MAXIMUM PERFORMANCE.
MAXIMALLY TESTED.
W WW.R EIN HAU S E N.COM
VACUTAP ® VR
More than 20,000 VACUTAP® VR units are currently Reliable. Rugged. Economical.
demonstrating their value for our customers around the
world. Our engineers incorporated this one-of-a-kind These three traits are the essence of our VACUTAP®
operating experience into the development of the new technology. And the VACUTAP® VR takes advantage of the
VACUTAP® VR. The result is sure to impress: Optimization enormous versatility offered by this technology. It is ideal
of the design allowed us to increase the permitted values for all operating applications:
for step voltage and switching capacity once again.
I Grid
The option of combining the VR with the brand new I Electric arc furnace
R-selector design provides additional advantages. The I HVDC
new R-selector displays these advantages through the I Variable shunt reactors
significantly increased tap-changing capacity of the I Phase shifters
change-over selector and higher permissible operating
and testing voltages. This means that higher power In terms of economy, the VACUTAP® VR makes no com-
requirements are ideal for taking full advantage of the promises, enabling 300,000 tap change operations with-
strengths of this combination. In addition, the Active Gas out any maintenance. The diverter switch insert can be
Inhibition System®* can be used to reduce gas gene- used for 1.2 million tap changes before needing replace-
ration in the transformer tank caused by tap selector ment.
operations by up to 90 percent.
3
VACUTAP ® VR
VACUTAP® VR – EXPERTISE
MAKES THE DIFFERENCE.
The VACUTAP® VR is delivered with all of our expertise gained through 25 years
of vacuum technology development. This expert knowledge can be seen in many
technical details. Details that make the difference and guarantee reliable and safe
operation. This makes the VACUTAP® VR much more than an on-load tap-changer.
It is the original. Original VACUTAP®.
64 . 7
VACUTAP® VR WITH R-SELECTOR -
A FUTURE-DEFINING COMBINATION.
The new R-selector and the VACUTAP® VR are an unbeatable team for high
power capacities. The new generation of selectors features more than just
an increased switching capacity of the change-over selector (up to 60 kV of
recovery voltage ⁄ 600 mA breaking capacity). The R-selector combines high
economy with maximum durability.
Optimized handling
Customer requests were consistently implemented in the design
of the R-selector. This made it possible to improve the handling
significantly. This enables shorter lead times for transformer
manufacturers and ultimately reduces costs. Lifting the selector
to the diverter switch oil compartment (using a forklift or
scissors lift) is also made easier, since the bottoms of the tap
selectors and change-over selectors are on the same level. This
means improved handling as well as increased work safety when
connecting to the diverter switch. Selector take-off leads on
the interior side and the resulting simplification of the cable
routing guarantee more space and flexibility for the connecting
leads. The contacts are also more accessible and provide a larger
connection surface.
VACUTAP® VR –
TECHNICAL DATA.
On-load tap-changer
VRM II 1002
VRM II 1302
VRS II 1002
VRS II 1302
VRL II 1302
VRM II 702
VRS II 702
Designation
Number of phases 3 3 3 3 3 3 3 2 2 2 2 2 2 2
Max. rated through-current I r (A) 700 1000 1300 700 1000 1300 1300 700 1000 1300 700 1000 1300 1300
Max. rated step voltage U ir (V) 4500 4500 4500 4500 4500 4500 4500 4500 4500 4500 4500 4500 4500 4500
VRH I 26221)2)
VRM III 700 Y
VRH II 13022)
VRM I 26221)
VRS III 700 Y
VRM II 1002
VRM II 1302
I 26221)
VRL I 26221)
VRH II 6522)
II 1002
II 1302
VRL II 1302
VRM II 702
VRX I 6522)
II 702
VRS
VRS
VRS
VRS
Designation
Highest voltage for equipment
72,5 123 170 245 72,5 123 170 245 300 362
Um (kV)
Rated lightning impulse withstand
350 550 750 1050 350 550 750 1050 1050 1175
voltage (kV, 1.2|50 µs)
Rated short-duration power
frequency withstand voltage 140 230 325 460 140 230 325 460 460 510
(kV, 50 Hz, 1 min.)
1)
Forced current splitting due to two parallel winding branches required
2)
Special applications upon request
6
VRH III 1300 Y2)
VRH III 650 Y2)
VRH I 26221)2)
VRH II 13022)
VRM I 26221)
VRH I 13012)
VRS I 26221)
VRL I 26221)
VRH II 6522)
VRM I 1001
VRM I 1301
VRH I 6512)
VRX I 6522)
VRS I 1001
VRS I 1301
VRL I 1301
VRM I 701
VRS I 701
1 1 1 1 1 1 1 1 1 1 3 3 2 2 1 1 1 1
700 1000 1300 2600 700 1000 1300 2600 1300 2600 650 1300 650 1300 650 1300 2600 650
10 12 16 26 10 12 16 26 16 26 10 16 10 16 10 16 26 10
3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3
25 30 40 65 25 30 40 65 40 65 25 40 25 40 25 40 65 25
4500 4500 4500 4500 4500 4500 4500 4500 4500 4500 6000 6000 6000 6000 6000 6000 6000 12000
VRL I 1301
VRM I 701
VRS I 701
7
VACUTAP ® VR
VACUTAP® VR –
TECHNICAL DATA.
Step capacity diagram for VR grid
6500
6000
6000 kVA
VRH II 1302*
5500
VRH I 1301*
VRH II 652*
VRH I 651*
VRM I 701
3500
2500
VRM I 1301
2000
1000
VRS III 700Y
VRS II 1002
VRS I 1001
VRS II 1302
VRS II 702
VRS I 1301
VRS I 701
500
0
0 200 400 600 800 1000 1200 1400
Rated through-current Ir [A]
5500
5000
4500
Rated step voltage Uir [V]
4000
VRM II 702
VRM III 700Y
VRM I 701
4800 kVA
3500
3000 kVA
VRL I 1301
VRL II 1302
3000
Rated step voltage Uir [V]
2500
1000
VRS III 1000Y
VRS II 1002
VRS II 1302
VRS I 1001
VRS I 1301
VRS II 702
500
VRS I 701
0
0 200 400 600 800 1000 1200 1400
Rated through-current Ir [A]
10000
9000
Rated step voltage Uir [V]
8000
7000
6000
5000
4000
3000
2000
1000
0
0 50 100 150 200 250 300 350 400 450 500 550 600 650
Rated through-current Ir [A]
10
MORE POWER.
MORE VALUE.
11
Maschinenfabrik Reinhausen GmbH
Falkensteinstrasse 8
93059 Regensburg, Germany
www.reinhausen.com
Please note:
The data in our publications may differ from
the data of the devices delivered. We reserve
the right to make changes without notice.
IN5062036/01 EN – VACUTAP® VR –
F0340001 – 11/17 – uw –
©Maschinenfabrik Reinhausen GmbH 2016