Professional Documents
Culture Documents
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
INDEX for Arrear Experiments
1.
2.
3.
4.
5.
MARKS MARKS
SL.NO TOPIC
ALLOTED SECURED
1 Attendance Regularity 10
Preparedness for conduct of
2 20
Exp.
3 Initiative to learn & interact 10
Presentation of Lab. report
4 20
Regularity in Submission
TOTAL 60
SESSIONAL MARKS 60
END SEMESTER MARKS 40
TOTAL MARKS 100
LABORATORY PRACTICE
I SEE, I REMEMBER
I DO, I UNDERSTAND
All students must observe the Dress Code while in the laboratory.
Sandals or open-toed shoes are NOT allowed.
Foods, drinks and smoking are NOT allowed.
All bags must be left at the indicated place.
The lab timetable must be strictly followed.
Be PUNCTUAL for your laboratory session.
Experiment must be completed within the given time.
Noise must be kept to a minimum.
Workspace must be kept clean and tidy at all time.
Handle all apparatus with care.
All students are liable for any damage to equipment due to their own
negligence.
All equipment, apparatus, tools and components must be
RETURNED to their original place after use.
Students are strictly PROHIBITED from taking out any items from
the laboratory.
Students are NOT allowed to work alone in the laboratory without
the Lab Supervisor
Report immediately to the Lab Supervisor if any injury occurred.
Report immediately to the Lab Supervisor any damages to
equipment.
You should be punctual for your laboratory session and should not
leave the lab without the permission of the teacher.
Each student is expected to have his/her own lab book where they
will take notes on the experiments as they are completed.
The lab books will be checked at the end of each lab session. Lab
notes are a primary source from which you will write your lab reports.
You and your batch mates will work closely on the experiments
together. One partner doing all the work will not be tolerated. All the
Batch mates should be able to explain the purpose of the experiment
and the underlying concepts.
Please report immediately to the member of staff or lab assistant
present in the laboratory; if any equipment is faulty.
LAB REPORTS
SAFETY – I
1. Power must be switched-OFF while making any connections.
2. Do not come in contact with live wire.
3. Power should always be in switch-OFF condition, EXCEPT while
you are taking readings.
4. The Circuit diagram must be checked by Technical Assistant/ faculty
member before making connections.
5. Circuit connections should be checked by the faculty before
switching on the power.
6. Keep your Experimental Set-up neat and tidy.
7. Check the polarities of meters and supplies while making
connections.
8. Always connect the voltmeter after making all other connections.
9. Check the Fuse and it’s rating.
10. Use right color and gauge of the fuse.
11. All terminations should be firm and no exposed wire.
12. Do not use joints for connection wire.
13. While making 3-phase motor ON, check its current rating from
motor name plate details and adjust its rated current setting on
MPCB (Motor Protection Circuit Breaker) by taking approval of the
faculty.
14. Before switch-ON the AC or DC motor, verify that the Belt load is
unloaded.
Place him/her on back. Clear his mouth and throat. Turn his/her
head to side and remove any foreign bodies with fingers.
Tilt his/her head back by holding lower jaw – this gives a clear air
passage way to his/her lungs and keep tongue out of throat.
You take deep breath of fresh air. Place mouth over his/her nose.
Hold mouth closed. Blow into nose. Adults-blow fully, children-puff
gently. Watch chest rise. Remove mouth – let chest fall. Continue
until patient resumes breathing.
Note: If chest does not rise when you blow check for obstruction in
his/her throat.
Listen to the air being exhaled. When flow of air stops blow it again.
OBJECTIVE OF THE EXPERIMENT : To analyze the time response of first and second order linear
Simulated Systems.
PREREQUISITES: Knowledge of System Transfer functions: Types and Order, Time domain
specifications, Time Response.
THEORY :
The time response analysis of open loop and closed loop systems are being studied with the help of linear
simulated system.
G(s)
Open Loop
Reference Input Output
+
Reference Input
-
G ( s) Output
T(s)
Closed Loop
The response of the first order system towards unit step input is given by
K K K
C ( s)
s( s 1) s ( s 1) (6)
Figure:
Open loop response of a first order system
3. Second Order System:
The following is the transfer function for a second order system given by
n2
G( s) 2
s 2 ns n2 (9)
is the damping factor and n is natural frequency.
The poles of the system is given by
s n jn
1 2 jd
(10)
Case 3: Overdamped
1
The response of the system is
c (t ) K1e s1t K 2 e s2t (13)
Here
s1 , s2 n n 1 and K , K
2
1 2 are constants.
Figure: Output of a critically damped
system
Closed Loop:
The open loop transfer function of a Type-1is given by
K
G(s)
s ( s 1) (14)
The closed loop transfer function is given by
K
T (s) 2
s s K (15)
By comparing the derived closed loop transfer function with the generalized transfer function of second
order system
K n2
T ( s)
s 2 s K S 2 2n n
K /
i.e n K /
S K
S2
1. Delay Time (td) - It is the time required for the response to reach 50% of the steady state value for
the first time.
2. Rise time (tr) - It is the time required for the response to reach 100% of the steady state value for
under damped systems. However, for over damped systems, it is taken as the time required for the
response to rise from 10% to 90% of the steady state value.
1 2
tan 1
tr
n 1 2 n 1 2 (16)
3. Peak Time (tp) - It is the time required for the response to reach the maximum or Peak value of the
response.
tp
n 1 2 (17)
4. Maximum Peak Overshoot (Mp) - It is defined as the difference between the peak value of the
response and the steady state value. It is usually expressed in percent of the steady state value. If the
time for the peak tp is percent peak overshoot is given by,
c(t p ) c()
(1 2 )
Mp 100 e 100
c ( ) (18)
5. Settling Time (ts) - It is the time required for the response to reach and remain within a specified
tolerance limits (usually ± 2% or ± 5%) around the steady state value.
Rise Time
Peak Time
RESULT : (Observe all the graphs in Scope for various cases separately and Paste here).
DISCUSSION QUESTIONS:
NAME: ....................................................................
ROLL.NO: ................................................................
BRANCH: ..........................SESSION:........................
SECTION: ........................... GROUP : ......................
OBJECTIVE THE EXPERIMENT : To understand the effect of each of the PID parameters on
the dynamics of a closed-loop system.
http://ctms.engin.umich.edu/CTMS/index.php?example=Introduction§ion=ControlPID#27
CIRCUIT DIAGRAM :
THEORY :
The output of a PID controller, which is equal to the control input to the plant/process, is calculated in the
time domain from the feedback error as follows:
(1)
The transfer function of a PID controller is found by taking the Laplace transform of Equation (1).
(2)
OBSERVATION :
The following are the observations for the parameters of different controllers.
SL.NO Controller Type Rise Time Overshoot Settling Time S-S Error
1 P
2 PI
3 PD
4 PID
CALCULATION:
DISCUSSION QUESTIONS:
OBJECTIVE THE EXPERIMENT: To understand the design steps and simulation study of lead
compensator for an uncompensated system
SPECIFICATION. : The open loop transfer function of the uncompensated system with gain
K
G(s)
s (0.5s 1)
K is . Design a suitable lead compensator so that the static velocity error constant kv is
20sec-1, the phase margin is atleast 55o and the gain margin is atleast 12 dB.
[1] “Control Systems Engineering”, R. Anandanatarajan and P. Ramesh Babu, SCITECH, 4th edition
[2] “Automatic Control Systems”, Benjamin. C. Kuo, Prentice Hall of India: 7 th Edition, pp. 671-678, pp.
691-694, pp.708-710.
[3] “Control Systems”, A. Anand Kumar, Prentice Hall of India, pp.231-248.
THEORY and MATLAB implementation of lead compensator :
Lead compensator
A compensator is a component or subsystem in control system that is used to compensate the deficiency in
the performance of the plant. For a given plant and a set of specifications, need to design suitable
compensator such that the overall system will meet the given specifications. Fig. 1 shows the closed loop
uncompensated system. The open loop transfer function (OLTF) of the system or plant is G(s). Fig. 2
shows the closed loop compensated system. Here Gc(s) is the transfer function for compensator which is
connected in cascade with the plant G(s). The compensator can be lead, lag or lag-lead compensators.
1
s
Gc ( s ) K c T K Ts 1 ; 0 1
c (1)
s
1 Ts 1
T
Fig. 1. Closed loop uncompensated system Fig. 2. Closed loop compensated system
1 (3)
m
T rad/sec
1 (4)
m 20 log dB
Gc ( s) K c
Ts 1
; 0 1
(5)
Ts 1
Ts 1 K Ts 1 K c K Ts 1 K' (6)
Gc ( s)G ( s) K c
Ts 1 s (0.5s 1) Ts 1 s(0.5s 1) Ts 1 s (0.5s 1)
Here K'=KcαK
The given kv=20sec-1
We know that
Ts 1 K' (7)
kv lim sGc ( s )G ( s ) lim s 20
s 0 s 0 Ts 1 s (0.5s 1)
'
K 20
20 20
s (0.5s 1) 0.5s 2 s
Step 2: Bode plot of G1(s )=
num1=[0 0 20];
den1=[0.5 1 0];
G1=tf(num1, den1)
bode(G1)
Bode Diagram
50
Magnitude (dB)
-50
-90
Phase (deg)
System: S1
-135 Frequency (rad/s): 5.98
Phase (deg): -162
-180
10 -1 10 0 10 1 10 2
Frequency (rad/s)
From Fig. 4, the phase margin (PM) of G1(s) is 18o. The required PM is 55o as per the given
specification.
To change the PM from 18o to 55o. The required phase lead is 37o
Step 3: To get suitable required phase angle of lead compensator, add 5o to 12o for the right shift of
corner frequency. Therefore suitable required phase angle of the lead compensator is
(37o+10o)=47o
So
CONTROL SYSTEM LABORATORY 37 SOEE
m 47o
Step 4: Using equation (2)
1
Sin 47o 0.16
1
Step 5: Using equation (4)
So
1 1
m 10rad/sec= 3.9
T T
So the pole and zeros for lead compensator is (-1/αT = -24.37) and (-1/T= -3.9) respectively in s plane.
Step6:
We have K'=KcαK
20(0.26s 1)
Gc ( s)G ( s )
s (0.5s 1)(0.04 s 1)
Bode plot of compensated system is shown in Fig. 5.
Magnitude (dB)
0
-50
-100
-90 System: S2
Frequency (rad/s): 10.4
Phase (deg): -122
Phase (deg)
-135
-180
10 -1 10 0 10 1 10 2 10 3
Frequency (rad/s)
num2=[5.2 20];
GcG=tf(num2,den2)
bode(GcG)
The PM of the compensated system is 58o. This value is greater than the required value 55o.
PROCEDURE:
CONCLUSION:
QUESTIONS:
1. What is compensation?
2. What is lag compensator?
3. What is lag-lead compensators?
K
G(s)
s ( s 1)
4. Consider a type 1 unity feedback system with an OLTF, . It is specified that kv=20sec-1
o
and PM =40 . Design the lead compensator and verify in MATLAB.
CONTROL SYSTEM LABORATORY 39 SOEE
CONTROL SYSTEM LABORATORY 40 SOEE
SPACE FOR TRACING
DISCUSSION QUESTIONS:
OBJECTIVE OF THE EXPERIMENT: To obtain the gain margin and phase margin of different linear
dynamic system by frequency response method.
[1] Nise, Norman S. CONTROL SYSTEMS ENGINEERING, (With CD). John Wiley & Sons, 2007.
[2] “Automatic Control Systems”, Benjamin. C. Kuo, Prentice Hall of India: 7th Edition.
[3] “Control Systems”, A. Anand Kumar, Prentice Hall of India.
CIRCUIT DIAGRAM :
THEORY :
A Bode plot is a graph commonly used in control system engineering to determine the stability of a control
system. A Bode plot maps the frequency response of the system through two graphs – the Bode magnitude
plot (expressing the magnitude in decibels) and the Bode phase plot (expressing the phase shift in degrees).
Gain Margin:
The gain margin refers to the amount of gain, which can be increased or decreased without making the
system unstable. It is usually expressed as a magnitude in dB. The greater the Gain Margin (GM), the
greater the stability of the system
Phase Margin
1
G.M where, pc phase cross over frequency
( j) H ( j) pc
1
In dB G.M 20 log
( j) H ( j) pc
MATLAB Program:
num=[0 1 2 ];
den=[1 7 12];
bode(num,den)
PROCEDURE :
RESULT: (Plot the Bode Diagram. Obtain the result for Gain Margin & Phase Margin).
-20
-25
Magnitude (dB)
-30
-35
-40
0
Phase (deg)
-45
-90
-1 0 1 2
10 10 10 10
Frequency (rad/s)
0
Magnitude (dB)
-50
-100
-90
-135
Phase (deg)
-180
-225
-270
-2 -1 0 1 2
10 10 10 10 10
Frequency (rad/s)
CALCULATION:
CONCLUSIONS:
DISCUSSION QUESTIONS:
NAME: ....................................................................
ROLL.NO: ................................................................
BRANCH: ..........................SESSION:........................
SECTION: ........................... GROUP : ......................
OBJECTIVE THE EXPERIMENT : To plot the root locus for a given transfer function using
MATLAB and investigate the system stability.
PREREQUISITES : Transfer function and system types, System stability, Root locus.
[1] Nise, Norman S. CONTROL SYSTEMS ENGINEERING, (With CD). John Wiley & Sons, 2007.
[2] “Automatic Control Systems”, Benjamin. C. Kuo, Prentice Hall of India: 7th Edition.
[3] “Control Systems”, A. Anand Kumar, Prentice Hall of India.
Online Resources on Process Reaction curve-
https://en.wikibooks.org/wiki/Control_Systems/Root_Locus
CIRCUIT DIAGRAM :
THEORY :
A root loci plot is simply a plot of the zeros and the poles values on a graph with real and imaginary
coordinates. The root locus is a curve of the location of the poles of a transfer function as some parameter
is varied. Such a plot shows clearly the contribution of each open loop pole or zero to the locations of the
closed loop poles. This method is very powerful graphical technique for investigating the effects of the
variation of a system parameter on the locations of the closed loop poles. The closed loop poles are the
roots of the characteristic equation of the system while the locus of the roots as the gain varies from zero to
infinity. From the design viewpoint, in some systems simple gain adjustment can move the closed loop
poles to the desired locations. Root loci are completed to select the best parameter value for stability. A
normal interpretation of improving stability is when the real part of a pole is further left of the imaginary
axis.
CONTROL SYSTEM LABORATORY 56 SOEE
A control system is often developed into an equation as shown below:
C (s)
F ( s)
R( s) (1)
k .( s z1 ).( s z2 )....( s zm )
F ( s)
( s p1 ).( s p2 )....( s pn ) (2)
Now, we know that to find the poles of the equation, we must set the denominator to 0, and solve the
characteristic equation. In other words, the locations of the poles of a specific equation must satisfy the
following relationship:
1 K .G ( s).H ( s ) 0
K .G ( s ).H ( s ) 1
Or
Magnitude of K:
1
| K |
| G ( s ).H ( s ) |
MATLAB Program:
num=[0 1 2 ];
den=[1 7 12];
MATLAB Program:
num=[0 0 1 0.4];
den=[1 3.6 0 0];
rlocus(num,den);
grid;
title(‘Root Locus Plot of G(s)=K(s+0.4)/[s^2(s+3.6)]’)
4th order System:
The 4th order transfer function (G(s)):
K ( s 3)
G(s)
s( s 1)( s 2 4 s 16)
MATLAB Program:
num=[0 0 0 1 3];
den=[1 5 20 16 0];
rlocus(num,den);
grid;
title(‘Root-Locus Plot of G(s)=K(s+3)/[s(s+1)(s^2+4s+16)]’)
PROCEDURE :
MODEL GRAPH :
0.4 1
)
-1
0.2 1
Imaginary Axis (seconds
14 12 10 8 6 4 2
0
-0.2 1
-0.4 1
DISCUSSION QUESTIONS:
11. 711Equation Chapter 1 Section 1 What are the advantages of root locus method?
14. Define stability of any system. What do you mean by asymptotic stability?
NAME: ....................................................................
ROLL.NO: ................................................................
BRANCH: ..........................SESSION:........................
SECTION: ........................... GROUP : ......................
EQUIPMENTS REQUIRED : Position Control Unit, D.C. Motor Unit, CRO, Probes.
CIRCUIT DIAGRAM :
THEORY :
Position
set point +
KA KM 1
1 s s
_
-
Error Amplifier Motor
s.KD
The input of the system is the desired angular position of the D.C. Motor which may be continuous or a
step signal. The output angular position is sensed with the help of a potentiometer. A tacho generator
attached to the motor shaft in a sense provides a voltage proportional to the speed in a sense here is a
derivative feedback. The error detector is a 4 input single output block. Two of the inputs are for reference
inputs and the other two are meant for position and velocity feedback signals with inputs 180 degrees out
CONTROL SYSTEM LABORATORY 64 SOEE
of phase. Forward path gain is adjustable from 0 to 10 and tacho generator gain may be varied from 0 to 1.
The driver circuit is a power amplifier in complimentary symmetry configuration that can drive the motor
in both the directions in full power. Since the response of the mechanical system is too slow for real-time
viewing one needs to use the storage oscilloscope. This is a microprocessor based capture system that can
store the response and plot it in X-Y mode later on.
KM
G ( s)
s ( s 1) (1)
Transfer function of closed loop system with feedback H(s) can be generalized as, G(s) H(s)/1+G(s)H(s).
Therefore, in the presence of a proportional feedback the closed loop transfer function is given as
K AG ( s )
T (s)
1 K AG ( s ) (2)
1
Position Set Point (VR)
+
_ KA KM
Error Amplifier 1 s s
Motor
KDs
Figure: Block Diagram of D.C. Motor Position control system with Derivative Feedback
In the presence of Tacho (derivative) feedback the closed loop system for above block diagram is given by
K AG ( s )
T (s )
1 K A (1 K D s)G ( s) (3)
By comparing above derived closed loop transfer function with generalized second order system which can
be given as follows,
1. Delay Time (td) - It is the time required for the response to reach 50% of the steady state value for
the first time.
1 0.7
td
n (5)
2. Rise time (tr) - It is the time required for the response to reach 100% of the steady state value for
under damped systems. However, for over damped systems, it is taken as the time required for the
response to rise from 10% to 90% of the steady state value.
1 2
tr , tan 1 ( )
n 1 2
(6)
3. Peak Time (tp) - It is the time required for the response to reach the maximum or Peak value of the
response.
tp
n 1 2 (7)
4. Maximum Peak Overshoot (Mp) - It is defined as the difference between the peak value of the
response and the steady state value. It is usually expressed in percent of the steady state value. If the
time for the peak tp is percent peak overshoot is given by,
c(t p ) c()
(1 2 )
Mp 100 e 100
c ( ) (8)
CONTROL SYSTEM LABORATORY 66 SOEE
5. Settling Time (ts) - It is the time required for the response to reach and remain within a specified
tolerance limits (usually ± 2% or ± 5%) around the steady state value.
4
ts
n (9)
6. Steady state error (Ess) - It is the error between the desired output and the actual output as or under
steady state conditions. The desired output is given by the reference input r (t) and the steady state
error:
sR ( s)
Ess lim
s 0 1 G(s) (10)
PROCEDURE :
Step Response:
1. Set the tacho generator feedback in the motor unit in ‘NEGATIVE’ mode.
K
2. Set A to 2, D
K 0.
3. Compute the time response specifications.
K 3, 4, .
4. Repeat for A
5. Now set A
K 6 , and choose various values of K D 0.1,0.2 and repeat the above observations.
6. Tabulate the results as shown.
7. Compare the results with theoretical predictions.
8. A set of observations is to be taken in positive feedback.
TABULATION :
RESULT: (State all the obtained values like rise time etc here for various cases separately).
DISCUSSION QUESTIONS:
1. What is a tachogenerator ?
3. What is the effect of proportional and derivative feedback on the response of the system?
5. Find the transfer function of a armature controlled DC motor and draw its block diagram
CONTROL SYSTEM LABORATORY 71 SOEE
NAME: ....................................................................
ROLL.NO: ................................................................
BRANCH: ..........................SESSION:........................
SECTION: ........................... GROUP : ......................
DISCUSSION QUESTIONS:
OBJECTIVE OF THE EXPERIMENT : To study the effect of derivative feedback on D.C. Motor
THEORY :
DC-motors that are used in feedback controlled devices are called DC-servomotors. Applications of DC-
servomotors abound, e.g., in robotics, computer disk drives, printers, aircraft flight control systems,
machine tools, flexible manufacturing systems, automatic steering control, etc. DC motors are classified as
armature controlled DC-motors and field controlled DC-motors. A schematic representation of an armature
i
controlled DC-motor is given in Figure 1. For an armature controlled DC-motor, the field current f is
T
constant and the torque m generated at the DC-motor shaft is given by:
Tm KT ia 1010\* MERGEFORMAT ()
T
Where m is the motor Torque Constant in Nm/A. The back e.m.f. induced in the armature due to armature
rotation is directly proportional to the armature angular velocity
CONTROL SYSTEM LABORATORY 82 SOEE
d m
Vb = K b
dt 1111\* MERGEFORMAT ()
K b is the back e.m.f constant in Vs/rad. The angular speed m of an armature controlled DC-motor is
V i
controlled by the armature voltage a . The deferential equation relating the armature current a and the
V V
back e.m.f. b to the armature voltage a can be obtained by applying Kirchhoff’s Voltage Law (KVL). In
particular, according to the KVL, at any given instant of time, the algebraic sum of voltages around any
loop in any electric network is zero. Thus, a direct application of the KVL to the armature circuit yields
dia
La Ra ia Vb Va
dt 1212\* MERGEFORMAT ()
Finally, we obtain the deferential equation governing the motion of the mechanical load. First,
note that in most applications, the DC-servomotor shaft is connected to a gear-box of a given
K 1
gear-ratio, g and the load is attached to the output shaft of the gear-box. Applying the moments to the
rotating system one gets the differential equation
d 2 d
J eq 2
bt Tm
dt dt 1313\* MERGEFORMAT ()
Taking the Laplace transform of Error: Reference source not found and Error: Reference source not found,
J Jm Jl b
here eq is the total inertia, t is the rotational viscous friction. The dynamics of the electrical
L
network can be neglected by assuming the armature inductance a as zero. The final transfer function is
given by
( s) KT K A K
M
Va ( s ) ( Ra J eq s Ra bt KT K b ) s 1
1414\* MERGEFORMAT ()
VR +
_ KA KM 1
1 s s
Error Amplifier Motor
KDs
Figure 2: D.C. Motor Speed Control schematic with Derivative (Tacho) feedback
1 1
(12)
2 f ln[1 C ( p p) 1 ]
R ( p p ) K eq
where C ( p p ) Response value
R p p Reference value
and f in Hz
−1 1
2f C( p− p) 1 (Rp-p=Ref voltage=1v,Cp-p=Response value Vt)
ln [ 1− ]
R( p− p) K eq
PROCEDURE :
V 1V and K A 3. Then the motor will start to run at low speed. Record
1. Set the reference voltage R
2 N
ss
the speed in RPM 60 . Tacho generator output VT and motor input VM .
2. Repeat with R
V 1V and K A 4,5, 610. and calculate N, VT and VM .
V V K K
3. Plot N vs M and T vs N. Obtained M and T from the linear region.
4. Obtain the open loop motor transfer function as in Error: Reference source not found.
5. Find the Tacho-generator transfer function.
1. Set
VR 1V and K A 5 , the motor will run in low speed Measure the speed in RPM and the tacho
1
Ess
V E VR VT and the theoretical value
voltage T . Find the ss K A K M KT .
TABULATION :
A. Open Loop System:
SL.NO KA N VT VM
1 3
2 4
3 5
4 6
5 7
6 8
7 9
8 10
Ess Ess
Sl No. KA N VT
(Theoretical) (Observational)
1 5
2 10
3 15
4 20
5 25
6 50
7 75
8 100
For
VR 0.5V & K A 5 .
K K
T .F TF= =¿
1 S eq 1+ τ eq S
RESULT : (State all the obtained values like rise time etc here for various cases separately).
CALCULATION:
DISCUSSION QUESTIONS:
2. Write the applications where DC motor speed control has been used?
5. Define steady state error. Determine the theoretical value of steady state error?
OBJECTIVE OF THE EXPERIMENT : To analyze the time response of first and second order linear
Simulated Systems.
PREREQUISITES: Knowledge of System Transfer functions: Types and Order, Time domain
specifications, Time Response.
THEORY :
The time response analysis of open loop and closed loop systems are being studied with the help of linear
simulated system.
G (s)
Open Loop
Reference Input Output
+
Reference Input
-
G ( s) Output
T(s)
Closed Loop
The response of the first order system towards unit step input is given by
K K K
C (s)
s( s 1) s ( s 1) (6)
Case 3: Overdamped
1
The response of the system is
c(t ) K1e s1t K 2e s2t (13)
Here
s1 , s2 n n 1 and K , K
2
1 2 are constants.
Figure: Output of a critically damped
system
Closed Loop:
The open loop transfer function of a Type-1is given by
K
G(s)
s ( s 1) (14)
The closed loop transfer function is given by
K
T (s) 2
s s K (15)
By comparing the derived closed loop transfer function with the generalized transfer function of second
order system
K n2
T ( s)
s 2 s K S 2 2n n
K /
i.e n K /
S K
S2
7. Delay Time (td) - It is the time required for the response to reach 50% of the steady state value for
the first time.
8. Rise time (tr) - It is the time required for the response to reach 100% of the steady state value for
under damped systems. However, for over damped systems, it is taken as the time required for the
response to rise from 10% to 90% of the steady state value.
1 2
tan 1
tr
n 1 2 n 1 2 (16)
9. Peak Time (tp) - It is the time required for the response to reach the maximum or Peak value of the
response.
tp
n 1 2 (17)
10. Maximum Peak Overshoot (Mp) - It is defined as the difference between the peak value of the
response and the steady state value. It is usually expressed in percent of the steady state value. If the
time for the peak tp is percent peak overshoot is given by,
c(t p ) c ()
(1 2 )
Mp 100 e 100
c ( ) (18)
11. Settling Time (ts) - It is the time required for the response to reach and remain within a specified
tolerance limits (usually ± 2% or ± 5%) around the steady state value.
Rise Time
Peak Time
Settling time
RESULT : (State all the obtained values like rise time etc here for various cases separately).
CALCULATION:
DISCUSSION QUESTIONS:
NAME: ....................................................................
ROLL.NO: ................................................................
BRANCH: ..........................SESSION:........................
SECTION: ........................... GROUP : ......................