ESD-1:

+ Cause:
1. Manual ESD_1 push button at WHP DH01 strategic locations.
2. Manual ESD_1 push button at drilling rig during SIMOPS.
3. Manual ESD_1 push button at FPU.
4. Confirmed fire detection in E&I Room
5. Confirmed fire detection in Temporary Shelter (in Manned mode)
6. Confirmed high high gas in E&I Room
7. Confirmed high high gas in Temporary Shelter (in Manned mode)
8. Confirmed high high gas in HVAC air intake

+ Effect:
1. Isolate UPS/batteries
2. Isolate non-certified telecom equipment & circuit
3. Initiate ESD-1 alarm to Jack-up Rig
4. Trip 6.6 kV Switch Gear
5. Feed forward ESD-1 signal to FPU
5. Shutdown HVAC system
6. Close all SCSSVs (with time delay)

ESD-2

+ Cause:
1. Manual ESD_2 push button at WHP DH01 strategic locations.
2. Manual ESD_2 push button at drilling rig during SIMOPS.
3. Manual ESD_2 push button at FPU.
4. Confirmed fire detection in process area
6. Confirmed high high gas in process area

+ Effect:
1. Initiate ESD-2 alarm to Jack-up Rig
2. Feed forward ESD-2 signal to FPU
3. Open all BDVs
4. Shutdown and inhibit SDG.

PSD
+ Cause:
1. Manual PSD push button at WHP DH01 strategic locations.
2. Manual PSD push button at drilling rig during SIMOPS.
3. Manual PSD push button at FPU.
4. Production Separator pressure high high (HOLD)
5. Production Separator level high high (HOLD)
6. Flare scrubber level high high
7. Instrument gas header pressure low low
8. Liquid export pipeline pressure high high
9. Liquid export pipeline pressure low low
10. HP hydraulic header pressure low low (with time delay)
11. MP hydraulic header pressure low low (with time delay)
12. Communication loss between WHP & FPU (with time delay)

+ Effect:
1. Initiate PSD alarm to Jack-up Rig
2. Feed forward PSD signal to FPU
3. Close all SSVs, WVs, SDVs, XVs, SVs to isolate inventory.
4. Trip gas cooler fans
5. Trip all chemical injection pumps

USD

+ Cause:
1. Manual shutdown from local unit or remotely from FPU CCR
2. Unit malfunction or process upset.
3. Confirmed high high gas in SDG air intake/enclosure.

+ Effect:
1. Specific alarm to HMI
2. Shutdown effected unit(s).
3. Close effected SSVs, WVs, SDVs, XVs
3. Shutdown and inhibit SDG.