Professional Documents
Culture Documents
LIST OF FIGURE...................................................................................................................... 3
LIST OF TABLE ....................................................................................................................... 4
1. Introduction ........................................................................................................................ 5
1.1 Objectives ........................................................................................................................ 5
1.2 Material type used ............................................................................................................ 5
2. Design of floor slab ............................................................................................................ 6
2.1 Overview of slab design................................................................................................... 6
2.2.1 Procedures ................................................................................................................. 6
2.3 Design of slab .................................................................................................................. 9
2.3.1 Load determination Live load ................................................................................. 10
2.3.2 Determination of slab depth .................................................................................... 11
2.3.3 Loading ................................................................................................................... 12
2.4 Support and span moment calculation ...................................................................... 17
2.5 Moment adjustment ....................................................................................................... 19
2.5.1 Support moment adjustment ................................................................................... 19
2.5.2 Span moment adjustment ........................................................................................ 21
2.6 Load transfer to beams ................................................................................................... 23
2.7 Span reinforcement calculations panel 1 ....................................................................... 26
2.7.1 Longitudinal / main reinforcement ......................................................................... 26
2.7.2 Distribution reinforcement ...................................................................................... 27
2.8 Support reinforcement calculation ................................................................................. 28
3. Analysis and design of stair case ......................................................................................... 31
3.1 Introduction .................................................................................................................... 31
3.2 Depth determination....................................................................................................... 31
3.3 Load calculation ............................................................................................................. 32
4. Beam design ......................................................................................................................... 37
4.1 introduction .................................................................................................................... 37
4.2 design of beam ............................................................................................................... 37
4.2.1 Determination of depth ........................................................................................... 38
4.2.2 Support moment ...................................................................................................... 38
4.2.3 Check concrete shear capacity ................................................................................ 40
4.24 Check concrete for diagonal compression ............................................................... 41
4.2.5 Calculating the required shear reinforcement ......................................................... 41
5. Column design ..................................................................................................................... 44
5.1 Introduction .................................................................................................................... 44
LIST OF FIGURE
This project work consists of a structural designs of beam, slab, stair and column in
Multipurpose G+1 Reinforced concrete building. The building is composed of solid slab in all
of the floors. Live load and dead load analysis is made according to as per ES EN 1991-1-
1:2015 and ES EN 1992:2015
1.1 Objectives
General objective of the project is design of G+1 beam, slab, stair and column of the
building.
Concrete C-25/30
Rebar S-500
Rebar S-500
Design strength
𝑓𝑐𝑘= 25 Mpa
0.85∗𝑓𝑐𝑘 0.85∗25
𝑓𝑐𝑑 = = = 14.17 𝑀𝑝𝑎
1.5 1.5
𝑓𝑦𝑘1 =500 Mpa for ф > 10
𝑓𝑦𝑘1 =300 Mpa for ф < 10
𝑓𝑦𝑘 500
𝑓𝑦𝑑 = 1.15 = 1.15 = 434.78 𝑀𝑝𝑎
𝑓𝑦𝑘 500
𝑓𝑦𝑑 = 1.15 = 1.15 = 260.87 𝑀𝑝𝑎
2. Design of floor slab
There are two types of slabs based on the load transferring mechanisms. These are one way
and two way slabs. One-way slabs transmit their load in one direction while two way slabs
resist applied load in two directions.
These types of slabs are composed of rectangular panels supported at all four edges by walls
or beams stiff enough to be treated as unyielding.
2.2.1 Procedures
Determining the loads
Slabs support area loads. The loads carried by slabs are of two types. These are
live load and dead load.
Live load
Live load or imposed loads are loads on the structure are those arising from occupancy. They
depend on the particular function of the slab. To determine the live load on a slab, we first
determine its occupancy or function.as per ES EN 1991-1-1:2015 section 6.3 PUTS possible
building occupancies in different categories. also gives the respective live load
value for each category on table 6.2. we will take this area loads and place them
on each slab according to their category.
DEPTH DETERMINATION
Where:
L/d is the limit span/depth
By adding the concrete cover and half of reinforcement diameter, we will get the
overall depth of the slab.
Dead load
These loads are come from materials that are permanently attached to the slab. Some of the
sources of dead load are shown on figure below and are the following
Slab it-self
Celling plaster (below slab)
Cement screed (above slab)
Finishing material (Above slab)
Exterior and interior walls resting on the slab
For the walls, we first check whether the factored area load from the wall exceeds 20 % of the
design load without wall load. If this wall load does not exceed 20% of the design load no need
to check shear capacity of slab. However, if the wall load exceeds 20% of the design load
checks shear capacity of the slab. After determining both dead load and live load, we will
calculate the design load by applying safety factors.
FIGURE 1 CANTILEVER SLABS WITH AND WITHOUT EDGE WALL
Using the span length and the loads, we will calculate the maximum moment that will occur
on the slab. Once we computed the maximum moment, we can proceed to the next design steps.
To do this we first have to calculate some design parameters need for the calculation. Then
adjust moment on the slab and using the adjusted moment find the amount of reinforcement.
From the steel area required, we can determine the spacing that should be used to provide rebar
area that is equal to the calculated area of steel. We check whether the spacing we calculate is
below the maximum amount of spacing allowed.
If our calculated spacing exceeds the maximum spacing allowed, we will take the maximum
spacing. Once we adjusted the spacing in to a value that can be easily used, the calculation of
main reinforcement (shorter direction) for the one way slab will be done. For the longer
direction (transvers direction), we do not have to calculate the moment and reinforcement since
entire load is transferred along the shorter direction. Instead, we will calculate the nominal
amount of reinforcement spacing needed.
Two-way slabs
For two-way slabs with edges either simply supported or fully fixed are calculated as follows:
Where:-
αi is the coefficient given in EBCS 2 1995 page 11 Table A-I as function of span ratio,
Using the formula we will be able to calculate 4 moments, which are represented in figure15
Span moment on the shorter side, Mxs
Span moment on the longer side, Mys
Field moment on the shorter side, Mxf
Field moment on the longer side, Myf
Often the support moment of one slab is not equal to the support moment of the adjacent
slab. This will require us to do support adjustment. To determine which method we have to
use we will check whether the difference of the two adjacent moments exceed 10% of the
larger moment. If it does not exceed we will use method I but if it exceed we will use
method II.
Method I
If difference of the two moments (ΔM) is less than 10% of the larger moment, the adjusted
moment will simply be the average of the two moment values.
Method II
If difference of the two moments (ΔM) is greater than 10% of the larger moment, the
adjusted moment have to be calculated considering the stiffness of the adjacent slabs.
We begin our analysis by determining the dead load and live load imposed on the slab.
2.3.1 Load determination Live load
As this load depends on the occupancy/function of the floor. From the architectural design, we
can see that the slab serves one functions. For slabs supporting one occupancies with different
live load, we will take the larger live load to be on the safe side. Both bedroom and bathroom
are listed under category A, Office areas are categorized under category B and Areas where
people may congregate are categorized under category C. Therefore we do have to choose the
larger. From the categories general use the given live load on PrES EN 1991-1-1:2015 table
6.2 is 3.0kN/m2.
Dead load
The primary permanent load on the slab is the weight of the slab itself. Other than the slab, the
finishing works lay on the slab including ceiling plaster, cement screed and finishing materials
are dead loads on the slab.
For finishing material: from the architectural drawing, we can see that the finishing material
of the slab. These materials exert different amount of load on the slab. To be on the safe side,
we will take the finishing material that exerts larger load on the slab.
Now we can get the overall dead load on the slab excluding the walls supported by the slab by
adding the above loads. Instead of distributing the wall load exerted at the end, we will place
them as a line load at the edge of the cantilever slab.
Moment determination
Since we have two types of loading at the same time, we will use superimposition. We will
calculate the maximum moment for both loading conditions and add the result.
Before we go to calculating reinforcement for our slab, we have to adjust the moment we
calculated with the support moment of the adjacent slabs
During design of cantilever slabs, we will only make support adjustments if the support
moment of the cantilever slab is less than the support moment of the adjacent slab.
FIGURE 3 FIRST FLOOR SLAB
The limiting span/depth ratio may be estimated using Expressions shown below and
multiplying this by correction factors to allow for the type of reinforcement used and other
variables, from prES EN 1991-1-1:2015, Sec.7.4
The Slab is lightly stressed (ρ= 0.5%) in accordance with prES EN 1991-1-1:2015, Table
7.4N
Determination of depth
ρ < ρo Implies 0.5% < 0.5% ES EN 1992-1-1:2015 article 7.4.3 Expressions (7.16a)
For end span (panel 1)
4200 0.5
0.8 = 1.3 [11 + 1.5√25 ∗ ] = 139.71 mm
𝑑 0.5
For Balcony
1650 0.5
0.8 = 0.4 [11 + 1.5√25 ∗ ] = 151.35 mm
𝑑 0.5
2.3.3 Loading
Panel 1
Dead load D=210 mm
0.15∗5∗2.81
= *14= 1.23 kN/ m2
4.2∗5.7
Panel 2
0.15∗5∗2.81
= *14= 1.23 kN/ m2
4.2∗5.7
0.15∗6.45∗2.81
= *14= 2.38 kN/ m2
4.2∗3.8
Panel 3
Panel 4
0.2∗3.5∗2.81
= *14= 0.83 kN/ m2
5.8∗5.7
Panel 5
0.15∗3.6∗2.81
= *14= 0.91 kN/ m2
5.8∗4
Panel 6
0.15∗7∗2.81
= *14= 1.19 kN/ m2
5.8∗3.8
Panel 7
0.20∗5.5∗2.81
= *14= 2.01 kN/ m2
5.8∗3.7
Balcony
Cantilever 1
0.15∗0.45∗2.81
= *14= 0.72 kN/ m2
0.65∗5.7
Cantilever 2
0.15∗0.45∗2.81
= *14= 1.08 kN/ m2
3.8∗0.65
For cantilever 1
For cantilever 2
For Balcony 3
𝛼xf=0.040 Mxf=11.42
𝛼yf=0.029 Myf=8.27
P2 𝛼xf=0.028 Mxf=7.84
𝛼xs=0.056 Mxs=8.94
𝛼xf=0.042 Mxf=6.60
𝛼xs=0.049 Mxs=24.90
𝛼xf=0.037 Mxf=18.80
P4 𝛼yf=0.036 Myf=18.29
𝛼xs=0.070 Mxs=17.22
𝛼xf=0.053 Mxf=13.04
𝛼yf=0.050 Myf=6.98
𝛼xs=0.074 Mxs=17.22
𝛼xf=0.056 Mxf=13.04
𝛼xs=0.066 Mxs=15.58
𝛼xf=0.044 Mxf=10.38
𝛼yf=0.036 Myf=8.50
∆m = Mmax – Mmin
∆m = 10.35-8.94
∆m = 1.41 KNm
1.41 KNm > 1.035 KNm, this implies that adjust the moments by considering stiffness
1 1
3.8 3.7
= 1 1 = 0.493 = 1 1 = 0.507
+
3.8 3.7
+
3.8 3.7
Md = Mmax – DFmax*∆m Md = Mmin+DFmin*∆m
Md = 10.35 – 0.493*1.41 Md = 8.94 + 0.507*1.41
Md = 9.65 KNm Md= 9.65 KNm
TABLE 2 MOMENT ADJUSTMENT
Along X
Along Y
Where
Mxf & Myf: - initially (before support moment adjustment was made) calculated field
moments in shorter and longer direction respectively
ΔMxs & ΔMys: - the difference between final support moment after support moment
adjustment and initial support moment in shorter and longer direction respectively.
Cx1 & Cx2:- factors for adjusting field moment in the shorter direction, ( Mxf) taken
from EBCS-2 Table A-2
Cy1 & Cy2:- factors for adjusting field moment in the longer direction, (Myf ) taken
from EBCS-2 Table A-2
ΔMxf (adj.) & ΔMyf (adj.):- the adjusted field moments in the shorter and longer
direction respectively
Panel 4
Mxf=∆Mxf+Mxf(original)
=01.58+23.88 =25.46 KNm
Myf=∆Myf+Myf(original)
=1.64+16.65=18.29 KNm
TABLE 3 FIELD MOMENT ADJUSTMENT
The design loads on beams supporting solid slabs spacing in two directions at right angles
supporting uniform load may be calculated using: [EBCS 2, 1995 PART 1]
Vx= βvxPd Lx
Vy= βvyPd Lx
According to our code (EBCS 2, 1995), it says that the loads from slab should distribute on
0.75L so to fill the load overall span we should reduce the load by multiplying 0.914 to proof
this concept:
c= (3/4) L
Now to have equal effect on the supports from the load we should have equal MF
w' L2
MF 0.083w' L2
12
MFAB =
3w L L 9L2
3
= =0.076172wL2
8L 2 6 64
w1 =0.076172w =0.914w
0.083
Beam carries
slab load
Stair load
roof load
SAMPLE CALCULATION
For 1st floor
For panel P1
Aspect ratio=1.36
Values of ly/lx Long span coefficients
Coefficient
1.3 1.36 1.4 βvyc& βvyd for all values of ly/lx
βvxc 0.50 0.51 0.52 0.40
βvxd 0.33 0.34 0.34 0.26
Panel Support Lx Ly/Lx PD shear coefficient design load modified design load
βvxc βvxd βvyc βvyd
condition Vxc Vxd Vyc Vyd Vxc Vxd Vyc Vyd
P-1 2 4.20 1.36 16.18 0.51 0.34 0.40 0.26 34.66 23.10 27.18 17.67 31.68 21.11 24.84 16.15
P -2 1 3.80 1.10 19.39 0.356 0.220 0.314 0.374 26.63 16.21 23.13 27.56 24.62 14.89 21.15 24.32
P -3 4 3.70 1.14 14.19 0.347 0.196 0.39 0.369 18.22 10.29 20.48 19.37 16.53 9.15 18.9 17.89
P -4 4 5.70 1.02 15.64 0.378 0.270 0.275 0.379 89.15 63.68 24.56 3.85 81.75 58.95 21.69 3.12
P -5 3 4.00 1.45 15.89 0.31 0.102 0.410 0.320 19.70 6.48 26.06 18.99 17.22 5.36 22.79 16.65
P -6 3 3.80 1.53 16.12 0.12 0.102 0.432 0.310 7.35 6.25 26.46 18.99 6.22 5.13 23.22 16.23
P -7 4 3.70 1.14 17.24 0.347 0.196 0.329 0.369 22.13 12.50 20.99 23.58 19.75 10.33 18.22 21.02
2.56∗1000∗188
𝐴𝑠.𝑚𝑖𝑛 = 0.26[ ] > 0.0013 ∗ 1000 ∗ 188
500
[1000∗78.54]
= = 313.82 mm ≈ 300 mm
250.27
2.56∗1000∗190
𝐴𝑠.𝑚𝑖𝑛 = 0.26[ ] > 0.0013 ∗ 1000 ∗ 190
500
[1000∗78.54]
= = 313.82 mm ≈ 300 mm
250.27
2.56∗1000∗190
𝐴𝑠.𝑚𝑖𝑛 = 0.26[ ] > 0.0013 ∗ 1000 ∗ 190
500
𝐴𝑠.𝑚𝑖𝑛 = 250.27 𝑚𝑚2 > 244.4 𝑚𝑚2
[1000∗78.54]
= = 313.82 mm ≈ 300 mm
250.27
SLAB DETAIL
FIGURE 5SLAB DETAIL
3. Analysis and design of stair case
3.1 Introduction
Concrete C-25/30
Rebar S-500
Rebar S-500
Design strength
𝑓𝑐𝑘= 25 Mpa
0.85∗𝑓𝑐𝑘 0.85∗25
𝑓𝑐𝑑 = = = 14.17 𝑀𝑝𝑎
1.5 1.5
𝑓𝑦𝑘1 =500 Mpa for ф > 10
𝑓𝑦𝑘1 =300 Mpa for ф < 10
𝑓𝑦𝑘 500
𝑓𝑦𝑑 = 1.15 = 1.15 = 434.78 𝑀𝑝𝑎
𝑓𝑦𝑘 500
𝑓𝑦𝑑 = 1.15 = 1.15 = 260.87 𝑀𝑝𝑎
Floor finish
Marble = 20 mm
Plastering = 25mm
Cement screed = 30 mm
K=1.0 for one – or two-way spanning simply supported slab prES EN 1992-1-1-2015 sec 7.4
Effective depth for 1st flight and 2nd flight
4200 0.5
0.8 = 1 [11 + 1.5√25 ∗ ] = 181.62 mm
𝑑 0.5
FIGURE 6 STAIR
Riser = 17 cm
Thread = 30 cm
Stair width = 130 cm
Steps=1/2∗ 𝑟𝑖𝑠𝑒𝑟 ∗ 𝑡ℎ𝑟𝑒𝑑 ∗ 𝑠𝑙𝑜𝑝𝑒 𝑙𝑒𝑛𝑔𝑡ℎ ∗ γc =1 2∗ 0.17 ∗ 0.3 ∗ 2.85 ∗ 25=1.817 kN/m2
(0.46+0.54)∗9∗0.17
Floor finish on riser = [ ] = 0.537 kN/m2
2.85
Total dead load = 5.25 +1.817 + 0.46 + 0.54 + 0.842 + 0.537 = 9.45 kN/m2
Total dead load on landing = 5.25 + 0.46 + 0.46 + 0.54 = 6.71 kN/m2
Design load
Flight Landing
Pd = 1.35DL + 1.5LL Pd = 1.35DL + 1.5LL
= 1.35*9.45 + 1.5*3 = 1.35*6.71 + 1.5*3
= 17.26 kN/m2 = 13.56 kN/m2
Moment analysis
ΣMB = 0
RA = 41.72 kN
ΣFy = 0
RB = 24.11 kN
Vmax = 41.72 kN
Reinforcement
2.56∗1000∗188
𝐴𝑠.𝑚𝑖𝑛 = 0.26[ ] > 0.0013 ∗ 1000 ∗ 188
500
Short direction
[1000∗50.24]
= = 200.74 mm ≈ 200 mm
250.27
Shear reinforcement
= 1.19 ∗ 10−3
[1000∗50.27]
= = 201.05 mm ≈ 200 mm
250.04
fcd= 14.17
Kz = 0.965 , Z= Kz*d = 0.965*188 = 181.42 mm
[1∗1000∗181.42∗0.6∗14.17]
𝑉𝑅𝑚𝑎𝑥 = = 531.88 kN
[2.5+1/2.5]
4.1 introduction
Shear force
Vertical shear forces are generated in a beam by the applied loads and by the support
reaction. The reaction pushes up while the load pushes down. In most cases, the maximum
value of shear occurs close to the support.
Material used
Concrete C-25/30
Rebar S-500
Rebar S-500
Design strength
𝑓𝑐𝑘= 25 Mpa
0.85∗𝑓𝑐𝑘 0.85∗25
𝑓𝑐𝑑 = = = 14.17 𝑀𝑝𝑎
1.5 1.5
𝑓𝑦𝑘1 =500 Mpa for ф > 10
𝑓𝑦𝑘1 =300 Mpa for ф < 10
𝑓𝑦𝑘 500
𝑓𝑦𝑑 = 1.15 = 1.15 = 434.78 𝑀𝑝𝑎
𝑓𝑦𝑘 500
𝑓𝑦𝑑 = 1.15 = 1.15 = 260.87 𝑀𝑝𝑎
4.2.1 Determination of depth
According to ES EN 1992-1-1:2015 section 7.16a
Fyk= 500 according to ES EN 1992-1-1:2015 section 3.2.2 (3)p the application rules for
design and detailing in this code of practice are valid for a specified yield strength range
Fyk=400 to 600 Mpa
2.56∗1000∗188
𝐴𝑠.𝑚𝑖𝑛 = 0.26[ ] > 0.0013 ∗ 1000 ∗ 188
500
𝟔𝟔𝟓.𝟗𝟖 =
= 3.31 = 4
𝟐𝟎𝟏.𝟎𝟔
Use 4 ø 16 c/c 80 mm
[1000∗113.1]
= = 245.46 mm ≈ 240 mm
460.76
5.1 Introduction
A column is a vertical structural member supporting axial compressive loads, with or without
moments. The cross-sectional dimensions of a column are generally considerably less than its
height. Columns support vertical loads from the floors and roof and transmit these loads to the
foundations. In a typical construction cycle, the reinforcement and concrete for the beams and
slabs in a floor system are placed first. Once this concrete has hardened, the reinforcement and
concrete for the columns over that floor are placed. The longitudinal (vertical) bars protruding
from the column will extend through the floor into the next-higher column and will be lap
spliced with the bars in that column. The longitudinal bars are bent inward to fit inside the cage
of bars for the next-higher column. The more general terms compression members and
members subjected to combined axial load and bending are sometimes used to refer to columns,
walls, and members in concrete trusses or frames. These may be vertical, inclined, or
horizontal. A column is a special case of a compression member that is vertical.