Job No.

: 322890
Order-Item No.: 4500126971-010
Purchaseorder No.: 1HC0068399M0001
Customer No.: 15469/10010

ROUTINE TESTS REPORT


VOLTAGE TRANSFORMER
Type: TJC 6-G Highest voltage: 24.0 kV
Rated frequency: 50 Hz Rated ratio: 13800/ 3//110/ 3/110/3 V
Accuracy class: 0,2/3P Output: 45/50 VA
Production number: 1VLT5211014513 Year of production: 2011

TESTS:
1. Verification of terminal marking acc. to clause 9.1
Conclusion: Satisfactory
2. Power-frequency voltage withstand tests on primary windings acc.to clause 9.2
Separate source withstand voltage test when applicable acc.to clause 9.2.2.2a
Test value: 3 kV, 50 Hz, 1 minute
Conclusion: Satisfactory
3. Induced overvoltage withstand test acc.to clause 9.2.2.2b
Test value: 60.0 kV, 100 Hz, 1 minute
Conclusion: Satisfactory
4. Partial discharge measurment acc.to clause 9.2.4.2 procedure A
1,2Um : 44 pC
1,2Um/ 3 : 4 pC
Conclusion: Satisfactory
5. Power-frequency voltage withstand test between sections and on secondary windings acc.to clause 9.3
Test value: 3 kV, 100 Hz, 1 minute
Conclusion: Satisfactory
6. Tests for accuracy- measuring and protective windings acc.to clause 12.4 and 13.7.1
Winding: I: 45 VA/class 0,2
Winding: II: 50 VA/class 3P
Winding: III: - VA/class -
Conclusion: Satisfactory

The voltage transformer complies with tests required according to IEC Publications
60044 - 2.

Brno, the: 05.09.2011 Ing. Ku!era Jan

Headquarters: Mail Address:


ABB s.r.o. ABB s.r.o. Phone: + 420 5 4715 2609
Sokolovska 84-86 Videnska 117 Fax: + 420 5 4715 2626
186 00 Prague 8 619 00 Brno
Czech Republic Czech Republic
Job No.: 322890
Order-Item No.: 4500126971-010
Purchaseorder No.: 1HC0068399M0001
Customer No.: 15469/10010

Measurements with Automatic Transformer Test Set, ZERA


VOLTAGE TRANSFORMER
Serial No.: 1VLT5211014513
Test Object: TJC6-G:E43907934
Nominal Freq.: 50 Hz
Date: 05.09.2011 Operator: Jiri Tesarek

Winding No. PXR//SXR(V) Burden(VA) COS ß % Un ei(%) di(min)


1 13800/ 3//110/ 3 45,00 0,80 120 -0.090 -0.198
1 13800/ 3//110/ 3 45,00 0,80 100 -0.091 -0.294
1 13800/ 3//110/ 3 45,00 0,80 80 -0.093 -0.346
1 13800/ 3//110/ 3 11,25 0,80 120 0.162 -0.082
1 13800/ 3//110/ 3 11,25 0,80 100 0.162 -0.157
1 13800/ 3//110/ 3 11,25 0,80 80 0.161 -0.222
2 13800/ 3//110/3 50,00 0,80 190 -0.882 7.625
2 13800/ 3//110/3 50,00 0,80 100 -0.870 6.733
2 13800/ 3//110/3 50,00 0,80 5 -0.963 8.719
2 13800/ 3//110/3 12,50 0,80 190 -0.437 2.204
2 13800/ 3//110/3 12,50 0,80 100 -0.424 1.620
2 13800/ 3//110/3 12,50 0,80 5 -0.487 2.150

Headquarters: Mail Address:


ABB s.r.o. ABB s.r.o. Phone: + 420 5 4715 2609
Sokolovska 84-86 Videnska 117 Fax: + 420 5 4715 2626
186 00 Prague 8 619 00 Brno
Czech Republic Czech Republic
Job No.: 322890
Order-Item No.: 4500126971-010
Purchaseorder No.: 1HC0068399M0001
Customer No.: 15469/10010

ROUTINE TESTS REPORT


VOLTAGE TRANSFORMER
Type: TJC 6-G Highest voltage: 24.0 kV
Rated frequency: 50 Hz Rated ratio: 13800/ 3//110/ 3/110/3 V
Accuracy class: 0,2/3P Output: 45/50 VA
Production number: 1VLT5211014520 Year of production: 2011

TESTS:
1. Verification of terminal marking acc. to clause 9.1
Conclusion: Satisfactory
2. Power-frequency voltage withstand tests on primary windings acc.to clause 9.2
Separate source withstand voltage test when applicable acc.to clause 9.2.2.2a
Test value: 3 kV, 50 Hz, 1 minute
Conclusion: Satisfactory
3. Induced overvoltage withstand test acc.to clause 9.2.2.2b
Test value: 60.0 kV, 100 Hz, 1 minute
Conclusion: Satisfactory
4. Partial discharge measurment acc.to clause 9.2.4.2 procedure A
1,2Um : 15 pC
1,2Um/ 3 : 4 pC
Conclusion: Satisfactory
5. Power-frequency voltage withstand test between sections and on secondary windings acc.to clause 9.3
Test value: 3 kV, 100 Hz, 1 minute
Conclusion: Satisfactory
6. Tests for accuracy- measuring and protective windings acc.to clause 12.4 and 13.7.1
Winding: I: 45 VA/class 0,2
Winding: II: 50 VA/class 3P
Winding: III: - VA/class -
Conclusion: Satisfactory

The voltage transformer complies with tests required according to IEC Publications
60044 - 2.

Brno, the: 06.09.2011 Ing. Ku!era Jan

Headquarters: Mail Address:


ABB s.r.o. ABB s.r.o. Phone: + 420 5 4715 2609
Sokolovska 84-86 Videnska 117 Fax: + 420 5 4715 2626
186 00 Prague 8 619 00 Brno
Czech Republic Czech Republic
Job No.: 322890
Order-Item No.: 4500126971-010
Purchaseorder No.: 1HC0068399M0001
Customer No.: 15469/10010

Measurements with Automatic Transformer Test Set, ZERA


VOLTAGE TRANSFORMER
Serial No.: 1VLT5211014520
Test Object: TJC6-G:E43907934
Nominal Freq.: 50 Hz
Date: 06.09.2011 Operator: Radek Putna

Winding No. PXR//SXR(V) Burden(VA) COS ß % Un ei(%) di(min)


1 13800/ 3//110/ 3 45,00 0,80 120 -0.101 -0.984
1 13800/ 3//110/ 3 45,00 0,80 100 -0.103 -1.064
1 13800/ 3//110/ 3 45,00 0,80 80 -0.109 -1.115
1 13800/ 3//110/ 3 11,25 0,80 120 0.154 -0.859
1 13800/ 3//110/ 3 11,25 0,80 100 0.152 -0.921
1 13800/ 3//110/ 3 11,25 0,80 80 0.148 -0.975
2 13800/ 3//110/3 50,00 0,80 190 -0.905 7.029
2 13800/ 3//110/3 50,00 0,80 100 -0.894 6.058
2 13800/ 3//110/3 50,00 0,80 5 -1.045 8.295
2 13800/ 3//110/3 12,50 0,80 190 -0.453 1.587
2 13800/ 3//110/3 12,50 0,80 100 -0.441 0.965
2 13800/ 3//110/3 12,50 0,80 5 -0.562 1.741

Headquarters: Mail Address:


ABB s.r.o. ABB s.r.o. Phone: + 420 5 4715 2609
Sokolovska 84-86 Videnska 117 Fax: + 420 5 4715 2626
186 00 Prague 8 619 00 Brno
Czech Republic Czech Republic
Job No.: 322890
Order-Item No.: 4500126971-010
Purchaseorder No.: 1HC0068399M0001
Customer No.: 15469/10010

ROUTINE TESTS REPORT


VOLTAGE TRANSFORMER
Type: TJC 6-G Highest voltage: 24.0 kV
Rated frequency: 50 Hz Rated ratio: 13800/ 3//110/ 3/110/3 V
Accuracy class: 0,2/3P Output: 45/50 VA
Production number: 1VLT5211014521 Year of production: 2011

TESTS:
1. Verification of terminal marking acc. to clause 9.1
Conclusion: Satisfactory
2. Power-frequency voltage withstand tests on primary windings acc.to clause 9.2
Separate source withstand voltage test when applicable acc.to clause 9.2.2.2a
Test value: 3 kV, 50 Hz, 1 minute
Conclusion: Satisfactory
3. Induced overvoltage withstand test acc.to clause 9.2.2.2b
Test value: 60.0 kV, 100 Hz, 1 minute
Conclusion: Satisfactory
4. Partial discharge measurment acc.to clause 9.2.4.2 procedure A
1,2Um : 28 pC
1,2Um/ 3 : 4 pC
Conclusion: Satisfactory
5. Power-frequency voltage withstand test between sections and on secondary windings acc.to clause 9.3
Test value: 3 kV, 100 Hz, 1 minute
Conclusion: Satisfactory
6. Tests for accuracy- measuring and protective windings acc.to clause 12.4 and 13.7.1
Winding: I: 45 VA/class 0,2
Winding: II: 50 VA/class 3P
Winding: III: - VA/class -
Conclusion: Satisfactory

The voltage transformer complies with tests required according to IEC Publications
60044 - 2.

Brno, the: 06.09.2011 Ing. Ku!era Jan

Headquarters: Mail Address:


ABB s.r.o. ABB s.r.o. Phone: + 420 5 4715 2609
Sokolovska 84-86 Videnska 117 Fax: + 420 5 4715 2626
186 00 Prague 8 619 00 Brno
Czech Republic Czech Republic
Job No.: 322890
Order-Item No.: 4500126971-010
Purchaseorder No.: 1HC0068399M0001
Customer No.: 15469/10010

Measurements with Automatic Transformer Test Set, ZERA


VOLTAGE TRANSFORMER
Serial No.: 1VLT5211014521
Test Object: TJC6-G:E43907934
Nominal Freq.: 50 Hz
Date: 06.09.2011 Operator: Petr Hykrda

Winding No. PXR//SXR(V) Burden(VA) COS ß % Un ei(%) di(min)


1 13800/ 3//110/ 3 45,00 0,80 120 -0.108 -0.900
1 13800/ 3//110/ 3 45,00 0,80 100 -0.109 -0.973
1 13800/ 3//110/ 3 45,00 0,80 80 -0.114 -1.022
1 13800/ 3//110/ 3 11,25 0,80 120 0.147 -0.839
1 13800/ 3//110/ 3 11,25 0,80 100 0.146 -0.895
1 13800/ 3//110/ 3 11,25 0,80 80 0.142 -0.944
2 13800/ 3//110/3 50,00 0,80 190 -0.907 7.068
2 13800/ 3//110/3 50,00 0,80 100 -0.896 6.130
2 13800/ 3//110/3 50,00 0,80 5 -1.020 8.308
2 13800/ 3//110/3 12,50 0,80 190 -0.459 1.568
2 13800/ 3//110/3 12,50 0,80 100 -0.448 0.964
2 13800/ 3//110/3 12,50 0,80 5 -0.543 1.671

Headquarters: Mail Address:


ABB s.r.o. ABB s.r.o. Phone: + 420 5 4715 2609
Sokolovska 84-86 Videnska 117 Fax: + 420 5 4715 2626
186 00 Prague 8 619 00 Brno
Czech Republic Czech Republic
Job No.: 322890
Order-Item No.: 4500126971-010
Purchaseorder No.: 1HC0068399M0001
Customer No.: 15469/10010

ROUTINE TESTS REPORT


VOLTAGE TRANSFORMER
Type: TJC 6-G Highest voltage: 24.0 kV
Rated frequency: 50 Hz Rated ratio: 13800/ 3//110/ 3/110/3 V
Accuracy class: 0,2/3P Output: 45/50 VA
Production number: 1VLT5211014522 Year of production: 2011

TESTS:
1. Verification of terminal marking acc. to clause 9.1
Conclusion: Satisfactory
2. Power-frequency voltage withstand tests on primary windings acc.to clause 9.2
Separate source withstand voltage test when applicable acc.to clause 9.2.2.2a
Test value: 3 kV, 50 Hz, 1 minute
Conclusion: Satisfactory
3. Induced overvoltage withstand test acc.to clause 9.2.2.2b
Test value: 60.0 kV, 100 Hz, 1 minute
Conclusion: Satisfactory
4. Partial discharge measurment acc.to clause 9.2.4.2 procedure A
1,2Um : 12 pC
1,2Um/ 3 : 3 pC
Conclusion: Satisfactory
5. Power-frequency voltage withstand test between sections and on secondary windings acc.to clause 9.3
Test value: 3 kV, 100 Hz, 1 minute
Conclusion: Satisfactory
6. Tests for accuracy- measuring and protective windings acc.to clause 12.4 and 13.7.1
Winding: I: 45 VA/class 0,2
Winding: II: 50 VA/class 3P
Winding: III: - VA/class -
Conclusion: Satisfactory

The voltage transformer complies with tests required according to IEC Publications
60044 - 2.

Brno, the: 05.09.2011 Ing. Ku!era Jan

Headquarters: Mail Address:


ABB s.r.o. ABB s.r.o. Phone: + 420 5 4715 2609
Sokolovska 84-86 Videnska 117 Fax: + 420 5 4715 2626
186 00 Prague 8 619 00 Brno
Czech Republic Czech Republic
Job No.: 322890
Order-Item No.: 4500126971-010
Purchaseorder No.: 1HC0068399M0001
Customer No.: 15469/10010

Measurements with Automatic Transformer Test Set, ZERA


VOLTAGE TRANSFORMER
Serial No.: 1VLT5211014522
Test Object: TJC6-G:E43907934
Nominal Freq.: 50 Hz
Date: 05.09.2011 Operator: Petr Hykrda

Winding No. PXR//SXR(V) Burden(VA) COS ß % Un ei(%) di(min)


1 13800/ 3//110/ 3 45,00 0,80 120 -0.114 -0.762
1 13800/ 3//110/ 3 45,00 0,80 100 -0.118 -0.827
1 13800/ 3//110/ 3 45,00 0,80 80 -0.125 -0.841
1 13800/ 3//110/ 3 11,25 0,80 120 0.145 -0.855
1 13800/ 3//110/ 3 11,25 0,80 100 0.142 -0.893
1 13800/ 3//110/ 3 11,25 0,80 80 0.136 -0.915
2 13800/ 3//110/3 50,00 0,80 190 -0.916 7.015
2 13800/ 3//110/3 50,00 0,80 100 -0.909 6.199
2 13800/ 3//110/3 50,00 0,80 5 -1.067 8.443
2 13800/ 3//110/3 12,50 0,80 190 -0.459 1.396
2 13800/ 3//110/3 12,50 0,80 100 -0.452 0.915
2 13800/ 3//110/3 12,50 0,80 5 -0.582 1.665

Headquarters: Mail Address:


ABB s.r.o. ABB s.r.o. Phone: + 420 5 4715 2609
Sokolovska 84-86 Videnska 117 Fax: + 420 5 4715 2626
186 00 Prague 8 619 00 Brno
Czech Republic Czech Republic
Job No.: 322890
Order-Item No.: 4500126971-010
Purchaseorder No.: 1HC0068399M0001
Customer No.: 15469/10010

ROUTINE TESTS REPORT


VOLTAGE TRANSFORMER
Type: TJC 6-G Highest voltage: 24.0 kV
Rated frequency: 50 Hz Rated ratio: 13800/ 3//110/ 3/110/3 V
Accuracy class: 0,2/3P Output: 45/50 VA
Production number: 1VLT5211014523 Year of production: 2011

TESTS:
1. Verification of terminal marking acc. to clause 9.1
Conclusion: Satisfactory
2. Power-frequency voltage withstand tests on primary windings acc.to clause 9.2
Separate source withstand voltage test when applicable acc.to clause 9.2.2.2a
Test value: 3 kV, 50 Hz, 1 minute
Conclusion: Satisfactory
3. Induced overvoltage withstand test acc.to clause 9.2.2.2b
Test value: 60.0 kV, 100 Hz, 1 minute
Conclusion: Satisfactory
4. Partial discharge measurment acc.to clause 9.2.4.2 procedure A
1,2Um : 28 pC
1,2Um/ 3 : 3 pC
Conclusion: Satisfactory
5. Power-frequency voltage withstand test between sections and on secondary windings acc.to clause 9.3
Test value: 3 kV, 100 Hz, 1 minute
Conclusion: Satisfactory
6. Tests for accuracy- measuring and protective windings acc.to clause 12.4 and 13.7.1
Winding: I: 45 VA/class 0,2
Winding: II: 50 VA/class 3P
Winding: III: - VA/class -
Conclusion: Satisfactory

The voltage transformer complies with tests required according to IEC Publications
60044 - 2.

Brno, the: 05.09.2011 Ing. Ku!era Jan

Headquarters: Mail Address:


ABB s.r.o. ABB s.r.o. Phone: + 420 5 4715 2609
Sokolovska 84-86 Videnska 117 Fax: + 420 5 4715 2626
186 00 Prague 8 619 00 Brno
Czech Republic Czech Republic
Job No.: 322890
Order-Item No.: 4500126971-010
Purchaseorder No.: 1HC0068399M0001
Customer No.: 15469/10010

Measurements with Automatic Transformer Test Set, ZERA


VOLTAGE TRANSFORMER
Serial No.: 1VLT5211014523
Test Object: TJC6-G:E43907934
Nominal Freq.: 50 Hz
Date: 05.09.2011 Operator: Jiri Tesarek

Winding No. PXR//SXR(V) Burden(VA) COS ß % Un ei(%) di(min)


1 13800/ 3//110/ 3 45,00 0,80 120 -0.088 -0.497
1 13800/ 3//110/ 3 45,00 0,80 100 -0.088 -0.585
1 13800/ 3//110/ 3 45,00 0,80 80 -0.089 -0.655
1 13800/ 3//110/ 3 11,25 0,80 120 0.165 -0.401
1 13800/ 3//110/ 3 11,25 0,80 100 0.166 -0.470
1 13800/ 3//110/ 3 11,25 0,80 80 0.165 -0.539
2 13800/ 3//110/3 50,00 0,80 190 -0.887 7.366
2 13800/ 3//110/3 50,00 0,80 100 -0.873 6.485
2 13800/ 3//110/3 50,00 0,80 5 -0.966 8.364
2 13800/ 3//110/3 12,50 0,80 190 -0.439 1.903
2 13800/ 3//110/3 12,50 0,80 100 -0.425 1.332
2 13800/ 3//110/3 12,50 0,80 5 -0.486 1.730

Headquarters: Mail Address:


ABB s.r.o. ABB s.r.o. Phone: + 420 5 4715 2609
Sokolovska 84-86 Videnska 117 Fax: + 420 5 4715 2626
186 00 Prague 8 619 00 Brno
Czech Republic Czech Republic
Job No.: 322890
Order-Item No.: 4500126971-010
Purchaseorder No.: 1HC0068399M0001
Customer No.: 15469/10010

ROUTINE TESTS REPORT


VOLTAGE TRANSFORMER
Type: TJC 6-G Highest voltage: 24.0 kV
Rated frequency: 50 Hz Rated ratio: 13800/ 3//110/ 3/110/3 V
Accuracy class: 0,2/3P Output: 45/50 VA
Production number: 1VLT5211014524 Year of production: 2011

TESTS:
1. Verification of terminal marking acc. to clause 9.1
Conclusion: Satisfactory
2. Power-frequency voltage withstand tests on primary windings acc.to clause 9.2
Separate source withstand voltage test when applicable acc.to clause 9.2.2.2a
Test value: 3 kV, 50 Hz, 1 minute
Conclusion: Satisfactory
3. Induced overvoltage withstand test acc.to clause 9.2.2.2b
Test value: 60.0 kV, 100 Hz, 1 minute
Conclusion: Satisfactory
4. Partial discharge measurment acc.to clause 9.2.4.2 procedure A
1,2Um : 25 pC
1,2Um/ 3 : 3 pC
Conclusion: Satisfactory
5. Power-frequency voltage withstand test between sections and on secondary windings acc.to clause 9.3
Test value: 3 kV, 100 Hz, 1 minute
Conclusion: Satisfactory
6. Tests for accuracy- measuring and protective windings acc.to clause 12.4 and 13.7.1
Winding: I: 45 VA/class 0,2
Winding: II: 50 VA/class 3P
Winding: III: - VA/class -
Conclusion: Satisfactory

The voltage transformer complies with tests required according to IEC Publications
60044 - 2.

Brno, the: 05.09.2011 Ing. Ku!era Jan

Headquarters: Mail Address:


ABB s.r.o. ABB s.r.o. Phone: + 420 5 4715 2609
Sokolovska 84-86 Videnska 117 Fax: + 420 5 4715 2626
186 00 Prague 8 619 00 Brno
Czech Republic Czech Republic
Job No.: 322890
Order-Item No.: 4500126971-010
Purchaseorder No.: 1HC0068399M0001
Customer No.: 15469/10010

Measurements with Automatic Transformer Test Set, ZERA


VOLTAGE TRANSFORMER
Serial No.: 1VLT5211014524
Test Object: TJC6-G:E43907934
Nominal Freq.: 50 Hz
Date: 05.09.2011 Operator: Petr Hykrda

Winding No. PXR//SXR(V) Burden(VA) COS ß % Un ei(%) di(min)


1 13800/ 3//110/ 3 45,00 0,80 120 -0.112 -0.430
1 13800/ 3//110/ 3 45,00 0,80 100 -0.117 -0.491
1 13800/ 3//110/ 3 45,00 0,80 80 -0.124 -0.510
1 13800/ 3//110/ 3 11,25 0,80 120 0.143 -0.412
1 13800/ 3//110/ 3 11,25 0,80 100 0.140 -0.458
1 13800/ 3//110/ 3 11,25 0,80 80 0.133 -0.483
2 13800/ 3//110/3 50,00 0,80 190 -0.901 7.324
2 13800/ 3//110/3 50,00 0,80 100 -0.892 6.395
2 13800/ 3//110/3 50,00 0,80 5 -1.079 8.663
2 13800/ 3//110/3 12,50 0,80 190 -0.454 1.794
2 13800/ 3//110/3 12,50 0,80 100 -0.444 1.228
2 13800/ 3//110/3 12,50 0,80 5 -0.601 2.006

Headquarters: Mail Address:


ABB s.r.o. ABB s.r.o. Phone: + 420 5 4715 2609
Sokolovska 84-86 Videnska 117 Fax: + 420 5 4715 2626
186 00 Prague 8 619 00 Brno
Czech Republic Czech Republic
Job No.: 322890
Order-Item No.: 4500126971-020
Purchaseorder No.: 1HC0068399M0001
Customer No.: 15469/10010

ROUTINE TESTS REPORT


VOLTAGE TRANSFORMER
Type: TJC 6-G Highest voltage: 24.0 kV
Rated frequency: 50 Hz Rated ratio: 13800/ 3//110/ 3/110/ 3 V
Accuracy class: 0,2/3P Output: 25/20 VA
Production number: 1VLT5211014528 Year of production: 2011

TESTS:
1. Verification of terminal marking acc. to clause 9.1
Conclusion: Satisfactory
2. Power-frequency voltage withstand tests on primary windings acc.to clause 9.2
Separate source withstand voltage test when applicable acc.to clause 9.2.2.2a
Test value: 3 kV, 50 Hz, 1 minute
Conclusion: Satisfactory
3. Induced overvoltage withstand test acc.to clause 9.2.2.2b
Test value: 60.0 kV, 100 Hz, 1 minute
Conclusion: Satisfactory
4. Partial discharge measurment acc.to clause 9.2.4.2 procedure A
1,2Um : 18 pC
1,2Um/ 3 : 3 pC
Conclusion: Satisfactory
5. Power-frequency voltage withstand test between sections and on secondary windings acc.to clause 9.3
Test value: 3 kV, 100 Hz, 1 minute
Conclusion: Satisfactory
6. Tests for accuracy- measuring and protective windings acc.to clause 12.4 and 13.7.1
Winding: I: 25 VA/class 0,2
Winding: II: 20 VA/class 3P
Winding: III: - VA/class -
Conclusion: Satisfactory

The voltage transformer complies with tests required according to IEC Publications
60044 - 2.

Brno, the: 05.09.2011 Ing. Ku!era Jan

Headquarters: Mail Address:


ABB s.r.o. ABB s.r.o. Phone: + 420 5 4715 2609
Sokolovska 84-86 Videnska 117 Fax: + 420 5 4715 2626
186 00 Prague 8 619 00 Brno
Czech Republic Czech Republic
Job No.: 322890
Order-Item No.: 4500126971-020
Purchaseorder No.: 1HC0068399M0001
Customer No.: 15469/10010

Measurements with Automatic Transformer Test Set, ZERA


VOLTAGE TRANSFORMER
Serial No.: 1VLT5211014528
Test Object: TJC6-G:E43920144
Nominal Freq.: 50 Hz
Date: 05.09.2011 Operator: Petr Hykrda

Winding No. PXR//SXR(V) Burden(VA) COS ß % Un ei(%) di(min)


1 13800/ 3//110/ 3 25,00 0,80 120 -0.135 -2.025
1 13800/ 3//110/ 3 25,00 0,80 100 -0.135 -2.153
1 13800/ 3//110/ 3 25,00 0,80 80 -0.138 -2.251
1 13800/ 3//110/ 3 6,25 0,80 120 0.101 -0.118
1 13800/ 3//110/ 3 6,25 0,80 100 0.101 -0.227
1 13800/ 3//110/ 3 6,25 0,80 80 0.099 -0.326
2 13800/ 3//110/ 3 20,00 0,80 190 -0.091 0.198
2 13800/ 3//110/ 3 20,00 0,80 100 -0.072 -0.842
2 13800/ 3//110/ 3 20,00 0,80 5 -0.186 0.735
2 13800/ 3//110/ 3 5,00 0,80 190 0.131 1.268
2 13800/ 3//110/ 3 5,00 0,80 100 0.149 0.410
2 13800/ 3//110/ 3 5,00 0,80 5 0.059 1.289

Headquarters: Mail Address:


ABB s.r.o. ABB s.r.o. Phone: + 420 5 4715 2609
Sokolovska 84-86 Videnska 117 Fax: + 420 5 4715 2626
186 00 Prague 8 619 00 Brno
Czech Republic Czech Republic
Job No.: 322890
Order-Item No.: 4500126971-020
Purchaseorder No.: 1HC0068399M0001
Customer No.: 15469/10010

ROUTINE TESTS REPORT


VOLTAGE TRANSFORMER
Type: TJC 6-G Highest voltage: 24.0 kV
Rated frequency: 50 Hz Rated ratio: 13800/ 3//110/ 3/110/ 3 V
Accuracy class: 0,2/3P Output: 25/20 VA
Production number: 1VLT5211014529 Year of production: 2011

TESTS:
1. Verification of terminal marking acc. to clause 9.1
Conclusion: Satisfactory
2. Power-frequency voltage withstand tests on primary windings acc.to clause 9.2
Separate source withstand voltage test when applicable acc.to clause 9.2.2.2a
Test value: 3 kV, 50 Hz, 1 minute
Conclusion: Satisfactory
3. Induced overvoltage withstand test acc.to clause 9.2.2.2b
Test value: 60.0 kV, 100 Hz, 1 minute
Conclusion: Satisfactory
4. Partial discharge measurment acc.to clause 9.2.4.2 procedure A
1,2Um : 20 pC
1,2Um/ 3 : 3 pC
Conclusion: Satisfactory
5. Power-frequency voltage withstand test between sections and on secondary windings acc.to clause 9.3
Test value: 3 kV, 100 Hz, 1 minute
Conclusion: Satisfactory
6. Tests for accuracy- measuring and protective windings acc.to clause 12.4 and 13.7.1
Winding: I: 25 VA/class 0,2
Winding: II: 20 VA/class 3P
Winding: III: - VA/class -
Conclusion: Satisfactory

The voltage transformer complies with tests required according to IEC Publications
60044 - 2.

Brno, the: 05.09.2011 Ing. Ku!era Jan

Headquarters: Mail Address:


ABB s.r.o. ABB s.r.o. Phone: + 420 5 4715 2609
Sokolovska 84-86 Videnska 117 Fax: + 420 5 4715 2626
186 00 Prague 8 619 00 Brno
Czech Republic Czech Republic
Job No.: 322890
Order-Item No.: 4500126971-020
Purchaseorder No.: 1HC0068399M0001
Customer No.: 15469/10010

Measurements with Automatic Transformer Test Set, ZERA


VOLTAGE TRANSFORMER
Serial No.: 1VLT5211014529
Test Object: TJC6-G:E43920144
Nominal Freq.: 50 Hz
Date: 05.09.2011 Operator: Petr Hykrda

Winding No. PXR//SXR(V) Burden(VA) COS ß % Un ei(%) di(min)


1 13800/ 3//110/ 3 25,00 0,80 120 -0.101 -1.260
1 13800/ 3//110/ 3 25,00 0,80 100 -0.101 -1.406
1 13800/ 3//110/ 3 25,00 0,80 80 -0.105 -1.534
1 13800/ 3//110/ 3 6,25 0,80 120 0.133 0.599
1 13800/ 3//110/ 3 6,25 0,80 100 0.133 0.475
1 13800/ 3//110/ 3 6,25 0,80 80 0.131 0.352
2 13800/ 3//110/ 3 20,00 0,80 190 -0.047 1.042
2 13800/ 3//110/ 3 20,00 0,80 100 -0.026 -0.108
2 13800/ 3//110/ 3 20,00 0,80 5 -0.149 1.929
2 13800/ 3//110/ 3 5,00 0,80 190 0.174 2.104
2 13800/ 3//110/ 3 5,00 0,80 100 0.194 1.164
2 13800/ 3//110/ 3 5,00 0,80 5 0.094 2.527

Headquarters: Mail Address:


ABB s.r.o. ABB s.r.o. Phone: + 420 5 4715 2609
Sokolovska 84-86 Videnska 117 Fax: + 420 5 4715 2626
186 00 Prague 8 619 00 Brno
Czech Republic Czech Republic
Job No.: 322890
Order-Item No.: 4500126971-020
Purchaseorder No.: 1HC0068399M0001
Customer No.: 15469/10010

ROUTINE TESTS REPORT


VOLTAGE TRANSFORMER
Type: TJC 6-G Highest voltage: 24.0 kV
Rated frequency: 50 Hz Rated ratio: 13800/ 3//110/ 3/110/ 3 V
Accuracy class: 0,2/3P Output: 25/20 VA
Production number: 1VLT5211014530 Year of production: 2011

TESTS:
1. Verification of terminal marking acc. to clause 9.1
Conclusion: Satisfactory
2. Power-frequency voltage withstand tests on primary windings acc.to clause 9.2
Separate source withstand voltage test when applicable acc.to clause 9.2.2.2a
Test value: 3 kV, 50 Hz, 1 minute
Conclusion: Satisfactory
3. Induced overvoltage withstand test acc.to clause 9.2.2.2b
Test value: 60.0 kV, 100 Hz, 1 minute
Conclusion: Satisfactory
4. Partial discharge measurment acc.to clause 9.2.4.2 procedure A
1,2Um : 26 pC
1,2Um/ 3 : 4 pC
Conclusion: Satisfactory
5. Power-frequency voltage withstand test between sections and on secondary windings acc.to clause 9.3
Test value: 3 kV, 100 Hz, 1 minute
Conclusion: Satisfactory
6. Tests for accuracy- measuring and protective windings acc.to clause 12.4 and 13.7.1
Winding: I: 25 VA/class 0,2
Winding: II: 20 VA/class 3P
Winding: III: - VA/class -
Conclusion: Satisfactory

The voltage transformer complies with tests required according to IEC Publications
60044 - 2.

Brno, the: 05.09.2011 Ing. Ku!era Jan

Headquarters: Mail Address:


ABB s.r.o. ABB s.r.o. Phone: + 420 5 4715 2609
Sokolovska 84-86 Videnska 117 Fax: + 420 5 4715 2626
186 00 Prague 8 619 00 Brno
Czech Republic Czech Republic
Job No.: 322890
Order-Item No.: 4500126971-020
Purchaseorder No.: 1HC0068399M0001
Customer No.: 15469/10010

Measurements with Automatic Transformer Test Set, ZERA


VOLTAGE TRANSFORMER
Serial No.: 1VLT5211014530
Test Object: TJC6-G:E43920144
Nominal Freq.: 50 Hz
Date: 05.09.2011 Operator: Petr Hykrda

Winding No. PXR//SXR(V) Burden(VA) COS ß % Un ei(%) di(min)


1 13800/ 3//110/ 3 25,00 0,80 120 -0.130 -2.376
1 13800/ 3//110/ 3 25,00 0,80 100 -0.132 -2.475
1 13800/ 3//110/ 3 25,00 0,80 80 -0.138 -2.535
1 13800/ 3//110/ 3 6,25 0,80 120 0.104 -0.523
1 13800/ 3//110/ 3 6,25 0,80 100 0.102 -0.594
1 13800/ 3//110/ 3 6,25 0,80 80 0.097 -0.662
2 13800/ 3//110/ 3 20,00 0,80 190 -0.090 -0.341
2 13800/ 3//110/ 3 20,00 0,80 100 -0.074 -1.241
2 13800/ 3//110/ 3 20,00 0,80 5 -0.212 0.424
2 13800/ 3//110/ 3 5,00 0,80 190 0.131 0.710
2 13800/ 3//110/ 3 5,00 0,80 100 0.145 0.006
2 13800/ 3//110/ 3 5,00 0,80 5 0.031 0.987

Headquarters: Mail Address:


ABB s.r.o. ABB s.r.o. Phone: + 420 5 4715 2609
Sokolovska 84-86 Videnska 117 Fax: + 420 5 4715 2626
186 00 Prague 8 619 00 Brno
Czech Republic Czech Republic
^ I S ^

PFIFFNER .«É^.'
Stückprüfung / Routine Test STS210I
Pli
^ST\t

Prüfprotokoll für Stromwandler Test report for current transformers


Kunde/Client ABB Schweiz AG Komm.-Nr./Komm.No. 2011.3391.02
Best-Nr./ Order No. 4500127514 Stück/ Units 3
Anlage/Station Kont: 15469/10010 Hua Na HPP Seite/Page 1/11
Typ/ Type JKQ 870 C Frequenz/ Frequency 50 Hz
Norm/ Standard IEC 60044-1 I cth 100 %
Spannung/Voltage 36/80/150kV

Routineprüfungen/ Routine tests:


Steh-Wechsefspannungsprüfungen/ Power frequency voltage withstand tests
Sec - (Sec, Masse/ Ground) 3.0 kV 50 Hz 60s 0
Windungsprüfung CT/ Interturn overvoltage test CT 0
Genauigkeitsmessung/ Accuracy measurements
Fehlerbestimmung CT / Determination of errors CT 50 Hz 0
Polarität CT/ Polarity CT 0
Visuelle Kontrollen/ Visual check
Klemmenbezeichnung/ Terminal markings 0
Typenschild/ Rating plate 0
Visuelle Kontrollen/ Visual check 0

Kern IPR ISR Klasse Klemme


Core [A] [A] Class Terminal
1 5000 1 50 VA cl. 5P20 1S1-1S2
2 5000 1 50 VA cl. 5P20 2S1-2S2
3 5000 1 50 VA cl. 5P20 3S1-3S2

Datum: Geprüft: 'Alle Anforderungen erfüllt: fîFFNÉR


Date: Checked by i All requirements fulfilled: LABORATORY
04.10.2011
Hirschthal
..i__
ftjHISs^

PFIFFNER < ^ * STS210

Fehlerbestimmung Determination of errors


Typ/Type: JKQ 870 C Komm. No.: 2011.3391.02 Seite/Page: 2

Serie Kern Ubersetzunç / Ratio Grenzen/ Limits Fehler/ Error


Serial Core I prim. I sec. s cos ß Isec
No. No. [A] [A] [VA] [%] [%] [min] [%] [min]
001 1 5000 1.0 50.00 0.80 100 ±1.00 ±60 -0.12 +1
2 5000 1.0 50.00 0.80 100 ±1.00 ±60 -0.21 +3
3 5000 1.0 50.00 0.80 100 ±1.00 ±60 -0.13 +1

002 1 5000 1.0 50.00 0.80 100 ±1.00 ±60 -0.10 +1


2 5000 1.0 50.00 0.80 100 ±1.00 ±60 -0.14 +2
3 5000 1.0 50.00 0.80 100 ±1.00 ±60 -0.21 +2

003 1 5000 1.0 50.00 0.80 100 ±1.00 ±60 -0.08 +1


2 5000 1.0 50.00 0.80 100 ±1.00 ±60 -0.22 +3
3 5000 1.0 50.00 0.80 100 ±1.00 ±60 -0.29 +1

Form 302 De/En 4. Oktober 2011


^t»s^
PRFFNER ^ ^
Stückprüfung / Routine Test STS210
&i
^s T \f
Magnetisierungskurve Magnetization curve
I Typ/Type: JKQ 870 C Seite / Page: 3
! Komm.-Nr./Komm.No.: 2011.3391.02

-
- -"_ I I ^1 -~ ■ t
' 1
f
- I
f _ 1
i
' ! i
1
1 Ì
5000/1
!
1
- 1 --
- 1
f
/
- j 1 !- T r • I l ' I --- i". I
/ i 1 i
! ! , •

- -
Ì
! I j — ~
i
" T
i
/ i I
i
100 V-.

E
i - -_j_ 1

1 ! t
~ ' 1
f
i i
1 ',
i f ". .
i ,
1
10V —
1 " i
1
' t K
I !
• '
. 1 _
1
- 1 i
S
.'

i I
~ !
1
'. i I 1
1 V-
! ji. 1 1 î

0.001 A 0.01 A 0.1 A 1 A 10A

001 5000/1 5P20 50VA 14.3 lm@1241V| <1.0A\ 0.0146A <5% <0.1 % !0

04.10.2011
%JIS^

PFIFFNER ^529' Stückprüfung / Routine Test STS210


^ST\fPh

Magnetisierungskurve Magnetization curve


| Typ/Type: JKQ87ÖC Seite / Page: 4 ;
^Komm.-Nr./Komm.No.: 2011.3391.02

.,
: :'

1 "
~
i 1

, i î
• 5000/1
— - '
I i
' !
rooov-
K
- - A
, »
/ i
__ i . •
1 1

» i
i i i
100 v :
) " t

* _ __ lm
- -'-- --
Î
-

-• : i !- | . Ì


Î

--- .
1
[ i
j 1

! I !
; i f ( i
i
-I!

1V-
0.001 A 0.01 A 0.1 A 1 A 10A
ial N o.

Klasse Ret (75 °C) gefordert gemessen gefordert j gemessen


ie-Nr.

'PR/'SR
e-No.
n-Nr.

[A]/[A] Class [Q] required measured required ; measured


U. 1-
V O CD O
CO co !
* O
002 h 5000/1 5P20 50VA 14.4 lm@1242V| <1.0A 0.0131A Sc <5% <0.1 % 0

04.10.2011
*^ms^
PFIFFNER ^233' Stückprüfung / Routine Test STS210
Sah
^STVt

Magnetisierungskurve Magnetization curve


; Typ/Type: JKQ 870C Seite / Page: 5
i Komm.-Nr./Komm.No.: 2011.3391.02

10'OOOV
'
_ 1
i
; ' if
. '.J.|.
*
i
5000/1
i ; *
rooov - ' ! / *~ s
i
i
f , .
J ■' i _ _ _ _ _i_
i ;

i/ ! I I ! M j i
! / I IM ! 1 i
100 V
/ ' ' > ''"il :'
t
J'
— - 1 \
i

-
; " "i ì

10V
Ì
MMl i !
i

-. s , _" _ f
1" -
i

- — _i _ i
f
i
; " ;

i
i

i
1v
0.001 A 0.01 A 0.1 A 1 A 10A

'PR/'SR J Klasse R ct (75°C) gefordert gemessen gefordert j gemessen


âè ; il
1
z
O
z [A]/[A] ; Class [D] required measured required j measured
o « c i
o o> ! <u
co co 1 *
o
Ü

003 1 5000/1 j 5P20 50VA 14.4 Im @1242V <1.0A I 0.0127A <5% <0.1 % 0

04.10.2011
7$\\S^

PFIFFNER ^ ^ Stückprüfung / Routine Test STS210


^ST\S

Magnetisierungskurve Magnetization curve


: Typ/Type: JKQ 870 C Seite/Page: 6 !
! Komm.-Nr./Komm.No.: 2011.3391.02

10'OOOV

j I >/• 1 L.
. ' f
!
1 i J
"
1
i
■ "' :
f , , ', ■-
5000/1
i ,
" 1i i | l '
1'OOOV l
s 5- ' J
! *
1
i

._} i_._J_.ji ..... _ j i ,

. „ i :. i.

100 V . ' ' '. i


i

< 1 f
< i
... ^ _ . i ,„_
* ,-i i.
\ -
?

! f
.....
j 1
i

j i
10 V ~-~
: i
j
! i i *"" , i 1
1 i
' , i ' r i i
f
t
! ! i !. i 1 !I
! i

i T ' ! ; • | ì Î
4-
i ' ' 1 1 i 1 I
1 V
0.001 A
t . < .

0.01 A
.

0.1 A
1 ; '1 A , i . .

10A
Core-No. ,
i
Kern-Nr. .

R c t (75_0C)
Serial No.

'PR/'SR Klasse gefordert gemessen gefordert igemessen


Serie-Nr.

[A]/[A] Class [Q] required measured required i measured

001 2 5000/1 5P20 50VA 14.4 lm@1243v! <1.0A 0.0142A Sc <5% f <0.1 % 0

04.10.2011
<^ns^
PFIFFNER ^ ^
Stückprüfung / Routine Test STS210
, A . V .©
'sj\t>

Magnetisierungskurve Magnetization curve


Typ/Type: JKQ870 C Seite/Page: 7
Komm.-Nr./Komm.No.: 2011.3391.02

• - U . . >} '
i : ' 1:
, 4—.'
-- ; , .1 i ' t i . * J.l
J '
!i A
) - ' ! -
1 | ,'
1 i'
• 5000/1
l
t /"""I ' ' , | ,
si ; '_' /
- -- -[ Y
f
~ '-,- - i
i i

... i. 1 i.
1 / i
_. . ._
i X
! ! { i
/ i , • ... ,
100 v : !
!
t ' F 1 } '
_ 1 f
_ "l - - - —
!
1
1 ; ,
.. -
'
f

--- ,. .^-.
; : ' .'
i t
r
i { > - t
i i !
i i
—£....,

f \ ' !
~ 1

! [ '
. 1 . :.Ü 1 > j i 'i
1 V- l !
0.001 A 0.01 A 0.1 A 1A 10A
ial No.

'PR/ISR Klasse R c t (75°C) gefordert gemessen gefordert gemessen


e-No.
ie-Nr.

n-Nr.

[A]/[A] Class [Q] required measured required measured


cu o
! CO CO * O

002 12 5000/1 5P20 50VA 14.4 lm@1242Vj <1.0A 0.0136A <5% | <0.1 % M

04.10.2011
Î ^ I S ^

PFIFFNER ^233' Stückprüfung / Routine Test STS210 .©//


^ST\t

Magnetisierungskurve Magnetization curve


; Typ/Type: JKQ 870 C Seite / Page: 8
Komm.-Nr./Komm.No.: 2011.3391.02

10'OOOV
. • !
- : - -': i
1

! , i
• 5000/1
\ ^ - i
,
j
1'OOOV
• " --" - i ì -i
< i

i ! i1 ! ' ì
r
1 [ l i , • j
1 Ì ' ! i ! i
100 V
-
. "...
1

' 1 , i 1
i

10V
!

-
i
- i

' l i
! ]
l i l i ' .

\r !
1V \ —H- ! ! i î !
0.001 A 0.01 A 0.1 A 1 A 10A

Klasse R c t (75°C) gefordert gemessen gefordert


±£ ! * ° 'PR/'SR
[A]/[A] Class required i measured required
I gemessen
measured
[Q]
"C 'C i i- t
D ni : ni o
CO </) ! * O

! 003 <2 5000/1 5P20 50VA 14.4 lm@1243V| <1.0A 0.0127A <5% <0.1 % |0

04.10.2011
^NIS^

PFIFFNER d^' Stückprüfung / Routine Test STS210


^ST\^

Mag netisierungs kurve Magnetization curve


JTyp/Type: JKQ870C Seite / Page: 9
| Komm.-Nr./Komm.No.: 2011.3391.02

1
\
f ; |!
1
i -
1 •
• 5000/1
, , I . f 1
f
rooov : i
î
J
i"
[
i I
_ , -|-- -
1
1 ", 1
t
i
i
1 1

™ Tj
/
- _ !_
T,T1
! ._
- " 1
-| |r r " 1
- \ , i ; i
- "Î
î î
i ™ {"

. t
i
> f

\ i

i 1 1
i
i i i j
!
7 t
- t
- - • ,
1 _ ' 11
• r i V;i i
> i -j
1 t
-
f . (- i

! •1
IV-
r ! i l :
! i 1 1 ii 1

0.001 A 0.01 A 0.1 A 1 A 10A

gemessen gefordert
Serial No.

'PR/'SR Klasse Ret (75 °C) gefordert gemessen


Core-No.
Serie-Nr.

Kern-Nr.

[A]/[A] Class [Q] required measured required measured

5000/1] i 5P20 50VA 14.4 Im @1242V <1.0A <5% <0.1 % IEI


1001
A: 0.0139A

04.10.2011
PFIFFNER ^ ^
Stückprüfung / Routine Test STS210

Magnetisierungskurve Magnetization curve


i Typ/Type: JKQ 870 C Seite/ Page: 10
i Komm.-Nr./Komm.No.: 2011.3391.02

* ■

l!
- - il-- .
. ' ' I i f
) i
Ì -
1!
• ' ii "1 1
1
!
1 5000/1
I ' i
■, 1 ■ i:
4 -'
) • i
* !
„„_ ,„

*
i À
1 M, î_4_=_u.
I 11 1 1 1 I
i
1
1
i
J

1 1
!
- _ - i-
1
.
!
i
ä
i
1
;
i
!
;
iff:
:
_
i
—- "i

! *j"
, i
1 11
1
1
j
| !
!1
10V
i i
r -* — :
" - " r ; j
■ i™™ - ~„ - ~~r
zz4^ti:
1
1 -. r-T,i, ! f H-
...... „...j...
'i

i i
' i f
i ..! .. i.
i
i
ä
)
! 1
1 V-
0.001 A 0.01 A 0.1 A 1 A 10A

^ J i ^ d I 'PR/'SR Klasse R ct (75°C) gefordert ! gemessen gefordert gemessen


1
A « A ^ ! [A]/[A] Class required measured required measured
0) o V o
co co * o
1002 ì3 5000/1 5P20 50VA 14.4 lm(® 1242V <1.0A ! 0.0131A I <5% <0.1 % 0

04.10.2011
^JIS^

PFIFFNER ^ ^
Stückprüfung / Routine Test STS210
^ST\^

Magnetisierungskurve Magnetization curve


Ì Typ/Type: JKQ 870 C Seite / Page: 11
Komm.-Nr./Komm.No.: 2011.3391.02

î! ,
; ; 1
. '.
, 1

! , ,
- :
1 •

• :!: i
5000/1
—■- i ; 1 , '
rooov-
i ' i
j
1
i "' > ' '
1
...
-i -
1

f\ : i

, .
100 V
i ' * ■ •
j
/ I

, j ,- s j
j i
, 1
f
1 '
' i <
- i ; i "i f -
1 i 1
1 . 1 , I
i
10 V-
l i
1 1

J
' :
i ■ ;
! i i__

1 V-
f ' , '
1 ! ! . i,,! ; ; | ; ; i M-

! , 1 , 1 1 ,

0.001 A 0.01 A 0.1 A 1 A 10A

a
CO M
c o 'PR/'SR
[A]/[A]
Klasse
Class
Ret (75 °C)
[Q]
gefordert
required
j gemessen gefordert
j measured required
gemessen
measured
0) o
<D CO
* o
CO co
! 003 !3 5000/1 5P20 50VA 14.3 lm@1241V <1.0A [ i0.0130A
<l.UA -c i
<5% } <0.1 % i0

04.10.2011
ABB Switzerland Ltd.
page 1 / 4

Test report
Factory tests on Metal-oxide Surge Arresters without gaps (MO-arresters)

Standard: EN / IEC 60099-4


ABB internal test specification: HATW 600 359

Ordernumber 535828 Type of arrester POLIM-H 17 N 20KA


Order item 10 Pieces 6
Date of delivery 23.09.2011
Test station Mittelspannung 2

Required measurements and tolerances


Measurement with AC at f = 50.0 Hz
Measurement Urefat iref = 5.0 mA pk Required value Uref = 20.6....23.8 kV rms
Measurement ic at Uc = 17.0 kV rms Required value ic = 0.7....1.8 mA pk
Measurement Partial discharges at 1.05 Uc Required value TE ≤ 5.0 pC

A
This test report contains 4 pages Factory test carried out 254
- Cover sheet
- measured values
- Annex

Date: 21. September 2011 ABB Switzerland Ltd.


Surge Arresters PTHA
CH-Wettingen

EN
1761032

We reserve all rights in this document and the information contained therein. Reproduction, use or disclosure to third parties without express authority is
strictly forbidden.(c) Copyright 2006 ABB. All rights reserved.
ABB Switzerland Ltd.
page 2 / 4

Ordernumber 535828 Type of arrester POLIM-H 17 N 20KA

Order item 10 Required values


Uref = 20.6....23.8 kV rms
ic = 0.7....1.8 mA pk
TE ≤ 5.0 pC

Measured
values
HA - number Uref ic TE
[U] = kV rms [i] = mA pk [TE] = pC
10540725 22.47 1.241 2.904
10540726 22.48 1.245 2.215
10540727 22.45 1.247 2.461
10540728 22.39 1.237 2.362
10540729 22.37 1.243 2.313
10540730 22.51 1.241 2.313

We reserve all rights in this document and the information contained therein. Reproduction, use or disclosure to third parties without express authority is
strictly forbidden.(c) Copyright 2006 ABB. All rights reserved.
ABB Switzerland Ltd.
page 3 / 4

Ordernumber 535828 Type of arrester POLIM-H 17 N 20KA

Order item 10

Principle diagram of test circuit


AC/DC switch

DC source
0 - 100 kV
0 - 10 mA

Arrester

Voltage
divider
AC source

Shunt
0 - 100 kV pC kV W mA

0 - 300 V 0 - 10 mA
15 - 62 Hz

Measuring equipment

Test circuit and measuring devices are calibrated on a regulare base acc. to SQS requirements

Ambient conditions during test


Airpressure 969.6 mbar
relative humidity 46.9 %
Ambient temperature 25.7 ° C

Current- / voltage curves


The u-i-curves of the first surge arrester only are given
Surge Arrester with HA - number 10540725
Uref at iref ic at Uc
30
25 4 U 20 1 U
20 I 15 I
15
2 10 0.5
10
U, [U] = kV

U, [U] = kV
I, [I] = mA

I, [I] = mA

5 5
0 0 0 0
-5 -5
-10
-2 -10 -0.5
-15
-20 -15
-25 -4 -20 -1
-30
0 5 10 15 0 5 10 15
t, [t] = ms t, [t] = ms

Note: the given current and voltage curves are for information only. Deciding for the result of the routine test is exclusively
the value in the list of measuring results.

We reserve all rights in this document and the information contained therein. Reproduction, use or disclosure to third parties without express authority is
strictly forbidden.(c) Copyright 2006 ABB. All rights reserved.
ABB Switzerland Ltd.
page 4 / 4

Legend

Routine tests
According to IEC 60099-4 the required routine tests to be made by the manufacturer shall be in minimum the following:

a) Measurement of reference voltage Uref. The measured values shall be within a range specified by the manufacturer.
b) Residual voltage test. The test may be performed either on complete arresters, assembled arrester units a single resistor
element. In ABB each MO-resistor is routine tested with I = 10 kA 8/20 µs. Therefore, on complete arresters the residual
voltage test is not performed.
c) Internal partial discharge test. This test is performed on each arrester unit. For distribution arresters this is generally the
complete arrester.
d) Leakage check. This test is not applicable for completely moulded arresters (e.g. for all arresters without a gas volume in
the inside).
e) Current distribution test for multi-column arresters. This test is carried out on all resistors or groups of resistors connected
electrically in parallel, if they are to be installed in one arrester housing.

In addition ABB Switzerland carries out the following routine test:


- Measurement of the continuous current ic at continuous operating voltage Uc.

Definitions
In IEC 60099-4 are given the following arrester related definitions:

Continuous operating voltage of an arrester Uc: designated permissible r.m.s. value of power-frequency voltage that may be
applied continuously between the arrester terminals.

Rated voltage of an arrester Ur: maximum permissible r.m.s. value of power-frequency voltage between its terminals at which it
is designated to operate correctly under temporary overvoltage conditions as established in the operating duty tests.

Reference voltage of an arrester Uref: peak value of power-frequency voltage divided by √2 which is applied to the arrester to
obtain the reference current.

Residual voltage of an arrester Ures: peak value of voltage that appears between the terminals of an arrester during the passage
of discharge current.

Continuous current of an arrester (ic): current flowing through the arrester when energized at the continuous operating voltage.

Reference current of an arrester (iref): peak value (the higher peak value of the two polarities if the current is asymmetrical) of
the resistive component of a power-frequency current used to determine the reference voltage of the arrester.

Nominal discharge current of an arrester In: peak value of lightning current impulse which is used to classify an arrester.

We reserve all rights in this document and the information contained therein. Reproduction, use or disclosure to third parties without express authority is
strictly forbidden.(c) Copyright 2006 ABB. All rights reserved.
TESTREPORT SF6-DENSITY-CONTROLLER TRAFAG AG

Type No: 8730.20.2001.IL Order No. ABB: I43-4500122561


Production lot: 409540 Account No. ABB:
Ident No. ABB: 1HC0023254R0001
Tests:
Leakage test: 100% tested with He date: 29.08.2011 tested by: 2524 ADA
Voltage test: 2kV; 50Hz (between circuits and ground) date: 30.08.2011 tested by: 2209 SL

Setpoint test: Absolute pressure measurement date: 30.08.2011 tested by: 2209 SL
Switch 1: Setpoint tolerance ± 8kPa* (decr. Pressure)
Switch 2: Setpoint tolerance ± 8kPa* (decr. Pressure)
Switch 3: Setpoint tolerance ± 8kPa* (decr. Pressure)
Switch 4: Setpoint tolerance ± 8kPa* (incr. Pressure)

Switch 1 Switch 2 Switch 3 Switch 4


Serial No. temp. setp. decr. incr. setp. decr. incr. setp. decr. incr. setp. decr. incr.
[°C] [kPa] [kPa] [kPa] [kPa] [kPa] [kPa] [kPa] [kPa] [kPa] [k Pa] [kPa] [kPa]

409540-025
025 50.7 608 607 610 628 627 632 608 607 611 --- --- ---
19.9 540 540 543 560 560 565 540 540 543 --- --- ---
-25.4 439 440 443 459 459 465 439 440 445 --- --- ---
409540-026
026 50.7 608 607 611 628 627 630 608 607 611 --- --- ---
19.9 540 540 544 560 559 563 540 540 544 --- --- ---
-25.4 439 440 444 459 459 462 439 441 445 --- --- ---
409540-027
027 50.7 608 606 610 628 628 632 608 606 610 --- --- ---
19.9 540 539 543 560 561 565 540 540 543 --- --- ---
-25.4 439 439 444 459 460 464 439 440 444 --- --- ---
409540-028
028 50.6 608 607 610 628 628 631 608 606 609 --- --- ---
19.9 540 541 544 560 561 564 540 540 543 --- --- ---
-25.4 439 441 445 459 461 464 439 440 444 --- --- ---
409540-029
029 50.6 608 606 611 628 627 630 608 606 610 --- --- ---
19.9 540 540 544 560 560 564 540 540 544 --- --- ---
-25.4 439 439 444 459 459 462 439 440 444 --- --- ---
409540-030
030 50.6 608 607 611 628 627 631 608 607 612 --- --- ---
19.9 540 541 545 560 560 564 540 541 545 --- --- ---
-25.4 439 440 443 459 458 462 439 440 445 --- --- ---
409540-031
031 50.6 608 607 611 628 628 632 608 607 612 --- --- ---
19.9 540 541 545 560 562 566 540 542 546 --- --- ---
-25.4 439 439 444 459 458 464 439 439 445 --- --- ---
409540-032
032 50.6 608 606 610 628 627 631 608 606 610 --- --- ---
19.9 540 541 545 560 562 566 540 541 545 --- --- ---
-25.3 439 440 444 459 459 463 439 439 444 --- --- ---

*or according to the agreement