BASE SIZE:
Size of foundation block in X direction, Lx = 1.000 m
Size of foundation in Y direction, Ly = 2.500 m
Thickness of foundation = 2.4 m
Grout thickness = 0 m
Shaft C.G. from grout top in z dir. = 0.465 m
C.G. of skid from grout top in z dir = 0.465 m
Operating Frequency of machine = 3000 r.p.m.
wm = 314.159 Rad/Sec
1.0 MACHINE LOAD DATA:
Weight, Wi Mass, mi CG of Element
Machine Fdn Parts Description of Load
(Tons) (t-sec /m)
2
xi (m) yi (m) zi (m)
A Pump 0.167 0.02 0.500 0.475 2.865
B Motor 0.800 0.08 0.500 1.391 2.865
Foundation stability
Vertical Force on Foundation base Pv = 163.43 kN
Area of foundation = 2.50 m2
Pressure on soil due to foundation & machine = 65.37 kN/m2
NET Soil Bearing capacity in compression = 100 kN/m2 …..As per Soil Report.
Assumed
2.865
2.865
ement
zi (m)
1.200