You are on page 1of 2

6F2S1910(Rev. 1.

6)

GR-200 series IED CAUTON


Earth
GETTING STARTED A terminal of the equipment shall be earthed.
This is a guide of GR-200 series relays. See the below Operating environment
instruction manuals to read the settings, specifications, The equipment shall be used in the environment
etc., respectively. specification condition; e.g. temperature and humidity.
Doc.# Models GR200 Instruction manuals Ratings
Before applying AC voltage & current or DC power to
6F2S1915 GRZ Distance Protection IED
the equipment, check the rated current & voltage values.
6F2S1914 GRL Line differential Protection IED Printed circuit board
6F2S1933 GRB Busbar Protection IED(Decentralized) Do not insert or remove printed circuit boards when the
equipment is powered on, as this may cause the
6F2S1931 GRB Busbar Protection IED(Centralized)
equipment to malfunction.
6F2S1924 GRT Transformer Protection IED External circuit
6F2S1927 GRD Multi functional Protection IED When connect equipment’s output contacts to external
6F2S1926 GBU Bay Control IED circuits, check supply voltage used there, because the
connected circuits shall be prevented from overheating.
6F2S1950 GRS Fault detector relay IED Connection cable
In addition to the instruction manuals, there are other Carefully handle cables without applying excessive
service manuals shown in the following table. See the force.
service manual when an applicable work is required. Modification
Doc.# GR200 Service manuals Do not modify this equipment, as this may cause the
Installation handbook for rack mounting, cable work, equipment to malfunction.
6F2S1954 etc. Short-wire (short-bar) on the PSW
-for type using compression
6F2S1955 Guide for replacement terminals <The one between terminal screw No.35 and No.37>
of inner modules Do not remove the short-wire between terminal screw No.
6F2S1956 -for type using ring terminals 35 and No. 37 during in-service.
Safety Precautions <The one between terminal screw No.37 and FG>
Before the installation or use of this equipment, read this Never remove the short-wire (Short-bar) between terminal
document and understand fully. This describes the safety screw No. 37 and FG.
precautions for these for this equipment. Note: Refer to Appendix: Notes for the dielectric voltage test
Explanation of symbols used of each GR200 instruction manual, when the dielectric
Signal words such as DANGER, WARNING, and test is required.
CAUTION, will be followed by important safety
information that must be carefully reviewed.
DANGER indicates that death, severe personal
injury or substantial property damage will result if
proper precautions are not taken.
WARNIG indicates that death, severe personal
injury or substantial property damage can result if
proper precautions are not taken.
CAUTION indicates a potentially hazardous
situation which if not avoided, may result in injury.
DANGER
Current transformer circuit (CT)
Never allow the current transformer (CT) secondary
circuit connected to this equipment to be opened while
the primary system is alive. Opening the CT circuit will
produce a dangerously high voltage.
WARNIG
Exposed terminals
Do not touch the terminals of this equipment while the
power is on, as the high voltage generated is dangerous.
Residual voltage
Hazardous voltage can be remained in the circuit right
after switching off the power supply. Wait more than
30sec until the residual voltage will discharge under
safety level.

Getting started
- 1 -
6F2S1910(Rev. 1.6)

Unpacking & storage Case description


•Unpacking
Upon receipt, open the relay (IED) packing and inspect
the physical damage. LED indicators
Ensure that the following items are included: LCD
- Relay (IED) unit Pocket sheet
- Test record: One report sheet label for LEDs
- Getting started: This paper
- Instruction manuals and
service manuals: CD-ROM
- Flange cover: Left cover and right cover Operation keys
- Function keys label: One label sheet
- LEDs Label: One label sheet Pocket sheet label for
Function keys
- White-plastic-sheet: Two sheets† Function keys
If there is any noticeable physical damage, or any of the
Monitoring jacks USB port
above contents are missing, please contact the Toshiba
or its agent. The contact information is described in this
paper.
Example: (19’’ x 3/4 size case)
†: The white ones are just provided to lock the screws
Power Binary input and output Communication ports
on the flanges. These are not provided when the case is supply (BI, BO)
produced in 1/1 size and flush-mounting type. Type using Compression
terminals

•Hardware nameplate
Confirm rated currents and voltages on Hardware
nameplate in accordance with user conditions.

•Storage
If the equipment is not installed immediately, it should
be repacked in the original boxes and should be stored
in dry and clean condition.
Recommended storage condition:
- Temperature: 0°C to +40°C
- No condensation Type using Ring terminals

•Disposal
When disposing this equipment, please follow the local
regulations of industrial disposal. For information of
disposal, please contact the local dealer or sale staff of
Toshiba Energy Systems & Solutions Corporation.

Contact information
Toshiba Energy Systems & Solutions
Corporation (ESS)
Quality Assurance section
Power Systems Protection & Control Department Protective earth CT and VT
inputs
Fuchu Operations
1, Toshiba-cho, Fuchu, Tokyo 183-8511 •Protective earth
Japan Make connections between the earthing screw
terminal (M5) and the protective earth of the panel
Toshiba Transmission & Distribution •CT/VT connections
Systems (TTDV) Ltd. Connect wires with screwed terminals (M3.5). For
Sales & Engineering Group details, refer to each GR200 Instruction manuals. Use
Thang Long industrial Park, Dong Anh Dist., Hanoi, compression plug (ring tongue) type terminals.
Vietnam •BI/BO connections
IO configuration label shows the connecting
Inquiry positions for binary input and output signals. For
https://www.toshiba- more detail, see each GR200 Instruction manuals.
energy.com/en/transmission/contact/index.htm

Getting started
- 2 -