Abstract— This paper discusses Dissolved Gas Analysis II. DISSOLVED GAS DIAGNOSTIC METHOD
(DGA) in transformer oil from two 69/24 kV 24/32 MVA The DGA analysis is an important method widely used to
installed in urban areas. By detecting unusual increasing gas, monitor transformers in service. The Gas chromatography
then transformer oil samples were collected frequently
according to Standards. First transformer was failed by inside
has been used for DGA analysis. Chromatography is a set of
short circuit. All loads were transfer to second transformer. laboratory techniques for separating mixture of gases. There
The risk of failure on last transformer is very high. Standards are two main methods to find out abnormal situation within
used for DGA interpretation is IEEE C57.104. Evaluation of transformer using DGA. The first method uses the absolute
fault type used Key gas method, Doernenburg ratio, Rogers value of the gas. The other method uses the gas ratio.
ratio and Duval Triangle.
Evaluation using individual and TDCG concentration
Keywords—transformer, Dissolved Gas Analysis, Duval
triangle, key gas method A four-level criterion has been developed to classify risk of
transformers[2]. The criterion concentration for separate gases and the
I. INTRODUCTION total concentration of all combustible gases are shown in Table I.
Power transformer is one of the most importance equipment in
electrical network. The health of a power transformer depends on the TABLE I. GAS CONCENTRATION
condition of its major components. Dissolved gas analysis (DGA) is Status
one of the transformer assessment technique to determine the Condition Condition Condition Condition
condition of transformer. It can detect certain gases generated in an 1 2 3 4
oil-filled transformer in service. The two principal causes of gas Hydrogen(H2) 100 101-700 701-1800 >1800
formation within an operating transformer are cellulosic Methane(CH4) 120 121-400 401-1000 >1000
decomposition and oil decomposition [1,6]. The thermal
decomposition of oil-impregnated cellulose insulation produces Acetylene(C2H2) 1 2-9 10-35 >35
carbon oxides(CO,CO2) and some hydrogen or methane. Ethylene(C2H4) 50 51-100 101-200 >200
Transformer oil contains a mixture of many different hydrocarbon Ethane(C2H6) 65 66-100 101-150 >150
molecules. The decomposition process of these hydrocarbons caused Carbon
by thermal or electrical faults are highly complex. Gas generation in 350 351-570 571-1400 >1400
Monoxide(CO)
transformer oil is shown in Fig.1 [1,5]. Carbon
2500 2500-4000 4001-10k >10k
Dioxide(CO2)
TDCG 720 721-1920 1921-4630 >4630
Electrical-Arcing C2H2
Fig. 1. Gas generation chart.
Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on June 08,2021 at 17:48:34 UTC from IEEE Xplore. Restrictions apply.
2020 International Conference on Power, Energy and Innovations (ICPEI)
October 14-16, 2020, Chiang Mai, THAILAND
Limit(ppm)
Key gas
L1 2L1
TABLE IV. FAULT DIAGNOSIS BY DOERNENBURG RATIO METHOD D2 High energy discharge
DT Mixture of electrical and thermal faults
Fault type R1 R2 R3 R4
Thermal T1 Thermal fault, T<300 °C
>1.0 <0.75 <0.3 >0.4
decomposition
T2 Thermal fault, 300<T<700 °C
Corona <0.1 Insignificant <0.3 >0.4
T3 Thermal fault, T>700 °C
Arcing >0.1& <1.0 >0.75 >0.3 <0.4
166
Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on June 08,2021 at 17:48:34 UTC from IEEE Xplore. Restrictions apply.
2020 International Conference on Power, Energy and Innovations (ICPEI)
October 14-16, 2020, Chiang Mai, THAILAND
Transformer No.1
The DGA sample of transformer no.1 are given in Table
VII. They are interpreted using methods as follows.
A. Evaluation using individual and TDCG concentration
From DGA data on Table VII, The highest gases are H2,
CH4, C2H2, C2H6 and TDCG. According to the information,
transformer no.1 would be classified as Condition 4 [8,9].
The two gases, Acetylene and Hydrogen, indicate that this
transformer is in severe condition and immediate attention is
required.
B. Evaluation using key gas method
Fig. 4. Duval’s triangle result of transformer 1.
The percentage of TDCG (%TDCG) are calculated and
shown as a graph in Fig. 3. The results shown high amounts Transformer No.2
of H2 and CH4 caused by partial discharge [7]. The gases
were likely to increase. Therefore, this transformer must be The DGA sample of transformer no.2 are given in Table
inspected continuously and maintained. VIII. They are interpreted using methods as follows.
A. Evaluation using individual and TDCG concentration
%TDCG
From DGA data on Table VIII, The highest gases are H2,
100 CH4, C2H2, C2H6 and TDCG. According to the information,
80.6 transformer no.1 would be classified as Condition 4 [8,9].
80 The two gases, Acetylene and Hydrogen, indicate that this
transformer is in severe condition and immediate attention is
60
required.
40 B. Evaluation using key gas method
14.2 The percentage of TDCG (%TDCG) are calculated and
20
4 shown as a graph in Fig. 5. The results shown high amounts
1.1 0.1 0.1
0 of H2 and CH4 caused by partial discharge [7]. The gases
CO H2 CH4 C2H6 C2H4 C2H2 were likely to increase. These results are the same as
transformer no.1. Therefore, this transformer must be
Fig. 3. Key gas result of transformer 1. inspected continuously and maintained.
167
Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on June 08,2021 at 17:48:34 UTC from IEEE Xplore. Restrictions apply.
2020 International Conference on Power, Energy and Innovations (ICPEI)
October 14-16, 2020, Chiang Mai, THAILAND
V. CONCLUSION
%TDCG The DGA results from two transformers in service are
reported and its interpretation is given with reference to
100.0 86.9 prevailing standard. The DGA results used four analytical
80.0 methods. The results are summarized that both transformers
should be replaced immediately and the results shows a very
60.0 high risk of failure.. However, since the building was unable
to immediately turn off the electricity supply, the transformer
40.0
oil samples were frequently collected. In this case study, the
20.0 9.7 individual and TDCG concentration and key gas method are
0.9 2.4 sufficient to indicate the fault in transformers. The
0.0 engineering judgement can be applied to determine the final
CO H2 CH4 C2H6 C2H4 C2H2 sampling interval and operating procedure. In this case , It
should be consider removal from service immediately.
Fig. 5. Key gas result of transformer 2.
The results from ratio methods are similar for both
C. Evaluation using Doernenburg ratios transformers. The analysis results from the Doernenburg
ratio and the Duval triangle showed that partial discharge
The results from the Doernenburg ratio in Table XI show occurred. The three gas ratio methods(Doernenburg ratio,
that PD occurs.
Rogers ratio and Duval’s triangle) can’t provide complete
TABLE XI. DOERNENBURG RATIO OF TRANSFORMER 2 diagnosis for the fault present in these transformers.
168