00443 EYT PAS 2 PAS 2 Siemens
CL001/CL002/CL003 (CL901) >= HIGH 5 LCR
(incl. Alarm on LP heater 4 level 30LCC40 LCW
AL: N

CL001/CL002/CL003 (CL901) >= HIGH 5)


Stop protection condensate extraction
pumps 30LCB11/12/13AP001 on LP
heater 4 level 30LCC40 LCC
xFSD00443 EYT PAS 2 PAS 2 Siemens
CL001/CL002/CL003 (CL901) >= HIGH 5 LCJ
(incl. Alarm on LP heater 4 level 30LCC40
CL001/CL002/CL003 (CL901) >= HIGH 5)
Stop protection LP HTR drains pump
30LCJ30 AP001 on LP heater 4 level
30LCC40 CL001/CL002/CL003 (CL901) LCC
xFSD00444 EYT PAS 2 PAS 2 Siemens
>= HIGH 4 (incl. Alarm on LP heater 4 LCJ
level 30LCC40 CL001/CL002/CL003
(CL901) >= HIGH 4)
Close protection Emergency drains C-V
30LCJ30 AA111 on LP heater 3 level
30LCC30 CL001/CL002/CL003 (CL901) LCC
xFSD00451 EYT PAS 2 PAS 2 Siemens
=< LOW 2 (incl Alarm on LP heater 3 level LCJ
30LCC30 CL001/CL002/CL003 (CL901)
=< LOW 2)
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A80 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Close protection Normal drains C-V
30LCJ30 AA101 on LP heater 3 level LCC
xFSD00452 EYT PAS 2 PAS 2 Siemens
30LCC30 CL001/CL002/CL003 (CL901) LCJ
=< LOW 2
Closing protection normal drains A4 on LP
heater 3 level 30LCC30
LCC
xFSD00453 CL001/CL002/CL003 (CL901) >= HIGH 3 EYT PAS 2 PAS 2 Siemens
LCJ
(Warning on LP heater 3 level 30LCC30
CL001/CL002/CL003 (CL901) >= HIGH 3)
Emergency drains level control (incl
LCC
xFSD00454 Warning on LP heater 3 level 30LCC30 EYT PAS 2 PAS 2 Siemens
LCJ
CL001/CL002/CL003 (CL901) >= HIGH 2)
Heater bypass operation on LP heater 3
LCA
level 30LCC30 CL001/CL002/CL003
LCB
xFSD00455 (CL901) >= HIGH 4 (incl Warning on LP EYT PAS 2 PAS 2 Siemens
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

LCR
heater 3 level 30LCC30
LCW
CL001/CL002/CL003 (CL901) >= HIGH 4)
Heater bypass operation on LP heater 3
level 30LCC30 CL001/CL002/CL003
LCC
xFSD00455 (CL901) >= HIGH 4 (incl Warning on LP EYT PAS 2 PAS 2 Siemens
LCJ
heater 3 level 30LCC30
CL001/CL002/CL003 (CL901) >= HIGH 4)
Normal drains level control on LP heater
3 level 30LCC30 CL001/CL002/CL003
within range (incl Warning on LP heater 3
LCC
xFSD00456 level 30LCC30 CL001/CL002/CL003 EYT PAS 2 PAS 2 Siemens
LCJ
(CL901) >= HIGH 1 and Warning on LP
heater 3 level 30LCC30
CL001/CL002/CL003 (CL901) =< LOW 1)
Stop protection condensate extraction
LCA
pumps on LP heater 3 level 30LCC30
LCB
xFSD00457 CL001/CL002/CL003 (CL901) >= HIGH 5 EYT PAS 2 PAS 2 Siemens
LCR
(incl. Alarm on LP heater 3 level 30LCC30
LCW
CL001/CL002/CL003 (CL901) >= HIGH 5)

Stop protection condensate extraction


pumps on LP heater 3 level 30LCC30
LCC
xFSD00457 CL001/CL002/CL003 (CL901) >= HIGH 5 EYT PAS 2 PAS 2 Siemens
LCJ
ECCN: N

(incl. Alarm on LP heater 3 level 30LCC30


CL001/CL002/CL003 (CL901) >= HIGH 5)
Stop protection LP heater drains pump
30LCJ30 AP001 on LP heater 3 level LCC
xFSD00458 EYT PAS 2 PAS 2 Siemens
AL: N

30LCC30 CL001/CL002/CL003 (CL901) LCJ


=< LOW 2
Heater bypass operation on LP heater 2
level 30LCC21/22/23
CL001/CL002/CL003 (CL901) >= HIGH 2 LCA
(incl Warning on LP heater 2 level LCB
xFSD00465 EYT PAS 2 PAS 2 Siemens
30LCC21/22/23 CL001/CL002/CL003 LCR
(CL901) >= HIGH 1 and Warning on LP LCW
heater 2 level 30LCC21/22/23
CL001/CL002/CL003 (CL901) >= HIGH 2)
Heater bypass operation on LP heater 2
level 30LCC21/22/23
CL001/CL002/CL003 (CL901) >= HIGH 2
(incl Warning on LP heater 2 level LCC
xFSD00465 EYT PAS 2 PAS 2 Siemens
30LCC21/22/23 CL001/CL002/CL003 LCJ
(CL901) >= HIGH 1 and Warning on LP
heater 2 level 30LCC21/22/23
CL001/CL002/CL003 (CL901) >= HIGH 2)
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A81 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Stop protection condensate extraction
pumps 30LCB11/12/13 AP001on LP
LCA
heater 2 level 30LCC21/22/23
LCB
xFSD00467 CL001/CL002/CL003 (CL901) >= HIGH 3 EYT PAS 2 PAS 2 Siemens
LCR
(incl Alarm on LP heater 2 level
LCW
30LCC21/22/23 CL001/CL002/CL003
(CL901) >= HIGH 3)
Stop protection condensate extraction
pumps 30LCB11/12/13 AP001on LP
heater 2 level 30LCC21/22/23
LCC
xFSD00467 CL001/CL002/CL003 (CL901) >= HIGH 3 EYT PAS 2 PAS 2 Siemens
LCJ
(incl Alarm on LP heater 2 level
30LCC21/22/23 CL001/CL002/CL003
(CL901) >= HIGH 3)
Heater bypass operation on LP heater 1
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

level 30LCC11/12/13
CL001/CL002/CL003 (CL901) >= HIGH 2 LCA
(incl Warning on LP heater 1 level LCB
xFSD00471 EYT PAS 2 PAS 2 Siemens
30LCC11/12/13 CL001/CL002/CL003 LCR
(CL901) >= HIGH 1 and Warning on LP LCW
heater 1 level 30LCC11/12/13
CL001/CL002/CL003 (CL901) >= HIGH 2)
Heater bypass operation on LP heater 1
level 30LCC11/12/13
CL001/CL002/CL003 (CL901) >= HIGH 2
(incl Warning on LP heater 1 level LCC
xFSD00471 EYT PAS 2 PAS 2 Siemens
30LCC11/12/13 CL001/CL002/CL003 LCJ
(CL901) >= HIGH 1 and Warning on LP
heater 1 level 30LCC11/12/13
CL001/CL002/CL003 (CL901) >= HIGH 2)
Stop protection condensate extraction
pumps 30LCB11/12/13 AP001LP heater 1
LCA
level 30LCC11/12/13
LCB
xFSD00472 CL001/CL002/CL003 (CL901)>= HIGH 3 EYT PAS 2 PAS 2 Siemens
LCR
(incl. Alarm LP heater 1 level
LCW
30LCC11/12/13 CL001/CL002/CL003
(CL901) >= HIGH 3)
Stop protection condensate extraction
pumps 30LCB11/12/13 AP001LP heater 1
ECCN: N

level 30LCC11/12/13
LCC
xFSD00472 CL001/CL002/CL003 (CL901)>= HIGH 3 EYT PAS 2 PAS 2 Siemens
LCJ
(incl. Alarm LP heater 1 level
30LCC11/12/13 CL001/CL002/CL003
AL: N

(CL901) >= HIGH 3)


Protection OFF command of LP heater
drains pump protection in case of high LCC
xFSD00475 EYT PAS 2 PAS 2 Siemens
motor winding temperature (30LCJ30 LCJ
CT971/973/975)
Protection OFF command of LP heater
drains pump protection in case of low flow
LCC
xFSD00476 by control valve LP heater A3 drains EYT PAS 2 PAS 2 Siemens
LCJ
(30LCJ30 AA101) position higher than 5%
(cavitation protection)
Protection OFF command of LP heater
drains pump protection in case of too high LCC
xFSD00477 EYT PAS 2 PAS 2 Siemens
flow downstream the LP heater drains LCJ
pump ( 30LCJ30 CF001 )
Protection OFF command of LP heater
LAA
drains pump protection in case of too high
xFSD00478 LBS EYT PAS 2 PAS 2 Siemens
level feedwater storage tank ( 30LAA10
LBS50
CL901 )
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A82 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Protection OFF command of LP heater
drains pump protection in case of too high LCC
xFSD00478 EYT PAS 2 PAS 2 Siemens
level feedwater storage tank ( 30LAA10 LCJ
CL901 )
Protection OFF command of LP heater
drains pump protection in case of too high LCC
xFSD00479 EYT PAS 2 PAS 2 Siemens
level in the LP Heater A4 ( 30LCC40 LCJ
CL901 )
Protection OFF command of LP heater
LCC
xFSD00480 drains pump protection in case of too low EYT PAS 2 PAS 2 Siemens
LCJ
level LP Heater A3 ( 30LCC30 CL901 )
Monitoring of the LP-extraction steam LCC
xFSD00481 EYT PAS 2 PAS 2 Siemens
system LCJ
Monitoring of the LP-feedwater heating LCC
xFSD00482 EYT PAS 2 PAS 2 Siemens
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

system LCJ
LCC
xFSD00483 Monitoring of the LP heater drains pump EYT PAS 2 PAS 2 Siemens
LCJ
LCC
xFSD00484 Monitoring of the LP heater drains system EYT PAS 2 PAS 2 Siemens
LCJ
Close make up water supply on
xFSD00485 Condenser level 30MAG00FL921 > HIGH GHC SC4 PAS 2 PAS 2 Siemens
1
LCA
Close make up water supply on
LCB
xFSD00485 Condenser level 30MAG00FL921 > HIGH SC4 PAS 2 PAS 2 Siemens
LCR
1
LCW
Close protection Make-up water supply on
xFSD00486 Condenser level 30MAG00FL921 > HIGH GHC SC4 PAS 2 PAS 2 Siemens
2
LCA
Close protection Make-up water supply on
LCB
xFSD00486 Condenser level 30MAG00FL921 > HIGH SC4 PAS 2 PAS 2 Siemens
LCR
2
LCW
Open make up water supply on
xFSD00487 Condenser level 30MAG00FL921 < GHC SC4 PAS 2 PAS 2 Siemens
LOW1
ECCN: N

LCA
Open make up water supply on
LCB
xFSD00487 Condenser level 30MAG00FL921 < SC4 PAS 2 PAS 2 Siemens
LCR
LOW1
LCW
AL: N

Control the demineralized water to the


hotwell with demineralized water control
xFSD00488 valve 30GHC50AA101 (incl Warning on GHC SC4 PAS 2 PAS 2 Siemens
Condenser level 30MAG00FL921 =<
LOW 2)
Control the demineralized water to the
LCA
hotwell with demineralized water control
LCB
xFSD00488 valve 30GHC50AA101 (incl Warning on SC4 PAS 2 PAS 2 Siemens
LCR
Condenser level 30MAG00FL921 =<
LCW
LOW 2)
Close protection Emergency drains on
Condenser level 30MAG00FL921 >= LAA
xFSD00490 HIGH 2 (incl Warning (via LBS SC4 PAS 2 PAS 2 Siemens
30MAG10EZ120) on Condenser level LBS50
30MAG00FL921 >= HIGH 2)
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A83 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Close protection Emergency drains on
Condenser level 30MAG00FL921 >= LAD
xFSD00490 HIGH 2 (incl Warning (via LBQ SC4 PAS 2 PAS 2 Siemens
30MAG10EZ120) on Condenser level LCH
30MAG00FL921 >= HIGH 2)
Close protection Emergency drains on
LCA
Condenser level 30MAG00FL921 >=
LCB
xFSD00490 HIGH 2 (incl Warning (via SC4 PAS 2 PAS 2 Siemens
LCR
30MAG10EZ120) on Condenser level
LCW
30MAG00FL921 >= HIGH 2)
Close protection Emergency drains on
Condenser level 30MAG00FL921 >=
LCC
xFSD00490 HIGH 2 (incl Warning (via SC4 PAS 2 PAS 2 Siemens
LCJ
30MAG10EZ120) on Condenser level
30MAG00FL921 >= HIGH 2)
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

Close protection Emergency drains on


Condenser level 30MAG00FL921 >=
xFSD00490 HIGH 2 (incl Warning (via LCS SC4 PAS 2 PAS 2 Siemens
30MAG10EZ120) on Condenser level
30MAG00FL921 >= HIGH 2)
Close protection Emergency drains on
Condenser level 30MAG00FL921 >=
xFSD00490 HIGH 2 (incl Warning (via LCT SC4 PAS 2 PAS 2 Siemens
30MAG10EZ120) on Condenser level
30MAG00FL921 >= HIGH 2)
Close protection LCQ drains 30LCQ51
LCA
AA104 on Condenser level
LCB SCP LCQ-
xFSD00491 30MAG00FL921 >= HIGH 3 (incl. Warning SC4 PAS 2
LCR LCA90
(via 30MAG10EZ120) on Condenser level
LCW
30MAG00FL921 >= HIGH 3)
Close protection LCQ drains 30LCQ51
AA104 on Condenser level
LCA90 SCP LCQ-
xFSD00491 30MAG00FL921 >= HIGH 3 (incl. Warning SC4 PAS 2
LCQ LCA90
(via 30MAG10EZ120) on Condenser level
30MAG00FL921 >= HIGH 3)
LCA
Release condensate extraction pump on
LCB
xFSD00492 Condenser level 30MAG00FL921 =< SC4 PAS 2 PAS 2 Siemens
LCR
LOW1
LCW
ECCN: N

Stop protection condensate extraction


LCA
pumps on Condenser level
LCB
xFSD00493 30MAG00FL921 =< LOW 3 (incl. Alarm SC4 PAS 2 PAS 2 Siemens
LCR
on Condenser level 30MAG00FL921 =<
AL: N

LCW
LOW 3)
LCA
Open loop control condensate flow gland LCB
xFSD00498 SC4 PAS 2 PAS 2 Siemens
steam condenser 30LCA38DF001 LCR
LCW
LCA
Open loop control minimum flow main LCB
xFSD00499 SC4 PAS 2 PAS 2 Siemens
condensate pump 30LCA11/12/13EE021 LCR
LCW
LCA
Closed loop control pressure LCW/LCR LCB
xFSD00500 EYT PAS 2 PAS 2 Siemens
system 30LCW10DP001 LCR
LCW
Release seal and cooling drains system
xFSD00501 valve 30LCW10AA101 demineralized GHC EYT PAS 2 PAS 2 Siemens
water pressure 30GHC20 CP001 high
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A84 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
LCA
Release seal and cooling drains system
LCB
xFSD00501 valve 30LCW10AA101 demineralized EYT PAS 2 PAS 2 Siemens
LCR
water pressure 30GHC20 CP001 high
LCW
LCA
Open loop control for mechanical filtering LCB
xFSD00502 SC4 PAS 2 PAS 2 Siemens
system 30LCA45EC001 LCR
LCW
Protection OFF command of main
LCA
condensate pump (30LCB11/12/13
LCB
xFSD00503 AP001) in case of failure of 1 out of 2 EYT PAS 2 PAS 2 Siemens
LCR
lubrication oil temperature measurements
LCW
(30LCB11/12/13 CT901)
Protection OFF command of main
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

LCA
condensate pump (30LCB11/12/13
LCB
xFSD00504 AP001) in case of failure of 1 out of 2 EYT PAS 2 PAS 2 Siemens
LCR
winding or bearing measurements
LCW
(30LCB11/12/13CT971/973/975/977/979)
Protection OFF command of main
condensate pump (30LCB11/12/13 LCA
AP001) in case of failure of 2 out of 3 LCB
xFSD00505 EYT PAS 2 PAS 2 Siemens
feedwater heater A1/A2, A3, A4 water LCR
level measurements LCW
(30LCC11/12/13/21/22/23/30/40 CL901)
Protection OFF command of main
condensate pump (30LCB11/12/13
AP001) in case of failure of 2 out of 3 LCC
xFSD00505 EYT PAS 2 PAS 2 Siemens
feedwater heater A1/A2, A3, A4 water LCJ
level measurements
(30LCC11/12/13/21/22/23/30/40 CL901)
Protection OFF command of main
condensate pump (30LCB11/12/13 LAA
xFSD00506 AP001) in case of failure of 2 out of 3 LBS SC4 PAS 2 PAS 2 Siemens
feedwater storage tank level LBS50
measurements (30LAA10 CL901)
Protection OFF command of main
LCA
condensate pump (30LCB11/12/13
LCB
xFSD00506 AP001) in case of failure of 2 out of 3 SC4 PAS 2 PAS 2 Siemens
ECCN: N

LCR
feedwater storage tank level
LCW
measurements (30LAA10 CL901)
Protection OFF command of main
LCA
condensate pump (30LCB11/12/13
LCB
AL: N

xFSD00507 AP001) in case of failure of 2 out of 3 SC4 PAS 2 PAS 2 Siemens


LCR
condensate flow measurements
LCW
(30LCA30 CF901)
Protection OFF command of main LCA
condensate pump (30LCB11/12/13 LCB
xFSD00508 SC4 PAS 2 PAS 2 Siemens
AP001) in case of failure of both LCR
condenser level measurement circuits LCW
Protection OFF command of main LCA
condensate pump (30LCB11/12/13 LCB
xFSD00509 EYT PAS 2 PAS 2 Siemens
AP001) in case of high lubrication oil LCR
temperature (30LCB11/12/13 CT901) LCW
Protection OFF command of main
LCA
condensate pump (30LCB11/12/13
LCB
xFSD00510 AP001) in case of high motor winding or SC4 PAS 2 PAS 2 Siemens
LCR
bearing temperature (30LCB11/12/13
LCW
CT971/973/975/977/979)
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A85 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Protection OFF command of main
condensate pump (30LCB11/12/13
LCA
AP001) in case of low flow main
LCB
xFSD00511 condensate pump (30LCA30 CF901) SC4 PAS 2 PAS 2 Siemens
LCR
additionally min flow valve not open
LCW
(30LCA11/12/13 AA021) and CEP
(30LCB11/12/13 AP001) in operation
Protection OFF command of main LCA
condensate pump (30LCB11/12/13 LCB
xFSD00512 SC4 PAS 2 PAS 2 Siemens
AP001) in case of low water level LCR
condenser LP Turbine (30MAG00 FL921) LCW
Protection OFF command of main
condensate pump (30LCB11/12/13
LCA
AP001) in case of valves LCA45AA001
LCB
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

xFSD00513 and LCA81AA001 closed or valves SC4 PAS 2 PAS 2 Siemens


LCR
LCA45AA001 and LCA82AA001
LCW
closed (signal 30LCA45EZ001 XV01; no
condensate flow to FWST)
LCA
Monitoring of the main condensate system LCB
xFSD00514 EYT PAS 2 PAS 2 Siemens
during acceptance test LCR
LCW
LCA
LCB
xFSD00515 Monitoring of the main condensate system SC4 PAS 2 PAS 2 Siemens
LCR
LCW
LCA
LCB
xFSD00516 Monitoring of the main condensate pump EYT PAS 2 PAS 2 Siemens
LCR
LCW
LCA
Monitoring of the main condensate pump LCB
xFSD00517 SC4 PAS 2 PAS 2 Siemens
motor LCR
LCW
LCA
ECCN: N

Monitoring of the Standby Condensate LCB


xFSD00518 EYT PAS 2 PAS 2 Siemens
Distribution system LCR
LCW
LCA
AL: N

Monitoring of the Sealing and Cooling LCB


xFSD00519 EYT PAS 2 PAS 2 Siemens
Drains System LCR
LCW
Monitoring of collection and discharge of
xFSD00520 LCM EYT PAS 2 PAS 2 Siemens
drains
Control of pumping the drains from the
clean drains collecting tank to the
xFSD00521 condensate system or to the plant LCM EYT PAS 2 PAS 2 Siemens
drainage system: Start of operation and
shutdown of the clean drains system
xFSD00522 Overpressure protection via drain loop LCM EYT PAS 2 PAS 2 Siemens
Setpoint for auxiliary steam control valve
xFSD00523 30LCM10AA101 during discharge to GM LCM EYT PAS 2 PAS 2 Siemens
system
Setpoint for injection water control valve
xFSD00524 30LCM10AA102 or 30LCM10AA103 LCM EYT PAS 2 PAS 2 Siemens
during discharge to GM system
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A86 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Setpoint for auxiliary steam control valve
xFSD00525 30LCM10AA101 during discharge to LCA LCM EYT PAS 2 PAS 2 Siemens
system
Setpoint for injection water control valve
xFSD00526 30LCM10AA102 or 30LCM10AA103 LCM EYT PAS 2 PAS 2 Siemens
during discharge to LCA system
Close discharge valves 30LCM23 AA101,
30LCM24 AA002, 30LCM25 AA002 on
xFSD00528 LCM EYT PAS 2 PAS 2 Siemens
level measurements of the clean drains
collecting tank 30LCM20CL901 =< LOW 1
Open discharge valve (30LCM23 AA101
or 30LCM24 AA002 or 30LCM25 AA002)
xFSD00529 on level measurements of the clean LCM EYT PAS 2 PAS 2 Siemens
drains collecting tank 30LCM20CL901 >=
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

HIGH 2
Protective shutdown of clean drains pump
30LCM21 AP001 and 30LCM22 AP001
on level measurements of the clean
drains collecting tank 30LCM20CL901 =<
xFSD00530 LCM EYT PAS 2 PAS 2 Siemens
LOW 2 (incl. Alarm on level
measurements of the clean drains
collecting tank 30LCM20CL901 =< LOW
2)
Start standby pump 30LCM21 AP001 or
30LCM22 AP001 on level measurements
xFSD00531 LCM EYT PAS 2 PAS 2 Siemens
of the clean drains collecting tank
30LCM20CL901 >= HIGH 3
Start the selected clean drains pump
30LCM21 AP001 or 30LCM22 AP001 on
xFSD00532 level measurements of the clean drains LCM EYT PAS 2 PAS 2 Siemens
collecting tank 30LCM20CL901 >= HIGH
1
PCB
Isolation of the closed cooling water heat
xFSD00533 PCC SC4 PAS 2 PAS 2 Siemens
exchangers
PCH
PCB
Monitoring of the auxiliary cooling water
xFSD00534 PCC SC4 PAS 2 PAS 2 Siemens
system
ECCN: N

PCH
Auxiliary cooling water pump
(30PCC11/12 AP001) protection through PCB
xFSD00535 the protection OFF command in case of PCC SC4 PAS 2 PAS 2 Siemens
AL: N

difference pressure auxiliary cooling water PCH


pump too high(30PCC10 FP901)
Auxiliary cooling water pump
(30PCC11/12 AP001) protection through PCB
xFSD00536 the protection OFF command in case of PCC SC4 PAS 2 PAS 2 Siemens
difference pressure auxiliary cooling water PCH
pump too low(30PCC10 FP901)
Auxiliary cooling water pump
(30PCC11/12 AP001) protection through PCB
xFSD00537 the protection OFF command in case of PCC SC4 PAS 2 PAS 2 Siemens
high motor winding temperature PCH
(30PCC11/12 CT971/973/975)
Auxiliary cooling water pump
(30PCC11/12 AP001) protection through PCB
xFSD00538 the protection OFF command in case of PCC SC4 PAS 2 PAS 2 Siemens
low level in the intake pit (30PCB10 PCH
CL901)
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A87 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Control of Pumping of auxiliary cooling PCB
xFSD00539 water to the closed cooling water heat PCC EYT PAS 2 PAS 2 Siemens
exchangers PCH
PCB
Monitoring of the auxiliary cooling water
xFSD00540 PCC SC4 PAS 2 PAS 2 Siemens
pump
PCH
PCB
Control of cleaning of the closed cooling
xFSD00541 PCC EYT SSS SSS Siemens
water heat exchangers by rubber balls
PCH
PCB
xFSD00542 Monitoring of the tube cleaning system PCC EYT SSS SSS Siemens
PCH
Monitoring of the moisture separator
xFSD00543 LCT EYT PAS 2 PAS 2 Siemens
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

drains system
Close protection emergency drains valve
(30LCT11/21 AA111) on Moisture
xFSD00547 Separator Condensate Tank Level LCT EYT PAS 2 PAS 2 Siemens
30LCT11/21 CL001/002/003 (CL901) =<
LOW2
Close protection normal drains valve
(30LCT11/21 AA101) on Moisture
Separator Condensate Tank Level
30LCT11/21 CL001/002/003 (CL901] =<
xFSD00548 LCT EYT PAS 2 PAS 2 Siemens
LOW2 (incl. Warning on Moisture
Separator Condensate Tank Level
30LCT11/21 CL001/002/003 (CL901) =<
LOW2)
Emergency drains level control
(30LCT11/21 AA111) on Moisture
Separator Condensate Tank Level
30LCT11/21 CL001/002/003 (CL901] >=
HIGH 1 (incl Alarm on Moisture Separator
xFSD00549 LCT EYT PAS 2 PAS 2 Siemens
Condensate Tank Level 30LCT11/21
CL001/002/003 (CL901) >= HIGH 2 and
Alarm on Moisture Separator Condensate
Tank Level 30LCT11/21 CL001/002/003
(CL901) >= HIGH 3)
ECCN: N

Enable moisture separator condensate


pump (30LCT11/21 AP001) start on
xFSD00550 Moisture Separator Condensate Tank LCT EYT PAS 2 PAS 2 Siemens
Level 30LCT11/21 CL001/002/003
AL: N

(CL901] =< LOW1


Normal drains level control when Moisture
Separator Condensate Tank Level
xFSD00551 LCT EYT PAS 2 PAS 2 Siemens
30LCT11/21 CL001/002/003 (CL901)
within range
Steam Turbine Trip on Moisture Separator
xFSD00552 Condensate Tank Level 30LCT11/21 LCT EYT PAS 2 PAS 2 Siemens
CL001/002/003 (CL901) >= HIGH 3
Trip moisture separator condensate pump
(30LCT11/21 AP001) on Moisture
Separator Condensate Tank Level
xFSD00553 30LCT11/21 CL001/002/003 (CL901) =< LCT EYT PAS 2 PAS 2 Siemens
LOW3 (incl. Alarm on Moisture Separator
Condensate Tank Level 30LCT11/21
CL001/002/003 (CL901) =< LOW3)
Injection water control of drains piping
xFSD00555 LCT EYT PAS 2 PAS 2 Siemens
(30LCT19/29 DT101)
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A88 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Protection OFF command of Moisture
separator condensate pump (30LCT11/21
xFSD00556 LCT EYT PAS 2 PAS 2 Siemens
AP001) in case of high flow downstream
the pump (30LCT11/21 CF001)
Protection OFF command of Moisture
separator condensate pump (30LCT11/21
xFSD00557 AP001) in case of high motor winding LCT EYT PAS 2 PAS 2 Siemens
temperature (30LCT11/21
CT971/973/975)
Protection OFF command of Moisture
separator condensate pump (30LCT11/21
AP001) in case of high pressure drop in
xFSD00558 condensate tank caused by a rapid load LCT EYT PAS 2 PAS 2 Siemens
decrease (i.e. steam turbine
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

trip or load change to house load


operation) (cavitation protection)
Protection OFF command of Moisture
separator condensate pump (30LCT11/21
xFSD00559 AP001) in case of low flow by normal LCT EYT PAS 2 PAS 2 Siemens
drains control valve position higher than
5% (cavitation protection)
Protection OFF command of Moisture
separator condensate pump (30LCT11/21
xFSD00560 LCT EYT PAS 2 PAS 2 Siemens
AP001) in case of low level in the
condensate tank (30LCT11/21 CL901)
Protection OFF command of Moisture
separator condensate pump (30LCT11/21
xFSD00561 LCT EYT PAS 2 PAS 2 Siemens
AP001) in case of high feedwater storage
tank level (30LAA10 CL901)
Level control of the drain pots
xFSD00562 LBA* SC4 PAS 2 PAS 2 Siemens
(30LBA10/20/30/40/50 EE401)
Level control of the drain pots
xFSD00563 LBA* SC4 PAS 2 PAS 2 Siemens
(30LBA10/20/30/40 EE448)
xFSD00564 Monitoring of main steam piping system LBA* SC4 PAS 2 PAS 2 Siemens
LBB
xFSD00565 Monitoring of the hot reheat piping system LBC SC4 TGI TGI (Siemens)
ECCN: N

LBJ
LBB
Monitoring of the cold reheat piping
xFSD00566 LBC SC4 TGI TGI (Siemens)
system
LBJ
AL: N

LBB
Pilot Control Heating Steam Reheater 1/2
xFSD00567 LBC SC4 TGI TGI (Siemens)
30LBJ60DT001
LBJ
LBB
Warm-up Valve Step Control
xFSD00568 LBC SC4 TGI TGI (Siemens)
30LBJ51/52DT001
LBJ
LBB
Cooldown Control Reheater Stage2
xFSD00569 LBC SC4 TGI TGI (Siemens)
30LBJ60FT001/2
LBJ
Calculation Waiting Time 30LBJ70FT002 LBB
xFSD00570 for warming up the turbine shaft after LBC SC4 TGI TGI (Siemens)
exceeding 160MW load LBJ
LBB
Cooldown Control Reheater Stage1
xFSD00571 LBC SC4 TGI TGI (Siemens)
30LBJ70FT001
LBJ
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A89 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Group Control Preheat Reheater 1/2
LBB
30LBJ01EB001 to put the moisture
xFSD00572 LBC SC4 TGI TGI (Siemens)
separator reheater stage 1 and 2 into
LBJ
operation one after the other
LBB
Monitoring of the moisture separator
xFSD00573 LBC SC4 TGI TGI (Siemens)
reheater and heating steam supply
LBJ
Control of warming up Closed loop control LBB
xFSD00574 of the second stage of the reheater by LBC SC4 TGI TGI (Siemens)
warmup valves and heating steam valves LBJ
Subgroup Control Preheat Reheater
Stage 1 30LBJ70EC001 to put in LBB
xFSD00575 operation the reheater stage 1 of both LBC SC4 TGI TGI (Siemens)
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

moisture separator reheaters and to shuts LBJ


down the reheater stages 1
Subgroup Control Preheat Reheater
Stage 2 30LBJ60EC001 to put in LBB
xFSD00576 operation the reheater stage 2 of both LBC SC4 TGI TGI (Siemens)
moisture separator reheaters and to shuts LBJ
down the reheater stages 2
LBB
xFSD00577 MSR overpressure protection LBC SC4 TGI TGI (Siemens)
LBJ
MAK
xFSD00578 Monitoring of the Shaft Turning Gear EYT TGI TGI (Siemens)
MAV
MAK
xFSD00579 Monitoring of the Lube Oil System SC4 TGI TGI (Siemens)
MAV
MAK
xFSD00580 Automatic start of the turbine oil supply EYT TGI TGI (Siemens)
MAV
Fire protection (Oil supply emergency MAK
xFSD00581 EYT TGI TGI (Siemens)
operation) MAV
MAK
xFSD00582 Control of Lube oil supply EYT TGI TGI (Siemens)
MAV
MAK
xFSD00583 SGC (sub group control) oil pump tests EYT TGI TGI (Siemens)
MAV
ECCN: N

MAK
xFSD00584 Control of Lifting oil supply EYT TGI TGI (Siemens)
MAV
MAK
xFSD00585 Control of Turning gear EYT TGI TGI (Siemens)
MAV
AL: N

MAK
xFSD00586 Control of Oil Vapour Exhaust System EYT TGI TGI (Siemens)
MAV
MAK
xFSD00587 Control of Oil Purification System EYT TGI TGI (Siemens)
MAV
xFSD00588 Starting up Turbine Generator MYA SC4 TGI TGI (Siemens)
Control of the turbine speed MAA
xFSD00589 SC4 TGI TGI (Siemens)
(30MYA01CS901) MAC
Control of the turbine speed
xFSD00589 MYA SC4 TGI TGI (Siemens)
(30MYA01CS901)
Control of turbine Load (30 MAA
xFSD00590 SC4 TGI TGI (Siemens)
MKA01CE903A) and Load limitiation MAC
Control of turbine Load (30
xFSD00590 MYA SC4 TGI TGI (Siemens)
MKA01CE903A) and Load limitiation
Controlling of the main steam HP MAA
xFSD00591 SC4 TGI TGI (Siemens)
pressure (30LBA50CP901) MAC
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A90 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Controlling of the main steam HP
xFSD00591 MYA SC4 TGI TGI (Siemens)
pressure (30LBA50CP901)
Limitation of the generator maximum load
xFSD00592 MYA SC4 TGI TGI (Siemens)
set-point from reactor
Limitation of the output of main steam
xFSD00593 MYA SC4 TGI TGI (Siemens)
minimum pressure controller
Limitation of the load capability from the
secondary and primary side (currently
xFSD00594 possible load with due consideration of MYA SC4 TGI TGI (Siemens)
load limiting faults and existing energy
storage)
MAA
xFSD00595 Valve position control SC4 TGI TGI (Siemens)
MAC
xFSD00595 Valve position control MYA SC4 TGI TGI (Siemens)
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

Maintaining Turbine Operation in the


xFSD00596 MYA SC4 TGI TGI (Siemens)
Event of Grid Faults
xFSD00597 Run back from generator MYA SC4 TGI TGI (Siemens)
Throttling Main Steam Turbine Control
xFSD00599 MYA SC4 TGI TGI (Siemens)
Valves
xFSD00600 Maintenance key switch MAY SC4 TGI TGI (Siemens)
Turbine trip by bearing casing vibration MAA
xFSD00601 SC4 TGI TGI (Siemens)
HIGH 2 out of 2 MAC
Turbine trip by bearing casing vibration
xFSD00601 MAD SC4 TGI TGI (Siemens)
HIGH 2 out of 2
Turbine trip by bearing casing vibration
xFSD00601 MAY SC4 TGI TGI (Siemens)
HIGH 2 out of 2
Turbine trip by Axial shaft displacement MAA
xFSD00602 SC4 TGI TGI (Siemens)
HIGH 2 out of 3 MAC
Turbine trip by Axial shaft displacement
xFSD00602 MAD SC4 TGI TGI (Siemens)
HIGH 2 out of 3
Turbine trip by Axial shaft displacement
xFSD00602 MAY SC4 TGI TGI (Siemens)
HIGH 2 out of 3
Turbine trip by Condenser level HIGH 2 MAA
xFSD00603 SC4 TGI TGI (Siemens)
out of 3 MAC
ECCN: N

Turbine trip by Condenser level HIGH 2


xFSD00603 MAG SC4 TGI TGI (Siemens)
out of 3
Turbine trip by Condenser level HIGH 2
xFSD00603 MAN SC4 TGI TGI (Siemens)
out of 3
AL: N

Turbine trip by Condenser level HIGH 2


xFSD00603 MAY SC4 TGI TGI (Siemens)
out of 3
Turbine trip by Condenser pressure HIGH MAA
xFSD00604 SC4 TGI TGI (Siemens)
2 out of 3 MAC
Turbine trip by Condenser pressure HIGH
xFSD00604 MAG SC4 TGI TGI (Siemens)
2 out of 3
Turbine trip by Condenser pressure HIGH
xFSD00604 MAN SC4 TGI TGI (Siemens)
2 out of 3
Turbine trip by Condenser pressure HIGH
xFSD00604 MAY SC4 TGI TGI (Siemens)
2 out of 3
Turbine trip if control fluid supply is not
MAA
xFSD00605 available: Emergency push button at SC4 TGI TGI (Siemens)
MAC
control fluid supply module activated
Turbine trip if control fluid supply is not
xFSD00605 available: Emergency push button at MAX SC4 TGI TGI (Siemens)
control fluid supply module activated
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A91 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Turbine trip if control fluid supply is not
xFSD00605 available: Emergency push button at MAY SC4 TGI TGI (Siemens)
control fluid supply module activated
Turbine trip if tank level
xFSD00606 30MAX01/02/03/05/06/001/002/003 too MAX SC4 TGI TGI (Siemens)
low
Turbine trip if tank level
xFSD00606 30MAX01/02/03/05/06/001/002/003 too MAY SC4 TGI TGI (Siemens)
low
xFSD00608 Tank level protection MAX MAX SC4 TGI TGI (Siemens)
xFSD00608 Tank level protection MAX MAY SC4 TGI TGI (Siemens)
Turbine trip by control fluid supply if
MAA
xFSD00609 Control fluid supply pressure <MIN (2 out SC4 TGI TGI (Siemens)
MAC
of 2 analogue configuration)
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

Turbine trip by control fluid supply if


xFSD00609 Control fluid supply pressure <MIN (2 out MAX SC4 TGI TGI (Siemens)
of 2 analogue configuration)
Turbine trip by control fluid supply if
xFSD00609 Control fluid supply pressure <MIN (2 out MAY SC4 TGI TGI (Siemens)
of 2 analogue configuration)
Turbine trip by control fluid supply if
xFSD00610 Control fluid supply pressure >MAX (2 out MAY SC4 TGI TGI (Siemens)
of 2 analogue configuration)
Turbine trip by control fluid supply if
xFSD00611 Control fluid temperature <MIN (2 out of 2 MAY SC4 TGI TGI (Siemens)
analogue configuration)
Turbine trip by control fluid supply if
Emergency push button at control fluid
xFSD00612 MAY SC4 TGI TGI (Siemens)
supply module activated. (1 out of 2 binary
configuration, energise to trip principle)
Turbine trip by CRH pressure HIGH 2 out MAA
xFSD00613 SC4 TGI TGI (Siemens)
of 3 MAC
Turbine trip by CRH pressure HIGH 2 out
xFSD00613 MAY SC4 TGI TGI (Siemens)
of 3
ECCN: N

Turbine trip by Electronic generator


xFSD00614 protection (for mechanical components) MAY SC4 TGI TGI (Siemens)
system
MAK
xFSD00615 Turbine trip by Fire protection system SC4 TGI TGI (Siemens)
MAV
AL: N

xFSD00615 Turbine trip by Fire protection system MAY SC4 TGI TGI (Siemens)
Turbine trip by Generator unit protection
xFSD00616 MAY SC4 TGI TGI (Siemens)
(for electrical components) system
Turbine trip by HP casing bending HIGH 2 MAA
xFSD00617 SC4 TGI TGI (Siemens)
out of 2 MAC
Turbine trip by HP casing bending HIGH 2
xFSD00617 MAY SC4 TGI TGI (Siemens)
out of 2
Turbine trip by LP exhaust temperature MAA
xFSD00618 SC4 TGI TGI (Siemens)
HIGH 2 out of 3 MAC
Turbine trip by LP exhaust temperature
xFSD00618 MAY SC4 TGI TGI (Siemens)
HIGH 2 out of 3
Turbine trip by Lube oil pressure LOW 2 MAA
xFSD00619 SC4 TGI TGI (Siemens)
out of 3 MAC
Turbine trip by Lube oil pressure LOW 2 MAK
xFSD00619 SC4 TGI TGI (Siemens)
out of 3 MAV
xFSD00619 Turbine trip by Lube oil pressure LOW 2 MAY SC4 TGI TGI (Siemens)
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A92 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
out of 3
Turbine trip by Lube oil tank level MAA
xFSD00620 SC4 TGI TGI (Siemens)
LOW/HIGH 2 out of 3 MAC
Turbine trip by Lube oil tank level MAK
xFSD00620 SC4 TGI TGI (Siemens)
LOW/HIGH 2 out of 3 MAV
Turbine trip by Lube oil tank level
xFSD00620 MAY SC4 TGI TGI (Siemens)
LOW/HIGH 2 out of 3
Turbine trip by Manual trip push button in
xFSD00621 MAY SC4 TGI SCP CLT
the main control room / local 2 out of 3
Turbine trip by Overspeed HIGH (System MAA
xFSD00622 SC4 TGI TGI (Siemens)
1/2) 2 out of 3 MAC
Turbine trip by Overspeed HIGH (System
xFSD00622 MAY SC4 TGI TGI (Siemens)
1/2) 2 out of 3
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

xFSD00623 Turbine trip by SGC steam turbine steam MAY SC4 TGI TGI (Siemens)
Turbine trip by Turbine bearing MAA
xFSD00624 SC4 TGI TGI (Siemens)
temperature HIGH 2 out of 3 MAC
Turbine trip by Turbine bearing
xFSD00624 MAD SC4 TGI TGI (Siemens)
temperature HIGH 2 out of 3
Turbine trip by Turbine bearing
xFSD00624 MAY SC4 TGI TGI (Siemens)
temperature HIGH 2 out of 3
Turbine trip initiation by internal failures of
xFSD00625 MAY SC4 TGI TGI (Siemens)
turbine trip system
Turbine Trip initiation by moisture
xFSD00626 MAY SC4 TGI TGI (Siemens)
separator condensate tank level high
MAA
xFSD00627 Steam turbine start up SC4 TGI TGI (Siemens)
MAC
xFSD00627 Steam turbine start up MAY SC4 TGI TGI (Siemens)
MAA
xFSD00628 Control of vacuum breaker SC4 TGI TGI (Siemens)
MAC
xFSD00628 Control of vacuum breaker MAG SC4 TGI TGI (Siemens)
xFSD00628 Control of vacuum breaker MAY SC4 TGI TGI (Siemens)
Opening of control valves have when
xFSD00629 MAY SC4 TGI TGI (Siemens)
conservation mode is active
ECCN: N

xFSD00630 Steam turbine testing MAY SC4 TGI TGI (Siemens)


Condenser level protection 2oo3 for
xFSD00634 MAN SC4 TGI TGI (Siemens)
Bypass trip
Condensor Pressure Protection 2oo3 for
AL: N

xFSD00635 MAN SC4 TGI TGI (Siemens)


Bypass Trip
xFSD00636 Control fluid MAN SC4 TGI TGI (Siemens)
xFSD00637 Leakage Monitoring MAN SC4 TGI TGI (Siemens)
Main Steam Bypass Valves Position
xFSD00638 MAN SC4 TGI TGI (Siemens)
Control
xFSD00639 Pushbutton MSB Trip MAN SC4 TGI TGI (Siemens)
Water injection protection 2oo3 for 2 stage
xFSD00640 with pressure (analog) and position MAN SC4 TGI TGI (Siemens)
(binary) monitoring
Monitoring and controlling of the HP
xFSD00641 MAN SC4 TGI TGI (Siemens)
bypass system MAN
xFSD00642 Monitoring of the condensing system MAG SC4 TGI TGI (Siemens)
xFSD00643 Monitoring of the Drainage system MAL EYT TGI TGI (Siemens)
xFSD00644 Position control of drain valve MAL MAL EYT TGI TGI (Siemens)
Monitoring of the main condenser MAJ
xFSD00645 SC4 TGI TGI (Siemens)
evacuation system MAQ
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A93 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Routing of the extracted air to the vent MAJ
xFSD00646 SC4 TGI TGI (Siemens)
stack in case of SGTR MAQ
Start of the spare vacuum unit, if annother
MAJ
xFSD00647 unit fails, or the condenser pressure is SC4 TGI TGI (Siemens)
MAQ
high
Protection OFF command of vacuum
pumps (3 0MAJ60/70/80AN001) in case MAJ
xFSD00648 SC4 TGI TGI (Siemens)
of high cool medium temperature in the MAQ
vacuum pump (3 0MAJ60/70/80CT001).
Operation of vacuum units to evacuate
MAJ
xFSD00649 residual air from the condensers SC4 TGI TGI (Siemens)
MAQ
30MAJ60/70/80AN001
MAJ
xFSD00650 Monitoring of the gas dryer EYT PAS 2 PAS 2 Siemens
MAQ
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

Monitoring of Spindel Leak-Off System MAM


xFSD00651 EYT TGI TGI (Siemens)
MAM MAW
MAM
xFSD00653 Control of Gland Steam Exhaust Fans EYT TGI TGI (Siemens)
MAW
Monitoring of Seal and Gland Steam
MAM
xFSD00654 System MAW (incl. Alarm in case of EYT TGI TGI (Siemens)
MAW
Gland Steam Condenser High Level)
MAM
xFSD00655 Seal Steam Pressure Control EYT TGI TGI (Siemens)
MAW
MAM
xFSD00656 Seal Steam Temperature Control EYT TGI TGI (Siemens)
MAW
Monitoring of the Hydraulic Supply Station
xFSD00657 MAX SC4 TGI TGI (Siemens)
MAX
xFSD00658 Control fluid temperature control MAX SC4 TGI TGI (Siemens)
xFSD00659 Control fluid temperature protection MAX SC4 TGI TGI (Siemens)
xFSD00660 Filter monitoring MAX SC4 TGI TGI (Siemens)
xFSD00661 Fire protection MAX SC4 TGI TGI (Siemens)
xFSD00662 Leakage monitoring MAX SC4 TGI TGI (Siemens)
Operation of the supply pumps for
xFSD00663 MAX SC4 TGI TGI (Siemens)
hydraulic oil
ECCN: N

xFSD00664 Switchover of pumps MAX SC4 TGI TGI (Siemens)


xFSD00665 Control of Startup and Shutdown MAX SC4 TGI TGI (Siemens)
xFSD00666 Main Pressure / Pump Control MAX SC4 TGI TGI (Siemens)
Manual emergency switch off Control
AL: N

xFSD00667 MAX SC4 TGI TGI (Siemens)


Fluid Supply Unit
Manual initiatiation of “Oil supply
xFSD00668 emergency operation” (Fire Protection MAX SC4 TGI TGI (Siemens)
Measures)
Monitoring of thermodynamic conditions MAA
xFSD00670 SC4 TGI TGI (Siemens)
(display in control room) MAC
MAA
xFSD00671 Control of extraction check valves SC4 TGI TGI (Siemens)
MAC
MAA
xFSD00672 Control of LP water injection valve SC4 TGI TGI (Siemens)
MAC
Monitoring of thermal stress (Turbine MAA
xFSD00673 SC4 TGI TGI (Siemens)
stress controller (TSC)) MAC
MAA
xFSD00674 Monitoring of valve actuator leakage SC4 TGI TGI (Siemens)
MAC
MAA
xFSD00675 Monitoring of LP blading temperature SC4 TGI TGI (Siemens)
MAC
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A94 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
MAA
xFSD00676 Monitoring of LP blading vibration SC4 TGI TGI (Siemens)
MAC
Monitoring of turbine bearing metal MAA
xFSD00677 SC4 TGI TGI (Siemens)
temperature MAC
Monitoring of turbine bearing metal
xFSD00677 MAD SC4 TGI TGI (Siemens)
temperature
Monitoring of valve position in ST position MAA
xFSD00678 SC4 TGI TGI (Siemens)
controller MAC
MAA
xFSD00679 Monitoring of relative expansion SC4 TGI TGI (Siemens)
MAC
xFSD00679 Monitoring of relative expansion MAD SC4 TGI TGI (Siemens)
MAA
xFSD00680 Monitoring of relative shaft vibration SC4 TGI TGI (Siemens)
MAC
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

xFSD00680 Monitoring of relative shaft vibration MAD SC4 TGI TGI (Siemens)
MAA
xFSD00682 Turbine Stress Control SC4 TGI TGI (Siemens)
MAC
xFSD00683 Monitor the voltage regulator MKY SC4 TGI TGI (Siemens)
Automatic mode: automatic regulation of
xFSD00684 MKY SC4 TGI TGI (Siemens)
the generator terminal voltage
Manual mode: automatic regulation of the
xFSD00685 excitation current of the main exciter and MKY SC4 TGI TGI (Siemens)
consequently of the generator
xFSD00686 Over excitation limiting MKY SC4 TGI TGI (Siemens)
xFSD00687 Power system stabilization MKY SC4 TGI TGI (Siemens)
xFSD00688 Stator current limiting MKY SC4 TGI TGI (Siemens)
xFSD00689 U/f limiting MKY SC4 TGI TGI (Siemens)
xFSD00690 Under-excitation limiting MKY SC4 TGI TGI (Siemens)
Monitoring of LDB (Condensate
xFSD00691 LDB EYT SSS SSS Siemens
mechanical filtering system) -System
Generator trip in case of high bearing
xFSD00694 MKD SC4 TGI TGI (Siemens)
pedestal vibration
Generator trip in case of high bearing
xFSD00695 MKD SC4 TGI TGI (Siemens)
tempearture values
ECCN: N

Pressure control of the auxiliary steam


xFSD00696 LBA* EYT PAS 2 PAS 2 Siemens
header (30 LBG10 DP001/002/003)
Pressure control of the auxiliary steam LBG
xFSD00696 EYT PAS 2 PAS 2 Siemens
header (30 LBG10 DP001/002/003) LCN
AL: N

Maintain acceptable humidity conditions in SAD


xFSD00700 EYT PAS 1 SCP SAD-SAL
the electrical rooms SAL
Maintain minimum ambient temperature in
diesel hall when diesel generator is not in SAD
xFSD00702 EYT PAS 1 SCP SAD-SAL
operation (diesel is heated by its own SAL
heating system)
Ensure the extraction of heat generated
by the electrical and I&C equipment in the SAD
xFSD00703 SC3 SAS SCP SAD-SAL
diesel building; Maintain minimum SAL
ambient temperature
Ensure the extraction of heat generated
SAD
xFSD00704 by the SBO diesel generator during its SC3 SAS SCP SAD-SAL
SAL
operation
Maintain minimum ambient temperature in SAD
xFSD00705 SC3 SAS SCP SAD-SAL
main tank, service tank rooms SAL
xFSD00706 IRWST water level: Low level in IRWST JMQ SC3 SAS SCP JN
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A95 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
JNA; JND;
xFSD00706 IRWST water level: Low level in IRWST SC3 SAS SCP JN
JNG, JNK
KBA, KBD,
xFSD00706 IRWST water level: Low level in IRWST SC3 SAS SCP JN
JEW
Boration / Dilution on demand of Core
xFSD00707 KBC SC3 RCSL SCP KBC
Control
KBA, KBD,
xFSD00708 Boration on demand of limitation functions SC3 RCSL SCP KBC
JEW
xFSD00708 Boration on demand of limitation functions KBC SC3 RCSL SCP KBC
xFSD00709 Injection of boric acid KBC SC3 SAS SCP KBC
xFSD00710 Injection of demineralized water KBC SC3 SAS SCP KBC
xFSD00711 Mixing of the boric acid storage tanks KBC SC3 SAS SCP KBC
Refilling of the boric acid storage tanks
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

with fresh boric acid from 30KBC10


xFSD00712 KBC SC3 SAS SCP KBC
(Reactor boron and water make-up
system)
Refilling of the tanks with boric acid from
xFSD00713 reactor coolant treatment system 30KBF KBC SC3 SAS SCP KBF
(Coolant treatment system)
Transfer of boric acid between the boric
xFSD00714 KBC SC3 SAS SCP KBC
acid storage tanks
Preparation of boric acid solution used to FAK
xFSD00715 SC4 PAS 1 SCP KBC
fill all capacities containing boron solution FAL
Preparation of boric acid solution used to
xFSD00715 KBC SC4 PAS 1 SCP KBC
fill all capacities containing boron solution
KBA, KBD,
xFSD00716 Auto Makeup control SC3 RCSL SCP KBC
JEW
xFSD00716 Auto Makeup control KBC SC3 RCSL SCP KBC
xFSD00717 Prevent Dilution via RCSL KBC SC3 RCSL SCP KBC
Safe plant and operation control:
xFSD00718 Monitoring of containment closure status JMA90 SC3 SSS SCP JMA
and fuel assemblies integrity protection
Safe plant and operation control:
Monitoring of double barrier integrity of
ECCN: N

xFSD00719 JMA90 SC4 SSS SCP JMA


compensators and valve stem
penetrations
xFSD00720 EFW pumps protection LAR, LAS SC3 SAS SCP LAR-LAS
xFSD00721 EFW pools water make-up LAR, LAS SC3 SAS SCP LAR-LAS
AL: N

xFSD00722 EFWS pump monitoring LAR, LAS SC3 SAS SCP LAR-LAS
xFSD00724 Risk of Heterogenous Dilution KAA, KAB SC3 SAS SCP KAA/KAB
xFSD00726 Emergency Backup Switchover KAA, KAB SC3 SAS SCP KAA/KAB
xFSD00726 Emergency Backup Switchover PEB/PEH SC3 SAS SCP KAA/KAB
xFSD00727 CCW supply temperature control KAA, KAB SC3 SAS SCP KAA/KAB
xFSD00728 CCWS high temperature KAA, KAB SC3 SAS SCP KAA/KAB
SAS differential pressure control at the
xFSD00729 KAA, KAB SC3 SAS SCP KAA/KAB
heat exchanger outlet
xFSD00730 Leak detection sequence KAA, KAB SC3 SAS SCP KAA/KAB
FAK
xFSD00731 CCWS trains abnormal flow rate SC3 SAS SCP KAA/KAB
FAL
xFSD00731 CCWS trains abnormal flow rate KAA, KAB SC3 SAS SCP KAA/KAB
xFSD00732 CCWS surge tank make-up KAA, KAB EYT PAS 1 SCP KAA/KAB
xFSD00733 Dedicated CCWS: Cooling function KAA50/80 SC3 SAS SCP KAA50/80
xFSD00734 Dedicated CCWS: Water make-up KAA50/80 SC3 SAS SCP KAA50/80
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A96 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
xFSD00735 Dedicated CCWS: Circuit pressurization KAA50/80 SC3 SAS SCP KAA50/80
Automatic trip orders for cooling pumps in FAK
xFSD00736 SC3 SAS SCP FAK/FAL
case of high temperature FAL
Automatic trip orders for cooling pumps in FAK
xFSD00737 SC3 SAS SCP FAK/FAL
case of low pressure FAL
Automatic trip orders for cooling pumps in FAK
xFSD00738 SC3 SAS SCP FAK/FAL
case of low SFP level FAL
Opening and closing of IRWST suction FAK
xFSD00739 SC3 SAS SCP JN
valves FAL
Opening and closing of IRWST suction JNA; JND;
xFSD00739 SC3 SAS SCP JN
valves JNG, JNK
Opening and closing of motorized
FAK
xFSD00740 isolation valve downstream of cooling SC3 SAS SCP FAK/FAL
FAL
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

trains
FAK
xFSD00742 Physical protections for skimming pumps SC4 PAS 1 SCP FAK/FAL
FAL
Protection closing order for ILCO water FAK
xFSD00743 SC4 PAS 1 SCP FAK/FAL
make-up valve FAL
Component and system protection of fuel FAK
xFSD00744 SC4 PAS 1 SCP JN
pool purification system FAL
JAA
JAC
Component and system protection of fuel JEA
xFSD00744 SC4 PAS 1 SCP JN
pool purification system JEB
JEC
JEF, JEG
Component and system protection of fuel JNA; JND;
xFSD00744 SC4 PAS 1 SCP JN
pool purification system JNG, JNK
Component and system protection of fuel
xFSD00744 KBE SC4 PAS 1 SCP JN
pool purification system
Enable conditions for purification and FAK
xFSD00745 SC4 PAS 1 SCP FAK/FAL
skimming pumps start FAL
Motorized control valve downstream of FAK
xFSD00746 SC4 PAS 1 SCP FAK/FAL
purification pumps FAL
ECCN: N

Maintain the room ambient conditions in


FAK
xFSD00747 30JDH pump rooms and 30FAK pump SC3 SAS SCP KLL
FAL
rooms
Maintain the room ambient conditions in
AL: N

xFSD00747 30JDH pump rooms and 30FAK pump KLL SC3 SAS SCP KLL
rooms
FAK
xFSD00748 Fuel handling hall isolation SC3 SAS SCP KLL
FAL
xFSD00748 Fuel handling hall isolation KLL SC3 SAS SCP KLL
xFSD00749 Room in front of the hatch isolation KLL SC3 SAS SCP KLL
Room in front of the emergency airlock
xFSD00750 KLL SC3 SAS SCP KLL
isolation
Maintain sub-pressure in the Fuel Building
xFSD00751 KLL SC4 PAS 1 SCP KLL
with respect to outside atmosphere
Reduce the concentration of aerosols and
xFSD00752 KLL SC4 PAS 1 SCP KLL
radioactive gases in the air of the rooms
Maintain acceptable room ambient
conditions in the Fuel Building for FAK
xFSD00753 EYT PAS 1 SCP KLL
equipment operation and personnel FAL
access
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A97 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Maintain acceptable room ambient
conditions in the Fuel Building for
xFSD00753 KLL EYT PAS 1 SCP KLL
equipment operation and personnel
access
Maintain acceptable ambient conditions
for the personnel
xFSD00754 KLA EYT PAS 1 SCP KLA
working in the RB during cold shutdown
periods
Maintain the ambient conditions needed to
ensure the correct operation of equipment JNA; JND;
xFSD00755 EYT PAS 1 SCP KLA
in equipment and service compartments JNG, JNK
of the Reactor Building
Maintain the ambient conditions needed to
ensure the correct operation of equipment
xFSD00755 KLA EYT PAS 1 SCP KLA
in equipment and service compartments
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

of the Reactor Building


xFSD00756 Pit cooling ventilation and cooling KLA SC3 SAS SCP KLA
Closing of the air supply in front of the
xFSD00757 JYK, KLK SC3 SAS SCP KLA
hatch and of KLA2 filter isolation dampers
Closing of the air supply in front of the
xFSD00757 KLA SC3 SAS SCP KLA
hatch and of KLA2 filter isolation dampers
Closing of the air supply in front of the
xFSD00757 KLC SC3 SAS SCP KLA
hatch and of KLA2 filter isolation dampers
Create a pressure difference between the
xFSD00758 atmospheric pressure and the service KLA SC4 PAS 1 SCP KLA
compartments in Reactor Building.
Create a pressure difference between the
xFSD00759 KLA SC4 PAS 1 SCP KLA
service and the equipment compartments
Perform a mini sweep ventilation of the
xFSD00760 service KLA SC4 PAS 1 SCP KLA
compartment of Reactor Building
Reduce the aerosol and radioactive iodine
xFSD00761 contamination inside the equipment KLA SC4 PAS 1 SCP KLA
compartment of the containment
Remove the radioactivity by exhaust
xFSD00762 KLA SC4 PAS 1 SCP KLA
filtering
ECCN: N

Continuous ventilation lines: Isolation of


xFSD00765 KLB SC3 SAS SCP KLB
the continuous lines
Continuous ventilation lines: Isolation of
xFSD00766 KLB SC3 SICS SCP KLB
the continuous lines
AL: N

Continuous ventilation lines: Subpressure


xFSD00767 KLB SC4 SAS SCP KLB
inside the annulus
Accidental line: Sub pressure of the
xFSD00768 KLB SC3 SAS SCP KLB
annulus in the case of accidents
Provide the status of the doors to confine
inside the reactor containment radioactive
xFSD00770 JME EYT SSS SCP JME
substances released from the reactor in
consequence of an accident
Signal used to allow opening sequence of
xFSD00771 JME EYT SSS SCP JME
the Hatch from MCR
xFSD00772 Signal used to allow closing of the Hatch JME EYT SSS SCP JME
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A98 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Air intake isolation to stop the pressure
inside UJA containment in order to
prevent damages on the structures of the
xFSD00773 JMM EYT PAS 1 SCP JMM
building and their equipments in case of
excessive pressurization during the
Inflating phase of UJA containment.

Air intake isolation to stop the pressure


inside UJA containment in order to
prevent damages on the structures of the
xFSD00773 JMQ EYT PAS 1 SCP JMM
building and their equipments in case of
excessive pressurization during the
Inflating phase of UJA containment.
Air exhaust isolation to stop the de-
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

pressurisation of UJA containment in


order to prevent damages on the
xFSD00774 structures of the building and their JMM EYT PAS 1 SCP JMM
equipments in case of excessive flow rate
in the discharge line to the atmosphere
during the global leaktightness test.
Inflating and deflating function . Control
xFSD00775 the containment pressure during testing JMM EYT PAS 1 SCP JMM
(type A)
Leaktightness test . Calculate and check
xFSD00776 the global leak rate of the containment JMM EYT SSS SCP JMM
during testing (type A)
Containment isolation: manage the
position of containment isolation valves
xFSD00777 during the tightness tests of UJA JMM EYT PAS 1 SCP JMM
containment and during the operability
tests of the JMM containment valves
Provide the status of the doors (airlocks) JMF
xFSD00797 SC4 SSS SCP JMF-JMG
to main control room JMG
XJA10-40 SCP XJA-
xFSD00798 Operational Stop EDG SC4 PAS 1
XKA10-40 XKA10-20-30-40
XJA10-40 SCP XJA-
xFSD00799 Operational Start EDG SC4 PAS 1
XKA10-40 XKA10-20-30-40
ECCN: N

XJA10-40 SCP XJA-


xFSD00802 EDG Operational interlocking SC4 PAS 1
XKA10-40 XKA10-20-30-40
XJA10-40 SCP XJA-
xFSD00804 Speed Cubicle Control SC4 PAS 1
XKA10-40 XKA10-20-30-40
AL: N

XJA10-40 SCP XJA-


xFSD00805 EDG Operational Preheating function SC4 PAS 1
XKA10-40 XKA10-20-30-40
XJA10-40 SCP XJA-
xFSD00807 Diesel engine fuel oil system Control SC4 PAS 1
XKA10-40 XKA10-20-30-40
XJA10-40 SCP XJA-
xFSD00810 Diesel engine lube oil system Control SC4 PAS 1
XKA10-40 XKA10-20-30-40
XJA10-40 SCP XJA-
xFSD00816 Diesel engine cooling systems control SC4 PAS 1
XKA10-40 XKA10-20-30-40
XJA50/80, SCP XJA-XKA
xFSD00818 Test operation SC4 SSS
XKA50/80 50/80
XJA50/80, SCP XJA-XKA
xFSD00822 Generator protection SC4 SSS
XKA50/80 50/80
XJA50/80, SCP XJA-XKA
xFSD00823 Cooling function SC3 SSS
XKA50/80 50/80
XJA50/80, SCP XJA-XKA
xFSD00824 LT Preheating function SC3 SSS
XKA50/80 50/80
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A99 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
XJA50/80, SCP XJA-XKA
xFSD00825 Cooling function SC4 SSS
XKA50/80 50/80
XJA50/80, SCP XJA-XKA
xFSD00826 HT Preheating function SC4 SSS
XKA50/80 50/80
XJA50/80, SCP XJA-XKA
xFSD00827 Fuel transfer pumps SC3 SSS
XKA50/80 50/80
XJA50/80, SCP XJA-XKA
xFSD00828 Fuel transfer pumps SC4 SSS
XKA50/80 50/80
XJA50/80, SCP XJA-XKA
xFSD00829 Stop of SBO diesel SC4 SSS
XKA50/80 50/80
XJA50/80, SCP XJA-XKA
xFSD00830 Air compressor SC4 SSS
XKA50/80 50/80
Maintain acceptable ambient temperature
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

xFSD00832 in the main control room 32UJK26030 SAB90 SC3 SSS SCP SAB
during first 2hours of SBO
Isolate the volume of mechanical divisions
xFSD00833 of Safeguard Buildings when the SIS KLC SC3 SAS SCP KLC
system is used after an accident in the RB
Ensure the extraction of heat generated
by the SIS/RHR, KAA/LAR and JMU/KUL
xFSD00834 (Div 1 and 4 only) systems equipment to KLC SC3 SAS SCP KLC
maintain ambient temperatures below the
maximum limits
Maintain subpressure in the affected area
and remove iodine released in the RB or
xFSD00835 KLC SC3 SAS SCP KLC
fuel handling hall in the event of a fuel
handling accident
Maintain sub-pressure in controlled area
of Safeguard Buildings with respect to
xFSD00836 adjacent areas and the airflow direction KLC SC4 SAS SCP KLC
inside the building during normal
operation
Isolate the rooms of the SIS/RHR systems
in Divisions 1 and 4 if the plant is in RHR
xFSD00837 KLC SC3 SAS SCP KLC
mode with 30JN system temperatures >=
100°C
ECCN: N

Ensure the ventilation of rooms in relation


xFSD00838 KLC SC4 SAS SCP KLC
with 30SAC and 30KLE systems
Providing a minimum required air renewal
xFSD00839 KLC EYT SAS SCP KLC
rate
AL: N

Maintaining acceptable ambient


conditions taking into account internal and
external heat loads for rooms, which do
xFSD00840 KLC EYT SAS SCP KLC
not belong to the rooms of the 30JN
systems, 30KAA/LAR valve rooms and
rooms of the 30JMU and 30KUL systems
Maintain acceptable ambient conditions in
xFSD00841 the NAB for equipment operation and KLE EYT PAS 1 SCP KLE
personnel access.
Maintain acceptable ambient conditions in
xFSD00841 the NAB for equipment operation and SBA EYT PAS 1 SCP KLE
personnel access.
Maintain a sub-pressure in the NAB, FB,
Annulus and Containment with respect to
xFSD00842 outside atmosphere and maintain the air KLE SC4 PAS 1 SCP KLE
flow direction inside the NAB during
normal operation
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A100 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Ensure the necessary conditioning and
filtration of the air passing through the
xFSD00843 KLE SC4 PAS 1 SCP KLE
nuclear auxiliary, fuel building and
annulus ventilation system
Ensure, during normal operation, the
necessary conditioning of the supply air
xFSD00844 KLE SC4 PAS 1 SCP KLE
for the containment mini sweep ventilation
system
Ensure, during shutdown, the necessary
condition of the air supplied to the
xFSD00845 containment sweeping ventilation system KLE SC4 PAS 1 SCP KLE
and filter the exhaust air, upstream of the
fans
During normal operation, ensure that
exhaust air from the Safeguard Building
xFSD00846 KLE SC4 PAS 1 SCP KLE
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

controlled area Ventilation system is


properly filtered
Reduce airborne radioactivity released via
xFSD00847 the stack KLE SC4 PAS 1 SCP KLE
during normal operation
Prevent the spread of airborne
contamination outside of the Nuclear
xFSD00848 KLD SC3 SAS SCP KLE
Auxiliary Building by means of building
isolation
Prevent the spread of airborne
contamination outside of the Nuclear
xFSD00848 KLE SC3 SAS SCP KLE
Auxiliary Building by means of building
isolation
Prevent the spread of airborne
contamination outside of the Nuclear
xFSD00848 KLF SC3 SAS SCP KLE
Auxiliary Building by means of building
isolation
Building isolation to avoid low room
xFSD00849 KLE SC3 SAS SCP KLE
temperature in the boron rooms in FB
Provide additional supply and exhaust air
xFSD00850 SAC EYT PAS 1 SCP SAC
for maintenance purposes
Maintain acceptable ambient conditions
xFSD00851 and air renewal conditions in the non- SAC EYT PAS 1 SCP SAC
ECCN: N

controlled and mechanical area


Maintain ambient temperature conditions
xFSD00852 below maximum limits for EFWS (30LAS) SAC SC3 SAS SCP SAC
pumps and 30KAA system components
AL: N

Maintain acceptable ambient conditions BM, BN, BL,


xFSD00853 SC3 SAS SCP SAC
for the electrical and I&C rooms BR
Maintain acceptable ambient conditions
xFSD00853 SAC SC3 SAS SCP SAC
for the electrical and I&C rooms
Avoid incoming of hot combustion gases
in the fresh air intakes of the SAC system
xFSD00855 SAC SC4 SSS SCP SAC
in case of fire in the outside vicinity of the
Safeguard Buildings
Building Isolation function in case of
xFSD00856 SAC SC4 SAS SCP SAC
external hazards
Building Isolation function in case of
xFSD00857 SAC SC4 PAS 1 SCP SAC
external hazards
Provide air supply to the Safeguard
xFSD00858 SAC SC4 SAS SCP SAC
Building controlled area
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A101 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Provide heat sink in exhaust air plenum
for loading operation of Emergency
xFSD00859 SAC EYT SAS SCP SAC
Cooling System for the Main Control
Room 30SAB90 (only Division 2 + 3)
humidity control in the Main Control Room
and associated rooms and 30SAB air
xFSD00860 SAB EYT PAS 1 SCP SAB
conditioning technical rooms for
equipment and personnel
Overpressure control function in the main
control room during normal operation and
xFSD00861 accident operation to prevent uncontrolled SAB SC3 SAS SCP SAB
incoming leakages (for example smoke
during a fire outside the MCR)
Control of Temperature conditions for
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

equipment and personnel for the Main


BM, BN, BL,
xFSD00862 Control Room and associated rooms and SC3 SAS SCP SAB
BR
support their operability under accident
conditions
Control of Temperature conditions for
equipment and personnel for the Main
xFSD00862 Control Room and associated rooms and SAB SC3 SAS SCP SAB
support their operability under accident
conditions
Control the extraction of heat generated
xFSD00863 SAB SC3 SAS SCP SAB
by the electrical and I&C equipment
Control the habitability of the Main Control
Room and associated rooms in case of
xFSD00864 SAB SC3 SAS SCP SAB
radioactive or toxic gases contamination
of the environment
Control of Iodine and aerosol filtration in
xFSD00865 SAB SC3 SAS SCP SAB
case of severe accident
Control for Avoid incoming of hot
combustion gases in the fresh air intakes
xFSD00866 of SAB system after fire in the outside SAB SC4 SSS SCP SAB
vicinity of the Safeguard Buildings
(Division 2/3)
Control for Provide minimum air change
xFSD00867 SAB SC4 SAS SCP SAB
ECCN: N

rate
Monitoring and controls to maintain
acceptable ambient conditions in the Main
xFSD00868 SAM3 EYT PAS 1 SCP SAM3
Steam and Feedwater Valve
AL: N

compartments and the Service corridors.


Maintain acceptable ambient conditions in
xFSD00869 the Nuclear Auxiliary Building non SAM4 EYT PAS 1 SCP SAM4
controlled area
Maintain acceptable ambient conditions in
xFSD00869 the Nuclear Auxiliary Building non SBA EYT PAS 1 SCP SAM4
controlled area
xFSD00870 Flow sampling monitoring KLK SC3 SAS SCP JYK - KLK
xFSD00871 Temperature pipe tracing KLK SC3 SAS SCP JYK - KLK
Cooling of safety classified ventilation
xFSD00873 systems in the 4 safeguard building QKA-QKC SC3 SAS SCP QK
divisions
Cooling of non classified ventilation
systems as well as heat exchangers of the
xFSD00874 QN EYT SSS SCP QN
30KPL, 30KBG, 30KUA/QUC systems in
normal plant conditions
Monitoring of the operational chilled water
xFSD00875 QN EYT SSS SCP QN
system
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A102 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Protect systems carrying out safety
xFSD00876 CYE SC4 PAS 1 SCP SAG
functions in case of fire
Protect systems carrying out safety
xFSD00876 SAG SC4 PAS 1 SCP SAG
functions in case of fire
Maintain acceptable ambient conditions
xFSD00877 and air renewal conditions in the SAC80 EYT PAS 1 SCP SAC80
switchgear and cable rooms
Humidity Leakage monitoring outside
xFSD00878 JYH40 SC3 SSS SCP JYH40
containment
Automatic control and the protective
xFSD00879 KPL SC4 PAS 1 SCP KPL
interlocks of KPL
Automatic control and the protective
xFSD00879 KTA-KTE SC4 PAS 1 SCP KPL
interlocks of KPL
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

SCP JYH10-20-
xFSD00880 Humidity Leakage monitoring JYH80 SC3 SSS
80
Vent and drainage inside reactor building:
xFSD00881 Monitoring for normal operation, non KTA-KTE EYT PAS 1 SCP KT10/11
safety related
Vent and drainage inside reactor building:
xFSD00882 Manual or automatic orders to the KTA-KTE SC4 PAS 1 SCP KT10/11
isolation valves and pumps
Vent and drainage inside reactor building:
xFSD00883 KTA-KTE SC3 SAS SCP KT10/11
Protection of the KPL system
Vent and drainage inside reactor building:
xFSD00884 KTA-KTE SC3 SAS SCP KT10/11
Monitoring of the RCS leaktightness
Vent and drainage inside reactor building:
xFSD00885 KTA-KTE SC3 SAS SCP KT10/11
Water detection in the spreading area
Vent and drainage inside reactor building:
Monitoring of leakage by the floor drain
xFSD00886 KTA-KTE SC4 SAS SCP KT10/11
sumps to detect flooding in the annulus
building (UJB)
Vent and drainage inside reactor building:
Monitoring of leakage by the floor drain
xFSD00887 KTA-KTE SC4 SAS SCP KT10/11
sumps to detect flooding inside the reactor
building (UJA)
ECCN: N

Vent and drainage inside reactor building:


Monitoring of leakage by the floor drain
xFSD00888 KTA-KTE SC4 PAS 1 SCP KT10/11
sumps to detect flooding inside the reactor
building (UJA)
Vent and drainage outside reactor building
AL: N

xFSD00889 KTA-KTE SC4 PAS 1 SCP KTA/B


in UJH building
Vent and drainage outside reactor
xFSD00890 building: Sump level measurement; KTA-KTE SC3 SAS SCP KTC/D/E
flooding detection in UJH building
Vent and drainage outside reactor building
xFSD00893 KTA-KTE SC4 PAS 1 SCP KTA/B
in UFA building
Vent and drainage outside reactor
xFSD00894 building: Sump level measurement; KTA-KTE SC3 SAS SCP KTC/D/E
flooding detection in UFA building
Vent and drainage outside reactor building
xFSD00895 KTA-KTE SC4 PAS 1 SCP KTA/B
in UKA building
Vent and drainage: Monitoring of leakage
xFSD00896 by the floor drain sumps to detect flooding KTA-KTE SC4 PAS 1 SCP KTC/D/E
inside the waste building (UKS)
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A103 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Vent and drainage: Monitoring of leakage
xFSD00897 by the floor drain sumps to detect flooding KTA-KTE EYT PAS 1 SCP KTC/D/E
inside the access building (UKE)
xFSD00898 Tank medium selection KBB SC3 SAS SCP KBB
xFSD00899 Interlocking of Motor operated valves KBB SC3 SAS SCP KBB
xFSD00900 Level protection of coolant storage tanks KBB SC3 SAS SCP KBB
Sub group control for storage and supply
xFSD00901 KBB SC3 SAS SCP KBB
of borated water
Sub group control for storage and supply
xFSD00902 KBB SC3 SAS SCP KBB
of demineralized water
Temperature protection for resins in
xFSD00903 KBB SC4 PAS 1 SCP KBB
KBE20 AT001
xFSD00904 Local pressure measurements KBB EYT SSS SCP KBB
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

xFSD00905 Differential pressure protection of filters KBE SC3 SAS SCP KBE
Monitoring for wrong alignment of KBA FAK
xFSD00906 SC4 SAS SCP KBE
and FAL systems within KBE FAL
Monitoring for wrong alignment of KBA
xFSD00906 KBE SC4 SAS SCP KBE
and FAL systems within KBE
xFSD00909 Level protection of degasifier column KBG SC3 SAS SCP KBG
Automatic start-up and shutdown of
xFSD00913 KBG SC4 PAS 1 SCP KBG
degasification
xFSD00914 I&C performed by BBX KBG SC4 SSS SCP KBG
Sub loop control for Operator Mode
xFSD00915 Selector and for Automatic activation of KBF SC4 PAS 1 SCP KBF
start-up/shutdown program
xFSD00919 Group control for vapor compressor KBF SC4 PAS 1 SCP KBF
Overpressure protection due to safety
xFSD00922 KBF SC3 SSS SCP KBF
switch off of the electrical heaters
xFSD00923 Monitoring and automated operation JMT SC3 SAS SCP JMT
xFSD00924 Loss of Power supply function JMT SC3 SAS SCP JMT
Subgroup control 30GDA10 EC001
GDA, GDN;
xFSD00925 backwashing of the cartridge filter EYT PAS 1 SCP GD
GDP
30GDA10 AT010
Sub loop control 30GDA13 EE001
ECCN: N

emptying of drain buffer tank 30GDA13 GDA, GDN;


xFSD00926 EYT PAS 1 SCP GD
AT012 with waste water pump 30GDA13 GDP
AP001
Subgroup control 30GDA10 EC002
GDA, GDN;
AL: N

xFSD00928 regeneration of the cation exchanger EYT PAS 1 SCP GD


GDP
30GDA10 AT001
Subgroup control 30GDA10 EC002
xFSD00928 regeneration of the cation exchanger QUC EYT PAS 1 SCP GD
30GDA10 AT001
Subgroup control 30GDA10 EC003
GDA, GDN;
xFSD00929 regeneration of the mixed bed exchanger EYT PAS 1 SCP GD
GDP
30GDA10 AT002
Subgroup control 30GDA10 EC003
xFSD00929 regeneration of the mixed bed exchanger QUC EYT PAS 1 SCP GD
30GDA10 AT002
Subgroup control 30GDA10 EC004 step
GDA, GDN;
xFSD00930 still program for backwash of the cartridge EYT PAS 1 SCP GD
GDP
filter 30GDA10 AT010
Subgroup control 30GDA10 EC004 step
xFSD00930 still program for backwash of the cartridge QUC EYT PAS 1 SCP GD
filter 30GDA10 AT010
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A104 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Subgroup control 30GDA10 EC005 step
GDA, GDN;
xFSD00931 still program for regeneration of the cation EYT PAS 1 SCP GD
GDP
exchanger 30GDA10 AT001
Subgroup control 30GDA10 EC005 step
xFSD00931 still program for regeneration of the cation QUC EYT PAS 1 SCP GD
exchanger 30GDA10 AT001
Subgroup control 30GDA10 EC006 step
GDA, GDN;
xFSD00932 still program for regeneration of the mixed EYT PAS 1 SCP GD
GDP
bed exchanger 30GDA10 AT002
Subgroup control 30GDA10 EC006 step
xFSD00932 still program for regeneration of the mixed QUC EYT PAS 1 SCP GD
bed exchanger 30GDA10 AT002
GDA, GDN;
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

xFSD00934 Dilution water preheater 30GDP02 GH001 EYT SSS SCP GD


GDP
GDA, GDN;
xFSD00935 Frequency converter 30GDN01 GU001 EYT SSS SCP GD
GDP
KUA, KUB, SCP KUA-KUB-
xFSD00938 Control of the Boron measurement SC3 SSS
KUF KUF
Control of actuators within the sampling
modules of KUL (30KUL53/54/55/56
xFSD00940 KUL SC3 SSS SCP KUL
BZ001), heaters and valves for auxiliary
media supply
Monitoring of leakages of the reactor
SCP JYH10-20-
xFSD00941 coolant system to detect deviations from JYH10/20 SC3 SSS
80
normal operation
Hydrogen and containment atmosphere
xFSD00942 monitoring : Detection of hydrogen JMU SC3 SAS SCP JMU
release in fuel building with JMU20
Control of actuators within the sampling
modules of JMU (30JMU50/51BZ010),
xFSD00943 JMU SC3 SSS SCP JMU
heaters and valves for auxiliary media
supply
JAA
JAC
FAMOS data acquisition, measuring,
JEA
ECCN: N

xFSD00945 transferring, processing and storing the SC4 PAS 1 SCP JYL
JEB
data.
JEC
JEF, JEG
FAMOS data acquisition, measuring,
AL: N

JNA; JND;
xFSD00945 transferring, processing and storing the SC4 PAS 1 SCP JYL
JNG, JNK
data.
FAMOS data acquisition, measuring,
xFSD00945 transferring, processing and storing the JYL SC4 PAS 1 SCP JYL
data.
FAMOS data acquisition, measuring,
KBA, KBD,
xFSD00945 transferring, processing and storing the SC4 PAS 1 SCP JYL
JEW
data.
FAMOS data acquisition, measuring,
xFSD00945 transferring, processing and storing the LAB SC4 PAS 1 SCP JYL
data.
FAMOS data acquisition, measuring,
xFSD00945 transferring, processing and storing the LAR, LAS SC4 PAS 1 SCP JYL
data.
FAMOS data acquisition, measuring,
xFSD00945 transferring, processing and storing the LBA SC4 PAS 1 SCP JYL
data.
Normal operation of rainwater collection
xFSD00946 GUA EYT SSS SCP GUA
and drain system pump
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A105 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
xFSD00947 Hot Laundry Facilities SRP EYT SSS SCP SRP
xFSD00949 Water Leakage detection CYE SC4 SSS SCP CYE
xFSD00949 Water Leakage detection KTL SC4 SSS SCP CYE
Reactor Pressure Vessel Dome SCP JKS
xFSD00950 JKS EYT PAS 1
Temperature measurement RPVL/RPVDT
xFSD00951 JDH tanks filling JDH EYT SAS SCP JDH
xFSD00952 JDH Tanks mixing JDH EYT SAS SCP JDH
xFSD00953 Pumps protection orders JDH SC3 SAS SCP JDH
xFSD00954 JDH line-up Alarms (LCO related) JDH SC4 SAS SCP JDH
xFSD00955 Tank anti-dilution protection orders JDH SC3 SAS SCP JDH
Monitoring of the EBS tanks level and
xFSD00956 JDH SC4 SAS SCP JDH
temperature (LCO related)
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

JNA; JND;
xFSD00957 LHSI/RHR flowrate control in RHR mode SC3 SAS SCP JN
JNG, JNK
JNA; JND;
xFSD00958 RHR conditioning EYT SAS SCP JN
JNG, JNK
xFSD00958 RHR conditioning KAA, KAB EYT SAS SCP JN
JNA; JND;
xFSD00959 RHR deconditioning EYT SAS SCP JN
JNG, JNK
Coolant letdown to CVCS for low pressure JNA; JND;
xFSD00960 EYT SAS SCP JN
purification JNG, JNK
JNA; JND;
xFSD00961 IRWST mixing and cooling EYT SAS SCP JN
JNG, JNK
JNA; JND;
xFSD00962 Filling the refueling cavities EYT SAS SCP JN
JNG, JNK
JNA; JND;
xFSD00963 Filling and make-up of the accumulators EYT SAS SCP JN
JNG, JNK
Depressurization and venting of the JNA; JND;
xFSD00964 EYT SAS SCP JN
accumulators JNG, JNK
JNA; JND;
xFSD00965 Sampling of the accumulators EYT SAS SCP JN
JNG, JNK
JNA; JND;
xFSD00966 Sampling of the LHSI heat exchanger EYT SAS SCP JN
JNG, JNK
ECCN: N

Sampling of the RCS during RHR mode JNA; JND;


xFSD00967 EYT SAS SCP JN
(all RCPs off) JNG, JNK
JNA; JND;
xFSD00968 Periodic Tests on the JN system EYT SAS SCP JN
AL: N

JNG, JNK
Monitoring of the dead legs piping
xFSD00969 JDH SC4 SAS SCP JN
sections (LCO related)
Monitoring of the dead legs piping JNA; JND;
xFSD00969 SC4 SAS SCP JN
sections (LCO related) JNG, JNK
Monitoring of the IRWST suction lines JNA; JND;
xFSD00970 SC4 SAS SCP JN
guard pipes (LCO related) JNG, JNK
Monitoring of the IRWST level and JNA; JND;
xFSD00971 SC4 SAS SCP JN
temperature (LCO related) JNG, JNK
Monitoring of the accumulators pressure JNA; JND;
xFSD00972 SC4 SAS SCP JN
and level (LCO related) JNG, JNK
JNA; JND;
xFSD00973 Pumps protection orders SC3 SAS SCP JN
JNG, JNK
JNA; JND;
xFSD00975 JN line-up Alarms (LCO related) SC4 SAS SCP JN
JNG, JNK
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A106 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
JAA
JAC
Automatic N°3 Seal Supply Tank Level JEA
xFSD00976 EYT PAS 1 SCP JA-JE
Control JEB
JEC
JEF, JEG

JAA
JAC
Automatic N°2 Seal Leak-off Tank Level JEA
xFSD00977 EYT SAS SCP JA-JE
Control JEB
JEC
JEF, JEG

JAA
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

JAC
Automatic Closure of RCP Seal N°1 leak- JEA
xFSD00978 SC3 SAS SCP JA-JE
off Isolation Valves JEB
JEC
JEF, JEG
Automatic Closure of RCP Seal N°1 leak- JNA; JND;
xFSD00978 SC3 SAS SCP JA-JE
off Isolation Valves JNG, JNK
Automatic Closure of RCP Seal N°1 leak- KBA, KBD,
xFSD00978 SC3 SAS SCP JA-JE
off Isolation Valves JEW
JAA
JAC
Automatic Isolation of RCP Thermal
JEA
xFSD00979 Barrier for heterogenous boron dilution SC3 SAS SCP JA-JE
JEB
protection
JEC
JEF, JEG
Automatic Isolation of RCP Thermal
JNA; JND;
xFSD00979 Barrier for heterogenous boron dilution SC3 SAS SCP JA-JE
JNG, JNK
protection
JAA
JAC
Automatic Isolation of RCP Thermal JEA
ECCN: N

xFSD00980 SC3 SAS SCP JA-JE


Barrier for V-LOCA mitigation JEB
JEC
JEF, JEG
Automatic Isolation of RCP Thermal
AL: N

xFSD00980 KAA, KAB SC3 SAS SCP JA-JE


Barrier for V-LOCA mitigation
Automatic Isolation of RCP Thermal KBA, KBD,
xFSD00980 SC3 SAS SCP JA-JE
Barrier for V-LOCA mitigation JEW
JAA
JAC
RCP start Sequence and Logic via Sub JEA
xFSD00981 EYT SAS SCP JA-JE
Group Control JEB
JEC
JEF, JEG
RCP start Sequence and Logic via Sub KBA, KBD,
xFSD00981 EYT SAS SCP JA-JE
Group Control JEW
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A107 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
JAA
JAC
Normal Manual RCP Stop Sequence via JEA
xFSD00982 EYT SAS SCP JA-JE
Sub-Group Control JEB
JEC
JEF, JEG

JAA
JAC
RCP Auto Stop Logic via Sub Group JEA
xFSD00983 EYT SAS SCP JA-JE
Control JEB
JEC
JEF, JEG

JAA
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

JAC
RCP guide or thrust bearings excessive JEA
xFSD00984 SC3 SAS SCP JA-JE
warming JEB
JEC
JEF, JEG

JAA
JAC
JEA
xFSD00985 Oil pump failure during RCP start-up SC3 SAS SCP JA-JE
JEB
JEC
JEF, JEG

JAA
JAC
SSSS automatic closure in case of loss of JEA
xFSD00986 SC3 SAS SCP JA-JE
seal n°1 and seal n°2 JEB
JEC
JEF, JEG
SSSS automatic closure in case of loss of JNA; JND;
xFSD00986 SC3 SAS SCP JA-JE
seal n°1 and seal n°2 JNG, JNK
JAA
ECCN: N

JAC
JEA
xFSD00987 Locked rotor protection SC4 PAS 1 SCP JA-JE
JEB
JEC
JEF, JEG
AL: N

xFSD00987 Locked rotor protection JYG SC4 PAS 1 SCP JA-JE


JAA
JAC
Automatic RCP trip at low primary JEA
xFSD00988 SC3 SAS SCP JA-JE
pressure on low deltaP seal 1 JEB
JEC
JEF, JEG
Automatic RCP trip at low primary JNA; JND;
xFSD00988 SC3 SAS SCP JA-JE
pressure on low deltaP seal 1 JNG, JNK
JAA
JAC
JEA
xFSD00989 RCS depressurized water level monitoring EYT PAS 1 SCP JA-JE
JEB
JEC
JEF, JEG
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A108 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
JAA
JAC
RCS thermal stress monitoring during JEA
xFSD00990 EYT PAS 1 SCP JA-JE
normal operation JEB
JEC
JEF, JEG

JAA
JAC
Detection of Pressurizer Safety Relief JEA
xFSD00991 SC3 SAS SCP JA-JE
Valves and Dedicated Valves leakages JEB
JEC
JEF, JEG

JAA
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

JAC
Isolation of PZR degassing and venting JEA
xFSD00992 EYT SAS SCP JA-JE
lines JEB
JEC
JEF, JEG
Isolation of PZR degassing and venting JNA; JND;
xFSD00992 EYT SAS SCP JA-JE
lines JNG, JNK
JAA
JAC
Refilling IRWST by water from the EFW JEA
xFSD00993 SC4 PAS 1 SCP JA-JE
storage pools JEB
JEC
JEF, JEG

JAA
JAC
Protection of KPL and confining JEA
xFSD00994 SC3 SAS SCP JA-JE
radioactive products in the PRT JEB
JEC
JEF, JEG

JAA
ECCN: N

JAC
Protection of KTA and GHC connected JEA
xFSD00995 EYT PAS 1 SCP JA-JE
systems to PRT JEB
JEC
JEF, JEG
AL: N

JAA
JAC
JEA
xFSD00996 Slow depressurization of PRT EYT PAS 1 SCP JA-JE
JEB
JEC
JEF, JEG

JAA
JAC
PRT filling/draining and protection against JEA
xFSD00997 EYT PAS 1 SCP JA-JE
overfilling JEB
JEC
JEF, JEG
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A109 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
JAA
JAC
JEA
xFSD00998 PRT temperature monitoring EYT PAS 1 SCP JA-JE
JEB
JEC
JEF, JEG

JAA
JAC
Reactor Pressure Vessel JEA
xFSD01000 EYT SAS SCP JA-JE
venting/sweeping protection JEB
JEC
JEF, JEG
Reactor Pressure Vessel JNA; JND;
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

xFSD01000 EYT SAS SCP JA-JE


venting/sweeping protection JNG, JNK
JAA
JAC
Reactor Pressure Vessel leak detection JEA
xFSD01001 SC3 SAS SCP JA-JE
and isolation JEB
JEC
JEF, JEG

JAA
JAC
Reactor Pressure Vessel water level JEA
xFSD01002 SC4 PAS 1 SCP JA-JE
monitoring (during outage) JEB
JEC
JEF, JEG

JAA
JAC
Sampling of the Steam Generators JEA
xFSD01003 SC3 SAS SCP JA-JE
secondary side JEB
JEC
JEF, JEG
Sampling of the Steam Generators LCA90
xFSD01003 SC3 SAS SCP JA-JE
secondary side LCQ
ECCN: N

JAA
JAC
Monitoring of steam generator level during JEA
xFSD01004 EYT SAS SCP JA-JE
AL: N

filling (SG) operation JEB


JEC
JEF, JEG

JAA
JAC
JEA
xFSD01005 Monitoring of RCP seal 1 temperature SC3 SAS SCP JA-JE
JEB
JEC
JEF, JEG

JAA
JAC
JEA
xFSD01006 Monitoring of PRT pressure (LCO related) SC4 SAS SCP JA-JE
JEB
JEC
JEF, JEG
xFSD01007 FLIV fast closure test LAB EYT SAS SCP LAB NI
xFSD01008 FLIV partial slow closure test LAB EYT SAS SCP LAB NI
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A110 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Monitoring of nitrogen pressure on FLIV
xFSD01009 LAB SC4 SAS SCP LAB NI
(LCO related)
xFSD01010 Measurements indication on PICS LAB SC4 PAS 1 SCP LAB NI
Periodic testing of MSIV (partial closure
xFSD01011 LBA EYT SAS SCP LBA NI
test)
Periodic testing of MSIV (fast closure test)
xFSD01012 LBA EYT SAS SCP LBA NI
, together with testing of drain valves
xFSD01013 Periodic testing of MSRIV LBA EYT SAS SCP LBA NI
xFSD01014 Periodic testing of MSRIV pilot valves LBA EYT SAS SCP LBA NI
xFSD01015 Periodic testing of MSRV LBA EYT SAS SCP LBA NI
xFSD01016 Measurements indication on PICS LBA EYT PAS 1 SCP LBA NI
Monitoring of nitrogen pressure on MSIV
xFSD01017 LBA SC4 SAS SCP LBA NI
(LCO related)
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

xFSD01018 Fire compartments isolation CYE SC4 SSS SCP CYE


xFSD01018 Fire compartments isolation KLA SC4 SSS SCP CYE
xFSD01018 Fire compartments isolation KLB SC4 SSS SCP CYE
xFSD01018 Fire compartments isolation KLC SC4 SSS SCP CYE
xFSD01018 Fire compartments isolation KLD SC4 SSS SCP CYE
xFSD01018 Fire compartments isolation KLE SC4 SSS SCP CYE
xFSD01018 Fire compartments isolation KLF SC4 SSS SCP CYE
xFSD01018 Fire compartments isolation KLL SC4 SSS SCP CYE
xFSD01018 Fire compartments isolation SAB SC4 SSS SCP CYE
xFSD01018 Fire compartments isolation SAC SC4 SSS SCP CYE
xFSD01018 Fire compartments isolation SAC80 SC4 SSS SCP CYE
SAD
xFSD01018 Fire compartments isolation SC4 SSS SCP CYE
SAL
xFSD01018 Fire compartments isolation SAM4 SC4 SSS SCP CYE
xFSD01018 Fire compartments isolation SAQ SC4 SSS SCP CYE
xFSD01018 Fire compartments isolation SAZ SC4 SSS SCP CYE
Manual actuation of the spray deluge
systems for the oil room and oil pipe duct
by pressing a push button installed in the
xFSD01019 CYE SC4 SSS SCP SG
ECCN: N

control room or next to the room


entrances, or manually at the relevant
valve station.
Manual actuation of the spray deluge
systems for the oil room and oil pipe duct
AL: N

by pressing a push button installed in the


xFSD01019 SGC SC4 SSS SCP SG
control room or next to the room
entrances, or manually at the relevant
valve station.
Manual actuation of the spray deluge
systems for the oil room and oil pipe duct
by pressing a push button installed in the
xFSD01019 SGC SC4 SSS SCP SG
control room or next to the room
entrances, or manually at the relevant
valve station.
Spraying : Automatic actuation of the
spray deluge systems for the oil room and
xFSD01020 CYE SC4 SSS SCP SG
oil pipe duct by the local control panel
30SGY10 GH001
Spraying : Automatic actuation of the
spray deluge systems for the oil room and
xFSD01020 SGC SC4 SSS SCP SG
oil pipe duct by the local control panel
30SGY10 GH001
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A111 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Spraying : Automatic actuation of the
spray deluge systems for the oil room and
xFSD01020 SGC SC4 SSS SCP SG
oil pipe duct by the local control panel
30SGY10 GH001
Spraying: Indication of operation of spray
xFSD01021 CYE SC4 SSS SCP SG
deluge system
Spraying: Indication of operation of spray
xFSD01021 SGC SC4 SSS SCP SG
deluge system
Spraying: Position monitoring of gate
xFSD01022 valves: monitoring valves with regards to CYE SC4 SSS SCP SG
water supply in case of fire
Spraying: Position monitoring of gate
xFSD01022 valves: monitoring valves with regards to SGC SC4 SSS SCP SG
water supply in case of fire
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

xFSD01023 Monitoring of SGE system TI CYE SC4 SSS SSS Siemens


xFSD01023 Monitoring of SGE system TI SGE SC4 SSS SSS Siemens
Monitoring of the incore power density
xFSD01024 JKQ SC4 SSS SCP JKQ
distribution -Aeroballsystem
xFSD01025 Drive rod position indication JDA SC4 SSS SCP JDA/BU NI
xFSD01025 Drive rod position indication JDA1 SC4 SSS SCP JDA/BU NI
Display system status in Main Control KPF
xFSD01029 SC4 SSS SCP KPF-KPK
Room KPK
KPF
xFSD01030 Waste water collection SC4 SSS SCP KPF-KPK
KPK
Chemical treatment as well as chemical KPF
xFSD01031 SC4 SSS SCP KPF-KPK
precipitation and biological treatment KPK
Processing by evaporation and KPF
xFSD01032 SC4 SSS SCP KPF-KPK
processing by centrifugation KPK
KPF
xFSD01033 Discharge of cleaned water SC3 SSS SCP KPF-KPK
KPK
Automatic control mechanism (protection KPF
xFSD01034 SC4 SSS SCP KPF-KPK
of components) KPK
Monitoring and control room temperature
xFSD01035 SAQ SC3 SAS SCP SAQ
in the pump chambers
ECCN: N

Start of the fans of the 30SAQ circulation


xFSD01036 SAQ SC3 SAS SCP SAQ
cooling units
xFSD01037 Supply and Exhaust Air system SAQ EYT SSS SCP SAQ
AL: N

Monitoring for maintain acceptable


ambient conditions in the Essential
xFSD01038 SAQ EYT SSS SCP SAQ
Service Water Pump Building installed
outside AHU
Monitoring for maintain acceptable
ambient conditions in the Essential
xFSD01039 SAQ EYT SSS SCP SAQ
Service Water Pump Building – installed
in AHU
Ensure an air exchange in ducts and
xFSD01040 SAZ EYT SSS SCP SAZ
channels
Measurements for control and protection
xFSD01041 SAZ EYT SSS SCP SAZ
of supply air heaters
xFSD01042 Display fault signal in Main control Room SAZ EYT SSS SCP SAZ
Pressure control of controlled area
xFSD01044 exhaust air in relation to atmosphere KLD EYT PAS 1 SCP KLD
(compensating of filter loading).
xFSD01045 Maintain the room ambient conditions KLD EYT PAS 1 SCP KLD
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A112 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
xFSD01045 Maintain the room ambient conditions SBA EYT PAS 1 SCP KLD
Pressure control of the controlled area in
xFSD01046 relation to KLD EYT PAS 1 SCP KLD
atmosphere.
Control of electrical air heaters for room
xFSD01048 KLD EYT SSS SCP KLD
heating
High-Pressure pumps Interlock by
xFSD01049 FKK SC4 SSS SCP FKK
Decontamination Booth door
Monitoring: missing underpressure in
xFSD01050 FKK SC4 SSS SCP FKK
decontamination booth/box
Level Alarm and control of
xFSD01051 Decontamination Waste Water Collection FKK SC4 SSS SCP FKK
Tank
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

Automatic/Manual Discharge of
xFSD01052 Decontamination Waste Water Collection FKK SC4 SSS SCP FKK
tank
Decontamination Waste Water Discharge
xFSD01053 FKK SC4 SSS SCP FKK
Pump 30FKK02 AP 001 dry-run protection
Position control of the roof hatch of the
xFSD01055 FKK EYT SSS SCP FKK
Decontamination Booth
Display system status in Main Control
xFSD01056 FKK SC4 SSS SCP FKK
Room
Heater Control of Immersion and
xFSD01057 FKK EYT SSS SCP FKK
Ultrasonic Bath
Level control for Buffer Tank of High
xFSD01058 Pressure Pumps 30FKK05AP 001/ FKK EYT SSS SCP FKK
30FKK60 AP001
xFSD01059 Receiving and preparation part KPC SC4 SSS SCP KPC
Treatment part (except temperature
xFSD01060 KPC EYT SSS SCP KPC
protections)
xFSD01061 Treatment part (temperature protections) KPC SC4 SSS SCP KPC
xFSD01062 Drum preparation and transfer part KPC EYT SSS SCP KPC
Display system status in Main Control
xFSD01063 KPC SC4 SSS SCP KPC
Room
Control and protection of the sorting box
xFSD01064 KPA EYT SSS SCP KPA/KPE
ECCN: N

and in-drum compactor


Protection of Decontamination Pump
xFSD01065 FKE SC4 SSS SCP FKE
FKE10AP001
Protection of Decontamination Solution
xFSD01066 FKE SC4 SSS SCP FKE
Heater FKE12AH001
AL: N

Control level in Decontamination Tanks


xFSD01067 (FKE14/15 BB001) respective dedicated FKE SC4 SSS SCP FKE
overflow pipes
Protection of Decontamination Filter
xFSD01068 FKE SC4 SSS SCP FKE
FKE13AT001
Venting of the connection line to
xFSD01069 FKE SC4 SSS SCP FKE
Decontamination Filter 30FKE13 AT001
Control principles(Heating up
xFSD01070 decontamination solution/controlling FKE SC4 SSS SCP FKE
speed of decontamination pump)
Manual I&C functions (Switch on/off
xFSD01071 FKE10AP001 and FKE12AH001; Control FKE SC4 SSS SCP FKE
of FKE10AA005)
Display system status in Main Control
xFSD01072 FKE SC4 SSS SCP FKE
Room
LCA90 SCP LCQ-
xFSD01073 SGBS Flash Tank Overflow Protection SC4 PAS 1
LCQ LCA90
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A113 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
SGBS Flash Tank Overpressure LCA90 SCP LCQ-
xFSD01074 SC4 PAS 1
Protection LCQ LCA90
LCA90 SCP LCQ-
xFSD01075 Pressure control of Blowdown Flash Tank SC4 PAS 1
LCQ LCA90
Interlocks for the Safeguard Building LCA90 SCP LCQ-
xFSD01076 SC4 PAS 1
Isolation Valves in Main Condensate Line LCQ LCA90
Sub loop control 30LCA90 EE001
LCA90 SCP LCQ-
xFSD01077 MCOND Temperature Limitation SC4 PAS 1
LCQ LCA90
downstream blowdown cooler
LCA90 SCP LCQ-
xFSD01078 Sampling line isolation valves SC3 SAS
LCQ LCA90
JAA
JAC
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

JEA SCP LCQ-


xFSD01079 Transfer Line valves closing signal SC3 SAS
JEB LCA90
JEC
JEF, JEG
LCA90 SCP LCQ-
xFSD01079 Transfer Line valves closing signal SC3 SAS
LCQ LCA90
LCA90 SCP LCQ-
xFSD01080 Main Condensate Leak Protection SC4 PAS 1
LCQ LCA90
Interlocks for the Containment Isolation LCA90 SCP LCQ-
xFSD01081 SC4 PAS 1
Valves in Main Condensate Line LCQ LCA90
Interlocks for the Containment Isolation
LCA90 SCP LCQ-
xFSD01082 Valves in Condensate Line to SC4 PAS 1
LCQ LCA90
Demineralizing System
LCA90 SCP LCQ-
xFSD01083 Interlocks for the Flash Tank Drain Valve SC4 PAS 1
LCQ LCA90
Interlocks for the Flash Tank Level Control GDA, GDN; SCP LCQ-
xFSD01084 SC4 PAS 1
Valve GDP LCA90
Interlocks for the Flash Tank Level Control LCA90 SCP LCQ-
xFSD01084 SC4 PAS 1
Valve LCQ LCA90
Interlocks for the SG Blowdown Adjusting GDA, GDN; SCP LCQ-
xFSD01085 SC4 PAS 1
Valves GDP LCA90
ECCN: N

Interlocks for the SG Blowdown Adjusting LCA90 SCP LCQ-


xFSD01085 SC4 PAS 1
Valves LCQ LCA90
JAA
AL: N

JAC
JEA SCP LCQ-
xFSD01086 Interlocks for the SG Isolation Valves SC4 PAS 1
JEB LCA90
JEC
JEF, JEG
LCA90 SCP LCQ-
xFSD01086 Interlocks for the SG Isolation Valves SC4 PAS 1
LCQ LCA90
LCA90 SCP LCQ-
xFSD01087 Level control of Blowdown Flash Tank SC4 PAS 1
LCQ LCA90
Protection for Safeguard Building in case
LCA90 SCP LCQ-
xFSD01088 of a break downstream the outside SC4 PAS 1
LCQ LCA90
containment isolation valve
Sub loop control 30LCQ10 / 20 / 30 / 40
LCA90 SCP LCQ-
xFSD01089 EE001Blowdown flow limitation to flash SC4 PAS 1
LCQ LCA90
tank
Sub loop control 30LCQ51 EE001
LCA90 SCP LCQ-
xFSD01090 Blowdown flow limitation to turbine SC4 PAS 1
LCQ LCA90
condenser
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A114 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Temperature Protection for GDA, GDN; SCP LCQ-
xFSD01091 SC4 PAS 1
Demineralizing System GDP LCA90
Temperature Protection for LCA90 SCP LCQ-
xFSD01091 SC4 PAS 1
Demineralizing System LCQ LCA90
Monitoring and adjustment of pressure;
xFSD01092 PROTECTION OFF of the respective seal GHW EYT PAS 2 SCP GHW NI
water consumers
Monitoring of the GHW pumps;
xFSD01093 GHW EYT PAS 1 SCP GHW NI
PROTECTION OFF of the solenoid valves
Monitoring of the seal water supply of the
xFSD01094 GHW EYT PAS 1 SCP GHW NI
KBA pumps
Seal water pumps 30GHW11/12 AP001
xFSD01095 GHW EYT PAS 2 SCP GHW NI
control
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

Seal water solenoid valves


xFSD01096 GHW EYT PAS 1 SCP GHW NI
30GHW41/44/45 AA002 control
Monitoring of the seal water supply of the
xFSD01097 GHW SC4 PAS 1 SCP GHW NI
JMQ pumps
Component protection function of the
xFSD01098 PEB/PEH SC3 SAS SCP PE
ESWS pumps
xFSD01100 Monitoring of trains 30PEB50/80 PEB/PEH SC4 SAS SCP PE
xFSD01102 HP Cooler Outlet Temperature Control KAA, KAB SC3 RCSL SCP KAA-KAB
KBA, KBD,
xFSD01102 HP Cooler Outlet Temperature Control SC3 RCSL SCP KAA-KAB
JEW
KBA, KBD, SCP KBA-KBD-
xFSD01103 Operational Interlocking CVCS SC3 RCSL
JEW JEW
Operational function initiated on demand
FAK SCP KBA-KBD-
xFSD01104 of the PS function "Anti-Dilution" and on SC3 SAS
FAL JEW
demand of "VCT Level < MIN5
Operational function initiated on demand
SCP KBA-KBD-
xFSD01104 of the PS function "Anti-Dilution" and on JMQ SC3 SAS
JEW
demand of "VCT Level < MIN5
Operational function initiated on demand
JNA; JND; SCP KBA-KBD-
xFSD01104 of the PS function "Anti-Dilution" and on SC3 SAS
JNG, JNK JEW
demand of "VCT Level < MIN5
ECCN: N

Operational function initiated on demand


KBA, KBD, SCP KBA-KBD-
xFSD01104 of the PS function "Anti-Dilution" and on SC3 SAS
JEW JEW
demand of "VCT Level < MIN5
AL: N

Seal water leak-off (inside fuel building, JNA; JND; SCP KBA-KBD-
xFSD01105 SC3 SAS
auxiliary building) JNG, JNK JEW
Seal water leak-off (inside fuel building, KBA, KBD, SCP KBA-KBD-
xFSD01105 SC3 SAS
auxiliary building) JEW JEW
Control of the pressure in the JEW seal KBA, KBD, SCP KBA-KBD-
xFSD01106 SC3 SAS
water leak off line JEW JEW
Seal water injection (inside fuel building, KBA, KBD, SCP KBA-KBD-
xFSD01107 SC3 SAS
auxiliary building) JEW JEW
SLC Seal water leak-off flow rate to KBA, KBD, SCP KBA-KBD-
xFSD01108 SC3 SAS
VCT/KTA (JEW50 EE001) JEW JEW
Seal Water Leak-off (component KBA, KBD, SCP KBA-KBD-
xFSD01109 SC3 SAS
protection) JEW JEW
KBA, KBD, SCP KBA-KBD-
xFSD01110 Letdown line pressure control SC3 SAS
JEW JEW
Position control of the adjusting valve
JNA; JND; SCP KBA-KBD-
xFSD01111 KBA34 AA101 in the charging line (KBA34 SC3 SAS
JNG, JNK JEW
DG001)
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A115 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Position control of the adjusting valve
KBA, KBD, SCP KBA-KBD-
xFSD01111 KBA34 AA101 in the charging line (KBA34 SC3 SAS
JEW JEW
DG001)
KBA, KBD, SCP KBA-KBD-
xFSD01112 Shiftleader release KBA10 EE001 SC3 SAS
JEW JEW
KBA, KBD, SCP KBA-KBD-
xFSD01113 SLC Protective Open KBA20 AA104 SC3 SAS
JEW JEW
SLC Aggregate switch-over HP charging KBA, KBD, SCP KBA-KBD-
xFSD01114 SC3 SAS
pumps JEW JEW
SLC Automatic start-up of a second HP KBA, KBD, SCP KBA-KBD-
xFSD01115 SC3 SAS
charging pump due to selective criteria JEW JEW
Containment Isolation Letdown Line KBA, KBD, SCP KBA-KBD-
xFSD01117 SC3 SAS
interlock JEW JEW
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

KBA, KBD, SCP KBA-KBD-


xFSD01118 Letdown line direction to KTA/JNK SC3 SAS
JEW JEW
KBA, KBD, SCP KBA-KBD-
xFSD01120 Isolation of Low Pressure Reducing Train SC3 SAS
JEW JEW
KBA, KBD, SCP KBA-KBD-
xFSD01121 Bypass and Isolation of Auxiliary Systems SC3 SAS
JEW JEW
H2 supply and Gas Separator Level KBA, KBD, SCP KBA-KBD-
xFSD01122 SC3 SAS
Control JEW JEW
KBA, KBD, SCP KBA-KBD-
xFSD01123 Volume Control Tank Level Control SC3 SAS
JEW JEW
KBA, KBD, SCP KBA-KBD-
xFSD01124 Volume Control Tank Pressure Control SC3 SAS
JEW JEW
HP-Charging Pumps auxiliary systems KBA, KBD, SCP KBA-KBD-
xFSD01125 SC3 SAS
and component protection JEW JEW
Isolation of Charging Line for Component KBA, KBD, SCP KBA-KBD-
xFSD01126 SC3 SAS
Protection JEW JEW
Isolation valves to nuclear sampling KBA, KBD, SCP KUA-KUB-
xFSD01127 SC3 SAS
system JEW KUF
Black Box / local control station / MCR
KBA, KBD, SCP KBA-KBD-
xFSD01128 indication interface and controls of the EYT PAS 1
JEW JEW
chemical Control System
ECCN: N

Black Box for operating of the chemical KBA, KBD, SCP KBA-KBD-
xFSD01129 EYT SSS
control system JEW JEW
Detection and localization of loose parts in
xFSD01136 RCS to prevent damages of primary JYF SC4 SSS SCP JYF
AL: N

components
Valve Monitoring: Providing sufficient
information for conditioning based
xFSD01137 maintenance and detection of failure of JYV SC4 SSS SCP JYV
electrical actuated valves and their
actuators (MOV and SOV)
Detection of changes in the vibration
xFSD01138 JYE SC4 SSS SCP JYE
behavior of rotating machinery.
Measurement of component vibrations for
early detection of mechanical changes:
xFSD01139 JYG SC4 SSS SCP JYG
Vibration Monitoring of RPV internals and
primary circuit components
Measurement of component vibrations for
xFSD01140 early detection of mechanical changes: JYG SC4 SSS SCP JYG
Vibration Monitoring of RCPs
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A116 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Measurement of component vibrations for
xFSD01141 early detection of mechanical changes: JYG SC4 SSS SCP JYG
Monitoring of RCP’s shaft low speed
Monitoring of the vibration on the main
xFSD01142 JYM SC4 SSS SCP JYM
steam and feedwater lines
Measurement of component vibrations
xFSD01143 JYM SC4 SSS SCP JYM
detecting critical load
Providing information to the operator
xFSD01146 about the seismic history on site for CPE SC4 SSS SCP CPE
normal, upset and accident conditions
xFSD01147 Detection of toxic substances and CO CYQ SC4 SSS SCP CYQ
Monitor the area of the control room and
remote shutdown station to protect the
xFSD01148 CYQ SC4 SSS SCP CYQ
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

operators against the possible risk of


ingress of toxic gases
Containment Heat Removal pump
xFSD01259 JMQ SC3 SAS SCP JMQ
protection
Containment Heat Removal pump JNA; JND;
xFSD01259 SC3 SAS SCP JMQ
protection JNG, JNK
Containment Heat Removal pump
xFSD01259 KAA, KAB SC3 SAS SCP JMQ
protection
Continuous monitoring of the core power
distributions and core follow (burnup)
CNM
xFSD01260 calculations with live input data from the SC4 SSS SCP JKQ
JKQ
plant obtained via the XU with high
temporal resolution
Evaluation of the AMS activation signals
by adapting the core wide flux map to the
measured activation values and CNM
xFSD01261 SC4 SSS SCP JKQ
calculation of all dependent values like JKQ
power distributions, hot channel factors,
DNB ratios, etc. from this flux distribution.
Graphical display of calculation results, CNM
xFSD01262 SC4 SSS SCP JKQ
calculated margins and process data JKQ
Reactivity and operation strategy
CNM
xFSD01263 calculations based on current core SC4 SSS SCP JKQ
JKQ
ECCN: N

conditions
Monitoring of pressure, temperature and
xFSD01264 KTA-KTE SC3 SAS SCP KT10/11
level in the Reator coolant drain tank
Sub loop control switch of hydrogen
xFSD01265 JMT SC3 SAS SCP JMT
AL: N

mixing dampers
Component Protection KBC: KBC20/30 JNA; JND;
xFSD01266 SC3 SAS SCP KBC
Part JNG, JNK
Component Protection KBC: KBC20/30
xFSD01266 KBC SC3 SAS SCP KBC
Part
Monitoring of the position of the safety
xFSD01267 KBB SC3 SAS SCP KBB
valves 30KBB10-16 AA191
xFSD01268 Resin waste tank level measurement KBE SC4 SSS SCP KBE
JNA; JND; SCP KBA-KBD-
xFSD01270 Automatic Functions in Charging line SC3 SAS
JNG, JNK JEW
KBA, KBD, SCP KBA-KBD-
xFSD01270 Automatic Functions in Charging line SC3 SAS
JEW JEW
xFSD01271 Electrical interlocks BB SC4 PAS 1 SCP BB-BD
SCP
BFJ
xFSD01272 Electrical interlocks SC4 PAS 1 BF/BH/BK/BL/B
BFK
M/BN/BR
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A117 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
SCP
xFSD01272 Electrical interlocks BF, BH, BK SC4 PAS 1 BF/BH/BK/BL/B
M/BN/BR
SCP
BM, BN, BL,
xFSD01273 Electrical interlocks SC4 SAS BF/BH/BK/BL/B
BR
M/BN/BR
xFSD01274 Sub loop control for resin flush pump GHW SC4 PAS 1 SCP KBE
xFSD01274 Sub loop control for resin flush pump KBE SC4 PAS 1 SCP KBE
xFSD01275 Sub loop control for overflow tank KBE SC4 PAS 1 SCP KBE
Interlocking for boron recycle purification
xFSD01276 KBE SC4 PAS 1 SCP KBF
30KBE20
Interlocking for boron recycle purification
xFSD01276 KBE SC4 PAS 1 SCP KBF
30KBE20
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

xFSD01277 Interlocking for resin flush pump KBE SC4 PAS 1 SCP KBE
xFSD01277 Interlocking for resin flush pump KBE SC4 PAS 1 SCP KBE
Interlocking for KLE and KPL systems
xFSD01278 KBE SC4 PAS 1 SCP KBE
with 30KBE17AA500
Interlocking for KLE and KPL systems
xFSD01278 KBE SC4 PAS 1 SCP KBE
with 30KBE17AA500
Degasifier heater output control
xFSD01279 KBG SC4 PAS 1 SCP KBG
(30KBG10 DE001)
Degasifier column level control (30KBG10
xFSD01281 KBG SC4 PAS 1 SCP KBG
DL001)
Degasifier column pressure control
xFSD01282 KBG SC4 PAS 1 SCP KBG
(30KBG10 DP003)
Condenser temperature control (30KBG10
xFSD01283 KBG SC4 PAS 1 SCP KBG
DT004)
Sub loop control black box electrical
xFSD01285 KBG SC4 PAS 1 SCP KBG
heater (30KBG10 EE001)
xFSD01287 Interlocking for Pumps and compressors KBG SC4 PAS 1 SCP KBG
xFSD01288 Interlocking for Valves KBG SC4 PAS 1 SCP KBG
xFSD01289 Interlocking for Sub group control BF, BH, BK SC4 PAS 1 SCP KBG
xFSD01289 Interlocking for Sub group control KBG SC4 PAS 1 SCP KBG
Interlocking for degasifier heater / Black
ECCN: N

xFSD01290 KBG SC4 PAS 1 SCP KBG


box
Sub loop control sealing liquid tank
xFSD01291 KBG SC4 PAS 1 SCP KBG
(30KBG30 EE001)
Start-up and shutdown programs:
AL: N

xFSD01292 30KBF10 EC001 for operating mode 1: KBF SC4 PAS 1 SCP KBF
Evaporation
Start-up and shutdown programs:
xFSD01293 30KBF10 EC003 for operating mode 4: KBF SC4 PAS 1 SCP KBF
Degasification of replenishment water
Closed loop control for : Boric acid column
xFSD01294 KBF SC4 PAS 1 SCP KBF
level control (30KBF20 DL901)
Closed loop control for : Condensate tank
xFSD01295 KBF SC4 PAS 1 SCP KBF
level control (30KBF20 DL903)
Closed loop control for : Condensate
xFSD01296 KBF SC4 PAS 1 SCP KBF
collector level control (30KBF20 DL905)
Closed loop control for : Excess vapor
xFSD01297 KBF SC4 PAS 1 SCP KBF
control (30KBF20 DP002)
Closed loop control for : Boric acid
xFSD01298 KBF SC4 PAS 1 SCP KBF
concentration control (30KBF20 DQ901)
Closed loop control for : Condensate
xFSD01299 KBF SC4 PAS 1 SCP KBF
cooler temperature control (30KBF20
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A118 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
DT011)

Closed loop control for : Bypass for vapor


xFSD01300 KBF SC4 PAS 1 SCP KBF
compressor 1 (30KBF31 DP001)
Closed loop control for : Bypass for vapor
xFSD01301 KBF SC4 PAS 1 SCP KBF
compressor 2 (30KBF32 DP001)
Closed loop control for : Bypass for vapor
xFSD01302 KBF SC4 PAS 1 SCP KBF
compressor 3 (30KBF33 DP001)
Sub loop control for Operating mode
xFSD01303 KBF SC4 PAS 1 SCP KBF
selector (30KBF00 EE001)
Start-up and shutdown programs:
30KBF10 EC002 for operating modes 2 &
xFSD01304 KBF SC4 PAS 1 SCP KBF
3: Evaporation & degasification with
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

recycling or release.
Start-up and shutdown programs:
30KBF10 EC002 for operating modes 2 & KPF
xFSD01304 SC4 PAS 1 SCP KBF
3: Evaporation & degasification with KPK
recycling or release.
Sub Loop Controls: Automatic activation
xFSD01305 of start-up/shutdown program (30KBF00 KBF SC4 PAS 1 SCP KBF
EE002)
Sub Loop Controls: Automatic activation
KPF
xFSD01305 of start-up/shutdown program (30KBF00 SC4 PAS 1 SCP KBF
KPK
EE002)
Sub Loop Controls: Aggregate change-
xFSD01306 over evaporator feed pumps (30KBF10 KBF SC4 PAS 1 SCP KBF
EE001)
Sub Loop Controls: Aggregate change-
xFSD01307 KBF SC4 PAS 1 SCP KBF
over circulating pumps (30KBF20 EE001)
Sub Loop Controls: Aggregate change-
xFSD01308 over boric acid metering pumps (30KBF20 KBF SC4 PAS 1 SCP KBF
EE002)
Sub Loop Controls: Aggregate change-
xFSD01309 over boric acid delivery pumps (30KBF20 KBF SC4 PAS 1 SCP KBF
EE003)
ECCN: N

Sub Loop Controls: Aggregate change-


xFSD01310 over condensate pumps (30KBF20 KBF SC4 PAS 1 SCP KBF
EE004)
Sub Loop Controls: Sub loop control
xFSD01311 KBF SC4 PAS 1 SCP KBF
condensate pumps (30KBF20 EE005)
AL: N

Sub Loop Controls: Selector level control


xFSD01312 valves of condensate collector (30KBF20 KBF SC4 PAS 1 SCP KBF
EE006)
Sub Loop Controls: Selector boric acid
xFSD01313 concentration control valves (30KBF20 KBF SC4 PAS 1 SCP KBF
EE007)
Sub Loop Controls: Selector level control
xFSD01314 valves of condensate tank (30KBF20 KBF SC4 PAS 1 SCP KBF
EE008)
Sub Loop Controls: Selector excess
xFSD01315 KBF SC4 PAS 1 SCP KBF
vapor control valves (30KBF20 EE009)
Sub Loop Controls: Selector level control
xFSD01316 valves of boric acid column (30KBF20 KBF SC4 PAS 1 SCP KBF
EE010)
Sub Loop Controls: Sub loop control
xFSD01317 black box electrical preheater (30KBF20 KBF SC4 PAS 1 SCP KBF
EE011)
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A119 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Sub Loop Controls: Sub loop control seal
xFSD01318 KBF SC4 PAS 1 SCP KBF
water tank (30KBF35 EE001)
Sub Loop Controls: Aggregate change-
xFSD01319 KBF SC4 PAS 1 SCP KBF
over seal water pumps (30KBF35 EE002)
Sub Loop Controls: Sub loop control
xFSD01320 black box degasifier heater (30KBF40 KBF SC4 PAS 1 SCP KBF
EE001)
Sub Loop Controls: Sub loop control
xFSD01321 black box make-up water preheater KBF SC4 PAS 1 SCP KBF
(30KBF40 EE002)
Sub Loop Controls: Reset counter inlet to
xFSD01322 KBF SC4 PAS 1 SCP KBF
degasifier column (30KBF40 EE003)
xFSD01323 Interlocking for Pumps KBF SC4 PAS 1 SCP KBF
xFSD01324 Interlocking for vapor Compressors KBF SC4 PAS 1 SCP KBF
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

xFSD01325 Interlocking for valves KBF SC4 PAS 1 SCP KBF


xFSD01326 Interlocking for black boxes KBF SC4 PAS 1 SCP KBF
Interlocking for sub group control
xFSD01327 BF, BH, BK SC4 PAS 1 SCP KBF
30KBF10 EC001
Interlocking for sub group control
xFSD01327 KBF SC4 PAS 1 SCP KBF
30KBF10 EC001
Interlocking for sub group control
xFSD01328 KBF SC4 PAS 1 SCP KBF
30KBF10 EC002
Interlocking for sub group control
xFSD01329 BF, BH, BK SC4 PAS 1 SCP KBF
30KBF10 EC003
Interlocking for sub group control
xFSD01329 KBF SC4 PAS 1 SCP KBF
30KBF10 EC003
I&C performed by BBXs : 30KBF20
xFSD01330 GH001 (black box for electrical preheater KBF SC4 SSS SCP KBF
30KBF20 AH001)
I&C performed by BBXs : 30KBF40
xFSD01331 GH001 (black box for degasifier heater KBF SC4 SSS SCP KBF
30KBF40 AH001)
I&C performed by BBXs : 30KBF40
xFSD01332 GH002 (black box for make-up water KBF SC4 SSS SCP KBF
preheater 30KBF40 AH002)
Automatic control mechanism (protection
xFSD01333 KPC EYT SSS SCP KPC
ECCN: N

of components)
xFSD01334 Manual Function: Mixed bed filter filling KBE SC4 PAS 1 SCP KBE
xFSD01335 Manual Function: Resin flushing KBE SC4 PAS 1 SCP KBE
xFSD01335 Manual Function: Resin flushing KBE SC4 PAS 1 SCP KBE
AL: N

Monitoring of the motor temperatures of


xFSD01336 larger engines from the digital process JYE SC4 SSS SCP JYE
control system (TXP).
Iodine filtration in case of iodine detection
xFSD01337 KLE SC4 PAS 1 SCP KLE
by the 30KLK system
Display Process/Electrical fault in Main
xFSD01338 SAQ EYT SSS SCP SAQ
Control Room
xFSD01340 Automatic Discharge via fast degas valves SC4 TGI TGI (Siemens)
xFSD01341 Activation of DC seal oil pump SC4 TGI TGI (Siemens)
xFSD01342 Activation of Fire protection valve SC4 TGI TGI (Siemens)
xFSD01343 Closing of hydrogen central supply SC4 TGI TGI (Siemens)
Closing of solenoid valves, fire protection
xFSD01344 SC4 TGI TGI (Siemens)
valve.
xFSD01345 Manual activation of Discharge SC4 TGI TGI (Siemens)
xFSD01346 Monitoring of Space heating system SBA SBA EYT SSS SSS Siemens
xFSD01349 start-up sequence LDB EYT SSS SSS Siemens
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A120 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
xFSD01350 stop filtration sequence LDB EYT SSS SSS Siemens
xFSD01351 drain sequence LDB EYT SSS SSS Siemens
xFSD01352 backwash sequence LDB EYT SSS SSS Siemens
xFSD01353 backwash receiving tank sequence LDB EYT SSS SSS Siemens
xFSD01354 Synchronization control LDB EYT SSS SSS Siemens
Backwash receiving tank overflow
xFSD01355 LDB EYT SSS SSS Siemens
protection
xFSD01356 Waste water pumps protection LDB EYT SSS SSS Siemens
Closed loop control for : Degasifier
xFSD01357 condenser temperature control (30KBF40 KBF SC4 PAS 1 SCP KBF
DT001)
Closed loop control for : Make-up water
xFSD01358 KBF SC4 PAS 1 SCP KBF
temperature control (30KBF40 DT905)
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

Leakage Detection in the Main Steam SCP JYH10-20-


xFSD01359 JYH10/20 SC3 SAS
Valve Rooms 80
FAK
xFSD01360 Fuel pool cooling system operation SC3 SAS SCP FAK/FAL
FAL
Closed loop control for : Degasifier
xFSD01361 column temperature control (30KBF40 KBF SC4 PAS 1 SCP KBF
DE001)
Closed loop control for : Degasifier level
xFSD01362 KBF SC4 PAS 1 SCP KBF
control (30KBF40 DL901)
Pressure control of the auxiliary boiler
when 30QHA11/12 CP002 XV03> QHA
>15,0bar(g) (inclu ALARM pressure HIGH QHE
xFSD01363 EYT SSS SSS Siemens
30QHA11/12 CP002 XV03> >15,0bar(g) QHG
and WARNING pressure HIGH QHX
30QHA11/12 CP001 XH01> >14,0bar(g))
xFSD01364 Component Protection KBC: KBC10 Part KBC SC4 PAS 1 SCP KBC
MAA
xFSD01365 Absolute bearing pedestal vibration SC4 TGI TGI (Siemens)
MAC
xFSD01365 Absolute bearing pedestal vibration MAD SC4 TGI TGI (Siemens)
MAA
xFSD01366 Relative bearing pedestal vibration SC4 TGI TGI (Siemens)
MAC
xFSD01366 Relative bearing pedestal vibration MAD SC4 TGI TGI (Siemens)
ECCN: N

MAA
xFSD01367 Monitoring of Absolute shaft vibration SC4 TGI TGI (Siemens)
MAC
xFSD01367 Monitoring of Absolute shaft vibration MAD SC4 TGI TGI (Siemens)
AL: N

MAA
xFSD01369 Monitoring of Absolute shaft expansion SC4 TGI TGI (Siemens)
MAC
xFSD01369 Monitoring of Absolute shaft expansion MAD SC4 TGI TGI (Siemens)
Safety function of KU system: Backfeed
tank level control; Sampling lines
KUA, KUB, SCP KUA-KUB-
xFSD01370 temperature protection; Sampling lines SC3 SAS
KUF KUF
overpressure protection; Backfeed pump
dry protection; Other interlocks
Sub loop controls 30KUA10/30 JNA; JND; SCP KUA-KUB-
xFSD01371 SC3 SAS
EE001/002/003 - Switch of sample points JNG, JNK KUF
Sub loop controls 30KUA10/30 KUA, KUB, SCP KUA-KUB-
xFSD01371 SC3 SAS
EE001/002/003 - Switch of sample points KUF KUF
Sub loop control 30KUA20 EE003 - Open KUA, KUB, SCP KUA-KUB-
xFSD01372 SC3 SAS
sample stream from Pressurizer KUF KUF
Sub loop control 30KUA10 EE004 – KUA, KUB, SCP KUA-KUB-
xFSD01373 SC3 SAS
Enabling automatic Close orders KUF KUF
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A121 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Sub loop control 30KUA67 EE001 – KUA, KUB, SCP KUA-KUB-
xFSD01374 SC3 SAS
backfeed of sample box effluents KUF KUF
Sub loop control 30KUA68 EE001 – KUA, KUB, SCP KUA-KUB-
xFSD01375 SC3 SAS
backfeed of primary samples KUF KUF
Protect systems carrying out safety
xFSD01376 CYE SC4 SSS SCP SAG
functions in case of fire
Protect systems carrying out safety
xFSD01376 SAG SC4 SSS SCP SAG
functions in case of fire
JNA; JND; SCP KBA-KBD-
xFSD01377 Automatic Functions in Letdown line SC3 SAS
JNG, JNK JEW
KBA, KBD, SCP KBA-KBD-
xFSD01377 Automatic Functions in Letdown line SC3 SAS
JEW JEW
xFSD01378 Backfeed tank level control QUC SC4 PAS 1 SCP QUC NI
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

xFSD01379 Sequencer for Sodium monitoring QUC SC4 PAS 1 SCP QUC NI
xFSD01380 Sampling lines temperature protection QUC SC4 PAS 1 SCP QUC NI
SGBS/SG samples overpressure
xFSD01381 QUC SC4 PAS 1 SCP QUC NI
protection
xFSD01382 SGBPS samples overpressure protection QUC SC4 PAS 1 SCP QUC NI
xFSD01383 Backfeed pump protection QUC SC4 PAS 1 SCP QUC NI
Vent and drainage outside reactor building
xFSD01384 KTA-KTE EYT SSS SCP KTC/D/E
in UKS building
Level control of the auxiliary boiler when
30QHA11/12 CL001 XV03> >1175mm
(incl ALARM level HIGH 30QHA11/12
QHA
CL001 XV03> >1175mm; WARNING level
QHE
xFSD01385 HIGH 30QHA11/12 CL004 XH01 > EYT SSS SSS Siemens
QHG
>1093mm; WARNING level LOW
QHX
30QHA11/12 CL004 XH52 <300mm,
ALARM level LOW 30QHA11/12 CL002
XV54 <250mm)
Ventilation component protection
xFSD01386 SAC SC3 SAS SCP SAC
functions
Ventilation component protection
xFSD01387 SAC EYT PAS 1 SCP SAC
functions
Alarm on I&C rooms 1/4UJK18 024/025
ECCN: N

xFSD01389 SAC SC3 HBS SCP SAC


and 2/3UJK18 004 temperature high
Alarm on I&C rooms 2/3UJK26 002
xFSD01391 SAB SC3 HBS SCP SAB
temperature high
Alarm on I&C rooms 1/2/3/4UBP10 002 SAD
AL: N

xFSD01393 SC3 HBS SCP SAD-SAL


temperature high SAL
Alarm on I&C rooms 1/4UBP10 012 SAD
xFSD01395 SC3 HBS SCP SAD-SAL
temperature high SAL
Display fault signal UKS in Main Control
xFSD01396 KTA-KTE EYT SSS SCP KTC/D/E
Room
Vent and drainage outside reactor building
xFSD01397 KTA-KTE EYT SSS SCP KTC/D/E
in UKE building
Display fault signal UKE in Main Control
xFSD01398 KTA-KTE EYT SSS SCP KTC/D/E
Room
Closure of QUC containment isolation
xFSD01399 valves on high temperature downstream QUC SC4 PAS 1 SCP QUC NI
of the QUC heat exchanger
Pressure control of exhaust air in relation
xFSD01400 to atmosphere (compensating of filter KLF SC4 PAS 1 SCP KLF
loading).
Pressure control of the Radioactive Waste
xFSD01401 KLF SC4 PAS 1 SCP KLF
Processing Building in relation to
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A122 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
atmosphere.

Control of electrical air heaters for room


xFSD01403 KLF EYT SSS SCP KLF
heating.
Display group fault signal of BBX
xFSD01404 KLF EYT SSS SCP KLF
30KLF01 GH001 in Main Control Room.
Display fault signal of BBX 3 0GQA11
xFSD01405 GQA EYT SSS SCP GQA
GH001 in the Main Control Room
Control for avoiding the incoming of
xFSD01406 smoke into the fresh air intakes in case of SAB SC4 SAS SCP SAB
external hazard
QHA
Hydracin (N2H4) dosing (inl Warning for
QHE
xFSD01407 low level in dosing tank (level switch EYT SSS SSS Siemens
QHG
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

30QHA03 CL091))
QHX
Monitoring of QJC (Gas Distribution
xFSD01408 QJA-QJE EYT SSS SCP QJ NI
system)
Opening and closing of FAK sampling FAK
xFSD01409 SC4 SAS SCP FAK/FAL
valves FAL
Opening and closing of FAK sampling KUA, KUB,
xFSD01409 SC4 SAS SCP FAK/FAL
valves KUF
Opening and closing of FAL sampling FAK
xFSD01410 SC4 SAS SCP FAK/FAL
valves FAL
Opening and closing of FAL sampling KUA, KUB,
xFSD01410 SC4 SAS SCP FAK/FAL
valves KUF
KUA, KUB, SCP KUA-KUB-
xFSD01411 Control of sample box KUA67 EYT SSS
KUF KUF
KUA, KUB, SCP KUA-KUB-
xFSD01412 Control of sample box KUA70 EYT SSS
KUF KUF
KUA, KUB, SCP KUA-KUB-
xFSD01413 Control of sample box KUA80 EYT SSS
KUF KUF
KUA, KUB, SCP KUA-KUB-
xFSD01414 Control of sample box KUB10 EYT SSS
KUF KUF
Component protection function of the
xFSD01415 PEB/PEH SC3 SAS SCP PE
ECCN: N

dedicated ESWS pumps


Monitoring and control of pressure loss
xFSD01416 across the debris filters 30PEB10-40 PEB/PEH EYT SSS SCP PE
AT002
AL: N

Monitoring and control of pressure loss


xFSD01418 across the debris filter 30PEB50-80 PEB/PEH EYT SSS SCP PE
AT001
Monitoring and Control of the ball
xFSD01419 PEB/PEH EYT SSS SCP PE
recirculation process
Monitoring of rainwater collection and
xFSD01423 GUA EYT SSS SCP GUA
drain system
Control of the waste water pumps
xFSD01424 GQA EYT SSS SCP GQA
30GQA11 AP001/002
Monitoring of QJD (Gas Distribution
xFSD01425 QJA-QJE EYT PAS 1 SCP QJ NI
System)
Monitoring of QJE (Gas Distribution
xFSD01426 QJA-QJE EYT PAS 1 SCP QJ NI
System)
Monitoring of QJB (Gas Distribution
xFSD01427 QJA-QJE EYT PAS 1 SCP QJ NI
system)
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A123 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
JAA
JAC
Seal n°2 leak-off tank demineralized water
JEA
xFSD01428 supply isolation for boron dilution SC3 SAS SCP JA-JE
JEB
protection
JEC
JEF, JEG
Seal n°2 leak-off tank demineralized water
JNA; JND;
xFSD01428 supply isolation for boron dilution SC3 SAS SCP JA-JE
JNG, JNK
protection
Manual closing of the containment
xFSD01429 isolation valves KLA10AA701/702 for KLA SC4 SAS SCP KLA
pressure measurement lines
Manual closing of the containment
xFSD01430 isolation valves KLA10AA701/702 for KLA SC3 SICS SCP KLA
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

pressure measurement lines


Start/stop of the dosing system for
xFSD01431 QCA EYT SSS SCP KPC
Hydrazin
xFSD01432 Supply N2 flow to UJA consumers QJA-QJE EYT PAS 1 SCP QJ NI
Space Heating System 30SBK inside
xFSD01433 30UKA Building – Mixing Pump 30KLE SBA EYT PAS 1 SCP SB NI
Operation
Space Heating System 30SBK inside
xFSD01434 30UKA Building – Mixing Pump 30SAM SBA EYT PAS 1 SCP SB NI
Operation
Control of heating water supply
xFSD01435 SBA EYT PAS 1 SCP SB NI
temperature of 30UKE
xFSD01436 Monitoring of the Chilled water systems QNM EYT SSS SSS Siemens
Monitoring og the ventilation and air
xFSD01437 SAC70 EYT SSS SSS Siemens
conditioning system
Manual closing of the containment
xFSD01439 isolation valves KLA60/70 for pressure KLA SC3 SSS SCP KLA
measurement lines
Manual closing of the containment
xFSD01440 isolation valves 30JMQ10/40AA307 for JMQ SC3 SSS SCP JMQ
pressure measurement lines
Ventilation component protection
xFSD01441 KLC SC3 SAS SCP KLC
ECCN: N

functions
Controlled Area Isolation function in case
xFSD01442 KLC SC4 SAS SCP KLC
of external hazards
Provide emergency exhaust in mechanical
AL: N

xFSD01443 rooms of QKA50/ 80 refrigerating SAC EYT PAS 1 SCP SAC


machines in case of refrigerant leakage
Interlocks for the waste water pump GDA, GDN;
xFSD01444 EYT PAS 1 SCP GD
30GDA13 AP001 GDP
Interlocks for the acid dosing pump GDA, GDN;
xFSD01445 EYT PAS 1 SCP GD
30GDN01 AP001 GDP
Interlocks for the sodium hydroxide dosing GDA, GDN;
xFSD01446 EYT PAS 1 SCP GD
pump 30GDN02 AP001 GDP
GDA, GDN;
xFSD01447 Interlocks for the valve 30GDA10 AA403A EYT PAS 1 SCP GD
GDP
Temperature protection for the resins GDA, GDN;
xFSD01448 EYT PAS 1 SCP GD
inside the demineralizers GDP
Temperature protection for the resins LCA90
xFSD01448 EYT PAS 1 SCP GD
inside the demineralizers LCQ
GDA, GDN;
xFSD01449 Drain buffer tank overfilling protection EYT PAS 1 SCP GD
GDP
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A124 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
GDA, GDN;
xFSD01450 Sulfuric acid tank overfilling protection EYT PAS 1 SCP GD
GDP
Sodium hydroxide storage tank overfilling GDA, GDN;
xFSD01451 EYT PAS 1 SCP GD
protection GDP
Prevent water or sulfuric acid losses into GDA, GDN;
xFSD01452 EYT PAS 1 SCP GD
the UKA-building GDP
Temperature protection of the mixed bed GDA, GDN;
xFSD01453 EYT PAS 1 SCP GD
exchanger resins GDP
Pressure release for valves 30GDP01/02 GDA, GDN;
xFSD01454 EYT PAS 1 SCP GD
AA101 GDP
Ventilation component protection SAD
xFSD01455 EYT PAS 1 SCP SAD-SAL
functions SAL
Ventilation component protection SAD
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

xFSD01456 SC3 SAS SCP SAD-SAL


functions SAL
Ventilation component protection SAD
xFSD01457 EYT PAS 1 SCP SAD-SAL
functions SAL
Ventilation component protection SAD
xFSD01458 SC3 SAS SCP SAD-SAL
functions SAL
Control of decontamination equipment for
xFSD01460 FKK SC4 SSS SCP FKK
small machine components
xFSD01461 Monitoring of trains 30PEB10/20/30/40 PEB/PEH SC4 SAS SCP PE
Monitoring and control of pressure loss
xFSD01462 across the debris filter 30PEB50-80 PEB/PEH SC3 SA I&C SCP PE
AT001
Monitoring and control of pressure loss
xFSD01463 across the debris filters 30PEB10-40 PEB/PEH SC3 SAS SCP PE
AT002
Component protection function of the
xFSD01464 KAA, KAB SC3 SAS SCP KAA/KAB
CCWS pumps
Component protection function of the
xFSD01465 KAA50/80 SC3 SAS SCP KAA50/80
dedicated CCWS pumps
Component protection function of the
xFSD01465 PEB/PEH SC3 SAS SCP KAA50/80
dedicated CCWS pumps
xFSD01466 Monitoring of SGE system NI CYE SC4 SSS SCP SG
ECCN: N

xFSD01466 Monitoring of SGE system NI SGE SC4 SSS SCP SG


Leakage monitoring in pressure
xFSD01467 JMQ SC3 SAS SCP KLA
measurement lines
Leakage monitoring in pressure
AL: N

xFSD01467 KLA SC3 SAS SCP KLA


measurement lines
xFSD01468 Electrical interlocks BD SC4 SAS SCP BB-BD
Maintain the ambient temperature
conditions for the Main Control Room
xFSD01469 32UJK26030 during first 2 hours of Loss SAB90 SC3 SSS SCP SAB
of Off-Site Power (LOOP) with Loss of
Computer-based I&C (HBS case)
Alarm in ice accumulator tank temperature
xFSD01472 SAB90 SC3 SAS SCP SAB
high
Control of the operation of the emergency
xFSD01473 SAB90 SC3 SAS SCP SAB
cooling of MCR
Control of temporarily loading of the
xFSD01474 integrated Ice Storage Tank to prepare a SAB90 EYT SSS SCP SAB
passive heat sink
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A125 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
QHA
QHE
xFSD01475 Monitoring of QH system EYT SSS SSS Siemens
QHG
QHX
Control of heating water supply
xFSD01476 SBA EYT PAS 1 SCP SB NI
temperature of 30UKA
xFSD01477 Monitoring of Humidity inside 30UKA SBA EYT PAS 1 SCP SB NI
Space Heating System 30SBK inside
xFSD01478 SBA EYT PAS 1 SCP SB NI
30UKA Building – Pump Operation
xFSD01479 Floor Heating System 30UKE SBA EYT SSS SCP SB NI
Space Heating System 30SBE inside
xFSD01480 SBA EYT SSS SCP SB NI
30UKE Building – Pump Operation
Space Heating System 30SBS inside
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

xFSD01481 SBA EYT PAS 1 PAS 1 Siemens


30UKS Building – Mixing Pump Operation
Maintain the room ambient conditions for
the Air Activity Measuring Rooms in UKA
xFSD01482 KLE SC3 SAS SCP KLE
for equipment operation and personnel
access
xFSD01483 Monitoring of Oil Separators GUA EYT SSS SCP GUA
xFSD01483 Monitoring of Oil Separators GUA EYT SSS SCP GUA
Control of heating of the static heating
xFSD01484 SBA EYT PAS 1 SCP SB NI
circuit of 30UKE
XJA10-40 SCP XJA-
xFSD01485 Diesel engine fuel oil system Monitoring SC4 PAS 1
XKA10-40 XKA10-20-30-40
XJA10-40 SCP XJA-
xFSD01486 Diesel engine lube oil system Monitoring SC4 PAS 1
XKA10-40 XKA10-20-30-40
Failures indication of the Fire Alarm
xFSD01487 CYE SC4 SSS SCP CYE
System
Fire Alarm: Fire indication at Info system
xFSD01488 CYE SC4 SSS SCP CYE
of FAS
Failures indication of the Telephone
xFSD01489 CYA SC4 SSS SCP CYA
System power supply
Failures indication of the LAN/telephone
xFSD01490 CYL EYT SSS SCP CYL
System power supply
ECCN: N

Failures indication of the


xFSD01491 CYB SC4 SSS SCP CYB
Intercommunication System power supply
Failures indication of the Clock system
xFSD01492 CYF SC4 SSS SCP CYF
power supply
AL: N

xFSD01493 Time Signal per division CYF SC4 SSS SCP CYF
Failures indication of the CCTV System
xFSD01494 CYP SC4 SSS SCP CYP01
power supply
Malfunction indication, under-voltage
xFSD01495 monitoring for the incoming feeder cable BZL SC4 SSS SCP BZL
of the lighting and installation system
Failures indication of the Public Address
xFSD01496 CYC SC4 SSS SCP CYC
and Alarm System power supply
XJA10-40 SCP XJA-
xFSD01498 EDG Operational Preheating Monitoring SC4 PAS 1
XKA10-40 XKA10-20-30-40
XJA10-40 SCP XJA-
xFSD01499 EDG Operational Component Protection SC4 PAS 1
XKA10-40 XKA10-20-30-40
EDG Operational Excitation Control XJA10-40 SCP XJA-
xFSD01501 SC4 PAS 1
Actuation XKA10-40 XKA10-20-30-40
XJA10-40 SCP XJA-
xFSD01502 Diesel engine compressed air control SC4 PAS 1
XKA10-40 XKA10-20-30-40
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A126 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Diesel engine compressed air system XJA10-40 SCP XJA-
xFSD01503 SC4 PAS 1
monitoring XKA10-40 XKA10-20-30-40
XJA10-40 SCP XJA-
xFSD01504 Diesel engine cooling systems Monitoring SC4 PAS 1
XKA10-40 XKA10-20-30-40
XJA10-40 SCP XJA-
xFSD01506 Operational Generator Protection SC4 SSS
XKA10-40 XKA10-20-30-40
XJA10-40 SCP XJA-
xFSD01507 Protection Cubicle Monitoring SC4 PAS 1
XKA10-40 XKA10-20-30-40
XJA10-40 SCP XJA-
xFSD01508 Excitation Cubicle Monitoring SC4 PAS 1
XKA10-40 XKA10-20-30-40
XJA10-40 SCP XJA-
xFSD01509 Speed Cubicle Monitoring SC4 PAS 1
XKA10-40 XKA10-20-30-40
XJA10-40 SCP XJA-
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

xFSD01510 Emergency Diesel Engine Monitoring SC4 PAS 1


XKA10-40 XKA10-20-30-40
XJA10-40 SCP XJA-
xFSD01511 Generator Temperature Monitoring SC4 PAS 1
XKA10-40 XKA10-20-30-40
Diesel Engine Cylinder Temperature XJA10-40 SCP XJA-
xFSD01512 SC4 PAS 1
Monitoring XKA10-40 XKA10-20-30-40
SAD
xFSD01513 EDG Hall Ambient Condition Monitoring SC4 PAS 1 SCP SAD-SAL
SAL
XJA10-40
xFSD01513 EDG Hall Ambient Condition Monitoring SC4 PAS 1 SCP SAD-SAL
XKA10-40
Maintain minimum ambient temperature in
diesel hall when diesel generator is not in SAD
xFSD01514 EYT PAS 1 SCP SAD-SAL
operation (diesel is heated by its own SAL
heating system)
Ensure the extraction of heat generated
by the electrical and I&C equipment in the SAD
xFSD01515 SC3 SAS SCP SAD-SAL
diesel building; Maintain minimum SAL
ambient temperature
Ensure the extraction of heat generated
SAD
xFSD01516 by the emergency diesel generator during SC3 SAS SCP SAD-SAL
SAL
its operation
Maintain minimum ambient temperature in SAD
xFSD01517 SC3 SAS SCP SAD-SAL
main tank, service tank rooms SAL
ECCN: N

Maintain acceptable humidity conditions in SAD


xFSD01518 EYT PAS 1 SCP SAD-SAL
the electrical rooms SAL
Monitoring the argon supply pressure with
xFSD01519 MKG SC4 SSS SSS Siemens
30MKG82CP001
AL: N

Monitoring of the Hydrogen Central


xFSD01520 SC4 TGI TGI (Siemens)
Supply Rack
Monitoring of the gas cooling system (Gas
xFSD01521 MKG SC4 TGI TGI (Siemens)
Purity, Purging and Dryer Skid)
Monitoring of Duct ventilation system for
cable-/pipe ducts in turbine island (Incl.
FAULT: Alarm: Fan pressure LOW
xFSD01522 30SAZ01AN001, FAULT: Alarm: Room SAZ* EYT SSS SCP SAZ
temperature pipe bridge 30UMY LOW,
FAULT: Alarm: Room temperature pipe
bridge 30UMY HIGH)
Control of heating of the 30KLF air supply
xFSD01523 SBA EYT PAS 1 PAS 1 Siemens
30UKS Pre-Heaters
Control of heating of the 30KLF air supply
xFSD01524 SBA EYT PAS 1 PAS 1 Siemens
30UKS Post-Heaters
Control of heating of the 30KLF air supply
xFSD01525 SBA EYT PAS 1 PAS 1 Siemens
30UKS Integral Heaters
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A127 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Control of heating of the 30KLF air supply
xFSD01526 SBA EYT PAS 1 PAS 1 Siemens
30UKS Post-Heater Duct System
Space Heating System 30KLF Frost
xFSD01527 SBA EYT PAS 1 PAS 1 Siemens
Protection of 30UKS
xFSD01528 Maintain the room ambient conditions KLF EYT PAS 1 SCP KLF
QHA
Trisodium Phosphate, (crystallized 98% QHE
xFSD01529 EYT SSS SSS Siemens
Na3PO4 +12H2O) dosing QHG
QHX
xFSD01530 Venturi scrubber pressure JMA30 SC3 SAS SCP JMA30
Monitoring of water levels in sump located
xFSD01531 GM SC4 PAS 1 SCP GM NI
in diesel building
Diesel building drainage system: Black
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

xFSD01532 GM EYT SSS SCP GM NI


box monitoring
xFSD01533 Diesel building drainage GM EYT SSS SCP GM NI
Monitoring of water levels in sump located
xFSD01534 GM EYT PAS 1 SCP GM NI
in access building
Access building drainage system: Black
xFSD01535 GM EYT SSS SCP GM NI
box monitoring
xFSD01536 Access building drainage GM EYT SSS SCP GM NI
Monitoring of water levels in sump located
xFSD01537 GM EYT PAS 1 SCP GM NI
in piping duct (31UMZ)
Piping duct (31UMZ) drainage system:
xFSD01538 GM EYT SSS SCP GM NI
Black box monitoring
xFSD01539 Piping duct (31UMZ) drainage GM EYT SSS SCP GM NI
Monitoring of water levels in sump located
in channel for service water system
xFSD01540 building, rock tunnel for service water GM SC4 PAS 1 SCP GM NI
system and channel for service water
system building.
Monitoring of water levels in sump located
xFSD01541 in essential service water system pumps GM SC3 SAS SCP GM NI
building
Essential service water system pumps
ECCN: N

xFSD01542 building drainage system: Black box GM EYT SSS SCP GM NI


monitoring
Essential service water system pumps
xFSD01543 GM EYT SSS SCP GM NI
building drainage
AL: N

Anti-Ice-Heating electrical fault (for AIH


xFSD01544 - SC3 SSS SCP AIH
systems: 30XJG)
Anti-Ice-Heating electrical fault (for AIH
xFSD01545 - SC3 SSS SCP AIH
systems: 30SAL)
Anti-Ice-Heating electrical fault (for AIH
xFSD01546 - SC3 SSS SCP AIH
systems: 30SAD)
Anti-Ice-Heating electrical fault (for AIH
xFSD01547 - SC3 SSS SCP AIH
systems: 30SAC)
Anti-Ice-Heating electrical fault (for AIH
xFSD01548 - SC3 SSS SCP AIH
systems: 30QKA)
Anti-Ice-Heating process fault (for AIH
xFSD01549 - SC3 SSS SCP AIH
systems: 30XJG)
Anti-Ice-Heating process fault (for AIH
xFSD01550 - SC3 SSS SCP AIH
systems: 30SAL)
Anti-Ice-Heating process fault (for AIH
xFSD01551 - SC3 SSS SCP AIH
systems: 30SAD)
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A128 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Anti-Ice-Heating process fault (for AIH
xFSD01552 - SC3 SSS SCP AIH
systems: 30SAC)
Anti-Ice-Heating process fault (for AIH
xFSD01553 - SC3 SSS SCP AIH
systems: 30QKA)
Anti-Ice-Heating electrical fault (for AIH
xFSD01554 - SC4 SSS SCP AIH
systems: 30KLE)
Anti-Ice-Heating process fault (for AIH
xFSD01555 - SC4 SSS SCP AIH
systems: 30KLE)
Anti-Ice-Heating electrical fault (for AIH
xFSD01556 - EYT SSS SCP AIH
systems: 30SAC81)
Anti-Ice-Heating electrical fault (for AIH
xFSD01557 - EYT SSS SCP AIH
systems: 30SAM4)
Anti-Ice-Heating electrical fault (for AIH
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

xFSD01558 - EYT SSS SCP AIH


systems: 30KLD)
Anti-Ice-Heating process fault (for AIH
xFSD01559 - EYT SSS SCP AIH
systems: 30SAC81)
Anti-Ice-Heating process fault (for AIH
xFSD01560 - EYT SSS SCP AIH
systems: 30SAM4)
Anti-Ice-Heating process fault (for AIH
xFSD01561 - EYT SSS SCP AIH
systems: 30KLD)
Prevent icing of the physical protection
xFSD01562 grids and blast valves during winter time - SC3 SSS SCP AIH
(for AIH systems: 30XJG)
Prevent icing of the physical protection
xFSD01563 grids and blast valves during winter time - SC3 SSS SCP AIH
(for AIH systems: 30SAL)
Prevent icing of the physical protection
xFSD01564 grids and blast valves during winter time - SC3 SSS SCP AIH
(for AIH systems: 30SAD)
Prevent icing of the physical protection
xFSD01565 grids and blast valves during winter time - SC3 SSS SCP AIH
(for AIH systems: 30SAC)
Prevent icing of the physical protection
ECCN: N

xFSD01566 grids and blast valves during winter time - SC3 SSS SCP AIH
(for AIH systems: 30QKA)
Prevent icing of the physical protection
xFSD01567 grids and blast valves during winter time - SC4 SSS SCP AIH
AL: N

(for AIH systems: 30KLE)


Prevent icing of the physical protection
xFSD01568 grids and blast valves during winter time - EYT SSS SCP AIH
(for AIH systems: 30SAC81)
Prevent icing of the physical protection
xFSD01569 grids and blast valves during winter time - EYT SSS SCP AIH
(for AIH systems: 30SAM4)
Prevent icing of the physical protection
xFSD01570 grids and blast valves during winter time - EYT SSS SCP AIH
(for AIH systems: 30KLD)
Protection off of Reactor building HVAC
xFSD01571 KLA SC3 SAS SCP KLA
system in case of containment isolation
Monitoring of the active reactive power of
xFSD01572 ACA SC4 PAS 2 PAS 2 Siemens
the switchyard 30ACA
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A129 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
CHY
Monitoring of the active reactive power of CHY10/ACA/A
xFSD01572 SC4 PAS 2 PAS 2 Siemens
the switchyard 30ACA CB/BAT/BBT/B
CT/MKA
Monitoring of the generator transformer
xFSD01573 BA SC4 PAS 2 PAS 2 Siemens
30BAT
CHY
Monitoring of the generator transformer CHY10/ACA/A
xFSD01573 SC4 PAS 2 PAS 2 Siemens
30BAT CB/BAT/BBT/B
CT/MKA
CHY
Monitoring of the turbine protection CHY10/ACA/A
xFSD01574 SC4 TGI TGI (Siemens)
system CB/BAT/BBT/B
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

CT/MKA
Component protection of the safety chiller
xFSD01575 QKA-QKC SC3 SAS SCP QK
water actuation system
Position indication of Containment and
xFSD01576 CYE SC4 PAS 1 SCP SG
Building isolation valves
Position indication of Containment and
xFSD01576 SGB SC4 PAS 1 SCP SG
Building isolation valves
Restart after loss of power: Undervoltage
BM, BN, BL,
xFSD01577 monitoring of fuel pool cooling system SC3 SAS SCP FAK/FAL
BR
(FAK)
Restart after loss of power: Undervoltage
FAK
xFSD01577 monitoring of fuel pool cooling system SC3 SAS SCP FAK/FAL
FAL
(FAK)
Restart after loss of power: Undervoltage
xFSD01578 monitoring of fuel pool purification system BF, BH, BK SC4 PAS 1 SCP FAK/FAL
(FAL)
Restart after loss of power: Undervoltage
FAK
xFSD01578 monitoring of fuel pool purification system SC4 PAS 1 SCP FAK/FAL
FAL
(FAL)
Restart after loss of power: Undervoltage
xFSD01579 monitoring of demineralized water BF, BH, BK SC4 PAS 1 SCP GHC NI
distribution system
ECCN: N

Restart after loss of power: Undervoltage


xFSD01579 monitoring of demineralized water GHC SC4 PAS 1 SCP GHC NI
distribution system
Restart after loss of power: Undervoltage
xFSD01580 BF, BH, BK EYT PAS 1 SCP GHW NI
AL: N

monitoring of seal water supply system


Restart after loss of power: Undervoltage
xFSD01580 GHW EYT PAS 1 SCP GHW NI
monitoring of seal water supply system
Restart after loss of power: Undervoltage BM, BN, BL,
xFSD01582 SC3 SAS SCP JDH
monitoring of extra-boration system BR
Restart after loss of power: Undervoltage
xFSD01582 JDH SC3 SAS SCP JDH
monitoring of extra-boration system
Restart after loss of power: Undervoltage
xFSD01583 BB SC4 SAS SCP JA-JE
monitoring of reator coolant pump system
Restart after loss of power: Undervoltage
xFSD01583 BF, BH, BK SC4 SAS SCP JA-JE
monitoring of reator coolant pump system
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A130 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
JAA
JAC
Restart after loss of power: Undervoltage JEA
xFSD01583 SC4 SAS SCP JA-JE
monitoring of reator coolant pump system JEB
JEC
JEF, JEG
Restart after loss of power: Undervoltage
BM, BN, BL,
xFSD01584 monitoring of containment heat removal SC3 SAS SCP JMQ
BR
system
Restart after loss of power: Undervoltage
xFSD01584 monitoring of containment heat removal JMQ SC3 SAS SCP JMQ
system
Restart after loss of power: Undervoltage
xFSD01585 monitoring of medium head safety BD SC3 SAS SCP JN
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

injection system
Restart after loss of power: Undervoltage
BM, BN, BL,
xFSD01585 monitoring of medium head safety SC3 SAS SCP JN
BR
injection system
Restart after loss of power: Undervoltage
JNA; JND;
xFSD01585 monitoring of medium head safety SC3 SAS SCP JN
JNG, JNK
injection system
Restart after loss of power: Undervoltage
xFSD01586 monitoring of component cooling water BD SC3 SAS SCP KAA/KAB
system
Restart after loss of power: Undervoltage
xFSD01586 monitoring of component cooling water KAA, KAB SC3 SAS SCP KAA/KAB
system
Restart after loss of power: Undervoltage SCP KBA-KBD-
xFSD01587 BD SC3 SAS
monitoring of volume control system JEW
Restart after loss of power: Undervoltage KBA, KBD, SCP KBA-KBD-
xFSD01587 SC3 SAS
monitoring of volume control system JEW JEW
Restart after loss of power: Undervoltage
BM, BN, BL,
xFSD01588 monitoring of reactor boron and water SC3 SAS SCP KBC
BR
makeup system
Restart after loss of power: Undervoltage
xFSD01588 monitoring of reactor boron and water KBC SC3 SAS SCP KBC
ECCN: N

makeup system
Restart after loss of power: Undervoltage SCP KBA-KBD-
xFSD01589 BF, BH, BK EYT PAS 1
monitoring of chemical control system JEW
Restart after loss of power: Undervoltage KBA, KBD, SCP KBA-KBD-
xFSD01589 EYT PAS 1
AL: N

monitoring of chemical control system JEW JEW


Restart after loss of power: Undervoltage
xFSD01590 BF, BH, BK SC4 PAS 1 SCP KBE
monitoring of coolant purification system
Restart after loss of power: Undervoltage
xFSD01590 KBE SC4 PAS 1 SCP KBE
monitoring of coolant purification system
Restart after loss of power: Undervoltage
xFSD01593 monitoring of containment ventilation BF, BH, BK SC4 PAS 1 SCP KLA
system
Restart after loss of power: Undervoltage
BM, BN, BL,
xFSD01593 monitoring of containment ventilation SC4 PAS 1 SCP KLA
BR
system
Restart after loss of power: Undervoltage
xFSD01593 monitoring of containment ventilation KLA SC4 PAS 1 SCP KLA
system
Restart after loss of power: Undervoltage BM, BN, BL,
xFSD01594 SC3 SAS SCP KLB
monitoring of annulus ventilation system BR
Restart after loss of power: Undervoltage
xFSD01594 KLB SC3 SAS SCP KLB
monitoring of annulus ventilation system
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A131 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Restart after loss of power: Undervoltage
BM, BN, BL,
xFSD01595 monitoring of safeguard building SC3 SAS SCP KLC
BR
ventilation system
Restart after loss of power: Undervoltage
xFSD01595 monitoring of safeguard building KLC SC3 SAS SCP KLC
ventilation system
Restart after loss of power: Undervoltage
xFSD01596 monitoring of Access building and office BF, BH, BK EYT PAS 1 SCP KLD
and amenities building ventilation system
Restart after loss of power: Undervoltage
xFSD01596 monitoring of Access building and office KLD EYT PAS 1 SCP KLD
and amenities building ventilation system
Restart after loss of power: Undervoltage
xFSD01599 monitoring of nuclear auxiliary building BF, BH, BK SC4 PAS 1 SCP KLE
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

ventilation system
Restart after loss of power: Undervoltage
xFSD01599 monitoring of nuclear auxiliary building KLE SC4 PAS 1 SCP KLE
ventilation system
Restart after loss of power: Undervoltage
xFSD01601 monitoring of radioactive waste BF, BH, BK SC4 PAS 1 SCP KLF
processing building ventilation system
Restart after loss of power: Undervoltage
xFSD01601 monitoring of radioactive waste KLF SC4 PAS 1 SCP KLF
processing building ventilation system
Restart after loss of power: Undervoltage
BM, BN, BL,
xFSD01602 monitoring of sampling activity monitoring SC3 SAS SCP JYK - KLK
BR
systems
Restart after loss of power: Undervoltage
xFSD01602 monitoring of sampling activity monitoring KLK SC3 SAS SCP JYK - KLK
systems
Restart after loss of power: Undervoltage
BM, BN, BL,
xFSD01603 monitoring of fuel building ventilation SC3 SAS SCP KLL
BR
system
Restart after loss of power: Undervoltage
xFSD01603 monitoring of fuel building ventilation KLL SC3 SAS SCP KLL
system
ECCN: N

Restart after loss of power: Undervoltage


xFSD01604 monitoring of fuel building ventilation BF, BH, BK EYT PAS 1 SCP KLL
system
Restart after loss of power: Undervoltage
AL: N

xFSD01604 monitoring of fuel building ventilation KLL EYT PAS 1 SCP KLL
system
Restart after loss of power: Undervoltage
KPF
xFSD01605 monitoring of liquid waste processing SC4 SSS SCP KPF-KPK
KPK
system
Restart after loss of power: Undervoltage KPF
xFSD01606 EYT SSS SCP KPF-KPK
monitoring of liquid waste storage system KPK
Restart after loss of power: Undervoltage
BM, BN, BL,
xFSD01607 monitoring of gaseous waste processing SC4 PAS 1 SCP KPL
BR
system
Restart after loss of power: Undervoltage
xFSD01607 monitoring of gaseous waste processing KPL SC4 PAS 1 SCP KPL
system
Restart after loss of power: Undervoltage
xFSD01608 monitoring of nuclear island drain and BF, BH, BK EYT PAS 1 SCP KT10/11
vent systems
Restart after loss of power: Undervoltage
BM, BN, BL,
xFSD01608 monitoring of nuclear island drain and EYT PAS 1 SCP KT10/11
BR
vent systems
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A132 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Restart after loss of power: Undervoltage
xFSD01608 monitoring of nuclear island drain and KTA-KTE EYT PAS 1 SCP KT10/11
vent systems
Restart after loss of power: Undervoltage SCP KUA-KUB-
xFSD01609 BF, BH, BK SC3 SAS
monitoring of nuclear sampling system KUF
Restart after loss of power: Undervoltage BM, BN, BL, SCP KUA-KUB-
xFSD01609 SC3 SAS
monitoring of nuclear sampling system BR KUF
Restart after loss of power: Undervoltage KUA, KUB, SCP KUA-KUB-
xFSD01609 SC3 SAS
monitoring of nuclear sampling system KUF KUF
Restart after loss of power: Undervoltage
xFSD01610 BF, BH, BK SC3 SAS SCP LAB NI
monitoring of feedwater piping system
Restart after loss of power: Undervoltage BM, BN, BL,
xFSD01610 SC3 SAS SCP LAB NI
monitoring of feedwater piping system BR
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

Restart after loss of power: Undervoltage


xFSD01610 LAB SC3 SAS SCP LAB NI
monitoring of feedwater piping system
Restart after loss of power: Undervoltage
xFSD01611 monitoring of emergency feedwater pump BD SC3 SAS SCP LAR-LAS
system
Restart after loss of power: Undervoltage
BM, BN, BL,
xFSD01611 monitoring of emergency feedwater pump SC3 SAS SCP LAR-LAS
BR
system
Restart after loss of power: Undervoltage
xFSD01611 monitoring of emergency feedwater pump LAR, LAS SC3 SAS SCP LAR-LAS
system
Restart after loss of power: Undervoltage
xFSD01612 BF, BH, BK SC3 SAS SCP LBA NI
monitoring of main steam piping system
Restart after loss of power: Undervoltage BM, BN, BL,
xFSD01612 SC3 SAS SCP LBA NI
monitoring of main steam piping system BR
Restart after loss of power: Undervoltage
xFSD01612 LBA SC3 SAS SCP LBA NI
monitoring of main steam piping system
Restart after loss of power: Undervoltage
xFSD01613 monitoring of essential service water BD SC3 SAS SCP PE
piping system
Restart after loss of power: Undervoltage
xFSD01613 monitoring of essential service water PEB/PEH SC3 SAS SCP PE
piping system
ECCN: N

Restart after loss of power: Undervoltage


xFSD01614 monitoring of hydrogen gaz distribution BF, BH, BK EYT PAS 1 SCP QJ NI
system
Restart after loss of power: Undervoltage
AL: N

xFSD01614 monitoring of hydrogen gaz distribution QJA-QJE EYT PAS 1 SCP QJ NI


system
Restart after loss of power: Undervoltage BM, BN, BL,
xFSD01615 SC3 SAS SCP QK
monitoring of safety chilled water system BR
Restart after loss of power: Undervoltage
xFSD01615 QKA-QKC SC3 SAS SCP QK
monitoring of safety chilled water system
Restart after loss of power: Undervoltage
xFSD01616 monitoring of operational chilled water BB EYT PAS 1 SCP QN
distribution system
Restart after loss of power: Undervoltage
xFSD01616 monitoring of operational chilled water BF, BH, BK EYT PAS 1 SCP QN
distribution system
Restart after loss of power: Undervoltage
BM, BN, BL,
xFSD01616 monitoring of operational chilled water EYT PAS 1 SCP QN
BR
distribution system
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A133 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Restart after loss of power: Undervoltage
xFSD01616 monitoring of operational chilled water QN EYT PAS 1 SCP QN
distribution system
Restart after loss of power: Undervoltage
xFSD01617 monitoring of sampling system for BF, BH, BK SC4 PAS 1 SCP QUC NI
condensate systems
Restart after loss of power: Undervoltage
xFSD01617 monitoring of sampling system for QUC SC4 PAS 1 SCP QUC NI
condensate systems
Restart after loss of power: Undervoltage
BM, BN, BL,
xFSD01618 monitoring of main control room air SC3 SAS SCP SAB
BR
conditioning system
Restart after loss of power: Undervoltage
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

xFSD01618 monitoring of main control room air SAB SC3 SAS SCP SAB
conditioning system
Restart after loss of power: Undervoltage
xFSD01619 monitoring of electrical division of BF, BH, BK EYT PAS 1 SCP SAC
safeguard building ventilation system
Restart after loss of power: Undervoltage
BM, BN, BL,
xFSD01619 monitoring of electrical division of EYT PAS 1 SCP SAC
BR
safeguard building ventilation system
Restart after loss of power: Undervoltage
xFSD01619 monitoring of electrical division of SAC EYT PAS 1 SCP SAC
safeguard building ventilation system
Restart after loss of power: Undervoltage
BM, BN, BL,
xFSD01620 monitoring of electrical division of SC3 SAS SCP SAC
BR
safeguard building ventilation system
Restart after loss of power: Undervoltage
xFSD01620 monitoring of electrical division of SAC SC3 SAS SCP SAC
safeguard building ventilation system
Restart after loss of power: Undervoltage
xFSD01621 monitoring of switchgear area of nuclear BF, BH, BK EYT PAS 1 SCP SAC80
auxiliary building ventilation system
ECCN: N

Restart after loss of power: Undervoltage


xFSD01621 monitoring of switchgear area of nuclear SAC80 EYT PAS 1 SCP SAC80
auxiliary building ventilation system
Restart after loss of power: Undervoltage
AL: N

xFSD01622 monitoring of diesel building ventilation BF, BH, BK EYT PAS 1 SCP SAD-SAL
system
Restart after loss of power: Undervoltage
SAD
xFSD01622 monitoring of diesel building ventilation EYT PAS 1 SCP SAD-SAL
SAL
system
Restart after loss of power: Undervoltage
BM, BN, BL,
xFSD01623 monitoring of diesel building ventilation SC3 SAS SCP SAD-SAL
BR
system
Restart after loss of power: Undervoltage
SAD
xFSD01623 monitoring of diesel building ventilation SC3 SAS SCP SAD-SAL
SAL
system
Restart after loss of power: Undervoltage
xFSD01624 monitoring of smoke confinement system BF, BH, BK SC4 PAS 1 SCP SAG
of nuclear island
Restart after loss of power: Undervoltage
xFSD01624 monitoring of smoke confinement system SAG SC4 PAS 1 SCP SAG
of nuclear island
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A134 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Restart after loss of power: Undervoltage
xFSD01625 monitoring of station black-out diesel BF, BH, BK EYT PAS 1 SCP SAD-SAL
building ventilation system
Restart after loss of power: Undervoltage
SAD
xFSD01625 monitoring of station black-out diesel EYT PAS 1 SCP SAD-SAL
SAL
building ventilation system
Restart after loss of power: Undervoltage
xFSD01626 monitoring of main steam and feedwater BF, BH, BK EYT PAS 1 SCP SAM3
valve compartment ventilation system
Restart after loss of power: Undervoltage
xFSD01626 monitoring of main steam and feedwater SAM3 EYT PAS 1 SCP SAM3
valve compartment ventilation system
Restart after loss of power: Undervoltage
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

BM, BN, BL,


xFSD01627 monitoring of station black-out diesel SC3 SAS SCP SAD-SAL
BR
building ventilation system
Restart after loss of power: Undervoltage
SAD
xFSD01627 monitoring of station black-out diesel SC3 SAS SCP SAD-SAL
SAL
building ventilation system
Restart after loss of power: Undervoltage
xFSD01628 monitoring of ventilation system for BF, BH, BK EYT PAS 1 SCP SAM4
operational chilled water system
Restart after loss of power: Undervoltage
xFSD01628 monitoring of ventilation system for SAM4 EYT PAS 1 SCP SAM4
operational chilled water system
Restart after loss of power: Undervoltage
monitoring of ventilation system for BM, BN, BL,
xFSD01629 SC3 SAS SCP SAQ
essential service water pump building BR
31/32/33/34UQB
Restart after loss of power: Undervoltage
monitoring of ventilation system for
xFSD01629 SAQ SC3 SAS SCP SAQ
essential service water pump building
31/32/33/34UQB
Restart after loss of power: Undervoltage SCP
xFSD01630 monitoring of space heating system in BF, BH, BK EYT PAS 1 BF/BH/BK/BL/B
UKE building M/BN/BR
ECCN: N

Restart after loss of power: Undervoltage SCP


xFSD01630 monitoring of space heating system in SBA EYT PAS 1 BF/BH/BK/BL/B
UKE building M/BN/BR
AL: N

Restart after loss of power: Undervoltage SCP


xFSD01631 monitoring of space heating system in BF, BH, BK EYT PAS 1 BF/BH/BK/BL/B
UKA building M/BN/BR
Restart after loss of power: Undervoltage SCP
xFSD01631 monitoring of space heating system in SBA EYT PAS 1 BF/BH/BK/BL/B
UKA building M/BN/BR
Restart after loss of power: Undervoltage SCP
xFSD01632 monitoring of space heating system in BF, BH, BK EYT PAS 1 BF/BH/BK/BL/B
UKS building M/BN/BR
Restart after loss of power: Undervoltage SCP
xFSD01632 monitoring of space heating system in SBA EYT PAS 1 BF/BH/BK/BL/B
UKS building M/BN/BR
Restart after loss of power: Undervoltage BM, BN, BL, SCP XJA-
xFSD01633 SC4 PAS 1
monitoring of diesel system BR XKA10-20-30-40
Restart after loss of power: Undervoltage XJA10-40 SCP XJA-
xFSD01633 SC4 PAS 1
monitoring of diesel system XKA10-40 XKA10-20-30-40
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A135 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Restart after loss of power: Undervoltage
BM, BN, BL,
xFSD01635 monitoring of containment ventilation SC3 SAS SCP KLA
BR
system
Restart after loss of power: Undervoltage
xFSD01635 monitoring of containment ventilation KLA SC3 SAS SCP KLA
system
Restart after loss of power: Undervoltage
xFSD01636 monitoring of reactor boron and water BF, BH, BK SC4 PAS 1 SCP KBC
makeup system
Restart after loss of power: Undervoltage
xFSD01636 monitoring of reactor boron and water KBC SC4 PAS 1 SCP KBC
makeup system
Stress-Monitoring System in 33-38UQZ
xFSD01637 CPT EYT SSS SCP CPT
Rock Tunnels
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

xFSD01638 Manual main trip breaker actuation BU SC4 SAS SCP JDA/BU NI
xFSD01639 Rodpilot reset BU SC4 SAS SCP JDA/BU NI
xFSD01640 Avoid smoke distribution in case of fire CYE SC4 SAS SCP SAG
xFSD01640 Avoid smoke distribution in case of fire KLA SC4 SAS SCP SAG
xFSD01640 Avoid smoke distribution in case of fire KLB SC4 SAS SCP SAG
xFSD01640 Avoid smoke distribution in case of fire KLC SC4 SAS SCP SAG
xFSD01640 Avoid smoke distribution in case of fire KLE SC4 SAS SCP SAG
xFSD01640 Avoid smoke distribution in case of fire SAB SC4 SAS SCP SAG
xFSD01640 Avoid smoke distribution in case of fire SAC SC4 SAS SCP SAG
SAD
xFSD01640 Avoid smoke distribution in case of fire SC4 SAS SCP SAG
SAL
Overpressure protection due to safety
switch off of the electrical heaters
30KBG10AH001 (30KBG GH001) by
xFSD01641 KBG SC3 SSS SCP KBF
activating of safety temperature limiter
30KBG10CT191/192 connected to BBX
30KBF50CH001
Measures to safeguard against tube
QMA, QME,
xFSD01642 rupture inside the nuclear auxiliary EYT PAS 1 SCP QM NI
QMK, QMS
building
ECCN: N

LCA
Monitoring of the correct running of the LCB SCP LCQ-
xFSD01643 SC4 PAS 1
Condensate system LCR LCA90
LCW
AL: N

Monitoring of the correct running of the LCA90 SCP LCQ-


xFSD01643 SC4 PAS 1
Condensate system LCQ LCA90
Flash Tank Overpressure Protection in
LCA90 SCP LCQ-
xFSD01644 case of containment islation stage 1 from SC4 PAS 1
LCQ LCA90
PS
Protection for Safeguard Building in case
of a break between containment LCA90 SCP LCQ-
xFSD01645 SC4 PAS 1
penetration and outside containment LCQ LCA90
isolation valve
Additional monitoring for main condensate
LCA90 SCP LCQ-
xFSD01646 system for steam generator blowdown SC4 PAS 1
LCQ LCA90
system LCA90
SC4 Additional monitoring for steam LCA90 SCP LCQ-
xFSD01647 SC4 PAS 1
genertor blowdown system LCQ LCA90
EYT Additional monitoring for steam LCA90 SCP LCQ-
xFSD01648 EYT PAS 1
genertor blowdown system LCQ LCA90
LCA90 SCP LCQ-
xFSD01649 Warm up, heating of flash tank SC4 PAS 1
LCQ LCA90
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A136 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Interlock for bypass valve in the flash LCA90 SCP LCQ-
xFSD01650 SC4 PAS 1
steam line LCQ LCA90
xFSD01651 Flooding protection in the UFA JMQ SC3 SAS SCP JMQ
Monitoring of demineralized water (UKA,
xFSD01652 GHC SC4 PAS 1 SCP GHC NI
UFA, 1/4UJH)
Excessive dilution of boron treated water
xFSD01653 during cleaning of the reactor pool GHC SC4 PAS 1 SCP GHC NI
(GHC74)
xFSD01654 Monitoring CCWS system parameters KAA, KAB SC4 SAS SCP KAA/KAB
xFSD01655 Leakage detection of KBA HP cooler KAA, KAB SC3 SAS SCP KAA-KAB
KBA, KBD,
xFSD01655 Leakage detection of KBA HP cooler SC3 SAS SCP KAA-KAB
JEW
xFSD01656 Operation of Hydraulic actuators KAA, KAB SC3 SAS SCP KAA/KAB
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

xFSD01657 JMQ pump monitoring JMQ SC4 SAS SCP JMQ


xFSD01659 CHRS / CVCS suction line interlock JMQ SC3 SAS SCP JMQ
Component protection function of the
xFSD01660 dedicated CCWS tank and water make-up KAA50/80 SC3 SAS SCP KAA50/80
pump
Retention Water Drainage of Reactor
FAK
xFSD01661 Pools in case SC4 SAS SCP FAK/FAL
FAL
of LOCA
FAK
xFSD01662 System Monitoring SC4 PAS 1 SCP FAK/FAL
FAL
xFSD01663 Chemical Monitoring QUC QUC SC4 PAS 1 SCP QUC NI
xFSD01664 Process Monitoring QUC QUC SC4 PAS 1 SCP QUC NI
xFSD01665 Component protection for sump pumps KTA-KTE SC4 PAS 1 SCP KT10/11
xFSD01666 Component protection for sump pumps KTA-KTE SC3 SAS SCP KT10/11
Water level detection 1/2 for the seal E
xFSD01667 FCJ10 SC4 SSS SCP FCJ10
monitoring (upper cover leak-tightness)
Water level detection 2/2 for the seal E
xFSD01668 FCJ10 SC4 SSS SCP FCJ10
monitoring (upper cover leak-tightness)
RB gate valve status (Gate closed –
xFSD01669 FCJ10 SC4 SSS SCP FCJ10
sensor NO contacts closed).
FB gate valve status (Gate closed –
ECCN: N

xFSD01670 FCJ10 SC4 SSS SCP FCJ10


sensor NO contacts closed).
RB leak (RB compensator leak proof
sensor OR RB valve command
xFSD01671 FCJ10 SC4 SSS SCP FCJ10
penetration leak sensor) (No leak –
AL: N

sensor NC contact closed)


FB leak (FB compensator leak proof
sensor OR FB valve command
xFSD01672 FCJ10 SC4 SSS SCP FCJ10
penetration leak sensor) (No leak –
sensor NC contact closed)
xFSD01673 Ventilation component protection SAM4 EYT PAS 1 SCP SAM4
xFSD01674 Ventilation component protection SAB SC4 PAS 1 SCP SAB
xFSD01675 Ventilation component protection SAB SC4 SAS SCP SAB
Monitoring and Alarm of Diesel Building SAD
xFSD01676 EYT PAS 1 SCP SAD-SAL
Staircases (SAL) SAL
Monitoring and Alarm of Diesel Building SAD
xFSD01677 EYT PAS 1 SCP SAD-SAL
Staircases (SAD) SAL
Reduction of airborne radioactivity
xFSD01678 released via the stack by filtration of the KLF SC4 PAS 1 SCP KLF
exhaust air
xFSD01679 Ventilation component protection KLL SC4 PAS 1 SCP KLL
xFSD01680 Ventilation component protection KLF EYT PAS 1 SCP KLF
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A137 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
xFSD01681 Ventilation component protection KLF SC4 SAS SCP KLF
xFSD01682 Ventilation component protection KLE SC4 PAS 1 SCP KLE
xFSD01683 Ventilation component protection KLA SC4 PAS 1 SCP KLA
xFSD01684 Ventilation component protection KLA SC4 SAS SCP KLA
Monitoring and alarm of CHRS Pump
xFSD01685 rooms during and after CHRS system KLC SC4 SAS SCP KLC
operation
Ventilation component protection
xFSD01686 KLD EYT PAS 1 SCP KLD
functions
Ventilation component protection
xFSD01687 KLB SC3 SAS SCP KLB
functions
Controlled Area Isolation in case of
xFSD01688 QKA50/80 chiller operation and high KLC SC3 SAS SCP KLC
ouside air temperature
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

Ventilation component protection


xFSD01689 SAC80 EYT PAS 1 SCP SAC80
functions
Full recirculation mode in case of
xFSD01690 QKA50/80 chiller operation and high SAC SC3 SAS SCP SAC
outside air temperatures
Full recirculation mode in case of
xFSD01691 QKA50/80 chiller operation and high SAC EYT PAS 1 SCP SAC
outside air temperatures
xFSD01692 Ventilation component protection KLE SC4 SAS SCP KLE
MHSI pump trip on high accumulator JNA; JND;
xFSD01693 SC4 SAS SCP JN
pressure or level during accumulator filling JNG, JNK
JNA; JND;
xFSD01694 Line-Up of LHSI in SI mode EYT SAS SCP JN
JNG, JNK
Closure of LHSI pump sealing valves for JNA; JND;
xFSD01695 SC3 SAS SCP JN
heterogeneous boron dilution protection JNG, JNK
xFSD01696 JDH valve interlocks JDH SC3 SAS SCP JDH
xFSD01697 JDH Monitoring on PICS JDH EYT SAS SCP JDH
xFSD01698 JDH Monitoring on SICS JDH SC3 SAS SCP JDH
xFSD01699 FLIV Oil pressure control LAB EYT SAS SCP LAB NI
xFSD01700 Measurement indication on PICS LAB SC4 SAS SCP LAB NI
xFSD01701 MSIV opening interlock LBA SC4 PAS 1 SCP LBA NI
ECCN: N

xFSD01702 MSIV oil pressure control LBA EYT SAS SCP LBA NI
KBA, KBD, SCP KBA-KBD-
xFSD01703 CVCS safety valve monitoring SC3 SAS
JEW JEW
AL: N

KBA, KBD, SCP KBA-KBD-


xFSD01704 CVCS flow balance SC3 SAS
JEW JEW
protection of CVCS letdown against
KBA, KBD, SCP KBA-KBD-
xFSD01705 undue temperature from RHR thermal SC3 SAS
JEW JEW
expansion line
JAA
JAC
JEA
xFSD01706 RCP motor monitoring (SAS) SC3 SAS SCP JA-JE
JEB
JEC
JEF, JEG

JAA
JAC
JEA
xFSD01707 RCP motor monitoring (PAS) EYT PAS 1 SCP JA-JE
JEB
JEC
JEF, JEG
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A138 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
JAA
JAC
JEA
xFSD01708 SC3 PZR monitoring SC3 SAS SCP JA-JE
JEB
JEC
JEF, JEG

JAA
JAC
JEA
xFSD01709 PZR monitoring EYT PAS 1 SCP JA-JE
JEB
JEC
JEF, JEG

JAA
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

JAC
RCP coast down test: simultaneous trip of JEA
xFSD01710 EYT SAS SCP JA-JE
all pumps JEB
JEC
JEF, JEG

JAA
JAC
Monitor CCWS flowrate to RCP motor and JEA
xFSD01711 SC4 SAS SCP KAA-KAB
bearing coolers. JEB
JEC
JEF, JEG
Monitor CCWS flowrate to RCP motor and
xFSD01711 KAA, KAB SC4 SAS SCP KAA-KAB
bearing coolers.
JAA
JAC
JEA
xFSD01712 Pressure monitoring in nitrogen tank EYT PAS 1 SCP JA-JE
JEB
JEC
JEF, JEG

JAA
ECCN: N

JAC
Flow monitoring at activity monitoring JEA
xFSD01713 SC4 SAS SCP JA-JE
points JEB
JEC
JEF, JEG
AL: N

Flow monitoring at activity monitoring LCA90


xFSD01713 SC4 SAS SCP JA-JE
points LCQ
Flow monitoring at activity monitoring
xFSD01713 QUC SC4 SAS SCP JA-JE
points
JAA
JAC
JEA
xFSD01714 PZR large degassing line EYT PAS 1 SCP JA-JE
JEB
JEC
JEF, JEG
Determination of the integral flow through GDA, GDN;
xFSD01715 EYT PAS 1 SCP GD
the cartridge filter GDP
Determination of the integral flow through GDA, GDN;
xFSD01716 EYT PAS 1 SCP GD
the cation exchanger GDP
Determination of the integral flow through GDA, GDN;
xFSD01717 EYT PAS 1 SCP GD
the mixed bed exchanger GDP
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A139 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Determination of the integral flow of the GDA, GDN;
xFSD01718 EYT PAS 1 SCP GD
dilution water for sulfuric acid GDP
Determination of the integral flow of the GDA, GDN;
xFSD01719 EYT PAS 1 SCP GD
dilution water for sodium hydroxyde GDP
Discharge of blowdown condensate via
GDA, GDN;
xFSD01720 the demineralizing system to the liquid EYT PAS 1 SCP GD
GDP
waste storage system KPK
GDA, GDN;
xFSD01721 Manual Cation Exchanger resin discharge EYT PAS 1 SCP GD
GDP
Manual Mixed Bed Exchanger resin GDA, GDN;
xFSD01722 EYT PAS 1 SCP GD
discharge GDP
GDA, GDN;
xFSD01723 Monitoring of operational values EYT PAS 1 SCP GD
GDP
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

Control of dilution water for sulfuric acid GDA, GDN;


xFSD01724 EYT PAS 1 SCP GD
measurement GDP
Control of dilution water for sodium GDA, GDN;
xFSD01725 EYT PAS 1 SCP GD
hydroxide measurements GDP
KPF
xFSD01726 Signal Transfer of Cooling Water Flow SC4 PAS 1 SCP KPF-KPK
KPK
Failure indication of the Aeroball
xFSD01727 JKQ SC4 SSS SCP JKQ
measurement system
Start and system status check of aeroball
xFSD01728 JKQ SC4 SSS SCP JKQ
measurement
Restart after loss of power: Undervoltage
xFSD01729 monitoring of dedicated component BF, BH, BK SC3 SAS SCP KAA50/80
cooling water system
Restart after loss of power: Undervoltage
BM, BN, BL,
xFSD01729 monitoring of dedicated component SC3 SAS SCP KAA50/80
BR
cooling water system
Restart after loss of power: Undervoltage
xFSD01729 monitoring of dedicated component KAA50/80 SC3 SAS SCP KAA50/80
cooling water system
Display group fault signal of BBX
xFSD01730 KLD EYT SSS SCP KLD
ECCN: N

30KLD01 GH001 in Main Control Room.


xFSD01731 Avoid smoke distribution in case of fire CYE SC4 PAS 1 SCP SAG
xFSD01731 Avoid smoke distribution in case of fire KLA SC4 PAS 1 SCP SAG
xFSD01731 Avoid smoke distribution in case of fire KLD SC4 PAS 1 SCP SAG
AL: N

xFSD01731 Avoid smoke distribution in case of fire KLE SC4 PAS 1 SCP SAG
xFSD01731 Avoid smoke distribution in case of fire KLF SC4 PAS 1 SCP SAG
xFSD01731 Avoid smoke distribution in case of fire SAB SC4 PAS 1 SCP SAG
xFSD01731 Avoid smoke distribution in case of fire SAC SC4 PAS 1 SCP SAG
xFSD01731 Avoid smoke distribution in case of fire SAC80 SC4 PAS 1 SCP SAG
SAD
xFSD01731 Avoid smoke distribution in case of fire SC4 PAS 1 SCP SAG
SAL
xFSD01731 Avoid smoke distribution in case of fire SAG SC4 PAS 1 SCP SAG
xFSD01731 Avoid smoke distribution in case of fire SAM3 SC4 PAS 1 SCP SAG
xFSD01731 Avoid smoke distribution in case of fire SAM4 SC4 PAS 1 SCP SAG

Automatic evacuation alarm in UKE


RFFR00799 CYC SC4 SAS SCP KLD
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A140 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP

Automatic evacuation alarm in UKE


RFFR00799 QJA-QJE SC4 SAS SCP KLD

Automatic evacuation alarm in UKE


RFFR00799 KLD SC4 SAS SCP KLD

RFFR00800 Monitoring of BB *JMU JMU SC4 SAS SCP JMU


monitoring of IRWST and atmosphere
RFFR00801 KUL SC4 SAS SCP KUL
sampling (BB *KUL)
Manual operation of the motor operated
RFFR00802 isolation valve 30JMQ12/42AA004 in the JMQ SC4 SAS SCP JMQ
flooding line.
Manual operation of the motor operated
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

RFFR00803 isolation valve 30JMQ12/42AA004 in the JMQ SC3 SICS SCP JMQ
flooding line
Manual closing of the containment
xFSD01732 isolation valves 30JMM23AA002 in case JMM SC3 SSS SCP JMM
of SA and postulated pipe break
Restart after loss of power: Undervoltage KUA, KUB, SCP KUA-KUB-
xFSD01733 SC3 SSS
monitoring of nuclear sampling system KUF KUF
Restart after loss of power: Undervoltage
xFSD01734 monitoring of essential service water PEB/PEH EYT SSS SCP PE
piping system
Restart after loss of power: Undervoltage
xFSD01735 monitoring of dedicated essential service PEB/PEH EYT SSS SCP PE
water piping system
Restart after loss of power: Undervoltage
xFSD01736 monitoring of dedicated essential service PEB/PEH SC3 SAS SCP PE
water piping system
Restart after loss of power: Undervoltage
BM, BN, BL,
xFSD01736 monitoring of dedicated essential service SC3 SAS SCP PE
BR
water piping system
Restart after loss of power: Undervoltage
xFSD01737 QKA-QKC SC3 SSS SCP QK
monitoring of safety chilled water system
ECCN: N

Restart after loss of power: Undervoltage


xFSD01738 monitoring of emetgency cooling system SAB90 SC3 SSS SCP SAB
for main control room
Restart after loss of power: Undervoltage
SAD
AL: N

xFSD01739 monitoring of diesel building ventilation SC3 SSS SCP SAD-SAL


SAL
system
Restart after loss of power: Undervoltage
SAD
xFSD01740 monitoring of station black-out diesel SC3 SSS SCP SAD-SAL
SAL
building ventilation system
Restart after loss of power: Undervoltage KUA, KUB, SCP KUA-KUB-
xFSD01741 SC3 SSS
monitoring of Nuclear Sampling system KUF KUF
Restart after loss of power: Undervoltage
xFSD01742 monitoring of Post accident atmosphere KUL SC3 SSS SCP KUL
Sampling system
Restart after loss of power: Undervoltage
GDA, GDN;
xFSD01743 monitoring of Steam Generator blowdown SC4 PAS 1 SCP GD
GDP
demineralizing system
Restart after loss of power: Undervoltage
xFSD01743 monitoring of Steam Generator blowdown BF, BH, BK SC4 PAS 1 SCP GD
demineralizing system
Project OL3 N° PEPS-G/2015/en/1050
Confidentiality:
RESTRICTED REV. A PAGE A141 / A141

Function Safety I&C Preliminary


Function Name System
Label Class System SCP
Restart after loss of power: Undervoltage
xFSD01744 monitoring of decontamination equipment FKK SC4 SSS SCP FKK
for small machine component
Restart after loss of power: Undervoltage
xFSD01745 FKK EYT SSS SCP FKK
monitoring of hot landry facilities
Ensure extraction of heat of the diesel SAD
xFSD01746 SC3 SAS SCP SAD-SAL
building when the EDG is out of operation SAL
Automatic venting on HP-charging pump KBA, KBD, SCP KBA - KBD
xFSD01747 SC3 SAS
start (KBA30 EE002) JEW - JEW
Automatic CVCS HP-letdown isolation on
KBA, KBD, SCP KBA - KBD
xFSD01748 CIV SC3 SAS
JEW - JEW
closure
xFSD01749 Monitoring of KAA train fail KAA, KAB SC3 SAS SCP KAA/KAB
CONFIDENTIAL as defined under the Olkiluoto 3 Plant Contract

xFSD01750 Start and Trip of a CCWS train KAA, KAB SC4 SAS SCP KAA/KAB
xFSD01751 Monitoring CCWS system parameters KAA, KAB EYT SAS SCP KAA/KAB
xFSD01752 Monitoring CCWS system parameters KAA, KAB EYT PAS 1 SCP KAA/KAB