CONTENTS
1. Specifications ................................................................................................2
2. Outline and Dimensions .................................................................................3
3. Operation .....................................................................................................5
4. Wiring Diagram..........................................................................................17
5. Refrigerant Cycle .........................................................................................22
6. Control Block Diagram.................................................................................23
7. Electric Circuit Diagram................................................................................24
8. Trouble Shooting..........................................................................................27
9. Disassembly Instructions ...............................................................................43
1) Indoor Unit..............................................................................................43
2) Outdoor Unit...........................................................................................45
3) Exploded Diagram (Indoor Unit) ...............................................................47
4) Exploded Diagram (Outdoor Unit) ............................................................50
5) Control Box Assembly ..............................................................................56
1. SPECIFICATIONS
◆DSA-151L/DSA-181L/DSB-181L
MODEL
DSA-151L DSA-181L DSB-181L
ITEM
Function Cooling
Class T
Type Flare
2
Connecting
¿‹ Æ˘˜ ˙` Pipe
2. OUTLINE AND DIMENSIONS
Plate
”fi Mounting
`⁄˘˙
453
453
1035
1035 REMOCON ˜
`⁄„«…–‚fi‚
3
Grille Insert
‰˙‡»– ‚Ø– ‚–
◆ DSA-151L/DSA-181L/DSB-181L
Body
‰˙‡»– ‚ ˆ…
1 INDOOR UNIT
322
205
Filter-L Filter-R
Inlet Inlet
277
367
Panel Top
Cabinet
Outlet Handle
4
Discharge 615
◆ DSA-151L/DSA-181L/DSB-181L
Grille
2 OUTDOOR UNIT
800
Indoor Unit
Deodorizing Filter
Removes bad
smells from the air.
Electrostatic Filter Test/Emergency/
Removes dust Remote Switch
particles from the air. Air In Slide to select
the desired position.
Indoor Cover
Fan Direction
(Left/Right)
.
MP
TE
/OFF
ON
DE
MO
P
R. EE
SL
N DI
FA T
D SE
EE RE EL
N SP NC
FA R CA
TE
EN
ER F
TIM OF
ON
5
◆ DSA-151L/DSA-181L/DSB-181L
EMERGENCY REMOTE
Timer
Quick
Airclean
ON
■ There is a switch panel at inside of Front Panel.
At the time of operating, open the Front Panel.
Timer (Yellow) ON (Red) Emergency switch can be used when the remote
Lights during the time Lights when the controller is lost or Testing.
reservation mode. operation is going on.
Remote switch is usually used by remote controller.
Quick (Red) Air clean (Green)
Lights during the
time Quick
Mode.
6
◆ DSA-151L/DSA-181L/DSB-181L
Outdoor Unit
AC Cover
Remove cover to
access the AC
AIR IN connection from
this unit to the
indoor unit.
Connection Wire
Drain Hose
COPPER TUBING
AIR OUT
Service Valves
The indoor and outdoor
units are connected by
copper tubes which are
connected here.
Grounding Screw
Ground the unit here.
Ground Wire
(Not supplied)
7
2 REMOTE CONTROLLER
◆ DSA-151L/DSA-181L/DSB-181L
AUTO Display
Displays information
pertaining to unit.
ON/OFF Button
Press to turn the unit
on or off.
TEMPERATURE Buttons
Press to raise or lower
FAN SPEED Button the desired temperature.
Press to select the fan speed
(High " ", Middle " ", FAN DIR. Button
Low " "). MODE FAN SPEED FAN DIR.
Press to select up/down
direction for fan.
MODE Button
Press to cycle through the modes SLEEP FAN DIR. FAN DIR. Button
TIMER
(Auto/Quick/Cooling/Fan/Dry) Press to select left/right
direction for fan.
SLEEP Button ON/OFF ENTER/ TURBO/MILD
CANCEL TURBO/MILD
Press to set the unit for
the sleep mode. Press to be colder the unit.
COVER
Slide down to access most
of the remote buttons.
Slide down further to
access the battery
compartment.
8
3 REMOTE CONTROLLER DISPLAY
◆ DSA-151L/DSA-181L/DSB-181L
AUTO
FAN Indicators
FAN DIRECTION Indicators
Lights to indicate
Lights to indicate the
the fan speed.
fan direction.
NATURAL Indicator
Lights to indicate the
speeds simulating a breeze.
TIMER Indicators (Include sleep)
Lights to indicate the timer function mode.
Replacing Batteries
+ –
– +
9
4 DESCRIPTION OF FUNCTIONS
OFF-Timer
If you set time in OFF-Timer Mode, the unit will stop at the set time.
Unit ON
ON
Unit OFF
OFF
ON-Timer
If you set time in ON-Timer Mode, the unit will run at the set time.
Unit ON
ON
Unit OFF
OFF
COMP (ON)
❇ Room temperatrue
COMP (OFF) (
< setting temperature
Compressor OFF
Room temperature
-1˚C 0˚C Temperature
(RT-DT) ( > setting temperafure
Compressor ON
(COOLING)
(3) During the time of test operating, Fan (Indoor, Outdoor) and Compressor is running regardless of room
temperature.
Buzzer
If the Indoor Unit Display receive the signal of Remote Controller, you can hear the signal "beep –" or "beep,
beep".
10
Fan Speed (Indoor Unit)
(1) Motor speed (high speed, normal speed, low speed).
(2) Remote controller setting fan speed. (Auto, L, M, H, Natural)
(3) Relation of operating mode between fan speed.
DEHUMI-
FAN ONLY COOL AUTO Quick
DIFICATION
H H H X H H
M M M X M X
L L L X L X
(COOLING)
• DSA-151L/DSA-181L/DSB-181L
H
M
L
11
Sleep Mode
(1) When you are going to sleep, select sleep switch and the unit controls the room to the desired temperature.
(The unit will not operate after 4 hour)
(2) For changing the temperature.
Difference 0.5°C
desired temperature
between room 0.5°C
temperature (°C) 0.5°C
Desired
Temperature
(3) To cancel sleep mode, press the SLEEP button again or press the MODE button once.: the SLEEP
indicator will disappear in the display.
Emergency Operation
(1) When the remote controller is lost, damaged or the battery is discharged, the Emergency operation can be
used to run the unit.
(2) The setting conditions of Emergency operation are as follows.
• Operation mode: AUTO
• Preset temperature: 26°C
• Fan speed: AUTO
12
Frost Prevention of Indoor Unit
When the unit operates at low ambient temperature, frost may appear on the Evaporator. When the indoor coil
temperature is lower than 0°C at the end of 10 minutes of continuous compressor operation from the start, the
microcomputer of the unit stops the compressor to protect the unit from the frost. The control procedure for
indoor coil freeze protection.
ON
Compressor and
OFF
Outdoor Fan
Set Speed
Indoor Fan
0°C 7°C
In normal operation, there is a time delay of three minutes between turn off and turning back on including initial
power up.
When indoor fan motor is on, it always starts at normal speed and then it operates desired speed.
13
Auto Mode
(1) When the room temperature is higher than 28°C (Cooling Mode)
!Compressor and lndoor Fan
ON
OFF
°C (Room temperature-
-1 0 Desired temperature)
H
M
L
(Room temerature-
°C Desired temperature)
0 +1 +2
(2) When the room temperature is lower than 28°C and higher than 22°C (Dehumidification Mode).
(3) When the room temperature is lower than 22°C (Fan only).
14
Dehumidification Mode
(1) When you turn on the unit, the flaps move to the position of keeping the room temperature comfortable.
(2) The air discharge direction is below.
Up/Down On/Off
Left/Right On/Off
ON
OFF
(Room temperature-18˚C)
-1 0
15
Self-Diagnostic Function
The control will contain diagnostic test to verify the integrity of the system.
8 seconds
0.5 second Room air thermistor, connector
1
Indoor coil thermistor, connector
8 seconds
0.5 second Compressor, Electrical parts of
2
comp. Gas leak
16
4. WIRING DIAGRAM
◆ DSA-151L
OUTDOOR UNIT
INDOOR UNIT
17
◆ DSA-181L/DSB-181L
18
1 MAIN ELECTRIC PARTS
◆ DSA-151L
19
◆ DSA-181L
20
◆ DSB-181L
21
5. REFRIGERANT CYCLE
INDOOR UNIT
Evaporator
Connecting pipe
Service valve
Service valve
Compressor
Dryer
Condenser
Propeller fan
OUTDOOR UNIT
Refrigerant flow
Note) If the pipe length exceeds the standard length, add 30g of refrigerant per extra meter.
22
6. CONTROL BLOCK DIAGRAM
◆ DSA-151L/DSA-181L/DSB-181L
Operating Mode
Unit on lamp Remote Signal
receiver Fan Speed
Quick lamp Emergency
Timer Selection
Air-clean lamp
Flap Position
Timer lamp Operation
Temp. Setting
ON/OFF
Turbo/MILD
Indoor coil temp.
Power
Relay
Indoor fan
motor
Outdoor
Compressor
fan motor
23
7. ELECTRIC CIRCUIT DIAGRAM
1 ELECTRIC CIRCUIT DIAGRAM
◆ DSA-151L/DSA-181L/DSB-181L
1
Indoor Unit
2
Fan Motor
3
TERMINAL
L N Y BLOCK
I.D.C
SWING
MOTOR
S TRANS-
SWING FORMER
MOTOR2
SWING
MOTOR1 POWER RELAY
Display Part
Control Part
ROOM AIR COMP COMP
Signal Receiver SENSOR
CMC FMC
Pemote Controller
INDOOR COIL
SENSOR
24
Description
1. After the power ON/OFF button is pressed once, the relay and triac are turned ON or OFF per the remote
control setpoint.
– TRIAC is controlled per the fan speed selection.
– RELAY is controlled per the operation mode selection.
2. If the power ON/OFF button is pressed once more, the relay and triac are turn off and the unit stops
operation.
3. The unit turns on or off according to the temperature setpoint by sensing the room air temperature through
thermistor.
4. If the fan speed selection is set to the auto position, the fan speed is automatically controlled according to the
temperature differance between room temperature and temperature setpoint.
25
2 PCB CIRCUIT DIAGRAM
2
26
Trouble
Is the Is the power NO Check power supply mains
unit display applied to the
normal? or interconnection wires
unit
YES YES
NO Outdoor unit does
not run?(note. 1) Is the
power normal? NO
YES check the voltage between Check the wiring of indoor
L & N of terminal
block
8. TROUBLE SHOOTING
Does
NO YES
the compressor run
normally?
Is the Place the switch
27
press the power ON/OFF switch position NO position to the
YES button on remote controller on switch pannel at "Remote" and then
"Remote" Check it once
YES more
Indoor unit does NO
not run(note 1) YES
NO
Is the unit YES
display Does the
Normal
mormal? beeper beep two
times? Does
NO Check the failure control PCB
code according to status LED repeat one
check the YES NO
the self diagnostic second "on and
(note 2) connecting off"?
YES point of
magnetic • control PCB fault
NO Is the display
contactor • Micom or reset
all off? IC fault YES
YES
check the failure
code according to • Check the connector on display • Check the remote signal receiver
the self-diagonostic PCB connected to control PCB • Check the connection between signal
(note 2) • Check the display PCB itself receiver and control PCB
Note 1)
!Neither indoor unit nor outdoor unit runs.
Check the following points first. (There are following case in normal operation)
a. Is the timer mode set the "timer ON".
b. Is the timer mode set the "timer-OFF" and the time had passed?
@ Neither outdoor fan nor compressor runs while indoor fan runs.
Check following points first. (There are following cases in normal operation)
a. Is the temperature set point suitable?
b. Has the 3 minutes time guard for compressor operated?
Self-Diagnostic Function
◆ DSA-151L/DSA-181L/DSB-181L
1) Error Code 1
!Check the connector of room air thermistor. (or connecting wire)
@ Check soldering of connecting on control P.C.B. (Error of soldering or short)
# Check the resistance of room air thermistor.
28
Neither Indoor Unit nor Outdoor Unit Runs
YES
YES
Press the ON/OFF switch of
NO
Remote Control Check according to
self Diagnostic function
Is the indoor unit display all off?
29
Outdoor Unit Runs but Indoor Unit Do Not Run
YES
Normal
Run again
30
Outdoor Fan Do Not Run
31
Only Compressor Do not Run
OK
32
Outdoor Fan and Compressor Do Not Run
Check compressor,
outdoor fan motor individually
33
PCB DRIVING DESCRIPTION
Power Supply (1)
0.1µF/250V
BD1
AC 220V
+ CE1
VAR 1000/35V
POWER
TRANS
DC 12V
3 1 3 1
7805 7812
CC3 2 + 2
0.1 CE3 CC2 CE2
100/25V 0.1 470/16V CC1
DESCRIPTION
DC Power Supply in circuit needs +12V and +5V. +12V is used for Compressor Driving Relay, Triac Driving
Photo Triac, Buzzer Driving Swing, Sweep Motor, and LED Display. AC voltage of secondary Power
Transformer is rectified by Bridge Diode, and it is filtering by Main Condensor CE1.
Filtered DC voltage is about +17V, is regulated +12V DC by Regulator IC7812.
And it is regulated +5V DC by Regulator IC7805.
VAR is surge filter and CE2, CE3, CC2, CC3 is Noise filter.
35
Oscillation (2)
19
20 X-TAL
8MHz
DESCRIPTION
VDD-10%
VSS+10%
Fig 2-1
36
Sensor(3)
25
3
R19
4 ROOM: SENSOR
MICOM CC8 CN8
DESCRIPTION
-5 1.12
0 1.37
15 2.22
25 2.79
40 3.52
Table 3-1
37
Triac Driving (4)
12V
R5 100 L1
L AC220V
TRIAC
SM3
KID 65004 JZ47 SN1 0.1µF/120OHM
MICOM TLP560J
38
R4 TO MOTOR
1K
DESCRIPTION
Number 38 Terminal of Micom is put out Pulse Output, by way of Buffer it is driving Photo Triac TLP560 and
then Triac SM3JZ47 is supplied Trigger Signal.
Trigger Test of Triac is detected Zero Cross Part of AC input and it is triggered from Zero Cross part to Time
delay part according to Fan Speed. (Ref. Fig 4-1) SN1 is Snubber.
AC220V
TRIGGER
LOW
LOW SPEED
SPEED MEDIUM SPEED
MEDIUM SPEED HIGH
HIGH SPEED
SPEED
MOTOR
INPUT
Fig 4-1
38
Selecting Mode (5)
R16
10K
CN1
13
R15 1K
EMERGENCY S/W
CC6
MICOM 0.01
DESCRIPTION
POSITION MODE
Close EMERGENCY
Open REMOTE
Table 6-1
39
Micom Power Supply (6)
Vcc
5V
CE2
42
10µF/16V
CC1
MICOM 22 104
21
DESCRIPTION
MICOM Power is supplied 5V at Number 42 using Digital, Number 22 using Reference of A/D Converter.
CE2 is Ripple filter and CC1 is Noise filter.
40
Reset (7)
5V 5V
MICOM R10
R9
1K 5.6K
3 1
18 7042P
+
CC3 CE1
104 4.7µF/50 2 RESET IC
DESCRIPTION
Voltage less than about 0.8V put in Micom Terminal of Number 18 and then Micom reset. Reset IC detect
Power ON and Voltage less than 4.2V, and then send Reset Signal. There is a Manual Reset S/W to reset
manually if necessary.
Vcc (+5V)
4.2V
t
DELAY TIME
FOR POWER ON
H RESET
L t
POWER
ON
41
Function Selecting (8)
Test
30
R14
1K
JS5
MICOM 29 R13 1K
JS3
28
R12 1K
JS4
27 RA
R11 1K
CA1
DESCRIPTION
SHORT OPEN
Table 9-1
42
9. DISASSEMBLY INSTRUCTIONS
1 INDOOR UNIT
PROCEDURES PHOTOS
1. Stop the Air conditioner and disconnect the power cord from the wall
outlet.
Fig 2
3. Removing the Control Box.
After doing above procedures:
!Disconnect indoor room and coil thermistors. (Fig 3)
@ Disconnect the fan motor lead wire from connection at the main
PCB. (Fig 3)
# Disconnect the swing motor connection wire. Fig 3
$ Loosen a screw for fixing ground wire.
% Loosen two screws for fixing the body.
43
PROCEDURES PHOTOS
Fig 7
Fig 8
44
2 OUTDOOR UNIT
¡ DSA-151L
PROCEDURES PHOTOS
1. Basic Procedures
!Stop the air conditioner and pull out power plug from wall outlet.
@ Remove CABINET TOP COVER. (Loosen ten screws)
# Remove CABINET SIDE COVER. (Loosen six screws)
$ Remove CABINET FRONT. (Loosen six screws)
Fig 1
Fig 3
3. Removing Motor Capacitor and Compressor Capacitor
!Do basic procedure.(!~$)
@ Diconnect lead wire from the Motor capacitor and compressor
capacitor.
# Loosen two screws for fixing the capacitor bracket.
$ Remove Motor capacitor and compressor capacitor. Fig 4
Fig 7
45
¡ DSA-181L/DSB-181L
PROCEDURES PHOTOS
1. Basic Procedures
!Stop the air conditioner and pull out power plug from wall outlet.
@ Remove CABINET TOP COVER. (Loosen ten screws)
# Remove CABINET SIDE COVER. (Loosen six screws)
$ Remove CABINET FRONT. (Loosen six screws)
Fig 1
Fig 3
3. Removing Motor Capacitor and Compressor Capacitor.
!Do basic procedure.(!~$)
@ Diconnect lead wire from the Motor capacitor and compressor
capacitor.
# Loosen two screws for fixing the capacitor bracket.
$ Remove Motor capacitor and compressor capacitor. Fig 4
46
3 EXPLODED DIAGRAM (Indoor Unit)
¡ DSA-151L/DSA-181L/DSB-181L
47
¡ DSA-151L/DSA181L/DSB-181L Parts List (Indoor Unit)
48
No PART CODE PART NAME Q'TY SPEC REMARK
49
4 EXPLODED DIAGRAM (Outdoor Unit)
¡ DSA-151L/DSA-181L
50
¡ DSA-151L/DSA-181L Parts List (Outdoor Unit)
13 3102600100 HANDLE R 1 PP
17 3102600200 HANDLE L 1 PP
51
No PART CODE PART NAME Q'TY SPEC REMARK
5
3100016200 PIPE DISCHARGE ASS’Y 1 CU 16 ¡T̈0.8 DSA-151L
21
5
3100016600 PIPE DISCHARGE ASS’Y 1 CU 16 ¡T̈0.8 DSA-181L
52
¡ DSB-181L
53
¡ DSB-181L Parts List (Outdoor Unit)
13 3102600100 HANDLE R 1 PP
17 3102600200 HANDLE L 1 PP
54
No PART CODE PART NAME Q'TY SPEC REMARK
3
21 3100016400 PIPE DISCHARGE ASS’Y 1 CU 8 ¡T̈0.8
55
5 CONTROL BOX ASSEMBLY
¡ DSA-151L/DSA-181L/DSB-181L
56
¡ DSA-151L/DSA-181L/DSB-181L
DSA-151L/DSA-181L 1 3100058320
1 CONTROL BOX ASS’Y
DSB-181L 1 3100058210
DWA-5423 1 5EPK633110
3 PCB TRANS ASS’Y
DWA-220V 1 5EPV633110
DSA-151L/DSA-181L 1 3104300120
14 CONTROL PCB ASS’Y
DSB-181L (COOL/50Hz) 1 3104300110
57