You are on page 1of 18

Article

Transactions of the Institute of


Measurement and Control
Real time assessment of power quality 1–18
Ó The Author(s) 2020

issues in 11 kV/440 V distribution Article reuse guidelines:


sagepub.com/journals-permissions
DOI: 10.1177/0142331220913009
feeder using distribution static journals.sagepub.com/home/tim

synchronous compensator

Suresh Srinivasan1 , Murugaperumal Krishnamoorthy2,


RK Pongiannan3 and S Jeyasudha4

Abstract
The effects of power quality (PQ) issues in a distribution feeder occur due to abnormal load condition. In this paper, first, the real time PQ issues in an
11 kV/440 V distribution feeder are measured and analyzed by PQ analyzers. The sudden load fluctuations in the distribution system result in different
PQ issues such as voltage sag/swell, transient, flicker and harmonics. Then, an improved interactive distribution static synchronous compensator (D-
STATCOM) is installed in distribution feeder to mitigate the PQ issues. A novel control algorithm will operate the interactive D-STATCOM in voltage
control mode (VCM) or current control mode (CCM). At normal operating conditions, the D-STATCOM operates in CCM, during abnormal condition
the D-STATCOM will operates in VCM to mitigates the PQ issues. The D-STATCOM is modeled and simulated in MATLAB-SIMULINK environment.
The field programmable gate array (FPGA)-based laboratory prototype D-STATCOM has been developed to validate the function of the controller.

Keywords
Power quality, distribution static synchronous compensator, adjustable speed drive, point of common coupling, voltage control mode, current control
mode, total harmonic distortion, short-term flicker

Introduction case studies are carried out to classify effective custom power
devices (CPD) for distribution generation system. Based on
The power quality (PQ) issues are induced in distribution sys- the analysis, it is identified that D-STATCOM can be the
tem due to the sudden varying load like electric arc furnaces, potential choice (Hossain et al., 2018). The control strategies
resistance welding, and induction motor and so on. Also, have been addressed for the operation of D-STATCOM, and
adjustable speed drive (ASD) alters the load current consist- mitigation methods only for the limited PQ issue (Khoshooei
ing of harmonics, reactive power component, neutral current, et al., 2018).
unbalanced currents, direct current (DC) offset. These PQ The design of D-STATCOM controller to regulate its DC-
issues affect the performance of distribution system as well as side capacitor voltage and feeder reactive power is discussed.
the protection and control devices. To mitigate these power A control technique is developed to reduce the inverter switch-
quality issues in distribution system dynamic voltage restorer ing losses and harmonics. The technique addressed is applica-
(DVR), unified power quality conditioner (UPQC) and ble during normal condition and its dynamic performance
D-STATCOM are utilized. Generally, the DSTATCOM can
mitigate the PQ issues such as harmonic elimination, load
balancing, power factor correction, and voltage regulation 1
Department of Electrical & Electronics Engineering, Annamacharya
based on the load requirement. In the past decade, the D- Institute of Technology & Science, India
STATCOM-based PQ mitigation system has been developed 2
Research Scholar, Department of Electrical Engineering, Pondicherry
by many researchers. Engineering College, Pondicherry University, India
3
In the distributed generation system, micro grid system, Department of Electrical Engineering, SRM Institute of Science and
PQ issues exists due to light emitting diode (LED) lamp, Technology, India
4
underground cables, and waveform distortion within the Department of Electrical Engineering, K. Ramakrishnan College of
ranges of 2KHz to 150KHz (Ronnberg and Bollen, 2016). Technology, India
The D-STATCOM is for the mitigation of unbalances in dis-
Corresponding author:
tribution system with microgrid application. A controller Suresh Srinivasan, Department of Electrical & Electronics Engineering,
design based on the mathematical model helps to find positive Annamacharya Institute of Technology & Science, New Boyanapalli,
and negative sequence component errors (Wang et al., 2018). Rajampet, Andhra Pradesh, 516126 India.
The PQ issues evaluation schemes, an optimal solution, and Email: sureshsrinivasan0719@gmail.com
2 Transactions of the Institute of Measurement and Control 00(0)

gets affected during abnormal condition (Ziaeinejad and in frequency domain with the standard test signal. The char-
Mehrizi-Sani, 2018). A hybrid modulation (HB) technique is acteristics of flicker meter were determined for amplitude and
implemented for cascaded H-bridge converter that is utilized frequency modulation of the input signal also with harmonics
in D-STATCOM application. This proposed topology with components (Majchrzak and Wiczynski, 2012).
self-voltage balancing mechanism has the advantage of swap- Implementations of a digital flicker meter for a voltage
ping laid off switching states and free from additional control- sample input to a software-based algorithm calculate the
ler. By increasing the number of switches the switching and short-term flicker (Pst). The flicker meter proposed algorithm
conduction losses gets increase which in turn reduces the per- performs accurately for fluctuation having low frequency
formance of the system (Vural, 2016). (Geiger and Halpin, 2017). Measurement of voltage variation
A novel coifletfraclet classifier is addressed to extract in distribution feeder has been carryout in two types as Pst
the characteristics feature of events for applied voltage sag. indicator and voltage fluctuations indices. Current variation
To obtain the maximum classification accuracy, affair correlated with the voltage and frequency fluctuation is
information is derived from time and frequency domain. observed from the time plot of Pst indicator (Wiczy’nski,
Comparisons were made between the various types of clarifier 2008). The method of converting voltage fluctuating indices
to find quickly the detection and classification of voltage sag into Pst indicator and possibilities of recalculating the Pst
with higher accuracy and causes of such events (Saini et al., measurement into voltage fluctuating indices is detailed.
2019). The design and implementation of a Mamdani fuzzy (Wiczynski, 2017).
proportional, integral, derivative power system stability con- The measured value that includes the perception of short-
troller to achieve the stability of the system are discussed. The term flicker (Pst) with period of severe voltage fluctuations
hybrid controller provides the robust control during distur- were noted and marked. The existence of the second harmo-
bances and recovers the steady-state condition in short dura- nic components can directly increase severity of voltage
tion by adopting the switch control approach. The stability flicker. Simulation of semi-converter has been done to acquire
analysis of a system for certain power system issues are dis- one even harmonic for justification with the experiment.
cussed (Gao et al., 2019). The harmonic estimation technique Results illustrate the proportional relationship between the
of numerous measured parameters for a time varying signal is Pst and percentage of second order harmonics (Goh and
discussed. This proposes iterative observer algorithm trade- Radzi, 2017). Numerous topologies for D-STATCOM are
off between the accuracy and change in amplitude (Ujile presented as a comprehensive study (Singh et al., 2014).
et al., 2015). The advancement of power electronics compo- Several control techniques and topology of D-STATCOM
nents provides solution to voltage fluctuation. The D- were presented for PQ enhancement in the three-phase, three-
STATCOM with control technique has the ability to compen- wire and four-wire distribution networks (Mahela and Shaik,
sate the reactive power and PQ control in distributing 2015; Zaveri et al., 2012). Different inverter topologies for D-
systems. STATCOM have been demonstrated and compared based on
The PQ measurements were carried out in wind generator the performance (Arindam Ghosh and Joshi, 2005).
to analyze the quality of power. The measured PQ events, har- The novel mitigating strategy using a Kalman Filter-based
monics are mitigated along with power factor correction by algorithm for the extraction and tracking of voltage distur-
using shunt compensator. The distribution system paved way bances with fast response and accuracy is presented. The vol-
to have a steep increase in PQ issues. One of the main non- tage flicker due to an arc furnace is mitigated (Elnady and
linear loads is which will induce voltage disturbances results Salama, 2005). The PQ improvement to mitigate the voltage
in degraded quality of power (Madhulingam et al., 2017). The disturbances at a weak node using D-STATCOM is developed
arc furnace operation induces high flicker level in the distribu- to eliminate the voltage distortion based on moving half-cycle
tion system (Maksi et al., 2016). To compensate the reactive average filter (Ghosh and Ledwich, 2003). Space vector mod-
power absorption and to reduce the harmonics, smart loads ulation method to reduce the switching harmonics, capacitor
were used to correct the power factor (Murugaperumal et al., voltage control to damp LC resonance and to regulate grid
2017). For analyzing the PQ of a network, simultaneous mea- current is discussed (Wang et al., 2012). A control algorithm
surements of several quantities at the point of common cou- to generate reference load voltage to enhance the performance
pling (PCC) are needed (Cristaldi et al., 2003). To reduce the of voltage-controlled D-STATCOM is presented (Kumar
PQ problems, a digital signal processing based implementa- and Mishra, 2014a). The multifunctional D-STATCOM with
tion was proposed (Faifer et al., 2011). To improve the PQ control algorithm having the ability to mitigate voltage and
and to have a constant output voltage, for a variable fre- current related PQ issues is addressed (Kumar and Mishra,
quency drive with power factor correction was developed 2014b).
(Gonzalez-Ramirez and Cruz-villar, 2017). The automatic From the literature reported, the control algorithm is
power factor correction (APFC) with booster circuits was implemented using digital signal processor (DSP) based
proposed for power measurement and to reduce the PQ issues (Pongiannan et al, 2010) realization. Due to the advancement
in the network. in very large scale integration (VLSI) technology, the field
Flicker meter is an instrument designed to measure the programmable gate array (FPGA) has been used as a digital
obnoxiousness of flicker. The most predominant and com- controller implementation (Pongiannan et al, 2006, 2011a,
monly accepted standards for flicker are IEC641000-4-15& 2011b & 2013). Hence, in this paper D-STATCOM for 11kV/
IEC 61000-4-15 2010. The flicker meter output is a value of 440V distribution system is modeled and implemented to
short-term flicker (Pst) severity indicator describes the numer- mitigate the PQ issues. This article is organized as follows.
ical simulations that construct the processing of flicker meter Chapter 2 discuss about the measurement of PQ issues in
Srinivasan et al. 3

Table 1. Feeder parameters in PEC distribution system.

S. no. Total Real power/ Reactive power/ Voltage (VL) Phase current Power factor
power phase (kw) phase (kVAr) (Volts) (Amps) (cosV)
(kw)

Tr-1 120 40 10 440 280 0.98


Tr-2 120 40 10 440 210 0.9
Tr-3 120 40 10 440 235 0.82

Figure 1. Power quality parameters. (a) Phasor measurement, (b) Phase voltage in RMS value obtained from transformer-1.

11kV/440V distribution feeder. Chapter 3 discuss about the unbalances. The 3F load connection is rescheduled; the repla-
PQ assessment and mitigation using D-STATCOM. Chapter cing of the power cable is done to obtain balance load condi-
4 discusses the experimental verification of a FPGA-based tion and reduce such high neutral current. This issue is
prototype D-STATCOM. Finally, the conclusions are sum- rectified by proper load sharing and replacing the cable. The
marized in Chapter 5. neutral current gets reduced from 87.3Amps to 0.9Amps,
shown in Figures 3(a) and (b).
Measurement of PQ issues in 11kV/440V
distribution feeder Voltage Disturbances
The distribution system is energized by 3F, three wire system, The PQ analyzer is designed as per the standard specified
which is connected through three step-down distribution by international electrotechnical commission (Moreno-Garcia
transformers, each having a power capacity of 200kVA; the et al., 2017) to detect the PQ disturbances. The PQ events such
connected load details of the transformer are given in Table 1. as voltage sag, in-rush current, voltage distortion, unbalances,
The power qualities issues like unbalance in voltage magni- flicker and interruptions are determined and demonstrated
tude, sag/swell, transients, flicker and harmonics are mea- successfully. The detection of voltage sag by PQ disturbance
sured and analyzed. detection system and the changes in the magnitude from 421V
Figure 1(a) shows the phasor measurement obtained to 409V values are illustrated in Figure 4.
from transformer-1. It indicates that the voltage and current
phasor quantity of each phase has the phase shift of exactly
120° and the current magnitude of each phase gets varied.
Current unbalances
Figure 1(b) shows the instantaneous phase voltage wave- The three-phase unbalanced system induces serious PQ issues.
form is obtained from the measurement point of transfor- Heavy single-phase load, improper distribution of single-
mer-1; it is maintained almost constant at balancing load. phase loads in three-phase distribution system is the major
Figures 2(a) and (b) show the phasor measurement and reason for imbalance. Ratio of negative sequence component
phase voltage magnitude in root main square (RMS) value and positive sequence component is termed as unbalance.
obtained from transformer-1. Unbalance may be voltage or current components that are
Figure 2(a) shows the voltage phasor angle is displaced usually expressed in percentage. This unbalanced system car-
exactly by 120° and the magnitude changed due to load ries the existence of a negative sequence that will be adverse
4 Transactions of the Institute of Measurement and Control 00(0)

Figure 2. Power quality parameter measurement (a) & (b) Phasor phase voltage magnitude in RMS value and instantaneous phase voltage waveform
obtained from transformer-1.

Figure 3. Amplitude of neutral current from transformer-1. (a) & (b) Comparison of neutral current for unbalanced and balanced condition.

to all three phase loads, effecting the power factor. A concern are categorized into two types: impulsive and oscillatory tran-
with power system is if unbalance increases then the cost of sients. Abrupt non-fundamental frequency change in steady
energy increases, which is caused by voltage asymmetry, state condition with unidirectional polarity of voltage, cur-
which may be harmful to the consumer’s load, reducing the rent, or both on a power line is known to be impulsive transi-
performance of the distribution system. Industrial drives and ent. This transient is generated during starting and
power electronics equipment are sensitive to the asymmetric disconnecting of heavy loads, switching on/off of a power fac-
supply voltage and ultimate deterioration of PQ. tor improvement capacitor or lighting. An oscillatory transi-
Figure 5(a) illustrates the variation of phase currents when ent is bidirectional variation in voltage, current, or both on a
the motor is operated. The measurements of phase currents power line, which occurs due to resonances during switching.
An, Bn, and Cn are carried with 600 samples in the time span Notching is also a PQ event that occurs during commutation
of 15 minutes. Fig. 5(b) illustrates the unbalances in the phase in single or three phase rectifiers. Figure 6(a) illustrates the
current An, Bn, Cn. It is observed that, the unbalance is 8.5, comparison of phase voltage and phase current with respect
9.2 and 11.2% for 500 samples with the measurement time to time in minutes for a 12-pulse three-phase rectifier load.
span of seven-minute. It is also observed, the that this unba- The generated notches that create undesirable harmonics to
lance is more than the specified value in the power quality the load voltage, increases the neutral current and decreases
IEEE-519 standard. the average load voltage.
Figures 6(b) & (c) illustrate the comparison of phase cur-
rent and phase voltage with respect to time in minutes for a
Transients 12-pulse three-phase rectifier load. The generated notches that
create undesirable harmonics to the load voltage increases the
Transients are disturbances, relatively than steady state varia- neutral current and decreases the average load voltage. It is
tions such as harmonic distortions or unbalances. Transients observed that the phase voltage An,,Bn, are lesser in
Srinivasan et al. 5

Figure 4. Voltage sag obtained in transformer-1.

Figure 5. The variation of phase currents when the motor is operated. (a) Three Phase current in RMS values, for 600 samples with respect to time
period in minutes. (b) Three phase current unbalances in % for 500 samples with respect to time period in minutes.

magnitude and the phase voltage Cn has higher magnitude served from single-phase or double-phase systems, adjustable
with spike due to heavy loads that come into operation, where speed drives, single-phase motor more than 3HP, fluctuating
a different phenomenon is observed with phase current. Air- loads such as (elevators, arc furnaces, rolling mill drives, arc
conditioning (AC) loads are connected in two phases An and welding loads and wind turbines) generates voltage fluctua-
Bn, respectively, and by switching-on these devices in a tions in distribution system. This causes nuisance tripping,
sequence creates transient. mis-operation of relays, contactors and unwanted triggering
of uninterruptible power source (UPS) control units. The vol-
tage flicker creates harmonics in the network causing various
Voltage flicker PQ issues. To demonstrate the flicker analysis, the measure-
A series of voltage changes or a continuous variation of the ment was taken from two-phase electric resistance welding
RMS or peak value of the voltage or the common effects of such as single phase welding machine with a capacity of
voltage variation is recognized as flicker. The impact of vol- 5KVA fluctuating load.
tage fluctuation (flicker) on lighting intensity due to large The line current in RMS value when the welding machine
loads that have rapidly changing active and reactive power is switched on and comparison of line voltage (VAB) and line
demands is generally termed as flicker. The variations range current in (RMS) value taken are illustrated in Figures 7(a)
from 0.1% to 7% of nominal voltage with frequencies less and (b). From this figure, it is observed that the line currents
than 25Hz causes voltage fluctuations. The three-phase magnitude is 4.5, 4.7, 4.2Amps and the line voltage of
motors above 35 HP or a three-phase motor over 10 HP 425Volts during on condition. Comparison of line voltage
6 Transactions of the Institute of Measurement and Control 00(0)

Figure 6. Transient measurement (a) Comparison of Phase voltage, phase current and neutral current with respect to time in minutes.
(b) & (c) Phase current and Phase voltage deviations for 600 samples with respect to time in minutes.

(VCA) and line current magnitude in RMS value without and supra harmonics along with other harmonics within the
with welding operation is illustrated in Figures 7(c) and (d). ranges of 2KHz to 150KHz.
During the welding operation, the line current in phase B and From Figure 9, it is observed that the current total harmo-
C that increases suddenly from 4.5Amps to 37Amps is nics distortion (THD)% during arc-load condition is very
observed from Figure 7(d). The phase A remains the same as high of 65%, where the harmonic frequencies are in the ranges
4.5Amps, since the load is connected between the line B and of 150 Hz to 2.5 KHz. It is inferred that the arc load is capable
C. The line voltage VBC, VCA, gets reduced whereas the line of producing supra harmonics with relevant THD%. These
current of B and C increases due to increase in arc load that effects of harmonics produce unbalances and frequency varia-
is illustrated in Figures 8(a) and (b). The effects of voltage tions are illustrated in Figure 10. By providing a filter capaci-
and current variations induce harmonics and flicker exists. tor across the point of common coupling (PCC), the higher
Measurement of harmonics with respect to fundamental is an order frequency components get restricted into the source
important constraint in distribution system applications. side.
Perception of instantaneous flicker (Pins) response is in
‘‘perception unit’’ one per unit defined as threshold of percep-
Harmonics tion, illustrated in Figure 11. From this, it is inferred that the
input voltage fluctuation of% is very high.
Harmonics are classified as integer harmonics, inter harmo- The perception of short-term flicker (Pst) can be expressed
nics, sub harmonics and supra harmonics. Integer harmonics as
are the integer multiples of fundamental frequency, inter har-
monics have their frequencies greater than fundamental fre- pffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi
quency and sub harmonics have their frequencies lesser then Pst = k1 P1 + k2 P2 +    kn Pn ð1Þ
fundamental frequency. Highly fluctuation loads can produce
Srinivasan et al. 7

Figure 7. Flicker measurement during welding operation. (a) & (b) shows the three-phase current and comparison of line voltage (VAB), current while
switching on the welding machine. Fig. 7(c) & (d) shows the comparison of three line voltage (VCA) and current before and during the welding operation.

Figure 8. Flicker measurement during welding operation. (a) & (b) shows the comparison of three line voltage and three line current in RMS value
for 1400 samples with respect to time in 12-minute intervals.

where Kn are the weighting coefficients and Pn are level corre- is 1 unit according to IEC 61000-4-15. Figure 12 illustrates
sponding to the percentiles. the perception of short-term flicker (Pst) for line voltage AB,
The measure of flicker severity based on an observation BC, CA with respect to time for 1300 samples. From this fig-
period of short term (1–10 minute) duration. The limit for Pst ure, it is observed that the Pst indicator value is beyond the
8 Transactions of the Institute of Measurement and Control 00(0)

Figure 9. % THD of current during arc-load.

Figure 10. Unbalances in % and frequency variations during arc load.

Figure 11. Perception of instantaneous flicker sensation (Pins) for line voltage AB with respect to time.

IEC regulatory norms. Hence, this kind of voltage distur- side. This system consists of loads like industrial, commercial
bances is mitigated through connecting custom power devices. and sensitive loads. They are connected to the point of com-
From the real time PQ measurements, it is observed that the mon coupling (PCC). The block diagram of 11kV/440V dis-
THD is above the recommended values, sag/swell, transients tribution system with D-STATCOM is illustrated in
are presented in the test system. To mitigate these PQ issues, Figure 13. It is realized by a three-phase, four-wire voltage
D-STATCOM is designed and implemented. source inverter (VSI) connected in parallel to feeder through
LC filter. The filter capacitor (Cfc ), connected in across the
feeder to suppress the higher frequency component and pro-
PQ assessment and mitigation using hibits them from entering into the feeder. Voltages across
both capacitors Cdc1 = Cdc2 = Cdc are maintain at a constant
D-STATCOM
value Vdc1 = Vdc2 = Vdc . Source voltage, PCC voltage, source
Distribution system comprises of utility system and step- current, load current and filter currents are vsj, vtj, isj, ilj, and
down transformer to decrease the voltage level in distribution iftj, with j = a, b, c as three phases.
Srinivasan et al. 9

Figure 12. Perception of short-term flicker (Pst) for line voltage AB, BC, CA with respect to time.

Sensitive loads

PCC

a Current varying loads


A like arc furnace,
b rolling mills
B c
C n
B2
Three-phase B1 11kV/440V
ac source T/F

+
-
n
+
-

Figure 13. General block diagram of D-STATCOM.

Several reference generations scheme have proposed for generates the voltage or current control laws. Finally, this law
compensation (Goh and Radzi, 2017; Mahela and Shaik, is changed into ON/OFF switching command to operate the
2015; Ronnberg and Bollen, 2016; Singh et al., 2014). In this VSI switches through deadbeat hysteresis controller.
work, instantaneous symmetrical component theory is used
to generate the source current and terminal voltage reference
for compensation. The control algorithm decides the D- Generation of current control law
STATCOM to operate in current control mode (CCM) or This research provides an independent control of each leg of
voltage control mode (VCM). In CCM, the DC-link voltage VSI. Single phase modelling is done to explain the operation.
is decreased to compensate the power losses in voltage source Output voltage of the VSI is represented by uVdc. The term,
inverter (VSI). Regulation of DC-link voltage is obtained u, is the switching control variable with value + 1or -1. State
through closed loop PI controller from Section 3.2. space equation for this circuit is given as follows
Generation of filter current reference from Section 3.3 in
CCM contributes to the performance of the D-STATCOM. x_ = Ax + Bz
ð2Þ
During voltage disturbances the mode is changed to VCM = ½ vfc ifi is t , z = ½ u ift vs  t
for compensation. Moving average filter is utilized to com-
pute the average load power (Pavg). This Pavg is used for com- Equation (2), given in continuous form, represented in a dis-
puting the reference filter current. Predictive control crete form as
10 Transactions of the Institute of Measurement and Control 00(0)

Figure 14. Control block diagram of D-STATCOM.

xðk + 1Þ = Gxðk Þ + Hzðk Þ ð3Þ For second order extrapolation, n = 2 in the above equation
and a linear prediction is given below
The filter current at ðk + 1Þ sampling instant, as of equation
(3), is given ifi ðk + 1Þ = 3ifi ðk Þ  3ifi ðk  1Þ + ifi ðk  2Þ ð8Þ

ifi ðk + 1Þ = G21 Vfc ðk Þ + G22 ifi ðk Þ + H21 ui ðk Þ + H22 ift ðk Þ ð4Þ By substituting the above equation in (4), the substitution
yields the deadbeat current control law. The reference current
When equation (4) is implemented, each switching state gives control law obtained from equations (4),(6) and (8) is given as
a different current estimation. In other words, each switching
strategy needs a future current through the switching device, ifi ðk + 1Þ  G21 vfc (k)  G22 ifi (k)  H21 ift (k)
which is unknown at the k th sampling. Hence, the cost func- ui ðk Þ = ð9Þ
H22
tion (J) is defined as
h i2
J = ifi ðk + 1Þ  ifi ðk + 1Þ ð5Þ Generation of voltage control law
where From equation (3), the voltage across filter capacitor at the
future sampling instant is
ifi ðk + 1Þ is reference current;
vfc ðk + 1Þ = G11 ifi ðk Þ + H11 uv ðk Þ + H12 ift ðk Þ ð10Þ
ui (k) reference for current control law;
uv (k) is reference for voltage control law. The procedure for obtaining uv (k) is followed to obtain the
reference voltage control law
To minimize cost function, it is differentiated with respect
to ui ðk Þ and equated to zero. Then, J is minimum at vfc ðk + 1Þ  G11 vfc (k)  G12 ifi (k)  H12 ift (k)
ui ðk Þ = ð11Þ
H11
ifi ðk + 1Þ = ifi ðk + 1Þ ð6Þ
Similarly
Reference current control law is obtained after replacing
equation (6) in (4). It can be noticed that equation (4) com- vt ðk + 1Þ = 3vt ðk Þ  3vt ðk  1Þ + vt ðk  2Þ ð12Þ
prises future reference current ifi ðk + 1Þ that is unknown. To
identify the future value of any signal in discrete domain with The reference control law is transformed into correspond-
constant sampling time, extrapolation is used to guesses the ing switching commands using deadbeat current and voltage
future value using known values of past sampling instants. controller. Control block diagram of D-STATCOM is shown
Order of extrapolation depends upon the sampling period. in Figure 14.
The future current reference can be obtained from
Lagrange’s extrapolation formula as follows
Control of DC link voltage
Xn  
n+1  The DC link voltage gradually decreases because of the losses
ifi (k + 1) = nn1 ifi (k + 1  n) ð7Þ
l=0 l in the inverter. Consequently, a control loop is needed to
Srinivasan et al. 11

maintain the capacitor voltage in the desired value by com- where


pensating the losses. It is achieved by taking small real power
from the source. Control of capacitor voltage in CCM and ifta reference filter current;
VCM is achieved as follows. v+ ta1 positive sequence component
cfc shunt capacitor.
Control of DC link voltage in CCM. The deviation of capacitor
voltage from reference voltage represents power losses (Ploss) The reference currents of the inverter for VSI is given as
in the VSI. The desired DC link voltage is obtained by com- 2 3 2  3 2  3
pensating the Ploss drawn from source. Compensation of Ploss ifia ifta ifca
4 ifib 5 = 4 iftb 5 + 4 ifcb 5

ð18Þ
is done through a proportional-integral (PI) controller, as
shown in Figure 14. It supports in maintaining the DC link ific iftc ifcc
voltage ðvdc1 + vdc2 Þ at a predefined reference value (2 Vdcref )
by taken a set of balanced currents from the source given as Deadbeat current predictive control is used to realize these
currents using the VSI.
ð
Ploss = Kpc evdc + Kic evdc dt ð13Þ
Generation of reference load voltages. The load voltages are
where Kpc , Kic and evdc = 2Vdcref  ðvdc1 + vdc2 Þ are propor- maintained at 0.9 -1.1 p.u. during sag and swell respectively
tional gain, integral gain and voltage error of PI controller. for the improvement of voltage regulation ability. The refer-
ence voltage magnitude (vt ), load angle d are computed from
(14); the three-phase reference load voltages are given as
Control
 of DC link voltage in VCM. The real power at pffiffiffi  
PCC Ppcc is sum of load power Plavg and VSI losses. The vta = 2vt sin vt  vta d ð19Þ
total power at PCC Ppcc , is taken from the source depend-
ing upon the load angle d. During VCM, DC link voltage is Similarly, vtb , vtc . This voltage is realized by the VSI using
regulated by selecting a suitable value of load angle. For sta- deadbeat predictive control law.
ble operating condition the load angle lies between 0 to 908
ð
d = Kpv evdc + Kiv evdc dt ð14Þ Transfer of modes in D-STATCOM
During normal condition, the D-STATCOM is operated in
CCM for reactive power compensation, load harmonics,
unbalances and unity power factor. However, the load vol-
Generation of reference quantities tage can change at any instant because of the voltage distur-
Generation of reference filter current. D-STATCOM perfor- bances. It will be affected the performance of sensitive load
mance in CCM mainly depends on the generation of reference connected in the distribution system. In this circumstance, D-
currents. In this research, reference filter current (ifta , iftb , iftc ) is STATCOM must switch to VCM from CCM to maintain
generated using instantaneous symmetrical components the- constant voltage at the load terminal. If Vs is lesser than 0.923
ory represented as p.u. and greater than 1.1 p.u. then the D-STATCOM can
operate in VCM to regulate load voltage. If Vs is between
v+ 0.93 and 1.1 p.u then the D-STATCOM can operate in CCM.
ifta = ila  ila = ila  taI
(Plavg + Ploss ) ð15Þ
D+I

Similarly, iftb = ilb  ilb , iftc = ilc  ilc , where D+


1 =
Development of DSTACOM uning MATLAB-
P + 2 SIMULINK
j = a, b, c (vtjI ) ,
are the instantaneous fundamental positive-
sequence component. Ploss , are calculated in PI controller, The D-STATCOM has been modeled using MATLAB and is
given in equation (13). The average load power is estimated an experimental model is developed and tested. A proposed
using moving average filter is represented as control algorithm and interactive D-STATCOM make the
ð t1 source currents balanced, sinusoid and maintain unity power
1 factor at the PCC, within the acceptable voltage range. In
Plavg = ðvta ila + vtb ilb + vtc itc Þ ð16Þ
T t1 T addition, reactive current components and load harmonics
are provided through the distribution static synchronous
where T and t1 are the time period and arbitrary time instant. compensator (D-STATCOM). Validation of the proposed
The reference current through capacitor leads the terminal control algorithm and implementation of three- phase D-
voltage by 908 . Therefore, reference current in capacitor is STATCOM was carried out through MATLAB/Simulation
estimated as follows platform. 440V RMS value per phase is considered as (1.0
2 3 2 +3 p.u.). The 3MVAr compensator contains a pulse width modu-
ifca vtaI lation (PWM) six-pulse inverter, with filter parameters of Lf
4 ifcb 5 = jvCfc 4 v+ 5 ð17Þ
tbI = 30 mH, Cf = 15mF,Vdc = 3400 V, Cdc = 5800mF and
ifcc v+
tcI PWM with switching frequency of 3kHz.
12 Transactions of the Institute of Measurement and Control 00(0)

Case 1 (voltage flickering): Initially, a three-phase unba- produces voltage and current oscillation during the time
lanced load of 4MW and a constant current load with a period t = 0.1 to 0.6 sec.
modulating frequency of 8.8 Hz is connected during the
time period from t = 0.1 to 0.6 sec. The corresponding This results in fluctuations of real and reactive power that
phase voltage in p.u, line current, real and reactive power changes rapidly leads to flickering are illustrated in Figures
and the flicker meter output of weighting filter and Pins 15(a) to (c). The severity of the flicker is identified and mea-
values are shown in Figures 15(a) to (e). It is inferior that sured by flickermeter are illustrated in Figures 15(d) and (e).
the constant current load with low frequency component The magnitude of weighting filter fluctuating voltage is 10

Figure 15. Continued


Srinivasan et al. 13

Figure 15. Simulation results without compensation. (a) Terminal voltage in p.u. (b) load current. (c) Real and reactive power. (d) Weighting filter
output p.u. (e) perception of instantaneous value (Pins).

Figure 16. Comparison of FFT alysis for ITHDin % without and with compensation.
(a) ITHDin % without compensation. (b) ITHD in % with compensation.

Figure 17. Comparison of flickermeter output Van p.u. for without and with compensation.
(a) Flickermeter output Van in p.u. without compensation. (b) Flickermeter output Van in p.u. with compensation.
14 Transactions of the Institute of Measurement and Control 00(0)

Figure 18. Simulation results of CCM.


(a) Terminal voltage and current in p.u. (b) Real and reactive power. (c) Weighting filter output p.u. (d) Perception of instantaneous value (Pins).(e) DC-
bus Voltage (Vdc). (f) Amplitude modulation index.

Figure 19. Simulation results of VCM. (a) Van average value in p.u without compensation. (b) Van average value in p.u with compensation.
Srinivasan et al. 15

Figure 22. Phase voltage, current, compensator injecting current and


voltage for linear load.
Figure 20. Experimental setups for the proposed D-STATCOM.

the PI controller. Figure 18(f) shows that the VSI amplitude


modulation index (ma) gets varied from (0.1–0.6 sec) and
attains the steady state at 0.8 sec.

Case 2 (voltage dip): To illustrate the voltage regulation


ability of D-STATCOM, at t= 0.1 sec, sag is generated
by an inflexible source by 15%, as shown in Figure 19(a).
Once sag is detected, the mode of operation is changed to
VCM and a constant voltage of 0.98 p.u. is maintained at
the load terminal. The source current increases during sag
period owing to reactive current supplied by the compen-
sator, illustrated in Figure 19(b). Voltage sag is cleared at
t = 0.6 sec, then the load voltage starts following the
source voltage. Hence, the operational mode of the D-
STATCOM is shifted to CCM. The inner and outer loop
Figure 21. Spartan-6-based FPGA, driver circuit and 5 level C-MLI. PI controller are used to regulate the DC-link capacitor
voltage under CCM and VCM of operation. Error
between the reference and actual DC-Link capacitor is fed
p.u., Pins value is about 300 % and percentage of line current as input for both the PI controller. The inner loop control-
total harmonics distortion (ITHD) is of 15% and that causes ler produces output proportional to power loss (Ploss). The
severe fluctuations in the feeder. Compensation performance outer loop PI controller generates load angle (d). During
of novel multifunction D-STATCOM operation is shown in the normal operating condition from 0–0.1 sec the load
Figure 16. Comparison of % ITHD value for without and with angle remains constant as 68 , at sag condition from 0.1–
compensation obtained from fast Fourier transform (FFT) 0.6 sec the load angle increases and reaches a peak value
analysis is shown in Figure 16. It is observed that the com- of 148 , Beyond the time period of 0.6 Sec, it remains at a
pensator can suppress the %ITHD from 15% to 1.3%. constant value of 68 . Once the sag disappears, the control-
Figure 17 illustrates the comparison of flickermeter output ler transfers from VCM to CCM. Controller gain values
VanRMS value p.u. without and with compensation. It is are Kpv = 9  106 , Kiv = 10  106 , Kpc = 20, Kic = 0:8:
inferior that the low frequency carrier signal is completely
suppressed, as shown in Figure 17. The D-STATCOM oper-
ates in CCM to compensate the voltage flicker by supplying
reactive current, which makes the terminal voltage and cur- Experimental verification of a FPGA-
rent inphase, with each other at PCC is illustrated in Figure
18(a). Real power and reactive power at PCC are illustrated
based prototype D-STATCOM
in Figure 18 (b). It is observed that the PQ gets disturbed dur- A laboratory prototype of FPGA-based D-STATCOM con-
ing transients and attains steady state because of compensa- troller has been developed and tested. The photograph of the
tor. The flickermeter output from weighting filter fluctuating experiments set is shown in Figure 20. And the FPGA con-
voltage is nearly 0.02 p.u during flicker and Pins value is about troller and MLI module is shown in Figure 21. The D-
10 %, illustrated in Figures 18(c) and (d). These parameters STATCOM consists of a 2-stage, 5-level cascade multilevel
are limited according to the IEEE-519 PQ standards by con- inverter controlled by a FPGA-based controller. The closed-
necting compensator. The DC bus voltage is observed in loop controller for D-STATCOM has been implemented
Figure 18(e) and is preserved at 3400V during the CCM using using the Spartan-6 field programmable gated array (FPGA).
16 Transactions of the Institute of Measurement and Control 00(0)

Figure 23. Single phase voltage, current, compensator injecting current and voltage for non-linear load.

Figure 24. Three-phase voltage, current, compensator injecting current and voltage for rectifier load.

The proposed system utilized the MATLAB/Simulink library sudden changes in the supply voltage and current waveforms.
specifically designed for Xilinx ISE, which supports model- As a result, the line current and voltage disturbances get miti-
based system design of FPGA based control systems. gated and the system behavior is restored to normalcy, illu-
Additionally, Simulink library enables model analysis for sys- strated in Figure 23.
tem diagnostics and fast prototyping, by identifying system In the second stage, the D-STATCOM has been tested for
issues prior to hardware implementation. a three-phase system. The system feeds power to an uncon-
trolled rectifier. The voltage and current waveforms of the
power system after the compensation is shown Figure 24. At
Experiment results time period of 20 msec, the D-STATCOM is compensating
Experimentations have been carried out for variety of distur- voltage and current. Figure 25 shows the THD value of cur-
bances like voltage sag/swell, transient and harmonics in rent harmonics content in the D-STATCOM. It is observed
power system. The D-STATCOM is tested initially, through a that the current THD value is 18.2% without compensation
supply phase voltage of 150Vfor linear loading conditions and and it has reduced to 3.9% with compensation.
the corresponding waveform is shown in Figure 22. Figure 22
shows that the supply phase current distortion gets compen-
sated through 2-stage, 5-level cascade multilevel inverter injec- Conclusion
tion (C-MLI) of compensating current and the corresponding
The real-time PQ measurement in a 11kV/440V power system
voltage from D-STATCOM are obtained for time duration
has been carried out, and the PQ issues are analyzed. The
from 0–0.2 sec.The phase current and voltage are measured
measured data have been utilized to evaluate the occurrences
using the digital storage oscilloscope. The phase voltage and
of PQ disturbance in the system. Then, a D-STATCOM is
current measurement for a single phase is shown in Figure 23.
designed to mitigate the system disturbances. The D-
It can be observed that the waveform consists of two distinct
STATCOM has been developed in MATLAB/Simulink envi-
phases. Initially, the presence of the non-linear load injects
ronment, and the simulation results are presented to mitigate
harmonics into the system, which in turn distorts the line
the PQ issues. The functionality of the D-STATCOM is
current.
experimentally verified using a FPGA-based prototype con-
In the second phase at time period of 80 msec the D-
troller. The D-STATCOM has been tested for difference dis-
STATCOM comes into operation, injecting voltage and cur-
rent into the system, which could be observed from the turbances such as voltage sag/swell, flicker and harmonics.
Srinivasan et al. 17

Figure 25. Current total harmonics distortion measurement. (a) & (b) Comparison of three-phase % ITHD without and with DSTATCOM.

The D-STATCOM is effectively compensating the distur- systems. IEEE Transactions on Instrumentation and Measurement
bances in the distribution system to meet the PQ standards. 60(6): 2007–2013.
Gao HL, Zhan XS, Yuan YR, et al. (2019) Mitigation of low fre-
quency oscillations in power systems based on Mamdani
Authors’ Note fuzzy inference. Transactions of the Institute of Measurement and
Control: 41(12): 3477–3489.
Murugaperumal Krishnamoorthy is now affiliated to
Geiger II DL and Halpin SM (2017) Assessing voltage fluctuations
Department of Electrical and Electronics Engineering, BIET
and lamp flicker using RMS voltages. IEEE Transactions on
Mangalpalli, Hyderabad, India. Power Delivery 32(6): 2481–2488.
Ghosh A and Ledwich G (2003) Load Compensating DSTATCOM
Declaration of conflicting interests in Weak AC Systems. IEEE Transactions on Power Delivery 18(4):
1302–1309.
The author(s) declared no potential conflicts of interest with Goh ZP and Radzi MAM (2017) Investigation of severity of voltage
respect to the research, authorship, and/or publication of this flicker caused by second harmonic. IET Science, Measurement &
article. Technology 11(3): 363–370.
Gonzalez-Ramirez M and Cruz-villar CA (2017) Variable speed drive
with PFC front-end for three-phase induction motor. Electronics
Funding Letters 53(16): 139–1140.
The author(s) received no financial support for the research, Hossain E, Tür MR, Padmanaban S, et al. (2018) Analysis and miti-
gation of power quality issues in distributed generation systems
authorship, and/or publication of this article.
using custom power devices. IEEE Access 6: 16816–16833.
Khoshooei A, Moghani JS, Candela I and Rodriguez P (2018) Con-
ORCID iD trol of D-STATCOM during unbalanced grid faults based on DC
voltage oscillations and peak current limitations. IEEE Transac-
Suresh Srinivasan https://orcid.org/0000-0002-6491-9310 tions on Industry Applications 54(2): 1680–1690.
Kumar C and Mishra MK (2014a) A multifunctional DSTATCOM
operating using stiff source. IEEE Transactions on Industrial Elec-
References tronics 61(7): 3131–3136.
Arindam Ghosh S and Joshi A (2005) Inverter topologies for Kumar C and Mishra MKA (2014b) Voltage-controlled DSTAT-
DSTATCOM applications a simulation study. International Jour- COM for power-quality improvement. IEEE Transactions on
nal of Electrical Power and Energy Systems 75(2): 161–170. Power Delivery 29(3): 1499–1507.
Cristaldi L, Ferrero A, Muscas C, et al. (2003) The impact of internet Madhulingam T, Subbaiysn T, Shanmugam P and Kannan S (2017)
transmission on the uncertainty in the electric power quality esti- Design and development of improved power quality based
mation by means of a distributed measurement system. IEEE micro- butt welding power supply. IET Power Electronics 10(7):
Transactions on Instrumentation and Measurement 52(4): 746–755.
1073–1078. Mahela OP and Shaik AG (2015) A review of distribution static com-
Elnady A and Salama MMA (2005) Unified approach for mitigating pensator. Renewable and Sustainable Energy Reviews 50(1):
voltage sag and voltage flicker using the DSTATCOM. IEEE 531–546.
Transactions on Power Delivery 20(2): 992–1000. Majchrzak J and Wiczynski G (2012) Basic characteristics of IEC
Faifer M, Toscani S and Otooboni R (2011) Electronic combined flickermeter processing. Modelling and Simulation in Engineering
transformer for power quality measurements in high-voltage 1(1): 1–9.
18 Transactions of the Institute of Measurement and Control 00(0)

Maksi M, Papi I and Blai B (2016) Simple continuous assessment of Wang Z, Chau KT, Yuwen B, et al. (2012) Power compensation and
transmission -network flicker levels caused by multiple sources. power quality improvement based on multiple-channel current
IEEE Transactions on Power Delivery 31(6): 2546–2552. source converter fed HT SMES. IEEE Transactions on Applied
Moreno-Garcia IM, Moreno-Munoz A, Pallares-Lopez V, et al. Superconductivity 22(3): 5701204–5701204.
(2017) Development and application of a smart grid test bench. Wiczynski G (2008) Description of voltage fluctuations in LV power
Journal of Cleaner Production 162: 45–60. network with the use of Pst indicator and voltage fluctuation
Murugaperumal K and Raj PADV (2019). Integrated energy manage- indices. In: 2008 13th International Conference on Harmonics and
ment system employing pre-emptive priority based load scheduling Quality of Power, Wollongong, NSW, Australia, pp. 1–4. IEEE.
(PEPLS) approach at residential premises. Energy 186(1): 115815. Wiczynski G (2017) Estimation of Pst Indicator values on the basis of
Pongiannan RK, Paramasivam S and Yadaiah N (2010) FPGA reali- voltage fluctuation indices. IEEE Transactions on Instrumentation
zation of an area efficient SVPWM modulator for three phase and Measurement 66(8): 2046–2055.
induction motor drive. International Journal of Power Electronics, Zaveri T, Bhalja B and Zaveri N (2012) Comparison of control stra-
Inder Science Publications 2(2): 176–199. tegies for DSTATCOM in three-phase, four-wire distribution sys-
Pongiannan KR, Paramasivam S and Yadaiah N (2011) Dynamically tem for power quality improvement under various source voltage
reconfigurable PWM controller for three phase voltage source and load conditions. International Journal of Electrical Power and
inverters. IEEE Transactions on Power Electronics 26(6): Energy Systems 43(1): 582–594.
1790–1799. Ziaeinejad S and Mehrizi-Sani A (2018) Design tradeoffs in selection
Pongiannan RK, Paramasivam S and Yadaiah N (2011a) Dynami- of the DC-side voltage for a D-STATCOM. IEEE Transactions on
cally reconfigurable PWM controller for three phase voltage Power Delivery 33(6): 3230–3232.
source inverters. IEEE Transactions on Power Electronics 26(6):
1790–1799.
Pongiannan RK, Selvabharathi et al. (2011b) FPGA based three Abbreviations
phase sinusoidal PWM VVVF controller. International Conference
on Electrical Energy Systems 2011: 34–39. ASD adjustable speed drive
Pongiannan RK, Sathiyanathan M, Vinothkumar U, et al. (2013) APFC automatic power factor correction
FPGA realization of digital PWM controller using Q-format CCM current control mode
based signal processing. Journal of Vibration and Control 21(5): C-MLI cascade multilevel inverter injection
938–948. CPD custom power devices
Ronnberg S and Bollen M (2016) Power quality issues in the electric DC direct current
power system of the future. The Electricity Journal 29(10): 49–61. D-STATCOM distribution static synchronous
Saini MK, Kapoor R and Beniwal RK (2019) Recognition of voltage compensator
sag causes using fractionally delayed biorthogonal wavelet. Trans-
DVR dynamic voltage restorer
actions of the Institute of Measurement and Control 41(10):
FFT fast Fourier transform
2851–2863.
Singh B, Jayaprakash P and Kothari DP (2014) Comprehensive Study FPGA field programmable gate array
of DSTATCOM Configurations. IEEE Transactions on Industrial LED light emitting diode
Informatics 10(2): 854–869. PCC point of common coupling
Ujile A, Ding Z and Li H (2015) An iterative observer approach to PQ power quality
harmonic estimation for multiple measurements in power distribu- PWM pulse width modulation
tion systems. Transactions of the Institute of Measurement and RMS root mean square
Control 39(5): 599–610. THD total harmonic distortion
Vural AM (2016) Self-capacitor voltage balancing method foropti- UPQC unified power quality conditioner
mally hybrid modulated cascaded H-bridge D-STATCOM. IET
UPS uninterruptible power source
Power Electronics 9(14): 2731–2740.
VCM voltage control mode
Wang L, Liu WS, Yeh CC, et al. (2018) Reduction of three-phase vol-
tage unbalance subject to special winding connections of two VLSI very large scale integration
single-phase distribution transformers of a microgrid system using VSI voltage source inverter
a designed D-STATCOM controller. IEEE Transactions on Indus-
try Applications 54(3): 2002–2011.

You might also like