LG CONTROL
MULTI V 5 offers a diverse range of effective control solutions that satisfy specific needs of each building and its user scene.
These controlling systems are equipped with user friendly interface, flexible interlocking environment, energy management and
smart individual controller for optimized controlling conditions and smart building management.

SOLUTION
HOTEL OFFICE

Hotel Room Solution


Central Control Solution

3rd Party BMS Service/Maintenance

· Energy Management

54kW

· External Device

36kW

Lighting Pump Fan CO2 SensorTemp. Sensor

24kW

APARTMENT RESIDENTIAL SMALL BUILDING

Power Distribution Solution Smart Individual Control Solution Small Central Control Solution

Integration Solution

008 009
OUTDOOR UNIT
MULTI V 5 MULTI V S
MULTI V WATER IV MULTI V WATER S
BRAND HISTORY
From the moment when LG introduced Korea’s first residential air conditioner in 1968, the company has continuously enhanced
its technological innovation and credibility. As a result of sustained improvement, LG VRF launched the first generation of MULTI V
in 2006 and achieved significant development. With world’s top class compressor and innovative technology competency applied
on every part, cycle and controlling solutions, it has evolved to be one of the world’s most efficient and reliable VRFs.

Following the first and second generations with Inverter technology and non-ozone depleting refrigerant, MULTI V III has advanced
its efficiency with diverse cutting-edge technologies such as HiPORTM that directly returns oil to compressor and Vapor Injection
that allows double compression by adding mid-pressure refrigerant. As acknowledged by the Eurovent Certification, the innovative
technologies of 4th generation secured MULTI V brand the product leadership based on efficient system like Smart Load Control that
controls operational load according to external temperature and other technologies that are optimized to manage refrigerant and
heat exchange for all cooling, heating and part load operations. Moreover, MULTI V developed wide range of VRF line-up that
could satisfy various types and size of building; MULTI V S is the VRF with side discharge, designed for small to mid-sized building and
MULTI V WATER is the water-cooled VRF solution with variable water flow controlling technology.

In 2017, finally, the time has arrived for the ultimate VRF system, MULTI V 5. This generation has fully improved its technological potential with
ever powerful and reliable yet economical LG’s Ultimate Inverter Compressor, Ocean Black Fin with the most effective corrosion resistance
performance and biomimetics technology-applied, enlarged fans. At the same time, the Dual Sensing Control offers users the most
pleasant environment while minimizing the unnecessary energy loss with system that senses both the temperature and humidity to
efficiently manage cooling, heating and part load operations. 2017
With MULTI V 5 that has been solely designed for the ultimate efficiency, performance, flexibility, comfort and control, we are
highly confident to bring the ultimate pleasant air experience.

*High Efficiency 220V, 460V only

· Dual Sensing Control


· Ultimate Inverter Compressor
· Large Capacity ODU with
Biomimetics Technology Fan
· Continuous Heating
· Ocean Black Fin

2006 2008 2010 2013

· Ø7.0 Corrugate · Heat Recovery · High Pressure Oil Return · Eurovent Certification
· Fuzzy Algorithm · Ø7.0 Wide louver · Vapor Injection · Active Refrigerant Control
· AC Inverter · Fuzzy Algorithm · Continuous Heating · Variable Heat Exchanger Circuit
· R410A · LGDC Inverter · Smart Load Control
· Smart Oil Return
· Vapor Injection (Advanced)

014 015
DUAL SENSING
The cooling load is based on the amount of both sensible heat load and latent heat load. Most importantly, the cooling load is keen
to, and thus, greatly affected by external humidity, rather than the outdoor temperature. For this reason, MULTI V 5’s Dual Sensing
Control applied function senses both temperature and humidity and applies sensed data for load control in order to obtain in-depth

CONTROL understanding of sensible heat load and latent heat load. This helps preventing excessive cooling load supply and offers the most
pleasant and comfortable cooling environment the users want combined with reduction in energy consumption.

Regular VRF : Single Sensing : Dual Sensing

Smart Load Control (SLC)


Were you aware that until now VRF has This comprehensive understanding of
Seasonal Efficiency
environmental conditions allows
only sensed a single referenced value? optimized energy efficiency and Up to 32%
maximized indoor comfort level. (vs. Standard mode
at 16RT, C/O model)

Comfort Cooling
This maintains operation at mild
cooling mode around set Improved Indoor
temperature without stopping in
between operations for maximized Comfort
user comfort.

016 017
ULTIMATE INVERTER
COMPRESSOR
As the core technology of the air conditioning system, the Ultimate Inverter Compressor of MULTI V 5 boasts its
ultimate efficiency and durability, designed based on the unique technology and innovation of LG HVAC.

All Inverter
Provide high efficiency with low vibration and low noise

Six By-pass Valves


Prevent compressor damage due to excessively
compressed refrigerant more efficiently than 4 by-pass valves

01. Vapor Injection


Maximize heating capacity via two-stage compression

02. Enhanced Bearing with PEEK Material


Newly invented system motivated by PEEK (Polyetheretherketone)
bearing used for aero engine to increase operation range and durability

03. Wide Operation Range from 10 to 165Hz


Improved part load efficiency at all operation ranges

04. HiPORTM (High Pressure Oil Return)


Resolve compressor efficiency loss caused by oil return

05. Smart Oil Management


Oil level detection in real time

018 019
*Based on 290 m3/min

LARGE CAPACITY ODU


WITH BIOMIMETICS As a result of the biomimetics technology invented through years of joint study with Department of Mechanical and Aerospace

TECHNOLOGY FAN Engineering of Seoul National University, the fan of MULTI V 5 increased wind capacity while it reduced its power consumption
when operating.

Large Capacity Outdoor Unit

Humpback Whale Design Clam Shell Pattern Increased Air Flow Rate Enhanced core parts like biomimetics technology-based fans, 4-sided heat exchanger as opposed to 3-sided heat exchanger of
Inspired by the bumps on the humpback Like the clam shell textures, the range With extended shroud, discharged previous model and compressor with increased efficiency and capacity allow large capacity for outdoor units. A single unit of
whale’s flipper, the tubercles on the back difference created by moire pattern air current is stabilized and power MULTI V 5 can provide up to 22RT.
side increased wind power by reducing reduced noise level. consumption is reduced.
flacking.

020 021
OCEAN BLACK FIN CONTINUOUS
HEAT EXCHANGER HEATING * High Efficiency line up onlys

LG’s exclusive “Ocean Black Fin” heat exchanger is specially designed for durable and long-lasting performance even in corrosive Improved technologies such as Dual Sensing Control, Partial Defrost and Smart Oil Management enhance Continuous Heating for
environments. The black coating is applied for protection from various corrosive external conditions and the hydrophilic film keeps increased heating capacity and indoor comfort. The delayed and partial defrost technologies minimize unnecessary operational
water from accumulating on the heat exchanger’s fin, minimizing moisture buildup. This improvement in durability prolongs the consumption to provide consistent heating.
product’s lifespan and lowers both the operational and maintenance costs.
Non-continuous heating model

Heating Operation Time Per Day Power Input


Up to 11% Down to 7%
* LG internal test result
* Test condition : Outdoor 2/1°C, Indoor 20/15°C, Humidity 83%

CERTIFICATE OF VALIDATION

Certificate Number / 4786735320-1 /


Report Reference 4786735320-15-1
Issue Date: 2015-03-25
Expiration Date: 2018-03-24
Issued to: LG Electronics Inc
76 Seongsan-dong, Changwon-Si, Gyeongnam,
641-713, Korea

Claim Validated: Aluminum Fin & Copper Tube Heat Exchanger


employed on the Outdoor Unit of Air-Conditioners.

Simulating the corrosive load for 27 years of


exposure in a more severe traffic environment with
salt contamination(Test Method B).

Tests: Test method B of ISO21207 :


Salt contaminated condition + severe industrial or
traffic environment

Standards / Regulations: ISO 21207, 6.2 & Annex A


LG(65)-E-8148

This certificate and the claim validation expire on the expiration date listed above. UL validated the claim
based upon criteria defined by the client. Client’s use of the validated claim on or in connection with the
product is and shall remain Client’s representation that the claim is true and accurate. UL neither
selected the samples nor determined whether the samples were representative of production units. The
test results apply only to the actual samples tested. UL is not responsible for the scope of the tests
performed or for the accuracy of test data generated by third parties. Please see test report for full
details including test standards.

This certificate in no way conveys or implies Listing, Classification or Recognition or other certification by
UL and does not authorize the use of UL Listing, Classification or Recognition Marks on or in connection
with the product. The validated claim relates solely to product performance and in no way conveys or
implies evaluation of the safety of the product identified above.

Churlbae Kim
Engineering Leader
Commercial & Industrial
UL Korea Ltd.
26th Fl. Gangnam Finance Center, 737
Yeoksam-dong, Gangnam-gu, Seoul, Korea

* Test Method B Simulation Validated Dual Sensing Control Partial Defrost Smart Oil Management
(Test condition: Salt contaminated condition +severe industrial/traffic environment (NO2/SO2)
* Based on 1,500 UL test hours

022 023
OUTDOOR UNIT
MULTI V 5 MULTI V 5

CONSULTANTS & HVAC DESIGNERS INSTALLERS


From accurate 3D-based building modeling to strong system capability regardless of the building size and climate Due to increased capacity provided by single outdoor units, installation became simpler with reduced number
conditions, MULTI V 5 offers the most efficient and flexible installation environment for consultants and HVAC of outdoor unit combination. Moreover, solutions connected to and operated by smart devices significantly
designers. Indeed, MULTI V 5 is the most reasonable HVAC system that has achieved the best efficiency through shortened physical hours required for test run, diagnose and monitoring of multiple services while making these
LG’s enhanced inner parts, operational cycle and controlling technology. controlling more accurate.

01 Improved designing effectiveness and accuracy via LATS Revit, 01 Increased installation convenience due to large capacity Previous Model

the BIM application units reducing number of outdoor units required for
combination
LG provides 3D-based BIM simulation tool, LATS Revit, in order to offer product
selection, positioning and piping from installation, interference check to correction
phases based on systematic consideration of the load. This enables the easiest, yet By providing up to 22RT for single unit line up, MULTI V 5 decreases the total number 436Kg
the most accurate system modeling support. of required outdoor units in order to ultimately simplify installation process, when x2
compared to previous models. For example, previous system required a combination
of a 20HP outdoor unit, a 18HP outdoor unit and a 10HP outdoor unit to run a total
of 48HP. For MULTI V 5, however, only 2 outdoor units with each providing 22RT can
02 Applicable to various climate conditions and purposes cover the same amount. This significantly reduces installation hours, especially those
48(DB)
that used to take long time such as using crane to properly place outdoor units on Reduction of
based on wide operational range for both heating and Installation
the rooftop.
cooling operations Space Area
18(WB)
312kg
Even in the extreme climate situations, MULTI V 5 can perform stable heating x1
0
and cooling operations. Due to LG’s improved inner parts and cycle technology, * Comparisons basis : 22RT
it can perform heating operation at extremely cold temperature as low as -25C. -15

For cooling performance, MULTI V 5 can operate from -15°C to 48°C. With wide -25
operational range, it can perfectly perform heating operation in cold environment, Heating Cooling
02 Simple and easy installation and service with Mobile LGMV
making the product adequate for uses in specialized venues like server rooms.
With LGMV, the smarter SVC application, hours and resources spent for installation
are significantly reduced and more accurate installation and service can be offered.

03 Flexible construction design available due to long piping Total Piping Length 1,000m
technology Actual longest piping length 225m Auto test run
Longest piping length after 1st branch Mobile application allows automatic address setting and test run report releasing.
40m (90m)
(conditional application)
Through the world’s best class piping technology MULTI V 5 provides the perfect Height between ODU ~ IDU 110m
solution for various types of building with diverse size and purposes. The longest Height between IDU ~ IDU 40m
piping length offered by MULTI V 5 is 225m and height difference between outdoor Height between ODU ~ ODU 5m Refrigerant diagnose solution
unit and indoor unit stretches up to 110m.
By regularly checking the amount of refrigerant, it automatically reloads if current
amount is not enough.

Easier setting for installers


04 The most economical solution with the world’s top class IEER (Cooling)
8.00 Unlike before when set up had to be done via DIP Switch of Outdoor unit, installers
energy efficiency can simply manage setting via mobile app for MULTI V 5. Indeed, settings for SLC
13% steps, Dual Sensing Control and outdoor unit fan’s maximum RPM control can be
Improved reliability based on LG’s Ultimate Inverter Compressor and other core parts, 7.08
easily managed via LGMV.
as well as the most developed controlling technology due to optimal cycle operation
achieved the world’s best class seasonal efficiency (IEER) of 8.00. As a result, this
Smart management
enables the most economical system capability for MULTI V 5 in comparison to any
other existing HVAC systems. By checking test run history, black box review and other previous records, site
Previous Model information can be managed efficiently.
* Comparison based on 8RT, C/O model *LGMV application is available for Android and iOS (iphone/ipad)
** IEER (Intergrated Energy Efficiency Ratio)
024 025
OUTDOOR UNIT
MULTI V 5 MULTI V 5

BUILDING OWNERS END USERS


With increased reliability of core parts such as compressor and heat exchanger, as well as high operational LG’s inverter technology and capability to actively respond to the building’s both internal and external
efficiency, building owners can significantly reduce operational costs in comparison to other systems. At the same environment allow users to quickly arrive at the desired ambient and systematically maintain such condition.
time, large capacity outdoor units minimize installation space which eventually allow better use of the floor space. Moreover, users can control the indoor environment remotely via smartphone from wherever and whenever.
Moreover, MULTI V 5 prevents overuse of the operational costs by planning and consuming the projected monthly Lastly, new Standard III Remote Controller with simple user interface and premium design provides users the
energy usage. optimal controlling experience.

01 Corrosion resistance via Ocean Black Fin 01 More comfortable cooling environment via Dual Sensing
Protection certified by UL (Underwriters Laboratories), LG’s exclusive Ocean Black Fin With the performance of LG’s Ultimate Inverter Compressor MULTI V 5 can quickly
is applied on the heat exchanger of MULTI V 5 in order to perform even in corrosive approach at user’s desired temperature. At the same time, the dual sensing technology
environments. The protection from various corrosive external environments such as controls and maintains indoor temperature pleasantly based on its recognition of
seaside with high salt contamination and industrial cities with severe air pollution both the temperature and humidity in order to offer the optimal user comfort.
caused by fumes from factories keeps MULTI V 5 operating without breakdown.

02 Minimized installation footprint via large capacity outdoor Previous Model 02 Continuous heating operation
units for flexible usage of the saved floor space Due to improved technologies of MULTI V 5 such as delayed defrost via Dual Sensing
• 53% Reduction in Space Control, partial defrost and smart oil management, users can enjoy pleasant and
MULTI V 5 provides up to 22RT for single unit line up. Considering that a total • 19% Reduction in Weight
of 220RT is being installed, the total installation space is saved up to 53% while comfortable indoor environment with no stopping of heating operations in between.
* Comparisons basis: 22RT
the overall product weight decreases up to 19% in comparison to previous model.
This eventually resulted in the maximized use of the saved floor space. Moreover,
reduced product weight of MULTI V 5 makes installation easier with less limitation
on product weight installed on the building’s rooftop.

03 Operational costs management by presetting energy 03 Optimal controlling environment with new Standard III
consumption Remote Controller
Energy management function allows MULTI V 5 to preset monthly energy usage and MULTI V 5’s new wired remote controller offers simple and easy controlling experience
consume what has been previously planned. By analyzing and comparing previous via simplified user interface and 4.3-inch large colored LCD screen. Moreover, it
consumption and planned energy usage for the month, overuse of the HVAC system provides diverse information such as indoor temperature, humidity, cleanliness and
operational costs can be prevented. real-time check on energy consumption.

04 Easy building remodeling with Integral system that offers


both the Heat Pump & Heat Recovery
MULTI V 5 offers HVAC solution with integrated system that offers both the Heat
Pump and the Heat Recovery Systems.
Even if the site has been previously installed with Heat Pump System, user
can easily replace it with Heat Recovery System or Hot Water Solution when
necessary, through simple piping construction which eventually allows more rooms
for future remodeling plans.
Heat Pump System Heat Recovery System

026 027
5
MAIN FEATURES
• ULTIMATE EFFICIENCY
• ULTIMATE PERFORMANCE
• ULTIMATE COMFORT
• ULTIMATE FLEXIBILITY
• ULTIMATE CONTROL
• HEAT RECOVERY

028 029
OUTDOOR UNIT
OUTDOOR UNIT KEY FEATURES

MULTI V 5
Due to improved supercooling circuit and refrigerant controlling technologies, MULTI V 5 allows users to install
world’s best class piping lengths, which results in more flexible installation design.
ULTIMATE EFFICIENCY
Piping length LG’s Ultimate Inverter Compressor
The newly designed bearing of the Ultimate Inverter Compressor allows low-frequency
1,000m
Total piping length operation at 10 Hz from the previously lowest speed at 15 Hz, increasing the ultimate
efficiency and reliability of MULTI V 5.

Vapor Injection Enhanced Bearing with PEEK Material


• Maximize heating capacity via two-stage compression for Increased Durability and Reliability
• Provide powerful heating in low temperature conditions • Applied newly invented scroll system driven by PEEK
110m • Improve energy efficiency and heating performance (Polyetheretherketone) bearing used for aero engine
225m Height between • Can operate longer without oil supply
Longest ODU ~ IDU
piping Extended Compressor Speed from 10 Hz • Increase durability and reliability
length
• Increase part load efficiency at all operation ranges
• Rapid operation response Concentration Motor
40m • Capable of reaching required temperature quickly
• 10% increase of magnetic flux density
Height
between 165 Hz
IDU ~ IDU
HiPOR™
• Minimizing energy loss with direct oil return
10 Hz
15 Hz
Previous Model Smart Oil Management
• Measuring the presence of oil through the oil sensor
150 Hz

World’s First Class, Energy Efficiency World’s First Class, IEER


(ISO Test Condition)
Piping capabilities EER (Cooling) IEER (Cooling) 8.00
Total Piping Length 1,000m

Actual longest piping length (Equivalent) 200m (225m) 13%


4.76 7.08
Longest piping length after 1st branch (conditional application) 40m (90m)

Height between ODU ~ IDU 110m 4.21 13%

Height between IDU ~ IDU 40m

Height between ODU ~ ODU 5m Previous Model Previous Model

* Comparison based on 8RT, C/O model (in same norminal capacity) * Comparison based on 8RT, C/O model
** IEER (Intergrated Energy Efficiency Ratio)

030 031
OUTDOOR UNIT
OUTDOOR UNIT KEY FEATURES

MULTI V 5

ULTIMATE EFFICIENCY
Smart Load Control (SLC) HiPOR™ (High Pressure Oil Return)
Smart Load Control function enables comprehensive understanding of environmental conditions in order to optimize energy HiPORTM technology enables oil to return directly into the compressor, instead of returning through the refrigerant suction pipe
efficiency and maximize indoor comfort level. This technology allows active control of discharge refrigerant temperature which in order to minimize energy losses while maximizing the efficiency of compressor. The previous model compressor that caused
eventually increases the seasonal efficiency up to 18% at standard humidity condition in comparison to the non SLC mode. loss of low pressure refrigerant return to the refrigerant pipe. However MULTI V 5 maximizes reliability and efficiency of the
compressor by reducing high pressure refrigerant loss.

Increased Seasonal Efficiency


Process comparison
Up to 18% 1
Refrigerant
Up to 14% (High humidity) ~ 29% (Low humidity) Compressor

* LG internal test result


3
4
Cooling load
Previous
Cooling Capacity
For low temperature, Adjusting capacity to
meet load
lower load and capacity
are required
Actually External Load
Required
Cooling Non-HiPOR™
Capacity
Internal Load 2
Temperature & humidity Low pressure High pressure
Compressor Oil separator
refrigerant refrigerant Oil
Evaporation temperature 1 2 3 4
Low Refrigerant 5
Humidity Oil
No energy loss
SLC in suction gas 5
Lower load and capacity
need higher evaporation High
temperature Humidity

Standard
(Non SLC) Outdoor
Efficiency comparison
temperature (°C)
Low temperature High temperature
Efficiency
Non-HiPORTM

Efficiency
Low
Humidity

Higher evaporation SLC

temperature results
High
in higher efficiency Humidity
Standard
(Non SLC)

Outdoor
temperature (°C)
Low temperature High temperature
15 20 30 60 90 120 150 (Hz)

* Rating condition (Tc=54.4 °C, Te=7.2 °C)


* Low humidity: Below 50% / Standard: 50~70% / High humidity: 70~100%
* Setting is available in indoor (Standard III Remote Controller)

032 033
OUTDOOR UNIT
OUTDOOR UNIT KEY FEATURES

MULTI V 5

ULTIMATE EFFICIENCY
Vapor Injection Active Refrigerant Control
Vapor Injection uses a two-stage compression effect, which is designed to provide efficient heating in very cold environments. Active Refrigerant Control monitors and adjusts the quantity of circulating refrigerant during each cycle to maximize efficiency
Combined with HiPORTM, this system boosts heating performance and enhances heating temperature range. in real time when it runs cooling and heating operation, as well as the part load operation. This five step control leads to an
improvement in energy efficiency, unlike when fixed amount of refrigerant is provided to the compressor regardless of operation
mode, which limits optimal efficiency for each operation.

Technology mechanism Technology mechanism Amount of refrigerant Receiver


in receiver

High-pressure
Low-pressure

Cooling Heating Part Load

Fixed refrigerant
accumulator

Mid-pressure
(Vapor injection port)

Accumulator Compressor

Performance comparison Efficiency performance

Heating performance
Efficiency

Heating
efficiency
Part load
Non-Vapor Injection efficiency

Cooling
-25 -20 -15 -10 -5 0 7 11 15 efficiency
Outdoor temp.(°C) Active Refrigerant Control
* Improved heating performance by 27% Refrigerant quantity (kg)
* Comparison tested on 10HP model

034 035
OUTDOOR UNIT
OUTDOOR UNIT KEY FEATURES

MULTI V 5

ULTIMATE EFFICIENCY
Smart Oil Management Variable Heat Exchanger Circuit
Compressor reliability and Efficiency are improved with an oil sensor that allows oil balancing and oil return. The value of the Variable Heat Exchanger Circuit intelligently selects the optimal path for both heating and cooling operations. With this
capacitance between the electrodes can measure the presence of oil in real-time. This real-time measurement of oil in the smart path selection technology, an average of 6% increase in the efficiency of both operations has been achieved. The paths
compressor reduces energy loss, providing consistent heating for the indoor environment. With Smart Oil Return, heating number and circuit velocity are adjusted to match temperatures and operation modes in order to maximize efficiency instead
operation time per day has increased up to 12% in comparison to previous model. of compromising efficiency for each operation when the number and direction of paths are fixed independently of temperature
operation mode.

Auto Oil Balancing Technology mechanism

Oil
Oil Level Fixed heat
Sensor exchanger circuit

Smart Oil Return

Cooling Heating

Oil Oil Efficiency performance


Oil Level
Sensor

Efficiency

Operation time comparison

• Non-oil sensor model • MULTI V 5


Heating
Heating performance Heating performance

Oil recovery operation only if necessary

Heating operation time per day up to 12%

Cooling

Number of circuit
Previous Design (Fixed)

Operation time Operation time

036 037
OUTDOOR UNIT
OUTDOOR UNIT KEY FEATURES

MULTI V 5

ULTIMATE PERFORMANCE
Heat Exchanger with Ocean Black Fin for Corrosion Resistance Corrosion Resistance Proven by Certified Tests
LG’s exclusive Ocean Black Fin is applied on the heat exchanger of MULTI V 5 in order to perform even in corrosive LG Corrosion Resistance solution passed ISO accelerated corrosion test conducted by an independent test organization and the
environments. The strong protection from various corrosive external environments such as seaside with high salt result has been certified by prestigious global certification organization, UL (Underwriters Laboratories).
contamination and industrial cities with severe air pollution caused by fumes from factories keeps MULTI V 5 operating without
breakdown. This improvement in durability prolongs the product’s lifespan and lowers both the operational and maintenance
costs.
Certified protection

4-sided heat exchanger

3-sided heat exchanger

Condition of salt spray test


Temperature 35°C

Mist of 5% sodium chloride solution

Condition of gas exposure test * Test Method B Simulation Validated


(Test condition: Salt contaminated condition +
R.H. NO2 SO2 severe industrial/traffic environment(NO2/SO2))
Previous Model
95% 10 x 10-5 5 x 10-6 * Based on 1,500 UL test hours

Enhanced Coating Layers


The black coating with enhanced epoxy resin is applied for strong protection from various corrosive external conditions such as
salt contamination and air pollution including fumes from factories. Moreover, the hydrophilic film keeps water from accumulating
on the heat exchanger’s fin, minimizing moisture buildup and eventually making it even more corrosion resistant.

Hydrophilic film (Water flow)


The Hydrophilic coating minimizes moisture buildup on the fin.

Epoxy resin (Corrosion resistant)


The Black coating provides strong protection from corrosion.

Aluminum fin

038 039
OUTDOOR UNIT
OUTDOOR UNIT KEY FEATURES

MULTI V 5

ULTIMATE PERFORMANCE
Larger Capacity ODU with Biomimetics Technology Fan Increased Air Flow Rate with Bigger Shroud
The moire pattern from external texture of clam shells has been applied on fans to create the range difference which results in In addition to the biomimetics technology-based fans, extended
reduction of noise level. At the same time, unlike the fans installed in previous products that generate separation of flow due to shroud of MULTI V 5 allows more high static pressure and helps
absence of tubercles, the bumpy back design inspired by the bumps on the humpback whale’s flipper is applied as the tubercles fans to blow higher air volume for efficient operation. With
on the back side of the fans, increasing wind power by reducing flacking. wider air guide, discharged air current is stabilized and noise
level is reduced.

Humpback Clam Shell


Whale Desigan Pattern

Enhanced Performance with Newly Developed Fan


Based on the biomimetics technology, the fans of MULTI V 5 increased air flow rate by 10% in comparison to previous model and
reduced its power consumption up to 20%. This eventually results in maximized performance with large capacity.

Air flow rate Power consumption

m3/min W
Flow difference comparison caused by tubercles
10% 20%
• Previous model • MULTI V 5
Without tubercles With tubercles 320 1,500

290

1,200

Previous Model

Previous Model Previous Model

* Biomimetic refers to human-made processes, substances, devices, or systems that imitate nature. * Comparison based on 16RT model * Comparison based on air volume of 290m3/min

040 041
OUTDOOR UNIT
OUTDOOR UNIT KEY FEATURES

MULTI V 5

ULTIMATE PERFORMANCE
Enhanced Bearing with PEEK Material Reliable Performance in Extreme Environment
Motivated by the lubricative material of PEEK(Polyetheretherketone) bearing used for aero engines, the newly invented scroll With enhanced inverter compressor and control technology coming from improved supercooling technology installation, vapor
system with refined shape increases durability and reliability of compressor. It also helps MULTI V 5 to operate longer without oil injection and Ocean Black Fin, MULTI V 5 extended range of cooling and heating operations. For heating, it can operate at as low
supply in comparison to the previous models. as -25°C to perform properly even at very cold environment. Moreover, MULTI V 5’s cycle technology with enhanced durability
enables optimal cooling performance at high temperature that increases up to 48°C. It is improved perfectly to fully function at
Technology mechanism comparison extreme conditions such as performing cooling operation at -15°C, making the product adequate for uses in specialized venues
like technical rooms.

1 Wider operational range for each performance


1
3 3 Outdoor air temp.(°C WB)

3 3
18°C
2
2 15°C

Previous Model

Material : FR160 Material : PEEK (Polyetheretherketone)


Structure : Inner Bearing Structure : New Outer Bearing
Supporter Supporter : High speed operation with reduction -20°C
2 1 1 2
of bearing load and vibration
-25°C
Operating time without oil supply 10°C 15°C 20°C 27°C
Up to 15% Indoor air temp.(°C DB)
< Heating >
Noise Level (Max. Sound Pressure)
Down to 3dB * Under the condition of -25°C for outdoor temperature and 20°C for indoor temperature

Outdoor air temp.(°C DB)

Oilless operation hours comparison


48°C

Friction coefficient (Defect) 43°C

Aluminum Previous Model


Previous Model

-10°C

-15°C

* LG Internal test result 10°C 14°C 25°C 27°C


* Test condition : Bearing oil blocking test (Oil blocking at 60 Hz) Indoor air temp.(°C WB)
Time < Cooling >

042 043
OUTDOOR UNIT
OUTDOOR UNIT KEY FEATURES

MULTI V 5

ULTIMATE COMFORT
Delayed Defrost via Humidity Sensor of Dual Sensing Control Comfort Cooling
By controlling the evaporation temperature considering the humidity, heating operation time is improved.
Heating performance
Without stopping in between operations, this function allows MULTI V 5 to
maintain operation at mild cooling mode around the set temperature by sensing
On On
both temperature and humidity with Dual Sensing Control. By preventing both cold
draft and repeated turn on/offs previously required to match the set temperature,
Heating supply
users can experience more comfortable indoor environment.

Time
Non-humidity sensor Effect of delayed defrost
Cooling operation comparison
Partial Defrost
Previous Model
Unlike the previous model that stopped heating operation for one-time defrost, MULTI V 5 partially defrosts the heat exchanger by dividing it to lower and
upper parts in order to provide consistent heating for the indoor environment and improve heating capacity.

Heating performance

On On
Continuous Heating supply
2 Heating
Effect of
1 1 Lower heat exchanger defrost partial defrost
2 Upper heat exchanger defrost Time
Non-humidity sensor

Cooling Mode Fan Mode Cooling Mode


Smart Oil Management
* Indoor unit set up available with Standard III Remote Controller
Oil sensor of the Ultimate Inverter (UI) Compressor enables smart oil management to provide enhanced heating operation without periodic oil recovery
operation.

Heating performance Previous Model


No heating stop for 200 days Preventing cold draft & repeated turn on/offs
Indoor temp. Improved indoor comfort

Not
Heating Heating Heating cool
Oil Level zone
Sensor
Non heating Non heating
Time
Eliminated Unnecessary Oil Return via Oil Sensor Non-humidity sensor Comfort
zone
* LG internal test result Setting temp.

Too
Continuous Heating cool
zone
With Dual Sensing Control, partial defrost and smart oil management via oil sensor,
continuous heating technology has been improved. Time

11% Increase in Heating Operation Time Per Day


7% Reduction in Power Input
*Applied only on high efficiency model

044 045
OUTDOOR UNIT
OUTDOOR UNIT KEY FEATURES

MULTI V 5

ULTIMATE COMFORT ULTIMATE FLEXIBILITY


Low-Noise Operation MULTI V 5 Outdoor Unit Line Up (High Efficiency)
(RT) 6 8 10 20 30 42
Unlike the previous model which enables Low-Noise Operation only during night after judgment time, the Low-Noise
Operation of MULTI V 5 can function regardless of the time at the noise sensitive areas.
6RT
Small Size Outdoor Unit

Operation hours comparison


Previous Model 8 ~ 20RT
Providing up to 20RT for Single Unit
Outdoor setting only

22 ~ 34RT
Capacity

Load

36 ~ 42RT
Sound level Off
Providing up to 42RT by combination
(Judgment time) Low-noise operation time

MULTI V 5 Outdoor Unit Line Up (Cooling Only)


On (RT) 8 10 20 30 40 50 60 70 80

6:00 12:00 13:00 18:00 21:00 0:00 6:00


Highest Start End
outdoor temp. 8 ~ 10RT
Providing up to 10RT for Small Size Outdoor Unit

Indoor setting available


12 ~ 22RT
Providing up to 22RT for Single Unit

Capacity

Load 24 ~ 40RT
Scheduled setting available

Sound level

Low-noise Low-noise 42 ~ 60RT


operation operation
On Off On

6:00 12:00 18:00 6:00 * Indoor unit set up available with Standard III Remote
Start End Start End Controller
62 ~ 80RT
Providing up to 80RT by combination

046 047
OUTDOOR UNIT
OUTDOOR UNIT KEY FEATURES

MULTI V 5

ULTIMATE FLEXIBILITY
Flexible Installation Space with Large Capacity Outdoor Units
Large capacity outdoor units of MULTI V 5 minimizes installation space that spares valuable floor space and significantly decreases
total installed weights. This allows users the flexible design potential and better use of the saved space.

Comparison on installation space Installation space area and product weight comparison

15%
23% Reduction
Reduction

Previous Model 12.25m 3


3,640kg

9.42m 3
3,100kg

Previous Model Previous Model

Installation space Product weight

* Comparison basis: 2 Rows of outdoor units 260HP (26HP X 10sets) installation case

*South America : Max 26HP, Central America High Effiency : Max 20RT, Central America Cooling only : Max 22RT

048 049
OUTDOOR UNIT
OUTDOOR UNIT KEY FEATURES

MULTI V 5

ULTIMATE CONTROL
Energy Management AC Manager 5 with User Friendly Interface
Energy Management allows MULTI V 5 to analyze previous data in order to forecast energy usage beforehand and prevent As an advanced central controller, AC Manager 5 offers flexible interface for each user by assessing the
from exceeding the monthly energy consumption plan by systematically controlling the cooling volume. With energy consulting device screen and automatically customizing the layout to provide the most optimized interface. Moreover, it
program that provides automatic operation options for 7 levels of energy management such as compressor capacity management provides effective system air conditioner management through user friendly interface and various functions.
and indoor unit operation level control, users can monitor energy usage anytime and efficiently manage their energy bills.

Energy consumption (kWh)

Saving energy consumption

Target

Predicted usage

2 Management
based on
real-time usage
Actual usage

1 Management based on monthly


predicted usage

5 10 15 20 25 30Day

Management setting example


When predicted usage is 120% When the real-time usage is 90%
* Energy Management allows maximum 7 steps (Input format is percent for predicted and real-time usage) [ PC ] [ Tablet ] [ Mobile ]
* Central control kit such as ACP IV or AC Smart IV and PDI are required for energy management function
11:00 am 2:00 pm 5:00 pm
Monitoring room Checking each room Monitoring at any time, anywhere

Control methods Various functions of AC Manager 5

Saving
30%

Schedule function Advanced energy monitoring Operational trend


Compressor capacity management Operation rate control of indoor unit Indoor unit operation management

050 051
OUTDOOR UNIT
OUTDOOR UNIT KEY FEATURES

MULTI V 5

ULTIMATE CONTROL
Expandability & Programmability Smart Individual Controller (with Standard III Remote Controller)
The expandable control system can be interlocked with sensors and facilities of building, as well as air conditioners. New Standard III Remote Controller of MULTI V 5 offers 4.3-inch large LCD screen with neat and premium design. This luxurious
It makes building management smart by setting up logic optimized for the site. design well-matches interior design through large colored LCD screen with curved display and simple button layout which makes
it easier to control. With diverse information offered such as temperature, humidity and cleanliness information, users can check
on currently consumed power in real-time and electricity consumption data(weekly/monthly/annually) to predict and plan power
A/C (Air Conditioner)
Occupancy sensor / Alarm / Key-tag consumption usage. Moreover, simple and geometrically neat design of user interface makes data comprehension visually easy.
DI (Digital Input) With circular visual theme, information are labelled in different-sized circles based on their priorities.

Intuitive &
LG AHU Fan / Lighting / Switch Emotional
DI (Digital Input) Interface
Interlocking
system

Pump / Valve Temperature / Humidity / CO2 Sensor


AO (Analog Output) AI (Analog Input)

Luxurious Design

System Flexibility Energy


It can be linked with 3rd party BMS via Gateway and provide flexible control system for each site via Dry Contact. Management

Interlock with 3rd LG BMS Open Protocol


3rd party BMS
party BMS HVAC [BACnet , LonWorks , Modbus]

Dry Contact optimized


for variable scenario
Hotel Room With 3rd Party Thermostat With Home Automation

Modbus
RTU

* Central control kit such as ACP IV or AC Smart IV and PDI are required for energy management function

052 053
OUTDOOR UNIT
OUTDOOR UNIT KEY FEATURES

MULTI V 5

ULTIMATE CONTROL HEAT RECOVERY


Simple Test Run via LGMV Applicable for Various Building Types with
In order to bring out performance to the 100% level, proper product test run is necessary. For previous product, professional Heat Pump & Heat Recovery Systems
engineer who is well-aware of more than 40 different functional settings and 200+ error codes had to check main parts in order
LG MULTI V 5 satisfies users’ various needs with just one platform. Heat Pump System works for the sites where either cooling or
to make sure that the test run had succeeded. With Mobile LGMV of MULTI V 5, however, fast and accurate auto test run can be
heating operation is needed, while Heat Recovery System fits perfectly to the sites wherein both the cooling and heating
executed and the professional installer running the test can receive test results via email, which shortens installation hours and
operations are simultaneously needed or locations installed with Hot Water Solution to provide hot water and heating via
increases overall efficiency in installation processes.
radiator. By providing suitable solutions that cater to any building types and their requirements, MULTI V 5 offers the best
HVAC system.
Test run comparison

Manual
Simple Piping System Changes
MULTI V 5 allows the building previously installed with Heat Pump System to switch to the Heat Recovery System for changing purpose of the
building or remodeling reasons via simple piping construction.
Automatic

Previous Model

2 pipes 3 pipes

Heat Recovery Unit

LGMV smartphone application setting pages


Type
Changeover

Heat Pump Slave 1


Outdoor unit
Master
Outdoor unit Heat Recovery Slave 1
Outdoor unit
Master
Outdoor unit
System System
High Pressure Gas
Pipe

Liquid Liquid
Pipe Pipe Gas Pipe Indoor unit Liquid Liquid Indoor unit
Pipe Pipe
Gas Pipe
Wi–Fi MV Module 37% Reduction in Installation Hours
Low Pressure HR unit
Gas Pipe
* This feature is provided only to qualified professional installers
**LGMV Application is available for Android and iOS (iphone/ipad)
*** Mobile LGMV is necessary to get wireless standard each country for using.
Please check whether it is available or not in your country

054 055
OUTDOOR UNIT
OUTDOOR UNIT KEY FEATURES

MULTI V 5

HEAT RECOVERY
Energy Saving with Simultaneous Operation Wide Operation Range
MULTI V 5 Heat Recovery system with HR Unit can perform both cooling and heating operations simultaneously. For continuous Both the low and high temperature operation ranges are expanded through condenser with various control. For heating mode,
operation, it minimizes in order to switch mode while it increases efficiency with simultaneous operation. Moreover, it allows the the outdoor temperature can go from as low as -25°C to 24°C, and from -15°C to as high as 48°C for cooling mode. As for the
COP to reach up to 8.5 under circumstances of 40% cooling and 60% heating operations, which results in the decreased energy synchronous mode, it can run from -10°C to 16°C.
consumption up to 30%.

Technology mechanism Operation range Indoor temp. (°C)*

27

1 3 2

Indoor Unit

Heating mode 14
HR Unit Heat
absorption

Indoor cooling
Cooling mode
10
Heat Synchronous mode
Heat Recovery emission -25 -15 -10 16 18 48
Outdoor temp. (°C)**
Hot water
Outdoor Temperature
1 Heating mode : - 25°C WB ~ 18°C WB 2 Cooling mode : - 15°C DB ~ 48°C 3 Synchronous mode : -10°C WB ~ 16°C WB
Hydro Kit * Heating (°C DB), Cooling (°C WB), Synchronous (°C DB) ** Heating (°C WB), Cooling (°C DB), Synchronous (°C WB)

COP with simultaneous operation


COP Flexible Connection of Heat Recovery Unit
LG MULTI V 5 Heat Recovery Unit allows flexible connection both in series and in a row. With the zone control function, up to
8 indoor units can be connected to a branch while the maximum of 32 indoor units can be connected to a HR unit, saving the
Cooling based 9.38 Heating based
operation (Conversion) operation installation cost by flexible connection.
9

8 Zoning control
7

6
HR Unit
5
4.22 4.33
(Conversion)

Operation rate (%)


0 20 40 60 80 100

*AHRI Certified test condition


*ARUM096DTE5

056 057
OUTDOOR UNIT
OUTDOOR UNIT SPECIFICATION

MULTI V 5 HIGH EFFICIENCY_220V


ARUM072BTE5 / ARUM096BTE5 / ARUM121BTE5 / ARUM144BTE5 / ARUM168BTE5 ARUM192BTE5 / ARUM216BTE5 / ARUM241BTE5 / ARUM264BTE5 / ARUM288BTE5

RT 6.0 8.0 10.0 12.0 14.0 RT 16.0 18.0 20.0 22.0 24.0
Combination Unit ARUM072BTE5 ARUM096BTE5 ARUM121BTE5 ARUM144BTE5 ARUM168BTE5 Combination Unit ARUM192BTE5 ARUM216BTE5 ARUM241BTE5ARUM264BTE5 ARUM288BTE5
Model Name Model Name
Independent Unit ARUM072BTE5 ARUM096BTE5 ARUM121BTE5 ARUM144BTE5 ARUM168BTE5 ARUM168BTE5 ARUM192BTE5
Independent Unit ARUM192BTE5 ARUM216BTE5 ARUM241BTE5
Btu/h 72,000 96,000 120,000 144,000 168,000 ARUM096BTE5 ARUM096BTE5
Cooling Btu/h 192,000 216,000 240,000 264,000 288,000
kW 21.1 28.1 35.2 42.2 49.2 Cooling
Norminal kW 56.3 63.3 70.3 77.4 84.4
Btu/h 81,000 108,000 135,000 162,000 189,000 Norminal
Heating Btu/h 216,000 243,000 243,000 297,000 324,000
kW 23.7 31.7 39.6 47.5 55.4 Heating
Capacity kW 63.3 71.2 71.2 87.0 95.0
Btu/h 69,000 92,000 114,000 138,000 160,000 Capacity
Cooling Btu/h 184,000 206,000 222,000 252,000 276,000
kW 20.2 27.0 33.4 40.4 46.9 Cooling
Rated kW 53.9 60.4 65.1 73.9 80.9
Btu/h 77,000 103,000 129,000 154,000 180,000 Rated
Heating Btu/h 206,000 230,000 230,000 283,000 309,000
kW 22.6 30.2 37.8 45.1 52.8 Heating
Cooling kW 4.28 5.33 7.72 9.30 12.23 kW 60.4 67.4 67.4 82.9 90.6
Norminal Cooling kW 13.61 15.37 16.80 17.56 18.94
Heating kW 5.39 6.74 9.20 10.54 13.98 Norminal
Input Heating kW 15.46 17.75 17.75 20.72 22.20
Cooling (Nonducted / Ducted) kW 5.15 / 5.31 6.39 / 6.82 8.7 / 9.12 11.04 / 11.41 13.68 / 14.41 Input
Rated Cooling (Nonducted / Ducted) kW 14.84 / 16.73 18.39 / 19.25 22 / 21.35 20.06 / 21.23 21.23 / 23.55
Heating (Nonducted / Ducted) kW 6.49 / 5.89 8.25 / 6.97 10.93 / 9.523 12.82 / 11.75 16.49 / 14.78 Rated
Norminal Cooling 16.82 18.01 15.54 15.48 13.74 Heating (Nonducted / Ducted) kW 18.3 / 16.1 21.07 / 19.1 21.07 / 20.12 24.74 / 21.75 26.55 / 23.07
EER Norminal Cooling 14.11 14.05 14.29 15.03 15.21
Rated Cooling (Nonducted / Ducted) 13.4 / 13 14.40 / 13.5 13.1 / 12.5 12.5 / 12.1 11.7 / 11.1 EER
IEER Rated Cooling (Nonducted / Ducted) 28.4 / 23.6 33 / 25.1 29.6 / 24.6 28.6 / 23 25.4 / 21.9 Rated Cooling (Nonducted / Ducted) 12.4 / 11 11.2 / 10.7 10.13 / 10.4 12.56 / 11.87 13 / 11.72
Norminal Heating 4.40 4.70 4.30 4.50 3.96 IEER Rated Cooling (Nonducted / Ducted) 25.9 / 23 24.8 / 22.4 23.5 / 22.7 22 / 21.5 22 / 21
COP Norminal Heating 4.09 4.01 4.01 4.20 4.28
Rated Heating (Nonducted / Ducted) 3.83 / 3.48 4.33 / 3.66 3.97 / 3.46 3.84 / 3.52 3.57 / 3.2 COP
Power Factor Rated - 0.93 0.93 0.93 0.93 0.93 Rated Heating (Nonducted / Ducted) 3.75 / 3.3 3.53 / 3.2 3.35 / 3.2 3.81 / 3.35 3.93 / 3.41
Casing Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Power Factor Rated - 0.93 0.93 0.93 0.93 0.93
Heat Exchanger Ocean Black Fin Ocean Black Fin Ocean Black Fin Ocean Black Fin Ocean Black Fin Casing Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray
Compressor Motor Output × Number W × No. 4,200 × 1 5,300 × 1 5,300 × 1 4,200 × 1 + 4,200 × 1 4,200 × 1 + 4,200 × 1 Heat Exchanger Ocean Black Fin Ocean Black Fin Ocean Black Fin Ocean Black Fin Ocean Black Fin
(5,300 × 1)
Type Propeller fan Propeller fan Propeller fan Propeller fan Propeller fan Compressor Motor Output × Number W × No. 5,300 × 2 5,300 × 2 5,300 × 2 5,300 × 3
+ (4,200 × 2)
Motor Output × Number W 1,200 × 1 900 × 2 900 × 2 900 × 2 900 × 2 Type Propeller fan Propeller fan Propeller fan Propeller fan Propeller fan
Fan m /min
3
240 × 1 320 × 1 320 × 1 320 × 1 320 × 1 Motor Output × Number W 900 × 2 900 × 2 900 × 2 900 × 2 900 × 4
Air Flow Rate (High)
ft3/min 8,476 × 1 1,1301 × 1 1,1301 × 1 1,1301 × 1 1,1301 × 1 Fan m3/min 320 × 1 320 × 1 320 × 1 320 × 1 320 × 2
Drive DC INVERTER DC INVERTER DC INVERTER DC INVERTER DC INVERTER Air Flow Rate (High)
ft /min
3
1,1301 × 1 1,1301 × 1 1,1301 × 1 11,301 × 2 11,301 × 2
Liquid Pipe mm (inch) 9.52(3/8) 9.52(3/8) 12.7(1/2) 12.7(1/2) 15.88(5/8) Drive DC INVERTER DC INVERTER DC INVERTER DC INVERTER DC INVERTER
Pipe Connections For Low Pressure Gas Pipe mm (inch) 19.05(3/4) 22.2(7/8) 28.58(1-1/8) 28.58(1-1/8) 28.58(1-1/8) Liquid Pipe mm (inch) 15.88(5/8) 15.88(5/8) 15.88(5/8) 19.05(3/4) 19.05(3/4)
Heat Pump
High Pressure Gas Pipe mm (inch) 15.88(5/8) 19.05(3/4) 19.05(3/4) 22.2(7/8) 22.2(7/8) Pipe Connections For Low Pressure Gas Pipe
Heat Pump mm (inch) 28.58(1-1/8) 28.58(1-1/8) 34.9(1-3/8) 34.9(1-3/8) 34.9(1-3/8)
Pipe Connections For Liquid Pipe mm (inch) 9.52(3/8) 9.52(3/8) 12.7(1/2) 12.7(1/2) 15.88(5/8) High Pressure Gas Pipe mm (inch) 28.58(1-1/8) 28.58(1-1/8) 28.58(1-1/8) 28.58(1-1/8) 28.58(1-1/8)
Heat Pump Gas Pipe mm (inch) 19.05(3/4) 22.2(7/8) 28.58(1-1/8) 28.58(1-1/8) 28.58(1-1/8)
Pipe Connections For Liquid Pipe mm (inch) 15.88(5/8) 15.88(5/8) 15.88(5/8) 19.05(3/4) 19.05(3/4)
(930 × 1,690 × 760) (1,240 × 1,690 × (1,240 × 1,690 × (1,240 × 1,690 × (1,240 × 1,690 × Heat Pump
mm Gas Pipe mm (inch) 28.58(1-1/8) 28.58(1-1/8) 34.9(1-3/8) 34.9(1-3/8) 34.9(1-3/8)
×1 760) × 1 760) × 1 760) × 1 760) × 1
Dimensions (W × H × D) (1,240 × 1,690 × (1,240 × 1,690 × (1,240 × 1,690 × (1,240 ×1,690 × (1,240 ×1,690 ×
(36-5/8 × 66-17/32 × (48-13/16 × 66-17/32 (48-13/16 × 66-17/32 (48-13/16 × 66-17/32 (48-13/16 × 66-17/32 mm
inch 760) × 1 760) × 1 760) × 1 760) × 2 760) × 2
29-29/32) × 1 × 29-29/32) × 1 × 29-29/32) × 1 × 29-29/32) × 1 × 29-29/32) × 1 Dimensions (W × H × D)
kg 195 × 1 230 × 1 230 × 1 290 × 1 290 × 1 (48-13/16 × 66-17/32 (48-13/16 × 66-17/32 (48-13/16 × 66-17/32 (48-13/16 × 66-17/32 (48-13/16 × 66-17/32
inch
Net Weight × 29-29/32) × 1 × 29-29/32) × 1 × 29-29/32) × 1 × 29-29/32) × 2 × 29-29/32) × 2
lbs 430 × 1 507 × 1 507 × 1 639 × 1 639 × 1
kg 299 × 1 302 × 1 302 × 1 (230 × 1) + (290 × 1) (230 × 1) + (299 × 1)
Sound Pressure Level Cooling dB(A) 58.0 58.0 59.0 60.0 61.0 Net Weight
lbs 659 × 1 666 × 1 666 × 1 (507 × 1) + (639 × 1) (507 × 1) + (659 × 1)
Sound Power Level Cooling dB(A) 77.0 78.0 79.0 83.0 85.0
Sound Pressure Level Cooling dB(A) 62.0 64.0 65.0 63.0 63.0
Communication Cable No.× mm2 (VCTF-SB) 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5
Sound Power Level Cooling dB(A) 87.0 88.0 88.0 86.0 87.0
Refrigerant name R410A R410A R410A R410A R410A
Communication Cable No.× mm2 (VCTF-SB) 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5
Precharged Amount in kg 13.0 16.0 20.0 24.0 29.0
Refrigerant name R410A R410A R410A R410A R410A
factory lbs 28.7 35.3 44.1 52.9 63.9
Refrigerant Precharged Amount in kg 32.0 35.0 39.0 45.00 48.00
GWP 2087.5 2087.5 2087.5 2087.5 2087.5 factory lbs 70.5 77.2 86.0 99.2 105.8
TCO2eq 27.1 33.4 41.8 50.1 60.5 Refrigerant GWP 2087.5 2087.5 2087.5 2087.5 2087.5
Electronic Expansion Electronic Expansion Electronic Expansion Electronic Expansion Electronic Expansion
Control TCO2eq 66.8 73.1 81.4 93.9 100.2
Valve Valve Valve Valve Valve
220, 3, 60 220, 3, 60 220, 3, 60 220, 3, 60 220, 3, 60 Electronic Expansion Electronic Expansion Electronic Expansion Electronic Expansion Electronic Expansion
Power Supply Ø , V, Hz Control
220-240, 3, 50 220-240, 3, 50 220-240, 3, 50 220-240, 3, 50 220-240, 3, 50 Valve Valve Valve Valve Valve
220, 3, 60 220, 3, 60 220, 3, 60 220, 3, 60 220, 3, 60
Number of maximum connectable indoor units5) 13 16 20 24 29 Power Supply Ø , V, Hz
220-240, 3, 50 220-240, 3, 50 220-240, 3, 50 220-240, 3, 50 220-240, 3, 50
Number of maximum connectable indoor units5) 32 35 39 42 45

Note : Note :
1. Nominal capacity applied with non-ducted indoor units, and is rated 0 m. above sea level with 7.5 m. of refrigerant line per indoor unit and a 0 m. level difference between outdoor and indoor units. 1. Nominal capacity applied with non-ducted indoor units, and is rated 0 m. above sea level with 7.5 m. of refrigerant line per indoor unit and a 0 m. level difference between outdoor and indoor units.
All capacities are net with a Combination Ratio between 95–105%. Nominal cooling capacity rating obtained with air entering the indoor unit at 80°F (27°C) dry bulb (DB) and 67°F (19°C) wet bulb All capacities are net with a Combination Ratio between 95–105%. Nominal cooling capacity rating obtained with air entering the indoor unit at 80°F (27°C) dry bulb (DB) and 67°F (19°C) wet bulb
(WB) and outdoor ambient conditions of 95°F (35°C) dry bulb (DB) and 75°F (24°C) wet bulb (WB). Nominal heating capacity rating obtained with air entering the indoor unit at 70°F (21°C) dry bulb (WB) and outdoor ambient conditions of 95°F (35°C) dry bulb (DB) and 75°F (24°C) wet bulb (WB). Nominal heating capacity rating obtained with air entering the indoor unit at 70°F (21°C) dry bulb
(DB) and 59°F (15°C) wet bulb (WB) and outdoor ambient conditions of 47°F (8°C) dry bulb (DB) and 43°F (6°C) wet bulb (WB). (DB) and 59°F (15°C) wet bulb (WB) and outdoor ambient conditions of 47°F (8°C) dry bulb (DB) and 43°F (6°C) wet bulb (WB).
2. Rated capacity is certified under AHRI Standard 1230. For AHRI ratings, refer to the AHRI website http://www.ahridirectory.org. 2. Rated capacity is certified under AHRI Standard 1230. For AHRI ratings, refer to the AHRI website http://www.ahridirectory.org.
3. The System Combination Ratio must be between 50–130%. 3. The System Combination Ratio must be between 50–130%.
4. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745. 4. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
5. Communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded or unshielded, and must comply with applicable local and national codes. 5. Communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded or unshielded, and must comply with applicable local and national codes.
If shielded, ensure the communication cable is properly grounded to chassis at the master ODU only. Do not ground the ODU-IDU (or HRU) communication cable at any other point. If shielded, ensure the communication cable is properly grounded to chassis at the master ODU only. Do not ground the ODU-IDU (or HRU) communication cable at any other point.
6. Power wiring is field provided, solid or stranded, and must comply with the applicable local and national codes.. 6. Power wiring is field provided, solid or stranded, and must comply with the applicable local and national codes..
7. LG requires that LATS software be used on all projects to ensure correct line sizing. Designer must verify the shop drawing design against the as built design using LATS. 7. LG requires that LATS software be used on all projects to ensure correct line sizing. Designer must verify the shop drawing design against the as built design using LATS.
Contractor must also use LG manufactured Y-Branch and Header Kits only. Contractor must also use LG manufactured Y-Branch and Header Kits only.

058 059
OUTDOOR UNIT
OUTDOOR UNIT SPECIFICATION

MULTI V 5 HIGH EFFICIENCY_220V


ARUM312BTE5 / ARUM336BTE5 / ARUM360BTE5 / ARUM384BTE5 / ARUM408BTE5 ARUM432BTE5 / ARUM456BTE5 / ARUM480BTE5 / ARUM504BTE5

RT 26.0 28.0 30.0 32.0 34.0 RT 36.0 38.0 40.0 42.0


Combination Unit ARUM312BTE5 ARUM336BTE5 ARUM360BTE5 ARUM384BTE5 ARUM408BTE5 Combination Unit ARUM432BTE5 ARUM456BTE5 ARUM480BTE5 ARUM504BTE5
Model Name ARUM216BTE5 ARUM216BTE5 ARUM216BTE5 ARUM216BTE5 ARUM216BTE5 ARUM192BTE5 ARUM216BTE5 ARUM216BTE5 ARUM216BTE5
Independent Unit Model Name
ARUM096BTE5 ARUM121BTE5 ARUM144BTE5 ARUM168BTE5 ARUM192BTE5 Independent Unit ARUM121BTE5 ARUM121BTE5 ARUM144BTE5 ARUM168BTE5
Btu/h 312,000 336,000 360,000 384,000 408,000 ARUM121BTE5 ARUM121BTE5 ARUM121BTE5 ARUM121BTE5
Cooling Btu/h 432,000 456,000 480,000 504,000
kW 91.4 98.5 105.5 112.5 119.6 Cooling
Norminal kW 126.6 133.6 140.7 147.7
Btu/h 351,000 378,000 405,000 432,000 459,000 Norminal
Heating Btu/h 486,000 513,000 540,000 567,000
kW 102.9 110.8 118.7 126.6 134.5 Heating
Capacity kW 142.4 150.4 158.3 166.2
Btu/h 298,000 320,000 344,000 366,000 390,000 Capacity
Cooling Btu/h 412,000 434,000 458,000 480,000
kW 87.3 93.8 100.8 107.3 114.3 Cooling
Rated kW 120.8 127.2 134.2 140.7
Btu/h 333,000 359,000 384,000 410,000 436,000 Rated
Heating Btu/h 464,000 488,000 513,000 539,000
kW 97.6 105.2 112.5 120.2 127.8 Heating
Cooling kW 20.70 23.09 24.67 27.60 28.98 kW 136.0 143.0 150.4 158.0
Norminal Cooling kW 29.05 30.81 32.39 35.32
Heating kW 24.49 26.95 28.29 31.73 33.21 Norminal
Input Heating kW 33.86 36.15 37.49 40.93
Cooling (Nonducted / Ducted) kW 24.78 / 26.07 27.1 / 28.37 29.43 / 30.66 32.07 / 33.66 33.23 / 35.98 Input
Rated
Heating (Nonducted / Ducted) kW 29.32 / 26.07 32 / 28.62 33.89 / 30.85 37.56 / 33.88 39.37 / 35.2 Cooling (Nonducted / Ducted) kW 32.24 / 34.97 35.8 / 37.49 38.14 / 37.78 40.77 / 42.78
Rated
Norminal Cooling 15.07 14.55 14.59 13.91 14.08 Heating (Nonducted / Ducted) kW 40.16 / 35.15 42.93 / 38.15 44.82 / 40.37 48.49 / 43.4
EER Norminal Cooling 14.87 14.80 14.82 14.27
Rated Cooling (Nonducted / Ducted) 12.02 / 11.43 11.81 / 11.28 11.69 / 11.22 11.41 / 10.87 11.74 / 10.84 EER
IEER Rated Cooling (Nonducted / Ducted) 22 / 21 20.5 / 20.5 20 / 19.5 19 / 19.3 18.8 / 19 Rated Cooling (Nonducted / Ducted) 12.78 / 11.78 12.12 / 11.58 12.01 / 11.51 11.77 / 11.22
Norminal Heating 4.20 4.11 4.20 3.99 4.05 IEER Rated Cooling (Nonducted / Ducted) 19.8 / 20 19.2 / 18.5 19 / 18 18.6 / 17.5
COP Norminal Heating 4.21 4.16 4.22 4.06
Rated Heating (Nonducted / Ducted) 3.74 / 3.33 3.68 / 3.29 3.65 / 3.32 3.55 / 3.2 3.63 / 3.25 COP
Power Factor Rated - 0.93 0.93 0.93 0.93 0.93 Rated Heating (Nonducted / Ducted) 3.87 / 3.36 3.75 / 3.33 3.72 / 3.36 3.64 / 3.26
Casing Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Power Factor Rated - 0.93 0.93 0.93 0.93
Heat Exchanger Ocean Black Fin Ocean Black Fin Ocean Black Fin Ocean Black Fin Ocean Black Fin Casing Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray
(5,300 × 2) (5,300 × 2) Heat Exchanger Ocean Black Fin Ocean Black Fin Ocean Black Fin Ocean Black Fin
Compressor Motor Output × Number W × No. 5,300 × 3 5,300 × 3 5,300 × 4
+ (4,200 × 2) + (4,200 × 2) Compressor Motor Output × Number W × No. 5,300 × 4 5,300 × 4 (5,300 × 3) + (4,200 × 2) (5,300 × 3) + (4,200 × 2)
Type Propeller fan Propeller fan Propeller fan Propeller fan Propeller fan Type Propeller fan Propeller fan Propeller fan Propeller fan
Motor Output × Number W 900 × 4 900 × 4 900 × 4 900 × 4 900 × 4 Motor Output × Number W 900 × 6 900 × 6 900 × 6 900 × 6
Fan m3/min 320 × 2 320 × 2 320 × 2 320 × 2 320 × 2 Fan m3/min 320 × 3 320 × 3 320 × 3 320 × 3
Air Flow Rate (High) Air Flow Rate (High)
ft /min
3
11,301 × 2 11,301 × 2 11,301 × 2 11,301 × 2 11,301 × 2 ft3/min 11,301 × 3 11,301 × 3 11,301 × 3 11,301 × 3
Drive DC INVERTER DC INVERTER DC INVERTER DC INVERTER DC INVERTER Drive DC INVERTER DC INVERTER DC INVERTER DC INVERTER
Liquid Pipe mm (inch) 19.05(3/4) 19.05(3/4) 19.05(3/4) 19.05(3/4) 19.05(3/4) Liquid Pipe mm (inch) 19.05(3/4) 19.05(3/4) 19.05(3/4) 19.05(3/4)
Pipe Connections For Low Pressure Gas Pipe Pipe Connections For Low Pressure Gas Pipe
Heat Pump mm (inch) 34.9(1-3/8) 34.9(1-3/8) 41.3(1-5/8) 41.3(1-5/8) 41.3(1-5/8) mm (inch) 41.3(1-5/8) 41.3(1-5/8) 41.3(1-5/8) 41.3(1-5/8)
Heat Pump
High Pressure Gas Pipe mm (inch) 28.58(1-1/8) 28.58(1-1/8) 34.9(1-3/8) 34.9(1-3/8) 34.9(1-3/8) High Pressure Gas Pipe mm (inch) 34.9(1-3/8) 34.9(1-3/8) 34.9(1-3/8) 34.9(1-3/8)
Pipe Connections For Liquid Pipe mm (inch) 19.05(3/4) 19.05(3/4) 19.05(3/4) 19.05(3/4) 19.05(3/4) Pipe Connections For Liquid Pipe mm (inch) 19.05(3/4) 19.05(3/4) 19.05(3/4) 19.05(3/4)
Heat Pump Gas Pipe mm (inch) 34.9(1-3/8) 34.9(1-3/8) 41.3(1-5/8) 41.3(1-5/8) 41.3(1-5/8) Heat Pump Gas Pipe mm (inch) 41.3(1-5/8) 41.3(1-5/8) 41.3(1-5/8) 41.3(1-5/8)
(1,240 ×1,690 × (1,240 ×1,690 × (1,240 ×1,690 × (1,240 ×1,690 × (1,240 ×1,690 × mm (1,240 ×1,690 × 760) × 3 (1,240 ×1,690 × 760) × 3 (1,240 ×1,690 × 760) × 3 (1,240 ×1,690 × 760) × 3
mm
760) × 2 760) × 2 760) × 2 760) × 2 760) × 2 Dimensions (W × H × D) (48-13/16 × 66-17/32 × 29- (48-13/16 × 66-17/32 × 29- (48-13/16 × 66-17/32 × 29- (48-13/16 × 66-17/32 × 29-
Dimensions (W × H × D) inch
(48-13/16 × 66-17/32 (48-13/16 × 66-17/32 (48-13/16 × 66-17/32 (48-13/16 × 66-17/32 (48-13/16 × 66-17/32 29/32) × 3 29/32) × 3 29/32) × 3 29/32) × 3
inch
× 29-29/32) × 2 × 29-29/32) × 2 × 29-29/32) × 2 × 29-29/32) × 2 × 29-29/32) × 2 (230 × 1) + (290 × 1) (230 × 1) + (290 × 1)
kg (230 × 1) + (302 × 1) (230 × 1) + (302 × 1) (290 × 1) + (302 × 1) (290 × 1) + (302 × 1) (299 × 1) + (302 × 1) kg (230 × 2) + (299 × 1) (230 × 2) + (302 × 1)
Net Weight + (302 × 1) + (302 × 1)
lbs (507 × 1) + (666 × 1) (507 × 1) + (666 × 1) (639 × 1) + (666 × 1) (639 × 1) + (666 × 1) (659 × 1) + (666 × 1) Net Weight
(507 × 1) + (639 × 1) (507 × 1) + (639 × 1)
lbs (507 × 2) + (659 × 1) (507 × 2) + (666 × 1)
Sound Pressure Level Cooling dB(A) 65.0 65.0 66.0 66.0 66.0 + (666 × 1) + (666 × 1)
Sound Power Level Cooling dB(A) 88.0 88.0 89.0 89.0 90.0 Sound Pressure Level Cooling dB(A) 66.0 66.0 67.0 67.0
Communication Cable No.× mm2 (VCTF-SB) 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5 Sound Power Level Cooling dB(A) 89.0 89.0 89.0 90.0
Refrigerant name R410A R410A R410A R410A R410A Communication Cable No.× mm2 (VCTF-SB) 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5
Precharged Amount in kg 51.00 55.00 59.00 64.00 67.00 Refrigerant name R410A R410A R410A R410A
factory lbs 112.4 121.3 130.1 141.1 147.7 Precharged Amount in kg 72.00 75.00 79.00 84.00
Refrigerant GWP 2087.5 2087.5 2087.5 2087.5 2087.5 factory lbs 158.7 165.3 174.2 185.2
Refrigerant
TCO2eq 106.5 114.8 123.2 133.6 139.9 GWP 2087.5 2087.5 2087.5 2087.5
Electronic Expansion Electronic Expansion Electronic Expansion Electronic Expansion Electronic Expansion TCO2eq 150.3 156.6 164.9 175.4
Control
Valve Valve Valve Valve Valve Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
220, 3, 60 220, 3, 60 220, 3, 60 220, 3, 60 220, 3, 60 220, 3, 60 220, 3, 60 220, 3, 60 220, 3, 60
Power Supply Ø , V, Hz Power Supply Ø , V, Hz
220-240, 3, 50 220-240, 3, 50 220-240, 3, 50 220-240, 3, 50 220-240, 3, 50 220-240, 3, 50 220-240, 3, 50 220-240, 3, 50 220-240, 3, 50
Number of maximum connectable indoor units5) 52 55 58 61 64 Number of maximum connectable indoor units5) 64 64 64 64
Note : Note :
1. Nominal capacity applied with non-ducted indoor units, and is rated 0 m. above sea level with 7.5 m. of refrigerant line per indoor unit and a 0 m. level difference between outdoor and indoor units. 1. Nominal capacity applied with non-ducted indoor units, and is rated 0 m. above sea level with 7.5 m. of refrigerant line per indoor unit and a 0 m. level difference between outdoor and indoor units.
All capacities are net with a Combination Ratio between 95–105%. Nominal cooling capacity rating obtained with air entering the indoor unit at 80°F (27°C) dry bulb (DB) and 67°F (19°C) wet bulb All capacities are net with a Combination Ratio between 95–105%. Nominal cooling capacity rating obtained with air entering the indoor unit at 80°F (27°C) dry bulb (DB) and 67°F (19°C) wet bulb
(WB) and outdoor ambient conditions of 95°F (35°C) dry bulb (DB) and 75°F (24°C) wet bulb (WB). Nominal heating capacity rating obtained with air entering the indoor unit at 70°F (21°C) dry bulb (WB) and outdoor ambient conditions of 95°F (35°C) dry bulb (DB) and 75°F (24°C) wet bulb (WB). Nominal heating capacity rating obtained with air entering the indoor unit at 70°F (21°C) dry bulb
(DB) and 59°F (15°C) wet bulb (WB) and outdoor ambient conditions of 47°F (8°C) dry bulb (DB) and 43°F (6°C) wet bulb (WB). (DB) and 59°F (15°C) wet bulb (WB) and outdoor ambient conditions of 47°F (8°C) dry bulb (DB) and 43°F (6°C) wet bulb (WB).
2. Rated capacity is certified under AHRI Standard 1230. For AHRI ratings, refer to the AHRI website http://www.ahridirectory.org. 2. Rated capacity is certified under AHRI Standard 1230. For AHRI ratings, refer to the AHRI website http://www.ahridirectory.org.
3. The System Combination Ratio must be between 50–130%. 3. The System Combination Ratio must be between 50–130%.
4. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745. 4. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
5. Communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded or unshielded, and must comply with applicable local and national codes. 5. Communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded or unshielded, and must comply with applicable local and national codes.
If shielded, ensure the communication cable is properly grounded to chassis at the master ODU only. Do not ground the ODU-IDU (or HRU) communication cable at any other point. If shielded, ensure the communication cable is properly grounded to chassis at the master ODU only. Do not ground the ODU-IDU (or HRU) communication cable at any other point.
6. Power wiring is field provided, solid or stranded, and must comply with the applicable local and national codes.. 6. Power wiring is field provided, solid or stranded, and must comply with the applicable local and national codes..
7. LG requires that LATS software be used on all projects to ensure correct line sizing. Designer must verify the shop drawing design against the as built design using LATS. 7. LG requires that LATS software be used on all projects to ensure correct line sizing. Designer must verify the shop drawing design against the as built design using LATS.
Contractor must also use LG manufactured Y-Branch and Header Kits only. Contractor must also use LG manufactured Y-Branch and Header Kits only.

060 061
OUTDOOR UNIT
OUTDOOR UNIT SPECIFICATION

MULTI V 5 HIGH EFFICIENCY_460V


ARUM072DTE5 / ARUM096DTE5 / ARUM121DTE5 / ARUM144DTE5 / ARUM168DTE5 ARUM192DTE5 / ARUM216DTE5 / ARUM241DTE5 / ARUM264DTE5 / ARUM288DTE5

RT 6.0 8.0 10.0 12.0 14.0 RT 16.0 18.0 20.0 22.0 24.0
Combination Unit ARUM072DTE5 ARUM096DTE5 ARUM121DTE5 ARUM144DTE5 ARUM168DTE5 Combination Unit ARUM192DTE5 ARUM216DTE5 ARUM241DTE5 ARUM264DTE5 ARUM288DTE5
Model Name Model Name
Independent Unit ARUM072DTE5 ARUM096DTE5 ARUM121DTE5 ARUM144DTE5 ARUM168DTE5 ARUM168DTE5 ARUM192DTE5
Independent Unit ARUM192DTE5 ARUM216DTE5 ARUM241DTE5
Btu/h 72,000 96,000 120,000 144,000 168,000 ARUM096DTE5 ARUM096DTE5
Cooling Btu/h 192,000 216,000 240,000 264,000 288,000
kW 21.1 28.1 35.2 42.2 49.2 Cooling
Norminal kW 56.3 63.3 70.3 77.4 84.4
Btu/h 81,000 108,000 135,000 162,000 189,000 Norminal
Heating Btu/h 216,000 243,000 243,000 297,000 324,000
kW 23.7 31.7 39.6 47.5 55.4 Heating
Capacity kW 63.3 71.2 71.2 87.0 95.0
Btu/h 69,000 92,000 114,000 138,000 160,000 Capacity
Cooling Btu/h 184,000 206,000 222,000 252,000 276,000
kW 20.2 27.0 33.4 40.4 46.9 Cooling
Rated kW 53.9 60.4 65.1 73.9 80.9
Btu/h 77,000 103,000 129,000 154,000 180,000 Rated
Heating Btu/h 206,000 230,000 230,000 283,000 309,000
kW 22.6 30.2 37.8 45.1 52.8 Heating
Cooling kW 4.28 5.33 7.72 9.30 12.23 kW 60.4 67.4 67.4 82.9 90.6
Norminal Cooling kW 13.61 15.37 16.80 17.56 18.94
Heating kW 5.39 6.74 9.20 10.54 13.98 Norminal
Input Heating kW 15.46 17.75 17.75 20.72 22.20
Cooling (Nonducted / Ducted) kW 5.15 / 5.31 6.39 / 6.82 8.7 / 9.12 11.04 / 11.41 13.68 / 14.41 Input
Rated Cooling (Nonducted / Ducted) kW 14.84 / 16.73 18.39 / 19.25 22 / 21.35 20.06 / 21.23 21.23 / 23.55
Heating (Nonducted / Ducted) kW 6.49 / 5.89 8.25 / 6.97 10.93 / 9.523 12.82 / 11.75 16.49 / 14.78 Rated
Norminal Cooling 16.82 18.01 15.54 15.48 13.74 Heating (Nonducted / Ducted) kW 18.3 / 16.1 21.07 / 19.1 21.07 / 20.12 24.74 / 21.75 26.55 / 23.07
EER Norminal Cooling 14.11 14.05 14.29 15.03 15.21
Rated Cooling (Nonducted / Ducted) 13.4 / 13 14.40 / 13.5 13.1 / 12.5 12.5 / 12.1 11.7 / 11.1 EER
IEER Rated Cooling (Nonducted / Ducted) 28.4 / 23.6 33 / 25.1 29.6 / 24.6 28.6 / 23 25.4 / 21.9 Rated Cooling (Nonducted / Ducted) 12.4 / 11 11.2 / 10.7 10.13 / 10.4 12.56 / 11.87 13 / 11.72
Norminal Heating 4.40 4.70 4.30 4.50 3.96 IEER Rated Cooling (Nonducted / Ducted) 25.9 / 23 24.8 / 22.4 23.5 / 22.7 22 / 21.5 22 / 21
COP Norminal Heating 4.09 4.01 4.01 4.20 4.28
Rated Heating(Nonducted / Ducted) 3.83 / 3.48 4.33 / 3.66 3.97 / 3.46 3.84 / 3.52 3.57 / 3.2 COP
Power Factor Rated - 0.93 0.93 0.93 0.93 0.93 Rated Heating(Nonducted / Ducted) 3.75 / 3.3 3.53 / 3.2 3.35 / 3.2 3.81 / 3.35 3.93 / 3.41
Casing Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Power Factor Rated - 0.93 0.93 0.93 0.93 0.93
Heat Exchanger Ocean Black Fin Ocean Black Fin Ocean Black Fin Ocean Black Fin Ocean Black Fin Casing Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray
Compressor Motor Output × Number W × No. 4,200 × 1 5,300 × 1 5,300 × 1 4,200 × 1 + 4,200 × 1 4,200 × 1 + 4,200 × 1 Heat Exchanger Ocean Black Fin Ocean Black Fin Ocean Black Fin Ocean Black Fin Ocean Black Fin
(5,300 × 1)
Type Propeller fan Propeller fan Propeller fan Propeller fan Propeller fan Compressor Motor Output × Number W × No. 5,300 × 2 5,300 × 2 5,300 × 2 5,300 × 3
+ (4,200 × 2)
Motor Output × Number W 1,200 × 1 900 × 2 900 × 2 900 × 2 900 × 2 Type Propeller fan Propeller fan Propeller fan Propeller fan Propeller fan
Fan m /min
3
240 × 1 320 × 1 320 × 1 320 × 1 320 × 1 Motor Output × Number W 900 × 2 900 × 2 900 × 2 900 × 2 900 × 4
Air Flow Rate (High)
ft3/min 8,476 × 1 1,1301 × 1 1,1301 × 1 1,1301 × 1 1,1301 × 1 Fan m3/min 320 × 1 320 × 1 320 × 1 320 × 1 320 × 2
Drive DC INVERTER DC INVERTER DC INVERTER DC INVERTER DC INVERTER Air Flow Rate (High)
ft /min
3
1,1301 × 1 1,1301 × 1 1,1301 × 1 11,301 × 2 11,301 × 2
Liquid Pipe mm (inch) 9.52(3/8) 9.52(3/8) 12.7(1/2) 12.7(1/2) 15.88(5/8) Drive DC INVERTER DC INVERTER DC INVERTER DC INVERTER DC INVERTER
Pipe Connections For
Low Pressure Gas Pipe mm (inch) 19.05(3/4) 22.2(7/8) 28.58(1-1/8) 28.58(1-1/8) 28.58(1-1/8) Liquid Pipe mm (inch) 15.88(5/8) 15.88(5/8) 15.88(5/8) 19.05(3/4) 19.05(3/4)
Heat Pump
High Pressure Gas Pipe mm (inch) 15.88(5/8) 19.05(3/4) 19.05(3/4) 22.2(7/8) 22.2(7/8) Pipe Connections For
Low Pressure Gas Pipe mm (inch) 28.58(1-1/8) 28.58(1-1/8) 34.9(1-3/8) 34.9(1-3/8) 34.9(1-3/8)
Pipe Connections For Liquid Pipe mm (inch) 9.52(3/8) 9.52(3/8) 12.7(1/2) 12.7(1/2) 15.88(5/8) Heat Pump
High Pressure Gas Pipe mm (inch) 28.58(1-1/8) 28.58(1-1/8) 28.58(1-1/8) 28.58(1-1/8) 28.58(1-1/8)
Heat Pump Gas Pipe mm (inch) 19.05(3/4) 22.2(7/8) 28.58(1-1/8) 28.58(1-1/8) 28.58(1-1/8)
Pipe Connections For Liquid Pipe mm (inch) 15.88(5/8) 15.88(5/8) 15.88(5/8) 19.05(3/4) 19.05(3/4)
(930 × 1,690 × 760) (1,240 × 1,690 × (1,240 × 1,690 × (1,240 × 1,690 × (1,240 × 1,690 × Heat Pump
mm Gas Pipe mm (inch) 28.58(1-1/8) 28.58(1-1/8) 34.9(1-3/8) 34.9(1-3/8) 34.9(1-3/8)
×1 760) × 1 760) × 1 760) × 1 760) × 1
Dimensions (W × H × D) (1,240 × 1,690 × (1,240 × 1,690 × (1,240 × 1,690 × (1,240 × 1,690 × (1,240 × 1,690 ×
(36-5/8 × 66-17/32 × (48-13/16 × 66-17/32 (48-13/16 × 66-17/32 (48-13/16 × 66-17/32 (48-13/16 × 66-17/32 mm
inch 760) × 1 760) × 1 760) × 1 760) × 2 760) × 2
29-29/32) × 1 × 29-29/32) × 1 × 29-29/32) × 1 × 29-29/32) × 1 × 29-29/32) × 1 Dimensions (W × H × D)
(48-13/16 × 66-17/32 (48-13/16 × 66-17/32 (48-13/16 × 66-17/32 (48-13/16 × 66-17/32 (48-13/16 × 66-17/32
kg 195 × 1 230 × 1 230 × 1 290 × 1 290 × 1 inch
Net Weight × 29-29/32) × 1 × 29-29/32) × 1 × 29-29/32) × 1 × 29-29/32) × 2 × 29-29/32) × 2
lbs 430 × 1 507 × 1 507 × 1 639 × 1 639 × 1 kg 299 × 1 302 × 1 302 × 1 (230 × 1) + (290 × 1) (230 × 1) + (299 × 1)
Sound Pressure Level Cooling dB(A) 58.0 58.0 59.0 60.0 61.0 Net Weight
lbs 659 × 1 666 × 1 666 × 1 (507 × 1) + (639 × 1) (507 × 1) + (659 × 1)
Sound Power Level Cooling dB(A) 77.0 78.0 79.0 83.0 85.0 Sound Pressure Level Cooling dB(A) 62.0 64.0 65.0 63.0 63.0
Communication Cable No.× mm2 (VCTF-SB) 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5 Sound Power Level Cooling dB(A) 87.0 88.0 88.0 86.0 87.0
Refrigerant name R410A R410A R410A R410A R410A Communication Cable No.× mm2 (VCTF-SB) 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5
Precharged Amount in kg 13.0 16.0 20.0 24.0 29.0 Refrigerant name R410A R410A R410A R410A R410A
factory lbs 28.7 35.3 44.1 52.9 63.9
Precharged Amount in kg 32.0 35.0 39.0 45.00 48.00
Refrigerant GWP 2087.5 2087.5 2087.5 2087.5 2087.5 factory lbs 70.5 77.2 86.0 99.2 105.8
TCO2eq 27.1 33.4 41.8 50.1 60.5 Refrigerant GWP 2087.5 2087.5 2087.5 2087.5 2087.5
Electronic Expansion Electronic Expansion Electronic Expansion Electronic Expansion Electronic Expansion
Control TCO2eq 66.8 73.1 81.4 93.9 100.2
Valve Valve Valve Valve Valve
Power Supply Ø , V, Hz 460, 3, 60 460, 3, 60 460, 3, 60 460, 3, 60 460, 3, 60 Electronic Expansion Electronic Expansion Electronic Expansion Electronic Expansion Electronic Expansion
Control
Valve Valve Valve Valve Valve
Number of maximum connectable indoor units5) 13 16 20 24 29
Power Supply Ø , V, Hz 460, 3, 60 460, 3, 60 460, 3, 60 460, 3, 60 460, 3, 60
Number of maximum connectable indoor units5) 32 35 39 42 45

Note : Note :
1. Nominal capacity applied with non-ducted indoor units, and is rated 0 m. above sea level with 7.5 m. of refrigerant line per indoor unit and a 0 m. level difference between outdoor and indoor units. 1. Nominal capacity applied with non-ducted indoor units, and is rated 0 m. above sea level with 7.5 m. of refrigerant line per indoor unit and a 0 m. level difference between outdoor and indoor units.
All capacities are net with a Combination Ratio between 95–105%. Nominal cooling capacity rating obtained with air entering the indoor unit at 80°F (27°C) dry bulb (DB) and 67°F (19°C) wet bulb All capacities are net with a Combination Ratio between 95–105%. Nominal cooling capacity rating obtained with air entering the indoor unit at 80°F (27°C) dry bulb (DB) and 67°F (19°C) wet bulb
(WB) and outdoor ambient conditions of 95°F (35°C) dry bulb (DB) and 75°F (24°C) wet bulb (WB). Nominal heating capacity rating obtained with air entering the indoor unit at 70°F (21°C) dry bulb (WB) and outdoor ambient conditions of 95°F (35°C) dry bulb (DB) and 75°F (24°C) wet bulb (WB). Nominal heating capacity rating obtained with air entering the indoor unit at 70°F (21°C) dry bulb
(DB) and 59°F (15°C) wet bulb (WB) and outdoor ambient conditions of 47°F (8°C) dry bulb (DB) and 43°F (6°C) wet bulb (WB). (DB) and 59°F (15°C) wet bulb (WB) and outdoor ambient conditions of 47°F (8°C) dry bulb (DB) and 43°F (6°C) wet bulb (WB).
2. Rated capacity is certified under AHRI Standard 1230. For AHRI ratings, refer to the AHRI website http://www.ahridirectory.org. 2. Rated capacity is certified under AHRI Standard 1230. For AHRI ratings, refer to the AHRI website http://www.ahridirectory.org.
3. The System Combination Ratio must be between 50–130%. 3. The System Combination Ratio must be between 50–130%.
4. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745. 4. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
5. Communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded or unshielded, and must comply with applicable local and national codes. 5. Communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded or unshielded, and must comply with applicable local and national codes.
If shielded, ensure the communication cable is properly grounded to chassis at the master ODU only. Do not ground the ODU-IDU (or HRU) communication cable at any other point. If shielded, ensure the communication cable is properly grounded to chassis at the master ODU only. Do not ground the ODU-IDU (or HRU) communication cable at any other point.
6. Power wiring is field provided, solid or stranded, and must comply with the applicable local and national codes.. 6. Power wiring is field provided, solid or stranded, and must comply with the applicable local and national codes..
7. LG requires that LATS software be used on all projects to ensure correct line sizing. Designer must verify the shop drawing design against the as built design using LATS. 7. LG requires that LATS software be used on all projects to ensure correct line sizing. Designer must verify the shop drawing design against the as built design using LATS.
Contractor must also use LG manufactured Y-Branch and Header Kits only. Contractor must also use LG manufactured Y-Branch and Header Kits only.

062 063
OUTDOOR UNIT
OUTDOOR UNIT SPECIFICATION

MULTI V 5 HIGH EFFICIENCY_460V


ARUM312DTE5 / ARUM336DTE5 / ARUM360DTE5 / ARUM384DTE5 / ARUM408DTE5 ARUM432DTE5 / ARUM456DTE5 / ARUM480DTE5 / ARUM504DTE5

RT 26.0 28.0 30.0 32.0 34.0 RT 36.0 38.0 40.0 42.0


Combination Unit ARUM312DTE5 ARUM336DTE5 ARUM360DTE5 ARUM384DTE5 ARUM408DTE5 Combination Unit ARUM432DTE5 ARUM456DTE5 ARUM480DTE5 ARUM504DTE5
Model Name ARUM216DTE5 ARUM216DTE5 ARUM216DTE5 ARUM216DTE5 ARUM216DTE5 ARUM192DTE5 ARUM216DTE5 ARUM216DTE5 ARUM216DTE5
Independent Unit Model Name
ARUM096DTE5 ARUM121DTE5 ARUM144DTE5 ARUM168DTE5 ARUM192DTE5 Independent Unit ARUM121DTE5 ARUM121DTE5 ARUM144DTE5 ARUM168DTE5
Btu/h 312,000 336,000 360,000 384,000 408,000 ARUM121DTE5 ARUM121DTE5 ARUM121DTE5 ARUM121DTE5
Cooling Btu/h 432,000 456,000 480,000 504,000
kW 91.4 98.5 105.5 112.5 119.6 Cooling
Norminal kW 126.6 133.6 140.7 147.7
Btu/h 351,000 378,000 405,000 432,000 459,000 Norminal
Heating Btu/h 486,000 513,000 540,000 567,000
kW 102.9 110.8 118.7 126.6 134.5 Heating
Capacity kW 142.4 150.4 158.3 166.2
Btu/h 298,000 320,000 344,000 366,000 390,000 Capacity
Cooling Btu/h 412,000 434,000 458,000 480,000
kW 87.3 93.8 100.8 107.3 114.3 Cooling
Rated kW 120.8 127.2 134.2 140.7
Btu/h 333,000 359,000 384,000 410,000 436,000 Rated
Heating Btu/h 464,000 488,000 513,000 539,000
kW 97.6 105.2 112.5 120.2 127.8 Heating
Cooling kW 20.70 23.09 24.67 27.60 28.98 kW 136.0 143.0 150.4 158.0
Norminal Cooling kW 29.05 30.81 32.39 35.32
Heating kW 24.49 26.95 28.29 31.73 33.21 Norminal
Input Heating kW 33.86 36.15 37.49 40.93
Cooling (Nonducted / Ducted) kW 24.78 / 26.07 27.1 / 28.37 29.43 / 30.66 32.07 / 33.66 33.23 / 35.98 Input
Rated Cooling (Nonducted / Ducted) kW 32.24 / 34.97 35.8 / 37.49 38.14 / 37.78 40.77 / 42.78
Heating (Nonducted / Ducted) kW 29.32 / 26.07 32 / 28.62 33.89 / 30.85 37.56 / 33.88 39.37 / 35.2 Rated
Norminal Cooling 15.07 14.55 14.59 13.91 14.08 Heating (Nonducted / Ducted) kW 40.16 / 35.15 42.93 / 38.15 44.82 / 40.37 48.49 / 43.4
EER Norminal Cooling 14.87 14.80 14.82 14.27
Rated Cooling (Nonducted / Ducted) 12.02 / 11.43 11.81 / 11.28 11.69 / 11.22 11.41 / 10.87 11.74 / 10.84 EER
IEER Rated Cooling (Nonducted / Ducted) 22 / 21 20.5 / 20.5 20 / 19.5 19 / 19.3 18.8 / 19 Rated Cooling (Nonducted / Ducted) 12.78 / 11.78 12.12 / 11.58 12.01 / 11.51 11.77 / 11.22
Norminal Heating 4.20 4.11 4.20 3.99 4.05 IEER Rated Cooling (Nonducted / Ducted) 19.8 / 20 19.2 / 18.5 19 / 18 18.6 / 17.5
COP Norminal Heating 4.21 4.16 4.22 4.06
Rated Heating(Nonducted / Ducted) 3.74 / 3.33 3.68 / 3.29 3.65 / 3.32 3.55 / 3.2 3.63 / 3.25 COP
Power Factor Rated - 0.93 0.93 0.93 0.93 0.93 Rated Heating(Nonducted / Ducted) 3.87 / 3.36 3.75 / 3.33 3.72 / 3.36 3.64 / 3.26
Casing Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Power Factor Rated - 0.93 0.93 0.93 0.93
Heat Exchanger Ocean Black Fin Ocean Black Fin Ocean Black Fin Ocean Black Fin Ocean Black Fin Casing Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray
(5,300 × 2) (5,300 × 2) Heat Exchanger Ocean Black Fin Ocean Black Fin Ocean Black Fin Ocean Black Fin
Compressor Motor Output × Number W × No. 5,300 × 3 5,300 × 3 5,300 × 4
+ (4,200 × 2) + (4,200 × 2) Compressor Motor Output × Number W × No. 5,300 × 4 5,300 × 4 (5,300 × 3) + (4,200 × 2) (5,300 × 3) + (4,200 × 2)
Type Propeller fan Propeller fan Propeller fan Propeller fan Propeller fan Type Propeller fan Propeller fan Propeller fan Propeller fan
Motor Output × Number W 900 × 4 900 × 4 900 × 4 900 × 4 900 × 4 Motor Output × Number W 900 × 6 900 × 6 900 × 6 900 × 6
Fan m3/min 320 × 2 320 × 2 320 × 2 320 × 2 320 × 2 Fan m3/min 320 × 3 320 × 3 320 × 3 320 × 3
Air Flow Rate (High) Air Flow Rate (High)
ft /min
3
11,301 × 2 11,301 × 2 11,301 × 2 11,301 × 2 11,301 × 2 ft3/min 11,301 × 3 11,301 × 3 11,301 × 3 11,301 × 3
Drive DC INVERTER DC INVERTER DC INVERTER DC INVERTER DC INVERTER Drive DC INVERTER DC INVERTER DC INVERTER DC INVERTER
Liquid Pipe mm (inch) 19.05(3/4) 19.05(3/4) 19.05(3/4) 19.05(3/4) 19.05(3/4) Liquid Pipe mm (inch) 19.05(3/4) 19.05(3/4) 19.05(3/4) 19.05(3/4)
Pipe Connections For Pipe Connections For
Low Pressure Gas Pipe mm (inch) 34.9(1-3/8) 34.9(1-3/8) 41.3(1-5/8) 41.3(1-5/8) 41.3(1-5/8) Low Pressure Gas Pipe mm (inch) 41.3(1-5/8) 41.3(1-5/8) 41.3(1-5/8) 41.3(1-5/8)
Heat Pump Heat Pump
High Pressure Gas Pipe mm (inch) 28.58(1-1/8) 28.58(1-1/8) 34.9(1-3/8) 34.9(1-3/8) 34.9(1-3/8) High Pressure Gas Pipe mm (inch) 34.9(1-3/8) 34.9(1-3/8) 34.9(1-3/8) 34.9(1-3/8)
Pipe Connections For Liquid Pipe mm (inch) 19.05(3/4) 19.05(3/4) 19.05(3/4) 19.05(3/4) 19.05(3/4) Pipe Connections For Liquid Pipe mm (inch) 19.05(3/4) 19.05(3/4) 19.05(3/4) 19.05(3/4)
Heat Pump Gas Pipe mm (inch) 34.9(1-3/8) 34.9(1-3/8) 41.3(1-5/8) 41.3(1-5/8) 41.3(1-5/8) Heat Pump Gas Pipe mm (inch) 41.3(1-5/8) 41.3(1-5/8) 41.3(1-5/8) 41.3(1-5/8)
(1,240 ×1,690 × (1,240 ×1,690 × (1,240 ×1,690 × (1,240 ×1,690 × (1,240 ×1,690 × mm (1,240 ×1,690 × 760) × 3 (1,240 ×1,690 × 760) × 3 (1,240 ×1,690 × 760) × 3 (1,240 ×1,690 × 760) × 3
mm
760) × 2 760) × 2 760) × 2 760) × 2 760) × 2 Dimensions (W × H × D) (48-13/16 × 66-17/32 × 29- (48-13/16 × 66-17/32 × 29- (48-13/16 × 66-17/32 × 29- (48-13/16 × 66-17/32 × 29-
Dimensions (W × H × D) inch
(48-13/16 × 66-17/32 (48-13/16 × 66-17/32 (48-13/16 × 66-17/32 (48-13/16 × 66-17/32 (48-13/16 × 66-17/32 29/32) × 3 29/32) × 3 29/32) × 3 29/32) × 3
inch
× 29-29/32) × 2 × 29-29/32) × 2 × 29-29/32) × 2 × 29-29/32) × 2 × 29-29/32) × 2 (230 × 1) + (290 × 1) (230 × 1) + (290 × 1)
kg (230 × 1) + (302 × 1) (230 × 1) + (302 × 1) (290 × 1) + (302 × 1) (290 × 1) + (302 × 1) (299 × 1) + (302 × 1) kg (230 × 2) + (299 × 1) (230 × 2) + (302 × 1)
Net Weight + (302 × 1) + (302 × 1)
Net Weight
lbs (507 × 1) + (666 × 1) (507 × 1) + (666 × 1) (639 × 1) + (666 × 1) (639 × 1) + (666 × 1) (659 × 1) + (666 × 1) (507 × 1) + (639 × 1) (507 × 1) + (639 × 1)
lbs (507 × 2) + (659 × 1) (507 × 2) + (666 × 1)
Sound Pressure Level Cooling dB(A) 65.0 65.0 66.0 66.0 66.0 + (666 × 1) + (666 × 1)
Sound Power Level Cooling dB(A) 88.0 88.0 89.0 89.0 90.0 Sound Pressure Level Cooling dB(A) 66.0 66.0 67.0 67.0
Communication Cable No.× mm2 (VCTF-SB) 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5 Sound Power Level Cooling dB(A) 89.0 89.0 89.0 90.0
Refrigerant name R410A R410A R410A R410A R410A Communication Cable No.× mm2 (VCTF-SB) 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5
Precharged Amount in kg 51.00 55.00 59.00 64.00 67.00 Refrigerant name R410A R410A R410A R410A
factory lbs 112.4 121.3 130.1 141.1 147.7 Precharged Amount in kg 72.00 75.00 79.00 84.00
Refrigerant GWP 2087.5 2087.5 2087.5 2087.5 2087.5 factory lbs 158.7 165.3 174.2 185.2
Refrigerant
TCO2eq 106.5 114.8 123.2 133.6 139.9 GWP 2087.5 2087.5 2087.5 2087.5
Electronic Expansion Electronic Expansion Electronic Expansion Electronic Expansion Electronic Expansion TCO2eq 150.3 156.6 164.9 175.4
Control
Valve Valve Valve Valve Valve Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
Power Supply Ø , V, Hz 460, 3, 60 460, 3, 60 460, 3, 60 460, 3, 60 460, 3, 60 Power Supply Ø , V, Hz 460, 3, 60 460, 3, 60 460, 3, 60 460, 3, 60
Number of maximum connectable indoor units5) 52 55 58 61 64 Number of maximum connectable indoor units5) 64 64 64 64

Note : Note :
1. Nominal capacity applied with non-ducted indoor units, and is rated 0 m. above sea level with 7.5 m. of refrigerant line per indoor unit and a 0 m. level difference between outdoor and indoor units. 1. Nominal capacity applied with non-ducted indoor units, and is rated 0 m. above sea level with 7.5 m. of refrigerant line per indoor unit and a 0 m. level difference between outdoor and indoor units.
All capacities are net with a Combination Ratio between 95–105%. Nominal cooling capacity rating obtained with air entering the indoor unit at 80°F (27°C) dry bulb (DB) and 67°F (19°C) wet bulb All capacities are net with a Combination Ratio between 95–105%. Nominal cooling capacity rating obtained with air entering the indoor unit at 80°F (27°C) dry bulb (DB) and 67°F (19°C) wet bulb
(WB) and outdoor ambient conditions of 95°F (35°C) dry bulb (DB) and 75°F (24°C) wet bulb (WB). Nominal heating capacity rating obtained with air entering the indoor unit at 70°F (21°C) dry bulb (WB) and outdoor ambient conditions of 95°F (35°C) dry bulb (DB) and 75°F (24°C) wet bulb (WB). Nominal heating capacity rating obtained with air entering the indoor unit at 70°F (21°C) dry bulb
(DB) and 59°F (15°C) wet bulb (WB) and outdoor ambient conditions of 47°F (8°C) dry bulb (DB) and 43°F (6°C) wet bulb (WB). (DB) and 59°F (15°C) wet bulb (WB) and outdoor ambient conditions of 47°F (8°C) dry bulb (DB) and 43°F (6°C) wet bulb (WB).
2. Rated capacity is certified under AHRI Standard 1230. For AHRI ratings, refer to the AHRI website http://www.ahridirectory.org. 2. Rated capacity is certified under AHRI Standard 1230. For AHRI ratings, refer to the AHRI website http://www.ahridirectory.org.
3. The System Combination Ratio must be between 50–130%. 3. The System Combination Ratio must be between 50–130%.
4. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745. 4. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
5. Communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded or unshielded, and must comply with applicable local and national codes. 5. Communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded or unshielded, and must comply with applicable local and national codes.
If shielded, ensure the communication cable is properly grounded to chassis at the master ODU only. Do not ground the ODU-IDU (or HRU) communication cable at any other point. If shielded, ensure the communication cable is properly grounded to chassis at the master ODU only. Do not ground the ODU-IDU (or HRU) communication cable at any other point.
6. Power wiring is field provided, solid or stranded, and must comply with the applicable local and national codes.. 6. Power wiring is field provided, solid or stranded, and must comply with the applicable local and national codes..
7. LG requires that LATS software be used on all projects to ensure correct line sizing. Designer must verify the shop drawing design against the as built design using LATS. 7. LG requires that LATS software be used on all projects to ensure correct line sizing. Designer must verify the shop drawing design against the as built design using LATS.
Contractor must also use LG manufactured Y-Branch and Header Kits only. Contractor must also use LG manufactured Y-Branch and Header Kits only.

064 065
OUTDOOR UNIT
OUTDOOR UNIT KEY FEATURES

MULTI V S

EFFICIENCY
150m
Longest
LG’s 4th Generation Inverter Compressor
piping length MULTI V S has high efficiency inverter scroll compressor with frequency range 15Hz~150Hz.

World Best Compressor Speed 150Hz


1. Compact Size - Rapid response capability
15m - Compact core design(concentrated motor)
Height difference 55%
Reduction
- Down to 15Hz : part load efficiency improvement
between IDU ~ IDU

760mm

Operation Range (Hz)


150

330mm
Conventional MULTI V S
8 HP 8 HP
120
920mm 950mm

40m 2. Piping Capabilities


Height difference Total Piping Length 300m
between ODU ~ IDU 150m**
Longest piping length (Equivalent) 20
(175m*)
15
40m
Longest piping length after 1st branch
(90m**)
Conventional
300m Height difference between ODU~IDU
40m
(50m*)
Total piping Height difference between IDU~IDU 15m 6 By-pass Valve
length * Equivalent
Compressor reliability is
** Conditional application
maximized with 6 By-pass Valve
3. Operation Range - Prevent compressor damage
• Heating : -20 ~ 18°C WB due to excessively compressed
• Cooling : -5°C ~ 48°C DB refrigerant more efficiently than
4 by-pass valve

High Pressure Compressor


- Viscosity of oil is secured due to high temperature and pressure.
- Do not need oil pump. (Efficiency Increases)

High
Pressure
Zone

High
Pressure
Low Zone
Benefit Application Pressure
Zone

• Saves valuable floor space • Premium residential apartment / House (with small balcony)
Low Pressure Compressor High Pressure Compressor
• Flexible design applications • Small sized office / Restaurant / Retail shops
- Slim, light and wide line up(4 ~ 12 HP) • Building with multiple owners
Inverter Scroll Compressor
- Combination of indoor unit
- Inverter SCROLL compressor of high efficiency
- Low vibration / Low noise

078 079
OUTDOOR UNIT
OUTDOOR UNIT KEY FEATURES

MULTI V S

EFFICIENCY
High Efficiency Optimal Heat Exchanger Circuit
EER (Cooling) COP (Heating) Variable Heat Exchanger Circuit is the world first technology which intelligently selects the optimal path for both heating and
cooling (Efficiency increased up to 5%).
EER

COP
10% 6HP 12% 6HP
Conventional
3.71 4.18 Variable Heat Exchanger Circuit adjusts the path number to match The number and direction of path are fixed independent of
temperatures and operation modes, thereby contributing to an temperature and operation mode. A fixed path limits efficiency
3.71 increase in energy efficiency
3.35

Cooling Heating Cooling Heating


B Company B Company

* Comparison Based on 6HP in cooling mode * Comparison Based on 6HP in heating mode Maximizing efficiency for all operations Compromising efficiency for each operation

Efficiency

Efficiency
Heating Heating

Reliable Inverter Compressor Cooling Cooling

1 2 3 4 Path Number 1 2 3 4 Path Number


MULTI V S Inverter compressors are highly efficient and reliable for all commercial & residential applications.

Compressor Efficiency Comparison


High reliability and efficiency at all capacity Heat Exchanger with Wide Louver Plus Fin
Efficiency

Scroll Compressor
- Below 7 HP : Rotary compressor
Rotary Compressor
- Upper 7 HP : Scroll compressor Improved heat exchanger efficiency of up to 7%.

Cooling Heating
4HP 6HP 8HP 12HP
Heat Exchange Rate (%)

Heat Exchange Rate (%)


Rotary Scroll
5% 7%
4 7 10 HP
* Based on internal test data
107%
105%
100% 100%

Conventional Wide Louver Plus Fin Conventional Wide Louver Plus Fin

080 081
INDOOR UNIT
INDOOR UNIT SPECIFICATION

ARTCOOL MIRROR
ARNU05GSJR4 / ARNU07GSJR4 / ARNU09GSJR4 ARNU18GSKR4 / ARNU24GSKR4
ARNU12GSJR4 / ARNU15GSJR4

Model Independent Unit ARNU05GSJR4 ARNU07GSJR4 ARNU09GSJR4 ARNU12GSJR4 ARNU15GSJR4 Model Independent Unit ARNU18GSKR4 ARNU24GSKR4
Cooling Nom kW 1.6 2.2 2.8 3.6 4.5 Cooling Nom kW 5.6 7.1
Capacity Capacity
Heating Nom kW 1.8 2.5 3.2 4.0 5.0 Heating Nom kW 6.3 7.5
Cooling / Heating Nom 1) W 11 12 13 15 23 Cooling / Heating Nom 1) W 32 39
Power Input Power Input
Cooling / Heating Rated 2) W 30 30 30 30 30 Cooling / Heating Rated 2) W 53 53
1 / 220 ~ 240 / 50 1 / 220 ~ 240 / 50 1 / 220 ~ 240 / 50 1 / 220 ~ 240 / 50 1 / 220 ~ 240 / 50 1 / 220 ~ 240 / 50 1 / 220 ~ 240 / 50
Power Supply Ø / V / Hz Power Supply Ø / V / Hz
1 / 220 / 60 1 / 220 / 60 1 / 220 / 60 1 / 220 / 60 1 / 220 / 60 1 / 220 / 60 1 / 220 / 60
Cooling H/M/L m3/min 6.8 / 6.5 / 5.9 7.2 / 6.8 / 5.9 7.8 / 7.2 / 5.9 8.5 / 7.8 / 6.8 10.5 / 9.5 / 6.8 Cooling H/M/L m3/min 14.0 / 12.0 / 10.5 15.2 / 12.7 / 10.2
Airflow Rate Airflow Rate
Heating H/M/L m3/min 6.8 / 6.5 / 5.9 7.2 / 6.8 / 5.9 7.8 / 7.2 / 5.9 8.5 / 7.8 / 6.8 10.5 / 9.5 / 6.8 Heating H/M/L m3/min 14.0 / 12.0 / 10.5 15.2 / 12.7 / 10.2
Sound Pressure H/M/L dBA 30 / 29 / 28 32 / 30 / 28 34 / 32 / 28 37 / 34 / 30 42 / 39 / 32 Sound Pressure H/M/L dBA 43 / 39 / 34 46 / 41 / 34
Sound Power H/M/L dBA 54 / 53 / 52 54 / 53 / 52 55 / 54 / 52 55 / 54 / 53 58 / 56 / 54 Sound Power H/M/L dBA 63 / 57 / 52 65 / 60 / 54
Dimensions Body WxHxD mm 837 x 308 x 192 837 x 308 x 192 837 x 308 x 192 837 x 308 x 192 837 x 308 x 192 Dimensions Body WxHxD mm 998 x 345 x 212 998 x 345 x 212
Net Weight kg 9.2 9.2 9.2 9.2 9.2 Net Weight kg 13.4 13.4
Liquid mm 6.35 6.35 6.35 6.35 6.35 Liquid mm 6.35 9.52
Piping Connection Gas mm 12.7 12.7 12.7 12.7 12.7 Piping Connection Gas mm 12.7 15.88
Drain I.D mm 16.0 16.0 16.0 16.0 16.0 Drain I.D mm 16.0 16.0

*This product contains Fluorinated Greenhouse Gases. (R410A) *This product contains Fluorinated Greenhouse Gases. (R410A)
1) Nom. : Performance tested under EN14511 1) Nom. : Performance tested under EN14511
2) Rated : 1. Max power input allowed for fan motor 2) Rated : 1. Max power input allowed for fan motor
Cooling - Indoor temp. 27°C (80.6°F)DB / 19°C( 66.2°F)WB, Outdoor temp. 35°C (95°F)DB / 24°C (75.2°F)WB, Interconnecting piping length 7.5m, Level difference of zero Cooling - Indoor temp. 27°C (80.6°F)DB / 19°C (66.2°F)WB, Outdoor temp. 35°C (95°F)DB / 24°C (75.2°F)WB, Interconnecting piping length 7.5m, Level difference of zero
Heating - Indoor temp. 20°C (68°F)DB / 15°C (59°F)WBn Outdoor temp. 7°C (44.6°F)DB / 6°C (42.8°F)WB, Interconnecting piping length 7.5m, Level difference of zero Heating - Indoor temp. 20°C (68°F)DB / 15°C (59°F)WBn Outdoor temp. 7°C (44.6°F)DB / 6°C (42.8°F)WB, Interconnecting piping length 7.5m, Level difference of zero
2. Due to our policy of innovation some specifications may be changed without notification 2. Due to our policy of innovation some specifications may be changed without notification
3. I.D - ‘Internal Diameter’ 3. I.D - ‘Internal Diameter’

Accessories Accessories
Model ARNU05GSJR4 ARNU07GSJR4 ARNU09GSJR4 ARNU12GSJR4 ARNU15GSJR4 Model ARNU18GSKR4 ARNU24GSKR4
Simple (1 Contact Point with Case) PDRYCB000 Simple (1 Contact Point with Case) PDRYCB000

Dry 2 Contact Point PDRYCB400 Dry 2 Contact Point PDRYCB400


Contact For Thermostat (On-Off / Mode / Fan Speed) PDRYCB300 Contact For Thermostat (On-Off / Mode / Fan Speed) PDRYCB300
Modbus Communication PDRYCB500 Modbus Communication PDRYCB500
EEV Kit for MULTI V Indoor PRGK024A0 EEV Kit for MULTI V Indoor PRGK024A0

Wired Remote Controller Wired Remote Controller


Wireless Remote Controller Wireless Remote Controller
Premium Standard III Standard II Simple Simple for Hotel Premium Standard III Standard II Simple Simple for Hotel

PREMTA000 PREMTB100 PREMTBB10 PREMTB001 PREMTBB01 PQRCVCL0Q (Black) PQRCHCA0Q (Black) PQWRHQ0FDB PREMTA000 PREMTB100 PREMTBB10 PREMTB001 PREMTBB01 PQRCVCL0Q (Black) PQRCHCA0Q (Black) PQWRHQ0FDB
(White) (Black) (White) (Black) PQRCVCL0QW (White) PQRCHCA0QW (White) (White) (Black) (White) (Black) PQRCVCL0QW (White) PQRCHCA0QW (White)

174 175
INDOOR UNIT
INDOOR UNIT SPECIFICATION

STANDARD
ARNU05GSJN4 / ARNU07GSJN4 / ARNU09GSJN4 / ARNU12GSJN4 / ARNU15GSJN4 ARNU18GSKN4 / ARNU24GSKN4 / ARNU30GSVA4 / ARNU36GSVA4

Model Independent Unit ARNU05GSJN4 ARNU07GSJN4 ARNU09GSJN4 ARNU12GSJN4 ARNU15GSJN4 Model Independent Unit ARNU18GSKN4 ARNU24GSKN4 ARNU30GSVA4 ARNU36GSVA4
Cooling Nom kW 1.6 2.2 2.8 3.6 4.5 Cooling Nom kW 5.6 7.1 8.5 10.4
Capacity Capacity
Heating Nom kW 1.8 2.5 3.2 4.0 5.0 Heating Nom kW 6.3 7.5 9.2 10.8
Cooling / Cooling /
Nom 1) W 10.0 11.0 12.0 15.0 23.0 Nom 1) W 32.0 39.0 83 98
Power Heating Power Heating
Input Cooling / Input Cooling /
Rated 2) W 30.0 30.0 30.0 30.0 30.0 Rated 2) W 53.0 53.0 154 154
Heating Heating
1 / 220 ~ 240 / 50 1 / 220 ~ 240 / 50 1 / 220 ~ 240 / 50 1 / 220 ~ 240 / 50 1 / 220 ~ 240 / 50 1 / 220 ~ 240 / 50 1 / 220 ~ 240 / 50 1 / 220 ~ 240 / 50 1 / 220 ~ 240 / 50
Power Supply Ø / V / Hz Power Supply Ø / V / Hz
1 / 220 / 60 1 / 220 / 60 1 / 220 / 60 1 / 220 / 60 1 / 220 / 60 1 / 220 / 60 1 / 220 / 60 1 / 220 / 60 1 / 220 / 60
Cooling H/M/L m3/min 6.8 / 6.5 / 5.9 7.2 / 6.8 / 5.9 7.8 / 7.2 / 5.9 8.5 / 7.8 / 6.8 10.5 / 9.5 / 6.8 Cooling H/M/L m3/min 14.0 / 12.0 / 10.5 15.2 / 12.7 / 10.5 22.0 / 19.0 / 16.0 27.0 / 24.0 / 20.0
Airflow Rate Airflow Rate
Heating H/M/L m3/min 6.8 / 6.5 / 5.9 7.2 / 6.8 / 5.9 7.8 / 7.2 / 5.9 8.5 / 7.8 / 6.8 10.5 / 9.5 / 6.8 Heating H/M/L m3/min 14.0 / 12.0 / 10.5 15.2 / 12.7 / 10.5 22.0 / 19.0 / 16.0 27.0 / 24.0 / 20.0
Sound Pressure H/M/L dBA 30 / 29 / 28 32 / 30 / 28 34 / 32 / 28 37 / 34 / 30 42 / 39 / 32 Sound Pressure H/M/L dBA 43/ 39 / 34 46 / 41 / 34 48 / 45 / 42 50 / 47 / 43
Sound Power H/M/L dBA 54 / 53 / 52 54 / 53 / 52 55 / 54 / 52 55 / 54 / 53 58 / 56 / 54 Sound Power H/M/L dBA 63 / 57 / 52 65 / 60 / 54 61 / 58 / 55 63 / 60 / 57
Dimensions Body WxHxD mm 837 x 302 x 189 837 x 302 x 189 837 x 302 x 189 837 x 302 x 189 837 x 302 x 189 Dimensions Body WxHxD mm 998 x 330 x 210 998 x 330 x 210 1,190 x 346 x 265 1,190 x 346 x 265
Net Weight kg 8.50 8.50 8.50 8.50 8.50 Net Weight kg 12.50 12.50 19.0 19.0
Liquid mm 6.35 6.35 6.35 6.35 6.35 Liquid mm 6.35 9.52 9.52 9.52
Piping Piping
Gas mm 12.7 12.7 12.7 12.7 12.7 Gas mm 12.7 15.88 15.88 15.9
Connection Connection
Drain I.D mm 16.0 16.0 16.0 16.0 16.0 Drain I.D mm 16.0 16.0 16.0 16.0

* This product contains Fluorinated Greenhouse Gases. (R410A) * This product contains Fluorinated Greenhouse Gases. (R410A)
1) Nom. : Performance tested under EN14511 1) Nom. : Performance tested under EN14511
2) Rated : Max power input allowed for fan motor 2) Rated : Max power input allowed for fan motor
Note : 1. Capacities are based on the following conditions Note : 1. Capacities are based on the following conditions
- Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero
- Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero
2. Due to our policy of innovation some specifications may be changed without notification 2. Due to our policy of innovation some specifications may be changed without notification
3. I.D : ‘ Internal Diameter ’ 3. I.D : ‘ Internal Diameter ’

Accessories Accessories
Model ARNU05GSJN4 ARNU07GSJN4 ARNU09GSJN4 ARNU12GSJN4 ARNU15GSJN4 Model ARNU18GSKN4 ARNU24GSKN4 ARNU30GSVA4 ARNU36GSVA4
Simple (1 Contact Point with Case) PDRYCB000 Simple (1 Contact Point with Case) PDRYCB000

Dry 2 Contact Point PDRYCB400 Dry 2 Contact Point PDRYCB400


Contact For Thermostat (On-Off / Mode / Fan Speed) PDRYCB300 Contact For Thermostat (On-Off / Mode / Fan Speed) PDRYCB300
Modbus Communication PDRYCB500 Modbus Communication PDRYCB500
EEV Kit for MULTI V Indoor PRGK024A0 EEV Kit for MULTI V Indoor PRGK024A0 -

Wired Remote Controller Wired Remote Controller


Wireless Remote Controller Wireless Remote Controller
Premium Standard III Standard II Simple Simple for Hotel Premium Standard III Standard II Simple Simple for Hotel

PREMTA000 PREMTB100 PREMTBB10 PREMTB001 PREMTBB01 PQRCVCL0Q (Black) PQRCHCA0Q (Black) PQWRHQ0FDB PREMTA000 PREMTB100 PREMTBB10 PREMTB001 PREMTBB01 PQRCVCL0Q (Black) PQRCHCA0Q (Black) PQWRHQ0FDB
(White) (Black) (White) (Black) PQRCVCL0QW (White) PQRCHCA0QW (White) (White) (Black) (White) (Black) PQRCVCL0QW (White) PQRCHCA0QW (White)

176 177
INDOOR UNIT
INDOOR UNIT KEY FEATURES

CEILING MOUNTED CASSETTE (4 Way)

Compact and Stylish Design Independent Vane Control


• New 4 Way cassette panel adapted unibody shape and matching with into the ceiling The Independent Vane Operation feature uses separate motors, making it possible to control all four vanes independently.
• Panel size is fit into the ceiling tile
All Vane Operation Independent Vane Control
Direct Air Flow Indirect Air Flow
Unibody 620m
Shape m
(No Inlet Line)

620m
m

Compact Size
The indoor unit with slim and compact dimensions has reduced the restriction which enables successful installation in various spaces.

Capacity Height
Auto Elevation Grille 7.1 ~ 9.0kW 204mm
10.6kW 246mm
The Independent Vane Operation feature uses separate motors, making it possible to control all four vanes independently. 12.3 ~ 15.8kW 288mm

Eas filter cleaning ith elevation grill. 4-Point Support Structure Auto Leveling
* Length Width : 840 x 840mm

Prevent Ceiling Pollution


Memory for User’s Level Auto Stop Detection
Coanda design of air outlet can prevent contamination of ceiling.

STOP Max. Coanda Design Conventional


4.5m
Memory

Product
* Operating with wired remote controller (Model Name : PREMTB001,PREMTBB01) Ceiling Product Ceiling Product Ceiling
and wireless remote controller included in PTEGM0.
* Except ARNU05GTRC4, ARNU07GTRC4, ARNU09GTRC4, ARNU12GTRC4,
Louver Louver Louver
ARNU15GTQC4, ARNU18GTQC4, ARNU21GTQC4
* Applied to Cassette panel PT-UMC1

Ceiling Ceiling
Pollutions Pollutions

178 179
INDOOR UNIT
INDOOR UNIT KEY FEATURES INDOOR UNIT KEY FEATURES

CEILING MOUNTED CASSETTE (4 Way / 2 Way) CEILING MOUNTED CASSETTE (1 Way)

Flexible Connection 6-Step Vane Control


Flexible connection of remote controller. There are 6 different steps to control air flow direction. Also 1 way cassette has vane to move auto swing between left and right as
- Group control : 1 remote controller up to 16 indoor units. / Second remote control : 2 remote controllers to 1 indoor unit. 120 degree.

Easy & Solid Attachment to the Wall Moving Air Flow_1 Way cassette Fixed Air Flow_Duct system
Left and Right (Auto Swing) Up and Down (6 step)

20˚

120˚ Adjustable
wall

wall

Vane

70˚

Convenient Panel Installation


The detachable corner design makes it easy to adjust the hanger during installation and to check for leakages in the drain
connection pipe.
Detachable Corner Design Drain leakage check Hanger adjust
Minimized Height
LG 1 Way cassette isn’t affected by installation environment. LG 1 Way cassette height is 132mm and duct is 190mm, so it can
provide ideal solution for installation in limited space.

Refrigerant Drain leakage Size Comparison (Unit : mm)


piping check check and 132mm
and Hanger hanger adjust LG A Company B Company
190mm
adjust 1 Way Cassette 132 215 230
It is easy to install the panel to the body, using the button type panel design. Duct 190 200 200
Hanger adjust Hanger adjust

Flexible Installation
2 Way air flow without temperature variation The access for inspection at 1 Way Cassette does not require additional ducted space making the installation environment
uncomplicated.
2 Way cassette is suitable for narrow type of space such as office / hotel / dormitory corridor and it provides thermal comfort without
1 Way cassette Duct
temperature variation.
Duct

Inspection hole

180 181
INDOOR UNIT
INDOOR UNIT SPECIFICATION INDOOR UNIT SPECIFICATION

4 Way CASSETTE (570 × 570) 4 Way CASSETTE (840 × 840)


ARNU05GTRC4 / ARNU07GTRC4 / ARNU09GTRC4 / ARNU12GTRC4 ARNU24GTPC4 / ARNU28GTPC4 / ARNU30GTPC4 / ARNU36GTNC4
ARNU15GTQC4 / ARNU18GTQC4 / ARNU21GTQC4 ARNU42GTMC4 / ARNU48GTMC4 / ARNU54GTMC4

Model Independent Unit ARNU05GTRC4 ARNU07GTRC4 ARNU09GTRC4 ARNU12GTRC4 ARNU15GTQC4 ARNU18GTQC4 ARNU21GTQC4 Model Independent Unit ARNU24GTPC4 ARNU28GTPC4 ARNU30GTPC4 ARNU36GTNC4 ARNU42GTMC4 ARNU48GTMC4 ARNU54GTMC4
Cooling Nom kW 1.6 2.2 2.8 3.6 4.5 5.6 6.0 Cooling Nom kW 7.1 8.2 9.0 10.6 12.3 14.1 15.8
Capacity Capacity
Heating Nom kW 1.8 2.5 3.2 4.0 5.0 6.3 6.8
Heating Nom kW 8.0 9.2 10.0 11.9 13.8 15.9 18.0
Cooling / Heating Nom 1) W 13 13 14 17 24 25 28
Power Input Cooling / Heating Nom 1) W 31 40 40 70 104 120 135
Cooling / Heating Rated 2) W 30 30 30 30 30 30 30 Power Input
1 / 220~240 / 50 1 / 220~240 / 50 1 / 220~240 / 50 1 / 220~240 / 50 1 / 220~240 / 50 1 / 220~240 / 50 1 / 220~240 / 50 Cooling / Heating Rated 2) W 40 40 40 144 144 144 144
Power Supply Ø / V / Hz
1 / 220 / 60 1 / 220 / 60 1 / 220 / 60 1 / 220 / 60 1 / 220 / 60 1 / 220 / 60 1 / 220 / 60 1 / 220~240 / 50 1 / 220~240 / 50 1 / 220~240 / 50 1 / 220~240 / 50 1 / 220~240 / 50 1 / 220~240 / 50 1 / 220~240 / 50
Cooling H/M/L m3/min 7.5 / 7.0 / 6.6 7.5 / 7.0 / 6.6 8.0 / 7.5 / 7.1 8.7 / 8.0 / 7.0 11.0 / 10.0 / 9.3 11.2 / 11.0 / 10.0 12.0 / 11.1 / 9.4 Power Supply Ø / V / Hz
1 / 220 / 60 1 / 220 / 60 1 / 220 / 60 1 / 220 / 60 1 / 220 / 60 1 / 220 / 60 1 / 220 / 60
Airflow Rate
Heating H/M/L m3/min 7.5 / 7.0 / 6.6 7.5 / 7.0 / 6.6 8.0 / 7.5 / 7.1 8.7 / 8.0 / 7.0 11.0 / 10.0 / 9.3 11.2 / 11.0 / 10.0 12.0 / 11.1 / 9.4 Cooling H/M/L m3/min 17.0 / 15.0 / 13.0 19.0 / 16.0 / 14.0 24.3 / 22.8 / 19.5 25.0 / 21.0 / 19.0 30.0 / 27.0 / 24.0 31.0 / 29.0 / 27.0 34.0 / 32.0 / 27.0
Sound Pressure H/M/L dBA 29 / 27 / 26 29 / 27 / 26 30 / 29 / 27 32 / 30 / 27 36 / 34 / 32 37 / 35 / 34 40 / 38 / 34 Airflow Rate
Heating H/M/L m3/min 17.0 / 15.0 / 13.0 19.0 / 16.0 / 14.0 24.3 / 22.8 / 19.5 25.0 / 21.0 / 19.0 30.0 / 27.0 / 24.0 31.0 / 29.0 / 27.0 34.0 / 32.0 / 27.0
Sound Power H/M/L dBA 46 / 44 / 43 46 / 44 / 43 47 / 46 / 44 48 / 47 / 44 51 / 49 / 47 52 / 50 / 49 55 / 53 / 49
Dimensions Body WxHxD mm 570 x 214 x 570 570 x 214 x 570 570 x 214 x 570 570 x 214 x 570 570 x 256 x 570 570 x 256 x 570 570 x 256 x 570 Sound Pressure H/M/L dBA 36 / 34 / 31 39 / 35 / 33 40 / 36 / 33 43 / 40 / 37 44 / 41 / 38 46 / 43 / 41 50 / 48 / 44
Net Weight kg 12.6 12.6 13.7 13.7 15.0 15.0 15.0 Sound Power H/M/L dBA 55 / 53 / 50 56 / 54 / 52 57 / 54 / 52 62 / 59 / 56 63 / 59 / 56 65 / 61 / 59 69 / 67 / 63
Liquid mm 6.35 6.35 6.35 6.35 6.35 6.35 9.52
Piping Dimensions Body WxHxD mm 840 x 204 x 840 840 x 204 x 840 840 x 204 x 840 840 x 246 x 840 840 x 288 x 840 840 x 288 x 840 840 x 288 x 840
Gas mm 12.7 12.7 12.7 12.7 12.7 12.7 15.88
Connection Net Weight kg 20.8 20.8 20.8 23.5 25.6 25.6 26.5
Drain I.D mm 25.0 25.0 25.0 25.0 25.0 25.0 25.0
Model PT-UQC PT-UQC PT-UQC PT-UQC PT-UQC PT-UQC PT-UQC Liquid mm 9.52 9.52 9.52 9.52 9.52 9.52 9.52
Morning Fog Morning Fog Morning Fog Morning Fog Morning Fog Morning Fog Morning Fog Piping
Decoration Color (RAL Code) Gas mm 15.88 15.88 15.88 15.88 15.88 15.88 15.88
(RAL 120-4) (RAL 120-4) (RAL 120-4) (RAL 120-4) (RAL 120-4) (RAL 120-4) (RAL 120-4) Connection
Panel 1 Drain I.D mm 25.0 25.0 25.0 25.0 25.0 25.0 25.0
Dimensions WxHxD mm 700 x 22 x 700 700 x 22 x 700 700 x 22 x 700 700 x 22 x 700 700 x 22 x 700 700 x 22 x 700 700 x 22 x 700
Weight kg 3.0 3.0 3.0 3.0 3.0 3.0 3.0 Model PT-UMC1 PT-UMC1 PT-UMC1 PT-UMC1 PT-UMC1 PT-UMC1 PT-UMC1
Model PT-QCHW0 PT-QCHW0 PT-QCHW0 PT-QCHW0 PT-QCHW0 PT-QCHW0 PT-QCHW0 Morning Fog Morning Fog Morning Fog Morning Fog Morning Fog Morning Fog Morning Fog
Decoration Color (RAL Code)
Morning Fog Morning Fog Morning Fog Morning Fog Morning Fog Morning Fog Morning Fog (RAL 120-4) (RAL 120-4) (RAL 120-4) (RAL 120-4) (RAL 120-4) (RAL 120-4) (RAL 120-4)
Decoration Color (RAL Code) Panel
(RAL 120-4) (RAL 120-4) (RAL 120-4) (RAL 120-4) (RAL 120-4) (RAL 120-4) (RAL 120-4) Dimensions WxHxD mm 950 x 25 x 950 950 x 25 x 950 950 x 25 x 950 950 x 25 x 950 950 x 25 x 950 950 x 25 x 950 950 x 25 x 950
Panel 2
Dimensions WxHxD mm 620 x 35 x 620 620 x 35 x 620 620 x 35 x 620 620 x 35 x 620 620 x 35 x 620 620 x 35 x 620 620 x 35 x 620
Weight kg 5.6 5.6 5.6 5.6 5.6 5.6 5.6
Weight kg 3.1 3.1 3.1 3.1 3.1 3.1 3.1
* This product contains Fluorinated Greenhouse Gases. (R410A) * This product contains Fluorinated Greenhouse Gases. (R410A)
1) Nom. : Performance tested under EN14511 2) Rated : Max power input allowed for fan motor 1) Nom. : Performance tested under EN14511 2) Rated : Max power input allowed for fan motor
Note : 1. Capacities are based on the following conditions Note : 1. Capacities are based on the following conditions
- Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero
- Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero
2. Due to our policy of innovation some specifications may be changed without notification 3. I.D : ‘ Internal Diameter ’ 2. Due to our policy of innovation some specifications may be changed without notification 3. I.D : ‘ Internal Diameter ’

Accessories Accessories
Model ARNU05GTRC4 ARNU07GTRC4 ARNU09GTRC4 ARNU12GTRC4 ARNU15GTQC4 ARNU18GTQC4 ARNU21GTQC4 Model ARNU24GTPC4 ARNU28GTPC4 ARNU30GTPC4 ARNU36GTNC4 ARNU42GTMC4 ARNU48GTMC4 ARNU54GTMC4
Simple (1 Contact Point with Case) PDRYCB000 Simple (1 Contact Point with Case) PDRYCB000
Dry 2 Contact Point PDRYCB400 Dry 2 Contact Point PDRYCB400
Contact For Thermostat (On-Off / Mode / Fan Speed) PDRYCB300 Contact For Thermostat (On-Off / Mode / Fan Speed) PDRYCB300
Modbus Communication PDRYCB500 Modbus Communication PDRYCB500
Front Panel PT-QCHW0 / PT-UQC Front Panel PT-UMC1
Ventilation Kit PTVK430 Ventilation Kit PTEGM0
EEV Kit for MULTI V Indoor PRGK024A0 - EEV Kit for MULTI V Indoor PTVK410 / PTVK420 / PTVK430

Wired Remote Controller Wired Remote Controller


Wireless Remote Controller Wireless Remote Controller
Premium Standard III Standard II Simple Simple for Hotel Premium Standard III Standard II Simple Simple for Hotel

PREMTA000 PREMTB100 PREMTBB10 PREMTB001 PREMTBB01 PQRCVCL0Q (Black) PQRCHCA0Q (Black) PQWRHQ0FDB PREMTA000 PREMTB100 PREMTBB10 PREMTB001 PREMTBB01 PQRCVCL0Q (Black) PQRCHCA0Q (Black) PQWRHQ0FDB
(White) (Black) (White) (Black) PQRCVCL0QW (White) PQRCHCA0QW (White) (White) (Black) (White) (Black) PQRCVCL0QW (White) PQRCHCA0QW (White)

182 183
INDOOR UNIT
INDOOR UNIT SPECIFICATION INDOOR UNIT SPECIFICATION

2 Way CASSETTE 1 Way CASSETTE


ARNU09GTSC4 / ARNU12GTSC4 ARNU07GTUC4 / ARNU09GTUC4 / ARNU12GTUC4
ARNU18GTSC4 / ARNU24GTSC4 ARNU18GTTC4 / ARNU24GTTC4

Model Independent Unit ARNU09GTSC4 ARNU12GTSC4 ARNU18GTSC4 ARNU24GTSC4 Model Independent Unit ARNU07GTUC4 ARNU09GTUC4 ARNU12GTUC4 ARNU18GTTC4 ARNU24GTTC4
Cooling Nom kW 2.8 3.6 5.6 7.1 Cooling Nom kW 2.2 2.8 3.6 5.6 7.1
Capacity Capacity
Heating Nom kW 3.2 4.0 6.3 8.0 Heating Nom kW 2.5 3.2 4.0 6.3 7.1
Cooling / Heating Nom 1) W 28 30 34 40 Cooling / Heating Nom 1) W 20 22 24 38 51
Power Input Power Input
Cooling / Heating Rated 2) W 70 70 70 70 Cooling / Heating Rated 2) W 40 40 40 70 70
1 / 220~240 / 50 1 / 220~240 / 50 1 / 220~240 / 50 1 / 220~240 / 50 1 / 220~240 / 50
1 / 220~240 / 50 1 / 220~240 / 50 1 / 220~240 / 50 1 / 220~240 / 50 Power Supply Ø / V / Hz
Power Supply Ø / V / Hz 1 / 220 / 60 1 / 220 / 60 1 / 220 / 60 1 / 220 / 60 1 / 220 / 60
1 / 220 / 60 1 / 220 / 60 1 / 220 / 60 1 / 220 / 60
Cooling H/M/L m3/min 8.2 / 7.3 / 6.4 9.2 / 8.6 / 8.2 10.0 / 9.2 / 8.2 13.3 / 12.1 / 10.9 14.6 / 13.3 / 11.5
Cooling H/M/L m3/min 10.8 / 9.8 / 9.1 11.1 / 10.3 / 9.4 11.8 / 10.8 / 9.8 14.5 / 12.4 / 10.3 Airflow Rate
Airflow Rate Heating H/M/L m3/min 8.2 / 7.3 / 6.4 9.2 / 8.6 / 8.2 10.0 / 9.2 / 8.2 13.3 / 12.1 / 10.9 14.6 / 13.3 / 11.5
Heating H/M/L m3/min 10.8 / 9.8 / 9.1 11.1 / 10.3 / 9.4 11.8 / 10.8 / 9.8 14.5 / 12.4 / 10.3
Sound Pressure H/M/L dBA 32 / 29 / 25 35 / 34 / 32 38 / 35 / 32 40 / 37 / 35 43 / 40 / 36
Sound Pressure H/M/L dBA 33 / 31 / 30 34 / 32 / 31 35 / 33 / 31 40 / 37 / 33
Sound Power H/M/L dBA 50 / 47 / 43 53 / 52 / 50 57 / 53 / 50 59 / 56 / 54 62 / 59 / 55
Sound Power H/M/L dBA 42 / 40 / 38 43 / 41 / 39 44 / 43 / 41 49 / 46 / 41
Dimensions Body W x H x D mm 860 x 132 x 450 860 x 132 x 450 860 x 132 x 450 1,180 x 132 x 450 1,180 x 132 x 450
Dimensions Body W x H x D mm 830 × 225 × 600 830 × 225 × 600 830 × 225 × 600 830 × 225 × 600
Net Weight kg 13.6 13.6 13.6 15.6 15.6
Net Weight kg 18.1 18.1 18.1 18.1
Liquid mm 6.35 6.35 6.35 6.35 9.52
Liquid mm 6.35 6.35 6.35 9.52 Piping Connection Gas mm 12.7 12.7 12.7 12.7 15.88
Piping Connection Gas mm 12.7 12.7 12.7 15.88 Drain I.D mm 25.0 25.0 25.0 25.0 25.0
Drain I.D mm 25.0 25.0 25.0 25.0 PT-UUC (Grill) / PT-UUC (Grill) / PT-UUC (Grill) / PT-UTC (Grill) / PT-UTC (Grill) /
Model
Model PT-USC PT-USC PT-USC PT-USC PT-UUD (Panel) PT-UUD (Panel) PT-UUD (Panel) PT-UTD (Panel) PT-UTD (Panel)
Decoration Color (RAL Code) Noble White (RAL 110-1) Noble White (RAL 110-1) Noble White (RAL 110-1) Noble White (RAL 110-1) Noble White (RAL 110-1)
Decoration Color Morning Fog (RAL 120-4) Morning Fog (RAL 120-4) Morning Fog (RAL 120-4) Morning Fog (RAL 120-4) Panel
Panel Dimensions W x H x D mm 1,100 x 34 x 500 1,100 x 34 x 500 1,100 x 34 x 500 1,420 x 34 x 500 1,420 x 34 x 500
Dimensions W x H x D mm 1,100 x 33 x 690 1,100 x 33 x 690 1,100 x 33 x 690 1,100 x 33 x 690
Weight kg 4.6 4.6 4.6 5.5 5.5
Weight kg 4.65 4.65 4.65 4.65
* This product contains Fluorinated Greenhouse Gases. (R410A) * This product contains Fluorinated Greenhouse Gases. (R410A)
1) Nom. : Performance tested under EN14511 1) Nom. : Performance tested under EN14511
2) Rated : Max power input allowed for fan motor 2) Rated : Max power input allowed for fan motor
Note : 1. Capacities are based on the following conditions Note : 1. Capacities are based on the following conditions
- Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero
- Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero
2. Due to our policy of innovation some specifications may be changed without notification 2. Due to our policy of innovation some specifications may be changed without notification
3. I.D : ‘ Internal Diameter ’ 3. I.D : ‘ Internal Diameter ’

Accessories Accessories
Model ARNU09GTSC4 ARNU12GTSC4 ARNU18GTSC4 ARNU24GTSC4 Model ARNU07GTUC4 ARNU09GTUC4 ARNU12GTUC4 ARNU18GTTC4 ARNU24GTTC4
Simple (1 Contact Point with Case) PDRYCB000 Simple (1 Contact Point with Case) PDRYCB000

Dry 2 Contact Point PDRYCB400 Dry 2 Contact Point PDRYCB400


Contact For Thermostat (On-Off / Mode / Fan Speed) PDRYCB300 Contact For Thermostat (On-Off / Mode / Fan Speed) PDRYCB300
Modbus Communication PDRYCB500 Modbus Communication PDRYCB500
Front Panel PT-USC Front Panel PT-UUC (Grill) / PT-UUD (Panel) PT-UTC (Grill) / PT-UTD (Panel)
EEV Kit for MULTI V Indoor PRGK024A0 - EEV Kit for MULTI V Indoor PRGK024A0 -

Wired Remote Controller Wired Remote Controller


Wireless Remote Controller Wireless Remote Controller
Premium Standard III Standard II Simple Simple for Hotel Premium Standard III Standard II Simple Simple for Hotel

PREMTA000 PREMTB100 PREMTBB10 PREMTB001 PREMTBB01 PQRCVCL0Q (Black) PQRCHCA0Q (Black) PQWRHQ0FDB PREMTA000 PREMTB100 PREMTBB10 PREMTB001 PREMTBB01 PQRCVCL0Q (Black) PQRCHCA0Q (Black) PQWRHQ0FDB
(White) (Black) (White) (Black) PQRCVCL0QW (White) PQRCHCA0QW (White) (White) (Black) (White) (Black) PQRCVCL0QW (White) PQRCHCA0QW (White)

184 185
INDOOR UNIT
INDOOR UNIT KEY FEATURES

CEILING CONCEALED DUCT

Operation for Multiple Rooms Minimized Height


Using a spiral duct (embedded or flexible type) and stream chamber, it is New mid-static ducts provide ideal solution for installation in limited space.
possible to operate cooling / heating for several rooms simultaneously.

270mm

8 / 10kW 12.5kW
380
mm
298
mm
E.S.P. (External Static Pressure) Control
E.S.P. control function can make air volume controlled easily with remote controller. The BLDC motor can control fan speed and air 270 270
volume regardless of the external static pressure. No additional accessories are necessary to control air flow. mm mm

Conventional e Conventional e
E.S.P. Control E.S.P. Control

Flexible Installation (Low Static Duct Only)


The new low static duct allows the air intake at the rear or bottom under installation condition.
Comfort Cooling / Heating Comfort Cooling / Heating
New Low Static Duct Conventional
Air intake at the rear or bottom Air intake at the only rear

Two Thermistors Control


The indoor temperature can be checked using the thermistors in the
remote controller as well as from the indoor unit. There may be a significant
Indoor Unit Thermistor
difference between ceiling and floor air temperature. Two thermistors can
optimise indoor air temperature for a more comfortable environment.

Compares temperatures sensed from different positions, and automatically selects the optimum temperature
for users. Remote Controller Thermistor

186 187
INDOOR UNIT
INDOOR UNIT SPECIFICATION

HIGH STATIC
ARNU07GBHA4 / ARNU09GBHA4 / ARNU12GBHA4 ARNU36GBGA4 / ARNU42GBGA4 / ARNU48GBGA4
ARNU15GBHA4 / ARNU18GBHA4 / ARNU24GBHA4 ARNU54GBRA4 / ARNU60GB7A4 / ARNU76GB8A4 / ARNU96GB8A4

Model Independent Unit ARNU07GBHA4 ARNU09GBHA4 ARNU12GBHA4 ARNU15GBHA4 ARNU18GBHA4 ARNU24GBHA4 Model Independent Unit ARNU36GBGA4 ARNU42GBGA4 ARNU48GBGA4 ARNU54GBRA4 ARNU60GB7A4 ARNU76GB8A4 ARNU96GB8A4
Cooling Nom kW 2.2 2.8 3.6 4.5 5.6 7.1 Cooling Nom kW 10.6 12.3 14.1 15.8 17.5 22.4 28.0
Capacity Capacity
Heating Nom kW 2.5 3.2 4.0 5.0 6.3 8.0 Heating Nom kW 11.9 13.8 15.9 18.0 19.7 25.2 31.5
Cooling Nom W 150.0 150.0 150.0 150.0 150.0 150.0 Cooling Nom W 350.0 350.0 450 450.0 600 800.0 800.0
Power Input Power Input
Heating Nom W 150.0 150.0 150.0 150.0 150.0 150.0 Heating Nom W 350.0 350.0 450 450.0 600 800.0 800.0
Power Supply ø/V/Hz 1 / 220 ~240 / 50, 60 1 / 220 ~240 / 50, 60 1 / 220 ~240 / 50, 60 1 / 220 ~240 / 50, 60 1 / 220 ~240 / 50, 60 1 / 220 ~240 / 50, 60 Power Supply ø/V/Hz 1 / 220 ~240 / 50, 60 1 / 220 ~240 / 50, 60 1 / 220 ~240 / 50, 60 1 / 220 ~240 / 50, 60 1 / 220 ~240 / 50, 60 1 / 220 ~240 / 50, 60 1 / 220 ~240 / 50, 60
Airflow Rate Cooling H/M/L m3/min 6.5 / 5.8 / 5.4 8.1 / 6.5 / 5.8 9.6 / 8.1 / 6.5 11.3 / 9.6 / 6.5 13.0 / 11.3 / 9.6 16.0 / 14.4 / 13.0 Airflow Rate Cooling H/M/L m3/min 32.3 / 29.0 / 25.3 34.5 / 32.3 / 30.7 34.6 / 31.8 / 27.9 51.0 / 44.8 / 40.6 51.6 / 48.5 / 44.3 64.0 / 50.0 / 50.0 76.0 / 64.0 / 64.0
(High mode) Heating H/M/L m3/min 6.5 / 5.8 / 5.4 8.1 / 6.5 / 5.8 9.6 / 8.1 / 6.5 11.3 / 9.6 / 6.5 13.0 / 11.3 / 9.6 16.0 / 14.4 / 13.0 (High mode) Heating H/M/L m3/min 32.3 / 29.0 / 25.3 34.5 / 32.3 / 30.7 34.6 / 31.8 / 27.9 51.0 / 44.8 / 40.6 51.6 / 48.5 / 44.3 64.0 / 50.0 / 50.0 76.0 / 64.0 / 64.0
Sound Pressure H/M/L dBA 34 / 33 / 32 36 / 35 / 33 37 / 35 / 34 39 / 37 / 34 40 / 38 / 37 42 / 41 / 40 Sound Pressure H/M/L dBA 44 / 43 / 42 45 / 44 / 44 45 / 43 / 42 46 / 45 / 43 48 / 46 / 45 50 / 48 / 48 52 / 50 / 50
Sound Power H/M/L dBA 54 / 53 / 52 55 / 54 / 53 57 / 55 / 54 59 / 57 / 54 60 / 58 / 57 62 / 61 / 60 Sound Power H/M/L dBA 62 / 61 / 60 64 / 62 / 62 64 / 62 / 61 65 / 62 / 60 68 / 66 / 65 70 / 68 / 68 72 / 70 / 70
Dimensions Body WxDxH mm 882 x 260 x 450 882 x 260 x 450 882 x 260 x 450 882 x 260 x 450 882 x 260 x 450 882 x 260 x 450 Dimensions Body WxDxH mm 1,182 x 298 x 450 1,182 x 298 x 450 1,182 x 298 x 450 1,230 x 380 x 590 1,320 × 400 × 534 1,562 x 460 x 688 1,562 x 460 x 688
Net Weight kg(lbs) 26.0 26.0 26.0 26.0 26.5 26.5 Net Weight kg(lbs) 38.0 38.0 38 51.0 55 87.0 87.0
Liquid mm(inch) Ø6.35 Ø6.35 Ø6.35 Ø6.35 Ø6.35 Ø9.52 Liquid mm(inch) Ø9.52 Ø9.52 Ø9.52 Ø9.52 Ø9.52 Ø9.52 Ø9.52
Piping Connection Gas mm(inch) Ø12.7 Ø12.7 Ø12.7 Ø12.7 Ø12.7 Ø15.88 Piping Connection Gas mm(inch) Ø15.88 Ø15.88 Ø15.88 Ø15.88 Ø19.05 Ø19.05 Ø22.2
Drain I.D. mm(inch) 25 25 25 25 25 25 Drain I.D. mm(inch) 25 25 25 25 25 25 25
Fan motor output x Number W 154 x 1 154 x 1 154 x 1 154 x 1 154 x 1 154 x 1 Fan motor output x Number W 350 x 1 350 x 1 350 185 x 2 195 × 2 375 x 2 375 x 2

* This product contains Fluorinated Greenhouse Gases.(R410A) * This product contains Fluorinated Greenhouse Gases.(R410A)
Note : Note :
1. Capacities are based on the following conditions 1. Capacities are based on the following conditions
- Cooling : Indoor temp. 27°C(80.6°F)DB, 19°C(66.2°F)WB / Outdoor temp. 35°C(95°F)DB, 24°C(75.2°F)WB / Interconnecting piping length 7.5m / Level difference of zero - Cooling : Indoor temp. 27°C(80.6°F)DB, 19°C(66.2°F)WB / Outdoor temp. 35°C(95°F)DB, 24°C(75.2°F)WB / Interconnecting piping length 7.5m / Level difference of zero
- Heating - Indoor temp. 20°C(68°F)DB, 15°C(59°F)WB / Outdoor temp. 7°C(44.6°F)DB, 6°C(42.8°F)WB / Interconnecting piping length 7.5m / Level difference of zero - Heating - Indoor temp. 20°C(68°F)DB, 15°C(59°F)WB / Outdoor temp. 7°C(44.6°F)DB, 6°C(42.8°F)WB / Interconnecting piping length 7.5m / Level difference of zero
2. Due to our policy of innovation some specifications may be changed without notification 2. Due to our policy of innovation some specifications may be changed without notification
3. BH : The Sound Pressure test condition is based on 50 Pa (Static Pressue) as standard. 3. BH : The Sound Pressure test condition is based on 50 Pa (Static Pressue) as standard.
4. I.D - ‘Internal Diameter’ 4. I.D - ‘Internal Diameter’

Accessories Accessories
Model ARNU07GBHA4 ARNU09GBHA4 ARNU12GBHA4 ARNU15GBHA4 ARNU18GBHA4 ARNU24GBHA4 Model ARNU36GBGA4 ARNU42GBGA4 ARNU48GBGA4 ARNU54GBRA4 ARNU60GB7A4 ARNU76GB8A4 ARNU96GB8A4
Simple (1 Contact point with case) PDRYCB000 Simple (1 Contact point with case) PDRYCB000
2 Contact point PDRYCB400 2 Contact point PDRYCB400
Dry Contact Dry Contact
For Thermostat (On-off / Mode / Fan speed) PDRYCB300 For Thermostat (On-off / Mode / Fan speed) PDRYCB300
Modbus Communication PDRYCB500 Modbus Communication PDRYCB500

Wired Remote Controller Wired Remote Wired Remote Controller Wired Remote
Premium Standard II Simple Simple for Hotel Controller Premium Standard II Simple Simple for Hotel Controller

PREMTA000 PREMTB001 (White) PREMTBBO1 (Black) PQRCVCL0Q (Black) PQRCHCA0Q(Black) PQWRHQ0FDB PREMTA000 PREMTB001 (White) PREMTBBO1 (Black) PQRCVCL0Q (Black) PQRCHCA0Q(Black) PQWRHQ0FDB
PQRCVCL0QW (White) PQRCHCA0QW(White) PQRCVCL0QW (White) PQRCHCA0QW(White)

188 189
VENTILATION
SOLUTION
ERV
VENTILATION
VENTILATION SOLUTION KEY FEATURES

SOLUTION
ERV

High Efficiency Heat Exchanger Exhaust Air Supply Air Bypass Ventilation
Efficiency and comfort is ensured through the high- LG ERV automatically switches the ventilation mode (Enthalpy Heat Exchange Mode / Bypass Mode) according to
efficiency energy recovery central core which recovers the indoor / outdoor temperature.
energy from the indoor air and transfers it to the fresh
incoming air without mixing airstream. Enthalpy Heat Exchange Mode (Summer / Winter) Bypass Mode (Seasonal Change)
Damper Damper
Outdoor Air Air Filter Indoor Air

Interlocking with Air Conditioning System


- LG ERV can be interlocked with air conditioners
and controlled individually.
- This function can be operated when the system is Cooling / Heating Mode
Set Temperature
connected with a remote control.

Flexibility of Installation
It’s possible to install upside down when you need only one inspection hole.

Normal installation of 2 units Reverse installation of 1 unit (Left unit)


Compulsory Exhausting System
The exhausting system using high static and sirocco fan removes contaminants effectively from indoor air. Supply
and exhaust air flows are completely separated in the total heat exchanger, LG ERV can filter out the impurities
before supplying outdoor air and make indoor air fresh and healthy.

Outdoors Indoors
Damper

Exhaust Air Return Air


Exhaust Air Supply Air

Inspection chamber
Outdoor Air Supply Air Top Low
Outdoor Air Return Air

Total Heat
Exchanger
Low Top

212 213
VENTILATION
VENTILATION SOLUTION KEY FEATURES

SOLUTION
ERV

Easy Cleaning and Filter Change Fast Ventilation Mode


It is easy and convenient to change and clean the filter. Fast ventilation mode prevents the spread of contaminants under negative indoor pressure, and makes indoor air
fresh and comfortable quickly.

Only Exhausting Fast Ventilation Mode

Exhaust
Exhausting Fan
and Supplying
Simultaneously Supply
Fan

ERV Unit Remove Side Panel

Exhausting operation causes negative indoor air


pressure, and cannot fully ventilate.

CO2 Concentration Control


Using CO2 sensor, LG ERV controls exhaust air flow automatically to keep indoor air fresh under settled CO2 concentration.

Change Filter Remove Heat Exchanger

CASE #1 CASE #2

External Static Pressure Control CO Sensor


2
New
Standard
Wired
Standard
Wired CO2 Sensor
(AHCS 100H0) Remote Remote (PES-C0RV0)
The high static pressure fan can control the air volume Air
Volume (Internal Type) Controller Controller (External Type)
depending on the length of the duct. It is also easy to
control the pressure level by using the remote controller CO2
H (ppm)
for a more flexible duct installation and easier testing.
M
L
Windows Windows Windows Windows
Closed Open Closed Open
H 2,500
M
L

External Static Pressure (mmAq) 1,000

0
ERV with CO2 Concentration Control
Time (min)

214 215
VENTILATION
VENTILATION SOLUTION KEY FEATURES

SOLUTION
ERV

New Easy Controller Night Time Cooling


New wired remote controller is easy for usage. Discharge the indoor heat in the summer night and supply cool outdoor air to indoors. so it can save energy.

Outdoor ERV is turned on automatically ERV is turned off


temperature at night is when the outside is when the inside temperature is
getting low. cooler than inside. lower than set temperature.
Convenient!
• Flexible display
- Dual display with air conditioner.
- Zoom selected directory to increase legibility.

Easy! Visible!
• Navigation buttons, easy to use. • Indoor CO2 level
• Easy installation setting • Alarm for filter change / Remained time to change filters
ERV makes inside cooler with bypass mode
Outside Temp. like nature ventilation.
Set Temp.

Inside Temp.

Air Purifying System (3 Steps) 2%


Energy Saving
(Annually)
LG ERV can effectively remove the various harmful substances, such as micro dust and viruses.
Possible selection of the high efficiency filter(F7) for micro dust removed.

Time
Step 2: Heat Exchanger Night Morning

Anti virus coating, block the breeding of harmful viruses.

* This function is operated with ‘Night Time Free Cooling’ on remote controller. (with MULTI V only)
** Energy saving ratio Can vary with condition.
*** Available only with Standard III

• Test Condition
- Office (49,000 ft 2) / Occupancy : 30 / Area : London, UK
- ERV (1 000 CMH) + MULTI V 4 (12 HP) Unit Combination
- Other conditions are subject to BREEAM.
(Building Research Establishment's Environmental Assessment Method)

Step 1: Basic Filter


Installed front and behind of heat exchanger Step 3: High Efficiency Filter (F7)
F7 filter blocks 80 ~ 90% of dust sized 0.4μm. (EN 779 : 2012)
Installed in front of heat exchanger. (option)

216 217
VENTILATION
VENTILATION SOLUTION SPECIFICATION

SOLUTION
ERV
LZ-H025GBA4 / LZ-H035GBA4 / LZ-H050GBA4 LZ-H080GBA4 / LZ-H100GBA4
LZ-H150GBA4 / LZ-H200GBA4

Model LZ-H025GBA4 LZ-H035GBA4 LZ-H050GBA4 Model LZ-H080GBA4 LZ-H100GBA4 LZ-H150GBA4 LZ-H200GBA4


Nominal Capacity CMH (CFM) 250 (147) 350 (206) 500 (294) Nominal Capacity CMH (CFM) 800 (471) 1,000 (589) 1,500 (883) 2,000 (1,177)
Power Supply Ø / V / Hz 1 / 220~240 / 50, 60 Power Supply Ø / V / Hz 1 / 220~240 / 50, 60
Step - SUPER-HIGH / HIGH / LOW Step - SUPER-HIGH / HIGH / LOW
Current SH / H / L Amps 0.70 / 0.60 / 0.42 1.10 / 0.95 / 0.60 1.92 / 1.58 / 0.79 Current SH / H / L Amps 2.77 / 2.16 / 1.44 3.41 / 2.90 / 1.76 5.60 / 5.40 / 2.90 6.80 / 5.90 / 3.60
Power Input SH / H / L W 97 / 78 / 52 180 / 163 / 88 240 / 220 / 90 Power Input SH / H / L W 390 / 280 / 187 480 / 385 / 210 780 / 540 / 377 960 / 770 / 420
250 / 250 / 150 350 / 350 / 210 500 / 500 / 320 800 / 800 / 660 1,000 / 1,000 / 800 1,500 / 1,500 / 1,200 2,000 / 2,000 / 1,600
Air Flow SH / H / L CMH (CFM) Air Flow SH / H / L CMH (CFM)
(147 / 147 / 88) (206 / 206 / 123) (294 / 294 / 124) (471 / 471 / 388) (589 / 589 / 471) (883 / 883 / 706) (1,177 / 1,177 / 942)
ERV Mode 100 / 70 / 50 150 / 130 / 100 150 / 100 / 50 ERV Mode 200 / 110 / 60 160 / 90 / 50 200 / 110 / 60 160 / 90 / 50
External Static Pressure SH / H / L Pa (inWTR) External Static Pressure SH / H / L Pa (inWTR)
(0.40 / 0.28 / 0.20) (0.60 / 0.52 / 0.40) (0.60 / 0.40 / 0.20) (0.80 / 0.44 / 0.24) (0.64 / 0.36 / 0.20) (0.80 / 0.44 / 0.24) (0.64 / 0.36 / 0.20)
Temperature Exchange Efficiency SH / H / L % 80 / 80 / 83 75 / 75 / 77 78 / 78 / 79 Temperature Exchange Efficiency SH / H / L % 79 / 79 / 82 77 / 77 / 78 79 / 79 / 82 77 / 77 / 78
Heating (SH / H / L) % 70 / 70 / 72 68 / 68 / 70 73 / 73 / 75 Heating (SH / H / L) % 72 / 72 / 74 70 / 70 / 72 72 / 72 / 74 70 / 70 / 72
Enthalpy Exchange Efficiency Enthalpy Exchange Efficiency
Cooling (SH / H / L) % 66 / 66 / 68 63 / 63 / 65 66 / 66 / 69 Cooling (SH / H / L) % 63 / 63 / 66 59 / 59 / 63 63 / 63 / 66 59 / 59 / 63
Noise Level (Sound Level, 1.5m) SH / H / L dB (A) 29 / 28 / 24 32 / 30 / 27 34 / 32 / 25 Noise Level (Sound Level, 1.5m) SH / H / L dB (A) 40 / 37 / 31 41 / 38 / 32 43 / 40 / 34 44 / 41 / 35
Step - SUPER-HIGH / HIGH / LOW Step - SUPER-HIGH / HIGH / LOW
Current SH / H / L Amps 0.70 / 0.60 / 0.42 1.10 / 0.95 / 0.60 1.92 / 1.58 / 0.79 Current SH / H / L Amps 2.77 / 2.16 / 1.44 3.41 / 2.90 / 1.76 5.60 / 5.40 / 2.90 6.80 / 5.90 / 3.60
Power Input SH / H / L W 97 / 78 / 52 180 / 163 / 88 240 / 220 / 90 Power Input SH / H / L W 390 / 280 / 187 480 / 385 / 210 780 / 540 / 377 960 / 770 / 420
250 / 250 / 150 350 / 350 / 210 500 / 500 / 320 800 / 800 / 660 1,000 / 1,000 / 800 1,500 / 1,500 / 1,200 2,000 / 2,000 / 1,600
Bypass Mode Air Flow SH / H / L CMH (CFM) Bypass Mode Air Flow SH / H / L CMH (CFM)
(147 / 147 / 88) (206 / 206 / 123) (294 / 294 / 124) (471 / 471 / 388) (589 / 589 / 471) (883 / 883 / 706) (1,177 / 1,177 / 942)
100 / 70 / 50 150 / 130 / 100 150 / 100 / 50 200 / 110 / 60 160 / 90 / 50 200 / 110 / 60 160 / 90 / 50
External Static Pressure SH / H / L Pa (inWTR) External Static Pressure SH / H / L Pa (inWTR)
(0.40 / 0.28 / 0.20) (0.60 / 0.52 / 0.40) (0.60 / 0.40 / 0.20) (0.80 / 0.44 / 0.24) (0.64 / 0.36 / 0.20) (0.80 / 0.44 / 0.24) (0.64 / 0.36 / 0.20)
Noise Level (Sound Level, 1.5m) SH / H / L dB (A) 29 / 29 / 25 32 / 30 / 27 35 / 33 / 25 Noise Level (Sound Level, 1.5m) SH / H / L dB (A) 41 / 38 / 32 41 / 39 / 33 44 / 41 / 35 44 / 42 / 36
Heat Exchanger Type - Air to air cross flow heat exchange Heat Exchanger Type - Air to air cross flow heat exchange
Net Weight kg 44 44 44 Net Weight kg 62 140
Dimension WxHxD mm 988 x 273 x 1,014 988 x 273 x 1,014 988 x 273 x 1,014 Dimension WxHxD mm 1,062 x 365 x 1,140 1,313 x 738 x 1,140
Qty EA 4 Qty EA 4 4+2
Duct work* Duct work*
Size (Ø) mm Ø200 Size (Ø) mm Ø250 Ø250 + Ø350
Qty EA 1 Qty EA 1 2
Supply Air Fan Supply Air Fan
Type - Direct-Drive (Sirocco Fan) Type - Direct-Drive (Sirocco Fan)
Qty EA 1 Qty EA 1 2
Exhaust Air Fan Exhaust Air Fan
Type - Direct-Drive (Sirocco Fan) Type - Direct-Drive (Sirocco Fan)
Qty EA 2 2 Qty EA 2 4
Filters (Default) Type - Cleanable fibrous fleeces Filters (Default) Type - Cleanable fibrous fleeces
Size (W x H x D) mm 855 x 10 x 160 855 x 6 x 230 Size (W x H x D) mm 1,056 x 6 x 212.5
Model - AHFT035H0 AHFT050H0 Model - AHFT100H0
Qty EA 2 2 Qty EA 2 4
Filters (Optional) Filters (Optional)
Type - F7 F7 Type - F7
Size (W x H x D) mm 423.5 x 132 x 25 425 x 194 x 25 Size (W x H x D) mm 520 x 192 x 25
Dry Contact PDRYCB000 Dry Contact PDRYCB000

Note : 1. ERV mode : Total Heat Recovery Ventilation mode Note : 1. ERV mode : Total Heat Recovery Ventilation mode
2. * : Refer to dimensional drawings. 2. * : Refer to dimensional drawings.
3. Noise level : 3. Noise level :
- The operating conditions are assumed to be standard - The operating conditions are assumed to be standard
- Sound measured at 1.5m below the center the body. - Sound measured at 1.5m below the center the body.
- Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed. - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.
- The sound level at the air discharge port is about 8 dB(A) higher than the unit's operating sound. - The sound level at the air discharge port is about 8 dB(A) higher than the unit's operating sound.
4. Temperature and Enthalpy Exchange Efficiency at cooling 4. Temperature and Enthalpy Exchange Efficiency at cooling
Indoor Temperature : 26.5°C DB, 64.5% RH, Outdoor Temperature : 34.5°C DB, 75% RH Indoor Temperature : 26.5°C DB, 64.5% RH, Outdoor Temperature : 34.5°C DB, 75% RH
5. Temperature and Enthalpy Exchange Efficiency at heating 5. Temperature and Enthalpy Exchange Efficiency at heating
Indoor Temperature : 20.5°C DB, 59.5% RH, Outdoor Temperature : 5°C DB, 65% RH Indoor Temperature : 20.5°C DB, 59.5% RH, Outdoor Temperature : 5°C DB, 65% RH
6. Temperature Exchange efficiency is tested at heating condition. 6. Temperature Exchange efficiency is tested at heating condition.
7. F7 Filter is 2 pieces in 1 filter package 7. F7 Filter is 2 pieces in 1 filter package

Premium Standard III Standard II CO2 Sensor Premium Standard III Standard II CO2 Sensor

PREMTA000 PREMTA000
PREMTB100 PREMTBB10 PREMTBB01 PREMTB001 PES-C0RV0 AHCS100H0 PREMTB100 PREMTBB10 PREMTBB01 PREMTB001 PES-C0RV0 AHCS100H0
PREMTA000A PREMTA000A
(External Type) (Internal Type) (External Type) (Internal Type)
PREMTA000B PREMTA000B

218 219
VENTILATION
VENTILATION SOLUTION SPECIFICATION

SOLUTION
ERV

LZ-H025GBA4 Ventilation Efficiency


LZ-H100GBA4 Ventilation Efficiency

Exchange Efficiency (%)


200 90 90
External Static Pressure (Pa)

Exchange Efficiency (%)

External Static Pressure (Pa)


Super-High 500 Super-High
180 85 85
High High
160 Low 80 Low 80
400
140 75 75
120 70 70
300
100 65 65
80 60 60
200
60 55 55
40 50 Temperature Exchange Efficiency 50 Temperature Exchange Efficiency
Enthalpy Exchange Efficiency (Heating) 100 Enthalpy Exchange Efficiency (Heating)
20 45 45
Enthalpy Exchange Efficiency (Cooling) Enthalpy Exchange Efficiency (Cooling)
40 40
0 100 200 300 400 500 0 100 200 300 400 500 0 200 400 600 800 1,000 1,200 500 700 900 1,100 1,300
Air Volume (m3/h) Air Volume (m3/h) Air Volume (m3/h) Air Volume (m3/h)

LZ-H035GBA4 Ventilation Efficiency


90
LZ-H150GBA4 Ventilation Efficiency

Exchange Efficiency (%)


90
External Static Pressure (Pa)

Exchange Efficiency (%)

External Static Pressure (Pa)


Super-High 500 Super-High
400 High 85 85
High
Low 80 Low 80
350 400
75 75
300
70 70
250 300
65 65
200 60 60
200
150 55 55
100 50 Temperature Exchange Efficiency Temperature Exchange Efficiency
100 50
Enthalpy Exchange Efficiency (Heating) Enthalpy Exchange Efficiency (Heating)
50 45 45
Enthalpy Exchange Efficiency (Cooling) Enthalpy Exchange Efficiency (Cooling)
40 40
0 100 200 300 400 500 0 100 200 300 400 500 0 400 800 1,200 1,600 2,000 1,000 1,200 1,400 1.600 1,800 2,000 2,200
Air Volume (m3/h) Air Volume (m3/h) Air Volume (m3/h) Air Volume (m3/h)

LZ-H050GBA4 Ventilation Efficiency


LZ-H200GBA4 Ventilation Efficiency
External Static Pressure (Pa)

Exchange Efficiency (%)

90

Exchange Efficiency (%)


400 Super-High 90

External Static Pressure (Pa)


500 Super-High
High 85 85
High
Low 80 Low 80
300 400
75 75
70 70
300
200 65 65
60 60
200
55 55
100 Temperature Exchange Efficiency
50 50 Temperature Exchange Efficiency
Enthalpy Exchange Efficiency (Heating) 100
45 Enthalpy Exchange Efficiency (Heating)
Enthalpy Exchange Efficiency (Cooling) 45
Enthalpy Exchange Efficiency (Cooling)
40 40
0 100 200 300 400 500 600 700 800 0 100 200 300 400 500 600 700 800 0 500 1,000 1,500 2,000 2,500 1,000 1,200 1,400 1.600 1,800 2,000 2,200
Air Volume (m3/h) Air Volume (m3/h) Air Volume (m3/h) Air Volume (m3/h)

LZ-H080GBA4 Ventilation Efficiency


External Static Pressure (Pa)

Exchange Efficiency (%)

500 90
Super-High
High 85
400 Low 80
75
300 70
65
200 60
55
100 Temperature Exchange Efficiency
50
Enthalpy Exchange Efficiency (Heating)
45 Enthalpy Exchange Efficiency (Cooling)
40
0 200 400 600 800 1,000 1,200 500 600 700 800 900 1,000 1,100 1,200
Air Volume (m3/h) Air Volume (m3/h)

220 221
VENTILATION
VENTILATION SOLUTION KEY FEATURES VENTILATION SOLUTION SPECIFICATION

SOLUTION
ERV WITH DX COIL ERV WITH DX COIL
LZ-H050GXH4 / LZ-H080GXH4 / LZ-H100GXH4
LZ-H050GXN4 / LZ-H080GXN4 / LZ-H100GXN4

Providing Cool & Warm Fresh Air


During the summer, ERV DX can transform outdoor warm air into cool air for indoors, and it can prevent cold drafts
during the winter by supplying warm air.

Model LZ-H050GXH4 LZ-H080GXH4 LZ-H100GXH4 LZ-H050GXN4 LZ-H080GXN4 LZ-H100GXN4


Fresh Air Cooling 1) kW 4.93 7.46 9.12 4.93 7.46 9.12
Conditioning Load Heating 2) kW 6.73 9.80 11.72 6.73 9.80 11.72
Temperature
SH / H / L % 86 / 86 / 87 80 / 80 / 81 76 / 76 / 78 86 / 86 / 87 80 / 80 / 81 76 / 76 / 78
Exchange Efficiency
Enthalpy Exchange Cooling (SH / H / L) % 61 / 61 / 63 50 / 50 / 53 45 / 45 / 50 61 / 61 / 63 50 / 50 / 53 45 / 45 / 50
Cooling Heating Efficiency Heating (SH / H / L) % 76 / 76 / 77 67 / 67 / 69 64 / 64 / 66 76 / 76 / 77 67 / 67 / 69 64 / 64 / 66
Heat Exchange Mode (SH / H / L) CMH 500 / 500 / 440 800 / 800 / 640 1,000 / 1,000 / 820 500 / 500 / 440 800 / 800 / 640 1,000 / 1,000 / 820
Air Flow Rate
Bypass Mode (SH / H / L) CMH 500 / 500 / 440 800 / 800 / 640 1,000 / 1,000 / 820 500 / 500 / 440 800 / 800 / 640 1,000 / 1,000 / 820
Fan External Static Pressure (SH / H / L) Pa 160 / 120 / 100 140 / 90 / 70 110 / 70 / 60 180 / 150 / 110 170 / 120 / 80 150 / 100 / 70
System Natural Evaporating Type -
Humidifier Amount 3) kg/h 2.70 4.00 5.40 -
Pressure Feed Water Mpa 0.02 ~ 0.49 -
Heat Exchange Mode (SH / H / L) dB (A) 38 / 36 / 33 39 / 37 / 34 40 / 38 / 35 39 / 37 / 35 41 / 38 / 36 41 / 39 / 36
Sound Pressure
Bypass Mode (SH / H / L) dB (A) 39 / 37 / 34 40 / 38 / 35 40 / 38 / 35 39 / 37 / 35 41 / 38 / 36 41 / 39 / 36
Refrigerant R410A
Power Supply Ø / V / Hz 1 / 220~240 / 50, 60
Heat Exchange Mode (SH / H / L) kW 0.25 / 0.20 / 0.15 0.42 / 0.35 / 0.25 0.48 / 0.42 / 0.27 0.25 / 0.20 / 0.15 0.42 / 0.35 / 0.25 0.48 / 0.42 / 0.27
Total Air Conditioning Solution
Power Input
(Nominal) Bypass Mode (SH / H / L) kW 0.25 / 0.20 / 0.15 0.42 / 0.35 / 0.25 0.48 / 0.42 / 0.27 0.25 / 0.20 / 0.15 0.42 / 0.35 / 0.25 0.48 / 0.42 / 0.27
Nominal Running Heat Exchange Mode (SH / H / L) A 1.5 / 1.3 / 1.0 2.5 / 2.0 / 1.5 3.6 / 3.2 / 2.3 1.5 / 1.3 / 1.0 2.5 / 2.0 / 1.5 3.6 / 3.2 / 2.3
Current (RLA) Bypass Mode (SH / H / L) A 1.5 / 1.3 / 1.0 2.5 / 2.0 / 1.5 3.6 / 3.2 / 2.3 1.5 / 1.3 / 1.0 2.5 / 2.0 / 1.5 3.6 / 3.2 / 2.3
LG ERV DX can be used as a Total Air Conditioning Heat exchange DX Coil Humidification Dimensions WxHxD mm 1,667 x 365 x 1,140 1,667 x 365 x 1,140
Net Weight kg 105 98
Solution. It can control condition of incoming air with the Liquid mm Ø6.35 Ø6.35
DX coil and humidifier for making comfortable indoor Exhaust Supply Piping Connection
Gas mm Ø12.7 Ø12.7
Air Water mm Ø6.35 -
air. In the summer, LG ERV DX controls the air indoors by Air
Drain (Outer Diameter) mm Ø25.4 Ø25.4
cooling and dehumidifying incoming air. In winter, it can Connection Duct
mm Ø250 Ø250
Diameter
provide warm air by heating and humidifying the incoming Remote Controller Refer to the below Wired Remote Controller table
Outdoor Return
air. Air Air
Simple (1 Contact Point with Case) PDRYCB000
2 Contact Point PDRYCB400
Dry Contact For Thermostat
PDRYCB300
(On-Off / Mode / Fan Speed)
Modbus Communication PDRYCB500
Mode - AHFT100H0
Qty EA 2
Filters (Optional)
Interlocking with MULTI V Type
Size (W x H x D)
-
mm
F7
520 x 192 x 25

Note : 1) Cooling Capacity Test condition - Indoor temperature : 27°C DB, 19°C WB / Outdoor temperature : 35°C DB
LG ERV DX can be interlocked with MULTI V. 2) Heating Capacity Test condition - Indoor temperature : 20°C DB / Outdoor temperature : 7°C DB, 6°C WB
3) Humidifying capacity is based on the following conditions - Indoor temperature : 20°C DB, 15°C WB / Outdoor temperature : 7°C DB, 6°C WB
It can be controlled individually by a wired remote controller connected to MULTI V indoor units. * Cooling and heating capacities are based on the following conditions. - Fan is based on High and Super-high. The figures in the parenthesis indicate the heat reclaimed from
the heat recovery ventilator.
* The operating sound measured at the point 1.5 m below the center of the unit is converted to that measured at an anechoic chamber built in accordance with the
ERV DX KS B 6879 conditions.
Indoor Units
* The actual operating sound varies depending on the surrounding conditions (near running unit's sound, reflected sound and so on) and is normally higher than this value.
* Air flow rate can be changed over to low mode or high mode.
* The specifications, designs and information here are subject to change without notice.
* This product contains Fluorinated Greenhouse Gases. (R410A)
4) F7 Filter is 2 pieces in 1 filter package

Premium Standard III Standard II CO2 Sensor

Outdoor
PREMTA000 PREMTB100 PREMTBB10 PREMTBB01 PREMTB001 PES-C0RV0 AHCS100H0
(External Type) (Internal Type)

222 223
ACCESSORIES
INDIVIDUAL CONTROL CENTRALIZED CONTROL
MECHANICAL ACCESSORIES SYSTEM INTEGRATION DEVICE
OTHER INTEGRATION CONTROL SOLUTION PIPING ACCESSORIES
COMPATIBILITY TABLE
ACCESSORIES
CONTROL SOLUTION & ACCESSORIES

LG HVAC CONTROL LINE-UP

Individual Control Centralized Control Centralized Control Other Integration Device


Wired Remote Controller Wireless Remote Indoor Unit Indoor Unit Indoor Unit System Integration Device Indoor Unit
Outdoor Unit AHU Kit
Premium Standard Simple Controller ~ 32 ~ 128 ~ 8,192 Facility Integrator Gateway for Protocol PI-485 Dry Contact Control Accessory
Standard III (White) AC Ez AC Smart IV AC Manager 5 PDI AC Smart BACnet PI-485 Group Control Wire IO Module Communication Kit
(Power Distribution Indicator) (Input / Output Module)

PREMTA000 PREMTB100 PQRCVCL0QW PQWRHQ0FDB PQCSZ250S0 PACS4B000 PACM5A000 Premium (8port) PBACNA000 For SINGLE / Simple Dry Contact PZCWRCG3 Demand Controller Return/Room Air Control
PQNUD1S40 MULTI / THERMA V PDRYCB000 for MULTI V IV PUCKA0 (For SINGLE SPLIT)
Standard (2port) PMNFP14A1 PVDSMN000 PRCKA1 (For MULTI V)
PPWRDB000
Indoor Unit Indoor Unit
~ 64 ~ 256 ACS IO Module ACP BACnet Remote Low Ambient Kit
(Input / Output Module) Temperature Sensor
AC Ez Touch ACP IV
Standard III (Black)

PEXPMB000 PQNFB17C0 For Indoor Unit 2 Points Dry Contact PQRSTA0 For MULTI V IV Discharge Air Control by DDC
(Air-Conditioner, ERV) (For Setback) PRVC2 PUDCA0 (For SINGLE SPLIT)
PREMTBB10 PQRCVCL0Q PACEZA000 PACP4B000 PHNFP14A0 PDRYCB400 PRDCA0 (For MULTI V)

Chiller Option Kit ACP Lonworks Zone Controller Dry Contact for Control kit
Standard II (White) Demand Control

PCHILLN000 PLNWKB000 Dry Contact for 4 Zones by Demand Controller for PRCKD21E (~ 4 ODUs)
Thermostat thermostat ABZCA MULTI V III PRCKD41E (~ 8 ODUs)
PREMTB001 PQRCHCA0QW
PDRYCB300 PQDSBCDVM0
(Simple for Hotel)

Variable Water Flow EEV Kit


Standard II (Black) Control kit (Electronic Expansion Valve)

For Modbus For MULTI V WATER IV PRLK048A0 (~ 10HP)


PREMTBB01 PQRCHCA0Q PDRYCB500 PWFCKN000 PRLK096A0 (~ 20HP)
(Simple for Hotel)
TXV Kit
(Thermal Expansion Valve)

For MULTI V WATER II PATX13A0E (8 ~ 16HP)


PRVCO PATX20A0E (18 ~ 26HP)
PATX25A0E (28 ~ 36 HP)
PATX35A0E (38 ~ 46 HP)
PATX50A0E (48~56 HP)

Cool / Heat Selector

PRDSBM

226 227
ACCESSORIES
INDIVIDUAL CONTROL SOLUTION
INDIVIDUAL LINE-UP
CONTROL SOLUTION

Standard III Wired Simple Wired


Remote controller Remote Controller

Premium Wired Wireless


Remote Controller Remote Controller

Standard II Wired
Remote Controller

Remote Controller Line Up


PQRCVCL0QW
PREMTB100 PREMTB001 PQRCVCL0Q
Model Name PREMTA000 PQWRHQ0FDB
PREMTBB10 PREMTBB01 PQRCHCA0QW
PQRCHCA0Q

On / Off • • • • •
Fan Speed Control • • • • •
Temperature Setting • • • • •
Mode Change • • • •* •
Additional Mode Setting • • • • •
Auto Swing • • • •* •
Vane Control • • • •* •
(Louver Direction)
E.S.P • • • • -
(External Static Pressure)
Reservation Weekly / Yearly Weekly / Yearly Weekly - Sleep, On / Off
Child lock / Total Lock • • • • -
Advanced Lock
(on/off, mode, • • Mode - -
set point range)
Electric Failure • • • •* •
Compensation
Time Display • • • - -
Filter Sign • • • - -
Energy Monitoring** • • • - -
2 Set Points 2 Set Points • - -
Home Leave
Control Control
External Ports - DO 1 - - -
* PQRCHCA0QW / PQRCHCA0Q doesn’t offer this function
** Centralized control(PACS4B000)~

228 229
ACCESSORIES
INDIVIDUAL CONTROL SOLUTION

STANDARD III WIRED REMOTE CONTROLLER


4.3 inch Color screen with a modern design

PREMTB100 (White) / PREMTBB10 (Black)


Fully Support MULTI V 5 functions
Inside Dual Sensing Comfort Cooling
Standard III remote controller can Without cooling operation stopping,
do sensing both Temperature and this function allows MULTI V 5 to
Humidity. maintain operation at mild cooling
mode.

Modern Design & Intuitive Interface


Features 1) Colorful Icon
Standard III remote controller
Weekly / Monthly / Yearly
Trend & Target Setting control
The Optimized Controller in MULTI V 5 External Device On/Off is possible to express various Standard III remote controller provides
colors. convenient trend & target graph for
- Humidity sensor embedded - Customized Interlocking control with Indoor status
- Comfort cooling setting different period.
- Smart Load Control setting
2 Set Points control 2)
- Outdoor unit low noise setting
Multi Language support Easy Checking Schedule
- Defrost mode setting Standard III remote controller provides
English, French, German, Spanish, Italian, Portuguese, Polish,
New Modern Design & Easy interface Czech, Russian, Chinese
clock type daily schedule.
Cool Heat Dry Fan Auto
- Seamless design / Touch button
- 4.3 inch Color LCD / Intuitive GUI

Model Name PREMTB100 / PREMTBB10 External Device On/Off


On / Off •
Fan Speed Control • External Equipment Control Customized Interlocking Control
Temperature Setting • User can turn on or off the external User can make control scenario.
Mode Change Cooling / Heating / Auto / Dehumidification / Fan equipment through contact point output. example) When temperature is under 10
Additional Mode Setting* Plasma Purification / Energy-Saving Cooling / Robot Cleaning / Heater / Humidification / Comfort Cooling
degree, turn on the external heater.
Auto Swing •
Vane Control (Louver direction) •
E.S.P (External Static Pressure)**
Reservation

Simple / Sleep / On & Off timer / Weekly / Yearly / Holiday
2 Set Points Control
Time Display •
Electric Failure Compensation •
2 Set Points Control
Temperature
Lock All / On & Off / Mode / Set temperature range Ambient indoor temperature is guaranteed
Filter Sign • (Remain time + Alarm) by setting two-point temperature for cooling
Energy Management
Check Energy Usage*** / Check Operation Time / Target Setting (Energy, Operation Time) / and heating. Standard III remote controller Cooling set point
Time Limit Operation / Alarm Popup / Initialization Usage Data for Home Leave Cooling
automatically changes from heating to cooling
Operation Status LED • Cooling Set Point
(and vice versa) depending on temperature. for Occupied
Home leave
Indoor Temperature Display • Occupied
Heating Set Point (Unoccupied)
Indoor Humidity Display • for Occupied
Display 4.3 inch TFT color LCD (480 x 272) Heating
Heating Set Point Indoor
Size (W x H x D, mm) 120 x 120 x 16 for Home Leave Temperature
Black light for Screen saver • Home Leave Cooling Heating
Time
Home Leave 2 set points control Changeable setting for occupied / Arrive at a room Leave a room

* It might not be indicated or operated at the partial product unoccupied status Thermo-Off
** This function is available for certain indoor unit type
*** Centralized control (PACS4B000 / PACP4B000 / PQNFB17C0 / PLNWKB000) and PDI (PQNUD1S40 / PPWRDB000) should be installed for this function
1) Indoor unit should have functions requested by the controller
2) 2 set points control works normally with MULTI V Heat Recovery and Single Heat Pump. But in case of MULTI V Heat Pump, It is not working in 2 set points control of indoor unit

230 231
ACCESSORIES
INDIVIDUAL CONTROL SOLUTION

PREMIUM WIRED REMOTE CONTROLLER


5 inch full touch screen with a premium design

PREMTA000 1)
1) English / Portuguese / Spanish / French
Energy Management
Self Energy Management Weekly / Monthly / Yearly
After it gathers information about Trend & Target Setting Control
usage time or electricity usage*, Premium remote controller provides
offer periodical history data to convenient trend & target graph for
users as visual information. By using different period.
various setting mode (operation
hour / electricity usage etc.), you can
manage on your own. * Centralized control (PACS4B000 / PACP4B000 /
PQNFB17C0 / PLNWKB000) and
PDI (PQNUD1S40 / PPWRDB000) should be

Features 4)
installed for this function

User Friendly Design


Self-Management for Energy Saving Improved Scheduling Intuitive UI & GUI Design Display Configuration
- Time limit operation / Power consumption monitoring - Timer / Daily / Weekly / Yearly / Holiday
It is more easy to use and control Users can use of five buttons as
- Weekly / Monthly / Yearly trend tracking
various functions. shortcuts for frequently used features.
- Target alert alarm 2 Set Points Control 5)
- Temperature range setting
Standard Mode Simple Mode
Design with User’s Convenience
- Full touch / Intuitive GUI (Graphic User Interface) Enhanced Schedule Function
- Main display simple mode / Touch buzzer
Yearly / Weekly Schedule Function Easy Pattern Schedule
Model Name PREMTA000
If you set the schedule all at once, you It is possible to embody various
On / Off •
will be able to effectively manage for schedules as pattern setting.
Fan Speed Control •
various lengths of time. It provides 5
Temperature Setting •
Mode Change Cooling / Heating / Auto / Dehumidification / Fan
Yearly Schedule kinds of reservation functions. (Timer, Weekly Schedule Pattern

Additional Mode Setting* Plasma Purification / Energy-Saving Cooling / Robot Cleaning / Heater / Humidification Daily, Weekly, Yearly, Holiday)
Auto Swing •
Vane Control (Louver direction) • * Available to save up to a maximum of 20 error
E.S.P (External Static Pressure)** • histories, 20 holiday reservations and 5 daily event
Reservation Simple / Sleep / On / Off / Weekly / Yearly / Holiday on week

Time Display • Weekly Schedule


Electric Failure Compensation
Child Lock


2 Set Points Control
Filter Sign • (Remain time + Alarm)
Energy Management
Check Energy Usage*** / Check Operation Time / Target Setting (Energy, Operation Time) / 2 Set Points Control
Time Limit Operation / Alarm Popup / Initialization Usage Data Temperature
Operation Status LED • Ambient indoor temperature is guaranteed
Indoor Temperature Display • by setting two-point temperature for
Wireless Remote Controller Receiver •**** cooling and heating. New Standard III Cooling set point
for Home Leave Cooling
Display 5 Inch TFT color LCD (480 x 272) remote automatically changes from heating
Cooling Set Point
Size (W x H x D, mm) 137 x 121 x 16.5 to cooling (and vice versa) depending on for Occupied
Home leave
Black Light for Screen Saver • temperature. Occupied (Unoccupied)
Heating Set Point
for Occupied
Home Leave 2 Set Points Control
Heating
* It might not be indicated or operated at the partial product
Heating Set Point Indoor
for Home Leave Temperature
** This function is available for certain indoor unit type
*** Centralized control (PACS4B000 / PACP4B000 / PQNFB17C0 / PLNWKB000) and PDI (PQNUD1S40 / PPWRDB000) should be installed for this function Home Leave Cooling Heating
Time
**** For ceiling type duct
4) Indoor unit should have functions requested by the controller Changeable setting for occupied / Arrive at a room Leave a room
5) 2 set points control works normally with MULTI V Heat Recovery and Single Heat Pump. But in case of MULTI V Heat Pump, It is not working in 2 set points control of indoor unit unoccupied status Thermo-Off

232 233
ACCESSORIES
INDIVIDUAL CONTROL SOLUTION INDIVIDUAL CONTROL SOLUTION

STANDARD II WIRED REMOTE CONTROLLER SIMPLE WIRED REMOTE CONTROLLER


Providing easy control of one or a group of indoor units with various functions A simple way to control office or hotel systems in a compact design

Standard II Simple
PREMTB001 (White) / PREMTBB01 (Black) PQRCVCL0QW (White) /
PQRCVCL0Q (Black)
Simple for Hotel
PQRCHCA0QW (White) /
PQRCHCA0Q (Black)

Simple Simple for Hotel

Features1) Features1)
Model Name PREMTB001 / PREMTBB01 Model Name PQRCVCL0QW / PQRCVCL0Q PQRCHCA0QW / PQRCHCA0Q
On / Off • On / Off • •
Fan Speed Control • Fan Speed Control • •
Temperature Setting • Temperature Setting • •
Mode Change Cooling / Heating / Auto / Dehumidification / Fan Mode Change Cooling / Heating / Auto / Dehumidification / Fan Only Changeable by Central Controller

Plasma Purification / Energy-Saving Cooling / Auto Swing • -


Additional Mode Setting
Robot Cleaning / Heater / Humidification Vane Control (Louver direction) • -
Auto Swing • E.S.P (External Static Pressure) • •
Vane Control (Louver direction) • Electric Failure Compensation • -
E.S.P (External Static Pressure) • Child Lock • •
Reservation Simple / Sleep / On / Off / Weekly / Holiday Indoor Temperature Display • •
Time Display • Wireless Remote Controller Receiver •* •*
Electric Failure Compensation • Size (W x H x D, mm) 70 x 121 x 16 70 x 121 x 16
Child Lock • Blacklight • •
Filter Sign • (Remain time + Alarm) * For Ceiling Concealed Duct type
Operation Status LED • 1) Indoor unit should have functions requested by the controller

Indoor Temperature Display •


Wireless Remote Controller Receiver •*
Size (W x H x D, mm) 120 x 121 x 16
Blacklight •
Power Consumption Monitoring •**
Check Model Information •

* For Ceiling Concealed Duct type


** Centralized control (PACS4B000 / PACP4B000 / PQNFB17C0 / PLNWKB000) and PDI (PQNUD1S40 / PPWRDB000) should be installed for this function
1) Indoor unit should have functions requested by the controller

234 235
ACCESSORIES
INDIVIDUAL CONTROL SOLUTION

WIRELESS REMOTE CONTROLLER

PQWRHQ0FDB

Features
Model Name PQWRHQ0FDB
On / Off •

Fan Speed Control •

Temperature Setting •

Mode Change Cooling / Heating / Auto / Dehumidification / Fan

Additional Mode Setting Plasma Purification / Energy-Saving Cooling / Robot Cleaning / Auto Dry

Auto Swing •

Vane Control (Louver direction) •

Reservation Sleep / On / Off

Indoor Temperature Display •

Sleep Mode Auto Max. 7 hours

Size (W x H x D, mm) 51.4 x 153 x 26

236 237
ACCESSORIES
CENTRALIZED CONTROL SOLUTION
CENTRALIZED LINE-UP
CONTROL SOLUTION

AC Ez Touch ACP IV

AC Smart IV AC Manager 5

AC Ez

Central Controller Line Up


Model Name PQCSZ250S0 PACEZA000 PACS4B000 PACP4B000 PACM5A000

Maximum number of units 32 64 128 256 8,192


Individual / Group Control
(On & Off, Mode, set point, • • • • •
fan speed)
Ventilation Control • • • • •
Individual Controller Lock • • • • •
Error Check • • • • •
Schedule • • • • •
Operation History - • • • •
Visual Navigation - - • • •
Operation Time Limit - - • • •
Temperature Limit - • • • •

Remote Access 1)
- By client S/W Web Web Web

Auto Changeover / Setback - • • • •


Power Consumption Monitoring - • • • •
(with PDI)
Interlock Control - - • • •
Virtual Group Control - - • • •
Emergency Alarm Display - • • • •
ACS IO Module Interlocking - - • • •
1) Assignment of public IP address is required to access central controller through internet.

238 239
ACCESSORIES
CENTRALIZED CONTROL SOLUTION

AC EZ TOUCH
Smart management with 5 inch touch screen for small site

PACEZA000
Features

Internet

Features PC Access Energy Statistics (with PDI)


Model Name PACEZA000 Users can control each space efficiently through PC access. Statistics of operational status (time, power consumption) are
Maximum number of indoor units 64 (Web access : Network configuration is locally necessary) provided to help make intelligent system operation decisions.
Individual / Group Control •
(On & Off, Mode, set point, fan speed)
Individual Controller Lock • (Temperature / Mode / Fan / All)
Error Check Self diagnosis
Mode Change Cooling / Heating / Auto / Dehumidification / Fan
Slave Mode (Interlocking with higher level controller) •
Schedule Daily / Weekly / Monthly / Yearly / Exception day
Operation History •
Temperature Limit •
Remote Access 1) By client S/W
Auto Changeover / Setback •
Power Consumption Monitoring (with PDI) • Energy Mode Schedule
Emergency Alarm Display • When using energy mode function, operation mode changes Schedule control allows user to set the events in advance to
External IO Port No. DI 1 from cooling to fan or heating to off mode by force. maximize system performance. Also, by blocking unnecessary
Compatible Model MULTI V / ERV / ERV DX / THERMA V / Hydro kit (It is available only air conditioner and ‘on’ mode indoor unit) operation, it prevents a waste of energy.
Size (W x H x D, mm) 137 x 25 x 121
1) Assignment of public IP address is required to access central controller through internet please contact regional office to have detailed Internet connection configuration

Installation Scene

• MULTI V 5 • MULTI V • MULTI V S • MULTI SPLIT • ERV


Alarm Indicator Group / Individual Control
• MULTI V IV WATER IV • MULTI V Mini • SINGLE SPLIT It works when there are some errors or it’s time to change the According to the situation, it can be controlled by group or each
• MULTI V III • MULTI V • MULTI V SPACE II
• MULTI V II WATER II oil or filter. Users can respond immediately according to alarm indoor unit. It is useful to monitor or control for the best fit of
Internet
indicator therefore HVAC system is monitored consistently. request.
• Appropriate PI 485 should be used according to PDB

240 241
ACCESSORIES
CENTRALIZED CONTROL SOLUTION

AC SMART IV
Large 10.2 inch touch screen with intuitive GUI (Graphic User Interface) allows easy control

PACS4B000
Features

Features Schedule Visual Navigation


Schedule control allows user to set the events in advance to Current operation status on floor plan is checked at one view.
Model Name PACS4B000 maximize system performance. Also, by blocking unnecessary
Maximum number of indoor units 128 operation, it prevents a waste of energy.
Individual / Group Control •
(On & Off, Mode, set point, fan speed)
Individual Controller Lock • (Temperature / Mode / Fan / All)
Error Check Self diagnosis
Mode Change Cooling / Heating / Auto / Dehumidification / Fan
Slave Mode (Interlocking with higher level controller) •
Schedule Daily / Weekly / Monthly / Yearly / Exception day
Operation History •
Visual Navigation •
Operation Time Limit •
Temperature Limit •
Web Access 1) •
Auto Changeover / Setback •
Power Consumption Monitoring • (with PDI) Energy navigation Operation Report
Energy Navigation • (with PDI)
Energy navigation function allows MULTI V 5 to preset monthly Report including control status and other information is
Interlock Control •
energy usage and consume what has been previously planned. provided so that operation history can be reviewed easily.
Virtual Group Control •
Emergency Alarm Display •
By analyzing and comparing previous consumption and planned Data can be sent by E-mail or stored on USB or external HDD.
ACS IO Module Interlocking • energy usage for the month, overuse of the HVAC system
External IO Port No. DI 2 / DO 2 operational costs can be prevented.
Interfaceable Products MULTI V / ERV / ERV DX / THERMA V / Hydro kit / AHU (Control kit)
1) Assignment of public IP address is required to access central controller through internet please contact regional office to have detailed Internet connection configuration

Installation Scene
CH1
CH2

OR
Interlocking Emergency Display
• MULTI V 5 • MULTI V • MULTI V S • MULTI SPLIT • ERV • AHU (Control Kit) • ACS IO MODULE
• MULTI V IV WATER IV • MULTI V Mini • SINGLE SPLIT Allows interlocked operation of devices or between digital Red alert takes up the whole display upon any urgency
• MULTI V III • MULTI V • MULTI V SPACE II
• MULTI V II WATER II
inputs and outputs on the AC Smart IV. situation and all other control signals are blocked to prevent
any possible accident.
Internet • Appropriate PI 485 should be used according to PDB

242 243
ACCESSORIES
CENTRALIZED CONTROL SOLUTION CENTRALIZED CONTROL SOLUTION

AC EZ ACP IV
Easy to manage up to 32 indoor unit, including ERV with simple interface ACP IV can be integrated to the web system that allows user can access the control system online any-
time, anywhere without access to PC or specific application

PQCSZ250S0 PACP4B000

Features Features
Model Name PQCSZ250S0 Model Name PACP4B000
Maximum number of indoor units 32 Maximum number of indoor units 256

Individual / Group Control Individual / Group Control •


(On & Off, Mode, set point, fan speed) • (On & Off, Mode, set point, fan speed)
Individual Controller Lock • (Temperature / Mode / Fan / All)
Ventilation Control •
Error Check Self diagnosis
Individual Controller Lock •
Mode Change Cooling / Heating / Auto / Dehumidification / Fan
Error Check LED / LCD Display Schedule Daily / Weekly / Repetition / Exception day
Mode Change Cooling / Heating / Auto / Dehumidification / Fan Operation History •
Visual Navigation •
Slave Mode (Interlocking with higher level controller) •
Operation Time Limit •
Schedule Weekly
Temperature Limit •
Display Operation status, Set temperature, Room temperature, Schedule Web Access 1) •
Size (W x H x D, mm) 190 x 120 x 17 Auto Changeover / Setback •
Power Consumption Monitoring (with PDI) • (with PDI)
Power DC 12V
Energy Navigation • (with PDI)
Interlock Control •
Virtual Group Control •
Emergency Alarm Display •
ACS IO Module Interlocking •
External IO Port No. DI 10 / DO 4
Interfaceable Products MULTI V / ERV / ERV DX / THERMA V / Hydro kit / AHU (Control kit)
1) Assignment of public IP address is required to access central controller through internet.

Installation Scene Installation Scene


CH6

CH5
CH1 ~ 4

• MULTI V 5 • MULTI V • MULTI V S • MULTI SPLIT • ERV Internet


• MULTI V IV WATER IV • MULTI V Mini • SINGLE SPLIT
• MULTI V III • MULTI V • MULTI V SPACE II
• MULTI V II WATER II
AC Smart IV • MULTI V 5 • MULTI V • MULTI V S • MULTI SPLIT • ERV AHU ACS IO MODULE
• MULTI V IV WATER IV • MULTI V Mini • SINGLE SPLIT (Control Kit)
• MULTI V III • MULTI V • MULTI V SPACE II
• Appropriate PI 485 should be used according to PDB • MULTI V II WATER II • Appropriate PI 485 should be used according to PDB

244 245
ACCESSORIES
CENTRALIZED CONTROL SOLUTION

AC MANAGER 5
Up to 32 ACP IV can be connected so that 8,192 indoor units can be controlled and monitored

PACM5A000

Features Solution Overview


Model Name PACM5A000
Maximum number of indoor units 8,192 (supports 32 ACP IV or AC Smart IV)
Individual / Group Control •
(On & Off, Mode, set point, fan speed)
PACP4B000
Ventilation Control •
Individual Controller Lock • (Temperature / Mode / Fan / All)
AC Ez PDI
Error Check Self diagnosis PACM5A000
Mode Change Cooling / Heating / Auto / Dehumidification / Fan
PACS4B000
Schedule Daily / Weekly / Repetition / Exception day
Operation History • Dry Contact
Visual Navigation •
Operation Time Limit • ACS IO Module
Temperature Limit •
Web Access 1) •
Auto Changeover / Setback •
Power Consumption Monitoring (with PDI) • PQNFB17C0
Energy Navigation • (with PDI) BMS System PLNWKB000
* BACnet / Lonworks
Interlock Control • G/W can be connected
Virtual Group Control • to AC Manager
Emergency Alarm Display •
ACS IO Module Interlocking •
1) Assignment of public IP address is required to access central controller through internet.

AC Comm. Kit
Manager
5
AC
Manager
5
Light Pump

Schedule Energy Operation Automatic Fan Etc


Function Management Trending Report E-mail Sending External Device
Control Kit
* Combination: we recommend you to connect separated wattmeter for Indoor units and Outdoor units to have correct power distribution value
• Appropriate PI 485 should be used according to PDB

246 247
ACCESSORIES
SYSTEM INTEGRATION DEVICE SYSTEM INTEGRATION DEVICE

LINE-UP PDI (POWER DISTRIBUTION INDICATOR)


PDI shows power consumption of up to 128 indoor units

Facility Integrator Gateway for Protocol PI-485 Premium


PQNUD1S40 (8 port)

PDI (Power Distribution Indicator) AC Smart BACnet(Modbus) Standard


PPWRDB000 (2 port)

Premium (8 port) For Outdoor Unit


PQNUD1S40 (SINGLE / MULTI / THERMA V)
PBACNA000
Standard (2 port) PMNFP14A1
PPWRDB000

Features
ACS IO Module ACP BACnet (Modbus)
• Data is backed up so that correct consumption can be checked when power outage occurred
• Connector can be separated for convenient installation
• Linkable with pulse type power meter

PEXPMB000 PQNFB17C0
For Indoor Unit
(Air-Conditioner, ERV)
Installation Scene
PHNFP14A0
Power Monitoring Watt Meter
Pulse Signal Power In
Power In
3 phase 4 wire
single phase
50Hz / 60Hz
Chiller Option Kit ACP Lonworks 50Hz / 60Hz
380V
220V RS485 (LGAP)

Power Cable of Indoor Unit


PCHLLN000 PLNWKB000 PACP4B000 PACS4B000 PACEZA000
or

PQNFB17C0 PLNWKB000
Power Cable for 3 Phase 4 Wire
Power Cable for Single Phase
Communication Cable (2 Wire Shielded Cable)
Pulse Signal Wire

* This value could be different with measured power consumption by power meter
Combination : we recommend you to connect separated watt meter for Indoor units and Outdoor units to have correct power distribution value

248 249
ACCESSORIES
SYSTEM INTEGRATION DEVICE SYSTEM INTEGRATION DEVICE

ACS IO MODULE CHILLER OPTION KIT


The module can be connected with PACS4B000 or PACP4B000 if additional control points are needed LG central controller IV series with Chiller Option Kit can provide LG chiller remote control and cycle
not only DI / DO but also AI / AO port. These central controller can control 3rd party device as pump, monitoring
security, lighting and so on through DI / DO and AI / AO

PEXPMB000 PCHLLN000

Features Features
Model Name PEXPMB000 Model Name Min. Max. Model Name PCHLLN000
NTC 10k 0.68k Ω 177k Ω
PACS4B000 Evaporator status / Compressor status (Scroll, Screw, Centrifugal chiller only)
PT 1000 803 Ω 1,573 Ω Monitoring Points
Linkable Products PACP4B000 Condensor status / Generator status (Abs. chiller only)
PACM5A000 Analog Input Ni 1000 871.7 Ω 1,675.2 Ω
10V On/Off •
DC (Voltage) 0V
Communication RS-485 1
DC (Current) 0mA 20mA Target Temp. setting •
Digital Input 3 Analog Output - 0V 10V Mode Change Scroll chiller only
Digital Output 3 Binary Input
I/O Digital Input (Dry Contact) - - Schedule •
Universal Input 4
30VAC / 30VDC,
Analog Output 4 Digital Output Normal open - Interfaceable Products Scroll, Screw, Centrifugal, Absorption (LG Only)
2A

PACS4B000 PACP4B000 PACM5A000


Number of Indoor Units 64 ~ 128 128 ~ 256 8,192
Max. I/O Points 130 224 1,260
Maximum Number of Node 9 16 -
* Maximum number of Indoor units may be reduced by increasing the number of I/O points.

Installation Scene Cycle Display Example


CH1 ~ 4

CH6

PACS4B000 or PACP4B000

PUMP DDC Lighting Fan Alarm

PACM5A000 • Sensor / Valve / Actuator • Pump / Fan etc.

* D I : Digital Input, DO : Digital Output, UI : Universal Input, AO : Analog Output / Please contact our regional office to have connectable relay specification for analog output

250 251
ACCESSORIES
SYSTEM INTEGRATION DEVICE SYSTEM INTEGRATION DEVICE

AC SMART BACNET ACP BACNET GATEWAY

PBACNA000 PQNFB17C0

* Please refer PDRYCB500 for Modbus RTU

Features Features
• Process Ability Controlling Monitoring Items • Process Ability Controlling Monitoring Items
On / Off Command On / Off Status On / Off Command On / Off Status
- EHP Type : 128 units (Indoor / ERV / ERV DX / Hydro Kit / THERMA V) Operation Mode Setting Operation Mode Status
- EHP Type : 256 units (Indoor / ERV / ERV DX / Hydro Kit / THERMA V) Operation Mode Setting Operation Mode Status
- AHU Control kit : Maximum 16 units Fan Speed Setting Fan Speed Status - AHU Control kit : Maximum 16 units Fan Speed Setting Fan Speed Status
• Self installation verification function on touch Lock Setting Lock Status • Self installation verification function Lock Setting Lock Status

screen or using Internet (Web Server Included) Air Flow Setting


Set Temperature Setting
Air Flow Setting
Set Temperature Status
using internet (Web Server Included) Air Flow Setting
Set Temperature Setting
Air Flow Setting
Set Temperature Status
- Setting gateway - Current Space Temperature Status - Setting gateway - Current Space Temperature Status
- Diagnosis of communication status on LG Air-conditioner network - Error Status - Diagnosis of communication status on LG Air-conditioner network - Error Status
User Mode Setting (for only ERV) User Mode Status (for only ERV) User Mode Setting (for only ERV) User Mode Status (for only ERV)
• Modbus TCP Protocol Support Accumulator Power • Modbus TCP Protocol Support Accumulator Power
- -
• BTL Certified (B-ASC) Upper Limit Temp. Setting
Distribution Status
Upper Limit Temperature Status
• BTL Certified (B-ASC) Distribution Status
Upper Limit Temp. Setting Upper Limit Temperature Status
Low Limit Temp. Setting Low Limit Temperature Status • It offers a variety of functions as ACP which allows
• It offers a variety of functions as ACP which allows Mode Lock Setting Mode Lock Status the customer to efficiently control various types of
Low Limit Temp. Setting Low Limit Temperature Status

the customer to efficiently control various types of AC Operation Mode Setting Air Conditioner Operation equipment from the customer’s own Integration.
Mode Lock Setting Mode Lock Status
AC Operation Mode Setting Air Conditioner Operation
equipment from the customer’s own Integration. (ERV DX only) Mode Status (ERV DX only)
(ERV DX only) Mode Status (ERV DX only)
AC On / Off Command Air Conditioner On / Off Status
(ERV DX only) (ERV DX only) AC On / Off Command Air Conditioner On / Off Status
* In case of using Modbus, the compatibility is different from BACnet. Refer to manual in detail. * In case of using Modbus, the compatibility is different from BACnet. Refer to manual in detail.
(ERV DX only) (ERV DX only)

Installation Scene Installation Scene

Lighting control Remote checking Utility control Lighting control Remote checking Utility control
CH1 BMS system CH5 BMS system
CH2 Indoor unit : Max. 128 units (Air conditioner & Ventilation) / Indoor address : 00 ~ 7F CH1 ~ 4 Indoor unit : Max. 256 units (Air conditioner & Ventilation) / Indoor address : 00 ~ FF

1) 1)

Internet Internet
PACS4B000

• MULTI V 5 • MULTI V • MULTI V S • MULTI SPLIT • ERV / • AHU (Control Kit) • MULTI V 5 • MULTI V • MULTI V S • MULTI SPLIT • ERV / • AHU (Control Kit)
• MULTI V IV WATER IV • MULTI V Mini • SINGLE SPLIT ERV DX • MULTI V IV WATER IV • MULTI V Mini • SINGLE SPLIT ERV DX
Backup operation • MULTI V III • MULTI V • MULTI V Backup operation • MULTI V III • MULTI V • MULTI V
• MULTI V II WATER II SPACE II • MULTI V II WATER II SPACE II
1) Assignment of public IP address is required to access central controller through internet. • Appropriate PI 485 should be used according to PDB 1) Assignment of public IP address is required to access central controller through internet. Appropriate PI 485 should be used according to PDB

252 253
ACCESSORIES
SYSTEM INTEGRATION DEVICE SYSTEM INTEGRATION DEVICE

ACP LONWORKS GATEWAY PI 485


PI 485 converts LG air conditioner’s protocol to the RS485 protocol for the central controller

PLNWKB000 PMMFP14A1 / PHNFP14A0

Features Features
• Process Ability Controlling Monitoring Items
- EHP Type : 64 units (Indoor / ERV / Hydro Kit / THERMA V) On / Off Command On / Off Status • Model Name : PMNFP14A1
- AHU Control kit : Maximum 16 units Operation Mode Setting Operation Mode Status • Power : Single Phase AC 220V 50/60Hz
Fan Speed Setting Fan Speed Status
• Connect to use Lonworks® protocol and Lock Setting Lock Status
• 1 for Each Outdoor Unit
LG air conditioner protocol. Air Flow Setting Air Flow Setting - MULTI V MINI (ARUN40GS2A / ARUV40GS2A Only needs PI485)
Set Temperature Setting Set Temperature Status - SINGLE SPILIT - MULTI SPLIT - THERMA V
• Self installation verification function - Current Space Temperature Status
using internet (Web Server Included) - Error Status
Accumulator Power
- Setting gateway -
Distribution Status
- Diagnosis of communication status on LG Air-conditioner network Accumulator Power
Upper Limit Temperature Setting
Distribution Status
• It offers a variety of functions as ACP which Low Limit Temperature Setting Low Limit Temperature Setting
• Model Name : PHNFP14A0
allows the customer to efficiently control Mode Lock Setting Mode Lock Status • Power : Connected with the Indoor Units
various types of equipment from the customer’s Peak Operation Ratio Setting Peak Operation Ratio Setting
• 1 for Each Indoor Unit
own Integration. All On / Off Setting -
- Total Accumulate Power Status - Indoor Unit (Air-Conditioner, ERV)

Installation Scene

Lighting control Remote checking Utility control


CH5 BMS system
CH1 ~ 4 Indoor unit : Max. 64 units (Air conditioner & Ventilation) / Indoor address : 00 ~ FF

1)

Internet

PACS4B000

• MULTI V 5 • MULTI V • MULTI V S • MULTI SPLIT • ERV • AHU (Control Kit)


• MULTI V IV WATER IV • MULTI V Mini • SINGLE SPLIT
Backup operation • MULTI V III • MULTI V • MULTI V
• MULTI V II WATER II SPACE II
* MULTI V PLUS II & MULTI V III & MULTI V IV series do not require any other PI 485 since these series have PI 485 in its outdoor unit PCB.
1) Assignment of public IP address is required to access central controller through internet. • Appropriate PI 485 should be used according to PDB

254 255
ACCESSORIES
OTHER INTERRATION CONTROL SOLUTION
OTHER INTEGRATION LINE-UP
CONTROL SOLUTION

Indoor Unit
Outdoor Unit AHU Kit
Dry Contact Control Accessory
Simple Dry Contact Group Control Wire IO Module (Input / Output Module) Communication Kit

PDRYCB000 PZCWRCG3 PVDSMN000 PUCKA0


PRCKA1

2 Points Dry Contact Remote Temperature Sensor Low Ambient Kit

PDRYCB400 PQRSTA0 PRVC2 PUDCA0


PRDCA0

Dry Contact for Thermostat Zone Controller Dry Contact for Demand Control Control Kit

PDRYCB300 ABZCA PQDSBCDVM0 PRCKD21E


PRCKD41E

For Modbus Variable Water Flow Control Kit EEV Kit (Electronic Expansion Valve)

PWFCKN000 PRLK048A0 / PRLK096A0


PDRYCB500

TXV Kit (Thermal Expansion Valve)

PRVCO PATX13A0E / PATX20A0E


PATX25A0E / PATX35A0E
PATX50A0E
Cool / Heat Selector

PRDSBM

256 257
ACCESSORIES
OTHER INTERRATION CONTROL SOLUTION

DRY CONTACT
Connection between an indoor unit and external devices to control various functions

PDRYCB000 PDRYCB400

Features Features
Model Name PDRYCB000 Model Name PDRYCB400
Contact Point 1 Contact Point Contact Point 2 Contact Point
Contact Voltage Rating AC 220V Contact Voltage Rating DC 5 ~ 12V / Non Voltage
On / Off Control • On / Off Control •
Error Alarm Output • Error Alarm Output •
Operation On / Off Output • Operation On / Off Output •
Rotary Switch 1 (Set Temperature selection) - Rotary Switch 1 (Set Temperature selection) •
Rotary Switch 2 (Operation Logic selection) - Rotary Switch 2 (Operation Logic selection) •
Size (W x H, mm) 120 x 120 Size (W x H, mm) 120 x 120
* Refer to each models PDB for applicable models. * Maximum operation AC : 3A * Refer to each models PDB for applicable models. * Maximum operation AC : 3A
* 4th generation indoor unit has 1 contact point function for On / Off control. But in case of using more function of Dry Contact besides On / Off control, Dry Contact is needed. * 4th generation indoor unit has 1 contact point function for On / Off control. But in case of using more function of Dry Contact besides On / Off control, Dry Contact is needed.

Signal Point Signal Point


Contact Point Input 1
Contact Point Input
Contact Point Input 2
Indoor Unit
PCB Operation On/Off Status
Indoor Unit Operation On/Off Status
PCB
CN - CC Error alarm
Error Alarm
CN - CC

Installation Scene
Installation Scene 2 inputs interworking Refrigerant leakage detection alarm

CN - CC CN - CC
CN - CC

Window Sensor Leakage Alarm


Dry contact Key Switch Lighting Fire Alarm Timer Motion Door Check
(Contact point linked Sensor Detect Sensor Sensor
with outer part)
System Structure

Card key Card key Leakage Detector

258 259
ACCESSORIES
OTHER INTERRATION CONTROL SOLUTION

DRY CONTACT
Connection between an indoor unit and external devices to control various functions

PDRYCB300 PDRYCB500

Features Features
Model Name PDRYCB300 Function
Contact Voltage Rating DC 5 ~ 12V / Non Voltage - MODBUS communicate with MODBUS master controller - MODBUS RTU slave / 2 wire RS485 / 9,600bps
On / Off Control • - MAX. 8 IDUs can be connected with one MODBUS master controller - Size (W x H x D) : 120mm x 120mm x 36.5mm
Mode Control •
Fan Speed Setting • Memory map
Thermo Off • Register Name Range Notes
Error Alarm Output • 00001 Operation 0 ··· 1 0 : Stop, 1 : Run
Operation On / Off Output •
30003 Indoor temperature 100 ··· 400 Degrees C x 100
Rotary Switch 1 (Set Temperature Selection) •
30100 Error alarm 0 ··· 1 0 : No Error, 1 : Error
Rotary Switch 2 (Operation Logic Selection) •
Size (W x H, mm) 120 x 120 40001 Set run mode 0 ··· 4 0 : Cooling, 1 : Dry, 2 : Fan, 3 : AI, 4 : Heating
40002 Set temperature 180 ··· 300 Degrees C x 100

Signal Point 40015 Set fan speed 1 ··· 3 1 : Low, 2 : Middle, 3 : High

Operation On/Off Installation Scene


Thermo On/Off <Modbus Communication Function>

Indoor Unit Operation Mode (Fan/Heat/Cool)


PCB Fan Speed (Low/Middle/High)
Operation On/Off Status CN-CC
CN - CC
Error Alarm
Modbus Master Controller
Indoor Unit
Max. 8 IDUs
Installation Scene
...
One to one connection between
dry contact and indoor unit
Control Module
CN-CC
CN - CC

Indoor Unit

* Please contact our regional office to have full compatible room controller list * Please contact our regional office to have full compatible room controller list

260 261
ACCESSORIES
OTHER INTERRATION CONTROL SOLUTION OTHER INTERRATION CONTROL SOLUTION

GROUP CONTROL WIRE REMOTE TEMPERATURE SENSOR


Cables used to connect a wired remote controller up to 16 indoor units Sensor for detecting the room temperature

PZCWRCG3 PQRSTA0

Features Features
Model Name PZCWRCG3 • It detects the exact room temperature instead of indoor unit’s air temperature sensor
Y-type Cable 0.25m Length • Applied to Ceiling Mounted Cassette, Ceiling Concealed Duct, THERMA V and Hydro Kit
Long Cable 9.6m Length • Extension cable (15m) is included

Installation Scene Installation Scene


Indoor 1 MAIN PCB 1. Wire to the control box in the indoor unit by removing the existing thermistor and connect the extension cable its place.
2. Cut the extension cable to the appropriate length and connect the screw terminal of the remote sensor.
Indoor 1 Indoor 2 Indoor 3
Indoor terminal block Indoor terminal block Indoor terminal block

RED (12V)
YL (SIGNAL) YL (SIGNAL)
YL (SIGNAL)
BK (GND) BK (GND)
BK (GND)

Extension Cable
CN-ROOM

Note : 1 Y type Cable assembly for connecting indoor unit and low cable.
Indoor Unit
2 Long Cable assembly for connecting indoor to indoor.
- Please connect cable assembly Y type Cable with already connected indoor unit.

Remote Wired Remote


Temperature Sensor Controller

262 263
ACCESSORIES
OTHER INTERRATION CONTROL SOLUTION

ZONE CONTROLLER
Controls air conditioning in up to 4 zones by external thermostat

ABZCA

Features Indoor Unit


ROOM1

Thermostat
ROOM2

Temperature sensor
(Duct Type)
• Controls different zones (up to 4 zones) by external thermostat
(AC a24V)
• Maintain proper air volume of each zone
• Auto variation of dampers
• Auto control of fan speed and On / Off operation
Temperature sensor Temperature sensor

Zone Control ROOM3 ROOM4


sub PCB

Models Applied
• Ceiling Concealed Duct (refer to PDB for applicable models)

Wiring Diagram
Ceiling Concealed Duct
1
2
3
4
5
CN - ZONE 6
7
8

AC 24V
ROOM(External) Damper
THERMOSTAT #1 Or Relay

Zone controller ROOM Damper


THERMOSTAT #2 Or Relay

ROOM Damper
THERMOSTAT #3 Or Relay

ROOM Damper
THERMOSTAT #4 Or Relay

264 265
ACCESSORIES
OTHER INTERRATION CONTROL SOLUTION

IO MODULE
Interface module between system air conditioner’s outdoor unit and external device

PVDSMN000
Installation Scene
Demand Control
Provides variable setting for demand control according to input method to reduce power consumption.
This function supports 2 types of input signal : AI (0 ~ 10V, 10 Step) and contact signal (3 Step).

DDC
(Direct Digital Controller)

Capacity Control with


or

Features Contact Signal (3 Points / 3 Steps)

MULTI V WATER IV MULTI V 5 IO Module Range of Operation Rate


Function AI 0 ~ 10V : 0%, 40% ~ 100%
Contact signal (3 steps) : 0%, 40% ~ 80%
- Demand control - Low noise operation
- Output outdoor or indoor unit operation status - Output error status
Low Noise Operation
Description To reduce noise level , control outdoor unit’s fan speed by dry contact input.
DDC
- IO Module is communication interface module for connection between MULTI V 5 and external IO (Input / Output Module) devices. (Direct Digital Controller) Timer
Max 7 dB*
Note : IO Module is not compatible for MULTI V III

(dB) or

Models Applied
Contact Signal
• MULTI V 5 • MULTI V IV
• MULTI V WATER IV • MULTI V S Noise Level MULTI V 5 IO Module
* 8 HP model, Sound power level can be changed by outdoor unit operation status and low noise operation input signal.
Part Description
1) Digital Input Part (DI : Dry Contact Input) Refrigerant Leakage detection with Pump-down
• Demand control by contact input (3 Step)
• Low Noise Operation input For safety, IO module close refrigerant valve with Pump-down
• Priority Setting input :
Setting the priority of demand control command
2. Valve Close
(Capacity control for external signal from DDC vs Peak control Liquid Pipe
by LG Central controller)
Gas Pipe
- Open : External signal has priority to central controller (Default)
- Close : Central controller has priority to external signal
2) Analog Input Part (AI : DC 0 ~ 10V)
• Demand control by analog input (10 Step) MULTI V 5 IO Module 3. Operation Stop 1. Sense the Gas
3) Digital Output Part (DO : 250VAC, Max 1A)
• Error status relay output Alarm
• Operation status relay output Gas Gas
• Valve control Sensor Sensor

Refrigerant

266 267
ACCESSORIES
OTHER INTERRATION CONTROL SOLUTION OTHER INTERRATION CONTROL SOLUTION

LOW AMBIENT KIT OUTDOOR UNIT DRY CONTACT


External integration module for cooling operation with -25°C low ambient temperature. Dry contact for demand control

PRVC2 PQDSBCDVM0

Features Features
Function Function
Error
- 25°C Low ambient cooling operation by Low ambient kit and hood with damper - Demand control (3 contact signal) Display
(Analog output 0 ~ 10V) - Demand control (Co-work with DDC)
- Demand control - Low noise operation - Outdoor unit fan low speed control (Night low noise operation)
- Output outdoor or indoor unit operation status (250VAC, Max 1A) - All Off
Low Noise
- Output error status (250VAC, Max 1A) - Error output (Display)

Description Description or
By DDC By Dry
- Low ambient kit supports -25° C cooling operation by making stable condensing - The product is especially designed for demand control. 0 ~ 10V Contact
pressure with reducing air flow rate from hood and damper control given
0 ~ 10V proportional to condensing pressure. Demand control (Input)
- Low ambient kit provides IO Module function. Front Back
- External snow hood and air damper are required for this item.*
- Transformer and terminal block are included.
* Before apply this accessory, please contact regional sales office.
: Field Supply item
Models Applied
• MULTI V S • MULTI V III • MULTI V MINI
Models Applied • MULTI V SPACE II • MULTI V WATER II • MULTI V WATER S
• MULTI V IV
Reference : Air Damper
Installation Scene Main PCB
Installation Scene
DDC
(Direct Digital Controller)
Damper Actuator
(0 ~ 10V)
Transformer
0 ~ 10V (Analog Input)
220VAC
-> 24VAC

Contact Signal (3 points / 3 steps)


MULTI V IV IO Module
MULTI V III Outdoor Unit Range of Operation Rate
Dry Contact AI 0 ~ 10V : 0%, 40% ~ 100%
Common DC 0 ~ 10V
Control 24VAC Contact signal (3 steps) : 0%, 40% ~ 80%

Note : The IO Module can control maximum three actuators. Please, review damper actuator’s installation manual.

268 269
ACCESSORIES
OTHER INTERRATION CONTROL SOLUTION OTHER INTERRATION CONTROL SOLUTION

VARIABLE WATER FLOW CONTROL KIT COOL / HEAT SELECTOR


Accessory developed for controlling the water flow Cooling, heating, or fan mode can be selected
to prevent cooling and heating mixing errors during seasonal changes

PWFCKN000 (MULTI V WATER IV) PRDSBM


PRVC0 (MULTI V WATER II)

Features Features
Fan Mode
Fan Mode ModeMode Change
Change
Function • Indoor unit mode control without central controller
- Water pump or valve control (0 ~ 10V) • Select operation mode : Cooling, Heating, Fan mode
- Minimum output voltage setting available • Mode lock for cooling & heating mixing error-proof Cooling
Cooling Heating
Heating
only only only only
- Operation, error output (250VAC, Max 1A) during the change of season
- Dry contact input and analog output for demand control
- Digital output for operation, error status (250VAC, Max 1A)

Advantage
- Water flow consumption reduction
- Pump electricity consumption reduction
- Including IO Module (Dry contact input, Analog input / output, Digital output)
: Using Dry contact and variable water flow control function simultaneously
Models Applied
Cooling Tower

Wiring Diagram • MULTI V IV • MULTI V WATER S • MULTI V WATER II


• MULTI V S • MUL TI V PLUS II, MULTI V PLUS • MULTI V SPACE II
Single Line • MULTI V WATER IV • MULTI V MINI
Cooling Tower

Water Flow Line


0 ~ 10V (Analog output)

Flow
control
Wiring Diagram
Pump / Cooling
valve
Tower Controller
<Outdoor Main PCB>
<Outdoor Main PCB > Push Button
Push Button • Connect Terminals (1, 2, GND) on the back side of the outdoor dry
Insert wire method contact to terminals (1, 2, GND) of outdoor as show below.
Flow Insert wire method
control
valve Pressure
sensor Push arrow direction
Push arrow direction

From Water Source


Insert wire to connector * Communication line length can be maximum 300m, use
Inverter pump Shows field wiring Insert wire to connectorCommunication line as thick as 1.25mm
Connected wiring
Shows field wiring
• Flow control valve : Regulates the flow or pressure of a fluid, normally responding to signals generated by independent devices.
Connected wiring
• Flow Meter : Measures mass flow rate of a fluid traveling through a tube. (The mass flow rate is the mass of the fluid traveling past a fixed point per unit time.)
• Pressure Sensor : Measures the pressure.

270 271
ACCESSORIES
OTHER INTERRATION CONTROL SOLUTION

AHU KITS
Solution to connect LG outdoor unit on the DX coil of an air handing unit,
with LG’s high efficient products for maximum cost saving

Communication Kit
PRCKA1 / PUCKA0 Features
PRDCA0 / PUDCA0
Control Kit Communication Kit
PRCKD21E / PRCKD41E PRCKA1 & PUCKA0
EEV Kit (Electronic Expansion Valve) List Description
PRLK048A0 / PRLK096A0
Communication Kit Operation On / Off
TXV Kit (Thermal Expansion Valve)
PATX13A0E / PATX20A0E / PATX50A0E Mode Change Cooling / Heating / Fan
PATX25A0E / PATX35A0E Return Air (or Room) Temperature Setting Cooling 18 ~ 30oC, Heating 16 ~ 30oC

Fan Speed Signal Output 3 steps fan signal output (220V)

Specifications Reservation On / Off, Weekly

Return Air (or Room) Temperature Display 10 ~ 39.5°C


Communication & Control Kit Note : PRCKA1 and PUCKA0 are controlled and monitored by LG wired remote controller or LG centralized controller
Combination Dimensions (mm)
Type Model Outdoor EEV TXV Centralized Description Accessories for PRCKA1 & PUCKA0
Unit Kit Controller W H D
Kit

PRCKA1 MULTI V • • • Return / room air control by remote controller or dry contact 280 280 135 Wired Remote Controller Dry Contact IO Module
Standard II Simple 2 point Thermostat Modbus (for Outdoor Capacity Control)
• • - Return / room air or discharge air (capacity) control by DDC
PRDCA0 MULTI V 330 430 180
Communication This unit is connected with outdoor unit 1:1
Kit PREMTB001 PREMTBB01 PVDSMN000 (MULTI V IV)
- - • (White) (Black) PDRYCB000 PDRYCB400 PDRYCB300 PDRYCB500
PUCKA0 Single Split Return / room air control by remote controller or dry contact 280 280 135 PWFCKN000 (MULTI V WATER IV)

PUDCA0 Single Split - - - Return / room air or discharge air (capacity) control by DDC 330 430 180

PRCKD21E MULTI V - • • Max capacity 1 ~ 4 master outdoor unit 600 750 285 PRDCA0 & PUDCA0
Control Kit
PRCKD41E MULTI V - • • Max capacity 5 ~ 8 master outdoor unit 600 750 285 List Description Type Min Max
Digital input* - -
Communication Kit Operation On / Off (Non voltage)
Digital input - -
Fan only / Heating / Cooling
Expansion Valves Mode Change (Non voltage)

Controlling
Digital input - -
Pipe Diameter (mm) Dimensions (mm) Fan Step High / Mid / Low (3 steps) (Non voltage)
Type Model Capacity Range Liquid Liquid Gas Gas
W H D Room Temperature Control Cooling 18 ~ 30oC, Heating 16 ~ 30oC Analog input 0V 10V
(ODU) (AHU) (ODU) (AHU)
Discharge Air Temperature Control Compressor Off, Compressor Off & Fan Off, Analog input
EEV Kit PRLK048A0 3 ~ 10 HP 12.7 12.7 - - 217 404 83 (by Outdoor unit Capacity Control) 0V 10V
40 ~ 100% capacity control
(Electronic
Expansion Valve) PRLK096A0 12 ~ 20HP 12.7 12.7 - - 217 404 83 Communication Kit Operation On / Off Digital output* Max : AC 250V, DC 30V, 1A
PATX13A0E 8 ~ 16HP 15.88 15.88 22.2 22.2 491 331 174
Outdoor Unit Operation On / Off Digital output Max : AC 250V, DC 30V, 1A
PATX20A0E 18 ~ 26HP 15.88 22.2 28.58 28.58 491 331 174 Monitoring
TXV Kit Mode Fan / Defrost / Cooling / Heating Digital output Max : AC 250V, DC 30V, 1A
(Thermal PATX25A0E 28 ~ 36HP 22.2 28.58 34.92 34.92 491 331 174
Expansion Valve) Fan Mode High / Mid / Low (3 steps) Digital output Max : AC 250V, DC 30V, 1A
PATX35A0E 38 ~ 46HP 28.58 34.92 41.3 41.3 491 331 174

PATX50A0E 48 ~ 56HP 28.58 34.92 41.3 41.3 561 331 192 Error Status No error / Error occurred Digital output Max : AC 250V, DC 30V, 1A
* Digital Output is Normal open type. For more detail please refer to installation manual.
Note : DDC or thermostat (field supplied item) is required to control PRDCA0 or PUDCA0

Accessories for PRDCA0 & PUDCA0


Wired Remote Controller
Standard II (Monitoring Only)
PREMTB001 PREMTBB01
(White) (Black)

272 273
ACCESSORIES
OTHER INTERRATION CONTROL SOLUTION

AHU KITS
Solution to connect LG outdoor unit on the DX coil of an air handing unit,
with LG’s high efficient products for maximum cost saving

Features Capacity Selection


Control Kit For Communication Kit with SINGLE SPLIT Detail

List Required Item


When selecting evaporator, change ‘Option PCB’ in Communication kit according to below table
(Basic ‘Option PCB’ is for 24k Btu/h)
Heating / Cooling SA / RA temperature sensor (or SA / RA temperature & humidity sensor)
Capacity setting
Automatic Ventilation SA / RA temperature, CO2 sensor, Damper actuator (OA, EA, MA) (Main PCB) 'Option PCB'

Energy Saving (Cooling Mode Only) SA temperature, OA / RA temp&humidity sensor, Damper actuator (OA, EA, MA) Outdoor Unit Capacity Applicable Outdoor Units
Recommended Heat Maximum Heat
Humidification SA temperature, RA temperature & humidity sensor, Humidifier Option PCB Air Flow Rate PUCKA0 PUDCA0
Exchanger Volume Exchanger Capacity
12kBTU kBTU kW (CMM)
(10-3 x m3) (kW)
Standard Inverter
Inverter Fan Control SA / RA temperature, Static pressure sensor, Inverter driver for fan control
EBR65102901 12 3.5 2.2 3.5 9 ~ 10 • -
Filter Alarm Difference pressure sensor
EBR65102902 18 5.0 2.4 5.0 13 ~ 16.5 • •*
Smoke Detecting Smoke detection sensor EBR65102903 24 7.1 2.6 7.1 14 ~ 18 • •*
EBR65102904 30 8.0 2.9 8.0 20 ~ 26.5 • •*
RA : Return Air, EA : Exhaust Air, OA : Outdoor Air, SA : Supply Air, MA : Mix air (RA + OA)
EBR65102905 36 10.0 3.1 10.0 26.5 ~ 32 • -
EBR65102906 42 12.5 3.4 12.5 28 ~ 36 • -
EBR65102907 48 14.0 4.0 14.0 30 ~ 40 • -
EBR65102908 60 15.0 4.7 15.0 40 ~ 50 • -
Field Supplied Item EBR77627409 70 19.0 5.2 20.0 60 ~ 70 • •
EBR77627406 85 23.0 5.9 23.0 64 ~ 80 • •
List Required Specification Apply Location
1) Evaporator Saturated Temperature = 6oC, Air Temperature = 27oC DBT / 19oC WBT
2) Combination allowed only for air-to-air system.
- Power : AC 24V, Output signal : DC 0 ~ 10V
Temperature Sensor - Apply to MA, SA, RA * UU18W.UE4 / UU24W.U44 / UU30W.U44 Available
- Temperature boundary : -50 ~ 50°C

- Power : AC 24V, Output signal : DC 0 ~ 10V


- Apply to SA, RA, OA
Temperature & Humidity Sensor - Temperature boundary : -40 ~ 70°C
- Humidity boundary : 0 ~ 95% RH
- Can not be applied to MA For Communication Kit with MULTI V Detail

- When selecting evaporator, change ‘Option PCB’ in Communication kit according to below table
- Power : AC 24V, In/Output signal : DC 0 ~ 10V
Damper Actuator - Torque : 15 Nm, Operation time : 150sec. - Apply to OA, EA, MA damper (Basic ‘Option PCB’ is for 36k Btu/h)
- Rotation angle : 90° - After checking the need capacity, remove the 36k Option PCB equipped in the main PCB, and Capacity setting
- Power : AC 24V, Output signal : DC 0 ~ 10V
set up the Option PCB fitted the need capacity in the main PCB. (Main PCB) 'Option PCB'

Difference Pressure Sensor (for Filter) - Boundary : 0 ~ 1000Pa - Apply to filter


* Switch type : Relay Open / Close Option PCB Capacity Index Recommended Heat Maximum Heat Air Flow Rate
P/No (Btu/h) Exchanger Volume (10-3 x m3) Exchanger Capacity (kW) (CMM)
- Power : AC 24V, Output signal : DC 0 ~ 10V EBR52358907 28k 2.7 8.6 22 ~ 26
Static Pressure Sensor - Apply to SA (for inverter control)
- Boundary : 0 ~ 1000pa EBR52358908 36k 3.1 11.0 25 ~ 32
EBR52358909 42k 3.4 13.8 31 ~ 35
- Power : AC 24V, Output signal : DC 0 ~ 10V EBR52358910 48k 4.0 15.4 33 ~ 45
CO2 Sensor - Apply to RA duct
- Boundary : 0 ~ 2000ppm EBR52358911 76k 5.4 22.2 50 ~ 64
EBR52358912 96k 6.3 28.1 64 ~ 72
EBR52358914 115k 7.3 33.7 72 ~ 88
Smoke Detection Sensor - Power : AC 24V, From : Contact point type - Apply to RA duct
EBR52358915 134k 8.5 39.3 88 ~ 103
EBR52358916 153k 9.5 45.4 103 ~ 116
Note : Boundary of specification can be changed through LGAV software. However, please make a specification referring to the above table
EBR52358917 172k 10.5 50.4 114 ~ 129
EBR52358913 192k 11.2 56.2 121 ~ 137
* Evaporator Saturated Temperature = 6oC, Air Temperature = 27oC DBT / 19oC WBT
* Heat exchanger volume (m3) : Pipe cross-section x Tube length
- Pipe cross-section (m2) = π x ID2 / 4
- Tube length (m) = Tube length of 1 pipe x Tube step x Tube row

274 275
ACCESSORIES
OTHER INTERRATION CONTROL SOLUTION

AHU KITS
Solution to connect LG outdoor unit on the DX coil of an air handing unit,
with LG’s high efficient products for maximum cost saving

Installation Scene Application


Simple Control with PUCKA0 Optional
Simple Control with PUCKA0
SINGLE SPLIT AHU (Field Supply) PUCKA0 Wired Remote Centralized Controller DDC (Field Supply) + Refrigerant Piping Wired Remote Comm. Kit Dry contact
Controller Dry Contact Communication Wire Controller PUCKA0 (option) *DDC
Sensor Signal
Expansion Valve
* DDC : Digital Direct Controller
is not Required *DDC

Return Exhaust Outdoor Supply


Simple Control with PUDCA0 Air Air Air Air

SINGLE SPLIT AHU (Field Supply) PUDCA0 Wired Remote DDC (Field Supply)
Controller
Expansion Valve
is not Required

(Monitoring Only)

Simple Control with PRCKA1


MULTI V AHU (Field Supply) PRCKA1 EEV Kit Wired Remote Centralized Controller DDC (Field Supply)+
or TXV Kit Controller Dry Contact
IO module

Simple Control with PUDCA0


Simple Control with PRDCA0 Refrigerant Piping
Wired Remote
Controller
Comm. Kit
PUDCA0
Communication Wire
(Monitoring Only)
Sensor Signal *DDC
MULTI V AHU (Field Supply) PRDCA0 EEV Kit Wired Remote DDC (Field Supply) AI (Analog Input) 0 ~ 10V
or TXV Kit Controller * DDC : Digital Direct Controller DI (Digital Input)
*DDC
DO (Digital Output)

(Monitoring Only)
Return Exhaust Outdoor Supply
Air Air Air Air

Various Control with Control Kit


MULTI V TXV Kit Only

AHU (Field Supply) Control Kit Centralized


Controller

Sensors and
Actuators are
Required According
MULTI V TXV Kit Only to Control Function

276 277
ACCESSORIES
OTHER INTERRATION CONTROL SOLUTION

AHU KITS
Solution to connect LG outdoor unit on the DX coil of an air handing unit,
with LG’s high efficient products for maximum cost saving

Application Application
Simple Control with PRCKA1 – EEV Kits + Indoor Units Simple Control with PRDCA0 – Single EEV Kit or TXV Kit
Wired Remote Comm. Kit Dry contact Comm. Kit
Refrigerant Piping Refrigerant Piping
Controller PRCKA1 (option) *DDC Wired Remote PRDCA0
Communication Wire Communication Wire Controller
Sensor Signal Sensor Signal (Monitoring Only) *DDC
AI (Analog Input) 0 ~ 10V
* DDC : Digital Direct Controller * DDC : Digital Direct Controller
DI (Digital Input)

DO (Digital Output)
Return Exhaust Outdoor Supply
Air Air Air Air Return Exhaust Outdoor Supply
Air Air Air Air

EEV kit
EEV Kit

TXV Kit

or

Various Control with Control kit – Multiple MULTI Vs + TXV Kits


Refrigerant Piping
Communication Wire
Thermistor (Pipe Temp.)
Signal (On / Off)
Signal (DC 0 ~ 10V)
Simple Control with PRCKA1 – Single TXV Kit (without Indoor Unit) Air Handling Unit Expansion Kit
Temperature Sensor
Wired Remote Comm. Kit Dry contact - Return Air, Supply Air (Essential)
Refrigerant Piping
Controller PRCKA1 (option) *DDC - Mixed Air
Communication Wire
Sensor Signal Temp & Humidity Sensor
* DDC : Digital Direct Controller - Return Air / Supply Air / Outdoor Air

Damper Actuator
- Exhaust Air / Outdoor Air / Mixed Air
Return Exhaust Outdoor Supply
Air Air Air Air Differential Pressure Switch

Valve for Humidifier

Control Kit
CO2 Sensor

Smoke Detector
TXV Kit

Fan
- Supply / Return

Wired Remote Controller


Local Control Kit

278 279
ACCESSORIES
MECHANICAL ACCESSORIES MECHANICAL ACCESSORIES

LINE-UP AUTO ELEVATION GRILLE


Easy filter cleaning with the elevation grille

Indoor Outdoor PTEGM0


Ceiling Mounted Cassette Ventilation MULTI V
Auto Elevation Grille Cassette Panel CO2 Sensor Air Guide

PTEGM0 4 Way Cassette PES-C0RV0 AHCS100H0 PRAGX3S0 / PRAGX2S0


(Compact panel) PT-QCHW0
Cassette Cover Refrigerant Leakage Detector F7 Filter Drain Pan
PTDCM / PTDCQ
Plasma Kit
PTPKM0 / PTPKQ0
Ventilation Kit
PTVK410 4 Way Cassette PRLDNVS0 AHFT035H0 PRODX20 / PRODX30 /
PTVK420
PTVK430
PT-UQC / PT-UMC1
2 Way Cassette
AHFT050H0
AHFT100H0
PHDPA (THERMA V)
Features
PT-HLC, PT-USC
1 Way Cassette (Grill Type) Easy Filter Cleaning with Elevation Grill
PT-UUC / PT-UUC1 / PT-UTC
(Panel Type)
- Installation inside main body - Auto horizontal control - 4 points support structure
PT-UUD / PT-UTD - Memory for user’s level - Max 4.5m length - Model : PTEGM0 (for chassis TM, TN, TP)
Ceiling Concealed Duct Etc.
4-Point Support Structure Auto Horizontal Control Memory for user’s Level Auto Bottom Detection
Drain Pump Kit Built-in Duck Kit Independent Power Module

STOP

ABDPG / PBDP9 Suction Grille PRIP0


PBSGB30 / PBSGB40 Operating with wired remote controller* and wireless remote controller included in PTEGM0.
EEV Kit IR Receiver * PREMTB001, PREMTBB01

Canvas PRG PWL


Models Applied
PBSC30 / PBSC40
• 4 Way Cassette : Refer to PDB for applicable models

Parts Included
• Inlet Grille (1EA) • Screws (4EA)
• Auto Elevation Grille Kit (1EA) • Installation Manual (1EA)
• Wireless Remote Controller (1EA)
Mechanical Accessories Line up and Application
Type 1 Type 2 SINGLE SPLIT MULTI MULTI V THERMA V Remark
Auto Elevation Grille
Cassette Panel


-



-
-
4-Way Cassette
4-Way / 2-Way / 1-Way Cassette
Application
Cassette Cover • • • - 4-Way Cassette
Ventilation Kit • • • - 4-Way Cassette
Plasma Kit • • • - 4-Way Cassette
Suction Grille / Canvas - - • - Ceiling Concealed Duct (Built-in)
INDOOR • •
Drain Pump Kit - - Ceiling Concealed Duct
Refrigerant Leakage Detection Kit - - • - MULTI V 4th Generation Indoors
Independent Power Module - - • - MULTI V Indoor
CO2 Sensor - - • - Energy Recovery Ventilator
EEV Kit - - • - MULTI V Indoors Auto elevation grille kit Install the kit inside Install the front panel Operate the auto elevation Easy maintenance
IR Receiver • • • - Ceiling Concealed Duct indoor unit and the Inlet grille grille by the wireless remote
Air Guide - - • - MULTI V IV
OUTDOOR controller
Drain Pan - - • • MULTI V IV / THERMA V
* Only for chassis TM, TN, TP
280 281
ACCESSORIES
MECHANICAL ACCESSORIES MECHANICAL ACCESSORIES

CASSETTE PANEL CASSETTE COVER / PLASMA KIT


Stylish designed panels make more unique space by various applications Air purifying filter to prevent dust and allergens Air purifying filter to repel dust and allergens

4 Way Cassette PTDCM / PTDCQ PTPKM0 / PTPKQ0


PT-QCHW0
PT-UQC / PT-UMC1
2 Way Cassette
PT-HLC / PT-USC
1 Way Cassette (Grill Type)
PT-UUC / PT-UUC1 / PT-UTC
(Panel Type)
PT-UUD / PT-UTD

Features Features Features


• Independent vane operation uses separate motors, making it Possible to control all four vanes independently. • Specially designed for indoor unit It can remove microscopic contaminants such as
• The detachable corner design makes it easy to adjust the hanger during installation and to check for leakages • Covers the side area of cassette dust and pollen to help reduce allergies.
in the drain connection pipe. • Gives elegant looks * Plasma kit and Auto Elevation Grille are not applicable at the same time

• Light weight
Compact and Stylish Design
• New 4 way cassette panel adapted unibody shape and matching with into the ceiling
nel si e is fi in o he eiling ile Models Applied Models Applied
• 4 Way Cassette (for chassis TP, TN, TM, TQ, TR) Type SINGLE SPLIT MULTI SPLIT MULTI V
Unibody Option
Shape 620m
m (2.5 / 3.5 / 5.0kw :
(No Inlet Line) Option
4 Way Cassette PTPKQ0) Built-in
(1.5 / 2.1kw : PTPKQ0)
(7.1kw ~ 15.0kw :
PTPKM0)
2 Way Cassette - - -
1 Way Cassette - Built-in Built-in
620m
m

Specifications Parts Included Parts Included


Dimension (mm) Applied model
• Cover A (4EA), Cover B (4EA) • Plasma Kit (1EA)
Color Weight
Model name Suction Type Gloss • Cover C (4EA), Cover D (4EA) • Screws
(RAL) (kg) W H D SINGLE SPLIT MULTI SPLIT MULTI V
PT-QCHW0 Horizontal Grill
Morning Fog
(RAL 120-4) X 3.0 620 20 620 2.5 ~ 5.0kw 2.5 ~ 5.0kw 1.5 ~ 5.0kw • Screws • Installation Manual (1EA)
4-Way PT-UQC Horizontal Grill
Morning Fog
X 3.0 700 22 700 2.5 ~ 5.0kw 1.5 ~ 5.0kw 1.5 ~ 5.0kw • Installation Manual (1EA)
(RAL 120-4)
Morning Fog
PT-UMC1 Horizontal Grill (RAL 120-4) X 5.6 950 25 950 7.1 ~ 15.0kw 7.1kw 7.1 ~ 14.0kw
Morning Fog
PT-HLC Grill (RAL 120-4) X 4.0 1,050 28 640 - - 5.0 ~ 7.1kw
2-Way
PT-USC Grill
Morning Fog
(RAL 120-4) X 4.7 1,100 33 690 - - 5.0 ~ 7.1kw Accessory Model Name
Noble White
PT-UUC Grill (RAL 110-1) O 4.6 1,100 34 500 - - 2.1 ~ 3.5kw
Morning Fog Weight (kg) Dimensions (mm)
PT-UUC1 Grill X 4.4 1,100 34 500 2.5 ~ 3.5kw 2.5 ~ 3.5kw Model Front Panel
(RAL 120-4) NET Gross W H D
Noble White TP / TN 5.9 8.8 1,157 1,157 268
1-Way PT-UTC Grill (RAL 110-1) O 5.5 1,420 34 500 - - 5.0 ~ 7.1kw PT-UMC /
PTDCM
Noble White PT-UMC1 TM 5.9 8.8 1,157 1,157 310
PT-UUD Panel (RAL 110-1) O 4.6 1,100 34 500 - - 2.1 ~ 3.5kw
- TR 5.0 7.2 907 907 268
Noble White PTDCQ
PT-UTD Panel (RAL 110-1) O 5.5 1,420 34 500 - - 5.0 ~ 7.1kw - TQ 5.0 7.2 907 907 310

282 283
ACCESSORIES
MECHANICAL ACCESSORIES MECHANICAL ACCESSORIES

VENTILATION KIT DRAIN PUMP KIT


Fresh air can be supplied from outside through this ventilation kit Drains away condensed water

PTVK410 ABDPG
PTVK420 PBDP9
PTVK430

Features Features
• The ventilation kit can be supplied air from outside. • In some places where natural drainage is not possible, a drain pump is very useful to pump out condensed water
from indoor units.
• Drain pump assembly (AC 220 ~ 240V, 50 / 60Hz)
Models Applied
There are 2 Solutions for Fresh Air Models Applied
- PTVK410+PTVK420 (for chassis TP, TN, TM) - PTVK430 (for chassis TR, TQ, TP, TN, TM)
* Users can purchase and use PTVK430 in addition to PTVK410+PTVK420 in need to phase in larger outdoor air volume.
• Ceiling Concealed Duct (Refer to PDB for applicable models)

Parts Included Accessory Model Name


Ceiling Concealed Duct (Refer to PDB for applicable models)
• PTVK410 : 1 Ventilation Kit, 8 Bolts, 1 Insulation • PTVK420 : 1 Flange, 7 Screws
• PTVK420 : 1 Flange, 4 Screws, 1 Insulation Product Model Drain Pump
H-INVERTER Included
CB**L Included
SINGLE / MULTI SPLIT Standard Inverter CM** / UM** ABDPG
Dimensions Assembly Diagram UB70 / UB85 PBDP9
Compact Inverter ABDPG
406
MULTI V Included

4 Application
81

13

High head drain pump automatically drains water up to 700mm of drain-head height.
840
443

435

It provides perfect solution for water drainage. Fixture

Drain Pipe Slope (1/50~1/100) Drain pipe

High Head Drain Pump


PTVK430
450mm

700mm
419
840 Flexible Drain Hose

300mm
55mm
* Included in H-Inverter
PTVK410+PTVK420 * Supplied as accessory for Standard Inverter (ABDPG/ PBDP9)

284 285
ACCESSORIES
MECHANICAL ACCESSORIES

SUCTION GRILLE / CANVAS


High flexibility for a wide variety of applications

SUCTION GRILLE
PBSGB30 / PBSGB40
CANVAS
PBSC30 / PBSC40

Features Dimensions
igh e e n l s i ess e ili es ni se wi h e i le d s o ying leng hs
• When using suction grille, unit requires only 270mm of ceiling space
• Blends unobtrusively with any interior decoration
C C C

A
Models Applied B
B
A
B
A

• Ceiling Concealed Duct _ Built-in type (Unit : mm) (Unit : mm)

Model Name A B C Model Name A B C


PBSGB30 910 359 56 PBSC30 821 274 42 ~ 250

Compatibility
PBSGB40 1,188 359 56 PBSC40 1,100 274 42 ~ 250

Capacity (Btu/h)
Category Model Name
ARNU07GB3G4 ARNU09GB3G4 ARNU12GB3G4 ARNU15GB3G4 ARNU18GB4G4 ARNU24GB4G4

Grille
PBSGB30 • • • • - - Application
PBSGB40 - - - - • •
Canvas
PBSC30 • • • • - -
PBSC40 - - - - • •

over 270mm
over 520mm

Parts Included
• For the Suction Grille :
- Suction panel with air filter (1EA) - Suction panel fix bolt M5x18 (4EA) - Installation manual (1EA)

• For the Suction canvas :


- Air suction canvas (1EA) - Screws for air suction canvas (4EA) - Adjusting chain (4EA)
- Screws for adjusting chain (8EA) - Installation manual (1EA)

286 287
ACCESSORIES
MECHANICAL ACCESSORIES

CO2 SENSOR
CO2 sensor in ventilation system.

PES-C0RV0 AHCS100H0

Features Features
• Specification • Description • Specification • Operation Table
• Applied Model : ERV, ERV DX The product is especially designed to detect CO2 concentration in ERV system. • Applied Model : ERV, ERV DX
CO2 Sensor Reading ERV Fan Operation
• Function • Supply voltage : DV12V 5%
- Supply Vottage : DV 12V 5% • Operation Table • Output : 0.6 ~ 4.4V (Linear output, 240 ~ 1,760 ppm CO2) <500ppm Off

• Accuracy : 10% (2 days after installation) 500 ~ 700ppm Low Speed


- Output : 0 ~ 5V CO2 Sensor Reading ERV Fan Operation
700 ~ 900ppm High Speed
(Linear output, 1 ~ 2,000ppm CO2) <500ppm Off • Description >900ppm Super High Speed
- Accuracy : 30ppm 5% of reading 500 ~ 700ppm Low Speed • The product is especially designed to detect CO
700 ~ 900ppm High Speed
• This model requires Standard III Wired Remote Controller for display
>900ppm Super High Speed

Installation Scene Installation Scene

Standard Wired CO2 Sensor CO2 Sensor (AHCS100H0) Standard III Wired
Remote Controller (PES-C0RV0) Install inside of ERV Remote Controller
CO2 (ppm)

CO2 (ppm)
Windows Windows Windows Windows Windows Windows Windows Windows
Closed Open Closed Open Closed Open Closed Open
2,500 2,500

1,000 1,000

0
ERV with CO2 Concentration Control 0
ERV with CO2 Concentration Control
Time (min) Time (min)

288 289
ACCESSORIES
MECHANICAL ACCESSORIES MECHANICAL ACCESSORIES

F7 FILTER REFRIGERANT LEAKAGE DETECTOR


F7 filter for ventilation system R410A refrigerant leakage detector makes our space safer

AHFT035H0 PRLDNVS0
AHFT050H0
AHFT100H0

Specification Features
For ERV • This detector senses refrigerant leakage and when the refrigerant concentration exceeds 6,000ppm not only
Filter Model AHFT035H0 AHFT050H0 AHFT100H0 AHFT100H0
it will stop indoor unit operation, but also it will give an alarm using buzzer and sensor LED.
Product Model LZ-H025GBA4 LZ-H035GBA4 LZ-H050GBA4 LZ-H080GBA4 LZ-H100GBA4 LZ-H150GBA4 LZ-H200GBA4 (The green and red LED lights blink simultaneously.)
W 423.5 423.5 425 520 520 520 520 • Alarm is “ON” over 6,000ppm has been maintained 5 seconds, and on the contrary to this,
Dimension H mm 132 132 194 192 192 192 192 Alarm is “OFF” under 6,000ppm has been maintained 5 seconds.
D 25 25 25 25 25 25 25 • When the alarm of the refrigerant leak detector is switched on the user must ventilate until the alarm is disabled.
Quantity EA 2 2 2 2 2 4 4 he de e o h s o e ins lled inside he oo nd i n e ins lled o oo
* 2 pieces in 1 filter package

For ERV DX
Specifications
Filter Model AHFT100H0 Parts Specifications
Product Model LZ-H050GXH4 LZ-H080GXH4 LZ-H100GXH4 LZ-H050GXN4 LZ-H080GXN4 LZ-H100GXN4 Rated Voltage (V) DC 5.0 5%
W 520 Dimensions (W x H x D, mm) 31 x 44 x 20
Dimension H mm 192 Weight (g) 22
Detectable Refrigerant R410A
D 25 Sensor
Detected Concentration (ppm) 0 / 6,000 Alarm Off / On
Quantity EA 2
Operating Temperature Range (oC) -10 ~ 50
* 2 pieces in 1 filter package
Preserved Temperature Range (oC) - 40 ~ 60
Average Power Consumption (mA) 35

Installation Connecting Cable Cable Length (m) 10

2
Dimensions of Front Plate (W x H x D, mm) 80 x 110 x 44.6
1 Sensor Protective Cover
Dimension of Backplate (W x H x D, mm) 80 x 110 x 6.5

Application

3 Stop Operation and


Ring Alarm
2 Senses Refrigerant Leakage
1. Please check the direction of the filter’s label.
2. Insert the filters on the right upper side of the total heat exchanger.
* Maintain once every 6 months. 1 Refrigerant Leakage
* The part and standard of installation is designed for LG product, it is not allowed them to adapt non - LG product.

290 291
ACCESSORIES
MECHANICAL ACCESSORIES MECHANICAL ACCESSORIES

EEV KIT IR RECEIVER


MULTI V EEV KIT is specially designed to reduce noise and make comfort environment IR RECEIVER can be connected to CCD where the customer wants to control by wireless remote controller

PRGK024A0 PWLRVN000

Features Features
• Decreasing noise level of Multi V Indoor units Easy installation • Designed for wireless control to operate Ceiling concealed duct Operation of Indication lamp (3 colors)
Self-diagnosis function

Models Applied
• Ceiling Cassette (up to 15kBtu)
• Wall mounted (up to 24kBtu)
• Ceiling concealed duct (up to 18kBtu)
• Console (up to 15kBtu)
Models Applied
• Floor Standing Unit (with case / without case) (up to 15kBtu) • MULTI V Indoors (Ceiling concealed duct, Floor standing units)
• Convertible (up to 12kBtu, Ceiling Suspended Type is not able to connect this Kit)
* Fresh Air intake Unit is not able to connect this Kit

Application Application

Note : If you don’t use EEV of same specification, Cooling (Heating) capacity may decrease. Note : Do not install both the IR Receiver and Wired Remote Controller. This may cause malfunctions.

292 293
ACCESSORIES
MECHANICAL ACCESSORIES MECHANICAL ACCESSORIES

INDEPENDENT POWER MODULE AIR GUIDE


EEV full close function in case of power cut Air discharge in difficult to access areas

PRIP0 PRAGX*S0

PRAGX2S0 PRAGX3S0
(8 / 10 / 12HP) (14 / 16 / 18 / 20HP)

Features Features 564


33

00
R6

512
Independent Power Module is specially designed to close the Indoor EEV at power cut-Off. Con e s e i l dis h ge in o ho i on l dis h ge ns ll ion e i ili y

512
- Supply Voltage : DC 12V 50% • Direction of air discharge can be changed by simple installation 632
50 652 • Designed for outdoor discharge air

45
618

Models Applied
0
60

Models Applied 564


33

652
• MULTI V IV 00

50
R6
• MULTI V Indoors

512
* In case of UX3, must purchase 2 units of PRAGX3SO.

512
570

50 652
632

45
Dimensions618

60
0
900
564
33
3 Phase R6
00
Model Name Gross Weight Net Weight

500

500
400V

652

512
PRAGX2S0 22.5kg 12.3kg

512
50
Outdoor Unit PRAGX3S0 832
17kg 9.4kg

50
45
760
570
Independent Power Module (Option) 50

• MULTI V IV (UX2) • MULTI V IV (UX3)


632

45
Switch BOX
4th 832
1 Phase Main Switch
618

718 564
33 0
60
220V Power Plug
900 564
33

3rd 00 00
R6 00 R6

652
512
762
2nd

500

500
A/C 1st R6

512

512
512
Switch

50
Each room 50 652
832 50 652

50
632

45

45
760 904 570

45
632

45
618
618
832 0

Application
0
0 6
Independent Power Module (Option) 60
718
Switch BOX 900

652
652
Main Switch
• MULTI V IV (UX2) • MULTI V IV (UX3)
762

Power Plug

500

500
50
50
3rd - ARU*080LTE4 - ARU*140LTE4
570
570
2nd A/C 1st
Switch
- ARU*100LTE4
904 - ARU*160LTE4
45

832

50
45
Each room - ARU*120LTE4 - ARU*180LTE4
* N : Heat Pump / B : Heat Recovery - ARU*200LTE4
900
900 832
* N : Heat pump / B : Heat recovery
0
60 718
00 R
R6

500

500
500

500

762
294 832
295

50
45
832 760

50
45
760

904

45
832
ACCESSORIES
MECHANICAL ACCESSORIES

DRAIN PAN
Easy drain installation

PRODX20 (MULTI V IV) / PRODX30 (MULTI V IV)


PHDPA (THERMA V)

Features
This unit can be applied for outdoor unit’s drain.

Installation

* Tuck drain pan below base pan

Service Valve

Drain Pipe

* In case of the installation of drain pan, drain pipe should be located below the SVC valve.

* Push drain pan in the direction of the arrow. • This unit does not cover water drops of the outside product.
Brackets can be fixed on the side panel.
• Connect drain hose to drain pipe for drain condensate.

Accessory Model Name


Model Name Width x Length Remark
PRODX20 920mm x 466mm MULTI V IV (8 / 10 / 12HP)
PRODX30 1,240mm x 466mm MULTI V IV (14 / 16 / 18 / 20HP)
PHDPA (AWHP) 478mm x 190mm

296 297
ACCESSORIES
PIPING ACCESSORIES PIPING ACCESSORIES

LINE-UP Y BRANCH AND HEADER BRANCH


Refrigerant distribution channel

SINGLE SPLIT MULTI SPLIT MULTI V ETC 2 UNITS


PMUB11A
Y Branch and Header Branch Branch Distributor Heat Recovery Unit Refrigerant Charging Kit
(Synchro) 3 UNITS
PMUB111A
4 UNITS
PMUB1111A

PMBD3620 PRHR022 PRAC1 Gas Pipe Liquid Pipe


PMBD3630 PRHR032
PMBD3640 PRHR042
Y Branch and Branch Kit Y Branch and Header Branch Stopper Valve
Features
2 Units
PMUB11A
3 Units
• Various Y Branch pipes of different capacities make installation easier
PMUB111A • Y Branch and header branch for both gas and liquid are provided
4 Units
PMUB1111A • Insulation material is also provided for covering the branches

2 Units
PMBL3620
PRVT120
PRVT780
Models Applied
PMBL5620 PRVT980
2 Units • H-inverter : 10.0 / 12.5 / 13.4kw
PMBL1203F0
• Standard inverter : 12.5 / 14.0 / 15.0 / 20.0 / 25.0kw
Drain Hose

Application

PHDHA05T
PHDHA07T
PHDHA05B
PHDHA07B

2 Branch 3 Branch 4 Branch

Mechanical Accessories Line up and Application Accessory Model Name


Model name SINGLE SPLIT MULTI MULTI V Remark Model name SINGLE SPLIT Remark
Y Branch and Header Branch (Synchro) • - - - 2 Units PMUB11A 50:50 (1:1)
3 Units PMUB111A 33:33:33 (1:1:1)
Branch Distributor (MULTI) - • - MULTI F DX systems
4 Units PMUB1111A 25:25:25:25 (1:1:1:1)
Y Branch and Branch Kit (MULTI) - • - MULTI F DX systems
Heat Recovery Unit (MULTI V) - - • MULTI V Sync II / MULTI V III Heat Recovery / MULTI V IV Heat Recovery
Y Branch and Header Branch (MULTI V) - - • Various type of MULTI V Series a b c Type
A Ø15.88 (5/8) Ø19.05 (3/4) Ø25.4 (1) 1
Ø9.52 (3/8) Ø12.7 (1/2)
B - 2
Ø12.7 (1/2) Ø15.88 (5/8)
C Ø6.35 (1/4) Ø9.52 (3/8) - 2
D Ø9.52 (3/8) Ø12.7 (1/2) - 2

298 299
ACCESSORIES
PIPING ACCESSORIES PIPING ACCESSORIES

BRANCH DISTRIBUTOR DISTRIBUTOR BOX Y BRANCH AND BRANCH KIT MULTI F DX


Effective way of distributing refrigerant Refrigerant distribution channel

PMBD3620 2 UNITS
PMBD3630 PMBL3620 / PMBL5620
PMBD3640
2 UNITS
PMBL1203F0

Features Features
• Distribution of refrigerant to various indoor units • Internally insulated (Prevents any chances of drainage) • Y Branch and Branch kit make Multi F DX installation easier
• 3 models (2, 3, 4 indoor units) • Flare joints for easy and clean installation • Y Branch and Branch kit for both gas and liquid are provided
• Consists of LEVs inside it • Compact design (Low height) • Insulation material is also provided for covering the branches
• Controlling PCB inside the unit • Flexible installation

Models Applied Models Applied Parts Included


• MULTI F DX systems (refer to PDB for applicable models) • Y Branch for gas side and liquid side (1set)
• MULTI F DX systems (Refer to PDB for applicable models) • Installation manual (1EA)

Parts Included Application


• BD (Banch Distributor) unit (1EA) • Brackets (4EA)
• Screws (8EA) • Installation Manual (1EA)

Models Applied
Model Name PMBD3620 PMBD3630 PMBD3640
Connectable Indoor Units Number of Indoor Units 1~2 1~3 1~4
Capacity (Btu/hr) 5k / 7k / 9k / 12k / 18k / 24k 5k / 7k / 9k / 12k / 18k / 24k 5k / 7k/9k / 12k / 18k / 24k
Casing Colour Paintingless Paintingless Paintingless
Power Source
Power Consumption
Ø / V / Hz
(W)
1 / 220-240 / 50
10
1 / 200-240 / 50
10
1 / 200-240 / 50
10 Accessory Model Name (Unit : mm)
Running Current (A) 0.05 0.05 0.05
No. of Branch Specifications
Dimensions (W x H x D) (mm) 302 x 143 x 252 302 x 143 x 252 302 x 143 x 252 Model Name Applicable Model
Distribution Units Gas Liquid
Packing Dimensions (W x H x D) (mm) 422 x 202 x 300 422 x 202 x 300 422 x 202 x 300
Net Weight 4.8 4.9 5.0 ØØ
15.88 ØØ
15.88 ØØ
6.35
6.35
ØØ
6.35
6.35
15.88 15.88
Indoor Unit No. x mm² 4 x 0.75 4 x 0.75 4 x 0.75 PMBL3620 2 units Only 3ø, 36k Btu/h
Connecting Cable ØØ
15.88
15.88
ØØ
6.35
6.35
Outdoor Unit No. x mm² 4 x 0.75 4 x 0.75 4 x 0.75
Piping Connection liquid (mm) 9.52 9.52 9.52
(Outdoor Unit) ØØ15.88
15.88 ØØ15.88
15.88 ØØ6.35
6.35 ØØ6.35
6.35
Gas (mm) 19.05 19.05 19.05 PMBL5620 2 units 1ø, 3ø
Piping Connection Liquid (mm) 6.35 x 2 6.35 x 3 6.35 x 4 ØØ
19.05
ØØ19.05
Ø
15.88
15.88 ØØ
9.52
9.52
ØØ6.35
ØØ
6.35
9.52
9.52
19.05 Ø 19.05
(Indoor Unit) Gas (mm) 9.52 x 2 9.52 x 3 9.52 x 4
ØØ
19.05 ØØ
9.52
9.52
19.05
Hanger (EA) 4 4 4
Parts Screw (EA) 8 8 8 PMBL1203F0 3 units 1ø, 3ø
Ø 9.52 Ø 9.52
Manual (EA) 1 1 1 ØØ19.05
19.05
Ø 19.05 Ø 19.05 ØØ19.05
19.05 Ø 9.52
ØØ9.52
9.52 ØØ9.52
9.52
Ø 9.52

ØØ19.05
19.05 ØØ9.52
9.52
300 301
ACCESSORIES
PIPING ACCESSORIES

HEAT RECOVERY UNIT

PRHR022 (2 branch Unit)


PRHR032 (3 branch Unit) Reducers for Indoor Unit and HR Unit
(Unit : mm)
PRHR042 (4 branch Unit)
Model Name Liquid High pressure Low pressure

Indoor Unit Reducer

PRHR022

Features
HR Unit Reducer
• Max. 32 indoor units can be connected (Max. 8 indoor units per branch)
• It is easy to install due to the automatic search algorithm for piping detection
S ooling y le in ni es he sys e e fi ien y i PRHR032 /
PRHR042

Models Applied
• MULTI V 5 • MULTI V IV Heat Recovery • MULTI V III Heat Recovery
• MULTI V SYNC II • MULTI V SYNC • MULTI V WATER IV Heat Recovery Convenient Free Zoning
• MULTI V WATER II Heat Recovery
e e o e y o ides e i le on ol o e
individual zones for the user’s convenience
Specifications • Individual Control
Office Kitchen

Model name PRHR022 PRHR032 PRHR042 - Perfect individual control over spaces ventilation needed
Number of Branch EA 2 3 4
Maximum Connectable Capacity of Indoor Units (Per branch / unit) kW 16 / 32 16 / 48 16 / 58
• Zone Control
Maximum Number of Connectable Indoor units per Branch EA 8 8 8
- Max. of 8 indoor units can be connected for one branch
Cooling kW 0.026 0.040 0.040
- Max. of 32 indoor units can be connected for one HR unit
Nominal Input - Same opeational model can be operated by indoor units
Heating kW 0.026 0.040 0.040
Net. Weight kg 18 20 22 with zone control function installed
Dimensions (W x H x D) mm 801 x 218 x 617 801 x 218 x 617 801 x 218 x 617
Liquid mm (inch) 9.52 (3/8) 9.52 (3/8) 9.52 (3/8)
• Combination of Individual and Zoning Installations Room
Indoor Unit
Gas mm (inch) 15.88 (5/8) 422 x 202 x 300 422 x 202 x 300
- Flexible piping design
Piping Liquid mm (inch) 9.52 (3/8) 15.88 (5/8) 15.88 (5/8)
connections
Outdoor Unit Low pressure mm (inch) 22.2 (7/8) 28.58 (11/8) 28.58 (11/8)
• Save Product and Installation Cost IT Room

High Pressure mm (inch) 19.05 (3/4) 22.2 (7/8) 22.2 (7/8)


[ Zoning Control]
Power supply Ø / V / Hz 1 / 220~240 / 50 1 / 220~240 / 50 1 / 220~240 / 50
HR Unit

Parts Included Zoning Control (Max Indoor Unit 8EA)

• HR unit (1EA) • Hanging bolts M10 or M8 (4EA) • Nut M8 or M10 (8EA)


• Washers M10 (8EA) • Reducers

302 303
ACCESSORIES
PIPING ACCESSORIES

Y BRANCH AND HEADERBRANCH


For refrigerant distribution of indoor units

Y Branch
Header Branch

Features Details of Model Name


• Various Y Branch pipe of different capacities make MULTI V installation much easier. Header Branch
• Y Branch and header branch for both gas and liquid are provided. R410A
• Insulation material is also provided for covering the branches.
(Unit : mm)

Model Name Gas Pipe Liquid Pipe

Piping Diagram
4 Branch /
Heat Pump System Heat Recovery system ARBL054

Y branch for Header for Y branch for


indoor units (2 pipes) indoor units (2 pipes) Heat Recovery units (3 pipes)
7 Branch /
ARBL057
HR unit
Y Branch for Heat Pump Y branch for Heat Recovery
Outdoor Units (2 Pipes) outdoor units (3 pipes)
Y branch for
Zoning control (2 pipes)
HR unit 4 Branch /
ARBL104

Models Applied 7 Branch /


ARBL107

• MULTI V 5 • MULTI V WATER II


• MULTI V IV • MULTI V WATER S
• MULTI V III, MULTI V PLUS II, MULTI V PLUS • MULTI V SPACE II
• MULTI V S • MULTI V MINI 10 Branch /
ARBL1010
• MULTI V WATER IV

10 Branch /
ARBL2010

304 305
ACCESSORIES
PIPING ACCESSORIES

PIPING ACCESSORIES
Y Branch pipe for connection of outdoor units

Heat Pump Heat Recovery


R410A MULTI V 5, MULTI V IV, MULTI V III, MULTI V WATER IV, MULTI V WATER II R410A MULTI V 5, MULTI V IV Heat Recovery, MULTI V III Heat Recovery, MULTI V WATER IV Heat Recovery,
MULTI V WATER II Heat Recovery

(Unit : mm) (Unit : mm)

2 Outdoor Units 2 Outdoor Units


Model Name High Pressure Gas Pipe Liquid Pipe Model Name High Pressure Gas Pipe Liquid Pipe Low Pressure Gas Pipe
Liquid Pipe High Pressure Gas Pipe Liquid Pipe High Pressure Gas Pipe
Low Pressure Gas Pipe Liquid Pipe High Pressure Gas Pipe Low Pressure Gas Pipe Liquid Pipe High Pressure Gas Pipe Low Pressure Gas Pipe Liquid Pipe

O.D.15.88 I.D. 19.05 O.D. 22.2 I.D. 19.05 O.D.15.88 I.D. 19.05 O.D. 22.2 I.D. 19.05 O.D.15.88 I.D. 19.05 O.D. 22.2 I.D. 19.05 O.D.15.88 I.D. 19.05 O.D. 22.2 I.D. 19.05 O.D.15.88 I.D. 19.05
I.D.22.2 O.D. 28.58 I.D.34.9 I.D.22.2 O.D. 28.58 I.D.34.9 I.D.22.2 O.D. 28.58 I.D.34.9
331 331 331 331 331
314 314 416 314 416 314 416 314
416 416 416 416
I.D.15.88 I.D.15.88 I.D.15.88 I.D.15.88 408 I.D.15.88 I.D.15.88 408 I.D.15.88 I.D.15.88 408 I.D.15.88 I.D.15.88
408 408 408 408
I.D.28.58 I.D.28.58 I.D.28.58 I.D.28.58 I.D.28.58 I.D.28.58
I.D.28.58 I.D.28.58 I.D.28.58 I.D.28.58 I.D.28.58 I.D.28.58 I.D.28.58 I.D.28.58

I.D.19.05 I.D.12.7 I.D.9.52 83 I.D.19.05 I.D.12.7 I.D.9.52 83 I.D.19.05 I.D.12.7 I.D.9.52 83 I.D.19.05 I.D.12.7 I.D.9.52 83 I.D.19.05 I.D.12.7 I.D.9.5
111 111 111
ARCNN21 I.D.31.8 I.D.34.9
I.D.22.2 111
I.D.31.8 I.D.34.9
I.D.22.2 111
I.D.31.8 I.D.34.9
I.D.22.2
ARCNB21 I.D.31.8 I.D.34.9
I.D.22.2 111
I.D.31.8 I.D.34.9
I.D.22.2
I.D.31.8 I.D.34.9
I.D.22.2 111
I.D.31.8 I.D.34.9
I.D.22.2

I.D.22.2 O.D.19.05 I.D.22.2 O.D.19.05 I.D.22.2 O.D.19.05 I.D.22.2 O.D.19.05 I.D.22.2 O.D.19.05
I.D.12.7 I.D.15.88 I.D.12.7 I.D.15.88 I.D.41.3 I.D.38.1 O.D.34.9 I.D.12.7 I.D.15.88 I.D.41.3 I.D.38.1 O.D.34.9 I.D.12.7 I.D.15.88 I.D.41.3 I.D.38.1 O.D.34.9 I.D.12.7 I.

Liquid Pipe
O.D.12.7 I.D.9.52 High Pressure GasI.D.28.58
Pipe Liquid Pipe
O.D.12.7 I.D.9.52 High Pressure GasI.D.28.58
Pipe Low Pressure Gas Pipe
I.D.28.58
Liquid Pipe
O.D.12.7 I.D.9.52 High Pressure Gas Pipe
I.D.28.58
Low Pressure Gas Pipe
I.D.28.58
Liquid Pipe
O.D.12.7 I.D.9.52 High Pressure Gas Pipe
I.D.28.58
Low Pressure Gas Pipe
I.D.28.58
Liquid Pipe
O.D.12.7
70 70 70 70 70
130 130 130

O.D.28.58 I.D. 19.05 O.D.28.58 I.D. 19.05 O.D.28.58 I.D. 19.05 O.D.28.58 I.D. 19.05
I.D.22.2 I.D.22.2 O.D.15.88 I.D. 19.05 I.D.22.2 O.D.15.88 I.D. 19.05 I.D.22.2 O.D.15.88 I.D. 19.05
O.D.15.88 I.D. 19.05 O.D.15.88 I.D. 19.05 I.D.22.2
I.D.22.2 O.D. 28.58O.D.28.58
I.D.34.9 I.D.34.9 O.D.15.88 I.D. 19.05 O.D. 22.2 I.D. 19.05 I.D.22.2
I.D.22.2 O.D. 28.58O.D.28.58
I.D.34.9 I.D.34.9 O.D.15.88 I.D. 19.05 O.D. 22.2 I.D. 19.05 I.D.22.2
I.D.22.2 O.D. 28.58O.D.28.58
I.D.34.9 I.D.34.9 O.D.15.88 I.D. 19.05
O.D.15.88 I.D. 19.05 O.D. 22.2 I.D. 19.05 O.D.15.88 I.D. 19.05 O.D. 22.2 I.D. 19.05 331 331 331
416 314 416 314 416 314
331 331 416 416
408 I.D.15.88 I.D.15.88 408 I.D.15.88 I.D.15.88 408 I.D.15.88 I.D.15.88
314 416 314 416 408 408
I.D.28.58 I.D.28.58 I.D.28.58 I.D.28.58 I.D.28.58 I.D.28.58
I.D.15.88 I.D.15.88 408 I.D.15.88 I.D.15.88 408 I.D.28.58 I.D.28.58 I.D.28.58 I.D.28.58
I.D.28.58 I.D.28.58 I.D.28.58 I.D.28.58
I.D.19.05 I.D.12.7 I.D.9.52 83 I.D.19.05 I.D.12.7 I.D.9.52 83 I.D.19.05 I.D.12.7 I.D.9.5
I.D.22.2 111 I.D.22.2 111 I.D.22.2 111
I.D.19.05 I.D.12.7 I.D.9.52 83 I.D.19.05 I.D.12.7 I.D.9.52 83 I.D.41.3 O.D.34.9 I.D.22.2 111 I.D.41.3 O.D.34.9 I.D.22.2 111 I.D.41.3 O.D.34.9
I.D.22.2 O.D.28.58 I.D.34.9 I.D.22.2 O.D.28.58 I.D.34.9 I.D.31.8 I.D.34.9 I.D.31.8 I.D.34.9 I.D.31.8 I.D.34.9
111 O.D.34.9 I.D.28.58 O.D.34.9 I.D.28.58 O.D.34.9 I.D.28.58
O.D.19.05
I.D.15.88
I.D.12.7 O.D.19.05 I.D.22.2
I.D.31.8 I.D.34.9 416
I.D.22.2 111 O.D.19.05
I.D.15.88
I.D.12.7 O.D.19.05 I.D.22.2
I.D.31.8 I.D.34.9 416
I.D.22.2 Low Pressure Gas Pipe Liquid Pipe
I.D.22.2 O.D.19.05 High Pressure
I.D.31.8 I.D.34.9
Gas Pipe
I.D.22.2 O.D.28.58 I.D.34.9 Low Pressure Gas Pipe Liquid Pipe
I.D.22.2 O.D.19.05 High Pressure
I.D.31.8 I.D.34.9
Gas Pipe
I.D.22.2 O.D.28.58 I.D.34.9 Low Pressure Gas Pipe Liquid Pipe
I.D.22.2 O.D.19.05
408 408 I.D.41.3 I.D.38.1 O.D.34.9 O.D.19.05 I.D.12.7 O.D.19.05 I.D.22.2
I.D.12.7 I.D.15.88 I.D.41.3 I.D.38.1 O.D.34.9 O.D.19.05 I.D.12.7 O.D.19.05 I.D.22.2
I.D.12.7 I.D.15.88 I.D.41.3 I.D.38.1 O.D.34.9 O.D.19.05 I.D.12.7 O.D.19.05
I.D.12.7 I.
I.D.22.2 O.D.19.05
334 I.D.22.2 O.D.19.05
334 125 I.D.15.88 416 125 I.D.15.88 416 125 I.D.15.88
I.D.12.7 I.D.15.88 I.D.28.58 I.D.28.58 I.D.12.7 I.D.15.88 I.D.28.58 I.D.28.58 I.D.28.58 I.D.28.58 I.D.28.58 I.D.28.58 I.D.28.58
281 281 341 I.D.9.52 408 341 I.D.9.52 408 341
334 O.D.12.7 334 O.D.12.7 334 O.D.12.7
I.D.28.58 I.D.28.58 298 70 I.D.28.58 I.D.28.58 298 70 I.D.28.58 I.D.28.58 298 70
O.D.12.7 I.D.9.52 O.D.12.7 I.D.9.52 130 O.D.15.88 281 I.D. 19.05 130 O.D.15.88 281 I.D. 19.05 130 O.D.15.88 281 I.D. 19.05
70
I.D.31.8 I.D.34.9
I.D.22.2 111
3 Outdoor Units 70
I.D.31.8 I.D.34.9
I.D.22.2 111 I.D.22.2 O.D. 28.58 I.D.34.9
331
O.D. 22.2 I.D. 19.05 I.D.22.2 O.D. 28.58 I.D.34.9
3 Outdoor Units 331
O.D. 22.2 I.D. 19.05 I.D.22.2 O.D. 28.58 I.D.34.9
331
Liquid Pipe
I.D.22.2 I.D.19.05 I.D.19.05 83 High
I.D.41.3
Pressure Gas Pipe
I.D.38.1 O.D.34.9 I.D. 19.05
O.D.28.58
Liquid Pipe
I.D.22.2 I.D.19.05 I.D.19.05 83 High
I.D.41.3
Pressure Gas Pipe
I.D.38.1 O.D.34.9 I.D. 19.05
O.D.28.58
416
408
314
O.D.28.58
416
I.D.31.8 I.D.34.9 I.D.22.2
I.D. 19.05
I.D.22.2 111 416
408
314
O.D.28.58
416
I.D.31.8 I.D.34.9 I.D.22.2
I.D. 19.05
I.D.22.2 111 416
408
314
I.D.41.3 I.D.22.2 O.D.28.58
I.D.34.9I.D.34.9
111 I.D.15.88
O.D.15.88 I.D.15.88
I.D. 19.05 408 I.D.41.3 I.D.22.2 O.D.28.58
I.D.34.9I.D.34.9
111 I.D.15.88
O.D.15.88 I.D.15.88
I.D. 19.05 408 I.D.41.3 I.D.22.2 O.D.28.58
I.D.34.9I.D.34.9
111 I.D.15.88
O.D.15.88 I.D.15.88
I.D. 19.05
Model Name O.D.15.88 I.D. 19.05 High Pressure GasI.D.28.58
Pipe
I.D.22.2
LiquidI.D. 19.05
O.D.15.88 Pipe I.D.22.2
I.D.28.58
I.D.28.58 I.D.28.58
Model Name
I.D.22.2 I.D.19.05 I.D.19.05 83
High Pressure Gas Pipe
I.D.41.3 I.D.38.1 O.D.34.9 I.D.28.58 I.D.28.58
I.D.28.58
I.D.28.58
Liquid Pipe
I.D.22.2 I.D.19.05 I.D.19.05 83 I.D.41.3 I.D.38.1 O.D.34.9 I.D.28.58
I.D.28.58 Low Pressure Gas Pipe
I.D.28.58 I.D.28.58 I.D.22.2 I.D.19.05 I.D.19.05

I.D.15.88 I.D.12.7 130 I.D.15.88 I.D.12.7 130 I.D.19.05 I.D.12.7 I.D.9.52 83 I.D.28.58 I.D.19.05 I.D.12.7 I.D.9.52 83 I.D.28.58 I.D.19.05 I.D.12.7 I.D.9.5
I.D.22.2 111 I.D.22.2 111 I.D.22.2 111
I.D.28.58 I.D.22.2 111 I.D.28.58 I.D.22.2 111 I.D.28.58
O.D.22.2
I.D.28.58O.D.15.88 I.D. 19.05 O.D.22.2
I.D.28.58O.D.15.88 I.D. 19.05 I.D.31.8 I.D.34.9 I.D.15.88 I.D.12.7 130 I.D.31.8 I.D.34.9 I.D.15.88 I.D.12.7 130 I.D.31.8 I.D.34.9 I.D.15.88
I.D. 34.9
O.D. 22.2 I.D.O.D.28.58
19.05 I.D.22.2 I.D. 34.9
O.D. 22.2 I.D.O.D.28.58
19.05 I.D.22.2
I.D.53.98 I.D. 44.5 O.D.41.3 I.D.31.8 I.D.34.9 I.D.53.98 I.D. 44.5 O.D.41.3 I.D.31.8 I.D.34.9 I.D.53.98 I.D. 44.5 O.D.41.3
331 331 O.D.19.05
I.D.22.2O.D.22.2
I.D.28.58 I.D. 34.9 O.D.28.58 I.D.41.3
I.D.22.2 I.D.38.1 O.D.34.9 I.D.28.58 O.D.19.05
I.D.22.2O.D.22.2 I.D. 34.9 O.D.28.58 I.D.22.2 I.D.28.58 O.D.19.05
I.D.22.2O.D.22.2
O.D.15.88 I.D.19.05 O.D.15.88 I.D.19.05 I.D.41.3 I.D.38.1 O.D.34.9I.D.41.3 O.D.34.9 I.D.12.7 I.D.15.88 I.D.41.3 O.D.34.9 I.D.12.7 I.D.15.88 I.D.41.3 I.D.38.1 O.D.34.9I.D.41.3 O.D.34.9 I.D.12.7 I.
314 416 314 416
I.D.15.88 I.D.15.88 I.D.53.98 I.D.44.5 O.D.41.3 I.D.15.88 I.D.15.88 I.D.53.98 I.D.44.5 O.D.41.3 O.D.34.9 I.D.28.58 I.D.28.58 O.D.34.9 I.D.28.58 I.D.28.58 O.D.34.9 I.D.28.58 I.D.28.58
I.D.22.2 O.D.28.58 I.D.34.9 O.D.15.88 I.D.19.05 I.D.28.58 I.D.22.2 O.D.28.58 I.D.34.9 O.D.15.88 I.D.19.05 I.D.28.58 I.D.22.2 O.D.28.58 I.D.34.9 O.D.15.88 I.D.1
I.D.22.2 408
O.D.28.58 I.D.34.9 I.D.22.2 408
O.D.28.58 I.D.34.9 O.D.12.7 I.D.9.52 O.D.12.7 I.D.9.52 O.D.12.7
O.D.19.05 I.D.12.7 O.D.19.05 I.D.22.2 I.D.28.58 I.D.28.58 O.D.19.05 I.D.12.7 O.D.19.05 I.D.22.2 I.D.28.58 I.D.28.58 I.D.22.2 O.D.41.3
I.D.53.98 I.D.44.5 O.D.28.58 I.D.34.9 I.D.22.2 O.D.41.3
I.D.53.98 I.D.44.5 O.D.28.58 I.D.34.9
I.D.15.88 I.D.15.88 O.D.19.05 70 I.D.12.7 O.D.19.05 I.D.22.2 O.D.19.05 70 I.D.12.7 O.D.19.05 I.D.22.2 O.D.19.05 70 I.D.12.7 O.D.19.05
416 416 130 I.D.15.88 130 I.D.15.88 130 I.D.15.88
I.D.12.7 I.D.9.52 I.D.12.7 I.D.9.52 125 416 125 416 125
I.D.19.05 83 408 I.D.19.05 83 408
334 334 341 408 341 408 341
I.D.28.58 I.D.28.58
I.D.22.2 111 I.D.28.58 I.D.28.58
I.D.22.2 111 334 O.D.28.58 I.D.I.D.28.58
19.05 334 O.D.28.58 I.D.I.D.28.58
19.05 334
281 281 298 I.D.28.58 298 I.D.28.58 298
I.D.31.8 I.D.34.9 I.D.31.8 I.D.34.9 281 I.D.22.2 281 I.D.22.2 281
O.D.19.05 I.D.22.2 I.D.28.58 O.D.34.9 I.D.41.3 I.D.44.5 O.D.19.05 I.D.22.2 I.D.28.58 O.D.34.9 I.D.41.3 I.D.44.5 I.D.22.2 O.D.28.58 I.D.34.9 O.D.15.88 I.D. 19.05 I.D.22.2 O.D.28.58 I.D.34.9 O.D.15.88 I.D. 19.05 I.D.22.2 O.D.28.58 I.D.34.9 O.D.15.88 I.D. 19.05
I.D.22.2 O.D.19.05 I.D.22.2 O.D.19.05
I.D.12.7 I.D.15.88 I.D.22.2 111 I.D.12.7 I.D.15.88 I.D.22.2 111
ARCNN31 334
281
I.D.19.05I.D.9.52 83
I.D.31.8 I.D.34.9 341
298 I.D.28.58
334
281
I.D.19.05I.D.9.52 83
I.D.31.8 I.D.34.9 341
298 I.D.28.58 I.D.41.3 I.D.34.9 111
ARCNB31 I.D.31.8 I.D.34.9
I.D.22.2
I.D.41.3
111
I.D.34.9 111
I.D.31.8 I.D.34.9
I.D.22.2 111
I.D.41.3 I.D.34.9 111
I.D.22.2 I.D.19.05 O.D.12.7 I.D.41.3 I.D.38.1 O.D.34.9 I.D.22.2 I.D.19.05 O.D.12.7 I.D.41.3 I.D.38.1 O.D.34.9 83 83
70 70 I.D.22.2 I.D.19.05 I.D.19.05 I.D.41.3 I.D.38.1 O.D.34.9 I.D.22.2 I.D.19.05 I.D.19.05 I.D.41.3 I.D.38.1 O.D.34.9 I.D.22.2 I.D.19.05 I.D.19.05
I.D.28.58 I.D.28.58
I.D.28.58 I.D.28.58
I.D.22.2 I.D.19.05 I.D.19.05 83 O.D.28.58 I.D. 19.05 I.D.22.2 I.D.19.05 I.D.19.05 83 O.D.28.58 I.D. 19.05
I.D.15.88 I.D.12.7 I.D.41.3 130 I.D.22.2 I.D.34.9 111 I.D.15.88 I.D.12.7 I.D.41.3 130 I.D.22.2 I.D.34.9 111 O.D.34.9
I.D.41.3 I.D.28.58 O.D.34.9
I.D.41.3 I.D.28.58 O.D.34.9
I.D.41.3 I.D.28.58
O.D.19.05 I.D.22.2 I.D.15.88
I.D.28.58I.D.12.7 130 I.D.41.3 O.D.19.05 I.D.22.2 I.D.15.88
I.D.28.58I.D.12.7 130 I.D.41.3 O.D.19.05 I.D.22.2 I.D.15.88
O.D.15.88 I.D. 19.05 O.D.15.88 I.D. 19.05 I.D.53.98 I.D.I.D.28.58
O.D.34.9
O.D.41.3 I.D.44.5
44.5 O.D.41.3I.D.53.98 O.D.34.9 I.D.44.5
I.D.53.98 I.D.I.D.28.58
O.D.34.9
O.D.41.3 I.D.44.5
44.5 O.D.41.3I.D.53.98 O.D.34.9 I.D.44.5 I.D.I.D.28.58
O.D.34.9
O.D.41.3
I.D.53.98 I.D.44.5
44.5 O.D.41.3I.D.53.98 I.D.28.58
I.D.28.58 O.D.22.2 I.D. 34.9 O.D.28.58 I.D.22.2 I.D.28.58 O.D.22.2 I.D. 34.9 O.D.28.58 I.D.22.2 I.D.22.2 O.D.28.58 I.D.34.9I.D.22.2 I.D.22.2 O.D.28.58 I.D.34.9I.D.22.2
415 I.D.28.58 O.D.22.2 I.D. 34.9 O.D.28.58 415 I.D.28.58 O.D.22.2 I.D. 34.9 O.D.28.58 415 I.D.28.58 O.D.22.2
O.D.19.05 I.D.12.7
334 O.D.19.05 I.D.22.2 341 O.D.19.05 I.D.12.7
334 O.D.19.05 I.D.22.2 341 O.D.19.05 334
I.D.12.7 O.D.19.05
I.D.15.88 I.D.12.7 I.D.15.88 I.D.12.7 375 125 I.D.15.88 281 416
298 375 125 I.D.15.88 281 416
298 375 125 I.D.15.88 281
O.D.15.88 I.D.19.05
I.D.31.8 I.D.28.58 O.D.22.2 I.D.53.98 I.D.44.5 O.D.41.3 I.D.28.58 O.D.15.88 I.D.19.05
I.D.31.8 I.D.28.58 O.D.22.2 I.D.53.98 I.D.44.5 O.D.41.3 I.D.28.58 I.D.22.2 O.D.28.58 I.D.34.9 I.D.22.2 O.D.28.58 I.D.34.9 I.D.22.2 O.D.28.58 I.D.34.9
341 O.D.15.88 I.D.19.05 408 341 O.D.15.88 I.D.19.05 408 341 O.D.15.88 I.D.1
I.D.53.98 I.D.44.5 O.D.41.3 I.D.53.98 I.D.44.5 O.D.41.3 298 334 I.D.28.58 298 334 298 334
I.D.53.98 I.D.44.5 O.D.41.3 I.D.28.58 I.D.28.58
I.D.53.98 I.D.44.5 O.D.41.3 I.D.28.58
281 281 281
O.D.15.88 I.D.19.05 I.D.34.9 O.D.28.58 I.D.22.2 O.D.15.88 I.D.19.05 I.D.34.9 O.D.28.58 I.D.22.2 I.D.19.05 83 I.D.19.05 83 I.D.19.05
I.D.41.3 134 I.D.22.2 I.D.19.05 I.D.41.3 I.D.34.9I.D.44.48 I.D.41.3 134 I.D.22.2 I.D.19.05 I.D.41.3 I.D.34.9 I.D.41.3 134 I.D.22.2 I.D.19.05
I.D.44.48 I.D.53.98 111111 I.D.53.98 111111 I.D.44.48 I.D.53.98
I.D.22.2 O.D.28.58 I.D.34.9 I.D.22.2 O.D.28.58 I.D.34.9 I.D.22.2 I.D.22.2
O.D.19.05 I.D.12.7 O.D.19.05 I.D.22.2 O.D.19.05 I.D.12.7 O.D.19.05 I.D.22.2 I.D.31.8 I.D.34.9 I.D.31.8 I.D.34.9
I.D.15.88 416 I.D.15.88 416 I.D.41.3 I.D.34.9 111 I.D.41.3 I.D.34.9 111 I.D.41.3 I.D.34.9 111
I.D.22.2 I.D.19.05 I.D.19.05 83 I.D.41.3 I.D.38.1 O.D.34.9 I.D.22.2 I.D.19.05 I.D.19.05 83 I.D.41.3 I.D.38.1 O.D.34.9 I.D.22.2 I.D.19.05 I.D.19.05
O.D.19.05 I.D.22.2 I.D.28.58 O.D.34.9 408
I.D.41.3 I.D.44.5 O.D.19.05 I.D.22.2 I.D.28.58 O.D.34.9 408
I.D.41.3 I.D.44.5 I.D.15.88 I.D.12.7 I.D.15.88 I.D.12.7 I.D.15.88
334 I.D.28.58 I.D.28.58 334 I.D.28.58 I.D.28.58 I.D.31.8 I.D.28.58 O.D.22.2 I.D.53.98 I.D.44.5 O.D.41.3 I.D.31.8 I.D.28.58 O.D.22.2 I.D.53.98 I.D.44.5 O.D.41.3 I.D.31.8 I.D.28.58 O.D.22.2
I.D.28.58 I.D.28.58 I.D.28.58 I.D.28.58 I.D.28.58
334
281 341 334
281 341 I.D.28.58 I.D.28.58
281 298 281 298
I.D.28.58 I.D.15.88 I.D.12.7 130 I.D.28.58 I.D.15.88 I.D.12.7 130 I.D.28.58 I.D.15.88
I.D.22.2
I.D.53.98 O.D.28.58
I.D. 44.5 O.D.41.3I.D.34.9 I.D.22.2
I.D.53.98 O.D.28.58
I.D. 44.5 O.D.41.3I.D.34.9 I.D.22.2
I.D.53.98 O.D.28.58
I.D. 44.5 O.D.41.3I.D.34.9
I.D.22.2 111 I.D.22.2 111 O.D.15.88 I.D.19.05 O.D.15.88 I.D.19.05 O.D.15.88 I.D
I.D.34.9 O.D.28.58 I.D.22.2 I.D.34.9 O.D.28.58 I.D.22.2
I.D.31.8 I.D.34.9 I.D.31.8 I.D.34.9 I.D.28.58 O.D.22.2 I.D. 34.9 O.D.28.58 I.D.22.2 I.D.28.58 O.D.22.2 I.D. 34.9 O.D.28.58 I.D.22.2 I.D.28.58 O.D.22.2
I.D.22.2 I.D.19.05 83
83 I.D.41.3 I.D.38.1 O.D.34.9 I.D.22.2 I.D.19.05 83
83 I.D.41.3 I.D.38.1 O.D.34.9
I.D.22.2 I.D.19.05
I.D.19.05 I.D.19.05
I.D.41.3 I.D.34.9 I.D.22.2 I.D.19.05
I.D.19.05 I.D.19.05
I.D.41.3 I.D.34.9 O.D.41.3 I.D.22.2
I.D.44.5 O.D.28.58
I.D.53.98 I.D.34.9 O.D.19.05 I.D.22.2 I.D.28.58 O.D.34.9 I.D.41.3 I.D.44.5 O.D.41.3 I.D.22.2
I.D.44.5 O.D.28.58
I.D.53.98 I.D.34.9 O.D.19.05 I.D.22.2 I.D.28.58 O.D.34.9 I.D.41.3 I.D.44.5 O.D.41.3 I.D.22.2
I.D.44.5 O.D.28.58
I.D.53.98 I.D.34.9 O.D.19.05 I.D.22.2 I.D.28.58
4 Outdoor Units
111 111 O.D.15.88 I.D.19.05 O.D.15.88 I.D.19.05 O.D.15.88 I.D.1
I.D.28.58 4 Outdoor Units I.D.28.58 415 334 I.D.53.98 I.D.44.5 O.D.41.3
341 415 334 I.D.53.98 I.D.44.5 O.D.41.3
341 415 334
375 281 298 375 281 298 375 281
I.D.15.88
I.D.15.88 I.D.12.7 130 I.D.15.88
I.D.15.88 I.D.12.7 130
Model Name
I.D.31.8 I.D.28.58 O.D.22.2
I.D.28.58 O.D.22.2 High Pressure
I.D.53.98 I.D.44.5 O.D.41.3
Gas Pipe
I.D.28.58
I.D. 34.9 O.D.28.58 I.D.22.2 Liquid Pipe
I.D.31.8 I.D.28.58 O.D.22.2
I.D.28.58 O.D.22.2
I.D.53.98 I.D.44.5 O.D.41.3 I.D.28.58
I.D. 34.9 O.D.28.58 I.D.22.2 Model Name High Pressure Gas Pipe Liquid Pipe Low Pressure Gas Pipe
134 I.D.22.2 I.D.19.05 I.D.19.05 83 134 I.D.22.2 I.D.19.05 I.D.19.05 83 134 I.D.22.2 I.D.19.05 I.D.19.05
O.D.15.88
O.D.15.88 I.D.19.05
I.D.19.05 O.D.15.88
O.D.15.88 I.D.19.05
I.D.19.05 I.D.44.48 I.D.53.98 I.D.41.3 I.D.41.3 I.D.34.9I.D.44.48
111 I.D.53.98 I.D.41.3 I.D.41.3 I.D.34.9 111 I.D.44.48 I.D.53.98 I.D.41.3
I.D.34.9 O.D.28.58 I.D.22.2 I.D.34.9 O.D.28.58 I.D.22.2
I.D.53.98 I.D.44.5 O.D.41.3 I.D.53.98 I.D.44.5 O.D.41.3

I.D.15.88 I.D.12.7 I.D.15.88 I.D.12.7 I.D.15.88


I.D.28.58 I.D.31.8 I.D.28.58 O.D.22.2 I.D.53.98 I.D.44.5 O.D.41.3 I.D.28.58 I.D.28.58 I.D.31.8 I.D.28.58 O.D.22.2 I.D.53.98 I.D.44.5 O.D.41.3 I.D.28.58 I.D.28.58 I.D.31.8 I.D.28.58 O.D.22.2

O.D.19.05 I.D.22.2 I.D.28.58 O.D.34.9 I.D.41.3 I.D.44.5 O.D.19.05 I.D.22.2 I.D.28.58 O.D.34.9 I.D.41.3 I.D.44.5 I.D.22.2 O.D.28.58
O.D.41.3 I.D.44.5 I.D.34.9
I.D.53.98 O.D.19.05 I.D.22.2 I.D.28.58 O.D.34.9 I.D.41.3 I.D.44.5 I.D.22.2
O.D.41.3 O.D.28.58
I.D.44.5 I.D.34.9
I.D.53.98 O.D.19.05 I.D.22.2 I.D.28.58 O.D.34.9 I.D.41.3 I.D.44.5 I.D.22.2
O.D.41.3 O.D.28.58
I.D.44.5 I.D.34.9
I.D.53.98 O.D.19.05 I.D.22.2 I.D.28.58
O.D.15.88 I.D.19.05 I.D.34.9 O.D.28.58 I.D.22.2 O.D.15.88 I.D.19.05 I.D.34.9 O.D.28.58 I.D.22.2 O.D.15.88 I.D
334 341 334 341 415 334 341 415 334 341 415 334
281 298 281 298 375 281 298 375 281 298 375 281

ARCNN41I.D.22.2 I.D.19.05 I.D.19.05 83 I.D.22.2 I.D.19.05 I.D.19.05 83 134


ARCNB41
I.D.22.2 I.D.19.05 I.D.19.05 83 134 I.D.22.2 I.D.19.05 I.D.19.05 83 134 I.D.22.2 I.D.19.05 I.D.19.05
I.D.41.3 I.D.34.9 111 I.D.41.3 I.D.34.9 111I.D.44.48 I.D.53.98 I.D.41.3 I.D.41.3 I.D.34.9I.D.44.48
111 I.D.53.98 I.D.41.3 I.D.41.3 I.D.34.9 111 I.D.44.48 I.D.53.98 I.D.41.3

I.D.15.88 I.D.12.7 I.D.15.88 I.D.12.7 I.D.15.88 I.D.12.7 I.D.15.88 I.D.12.7 I.D.15.88


I.D.31.8 I.D.28.58 O.D.22.2 I.D.53.98 I.D.44.5 O.D.41.3 I.D.28.58 I.D.31.8 I.D.28.58 O.D.22.2 I.D.53.98 I.D.44.5 O.D.41.3 I.D.28.58 I.D.28.58 I.D.31.8 I.D.28.58 O.D.22.2 I.D.53.98 I.D.44.5 O.D.41.3 I.D.28.58 I.D.28.58 I.D.31.8 I.D.28.58 O.D.22.2 I.D.53.98 I.D.44.5 O.D.41.3 I.D.28.58 I.D.28.58 I.D.31.8 I.D.28.58 O.D.22.2

I.D.22.2 O.D.28.58 I.D.34.9 I.D.22.2 O.D.28.58 I.D.34.9 I.D.22.2 O.D.28.58 I.D.34.9


O.D.15.88 I.D.19.05 I.D.34.9 O.D.28.58 I.D.22.2 O.D.15.88 I.D.19.05 I.D.34.9 O.D.28.58 I.D.22.2 O.D.15.88 I.D.19.05 I.D.34.9 O.D.28.58 I.D.22.2 O.D.15.88 I.D.19.05 I.D.34.9 O.D.28.58 I.D.22.2 O.D.15.88 I.D

306 307
ACCESSORIES
PIPING ACCESSORIES

PIPING ACCESSORIES
Y Branch pipe for connection of outdoor units

Heat Pump, Heat Recovery zone control Heat Recovery


R410A MULTI V 5, MULTI V IV, MULTI V III, MULTI V PLUS II, MULTI V PLUS, MULTI V S, MULTI V MINI, MULTI V SPACE II, R410A MULTI V 5, MULTI V IV Heat Recovery, MULTI V III Heat Recovery, MULTI V WATER IV Heat Recovery,
MULTI V WATER IV, MULTI V WATER S, MULTI V WATER II MULTI V WATER II Heat Recovery

(Unit : mm) (Unit : mm)

Model Name Gas Pipe Liquid Pipe Model Name High Pressure Gas Pipe Liquid Pipe Low Pressure Gas Pipe

I.D12.7 I.D15.88 I.D15.88


I.D9.52 I.D9.52 I.D6.35
I.D9.52 I.D9.52 I.D6.35 I.D12.7 I.D15.88

I.D6.35
ARBLN01621 I.D15.88
ARBLB01621 I.D6.35
I.D15.88
I.D12.7 I.D15.88 I.D. 9.52 I.D6.35
I.D19.05 I.D12.7
O.D15.88 O.D9.52 I.D. 9.52 I.D6.35 I.D12.7 I.D15.88
I.D12.7 I.D19.05
O.D9.52 O.D15.88

I.D22.2 I.D19.05 I.D15.88 I.D19.05


I.D9.52 I.D9.52 I.D6.35
I.D22.2 I.D19.05 I.D15.88 I.D19.05

I.D25.4 I.D12.7 I.D9.52 I.D9.52 I.D6.35


I.D12.7 I.D12.7
ARBLN03321 I.D28.58 O.D19.05
I.D15.88 I.D12.7
I.D25.4
I.D12.7

I.D19.05 I.D12.7 I.D12.7 I.D28.58 O.D19.05


I.D9.52 I.D6.35
ARBLB03321 I.D15.88 I.D12.7
O.D19.05 I.D25.4 O.D19.05 I.D19.05
I.D12.7
I.D 22.2 I.D 22.2 I.D9.52 I.D6.35
I.D12.7 I.D25.4 O.D19.05
O.D19.05
I.D 22.2 I.D 22.2

Model Name Gas Pipe Liquid Pipe


I.D19.05 I.D19.05

I.D12.7 I.D15.88 I.D15.88 I.D12.7 I.D28.58 I.D22.2 I.D15.88

I.D19.05 I.D19.05 I.D12.7


I.D12.7
I.D28.58 I.D22.2 I.D15.88 I.D12.7 I.D15.88 I.D15.88 I.D12.7 I.D19.05 I.D31.8
ARBLB07121
I.D12.7 I.D12.7 I.D19.05 I.D15.88
I.D15.88 I.D19.05
ARBLN07121 I.D31.8 I.D19.05
O.D12.7 I.D6.35
I.D31.8 O.D22.2
I.D19.05 I.D15.88 I.D15.88 I.D19.05 I.D9.52
I.D34.9 I.D28.58 O.D19.05 I.D28.58
I.D9.52
O.D12.7 I.D6.35 O.D31.8
I.D31.8 O.D22.2 I.D9.52 O.D12.7 I.D22.2
I.D34.9 I.D28.58 O.D19.05 I.D28.58 I.D9.52
O.D31.8 I.D22.2 O.D12.7

I.D34.9
I.D34.9 I.D41.3 I.D38.1 I.D28.58
I.D34.9
I.D34.9 I.D41.3 I.D38.1 I.D28.58
I.D28.58
I.D38.1
I.D28.58
I.D38.1
ARBLB14521 I.D34.9 I.D22.2
ARBLN14521 I.D41.3 I.D41.3 O.D34.9
I.D34.9 I.D22.2 I.D41.3
O.D38.1
I.D41.3
I.D38.1
O.D34.9

O.D38.1 I.D38.1

I.D12.7 O.D28.58 I.D19.05 O.D22.2 I.D15.88 I.D12.7 O.D28.58 I.D19.05


O.D22.2 I.D15.88 O.D15.88 O.D15.88
I.D19.05 I.D22.2 I.D19.05 I.D22.2

Model Name Gas Pipe Liquid Pipe Model Name High Pressure Gas Pipe Liquid Pipe Low Pressure Gas Pipe
I.D34.9 I.D34.9 I.D.44.48
I.D.41.3 I.D38.1 I.D28.58 I.D.53.98 I.D41.3 I.D38.1
2 I.D.25.4
2
I.D25.4 I.D22.2 I.D.22.2 I.D.19.05 1
I.D.44.48
I.D38.1 I.D28.58 2 I.D.44.48
I.D34.9 I.D22.2 125 I.D41.3 I.D38.1 134
I.D.25.4
471 3 I.D.22.2 I.D.19.05 96 420 3
517 490
346
ARBLN23220 ARBLB14521 I.D19.05 379
3
I.D.34.9 I.D31.8
I.D.53.98
O.D22.2 I.D15.88 O.D38.1 I.D41.3 O.D.38.1 I.D.28.58 O.D.44.48 I.D.25.4 I.D.22.2
O.D34.9 I.D38.1
O.D.28.58
2 2
3 2 3 I.D41.3 I.D.15.88 I.D19.52 X2 X2 3
O.D.19.05 I.D.12.7 O.D12.7 I.D6.35 3 3
120 90 130 175 100 115
2 3 X2 3 I.D12.7 I.D.19.05 I.D.15.88
I.D12.7 O.D28.58 I.D22.2
3 110 110 3 3
2 I.D19.05
O.D15.88 O.D15.88 O.D.22. 2
70 120 70 120

308 309
ACCESSORIES
PIPING ACCESSORIES PIPING ACCESSORIES

REFRIGERANT CHARGING KIT STOPPER VALVES


Recharging refrigerant after a pump down or when refrigerant is either insufficient or excessive

PRAC1 UNDER 1 / 2 (INCH)


PRVT120
UNDER 7 / 8 (INCH)
PRVT780
UNDER 9 / 8 (INCH)
PRVT980

Features Features
• Arrange manifold, capillary assembly, refrigerant vessel and scale Model Name Specification
Conne ni old o he g s i e se i e l e o o doo in s shown in he fig e
• Connect manifold and capillary tube. Use designated capillary assembly only If designated capillary
PRVT120
assembly isn’t used, the system may get damaged
• Connect capillary and refrigerant vessel
• Purge hose and manifold
• After “568” is displayed, open the valve and charge the refrigerant
PRVT780

Models Applied
PRVT980
• MULTI V 5
Mainfold
• MULTI V IV Heat Pump
• MULTI V IV Heat Recovery
Capillary Assembly
• MULTI V III Heat Pump
• MULTI V III Heat Recovery
Usage
• MULTI V PLUS II • This unit can be applied for the additional indoor unit’s installation.
• MULTI V SYNC II • This unit can be applied for each indoor unit’s service.

Installation
* Fault Detect & Diagnosis

Pin(Closed) Pin(Open)

Refrigerant
1. Cut the inlet side of the 2. If installing additional 3. When installing a stopper 4. When installing anad-
connector, and weld the indoor units, the outlet valve, the flare part should ditional indoor unit, the
pipe side connector should be be facing towards addi- SVC valve should be in
cut according to installa- tional indoor unit. closed state.
tion pipe.
* When welding, service valve shoud be wrapped by wet cloth.

310 311
ACCESSORIES
PIPING ACCESSORIES PIPING ACCESSORIES

STOPPER VALVES DRAIN HOSE


Easy drain installation

Details of Model Name PHDHA05T


PHDHA07T
PHDHA05B
• Case1 PHDHA07B
Cut inlet side of the connector, and weld In case of the installation of additional
(Room 3 & 4 : In use / Room 1 & 2 : Need to install indoor units)indoor unit, outlet side connector should
the pipe
be cut according to installation pipe.

* Stopper Valve is already installed


"A"

9.52 : 19.05
3.0m Room 1
9.52 : 19.05 Closed State
Pin(Closed) Pin(Open)

Features
3.0m
Stopper Valves
In case of installation of stopper valve,
9.52 : 15.88 In case of installation of additional
flare part should be facing towards indoor unit, SVC valve should be in Room 2
10.0m
additional indoor unit. closed state • It reduces the installation time by over 40% with elbow-less drain hose.
• Midget drain pump covers maximum 800mm high, featuring easy piping installation.
-When welding, service valve shoud be wrapped by wet cloth.
9.52 : 15.88
5.0m
Room 3

6.35 : 12.7
3.0m
Models Applied
Room 4 Max. 450
• Ceiling Mounted Cassette
and Ceiling Concealed Duct
• In case of installation of additional indoor unit, refrigerant of used indoor unit must be discharged. (Room 3 & Room 4) (refer to PDB for applicable model) Ceiling Mounted Cassette (4 Way, 1 Way) Flexible Hose
• If stopper valve is already installed, you can install additional indoor unit without refrigerant loss from the entire system. 250 Ceiling Concealed Duct Make a Loop Form
• After installation of additional indoor unit, you just need refrigerant charging for “A” section. (with Drain Pump)
• Then, open the Stopper Valve. Cut inlet side of the connector, and weld In case of the installation of additional
the pipe indoor unit, outlet side connector should (Unit : mm)
be cut according to installation pipe.

Open / Close Port


Charge Port

9.52 : 19.05
Accessory Model Name
3.0m
Model Name Length Quantity
9.52 : 19.05 Pin(Closed) Open State
Pin(Open)
PHDHA05T 500mm 30EA
3.0m Stopper Valves
In case of installation of 9.52 : 15.88valve,
stopper In case of installation of additional PHDHA07T 700mm 30EA
flare part should be facing towards indoor unit, SVC valve should be in PHDHA05B 500mm 5EA
additional indoor unit. 10.0m closed state
6.35 : 12.7 PHDHA07B 700mm 5EA
3.0m
-When welding, service valve shoud be wrapped by wet cloth. Room 1

9.52 : 15.88
3.0m
Room 2

Room 3

Room 4

312 313
ACCESSORIES
COMPATIBILITY TABLE

• : Compatible : Need wired remote controller / IR receiver X : Not compatible • : Compatible : Need wired remote controller / IR receiver X : Not compatible
Premium Standard llI Standard ll Simple Simple for Hotel Wireless Dry Contact Controller
Simple Dry Contact
Controller Model Premium Standard llI Standard ll Simple
for Hotel
Wireless

Product PREMTA000 PREMTBB10 PREMTB100 PREMTBB01 PREMTB001 PQRCVCLOQ PQRCVC0QW PQRCHCA0Q PQRCHCA0QW PQWRHQ0FDB
Simple Dry
Contact
2 points Dry
Contact
Dry Contact for
Thermostat
For Modbus Product Simple Dry 2 points Dry Dry Contact for
PDRYCB500 For Modbus
PREMTA000 PREMTBB10 PREMTB100 PREMTBB01 PREMTB001 PQRCVCLOQ PQRCVC0QW PQRCHCA0Q PQRCHCA0QW PQWRHQ0FDB Contact Contact Thermostat
PDRYCB000 PDRYCB400 PDRYCB300 PDRYCB500
PDRYCB000 PDRYCB400 PDRYCB300

ARNU-C4 • • • • • • • • • • Ceiling Mounted


Cassette • • • • • • • • • •
Ceiling 4 Way
Mounted
Cassette

ARNU-C4 • • • • • • • • • •
2 Way / 1 Way
High • • • • • • • • • •
ARNU-A4 • • • • • • • • •
High Sensible

SINGLE SPLIT
Ceiling

Ceiling
Standard
Inverter
Concealed Mid • • • • • • • • • •
Concealed
Duct
ARNU-A4 • • • • • • • • • Duct

High Statics
Mid Statics

ARNU-G4 • • • • • • • • • Low • • • • • • • • • •
Low Statics

FAU
(Fresh Air
intake Unit)
ARNU-Z4 • • • • • • • • •
Ceiling
Suspended Unit • • • • • • • • • •
Convertible
MULTI V

& Ceiling
Suspended
ARNU-A4 • • • • • • • • • •
Unit

4 Way • • • • • • • • • •
ARNU-R4 • • • • • • • • • • Ceiling
Wall Mounted
Mounted Cassette
Unit
ARNU-N4
• • • • • • • • • • 1 Way • • • • • • • • • •
ARNU-A4


MULTI SPLIT
HYDRO KIT 2) x x x x x x x x x
Mid • • • • • • • • •
Ceiling
Energy
Recovery
Ventilator
• x x x x x • x x x
Concealed
Duct

Ventilation Low • • • • • • • • •
Energy Recovery
Ventilator with
DX coil
• x x x x x • • • •

Wall Mounted Unit • • • • • • • • • •


AHU Communication Kit • • • • • • • • •

*It has a separate remote controller

314 315