2021
L G AI R
SOLUTION
LG Electronics Distributed by
SINGAPORE
http://www.lg.com
http://partner.lge.com
054 - 055
168 - 169
INDOOR
ACCESSORIES
UNITS
MECHANICAL ACCESSORIES 170
WALL MOUNTED 056
INDEX
CONSOLE 098
002 / 003
10 ADVANTAGES
OF MULTI V
5 SMART
CONTROLS 6 BUSINESS
SUPPORT
MULTI V responds to diverse building - Engineering Tools & Support
environments with LG ThinQ -based
TM
- LG Air Conditioning Academy
AI control and individual/central - Asia Regional HQ
integrated control solutions.
1 ULTIMATE
EFFICIENCY 3 SUPERIOR
DURABILITY 4 DESIGN
FLEXIBILITY
Ultimate Energy Saving with LG’s exclusive “Black Fin” Flexible Installation with
Dual Sensing Control. heat exchanger is designed
to perform even in corrosive
Environments.
Large Capacity Outdoor Unit.
2
Certified protection
INNOVATIVE
TECHNOLOGIES
8 DIVERSE
INTEGRATED
SOLUTION
MULTI V 5 Integrated solution optimized for
- Ultimate Inverter Compressor ※ Verification of corrosion resistance performance various business environments,
- Declared by TUV Rheinland
- Biomimetics Technology Fan - Test Method B of ISO21207 including hot water, AHU, BMS,
- Test condition : Salt contaminated condition
+ severe industrial/traffic and EMS.
environment
Scroll Compressor
004 / 005
WHY LG MULTI V
2017 ~
Since the time when LG launched Korea’s first residential air MULTI V’s wide range of VRF solutions satisfies various building
conditioner in 1968, the company has worked to continuously types and sizes. MULTI V S’s size discharge was designed Germany
Canada
UK Poland
enhance its technological innovation and reliability. As a for small to mid-sized buildings while MULTI V Water is a Russia
result of sustained improvement, LG VRF launched the first water-cooled VRF solution with variable water flow control Italy Hungary
Korea
USA
France
generation of MULTI V in 2006 and achieved significant technology. Kazakhstan
China
development. With the best-in-class compressor technology
and innovation applied to every part and control solution, In 2017, the ultimate VRF solution was introduced with MULTI V 5. Jordan
MULTI V has evolved to be on of the world’s most efficient This generation has fully improved its technological potential
and reliable VRF solutions. with the powerful and reliable yet economical Ultimate Inverter GF
Vietnam
Panama
Thailand
Compressor, effective corrosion resistance with the Ocean India
The first and second generations of MULTI V boasted inverter Black Fin coating and enlarged fans. Dual Sensing Control Philippines
Nigeria
technology and non-ozone depleting technology, while MULTI V III was offers the most pleasant indoor environment while minimizing Singapore
Colombia
produced with cutting edge tech like oil return with HiPORTM unnecessary energy loss by sensing both temperature and
and double compression features with mid-pressure refrigerant humidity to efficiently manage cooling, heating and part load. Kenya
Indonesia
Regional
temperature, while optimizing refrigeration management and pleasant indoor experience.
South Africa
heat exchange for both cooling and heating.
Local
Australia
Branch
006 / 007
WHY LG MULTI V
03 Model Selection
I II III LATS HVAC
LATS HVAC is a model selection program that accurately and quickly selects
Energy Estimation Model Selection Installation the most suitable LG commercial air conditioning systems for each design. In
addition to model selection, faster estimation on refrigerant piping diameter and
& Energy Modeling & Design Environment
additional refrigerant is possible, along with auto printing of reports.
Simulation
04 Design
LATS CAD
01 Planning LATS CAD enables faster and more accurate 2D design of LG commercial air
conditioning systems. It also enables modules for quotation and installation
LATS review that minimize inherent problems during installation and commissioning.
Energy
※ AutoCAD program is required.
03 Design Development
Energy
Modeling LATS CAD
- eQUEST Ⓡ
- TRNSYS
LATS REVIT
05 Environment Simulation
CFD CFD Analysis
04 Construction Design - FLUENT
CFD Analysis is applied in areas of estimating : indoor airflow and temperature
distribution while operating VRF products, outdoor airflow distribution, and
noise level. By running a simulation before construction, engineers estimate
possible issues and find optimal solutions for malfunctions that could occur after
construction.
05 Construction
008 / 009
WHY LG MULTI V
BENEFITS OF LG MULTI V
* Dual Smart Load Control ESEER based, below 50% humidity, model ARUM260LTE5
** LG internal test result
010 / 011
WHY LG MULTI V
APPLICATION SOLUTIONS
Office Residential
Supporting efficiency with flexibility Creating a comfortable home
High Rise Office Building Small to Medium sized Office Building Condominium Apartments
• MULTI V WATER IV • High Static Duct • Variable water flow • MULTI V 5 HR • Low static duct
• MULTI V 5 / S • 4 Way CST** • PDI • MULTI V 5 • 1 Way CST • PDI
• DX AHU • PDI* control kit • HYDRO KIT • 3rd party controller RTU gateway
The MULTI V series revitalizes the workspace by providing fresh air at all times. LG's intelligent control solutions add comfort MULTI V 5 HR/HP with various IDU enables optimal solution, providing comfort to every space through individual zone
to any space. control and hot water solution.
Commercial Hospitality
Maximizing business, minimizing cost Meeting diverse needs
The highly efficient, energy saving MULTI V 5 and MULTI V reduces operation costs, and provides comfort that suits any The diverse applications that can be applied to MULTI V 5 helps bring just the right solution to a sophisticated hotel business.
purpose and any space, helping to invest the extra space and expense to your business.
012 / 013
WHY LG MULTI V
BMS Protocol
BMS System
AHU
014 / 015
LINE-UP
● ● ●
● ● ● ● ● ● ●
HEAT PUMP
• Dual Sensing Control
• Large capacity ODU (Up to 26HP) ● ● ● ● ● ●
• Continuous Heating
• Black Fin heat exchanger
• Heat pump function
● ● ● ● ● ● ● ●
• For large space, high rise building and
individual control building
● ● ● ● ● ● ● ● ● ● ● ●
● ● ● ● ● ● ● ● ● ● ● ●
○ ○ ○
• Space saving
• Flexible design applications
- Slim, light, and broad range (3 to 6HP)
- Large number of connectable indoor units
(Up to 20 Units)
• For small / medium building ○
016 / 017
LINE-UP
4th generation
Wall Standard ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●
Mounted
4 Way Cassette
● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●
(570 x 570)
4 Way Cassette
● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●
(840 x 840)
2 Way Cassette ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●
1 Way Cassette ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●
High Statics ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●
4th generation
Ceiling
Mid Static ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●
Concealed
Duct
Low Statics ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●
4th generation
● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●
Fresh Air Intake
4th generation
● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●
Ceiling Suspended
4th generation
● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●
Console
4th generation
Floor Standing
Floor ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●
with Case
Standing
Low Temperature ● ● ● ● ● ● ● ● ● ● ● ● ● ●
4th generation
HYDRO KIT
High Temperature ● ● ● ● ● ● ● ● ● ● ● ● ●
※ If 4th generation indoor units are connected to MULTI V WATER S, several functions are not available.
※ If 4th generation indoor units are combined to 2nd generation indoor units, several functions are not available.
More detailed information, refer to the "MULTI V Indoor units Compatibility Table"
018 / 019
LINE-UP
PREMTB100 PQRCVCL0QW PWLSSB21H (H/P) PQCSZ250S0 PACP5A000 PLNWKB000 Premium (8 port) Simple Dry Contact PZCWRCG3 For MULTI V 5 Return / Room Air control
(Indoor Unit ~32) (Indoor Unit ~256) (Indoor Unit ~64) PQNUD1S40 PDRYCB000 PVDSMN000 PAHCMR000
BACnet IP / Standard (2 port)
Modbus TCP PPWRDB000
Wi-Fi Controller
ACS IO Module Variable Water Flow
Standard III (Black) LG Wi-Fi Modem AC Ez Touch AC Manager 5 Modbus RTU Gateway (Input / Output Module) Remote Temperature Sensor Control kit
PREMTBB10 PQRCVCL0Q For Indoor Unit PACEZA000 PACM5A000 PMBUSB00A PEXPMB000 Dry Contact for Thermostat PQRSTA0 For MULTI V WATER IV Discharge / Supply Air control
PWFMDD200 (Indoor Unit ~64) (Indoor Unit ~8,192) PDRYCB300 PWFCKN000 PAHCMS000
PREMTB001 PQRCHCA0QW PACS5A000 For Indoor Unit (ERV) PCHLLN000 Dry contact for Thermostat ZRTBS01 For MULTI V IV, 5 Main module
(Simple for Hotel) (Indoor Unit ~128) PHNFP14A0 (For using universal input) PRVC2 NEW
PAHCMM000
BACnet IP / NEW
PDRYCB320
Modbus TCP
ACU IO Module
PREMTBB01 PQRCHCA0Q PEXPMB300 2 Points Dry Contact (For Setback) 4 Zones by PRDSBM Communication module
(Simple for Hotel) PDRYCB400 thermostat ABZCA NEW
PAHCMC000
Premium
EEV Kit
UO Water Communication Module (Electronic Expansion Valve)
UI
PEXPMB100
020 / 021
OUTDOOR
UNITS
024 / 025
OUTDOOR UNITS _ MULTI V 5 _ KEY FEATURES
OUTDOOR
UNITS
Dual Sensing Smart Load Control (SLC) Energy Savings with Dual Sensing Control Comfort Cooling Intelligent Defrost
Enhanced energy saving & increased indoor comfort (Temperature & Humidity) Increased indoor comfort & enhanced operating efficiency Increased heating run-hours
Cooling loads vary according to both temperature and humidity. Case study First reference use Indoor Unit (IDU) is operating in a season when MULTI V has provided an intelligent defrost algorithm and settings
With Dual Sensing SLC, work exerted to meet the load depends its load is less than the design load, the comfort cooling algorithm based on current outdoor ambient temperature. With the addition
MULTI V 5
Weather characteristics of Warsaw, Poland
on both temperature and humidity. As a result, less capacity will be controls the indoor unit’s coil superheat, thus raising the discharged of the outdoor air humidity sensor, MULTI V 5 Intelligent Defrost just
The portion of cooling operation hours at low humidity condition (Below
required in lower humidity conditions. air temperature as the space temperature is approaching set point. got smarter.
50% RH) is big. The cooling load of this condition is less than the load at
MULTI V 5’s comfort control algorithm monitors the outdoor air MULTI V 5 computes the current ambient air dew point temperature
It influences the VRF system main processor’s decision on where to standard (50 ~ 70% RH) or high (over 70% RH) humidity condition even in
temperature and humidity conditions. When changing weather - the temperature at which frost will form on the outdoor unit coil in
set the system’s target high or low system pressure values. the same outdoor air temperature. MULTI V 5 raises the evaporating Temp
up at low load (Low humidity) condition to enable energy saving and prevent conditions are deteriorating and there is a high potential the indoor during winter operation. MULTI V 5 makes continuous adjustments to
over-cooling which can happen when the system is controlled only by using unit’s load will remain stable or may increase, comfort cooling delays the refrigeration cycle's operating parameters to keep the outdoor coil
Smart Load Control responds to : outdoor air Temp. or abandons raising the target superheat as the room temperature surface temperature above actual dew point which can be calculated
1) Outdoor ambient dry bulb temperature approaches set-point. When changing weather conditions are
Warsaw weather in Summer by using dry bulb Temp and relative humidity. When the refrigeration
2) Outdoor ambient relative humidity (when enabled) favorable to raising target superheat, target superheat is moderated. cycle's operating parameters can be adjusted no further without
90%
Cooling Indoor Units - adjusts target low pressure sacrificing heating comfort, further adjustment is stopped and frost is
80% High Humidity
Raises the target low pressure value as cooling load falls and/or ambient temperature falls.
Lowers the target low pressure value as cooling load rises and/or ambient temperature rises.
70% ~ 100% What are the benefits? allowed to build on the coil, therefore activating defrost.
Relative Humidity
70%
Heating Indoor Units - adjusts target high pressure Mid Humidity Dual Increased indoor comfort
60% SLC Sensing
Lowers the target high pressure as heating load falls and/or ambient temperature rises. 50% ~ 70%
SLC If comfort cooling is turned off, and the temperature of the leaving air is not What are the benefits?
Raises the target high pressure as heating load rises and/or ambient temperature falls. 50%
raised, when the fan speed is reduced to low speed, there is a potential that
Low Humidity The Intelligent Defrost algorithm increases the VRF system’s heating run-hours
40% 0% ~ 50% occupants located directly under a cassette IDU or supply air registers could
What are the benefits? feel cold air falling on them resulting in a lower overall comfort experience.
and reduces the number of defrost cycles required to maintain optimum
30% heating performance irrelevant of the mode and method of defrost selected.
Enhanced energy savings With comfort cooling turned on, the discharged air temperature is controlled.
20%
When the IDU controller reduces the fan speed, the potential for cold air falling
- Cooling Mode 23°C 25°C 27°C 29°C 31°C 33°C 35°C
on occupants located under the cassette IDU or supply air registers is reduced.
By raising the target low pressure during off-peak cooling operation, the Source : Outdoor Air Temperature
https://energyplus.net/weather
compressor lift is reduced. This slows compressor’s speed which leads to a
Time Portion of Relative Humidity in Summer
Enhanced operating efficiency
decrease in compressor’s power consumption.
(Warsaw, Poland) Raising superheat reduces refrigerant volume flowing through the coil.
- Heating Mode
RH (%) Portion As flow decreases, demand on the compressor decreases and the Conventional
By lowering the target high pressure during off-peak heating operation, the
compressor speed will be reduced, thus saving energy. Defrost
compressor lift is reduced. This slows compressor’s speed which leads to a 70% ~ 100% 8%
Cooling Load
EER ※ Indoor unit set up available with Standard III Remote Controller.
MULTI V 5 SLC
MULTI V 5 Dual Sensing SLC 9.4 9.4
9.2
9.0 Preventing cold draft & repeated turn On / Off
8.1 8.6
25°C 30°C 35°C Temperature 40% 60% 80% Relative 7.9
Humidity Improved Indoor Comfort
Latent heat load Sensible heat load 6.9 6.9
※ Constant indoor temp condition 6.0
Indoor temp
Cooling Load
Previous Cooling Capacity LG Intelligent Defrost /
For low temperature, Adjusting capacity Smart Heating
lower load and
to meet load Frost
Actually 31°C ~ 29 ~ 31°C 27 ~ 29°C 25 ~ 27°C 23 ~ 25°C Not cool accumulation begins
capacity are required External Load zone Coil
Required
Cooling
Outdoor Air Temperature Surface (°C)
Internal Load
Capacity
※ This energy simulation was performed in LG internally based on 16HP model.
Temperature & Humidity
Evaporation Temperature
Low Humidity
Power Consumption in Cooling Season
Dew
SLC
Yearly Power Input (kWh) - ODU Point (°C)
Lower load and Comfort
OAT MV4 (Fixed) MV5 SLC MV5 Dual SLC zone Set
capacity need High Humidity Additional Time
temperature
higher evaporation 31 ~ 17 15 13 Spent Heating
Outdoor
temperature Standard Temperature (°C) 29 ~ 31 91 73 62
(Non SLC)
Low Temperature High Temperature 27 ~ 29 183 136 124
026 / 027
OUTDOOR UNITS _ MULTI V 5 _ KEY FEATURES
OUTDOOR
UNITS
Variable Path Heat Exchanger Active Refrigerant Control HiPORTM Sub-cooling & Vapor Injection
Optimized system efficiency & continuous heating Stable operation & sustaining most efficient operation Advanced compressor reliability & efficiency Increased heating performance
MULTI V 5 outdoor units (ODU) are manufactured with horizontally The accumulator in the outdoor unit has a storage tank mounted HiPOR™ is an LG trademark that stands for High Pressure Oil Return. MULTI V 5 is equipped with advanced sub-cooler and vapor injection
split ODU coil consisting of two independent circuit sections. inside known as the receiver tank. The receiver tank is equipped It consists of an oil separator, oil drain line between the separator and the control system. The sub-cooler algorithm sub-cools liquid refrigerant
MULTI V 5
Each half of the coil is independently controlled. with inlet and outlet valves that are electronically opened and compressor. HiPOR™ technology enables oil to return directly into the just enough so that it can travel to the farthest IDU in the system
This split coil feature makes it possible for MULTI V 5 to provide closed. Refrigerant is being passed between the accumulator compressor, instead of returning through the refrigerant suction pipe. operating in cooling mode without changing state. During low
continuous heating during defrost. The split coil and valve and the receiver tank on a continuous basis. MULTI V 5 active This prevents energy waste when oil flows between the separator ambient operation down to -25°C (Heating mode), the sub-cooler
arrangement also makes it possible for the MULTI V 5 to change refrigerant control algorithm goal is to minimize the amount of and the compressor. Because the operating pressure in the chamber provides medium temperature refrigerant gas to the compressor’s
the flow path of refrigerant through one of the two coils only, or refrigerant in circulation. The lower the volume in circulation the containing the oil sump of the compressor and the pressure in the oil vapor injection system. When injected into the compression
through both coils in either a series or parallel arrangement. lower the cost to move it around the system and the higher the separator are nearly equal, there is no loss in compressor efficiency. chamber, system mass flow increases which stabilizes the system’s
Based on system pressures, ambient temperature conditions, and stability of the refrigeration cycle. It accomplishes this by constantly suction pressure. In all cases the vapor injection increases the
monitoring the system operating pressures and temperatures and What are the benefits? compressors cycle efficiency and reduces operating cost.
mode of operation, the system controller may modify the selected
a variety of other vital control metrics of the refrigeration cycle. Maximizes reliability and efficiency of the compressor.
path at any time.
When the cycle is out of balance, an adjustment in the amount of Non HiPOR™ HiPOR™ What are the benefits?
circulating refrigerant occurs. Compressor
1 Refrigerant Provides stable refrigeration cycle operation over a wide range of outdoor
What are the benefits? 3 ambient operating conditions.
4
Optimizes system efficiency regardless of operating modes as ambient weather Increases compressor efficiency when compared to systems without vapor
conditions change. What are the benefits? Efficiency Increase
Up to 33%
injection technology.
Customizes the used area of the outdoor unit’s heat exchange surface.
Widens the ambient temperature range at which stable operation occurs. 2
Amount of refrigerant
Full load cooling in receiver
• Upper & lower active 5 Energy loss in suction gas No energy loss in suction gas 5
Fixed refrigerant type Energy savings : fewer oil return cycles eliminate unnecessary energy
Heating performance
consumption.
Increases system heating run-time during winter operation.
Heating ODU Coil
efficiency 3% Increases compressor reliability.
Oil Oil
Non heating Non heating Non-Vapor Injection
Time
27%
Timed oil return logic (Non-oil Sensor) Oil Level Sensor Oil
Effect of partial defrost
Increased heating operation time per day Auto Oil Balancing Up to
: Up to 12% -25°C
• LG Internal Test result,
Cooling
efficiency • Test condition
- without oil level sensor : -25 -20 -15 -10 -5 0 7 11 15
Time Active Refrigerant Control
Non-Partial defrost Refrigerant quantity (kg) every 8 hour oil recovery operation Oil Outdoor temp(°C)
- with oil level sensor : ※ Improved heating performance by 27%.
non oil recovery operation ※ Comparison tested on 10HP model.
Oil Level Sensor
028 / 029
OUTDOOR UNITS _ MULTI V 5 _ KEY FEATURES
OUTDOOR
UNITS
Corrosion Resistance Black Fin Biomimetic Fan One Unified Model Flexible Installation with
Improved durability Maximized performance Heat pump / Heat recovery with one platform Large Capacity Outdoor Units
The black coating with enhanced epoxy resin is applied on the heat The fans in MULTI V 5's outdoor unit have been upgraded to feature LG MULTI V 5 satisfies users’ various needs with just one platform. More flexible design potential & space saving
exchanger for strong protection from various corrosive external a moire pattern similar to that of a clam shell's exterior that help with Heat Pump System works for the sites where either cooling or heating
MULTI V 5
Large capacity outdoor units of MULTI V 5 minimize installation
conditions such as salt contamination and air pollution. noise reduction. At the same time, unlike the fans installed in previous operation is needed, while Heat Recovery System fits perfectly to the
space that spares valuable floor space and significantly decreases
Moreover, the hydrophilic film keeps water from accumulating products that generate separation of flow due to absence of tubercles, sites wherein both the cooling and heating operations are simultaneously
total installed weight. This gives users more flexible design potential
on the heat exchanger’s fin, minimizing moisture buildup and the bumpy back design inspired by the bumps on the humpback needed or locations installed with Hot Water Solution to provide hot
and better use of the saved space.
eventually making it even more corrosion resistant. whale’s flipper is applied as the tubercles on the back side of the fans, water and heating via radiators.
LG Corrosion Resistance solution passed ISO 21207 accelerated increasing wind power by reducing flacking. In addition to the biomimetic 12.25m2
corrosion test conducted by an independent test organization technology-based fans, extended shroud of MULTI V 5 allows more high
and the result has been certified by prestigious global certification static pressure and helps fans to blow higher air volume for efficient
organization, TUV. operation. With wider air guide, discharged air current is stabilized and What are the benefits?
Previous Model
noise level is reduced. MULTI V 5 allows the building previously installed with Heat Pump system to
23%
What are the benefits? switch to the Heat Recovery system (by adding HR boxes and a third pipe) 9.42m2 Reduction
for changing purpose of the building or remodeling reasons via simple piping
This improvement in durability prolongs the product’s lifespan and lowers both What are the benefits?
construction.
the operational and maintenance costs. Based on the biomimetic technology, the fans of MULTI V 5 increased air
flow rate by 10% in comparison to previous model and reduced its power
Heat Pump System
consumption up to 20% when compared with the fan blade design on
MULTI V IV. This eventually results in maximized performance with large capacity. 23% 15%
Reduction Reduction
Changeover
from corrosion.
-15°C or as high as 48°C making it an adequate solution for specialized
Type
Aluminum fin areas like technical rooms. Moreover, MULTI V 5’s cycle technology
with enhanced durability enables optimal cooling performance at high
temperature that increases up to 48°C.
SST (Salt Spray Test)
Heat Recovery System Outdoor air temp (°C WB)
Test Process Test Result
(5% Area of defects compared to initial)
18°C
15°C
1,950 hr
Process
1,000 hr
1) repeated
Fog
(35°C, 24hr)
95%
Test process is conducted according to ISO 9227. Gold Fin Black Fin
1) Salty water concentration : NaCl aqueous solution (5%) 100% copper material to -20°C
Air flow rate Power consumption
prevent corrosion & refrigerant -25°C
leakage m3/min W 10°C 15°C 20°C 27°C
030 / 031
Multi V 5 Outdoor Units
OUTDOOR
Outdoor
Outdoor
Units
Units
Position of Sound Pressure Level Measuring Cooling / Heating Operation
UNITS
9.9.Operation
OperationLimits
Limits
Note
Low-Noise Operation Simple Test Run via LGMV Cooling
Cooling
Cooling / Heating
/ Heating
Operation
Operation Heating
For noise sensitive environment Increased overall efficiency in installation • Data is valid at free field condition
• Data
50°C is valid at nominal operating 20°Ccondition
48°C
Unlike the previous model which enables Low-Noise Operation To make sure that the product functions properly, conducting a test run • Sound level will vary depending on
18°C
15°C a range of
45°C
only during night after judgment time, the Low-Noise Operation of is recommended. For previous product, professional engineer who is well- factors such as the construction(acoustic
MULTI V 5
Outdoor Temperature (°C DB)
40°C
1m
MULTI V 5 can function regardless of the time at the noise sensitive aware of more than 40 different functional settings and more than 200 absorption coefficient) of particular
10°C room in
• Sound level can be increased in static pressure mode or used air guide.
ARUM100LTE5 58.0 59.0 -20°C
-5°C
Load
-10°C
ARUM120LTE5 59.0 60.0 -25°C
-15°C
ARUM140LTE5 60.0 10°C 14°C 15°C 20°C 25°C 27°C 30°C61.0 10°C 15°C 20°C 25°C27°C 30°C
Sound level Off Outdoor Units Function
ARUM160LTE5 60.5 Indoor Temperature (°C WB) 61.5 Indoor Temperature (°C DB)
Category Functions MULTI V 5 Note
Note
(Judgment time) Low-noise operation time ARUM180LTE5 61.0 1. 1.
These
These figures
figures
assume
assume thethefollowing
following
operating
operating6conditions:
2.0
conditions:
Variable Path of Outdoor Unit HEX ○ Note
ARUM20HiPOR 0LTETM5(High Pressure Oil Return) ○
62.0 Equivalent
Equivalent
Level
Level
piping
piping
difference:0m
difference:0m
length:7.5m
length:7.5m
1. These figures assume the following operating 6 4.5conditions :
Equivalent piping length : 7.5m
On ARUM22Humidity
Key Refrigerant 0LTE5Sensor ○ 64.5
2. 2.
Range
Range of pull
of pull
down
Level difference : 0m
downoperation:
operation: 65.5
Components If the
If the
relative
relative
humidity
humidity is too
is too
high,
high,
cooling
cooling
capacity
capacity
cancan
be be
decreased
decreased
by by
thethe
sensible
sensible
heat
heat
reduction.
reduction.
2. Range of pull down operation :
6:00 12:00 13:00 18:00 21:00 0:00 6:00 ARUM24Corrosion
0LTE5 Resistance Black Fin ○ 65.0 If the relative humidity is too high, cooling 67capacity
.0 can be decreased by the sensible heat
Highest Start End
outdoor temp ARUM26Oil 0LSensor
TE5 ○ 65.0 reduction.
67.0
3. Warming up operation means that the outdoor unit operates to reach the range
ARUM22Dual 1LTSensing
E5 ○ 61.5 of continuous operating, however it may6not 2.5operate continuously due to safety or
Low Noise Operation ○ protection logic.
ARUM241LTE5 62.0 63.0
High Static Mode of Outdoor Unit Fan ○
ARUM26Partial 1LTEDefrosting
5 ○
6 2.5 63.5
Multi
Multi V 5V 5 Outdoor Units
ARUM28Auto 0LTDust
E5 Removal of Outdoor Unit 62.8 63.8 Outdoor Units
○ 9. Operation
Simultaneous
9. Operation Limits Limits
Cooling / Heating Operation
ARUM30(Fan
Useful Function 0LTreverse
E5 rotation) 63.1 64.1
Indoor Cooling Comfort Mode Based Simultaneous
Cooling Cooling / Heating Operation
ARUM32Outdoor 0LTE5Temperature ○ 63.8 Simultaneous Cooling / Heating
65.8Heating
Operation
ARUM34Smart 0LTELoad
5 Control (SLC) 65.6 30°C
66.6 20°C
Load (Changing indoor discharge air ○
ARUM36temperature
0LTE5 according to load) 66.0 67.8
ARUM38Outdoor 0LTE5Unit Control Refer to Humidity ○ 66.2 68.0 16°C
25°C 675675
ARUM62AC 0LManager
TE5 5 PACM5A00068.6 Note
Note
Indoor Temperature (°C WB) 70.5 Indoor Temperature (°C DB)
ARUM64ACP
BNU (Building 0LTLonworks
E5 PLNWKB000
68.7 1. 1. These
These
Note
figures
figures
Equivalent
assume
assume
piping
thethe following
following
length:7.5m
operating
operating 7conditions:
0.6
conditions:
Network Unit) ACP BACnet PQNFB17C0 Equivalent piping length:7.5m
ARUM660LTE5 68.8 1. These
Level figures
difference:0m
Level difference:0m assume the following 70.6 conditions :
operating
Cycle Monitoring Diagnosis Installation Smart Management Refrigerant Charging Kit PRAC1 2. 2.
Range
Equivalent
Range of pull
of pull
piping
down
down
length : 7.5m
operation:
operation:
InstallationARUM68Variable0LTE5Water Flow Valve Control Kit - 69.0
IfLevel
If the the
relative
difference
relative humidity
humidity
: 0m
is toois too high,
high, cooling
cooling 7can
capacity 1.can
capacity 1be be decreased
decreased by the
by the sensible
sensible heatheat reduction.
reduction.
2. Range of pull down operation :
PDI (Power A R U M 7 0 0LTE5
Standard PPWRDB00069.6 If the relative humidity is too high, cooling 71capacity
.3 can be decreased by the sensible heat
LGMV reduction.
DistributionAIndicator)
RUM72Premium0LTE5 PQNUD1S4069.8 71.8
Cool / Heat AR UM740LTE5
Selector PRDSBM 69.1 70.9
Low Ambient Kit PRVC2
ARUM760LTE5 69.2 70.9
IO Module (ODU Dry Contact) PVDSMN000
Cycle Monitoring LGMV PRCTIL0
Device Mobile LGMV PLGMVW100 677
676676
032 / 033
OUTDOOR UNITS _ MULTI V 5 _ Q&A
Q1 What are the differences between MULTI V IV and MULTI V 5? Q3 How does MULTI V 5 operate when humidity reference of the dual sensing SLC is that of the outdoor?
A1 Category MULTI V IV H/P (ARUN***LTE4) MULTI V 5 H/P & H/R (ARUM***LTE5) A3 During dual sensing SLC, outdoor unit changes target pressure of the system referring to temperature and humidity in cooling mode.
MULTI V 5
- When the humidity of outdoor side is higher than that of indoor side, outdoor unit will lower target pressure to remove humidity, thus
Vapor Injection ◯ ◯
outdoor unit will consume more energy and indoor will be more cooled compared to SLC operation but more efficiency than normal operation.
HiPORTM ◯ ◯
Height Difference (ODU ~ IDU / IDU ~ IDU) 110m / 40m 110m / 40m
Normal operation (non -SLC)
Cooling Operating Range (OAT, °CDB) -10 ~ 43 -15 ~ 48
20°C 25°C 30°C 35°C
Heating Operating Range (OAT, °CWB) -25 ~ 18 -25 ~ 18
1 Unit 50 ~ 200% 50 ~ 200% - When the humidity of outdoor side is lower than that of indoor side, outdoor unit will rise target pressure to save energy and keep
Combination ratio of
2 Unit 50 ~ 160% 50 ~ 160% comfort, but indoor humidity will be less removed compared to normal operation.
IDU
3 or 4 Units 50 ~ 130% 50 ~ 130%
Outdoor humidity is lower than indoor unit Evaporation temperature & efficiency
※ ○ : Applied, - : Not Applied
Outdoor unit will consume less energy Dual Sensing SLC (Low Humidity)
30%< Relative Humidity<50%
ODU IDU Compatibility ODU DIP Switch No. 3 If dip switch setting is not correct Ref. 20°C 25°C 30°C 35°C
Discharge air will be less cold than normal or
SLC operation. Efficiency SLC under the low humidity condition
Can not communicate between Indoor (%)
Must be OFF
Gen. 2 (ARNU*2) ◯ & Outdoor unit
(factory default)
(System will not be operated)
ODU main PCB dip switch is all “OFF” at default state SW04C (X : cancel) Setting summary
SW03C (▶: forward) DIP-SW01 #5 On
(1) Check and make sure that all connected indoor units are 4 series. (ARNU******4.) SW02C (◀ : backward) Func > Fn14 >
(2) Change Dip switch No. 3 from OFF → ON Off, op1 ~ op3
SW01C (●: Confirm/
(3) Push the reset button. Automatic Addressing)
SW01D (reset)
Dip Switch 7 Segment
Indoor humidity CASE 2. Dual Sensing SLC with Indoor humidity sensor in New Standard
ON ON R/C setting (PREMTB100)
Setting summary
Reset Function>
button Smart Load Control>
Off, op1 ~ op3
1 2 3 4 5 6 7 1 2 3 4 5 6 7
1 2 3 4 5 6 7 1 2 3 4 5 6 7
※ User can turn off humidity control in ODU Setting (humidity reference)
<Setting summary> ODU DIP-SW01 #5 On > Func > Fn16 > Off
034 / 035
OUTDOOR UNITS _ MULTI V 5 _ Q&A
MULTI V 5
Upper electrode
The capacitive measurement principle established and proved itself as a standard in the past. Thin-film polymer
For this principle, the sensor element is built out of a capacitor. The dielectric is a polymer Lower electrode
Fan The static pressure of MULTI V 5 is max. 8 mmAq as MULTI V IV?? Yes, the static pressure of MULTI V 5 is the same as MULTI V IV.
which absorbs or releases water proportional to the relative environmental humidity, and thus Glass substrate
changes the capacitance of the capacitor. This change in capacitance can be measured by an
electronic circuit. For humidity sensors with CMOSensⓇ technology, a “micro-machined” finger
electrode system with different protective and polymer cover layers forms the capacitance for Is the limitation of Compressor max. Hz applied No, the limitation of comp Hz is not applied for default.
Compressor
the sensor chip, and, in addition to providing the sensor property, simultaneously protects the by the capacity of outdoor unit? But, it can be set by option for limitation of max. Hz (or current).
sensor from interference in ways previously not achieved.
Humidity
Where is Indoor Humidity sensor? It is placed inside of the RS3 remote controller.
Sensor
Remote Does remote controller show the humidity information (Status) as Yes. It shows the current humidity information on screen.
Q5 What is difference in refrigerant piping connection between heat pump and heat recovery? Controller well? (for RS3 Only) But has no function to control the humidity.
A5 From MULTI V 5, Low pressure gas pipe in heat pump operation changes to high pressure gas pipe in heat recovery operation
due to internal cycle. So for heat pump cycle, no. 1, 3 pipe should be connected and for heat recovery operation, No. 1, 2, 3 pipe is
connected. (For the heat pump operation, DO NOT connect No.2 pipe)
Remote Is it possible to connect the local humidity sensor with Remote No. All of RS3 remote controller can not be connected
Controller controller (RS3)? with local humidity sensor.
SLC Does dual sensing SLC function control the humidity ratio? No. There is no control of humidity ratio.
Close Close
Comfort cooling need super heating controlled and Comfort heating need sub
Low Pressure
Comfort
Liquid pipe
Liquid pipe
Why is not the comfort heating applied in product? cooling controlled. In case of controlling EEV for sub cooling, noise and stable
Gas pipe
Gas pipe
Gas pipe
Cooling
operation may be affected and critical.
8HP 9.52 19.05 15.88 8HP 9.52 No Use 19.05 15.88 19.05 Does the IDU – Central controller direct connection for
Installation No, it is not possible.
10HP 9.52 22.2 19.05 10HP 9.52 No Use 22.2 communication cable is possible? (Flat connection)
19.05 22.2
20HP 15.88 28.58 22.2 20HP 15.88 No Use 28.58 22.2 28.58
※ For using as Heat Pump, Reducer for Gas pipe should be used.
Reducer is included in outdoor unit.
036 / 037
1,000m
HEAT PUMP TOTAL PIPING LENGTH 225m
Longest Piping Length
MULTI V 5
Height Difference
- 22.4kW ~ 268.8kW (Cooling capacity based)
- 3Ø, 380 ~ 415V, 50Hz
110m
- Top discharge outdoor unit
Energy savings
Partial Defrost
Reliability
Designed
Design
For
For
The Ultimate Low noise
The Ultimate
Advanced performance
038 / 039
OUTDOOR UNITS _ MULTI V 5 _ SPECIFICATION
OUTDOOR
UNITS
ARUN080LTE5 / ARUN100LTE5 ARUN160LTE5 / ARUN180LTE5
ARUN120LTE5 / ARUN140LTE5 ARUN200LTE5 / ARUN220LTE5
MULTI V 5
HP 8 10 12 14 HP 16 18 20 22
Combination Unit ARUN080LTE5 ARUN100LTE5 ARUN120LTE5 ARUN140LTE5 Combination Unit ARUN160LTE5 ARUN180LTE5 ARUN200LTE5 ARUN220LTE5
Model Name Model Name
Independent Unit ARUN080LTE5 ARUN100LTE5 ARUN120LTE5 ARUN140LTE5 Independent Unit ARUN160LTE5 ARUN180LTE5 ARUN200LTE5 ARUN220LTE5
kW 22.4 28.0 33.6 39.2 kW 44.8 50.4 56.0 61.6
Cooling (Rated) Cooling (Rated)
Btu/h 76,400 95,500 114,600 133,800 Btu/h 152,900 172,000 191,100 210,200
Capacity Capacity
kW 25.2 31.5 37.8 44.1 kW 50.4 56.7 63.0 69.3
Heating (Rated) Heating (Rated)
Btu/h 86,000 107,500 129,000 150,500 Btu/h 172,000 193,500 215,000 236,500
Cooling (Rated) kW 4.59 5.70 7.91 9.12 Cooling (Rated) kW 10.80 10.96 12.31 14.84
Input Input
Heating (Rated) kW 4.74 5.78 8.06 9.78 Heating (Rated) kW 11.59 12.06 15.52 17.54
EER (Rated) 4.88 4.91 4.25 4.30 EER (Rated) 4.15 4.60 4.55 4.15
COP (Rated) 5.32 5.45 4.69 4.51 COP (Rated) 4.35 4.70 4.06 3.95
Power Factor Rated - 0.93 0.93 0.93 0.93 Power Factor Rated - 0.93 0.93 0.93 0.93
Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray
Exterior Exterior
RAL code NL503K / NA507K NL503K / NA507K NL503K / NA507K NL503K / NA507K RAL code NL503K / NA507K NL503K / NA507K NL503K / NA507K NL503K / NA507K
Heat Exchanger Wide Louver Plus Wide Louver Plus Wide Louver Plus Wide Louver Plus Heat Exchanger Wide Louver Plus Wide Louver Plus Wide Louver Plus Wide Louver Plus
Compressor Motor Output x Number W x No. 5,300 x 1 5,300 x 1 5,300 x 1 5,300 x 1 Compressor Motor Output x Number W x No. 5,300 x 1 5,300 x 1 + 4,200 x 1 5,300 x 2 5,300 x 2
Type Propeller fan Propeller fan Propeller fan Propeller fan Type Propeller fan Propeller fan Propeller fan Propeller fan
Motor Output x Number W 1,200 x 1 1,200 x 1 1,200 x 1 900 x 2 Motor Output x Number W 900 x 2 900 x 2 900 x 2 900 x 2
m3/min 240 x 1 240 x 1 240 x 1 320 x 1 m3/min 320 x 1 320 x 1 320 x 1 320 x 1
Air Flow Rate (High) Air Flow Rate (High)
Fan ft3/min 8,476 x 1 8,476 x 1 8,476 x 1 11,301 x 1 Fan ft3/min 11,301 x 1 11,301 x 1 11,301 x 1 11,301 x 1
External Static Pressure (Max, Pa) 80 80 80 80 External Static Pressure (Max, Pa) 80 80 80 80
Drive DC INVERTER DC INVERTER DC INVERTER DC INVERTER Drive DC INVERTER DC INVERTER DC INVERTER DC INVERTER
Discharge Side / Top TOP TOP TOP TOP Discharge Side / Top TOP TOP TOP TOP
Pipe Liquid Pipe mm (inch) 9.52 (3/8) 9.52 (3/8) 12.7 (1/2) 12.7 (1/2) Pipe Liquid Pipe mm (inch) 12.7 (1/2) 15.88 (5/8) 15.88 (5/8) 15.88 (5/8)
Connections Gas Pipe mm (inch) 19.05 (3/4) 22.2 (7/8) 28.58 (1-1/8) 28.58 (1-1/8) Connections Gas Pipe mm (inch) 28.58 (1-1/8) 28.58 (1-1/8) 28.58 (1-1/8) 28.58 (1-1/8)
Dimensions (W x H x D) mm x No. (930 x 1,690 x 760) x 1 (930 x 1,690 x 760) x 1 (930 x 1,690 x 760) x 1 (1,240 x 1,690 x 760) x 1 Dimensions (W x H x D) mm x No. (1,240 x 1,690 x 760) x 1 (1,240 x 1,690 x 760) x 1 (1,240 x 1,690 x 760) x 1 (1,240 x 1,690 x 760) x 1
kg 188 x 1 188 x 1 188 x 1 220 x 1 kg 220 x 1 260 x 1 274 x 1 274 x 1
Net Weight Net Weight
lbs 448 x 1 448 x 1 448 x 1 507 x 1 lbs 507 x 1 595 x 1 635 x 1 635 x 1
Sound Cooling dB(A) 58.0 58.0 59.0 60.0 Sound Cooling dB(A) 60.5 61.0 62.0 64.5
Pressure Level Heating dB(A) 59.0 59.0 60.0 61.0 Pressure Level Heating dB(A) 61.5 62.0 64.5 65.5
Sound Cooling dB(A) 78.0 78.0 79.0 82.0 Sound Cooling dB(A) 83.0 85.0 86.0 86.0
Power Level Heating dB(A) 79.0 79.0 80.0 84.0 Power Level Heating dB(A) 85.0 86.0 87.0 88.0
mm2 x No. mm2 x No.
Communication Cable 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C Communication Cable 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C
(VCTF-SB) (VCTF-SB)
Refrigerant name R410A R410A R410A R410A Refrigerant name R410A R410A R410A R410A
Precharged Amount kg 10.0 10.0 10.0 13.0 Precharged Amount kg 13.0 13.0 14.0 14.0
Refrigerant in factory lbs 22.0 22.0 22.0 28.7 Refrigerant in factory lbs 28.7 28.7 30.9 30.9
t-CO2eq 20.9 20.9 20.9 27.1 t-CO2eq 27.1 27.1 29.2 29.2
Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50
Power Supply Ø, V, Hz Power Supply Ø, V, Hz
3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60
Number of maximum connectable indoor units 13 (20) 16 (25) 20 (30) 23 (35) Number of maximum connectable indoor units 26 (40) 29 (45) 32 (50) 35 (56)
Note Note
1. Due to our policy of innovation some specifications may be changed without notification. 1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical work and design. 2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Power factor could vary less than ±1% according to the operating conditions. 3. Power factor could vary less than ±1% according to the operating conditions.
4. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard. 4. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard. Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard.
Therefore, these values can be increased owing to ambient conditions during operation. Therefore, these values can be increased owing to ambient conditions during operation.
5. Performances are based on the following conditions : 5. Performances are based on the following conditions :
*Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB *Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
*Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB *Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is Zero. Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is Zero.
6. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination. 6. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination.
The recommended ratio is 130%. The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases. (R410A, GWP(Global warming potential) = 2087.5) 7. This product contains Fluorinated greenhouse gases. (R410A, GWP(Global warming potential) = 2087.5)
040 / 041
OUTDOOR UNITS _ MULTI V 5 _ SPECIFICATION
OUTDOOR
UNITS
ARUN240LTE5 / ARUN260LTE5
ARUN261LTE5 / ARUN280LTE5
ARUN300LTE5 / ARUN320LTE5
MULTI V 5
HP 24 26
HP 26' 28 30 32
Combination Unit ARUN261LTE5 ARUN280LTE5 ARUN300LTE5 ARUN320LTE5
Model Name ARUN140LTE5 ARUN160LTE5 ARUN180LTE5 ARUN200LTE5
Independent Unit
ARUN120LTE5 ARUN120LTE5 ARUN120LTE5 ARUN120LTE5
kW 72.8 78.4 84.0 89.6
Combination Unit ARUN240LTE5 ARUN260LTE5 Cooling (Rated)
Model Name Btu/h 248,400 267,500 286,600 305,700
Independent Unit ARUN240LTE5 ARUN260LTE5 Capacity
kW 81.9 88.2 94.5 100.8
kW 67.2 72.8 Heating (Rated)
Cooling (Rated) Btu/h 279,500 301,000 322,500 344,000
Btu/h 229,300 248,400 Cooling (Rated) kW 17.02 18.70 18.86 20.21
Capacity Input
kW 74.3 74.3 Heating (Rated) kW 17.84 19.65 20.12 23.58
Heating (Rated)
Btu/h 253,400 253,400 EER (Rated) 4.28 4.19 4.45 4.43
Cooling (Rated) kW 16.76 19.41 COP (Rated) 4.59 4.49 4.70 4.28
Input
Heating (Rated) kW 18.85 19.49 Power Factor Rated - 0.93 0.93 0.93 0.93
EER (Rated) 4.01 3.75 Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray
COP (Rated) 3.94 3.81 Exterior
RAL code NL503K / NA507K NL503K / NA507K NL503K / NA507K NL503K / NA507K
Power Factor Rated - 0.93 0.93 Heat Exchanger Wide Louver Plus Wide Louver Plus Wide Louver Plus Wide Louver Plus
Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray Compressor Motor Output x Number W x No. 5,300 x 2 5,300 x 2 (5,300 x 2) + (4,200 x 1) (5,300 x 2) + (4,200 x 1)
Exterior
RAL code NL503K / NA507K NL503K / NA507K Type Propeller fan Propeller fan Propeller fan Propeller fan
Heat Exchanger Wide Louver Plus Wide Louver Plus Motor Output x Number W (900 x 2) + (1,200 x 1) (900 x 2) + (1,200 x 1) (900 x 2) + (1,200 x 1) (900 x 2) + (1,200 x 1)
Compressor Motor Output x Number W x No. 5,300 x 2 5,300 x 2 m3/min (320 x 1) + (240 x 1) (320 x 1) + (240 x 1) (320 x 1) + (240 x 1) (320 x 1) + (240 x 1)
Type Propeller fan Propeller fan Air Flow Rate (High)
Fan ft3/min (11,301 x 1) + (8,476 x 1) (11,301 x 1) + (8,476 x 1) (11,301 x 1) + (8,476 x 1) (11,301 x 1) + (8,476 x 1)
Motor Output x Number W 900 x 2 900 x 2 External Static Pressure (Max, Pa) 80 80 80 80
m3/min 320 x 1 320 x 1 Drive DC INVERTER DC INVERTER DC INVERTER DC INVERTER
Air Flow Rate (High)
Fan ft /min
3
11,301 x 1 11,301 x 1 Discharge Side / Top TOP TOP TOP TOP
External Static Pressure (Max, Pa) 80 80 Liquid Pipe mm (inch) 19.05 (3/4) 19.05 (3/4) 19.05 (3/4) 19.05 (3/4)
Pipe
Drive DC INVERTER DC INVERTER Connections Gas Pipe mm (inch) 34.9 (1-3/8) 34.9 (1-3/8) 34.9 (1-3/8) 34.9 (1-3/8)
Discharge Side / Top TOP TOP (1,240 x 1,690 x 760) x 1 (1,240 x 1,690 x 760) x 1 (1,240 x 1,690 x 760) x 1 (1,240 x 1,690 x 760) x 1
Dimensions (W x H x D) mm x No.
Pipe Liquid Pipe mm (inch) 15.88 (5/8) 19.05 (3/4) + (930 x 1,690 x 760) x 1 + (930 x 1,690 x 760) x 1 + (930 x 1,690 x 760) x 1 + (930 x 1,690 x 760) x 1
Connections Gas Pipe mm (inch) 34.9 (1-3/8) 34.9 (1-3/8) kg (220 x 1) + (188 x 1) (220 x 1) + (188 x 1) (260 x 1) + (188 x 1) (274 x 1) + (188 x 1)
Net Weight
Dimensions (W x H x D) mm x No. (1,240 x 1,690 x 760) x 1 (1,240 x 1,690 x 760) x 1 lbs (507 x 1) + (448 x 1) (507 x 1) + (448 x 1) (595 x 1) + (448 x 1) (635 x 1) + (448 x 1)
kg 276 x 1 276 x 1 Sound Cooling dB(A) 62.5 62.8 63.1 63.8
Net Weight Pressure Level Heating
lbs 639 x 1 639 x 1 dB(A) 63.5 63.8 64.1 65.8
Sound Cooling dB(A) 65.0 65.0 Sound Cooling dB(A) 83.8 84.5 86.0 86.8
Pressure Level Heating dB(A) 67.0 67.0 Power Level Heating dB(A) 85.5 86.2 87.0 87.8
Sound Cooling dB(A) 88.0 88.0 mm2 x No.
Communication Cable 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C
Power Level (VCTF-SB)
Heating dB(A) 90.0 90.0
Refrigerant name R410A R410A R410A R410A
mm x No.2
Communication Cable 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C kg 13.0 + 10.0 13.0 + 10.0 13.0 + 10.0 14.0 + 10.0
(VCTF-SB) Precharged Amount
Refrigerant name R410A R410A Refrigerant in factory lbs 28.7 + 22.0 28.7 + 22.0 28.7 + 22.0 30.9 + 22.0
Precharged Amount kg 16.0 16.0 t-CO2eq 48.0 48.0 48.0 50.1
Refrigerant in factory lbs 35.3 35.3 Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
t-CO2eq 33.4 33.4 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50
Power Supply Ø, V, Hz
Control Electronic Expansion Valve Electronic Expansion Valve 3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60
3, 380-415, 50 3, 380-415, 50 Number of maximum connectable indoor units 42 (52) 45 (56) 49 (60) 52 (64)
Power Supply Ø, V, Hz
3, 380, 60 3, 380, 60
Number of maximum connectable indoor units 39 (61) 42 (64)
Note Note
1. Due to our policy of innovation some specifications may be changed without notification. 1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical work and design. 2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Power factor could vary less than ±1% according to the operating conditions. 3. Power factor could vary less than ±1% according to the operating conditions.
4. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard. 4. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard. Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard.
Therefore, these values can be increased owing to ambient conditions during operation. Therefore, these values can be increased owing to ambient conditions during operation.
5. Performances are based on the following conditions : 5. Performances are based on the following conditions :
*Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB *Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
*Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB *Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is Zero. Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is Zero.
6. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination. 6. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination.
The recommended ratio is 130%. The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases. (R410A, GWP(Global warming potential) = 2087.5) 7. This product contains Fluorinated greenhouse gases. (R410A, GWP(Global warming potential) = 2087.5)
042 / 043
OUTDOOR UNITS _ MULTI V 5 _ SPECIFICATION
OUTDOOR
UNITS
ARUN340LTE5 / ARUN360LTE5 ARUN420LTE5 / ARUN440LTE5
ARUN380LTE5 / ARUN400LTE5 ARUN460LTE5 / ARUN480LTE5
MULTI V 5
HP 34 36 38 40 HP 42 44 46 48
Combination Unit ARUN340LTE5 ARUN360LTE5 ARUN380LTE5 ARUN400LTE5 Combination Unit ARUN420LTE5 ARUN440LTE5 ARUN460LTE5 ARUN480LTE5
Model Name ARUN220LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 Model Name ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5
Independent Unit Independent Unit
ARUN120LTE5 ARUN120LTE5 ARUN140LTE5 ARUN160LTE5 ARUN180LTE5 ARUN200LTE5 ARUN220LTE5 ARUN240LTE5
kW 95.2 100.8 106.4 112.0 kW 117.6 123.2 128.8 134.4
Cooling (Rated) Cooling (Rated)
Btu/h 324,800 343,900 363,100 382,200 Btu/h 401,300 420,400 439,500 458,600
Capacity Capacity
kW 107.1 112.1 118.4 124.7 kW 131.0 137.3 143.6 148.5
Heating (Rated) Heating (Rated)
Btu/h 365,500 382,400 403,900 425,400 Btu/h 446,900 468,400 489,900 506,800
Cooling (Rated) kW 22.75 24.66 25.87 27.55 Cooling (Rated) kW 27.71 29.07 31.60 33.52
Input Input
Heating (Rated) kW 25.60 26.91 28.62 30.43 Heating (Rated) kW 30.91 34.36 36.39 37.69
EER (Rated) 4.18 4.09 4.11 4.06 EER (Rated) 4.24 4.24 4.08 4.01
COP (Rated) 4.18 4.16 4.13 4.10 COP (Rated) 4.24 3.99 3.94 3.94
Power Factor Rated - 0.93 0.93 0.93 0.93 Power Factor Rated - 0.93 0.93 0.93 0.93
Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray
Exterior Exterior
RAL code NL503K / NA507K NL503K / NA507K NL503K / NA507K NL503K / NA507K RAL code NL503K / NA507K NL503K / NA507K NL503K / NA507K NL503K / NA507K
Heat Exchanger Wide Louver Plus Wide Louver Plus Wide Louver Plus Wide Louver Plus Heat Exchanger Wide Louver Plus Wide Louver Plus Wide Louver Plus Wide Louver Plus
Compressor Motor Output x Number W x No. 5,300 x 3 5,300 x 3 5,300 x 3 5,300 x 3 Compressor Motor Output x Number W x No. (5,300 x 3) + (4,200 x 1) 5,300 x 4 5,300 x 4 5,300 x 4
Type Propeller fan Propeller fan Propeller fan Propeller fan Type Propeller fan Propeller fan Propeller fan Propeller fan
Motor Output x Number W (900 x 2) + (1,200 x 1) (900 x 2) + (1,200 x 1) 900 x 4 900 x 4 Motor Output x Number W 900 x 4 900 x 4 900 x 4 900 x 4
m3/min (320 x 1) + (240 x 1) (320 x 1) + (240 x 1) 320 x 2 320 x 2 m3/min 320 x 2 320 x 2 320 x 2 320 x 2
Air Flow Rate (High) Air Flow Rate (High)
Fan ft3/min (11,301 x 1) + (8,476 x 1) (11,301 x 1) + (8,476 x 1) 11,301 x 2 11,301 x 2 Fan ft3/min 11,301 x 2 11,301 x 2 11,301 x 2 11,301 x 2
External Static Pressure (Max, Pa) 80 80 80 80 External Static Pressure (Max, Pa) 80 80 80 80
Drive DC INVERTER DC INVERTER DC INVERTER DC INVERTER Drive DC INVERTER DC INVERTER DC INVERTER DC INVERTER
Discharge Side / Top TOP TOP TOP TOP Discharge Side / Top TOP TOP TOP TOP
Pipe Liquid Pipe mm (inch) 19.05 (3/4) 19.05 (3/4) 19.05 (3/4) 19.05 (3/4) Pipe Liquid Pipe mm (inch) 19.05 (3/4) 19.05 (3/4) 19.05 (3/4) 19.05 (3/4)
Connections Gas Pipe mm (inch) 34.9 (1-3/8) 41.3 (1-5/8) 41.3 (1-5/8) 41.3 (1-5/8) Connections Gas Pipe mm (inch) 41.3 (1-5/8) 41.3 (1-5/8) 41.3 (1-5/8) 41.3 (1-5/8)
(1,240 x 1,690 x 760) x 1 (1,240 x 1,690 x 760) x 1 Dimensions (W x H x D) mm x No. (1,240 x1,690 x 760) x 2 (1,240 x1,690 x 760) x 2 (1,240 x1,690 x 760) x 2 (1,240 x1,690 x 760) x 2
Dimensions (W x H x D) mm x No. (1,240 x1,690 x 760) x 2 (1,240 x1,690 x 760) x 2
+ (930 x 1,690 x 760) x 1 + (930 x 1,690 x 760) x 1
kg (276 x 1) + (260 x 1) (276 x 1) + (274 x 1) (276 x 1) + (274 x 1) 276 x 2
kg (274 x 1) + (188 x 1) (276 x 1) + (188 x 1) (276 x 1) + (220 x 1) (276 x 1) + (220 x 1) Net Weight
Net Weight lbs (639 x 1) + (595 x 1) (639 x 1) + (635 x 1) (639 x 1) + (635 x 1) 639 x 2
lbs (635 x 1) + (448 x 1) (639 x 1) + (448 x 1) (639 x 1) + (507 x 1) (639 x 1) + (507 x 1)
Sound Cooling dB(A) 66.5 66.8 67.8 68.0
Sound Cooling dB(A) 65.6 66.0 66.2 66.3 Pressure Level Heating dB(A) 68.2 68.9 69.3 70.0
Pressure Level Heating dB(A) 66.6 67.8 68.0 68.1
Sound Cooling dB(A) 89.8 90.1 90.1 91.0
Sound Cooling dB(A) 86.8 88.5 89.0 89.2 Power Level Heating dB(A) 91.5 91.8 92.1 93.0
Power Level Heating dB(A) 88.6 90.4 91.0 91.2
mm2 x No.
mm x No.
2 Communication Cable 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C
Communication Cable 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C (VCTF-SB)
(VCTF-SB)
Refrigerant name R410A R410A R410A R410A
Refrigerant name R410A R410A R410A R410A
Precharged Amount kg 16.0 + 13.0 16.0 + 14.0 16.0 + 14.0 16.0 + 16.0
Precharged Amount kg 14.0 + 10.0 16.0 + 10.0 16.0 + 13.0 16.0 + 13.0 in factory
Refrigerant lbs 35.3 + 28.7 35.3 + 30.9 35.3 + 30.9 35.3 + 35.3
Refrigerant in factory lbs 30.9 + 22.0 35.3 + 22.0 35.3 + 28.7 35.3 + 28.7
t-CO2eq 60.5 62.6 62.6 66.8
t-CO2eq 50.1 54.3 60.5 60.5
Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50
3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 Power Supply Ø, V, Hz
Power Supply Ø, V, Hz 3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60
3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60
Number of maximum connectable indoor units 64 64 64 64
Number of maximum connectable indoor units 55 (64) 58 (64) 61 (64) 64
Note Note
1. Due to our policy of innovation some specifications may be changed without notification. 1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical work and design. 2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Power factor could vary less than ±1% according to the operating conditions. 3. Power factor could vary less than ±1% according to the operating conditions.
4. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard. 4. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard. Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard.
Therefore, these values can be increased owing to ambient conditions during operation. Therefore, these values can be increased owing to ambient conditions during operation.
5. Performances are based on the following conditions : 5. Performances are based on the following conditions :
*Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB *Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
*Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB *Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is Zero. Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is Zero.
6. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination. 6. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination.
The recommended ratio is 130%. The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases. (R410A, GWP(Global warming potential) = 2087.5) 7. This product contains Fluorinated greenhouse gases. (R410A, GWP(Global warming potential) = 2087.5)
044 / 045
OUTDOOR UNITS _ MULTI V 5 _ SPECIFICATION
OUTDOOR
UNITS
ARUN500LTE5 / ARUN520LTE5 ARUN580LTE5 / ARUN600LTE5
ARUN540LTE5 / ARUN560LTE5 ARUN620LTE5 / ARUN640LTE5
MULTI V 5
HP 50 52 54 56 HP 58 60 62 64
Combination Unit ARUN500LTE5 ARUN520LTE5 ARUN540LTE5 ARUN560LTE5 Combination Unit ARUN580LTE5 ARUN600LTE5 ARUN620LTE5 ARUN640LTE5
Model Name ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5
Model Name
Independent Unit ARUN140LTE5 ARUN160LTE5 ARUN180LTE5 ARUN200LTE5 Independent Unit ARUN220LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5
ARUN120LTE5 ARUN120LTE5 ARUN120LTE5 ARUN120LTE5 ARUN120LTE5 ARUN120LTE5 ARUN140LTE5 ARUN160LTE5
kW 140.0 145.6 151.2 156.8 kW 162.4 168.0 173.6 179.2
Cooling (Rated) Cooling (Rated)
Btu/h 477,700 496,800 515,900 535,000 Btu/h 554,100 573,200 592,400 611,500
Capacity Capacity
kW 156.2 162.5 168.8 175.1 kW 181.4 186.3 192.6 198.9
Heating (Rated) Heating (Rated)
Btu/h 532,900 554,400 575,900 597,400 Btu/h 618,900 635,800 657,300 678,800
Cooling (Rated) kW 33.78 35.46 35.62 36.97 Cooling (Rated) kW 39.51 41.42 42.63 44.31
Input Input
Heating (Rated) kW 36.68 38.49 38.97 42.42 Heating (Rated) kW 44.45 45.75 47.47 49.28
EER (Rated) 4.14 4.11 4.24 4.24 EER (Rated) 4.11 4.06 4.07 4.04
COP (Rated) 4.26 4.22 4.33 4.13 COP (Rated) 4.08 4.07 4.06 4.04
Power Factor Rated - 0.93 0.93 0.93 0.93 Power Factor Rated - 0.93 0.93 0.93 0.93
Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray
Exterior Exterior
RAL code NL503K / NA507K NL503K / NA507K NL503K / NA507K NL503K / NA507K RAL code NL503K / NA507K NL503K / NA507K NL503K / NA507K NL503K / NA507K
Heat Exchanger Wide Louver Plus Wide Louver Plus Wide Louver Plus Wide Louver Plus Heat Exchanger Wide Louver Plus Wide Louver Plus Wide Louver Plus Wide Louver Plus
Compressor Motor Output x Number W x No. 5,300 x 4 5,300 x 4 (5,300 x 4) + (4,200 x 1) 5,300 x 5 Compressor Motor Output x Number W x No. 5,300 x 5 5,300 x 5 5,300 x 5 5,300 x 5
Type Propeller fan Propeller fan Propeller fan Propeller fan Type Propeller fan Propeller fan Propeller fan Propeller fan
Motor Output x Number W (900 x 4) + (1,200 x 1) (900 x 4) + (1,200 x 1) (900 x 4) + (1,200 x 1) (900 x 4) + (1,200 x 1) Motor Output x Number W (900 x 4) + (1,200 x 1) (900 x 4) + (1,200 x 1) 900 x 6 900 x 6
m3/min (320 x 2) + (240 x 1) (320 x 2) + (240 x 1) (320 x 2) + (240 x 1) (320 x 2) + (240 x 1) m3/min (320 x 2) + (240 x 1) (320 x 2) + (240 x 1) 320 x 3 320 x 3
Air Flow Rate (High) Air Flow Rate (High)
Fan ft3/min (11,301 x 2) + (8,476 x 1) (11,301 x 2) + (8,476 x 1) (11,301 x 2) + (8,476 x 1) (11,301 x 2) + (8,476 x 1) Fan ft3/min (11,301 x 2) + (8,476 x 1) (11,301 x 2) + (8,476 x 1) 11,301 x 3 11,301 x 3
External Static Pressure (Max, Pa) 80 80 80 80 External Static Pressure (Max, Pa) 80 80 80 80
Drive DC INVERTER DC INVERTER DC INVERTER DC INVERTER Drive DC INVERTER DC INVERTER DC INVERTER DC INVERTER
Discharge Side / Top TOP TOP TOP TOP Discharge Side / Top TOP TOP TOP TOP
Pipe Liquid Pipe mm (inch) 19.05 (3/4) 19.05 (3/4) 19.05 (3/4) 19.05 (3/4) Pipe Liquid Pipe mm (inch) 19.05 (3/4) 19.05 (3/4) 22.2 (7/8) 22.2 (7/8)
Connections Gas Pipe mm (inch) 41.3 (1-5/8) 41.3 (1-5/8) 41.3 (1-5/8) 41.3 (1-5/8) Connections Gas Pipe mm (inch) 41.3 (1-5/8) 41.3 (1-5/8) 44.5 (1-3/4) 44.5 (1-3/4)
(1,240 x 1,690 x 760) x 2 (1,240 x 1,690 x 760) x 2 (1,240 x 1,690 x 760) x 2 (1,240 x 1,690 x 760) x 2 (1,240 x 1,690 x 760) x 2 (1,240 x 1,690 x 760) x 2
Dimensions (W x H x D) mm x No. Dimensions (W x H x D) mm x No. (1,240 x1,690 x 760) x 3 (1,240 x1,690 x 760) x 3
+ (930 x 1,690 x 760) x 1 + (930 x 1,690 x 760) x 1 + (930 x 1,690 x 760) x 1 + (930 x 1,690 x 760) x 1 + (930 x 1,690 x 760) x 1 + (930 x 1,690 x 760) x 1
(276 x 1) + (220 x 1) + (276 x 1) + (220 x 1) + (276 x 1) + (260 x 1) + (276 x 1) + (274 x 1) + (276 x 1) + (274 x 1) +
kg kg (276 x 2) + (188 x 1) (276 x 2) + (220 x 1) (276 x 2) + (220 x 1)
(188 x 1) (188 x 1) (188 x 1) (188 x 1) (188 x 1)
Net Weight Net Weight
(639 x 1) + (507 x 1) + (639 x 1) + (507 x 1) + (639 x 1) + (595 x 1) + (639 x 1) + (635 x 1) + (639 x 1) + (635 x 1) +
lbs lbs (639 x 2) + (448 x 1) (639 x 2) + (507 x 1) (639 x 2) + (507 x 1)
(448 x 1) (448 x 1) (448 x 1) (448 x 1) (448 x 1)
Sound Cooling dB(A) 67.0 67.1 67.2 67.4 Sound Cooling dB(A) 68.3 68.5 68.6 68.7
Pressure Level Heating dB(A) 68.6 68.7 68.8 69.5 Pressure Level Heating dB(A) 69.8 70.4 70.5 70.6
Sound Cooling dB(A) 89.4 89.6 90.1 90.4 Sound Cooling dB(A) 90.4 91.3 91.5 91.6
Power Level Heating dB(A) 91.3 91.5 91.8 92.0 Power Level Heating dB(A) 92.4 93.2 93.5 93.6
mm2 x No. mm2 x No.
Communication Cable 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C Communication Cable 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C
(VCTF-SB) (VCTF-SB)
Refrigerant name R410A R410A R410A R410A Refrigerant name R410A R410A R410A R410A
Precharged Amount kg 16.0 + 13.0 + 10.0 16.0 + 13.0 + 10.0 16.0 + 13.0 + 10.0 16.0 + 14.0 + 10.0 Precharged Amount kg 16.0 + 14.0 + 10.0 16.0 + 16.0 + 10.0 16.0 + 16.0 + 13.0 16.0 + 16.0 + 13.0
Refrigerant in factory lbs 35.3 + 28.7 + 22.0 35.3 + 28.7 + 22.0 35.3 + 28.7 + 22.0 35.3 + 30.9 + 22.0 Refrigerant in factory lbs 35.3 + 30.9 + 22.0 35.3 + 35.3 + 22.0 35.3 + 35.3 + 28.7 35.3 + 35.3 + 28.7
t-CO2eq 81.4 81.4 81.4 83.5 t-CO2eq 83.5 87.7 93.9 93.9
Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50
Power Supply Ø, V, Hz Power Supply Ø, V, Hz
3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60
Number of maximum connectable indoor units 64 64 64 64 Number of maximum connectable indoor units 64 64 64 64
Note Note
1. Due to our policy of innovation some specifications may be changed without notification. 1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical work and design. 2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Power factor could vary less than ±1% according to the operating conditions. 3. Power factor could vary less than ±1% according to the operating conditions.
4. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard. 4. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard. Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard.
Therefore, these values can be increased owing to ambient conditions during operation. Therefore, these values can be increased owing to ambient conditions during operation.
5. Performances are based on the following conditions : 5. Performances are based on the following conditions :
*Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB *Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
*Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB *Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is Zero. Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is Zero.
6. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination. 6. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination.
The recommended ratio is 130%. The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases. (R410A, GWP(Global warming potential) = 2087.5) 7. This product contains Fluorinated greenhouse gases. (R410A, GWP(Global warming potential) = 2087.5)
046 / 047
OUTDOOR UNITS _ MULTI V 5 _ SPECIFICATION
OUTDOOR
UNITS
ARUN660LTE5 / ARUN680LTE5 ARUN740LTE5 / ARUN760LTE5
ARUN700LTE5 / ARUN720LTE5 ARUN780LTE5 / ARUN800LTE5
MULTI V 5
HP 66 68 70 72 HP 74 76 78 80
Combination Unit ARUN660LTE5 ARUN680LTE5 ARUN700LTE5 ARUN720LTE5 Combination Unit ARUN740LTE5 ARUN760LTE5 ARUN780LTE5 ARUN800LTE5
Model Name ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5
Independent Unit ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 Model Name ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5
Independent Unit
ARUN180LTE5 ARUN200LTE5 ARUN220LTE5 ARUN240LTE5 ARUN140LTE5 ARUN160LTE5 ARUN180LTE5 ARUN200LTE5
kW 184.8 190.4 196.0 201.6 ARUN120LTE5 ARUN120LTE5 ARUN120LTE5 ARUN120LTE5
Cooling (Rated) kW 207.2 212.8 218.4 224.0
Btu/h 630,600 649,700 668,800 687,900 Cooling (Rated)
Capacity Btu/h 707,000 726,100 745,200 764,300
kW 205.2 211.5 217.8 222.8 Capacity
Heating (Rated) kW 230.4 236.7 243.0 249.3
Btu/h 700,300 721,800 743,300 760,200 Heating (Rated)
Cooling (Rated) kW 44.47 45.82 48.36 50.27 Btu/h 786,300 807,800 829,300 850,800
Input Cooling (Rated) kW 50.54 52.22 52.38 53.73
Heating (Rated) kW 49.76 53.21 55.24 56.54 Input
EER (Rated) 4.16 4.16 4.05 4.01 Heating (Rated) kW 55.53 57.34 57.82 61.27
COP (Rated) 4.12 3.97 3.94 3.94 EER (Rated) 4.10 4.08 4.17 4.17
Power Factor Rated - 0.93 0.93 0.93 0.93 COP (Rated) 4.15 4.13 4.20 4.07
Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Power Factor Rated - 0.93 0.93 0.93 0.93
Exterior Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray
RAL code NL503K / NA507K NL503K / NA507K NL503K / NA507K NL503K / NA507K Exterior
Heat Exchanger Wide Louver Plus Wide Louver Plus Wide Louver Plus Wide Louver Plus RAL code NL503K / NA507K NL503K / NA507K NL503K / NA507K NL503K / NA507K
Compressor Motor Output x Number W x No. (5,300 x 5) + (4,200 x 1) 5,300 x 6 5,300 x 6 5,300 x 6 Heat Exchanger Wide Louver Plus Wide Louver Plus Wide Louver Plus Wide Louver Plus
Type Propeller fan Propeller fan Propeller fan Propeller fan Compressor Motor Output x Number W x No. 5,300 x 6 5,300 x 6 (5,300 x 6) + (4,200 x 1) 5,300 x 7
Motor Output x Number W 900 x 6 900 x 6 900 x 6 900 x 6 Type Propeller fan Propeller fan Propeller fan Propeller fan
m3/min 320 x 3 320 x 3 320 x 3 320 x 3 Motor Output x Number W (900 x 6) + (1,200 x 1) (900 x 6) + (1,200 x 1) (900 x 6) + (1,200 x 1) (900 x 6) + (1,200 x 1)
Air Flow Rate (High) m3/min (320 x 3) + (240 x 1) (320 x 3) + (240 x 1) (320 x 3) + (240 x 1) (320 x 3) + (240 x 1)
Fan ft /min
3
11,301 x 3 11,301 x 3 11,301 x 3 11,301 x 3 Air Flow Rate (High)
External Static Pressure (Max, Pa) 80 80 80 80 Fan ft3/min (11,301 x 3) + (8,476 x 1) (11,301 x 3) + (8,476 x 1) (11,301 x 3) + (8,476 x 1) (11,301 x 3) + (8,476 x 1)
Drive DC INVERTER DC INVERTER DC INVERTER DC INVERTER External Static Pressure (Max, Pa) 80 80 80 80
Discharge Side / Top TOP TOP TOP TOP Drive DC INVERTER DC INVERTER DC INVERTER DC INVERTER
Liquid Pipe mm (inch) 22.2 (7/8) 22.2 (7/8) 22.2 (7/8) 22.2 (7/8) Discharge Side / Top TOP TOP TOP TOP
Pipe
Connections Gas Pipe mm (inch) 53.98 (2-1/8) 53.98 (2-1/8) 53.98 (2-1/8) 53.98 (2-1/8) Pipe Liquid Pipe mm (inch) 22.2 (7/8) 22.2 (7/8) 22.2 (7/8) 22.2 (7/8)
Connections Gas Pipe mm (inch) 53.98 (2-1/8) 53.98 (2-1/8) 53.98 (2-1/8) 53.98 (2-1/8)
Dimensions (W x H x D) mm x No. (1,240 x1,690 x 760) x 3 (1,240 x1,690 x 760) x 3 (1,240 x1,690 x 760) x 3 (1,240 x1,690 x 760) x 3
(1,240 x 1,690 x 760) x 3 (1,240 x 1,690 x 760) x 3 (1,240 x 1,690 x 760) x 3 (1,240 x 1,690 x 760) x 3
kg (276 x 2) + (260 x 1) (276 x 2) + (274 x 1) (276 x 2) + (274 x 1) 276 x 3 Dimensions (W x H x D) mm x No.
Net Weight + (930 x 1,690 x 760) x 1 + (930 x 1,690 x 760) x 1 + (930 x 1,690 x 760) x 1 + (930 x 1,690 x 760) x 1
lbs (639 x 2) + (595 x 1) (639 x 2) + (635 x 1) (639 x 2) + (635 x 1) 639 x 3 kg (276 x 2) + (220 x 1) + (188 x 1) (276 x 2) + (220 x 1) + (188 x 1) (276 x 2) + (260 x 1) + (188 x 1) (276 x 2) + (274 x 1) + (188 x 1)
Cooling dB(A) 68.8 69.0 69.6 69.8 Net Weight
Sound lbs (639 x 2) + (507 x 1) + (448 x 1) (639 x 2) + (507 x 1) + (448 x 1) (639 x 2) + (595 x 1) + (448 x 1) (639 x 2) + (635 x 1) + (448 x 1)
Pressure Level Heating dB(A) 70.6 71.1 71.3 71.8
Sound Cooling dB(A) 69.1 69.2 69.2 69.4
Sound Cooling dB(A) 92.0 92.2 92.2 92.8 Pressure Level Heating dB(A) 70.9 70.9 71.0 71.4
Power Level Heating dB(A) 93.8 94.0 94.2 94.8
Sound Cooling dB(A) 91.8 91.9 92.2 92.4
mm x No.2
Power Level
Communication Cable 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C Heating dB(A) 93.7 93.8 94.0 94.2
(VCTF-SB)
mm2 x No.
Refrigerant name R410A R410A R410A R410A Communication Cable 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C
(VCTF-SB)
Precharged Amount kg 16.0 + 16.0 + 13.0 16.0 + 16.0 + 14.0 16.0 + 16.0 + 14.0 16.0 + 16.0 + 16.0 Refrigerant name R410A R410A R410A R410A
Refrigerant in factory lbs 35.3 + 35.3 + 28.7 35.3 + 35.3 + 30.9 35.3 + 35.3 + 30.9 35.3 + 35.3 + 35.3
Precharged Amount kg 16.0 + 16.0 + 13.0 + 10.0 16.0 + 16.0 + 13.0 + 10.0 16.0 + 16.0 + 13.0 + 10.0 16.0 + 16.0 + 14.0 + 10.0
t-CO2eq 93.9 96.0 96.0 100.2 Refrigerant in factory lbs 35.3 + 35.3 + 28.7 + 22.0 35.3 + 35.3 + 28.7 + 22.0 35.3 + 35.3 + 28.7 + 22.0 35.3 + 35.3 + 30.9 + 22.0
Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve t-CO2eq 114.8 114.8 114.8 116.9
3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
Power Supply Ø, V, Hz
3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50
Number of maximum connectable indoor units 64 64 64 64 Power Supply Ø, V, Hz
3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60
Number of maximum connectable indoor units 64 64 64 64
Note Note
1. Due to our policy of innovation some specifications may be changed without notification. 1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical work and design. 2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Power factor could vary less than ±1% according to the operating conditions. 3. Power factor could vary less than ±1% according to the operating conditions.
4. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard. 4. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard. Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard.
Therefore, these values can be increased owing to ambient conditions during operation. Therefore, these values can be increased owing to ambient conditions during operation.
5. Performances are based on the following conditions : 5. Performances are based on the following conditions :
*Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB *Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
*Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB *Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is Zero. Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is Zero.
6. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination. 6. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination.
The recommended ratio is 130%. The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases. (R410A, GWP(Global warming potential) = 2087.5) 7. This product contains Fluorinated greenhouse gases. (R410A, GWP(Global warming potential) = 2087.5)
048 / 049
OUTDOOR UNITS _ MULTI V 5 _ SPECIFICATION
OUTDOOR
UNITS
ARUN900LTE5 / ARUN920LTE5
ARUN820LTE5 / ARUN840LTE5
ARUN940LTE5 / ARUN960LTE5
ARUN860LTE5 / ARUN880LTE5
MULTI V 5
HP 82 84 86 88 HP 92 94
Combination Unit ARUN820LTE5 ARUN840LTE5 ARUN860LTE5 ARUN880LTE5 Combination Unit ARUN920LTE5 ARUN940LTE5
ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5
Model Name ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 Model Name ARUN240LTE5 ARUN240LTE5
Independent Unit Independent Unit
ARUN220LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5
ARUN120LTE5 ARUN120LTE5 ARUN140LTE5 ARUN160LTE5 ARUN200LTE5 ARUN220LTE5
kW 229.6 235.2 240.8 246.4 kW 257.6 263.2
Cooling (Rated) Cooling (Rated)
Btu/h 783,400 802,500 821,700 840,800 Btu/h 879,000 898,100
Capacity Capacity
kW 255.6 260.6 266.9 273.2 kW 285.8 292.1
Heating (Rated) Heating (Rated)
Btu/h 872,300 889,200 910,700 932,200 Btu/h 975,200 996,700
Cooling (Rated) kW 56.27 58.18 59.39 61.07 Cooling (Rated) kW 62.58 65.12
Input Input
Heating (Rated) kW 63.30 64.60 66.32 68.13 Heating (Rated) kW 72.06 74.08
EER (Rated) 4.08 4.04 4.05 4.03 EER (Rated) 4.12 4.04
COP (Rated) 4.04 4.03 4.02 4.01 COP (Rated) 3.97 3.94
Power Factor Rated - 0.93 0.93 0.93 0.93 Power Factor Rated - 0.93 0.93
Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray
Exterior Exterior
RAL code NL503K / NA507K NL503K / NA507K NL503K / NA507K NL503K / NA507K RAL code NL503K / NA507K NL503K / NA507K
Heat Exchanger Wide Louver Plus Wide Louver Plus Wide Louver Plus Wide Louver Plus Heat Exchanger Wide Louver Plus Wide Louver Plus
Compressor Motor Output x Number W x No. 5,300 x 7 5,300 x 7 5,300 x 7 5,300 x 7 Compressor Motor Output x Number W x No. 5,300 x 8 5,300 x 8
Type Propeller fan Propeller fan Propeller fan Propeller fan Type Propeller fan Propeller fan
Motor Output x Number W (900 x 6) + (1,200 x 1) (900 x 6) + (1,200 x 1) 900 x 8 900 x 8 Motor Output x Number W 900 x 8 900 x 8
m3/min (320 x 3) + (240 x 1) (320 x 3) + (240 x 1) 320 x 4 320 x 4 m3/min 320 x 4 320 x 4
Air Flow Rate (High) Air Flow Rate (High)
Fan ft3/min (11,301 x 3) + (8,476 x 1) (11,301 x 3) + (8,476 x 1) 11,301 x 4 11,301 x 4 Fan ft3/min 11,301 x 4 11,301 x 4
External Static Pressure (Max, Pa) 80 80 80 80 External Static Pressure (Max, Pa) 80 80
Drive DC INVERTER DC INVERTER DC INVERTER DC INVERTER Drive DC INVERTER DC INVERTER
Discharge Side / Top TOP TOP TOP TOP Discharge Side / Top TOP TOP
Pipe Liquid Pipe mm (inch) 22.2 (7/8) 22.2 (7/8) 22.2 (7/8) 22.2 (7/8) Pipe Liquid Pipe mm (inch) 22.2 (7/8) 22.2 (7/8)
Connections Gas Pipe mm (inch) 53.98 (2-1/8) 53.98 (2-1/8) 53.98 (2-1/8) 53.98 (2-1/8) Connections Gas Pipe mm (inch) 53.98 (2-1/8) 53.98 (2-1/8)
(1,240 x 1,690 x 760) x 3 (1,240 x 1,690 x 760) x 3 Dimensions (W x H x D) mm x No. (1,240 x1,690 x 760) x 4 (1,240 x1,690 x 760) x 4
Dimensions (W x H x D) mm x No. (1,240 x1,690 x 760) x 4 (1,240 x1,690 x 760) x 4
+ (930 x 1,690 x 760) x 1 + (930 x 1,690 x 760) x 1
kg (276 x 3) + (274 x 1) (276 x 3) + (274 x 1)
kg (276 x 2) + (274 x 1) + (188 x 1) (276 x 3) + (188 x 1) (276 x 3) + (188 x 1) (276 x 3) + (220 x 1) Net Weight
Net Weight lbs (639 x 3) + (635 x 1) (639 x 3) + (635 x 1)
lbs (639 x 2) + (635 x 1) + (448 x 1) (639 x 3) + (448 x 1) (639 x 3) + (507 x 1) (639 x 3) + (507 x 1)
Sound Cooling dB(A) 70.4 70.9
Sound Cooling dB(A) 70.0 70.1 70.2 70.3 Pressure Level Heating dB(A) 72.5 72.7
Pressure Level Heating dB(A) 71.6 72.1 72.1 72.2
Sound Cooling dB(A) 93.6 93.6
Sound Cooling dB(A) 92.4 92.9 93.1 93.2 Power Level Heating dB(A) 95.4 95.6
Power Level Heating dB(A) 94.4 94.9 95.1 95.2
mm2 x No.
mm2 x No. Communication Cable 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C
Communication Cable 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C (VCTF-SB)
(VCTF-SB)
Refrigerant name R410A R410A
Refrigerant name R410A R410A R410A R410A
Precharged Amount kg 16.0 + 16.0 + 16.0 + 14.0 16.0 + 16.0 + 16.0 + 14.0
Precharged Amount kg 16.0 + 16.0 + 14.0 + 10.0 16.0 + 16.0 + 16.0 + 10.0 16.0 + 16.0 + 16.0 + 13.0 16.0 + 16.0 + 16.0 + 13.0 in factory
Refrigerant lbs 35.3 + 35.3 + 35.3 + 30.9 35.3 + 35.3 + 35.3 + 30.9
Refrigerant in factory lbs 35.3 + 35.3 + 30.9 + 22.0 35.3 + 35.3 + 35.3 + 22.0 35.3 + 35.3 + 35.3 + 28.7 35.3 + 35.3 + 35.3 + 28.7
t-CO2eq 129.4 129.4
t-CO2eq 116.9 121.1 127.3 127.3
Control Electronic Expansion Valve Electronic Expansion Valve
Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
3, 380-415, 50 3, 380-415, 50
3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 Power Supply Ø, V, Hz
Power Supply Ø, V, Hz 3, 380, 60 3, 380, 60
3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60
Number of maximum connectable indoor units 64 64
Number of maximum connectable indoor units 64 64 64 64
Note Note
1. Due to our policy of innovation some specifications may be changed without notification. 1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical work and design. 2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Power factor could vary less than ±1% according to the operating conditions. 3. Power factor could vary less than ±1% according to the operating conditions.
4. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard. 4. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard. Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard.
Therefore, these values can be increased owing to ambient conditions during operation. Therefore, these values can be increased owing to ambient conditions during operation.
5. Performances are based on the following conditions : 5. Performances are based on the following conditions :
*Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB *Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
*Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB *Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is Zero. Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is Zero.
6. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination. 6. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination.
The recommended ratio is 130%. The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases. (R410A, GWP(Global warming potential) = 2087.5) 7. This product contains Fluorinated greenhouse gases. (R410A, GWP(Global warming potential) = 2087.5)
050 / 051
OUTDOOR UNITS _ MULTI V 5 _ SPECIFICATION
OUTDOOR
UNITS
ARUV030GSD0 / ARUV040GSD0
ARUV050GSD5 / ARUV060GSD5
MULTI V 5
HP 3 4 5 6
052 / 053
INDOOR
INDOOR
UNITS
UNITS
WALL MOUNTED
CEILING SUSPENDED
CONSOLE
054 / 055
INDOOR UNITS _ WALL MOUNTED INDOOR UNITS _ WALL MOUNTED _ KEY FEATURES
SMART
Wi-Fi Control
WALL MOUNTED Anytime, anywhere access to the unit with Android & iOS-based smartphones.
LG ThinQTM
INDOOR
UNITS
Search “LG ThinQTM” on Google market or the App Store to download the app.
LG ThinQTM
Integrated Home Appliances Control Access your air conditioner anytime and from anywhere
Control / Monitor all your LG appliances from one place. With a Wi-Fi equipped device and LG’s exclusive control app, LG ThinQTM.
WALL MOUNTED
Easy Registration and Log-in
Follow the easy set-up steps that will activate LG ThinQTM’s user-friendly features. Wi-Fi Connectivity
Each user can set and save temperature and fan speed preferences in the
LG ThinQTM app. If a household has more than one indoor unit, separate
temperature settings can be set for each.
Multiple Devices
Features & Benefits Key Applications * Wi-Fi modem (Option) is necessary for this function
• 6 Different discharge angles can be programmed via the remote controller. • Retail • Hotel
• Easily detachable full surface cover helps to clean the air conditioner. • Restaurant • Multi-family Residence Simple operation for various functions
• Drain pipe can be easily hidden from sight. • Office ※ Can be controlled by multiple users, but not simultaneously.
Multi-Control
Wall Mounted Standard
Smart Wi-Fi ○
Energy Efficiency Energy Display ○
Fast Cooling & Jet Cool ○ On/Off, Current Temp Mode, Set Temp Vane Control
Heating Auto Swing (Up & Down) ○
○
Ionizer Straight forward Management
~7.1kW Only
Health Pre Filter ○
Auto Cleaning ○
Sleep Mode ○
Timer (On / Off) ○
Comfort Timer (Weekly) ○
Two Thermistor Control ○
Group Control ○
Reservation Energy Smart Filter
※ ○: Applied, - : Not applied Monitoring Diagnosis Management
056 / 057
INDOOR UNITS _ WALL MOUNTED _ KEY FEATURES
INDOOR
※ Wired remote controller need to be separately purchased.
※ Specifications may vary for each model.
UNITS
※ Depending on the experimental conditions.
H
H H
H
The
Thevertical vane,
vertical which
vane, moves
which up andup
moves down,
andhas 6 different
down, has 6settings including
different full-auto swing.
settings The louver, which sways left and right, has 5 different settings including full auto-swing.
H H
O- including full-auto swing.
H+ Sterilization and Deodorization (Utilizes Over 3 Million Ions) Schedule 1 Schedule 2
O- Ionizer PLUS reduces E.coli and Staphylococcus in the surface with over Setting temperature : 19°C Setting temperature : 21°C
By dehumidifying, (Some models are by Operation time : 09:00 ~ 12:00 Operation time : 13:00 ~ 18:00
H+ 3 million ions.
O- dehumidifying and ionizing), the auto cleaning
function prevents potentially harmful substances
WALL MOUNTED
1
from forming on the surface of the heat exchanger.
How It Works Up & Down 2
rmful Substances OH Radical Production Chemical Reaction Complete Sterilization
NqjfsxQnqyjw|nym]jlzqfwLnwņt| 70° 3
harmful particles Ion Cluster OH Surrounding
radicles inactivate OH
harmful 4
Radicalsubstances OH radicles
Chemical Reaction bond with H particles inThe
Sterilization thecomprehensive
air Hauto
2O molecules are produced
cleaning function prevents the formation of bacteria and mold on the heat exchanger, providing a more pleasant and comfortable environment. Heating 5
Generation
Ions are released
Harmful Substances Production
H- and O- bond to How It Works
OH radicles inactivate OH radicles bond H2O molecules are
6
into air
2
harmful particles harmful substances with H particles
H H
produced How It Works ※ Angle can be different from each model and working mode. 9:00 12:00 13:00 18:00
NqjfsxQnqyjw|nym]jlzqfwLnwņt|
H
H H
H
100
2 H
H H with the specimen in the
Hcenter of test chamber)
air conditioner, the auto cleaning function removes advanced LMWLWZQbQVON]VK\QWV
conditioner can be increased over 10 years. by various germs and bacteria, the cooling performance thermistors in the remote controller as well as from the
H H all substances that might be harmful to human body. and longevity ofthe air conditioner remains unchanged
80 Temperature & Humidity : Normal even after 10 years of usage.
4 Way Swing indoor unit. There may be a significant difference between
60 Pain Point Bacteria E.coli
Bacteria : E coil colon bacillus,
Staphylococcus Aureus NjwynŅhfyj
MjsjŅy ceiling and floor air temperature. Two thermistors can
4 Way Swing disperses cool air quickly and effectively in multiple directions to each corner of a room.
99.9% Tested by Intertek Auto cleaning
40
D/CtitwxywjslymijhwjfxjnsHBrnszyjx Air conditioners with
Sanitization
vanes that only move up and
By eliminating
staphylococcus
down are Removes
the humidity and bacteria left in the
Auto Harmful
TheCleaning
indoor Particles
Tsyjwyjp0ajwnŅhfyntsNjwynk~nslLsyngfhyjwnfq
environment
provides remains odorless
clean withpreventing
air by the By preventing the polluting
bacteria, mold of the
andheat exchanger
odors that Left & Right optimize indoor air temperature for a more comfortable
20 unable to suitably cool all areas of aairroom.
conditioner, the auto cleaning function removes
Auto Cleaning LMWLWZQbQVON]VK\QWV
advancedprovides clean air by eliminating bacteria, moldbyand
various
odorsgerms andotherwise
that can bacteria, the cooling performance
accumulate in an indoor unit.
30 min.
99.9%
LstitwtkxywjslymD or less indicates that there is odor but no sense
all substances that might be harmful to human body.
Sanitization
Function of Plasmaster Ionizer+ / Ionizer
can otherwise accumulate in an indoor unit. and longevity ofthe air conditioner remains unchanged
even after 10 years of usage.
110° environment.
Heating /
of displeasure
0 (degree of odor permissible).
MjsjŅy Cooling
d and bacteria growing on 15 30 45 60 Time (min)
※ Angle can be different from each model and working mode.
he heat exchanger is wet. Removes Harmful Particles
2.1
Odor
odor strength decrease
Autoin 60 minutes
Cleaning provides clean air by eliminating bacteria, mold and odors that can otherwise accumulate in an indoor unit. Easy and Simple Control Indoor Unit
1 2 3 4
Strength
An odor of measured as 2 European odor units (ouE/m³) or less Thermistor
Airflow direction can be changed
indicates that the level of odor falls within permissible limits.
by LG ThinQTM Wi-Fi app.
Normal Odor Strength 1 2 3 4
wjzx Offensive
odor MjsjŅy Bacteria Elimination Odor Elimination Mold Elimination
substance
Offensive
sensitivity odor
4 Way Swing
substance
Mountain
smell
Indoor life
smell
Bathroom
smell
Food waste
smell
How It Works
sensitivity Mountain Indoor life Bathroom Food waste 4 Way Swing disperses cool air quickly and effectively in multiple directions to each corner of a room.
smell smell smell smell Up / Down Swing
and down are Odor strength Light Moderate Strong Very Strong NqjfsxQnqyjw|nym]jlzqfwLnwņt| Remote Controller
level Thermistor
Odor strength level Light Moderate Strong Very Strong The comprehensive auto cleaning function prevents the formation of bacteria and mold on the heat exchanger, providing a more pleasant and comfortable environment.
Bacteria
Bacteria Elimination Odor Odor
Elimination MoldMold
Elimination Jet Cool
1.5 3.6 Prevention Elimination Elimination
LG air conditioners provide optimized high-speed airflow,
Odor strength reduce 3.6 1.5 / The Odor floating in the room as well as curtain and clothes. which can cool rooms faster while delivering cool air evenly Group Control
60
me(min)
ZitwxywjslymwjizhjE/HC/G&_mjZitwņtfynslnsymjwttrfx|jqqfxhzwyfnsfsihqtymjx/
※ Test conditions : in every direction. Group control by new remote controller (PREMTB100 /
Space: 8m3 Chamber
Temperature & Humidify : Normal ※ Specifications may vary for each model.
Tested by Intertek ※ Depending on the experimental conditions. PREMTBB10) has more functions than previous model.
Installation One Click “Jet Mode”
Auto Cleaning Installation Support
By eliminating the humidity and bacteria left in the The indoor environment remains odorless with the
Clip
air conditioner, the auto cleaning function removes advanced LMWLWZQbQVON]VK\QWV
By preventing
Reduces thetemperature
the polluting of theof
heat exchanger air to 18°C for 30 minutes with
outflowing
by various germs and bacteria, the cooling performance
The unit has a self-cleaning function that dries the heat all substances that might be harmful to human body. justlongevity
and one click.
ofthe air conditioner remains unchanged
A support clip creates adequate space between the wall and the unit for even after 10 years of usage.
exchanger before sterilizing the interior. easier installation.
MjsjŅy
Cooling / Heating Dehumidification
Removes Harmful Particles Fan only operating Setting temp.
Pain Point 25°
Auto Cleaning provides clean air by eliminating bacteria, mold and odors that can otherwise accumulate in an indoor unit.
The main cause of odor within air conditioners is mold and bacteria
growing on the heat exchanger. These germs can spread when the heat Standard Operation
exchanger is wet.
ng on
wet. More Powerful Performance In Case of Group Control
By reducing the second vortex, which
decreases airflow within the air outlet,
and enlarging the fan size, the amount of
167mm
air flow is increased to 13 CMM.
058 / 059
INDOOR UNITS _ WALL MOUNTED _ SPECIFICATION
STANDARD STANDARD
ARNU05GSJN4 / ARNU07GSJN4 ARNU18GSK*4 / ARNU24GSK*4
ARNU09GSJN4 / ARNU12GSJN4 ARNU30GSVA4 / ARNU36GSVA4
ARNU15GSJN4
INDOOR
UNITS
Model Unit ARNU05GSJN4 ARNU07GSJN4 ARNU09GSJN4 ARNU12GSJN4 ARNU15GSJN4 Model Unit ARNU18GSK*4 ARNU24GSK*4 ARNU30GSVA4 ARNU36GSVA4
WALL MOUNTED
Cooling Capacity kW 1.6 2.2 2.8 3.6 4.5 Cooling Capacity kW 5.6 7.1 8.8 10.4
Heating Capacity kW 1.8 2.5 3.2 4.0 5.0 Heating Capacity kW 6.3 7.5 9.4 10.8
Power Input Power Input
Nominal W 11 / 10 / 9 12 / 11 / 9 13 / 12 / 9 15 / 13 / 11 23 / 18 / 11 Nominal W 32 / 26 / 16 39 / 26 / 16 54 / 43 / 31 85 / 51 / 36
(H / M / L) (H / M / L)
Exterior Color White White White White White Exterior Color White White White White
RAL Code RAL 9016 RAL 9016 RAL 9016 RAL 9016 RAL 9016 RAL Code RAL 9016 RAL 9016 RAL 9016 RAL 9016
Dimensions Body mm 818 x 316 x 189 818 x 316 x 189 818 x 316 x 189 818 x 316 x 189 818 x 316 x 189 Dimensions Body mm 975 x 354 x 209 975 x 354 x 209 1,190 x 346 x 265 1,190 x 346 x 265
(W x H x D) Shipping mm 892 x 381 x 249 892 x 381 x 249 892 x 381 x 249 892 x 381 x 249 892 x 381 x 249 (W x H x D) Shipping mm 1,063 x 420 x 274 1,063 x 420 x 274 1,265 x 432 x 335 1,265 x 432 x 335
Type Cross Flow Fan Cross Flow Fan Cross Flow Fan Cross Flow Fan Cross Flow Fan Type Cross Flow Fan Cross Flow Fan Cross Flow Fan Cross Flow Fan
Motor Output x Number W x No. 30 x 1 30 x 1 30 x 1 30 x 1 30 x 1 Motor Output x Number W x No. 58 x 1 58 x 1 113 x 1 113 x 1
Fan Fan
Air Flow Rate (H / M / L) m³/min 6.8 / 6.5 / 5.9 7.2 / 6.8 / 5.9 7.8 / 7.2 / 5.9 8.5 / 7.8 / 6.8 10.5 / 9.5 / 6.8 Air Flow Rate (H / M / L) m³/min 14.0 / 12.0 / 10.5 15.2 / 12.7 / 10.5 23.0 / 20.0 / 17.0 26.0 / 23.0 / 19.0
Motor Type BLDC BLDC BLDC BLDC BLDC Motor Type BLDC BLDC BLDC BLDC
Air Filter Pre Filter Pre Filter Pre Filter Pre Filter Pre Filter Air Filter Pre Filter Pre Filter Pre Filter Pre Filter
Liquid Side mm (inch) Ø6.35 (1/4) Ø6.35 (1/4) Ø6.35 (1/4) Ø6.35 (1/4) Ø6.35 (1/4) Liquid Side mm (inch) Ø6.35 (1/4) Ø9.52 (3/8) Ø9.52 (3/8) Ø9.52 (3/8)
Pipe Pipe
Gas Side mm (inch) Ø12.7 (1/2) Ø12.7 (1/2) Ø12.7 (1/2) Ø12.7 (1/2) Ø12.7 (1/2) Gas Side mm (inch) Ø12.7 (1/2) Ø15.88 (5/8) Ø15.88 (5/8) Ø15.88 (5/8)
Connections Connections
Drain Pipe (Internal Dia.) mm (inch) Ø16 (5/8) Ø16 (5/8) Ø16 (5/8) Ø16 (5/8) Ø16 (5/8) Drain Pipe (Internal Dia.) mm (inch) Ø16 (5/8) Ø16 (5/8) Ø16 (5/8) Ø16 (5/8)
Weight Body kg 8.4 8.4 8.4 8.4 8.4 Weight Body kg 12.2 12.2 16.6 16.6
Sound Pressure Levels (H / M / L) dB(A) 30 / 29 / 28 32 / 30 / 28 34 / 32 / 28 37 / 34 / 30 42 / 39 / 32 Sound Pressure Levels (H / M / L) dB(A) 43 / 39 / 34 46 / 41 / 34 49 / 44 / 42 52 / 47 / 43
Sound Power Levels (H / M / L) dB(A) 54 / 53 / 52 54 / 53 / 52 55 / 54 / 52 55 / 54 / 53 58 / 56 / 54 Sound Power Levels (H / M / L) dB(A) 63 / 57 / 54 65 / 60 / 54
Power Supply Ø, V, Hz 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 Power Supply Ø, V, Hz 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50
Communication Cable mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C Communication Cable mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C
Note : 1. Performance tested under EN14511 * : N or C can be applied which has little bit different shape of panel.
2. Capacities are based on the following conditions. Note : 1. Performance tested under EN14511
- Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero 2. Capacities are based on the following conditions.
- Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero
3. Due to our policy of innovation, some specifications may be changed without notification. - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero
3. Due to our policy of innovation, some specifications may be changed without notification.
Accessories Accessories
Chassis ARNU05GSJN4 ARNU07GSJN4 ARNU09GSJN4 ARNU12GSJN4 ARNU15GSJN4 Chassis ARNU18GSK*4 ARNU24GSK*4 ARNU30GSVA4 ARNU36GSVA4
Drain Pump - Drain Pump - -
Cassette Cover - Cassette Cover - -
Refrigerant Leakage Detector PRLDNVS0 Refrigerant Leakage Detector PRLDNVS0 PRLDNVS0
EEV Kit PRGK024A0 EEV Kit PRGK024A0 -
Independent Power Module PRIP0 Independent Power Module PRIP0 PRIP0
Robot Cleaner - Robot Cleaner - -
Pre Filter (Washable) ○ Pre Filter (Washable) ○ ○
Ion Generator ○ Ion Generator ○ -
CO2 Sensor - CO2 Sensor - -
Ventilation Kit - Ventilation Kit - -
IR Receiver - IR Receiver - -
Zone Controller - Zone Controller - -
PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible), PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible),
Dry Contact (with additional accessory) Dry Contact (with additional accessory)
PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus) PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus)
External Input (1 point) ○ External Input (1 point) ○ ○
Wi-Fi ○ Wi-Fi ○ PWFMDD200
060 / 061
INDOOR UNITS _ CEILING MOUNTED CASSETTE INDOOR UNITS _ CEILING MOUNTED CASSETTE _ KEY FEATURES
NEW DESIGN
4 Way Air Flow with New Design Wide Design
CEILING MOUNTED New Excellent Technology (NET) certifies new 4 Way dual vane
design that promotes comfortable and convenient airflow.
Bigger inlet and outlet make faster cooling / heating airflow.
CASSETTE
INDOOR
UNITS
4 Way
Dual Vane Increased Inlet Area
Normal 4 Way
Direct
Wind
5m
Features & Benefits Key Applications
Indirect cooling & Heating Suitable for High Ceiling Provide high concentration
High Efficiency Heat Exchanger (HEX)
• New Dual Vane 4 Way cassette allows comfortable air flow. • Retail Ø5 High Density Heat Exchanger increases cooling
• Full 3D Turbo fan decreases air resistance, providing high air flow and Indirect Wind Direct Wind Refresh Mode
• School / heating efficiency by 10%.
low sound levels. • Office
Normal Ø7 HEX
• Hotel
Brighter Color
• Dormitory Color enhancement allows cassette to blend in to most
• Restaurant interior ceiling spaces. 20mm
062 / 063
INDOOR UNITS _ CEILING MOUNTED CASSETTE _ KEY FEATURES
INDOOR
Real-time indoor air quality status Fine dust concentration & air quality
UNITS
displayed on indoor unit status displayed on remote control
132mm
Installation Standard
① Horizontal Sensor ② Check Close grille ① Detect Obstacle ③ Set Stop Point
② Horizontal Sensor ④ Check Close grille
Human Detection for Optimized Air
purification Deodorization filter Phase 4 I Deodorizes
Efficiency kit
LG ThinQTM Connectivity
Indoor unit senses human presence to switch on or off for Anytime anywhere access to indoor units with LG ThinQTM
300 or more
Phase 3 I Captures microfine dust
maximum power savings of 54%. PM1.0 Filter mobile app. Ceiling
Ceiling Board
Dust electrification Ceiling Board
Operation On Turning Off Turning On
300 or less
On Off On
Phase 2 I Dust Electrification 500 or
or more
500 or
1,000
more more
4,000 or less
Above 2,500
Pre-filter
PM1.0
Sensor
Phase 1 I Captures fine dust
Unit : mm
Air
In office Absence In office purification
Floor
panel
Learning time for
↑2°C, running
Power saving Max. 54%
25min Power saving
Manageable set time Power saving
(If set time 30min) ① Monitoring Air status ② Mobile Remote Control
30min/60min/90min Smart Easy to check indoor air status Remote control by using mobile phone
indicator • Ultra Fine / Extra Fine / Fine Dust • Control Mode / Temperature
Absence → Turn off after 30min (Set turn off)
• Day / Week /Month / Yearly / Air flow etc.
Learning time for Absence Cycle Management
5min Dust ③ Display Power Consumption
Pre-filter Ultra Fine Dust Kit Deodorizing Filter Check power consumption of A/C
※ Smart Dual Vane Indoor Unit ‘20 Line up. Electrification
※ Data Based on actual test of LG, single product 2 hours measurement result. • Check energy display
Easy removable 6 months /
(Cooling 26 °C, strong wind) Washable Dry in sunlight • Set target energy consumption level
pre-filter Washable
064 / 065
INDOOR UNITS _ CEILING MOUNTED CASSETTE _ SPECIFICATION
DUAL VANE 4 Way CASSETTE (840 X 840) DUAL VANE 4 Way CASSETTE (840 X 840)
ARNU24GTBB4 / ARNU28GTBB4 ARNU36GTAB4 / ARNU42GTAB4
ARNU30GTBB4 ARNU48GTAB4
INDOOR
UNITS
Model Unit ARNU24GTBB4 ARNU28GTBB4 ARNU30GTBB4 Model Unit ARNU36GTAB4 ARNU42GTAB4 ARNU48GTAB4
Note : 1. Performance tested under EN14511 Note : 1. Performance tested under EN14511
2. Capacities are based on the following conditions. 2. Capacities are based on the following conditions.
- Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero
- Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero
3. Due to our policy of innovation, some specifications may be changed without notification. 3. Due to our policy of innovation, some specifications may be changed without notification.
Accessories Accessories
Chassis ARNU24GTBB4 ARNU28GTBB4 ARNU30GTBB4 Chassis ARNU36GTAB4 ARNU42GTAB4 ARNU48GTAB4
Drain Pump ○ Drain Pump ○
Cassette Cover PTDCA Cassette Cover PTDCA
Refrigerant Leakage Detector PRLDNVS0 Refrigerant Leakage Detector PRLDNVS0
EEV Kit - EEV Kit -
Independent Power Module PRIP0 Independent Power Module PRIP0
Robot Cleaner - Robot Cleaner -
Pre Filter (Washable) ○ Pre Filter (Washable) ○
Ion Generator - Ion Generator -
CO2 Sensor - CO2 Sensor -
Ventilation Kit - Ventilation Kit -
IR Receiver - IR Receiver -
Zone Controller - Zone Controller -
PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible), PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible),
Dry Contact (with additional accessory) Dry Contact (with additional accessory)
PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus) PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus)
External Input (1 Point) ○ External Input (1 Point) ○
Wi-Fi PWFMDD200 Wi-Fi PWFMDD200
Human detection sensor PTVSAA0 Human detection sensor PTVSAA0
Floor Temperature Sensor PT-AFGW0 :○ Floor Temperature Sensor PT-AFGW0 : ○
Air cleaning kit PT-AFGW0 : PTAHMP0 Air cleaning kit PT-AFGW0 : PTAHMP0
Elevation Grille PT-AEGW0 :○ Elevation Grille PT-AEGW0 : ○
066 / 067
INDOOR UNITS _ CEILING MOUNTED CASSETTE _ SPECIFICATION
DUAL VANE 4 Way CASSETTE (840 X 840) HIGH SENSIBLE DUAL VANE 4 Way CASSETTE (840 X 840) HIGH SENSIBLE
ARNU07GTAA4 / ARNU09GTAA4 ARNU24GTAA4 / ARNU28GTAA4
ARNU12GTAA4 / ARNU15GTAA4 ARNU36GTAA4 / ARNU42GTAA4
ARNU18GTAA4 ARNU48GTAA4
INDOOR
UNITS
Model Unit ARNU07GTAA4 ARNU09GTAA4 ARNU12GTAA4 ARNU15GTAA4 ARNU18GTAA4 Model Unit ARNU24GTAA4 ARNU28GTAA4 ARNU36GTAA4 ARNU42GTAA4 ARNU48GTAA4
Accessories Accessories
Chassis ARNU07GTAA4 ARNU09GTAA4 ARNU12GTAA4 ARNU15GTAA4 ARNU18GTAA4 Chassis ARNU24GTAA4 ARNU28GTAA4 ARNU36GTAA4 ARNU42GTAA4 ARNU48GTAA4
Drain Pump ○ Drain Pump ○
Cassette Cover PTDCA Cassette Cover PTDCA
Refrigerant Leakage Detector PRLDNVS0 Refrigerant Leakage Detector PRLDNVS0
EEV Kit - EEV Kit -
Independent Power Module PRIP0 Independent Power Module PRIP0
Robot Cleaner - Robot Cleaner -
Pre Filter (Washable) ○ Pre Filter (Washable) ○
Ion Generator - Ion Generator -
CO2 Sensor - CO2 Sensor -
Ventilation Kit - Ventilation Kit -
IR Receiver - IR Receiver -
Zone Controller - Zone Controller -
PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible), PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible),
Dry Contact (with additional accessory) Dry Contact (with additional accessory)
PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus) PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus)
External Input (1 Point) ○ External Input (1 Point) ○
Wi-Fi PWFMDD200 Wi-Fi PWFMDD200
Human detection sensor PTVSAA0 Human detection sensor PTVSAA0
Floor Temperature Sensor PT-AFGW0 : ○ Floor Temperature Sensor PT-AFGW0 : ○
Air cleaning kit PT-AFGW0 : PTAHMP0 Air cleaning kit PT-AFGW0 : PTAHMP0
Elevation Grille PT-AEGW0 : ○ Elevation Grille PT-AEGW0 : ○
068 / 069
INDOOR UNITS _ CEILING MOUNTED CASSETTE _ SPECIFICATION
INDOOR
UNITS
Model Unit ARNU05GTRB4 ARNU07GTRB4 ARNU09GTRB4 ARNU12GTRB4 Model Unit ARNU15GTQB4 ARNU18GTQB4 ARNU21GTQB4
Note : 1. Performance tested under EN14511 Note : 1. Performance tested under EN14511
2. Capacities are based on the following conditions. 2. Capacities are based on the following conditions.
- Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero
- Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero
3. Due to our policy of innovation, some specifications may be changed without notification. 3. Due to our policy of innovation, some specifications may be changed without notification.
Accessories Accessories
Chassis ARNU05GTRB4 ARNU07GTRB4 ARNU09GTRB4 ARNU12GTRB4 Chassis ARNU15GTQB4 ARNU18GTQB4 ARNU21GTQB4
Drain Pump ○ Drain Pump ○
Cassette Cover PTDCQ Cassette Cover PTDCQ
Refrigerant Leakage Detector PRLDNVS0 Refrigerant Leakage Detector PRLDNVS0
EEV Kit PRGK024A0 (~4.5kW) EEV Kit PRGK024A0 (~4.5kW)
Independent Power Module PRIP0 Independent Power Module PRIP0
Robot Cleaner - Robot Cleaner -
Pre Filter (Washable) ○ Pre Filter (Washable) ○
Ion Generator - Ion Generator -
CO2 Sensor - CO2 Sensor -
Ventilation Kit PTVK430 Ventilation Kit PTVK430
IR Receiver - IR Receiver -
Zone Controller - Zone Controller -
PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible), PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible),
Dry Contact (with additional accessory) Dry Contact (with additional accessory)
PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus) PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus)
External Input (1 point) ○ External Input (1 point) ○
Wi-Fi PWFMDD200 Wi-Fi PWFMDD200
※ ○ : Applied, - : Not applied ※ ○ : Applied, - : Not applied
Option : Refer to model name in table Option : Refer to model name in table
070 / 071
INDOOR UNITS _ CEILING MOUNTED CASSETTE _ SPECIFICATION
INDOOR
UNITS
Model Unit ARNU24GTPA4 ARNU28GTPA4 ARNU30GTPA4 ARNU36GTNA4 Model Unit ARNU42GTMA4 ARNU48GTMA4 ARNU54GTMA4
Accessories Accessories
Chassis ARNU24GTPA4 ARNU28GTPA4 ARNU30GTPA4 ARNU36GTNA4 Chassis ARNU42GTMA4 ARNU48GTMA4 ARNU54GTMA4
Drain Pump ○ Drain Pump ○
Cassette Cover PTDCM Cassette Cover PTDCM
Refrigerant Leakage Detector PRLDNVS0 Refrigerant Leakage Detector PRLDNVS0
EEV Kit - EEV Kit -
Independent Power Module PRIP0 Independent Power Module PRIP0
Robot Cleaner - Robot Cleaner -
Pre Filter (Washable) ○ Pre Filter (Washable) ○
Ion Generator - Ion Generator -
CO2 Sensor - CO2 Sensor -
Ventilation Kit PTVK430 Ventilation Kit PTVK430
IR Receiver - IR Receiver -
Zone Controller - Zone Controller -
PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible), PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible),
Dry Contact (with additional accessory) Dry Contact (with additional accessory)
PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus) PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus)
External Input (1 point) ○ External Input (1 point) ○
Wi-Fi PWFMDD200 Wi-Fi PWFMDD200
072 / 073
INDOOR UNITS _ CEILING MOUNTED CASSETTE _ SPECIFICATION
INDOOR
UNITS
Model Unit ARNU09GTSA4 ARNU12GTSA4 Model Unit ARNU18GTSA4 ARNU24GTSA4
Note : 1. Performance tested under EN14511 Note : 1. Performance tested under EN14511
2. Capacities are based on the following conditions. 2. Capacities are based on the following conditions.
- Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero
- Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero
3. Due to our policy of innovation, some specifications may be changed without notification. 3. Due to our policy of innovation, some specifications may be changed without notification.
Accessories Accessories
Chassis ARNU09GTSA4 ARNU12GTSA4 Chassis ARNU18GTSA4 ARNU24GTSA4
Drain Pump ○ Drain Pump ○
Cassette Cover - Cassette Cover -
Refrigerant Leakage Detector PRLDNVS0 Refrigerant Leakage Detector PRLDNVS0
EEV Kit PRGK024A0 (~5.6kW) EEV Kit PRGK024A0 (~5.6kW)
Independent Power Module PRIP0 Independent Power Module PRIP0
Robot Cleaner - Robot Cleaner -
Pre Filter (Washable) ○ Pre Filter (Washable) ○
Ion Generator - Ion Generator -
CO2 Sensor - CO2 Sensor -
Ventilation Kit - Ventilation Kit -
IR Receiver - IR Receiver -
Zone Controller - Zone Controller -
PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible), PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible),
Dry Contact (with additional accessory) Dry Contact (with additional accessory)
PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus) PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus)
External Input (1 point) ○ External Input (1 point) ○
Wi-Fi PWFMDD200 Wi-Fi PWFMDD200
074 / 075
INDOOR UNITS _ CEILING MOUNTED CASSETTE _ SPECIFICATION
INDOOR
UNITS
Model Unit ARNU07GTUB4 ARNU09GTUB4 ARNU12GTUB4 Model Unit ARNU18GTTB4 ARNU24GTTB4
Note : 1. Performance tested under EN14511 Note : 1. Performance tested under EN14511
2. Capacities are based on the following conditions. 2. Capacities are based on the following conditions.
- Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero
- Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero
3. Due to our policy of innovation, some specifications may be changed without notification. 3. Due to our policy of innovation, some specifications may be changed without notification.
Accessories Accessories
Chassis ARNU07GTUB4 ARNU09GTUB4 ARNU12GTUB4 Chassis ARNU18GTTB4 ARNU24GTTB4
Drain Pump ○ Drain Pump ○
Cassette Cover - Cassette Cover -
Refrigerant Leakage Detector PRLDNVS0 Refrigerant Leakage Detector PRLDNVS0
EEV Kit PRGK024A0 EEV Kit -
Independent Power Module PRIP0 Independent Power Module PRIP0
Robot Cleaner - Robot Cleaner -
Pre Filter (Washable) ○ Pre Filter (Washable) ○
Ion Generator - Ion Generator -
CO2 Sensor - CO2 Sensor -
Ventilation Kit - Ventilation Kit -
IR Receiver - IR Receiver -
Zone Controller - Zone Controller -
PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible), PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible),
Dry Contact (with additional accessory) Dry Contact (with additional accessory)
PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus) PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus)
External Input (1 point) ○ External Input (1 point) ○
Wi-Fi PWFMDD200 Wi-Fi PWFMDD200
076 / 077
INDOOR UNITS _ CEILING MOUNTED ROUND CASSETTE INDOOR UNITS _ CEILING MOUNTED ROUND CASSETTE _ KEY FEATURES
NEW DESIGN
Slim and Compact design Visible air flow
CEILING MOUNTED Reduce the height of the body by 15% save space and
maximize the openness of the interior space.
With crystal vein for 6-step precision control, you can send
cool / heated air wherever you want.
ROUND CASSETTE Other Brand LG Round Cassette Other Brand LG Round Cassette
INDOOR
UNITS
384mm
330mm
Other Brand LG Round Cassette Full 3D Fan, Air flow rate 5% ↑ Full 3D Fan, Low noise
Talking
❶ Drain Pipe Library 50 dB(A) Office
40 dB(A) 55 dB(A)
LG Vacuum
Round CST Cleaner
39 dB(A) 70 dB(A)
Previous New
(4 Way) (Round) ※ 48 kBtu, Low flow rate
❸ Exposed Hanger ❷ Hanger Cover Normal communication Library Noise level 40 dB(A)
Noise level 50 dB(A)
Cassette Round
Smart Wi-Fi ○
Energy Efficiency Human Detect Sensor - Other Brand LG Round Cassette
Drain Pump ○
Sleep Mode ○
Timer (On / Off) ○
Comfort
Timer (Weekly) ○
Two Thermistor Control ○
Group Control ○ Set temperature reach time 18 minutes Set temperature reach time 12 minutes
(Height 1.1m) (Height 1.1m)
※ Based on test results from LG chamber, this image is designed to help customers
understand. Experimental environment: height 3.2m, 48 kBtu, cooling mode,
3 Way airflow with blind spot. Perfect circular airflow without blind spots. high flow rate, horizontal air flow direction
078 / 079
INDOOR UNITS _ CEILING MOUNTED ROUND CASSETTE _ SPECIFICATION
INDOOR
UNITS
Model Unit ARNU24GTYA4 ARNU36GTYA4 ARNU48GTYA4
Accessories
Chassis ARNU24GTYA4 ARNU36GTYA4 ARNU48GTYA4
Drain Pump ○
Cassette Cover -
Refrigerant Leakage Detector PRLDNVS0
EEV Kit -
Independent Power Module PRIP0
Robot Cleaner -
Pre Filter (Washable) ○
Ion Generator -
CO2 Sensor -
Ventilation Kit -
IR Receiver -
Zone Controller -
PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible),
Dry Contact (with additional accessory)
PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus)
External Input (1 Point) ○
Wi-Fi PWFMDD200
Human detection sensor -
Floor Temperature Sensor -
Air cleaning kit -
Elevation Grille -
080 / 081
INDOOR UNITS _ CEILING CONCEALED DUCT INDOOR UNITS _ CEILING CONCEALED DUCT _ KEY FEATURES
INDOOR
download the app.
UNITS
LG ThinQTM
E.S.P. E.S.P.
Control Control
1 step
Static Pressure
Low Setting
* Wi-Fi modem (Option) is necessary for this function
Follow the easy set-up steps that will activate LG ThinQ ’s user-friendly features.
TM Static Pressure
Power Setting
Energy Monitoring
Accumulated electric energy of the indoor unit can be
identified with wired remote control, as well as with
the central controller. This function is an advantage for
energy management.
082 / 083
INDOOR UNITS _ CEILING CONCEALED DUCT _ KEY FEATURES
COMFORT
Multiple Room Operation Minimized Height
Using a spiral duct (Embedded or flexible type) and New mid-static ducts provide ideal solution for installation
stream chamber, it is possible to operate cooling / heating in limited space.
for several rooms simultaneously.
270mm
INDOOR
UNITS
8 / 10kW 12.5kW
380
mm
298
mm
Premium Wired
Remote Controller
Remote Controller Thermistor
Remain time until indoor filter cleaning 1,729hr.
Not Necessary
for Dry Contact
Cost Savings
Key Tag
※ In case of needing more functions beside on / off control, a dry contact is required
to be installed.
084 / 085
INDOOR UNITS _ CEILING CONCEALED DUCT _ SPECIFICATION
INDOOR
UNITS
Model Unit ARNU07GM1A4 ARNU09GM1A4 ARNU12GM1A4 ARNU15GM1A4 ARNU18GM1A4 ARNU24GM1A4 Model Unit ARNU28GM2A4 ARNU36GM2A4 ARNU42GM2A4 ARNU48GM3A4 ARNU54GM3A4
Accessories Accessories
Chassis ARNU07GM1A4 ARNU09GM1A4 ARNU12GM1A4 ARNU15GM1A4 ARNU18GM1A4 ARNU24GM1A4 Chassis ARNU28GM2A4 ARNU36GM2A4 ARNU42GM2A4 ARNU48GM3A4 ARNU54GM3A4
Drain Pump ○ Drain Pump ○
Cassette Cover - Cassette Cover -
Refrigerant Leakage Detector PRLDNVS0 Refrigerant Leakage Detector PRLDNVS0
EEV Kit PRGK024A0 (~5.6kW) EEV Kit -
Independent Power Module PRIP0 Independent Power Module PRIP0
Robot Cleaner - Robot Cleaner -
Pre Filter (Washable) ○ Pre Filter (Washable) ○
Ion Generator - Ion Generator -
CO2 Sensor - CO2 Sensor -
Ventilation Kit - Ventilation Kit -
IR Receiver PWLRVN000 IR Receiver PWLRVN000
Zone Controller ABZCA Zone Controller ABZCA
PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible), PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible),
Dry Contact (with additional accessory) Dry Contact (with additional accessory)
PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus) PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus)
External Input (1 point) ○ External Input (1 point) ○
Wi-Fi PWFMDD200 Wi-Fi PWFMDD200
086 / 087
INDOOR UNITS _ CEILING CONCEALED DUCT _ SPECIFICATION
INDOOR
UNITS
Model Unit ARNU76GB8A4 ARNU96GB8A4 Model Unit ARNU05GL1G4 ARNU07GL1G4 ARNU09GL1G4
Note : 1. Performance tested under EN14511 Note : 1. Performance tested under EN14511
2. Capacities are based on the following conditions. 2. Capacities are based on the following conditions.
- Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero
- Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero
3. Due to our policy of innovation, some specifications may be changed without notification. 3. Due to our policy of innovation, some specifications may be changed without notification.
Accessories Accessories
Chassis ARNU76GB8A4 ARNU96GB8A4 Chassis ARNU05GL1G4 ARNU07GL1G4 ARNU09GL1G4
Drain Pump ○ Drain Pump ○
Cassette Cover - Cassette Cover -
Refrigerant Leakage Detector PRLDNVS0 Refrigerant Leakage Detector PRLDNVS0
EEV Kit ○ EEV Kit PRGK024A0
Independent Power Module PRIP0 Independent Power Module PRIP0
Robot Cleaner - Robot Cleaner -
Pre Filter (Washable) ○ Pre Filter (Washable) ○
Ion Generator - Ion Generator -
CO2 Sensor - CO2 Sensor -
Ventilation Kit - Ventilation Kit -
IR Receiver PWLRVN000 IR Receiver PWLRVN000
Zone Controller ABZCA Zone Controller ABZCA
PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible), PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible),
Dry Contact (with additional accessory) Dry Contact (with additional accessory)
PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus) PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus)
External Input (1 point) ○ External Input (1 point) ○
Wi-Fi PWFMDD200 Wi-Fi PWFMDD200
088 / 089
INDOOR UNITS _ CEILING CONCEALED DUCT _ SPECIFICATION
INDOOR
UNITS
Model Unit ARNU12GL2G4 ARNU15GL2G4 ARNU18GL2G4 Model Unit ARNU21GL3G4 ARNU24GL3G4
Note : 1. Performance tested under EN14511 Note : 1. Performance tested under EN14511
2. Capacities are based on the following conditions. 2. Capacities are based on the following conditions.
- Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero
- Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero
3. Due to our policy of innovation, some specifications may be changed without notification. 3. Due to our policy of innovation, some specifications may be changed without notification.
Accessories Accessories
Chassis ARNU12GL2G4 ARNU15GL2G4 ARNU18GL2G4 Chassis ARNU21GL3G4 ARNU24GL3G4
Drain Pump ○ Drain Pump ○
Cassette Cover - Cassette Cover -
Refrigerant Leakage Detector PRLDNVS0 Refrigerant Leakage Detector PRLDNVS0
EEV Kit - EEV Kit PRGK024A0
Independent Power Module PRIP0 Independent Power Module PRIP0
Robot Cleaner - Robot Cleaner -
Pre Filter (Washable) ○ Pre Filter (Washable) ○
Ion Generator - Ion Generator -
CO2 Sensor - CO2 Sensor -
Ventilation Kit - Ventilation Kit -
IR Receiver PWLRVN000 IR Receiver PWLRVN000
Zone Controller ABZCA Zone Controller ABZCA
PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible), PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible),
Dry Contact (with additional accessory) Dry Contact (with additional accessory)
PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus) PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus)
External Input (1 point) ○ External Input (1 point) ○
Wi-Fi PWFMDD200 Wi-Fi PWFMDD200
※ ○ : Applied, - : Not applied ※ ○ : Applied, - : Not applied
Option : Refer to model name in table Option : Refer to model name in table
090 / 091
INDOOR UNITS _ FRESH AIR INTAKE INDOOR UNITS _ FRESH AIR INTAKE _ SPECIFICATION
The LG Fresh Air Intake Unit (FAU) is the alternative solution for ventilation, which supplies the fresh outdoor
air indoors as well as being able to cool and heat air inside simultaneously. It means the indoor space can have
positive air pressure consistently, which can block cold, hot or contaminated air from outside.
INDOOR
UNITS
This allows the indoor space to have consistent positive air pressure blocking cold.
100%
Outdoor Air Indoor Unit Diffuser Indoor Unit Diffuser Indoor Unit Diffuser Model Unit ARNU76GB8Z4 ARNU96GB8Z4
CAUTION
MULTI V 5 Outdoor Unit MULTI V 5 Outdoor Unit 1. Operation range (Cooling : 5°C ~ 43°C, Heating : -5°C ~ 43°C) 2. Installation of exhaust fan is recommended for a sealed room. 3. Indoor Unit Connection
No Connection Condition Combination
Fresh air intake units only 1) The total capacity of fresh air intake unit should be 50 ~ 100% of outdoor unit.
1
are connected with outdoor units 2) The max. quantity of fresh air intake is 4 units.
Installation Scene 2
Mixture connection with
general indoor unit and fresh intake units
1) The total capacity of indoor units (Standard Indoor Unit + Fresh Air Intake Unit) should be 50 ~ 100% of outdoor unit.
2) The total capacity of fresh air intake unit should be less than 30% of the total capacity of indoor units.
Min. 2m
Accessories
1/30 Slope Chassis ARNU76GB8Z4 ARNU96GB8Z4
Outlet Air Drain Pump ○
Cassette Cover -
Refrigerant Leakage Detector PRLDNVS0
EEV Kit -
Independent Power Module PRIP0
Robot Cleaner -
Exhaust Air
Pre Filter (Washable) ○
Ion Generator -
Inlet Hood Intake Air Duct Fresh Air Intake Unit CO2 Sensor -
Exhaust Fan Door Ventilation Kit -
IR Receiver PWLRVN000
Zone Controller -
PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible),
Dry Contact (with additional accessory)
PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus)
External Input (1 point) ○
Wi-Fi PWFMDD200
※ ○ : Applied, - : Not applied
Option : Refer to model name in table
092 / 093
INDOOR UNITS _ CEILING SUSPENDED INDOOR UNITS _ CEILING SUSPENDED _ KEY FEATURES
INDOOR
UNITS
LG ThinQTM
Wi-Fi
CEILING SUSPENDED
Easy Registration and Log-in
Follow the easy set-up steps that will Powerful Cooling & Heating
activate LG ThinQTM’s impressive feature. High ceiling mode provides powerful cooling and heating up to
4.2m in height from floor, 15m away from ceiling.
COMFORT(CONSOLE)
One Touch & 2 Piece Filter
Flexible Easy in / out filter structure as well as a simplified two-piece
The ceiling and floor models can be installed either on the filter, which slides out for easy cleaning and maintenance.
ceiling or on the floor.
• Modern design with V-shape and black vane • Retail Vertical air flow direction can be adjusted using remote controller,
• Powerful air speed and volume can reach up to 15m • Shop and horizontal Air flow direction can be adjusted manually.
• Restaurant Two Thermistors Control
Users can purchase a wired remote controller that includes
a second thermistor, allowing for temperature checks from
Horizontal Vertical
100 °
93 ° multiple locations.
Ceilings Ceiling & Floor Convertible Ceiling Suspended
Smart Wi-Fi ○ ○ 80 °
Close 63 ° Close
Fast Cooling & Heating Jet Cool ○ ○
Cooling Heating
Sleep mode ○ ○ Two
Thermistors
Comfort
Timer (On / Off)
Timer (Weekly)
○
○
○
○
Filter Change Alarm Indoor Unit
Remote
Controller Thermistor
The filter change alarm informs you when the unit has been
Two thermistor control
Group control
○
○
○
○
operating for 2,400 hours. 15M
15M
Thermistor
1,800e+001
1,600e+001
1,400e+001
1,200e+001
1,000e+001
8,000e+000
094 / 095
6,000e+000
4,000e+000
2,000e+000
Velocity in Stn Frame 0,000e+000 ANSYS
Contour 1 [m s^-1] R15. 0
2,000e+00 1
1,800e+00 1
1,600e+00 1
INDOOR UNITS _ CEILING SUSPENDED _ SPECIFICATION
INDOOR
UNITS
Model Unit ARNU18GV1A4 ARNU24GV1A4 Model Unit ARNU36GV2A4 ARNU48GV2A4
CEILING SUSPENDED
Cooling Capacity kW 5.6 7.1 Cooling Capacity kW 10.6 14.1
Heating Capacity kW 6.3 8.0 Heating Capacity kW 11.9 15.9
Power Input Power Input
Nominal W 23 / 20 / 17 25 / 21 / 17 Nominal W 84 / 77 / 66 91 / 79 / 66
(H / M / L) (H / M / L)
Exterior Color Morning Fog Morning Fog Exterior Color Morning Fog Morning Fog
RAL Code RAL 9001 RAL 9001 RAL Code RAL 9001 RAL 9001
Dimensions Body mm 1,200 x 235 x 690 1,200 x 235 x 690 Dimensions Body mm 1,600 x 235 x 690 1,600 x 235 x 690
(W x H x D) Shipping mm 1,315 x 320 x 772 1,315 x 320 x 772 (W x H x D) Shipping mm 1,715 x 320 x 772 1,715 x 320 x 772
Type Cross Flow Fan Cross Flow Fan Type Cross Flow Fan Cross Flow Fan
Motor Output x Number W x No. 85.9 x 1 85.9 x 1 Motor Output x Number W x No. 125 x 1 125 x 1
Fan Fan
Air Flow Rate (H / M / L) m³/min 13.5 / 12.5 / 12.0 14.0 / 13.0 / 12.0 Air Flow Rate (H / M / L) m³/min 27.0 / 24.0 / 20.0 29.0 / 24.0 / 20.0
Motor Type BLDC BLDC Motor Type BLDC BLDC
Air Filter Pre Filter Pre Filter Air Filter Pre Filter Pre Filter
Liquid Side mm (inch) Ø6.35 (1/4) Ø9.52 (3/8) Liquid Side mm (inch) Ø9.52 (3/8) Ø9.52 (3/8)
Pipe Pipe
Gas Side mm (inch) Ø12.7 (1/2) Ø15.88 (5/8) Gas Side mm (inch) Ø15.88 (5/8) Ø15.88 (5/8)
Connections Connections
Drain Pipe (Internal Dia.) mm (inch) Ø16 (5/8) Ø16 (5/8) Drain Pipe (Internal Dia.) mm (inch) Ø16 (5/8) Ø16 (5/8)
Weight Body kg 29.0 29.0 Weight Body kg 37.0 37.0
Sound Pressure Levels (H / M / L) dB(A) 36 / 34 / 33 37 / 35 / 33 Sound Pressure Levels (H / M / L) dB(A) 48 / 46 / 44 49 / 47 / 44
Sound Power Levels (H / M / L) dB(A) 61 / 59 / 56 62 / 59 / 56 Sound Power Levels (H / M / L) dB(A) 68 / 66 / 64 68 / 67 / 66
Power Supply Ø, V, Hz 1, 220-240, 50 1, 220-240, 50 Power Supply Ø, V, Hz 1, 220-240, 50 1, 220-240, 50
Communication Cable mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C Communication Cable mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C
Note : 1. Performance tested under EN14511 Note : 1. Performance tested under EN14511
2. Capacities are based on the following conditions. 2. Capacities are based on the following conditions.
- Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero
- Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero
3. Due to our policy of innovation, some specifications may be changed without notification. 3. Due to our policy of innovation, some specifications may be changed without notification.
Accessories Accessories
Chassis ARNU18GV1A4 ARNU24GV1A4 Chassis ARNU36GV2A4 ARNU48GV2A4
Drain Pump - Drain Pump -
Cassette Cover - Cassette Cover -
Refrigerant Leakage Detector PRLDNVS0 Refrigerant Leakage Detector PRLDNVS0
EEV Kit - EEV Kit -
Independent Power Module PRIP0 Independent Power Module PRIP0
Robot Cleaner - Robot Cleaner -
Pre Filter (Washable) ○ Pre Filter (Washable) ○
Ion Generator - Ion Generator -
CO2 Sensor - CO2 Sensor -
Ventilation Kit - Ventilation Kit -
IR Receiver - IR Receiver -
Zone Controller - Zone Controller -
PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible), PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible),
Dry Contact (with additional accessory) Dry Contact (with additional accessory)
PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus) PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus)
External Input (1 point) ○ External Input (1 point) ○
Wi-Fi PWFMDD200 Wi-Fi PWFMDD200
096 / 097
INDOOR UNITS _ CONSOLE INDOOR UNITS _ CONSOLE _ KEY FEATURES
SMART COMFORT
Wi-Fi Control Cold Draft Protection
CONSOLE Access your air conditioner anytime and from anywhere. The console protects cold draft from windows to provide
comfortable environment.
LG ThinQTM
Without Console
Search “LG ThinQTM” on Google market or Appstore then
download the app.
INDOOR
LG ThinQTM
UNITS
Wi-Fi
LG ThinQTM
CONSOLE
Without Console
COMFORT
Air Flow Direction Change
During the cooling operation, the vane adjusts upwards to direct the 5-Step Vane Control
air flow towards the ceiling. When heating, the vane directs the warm There are 5 different stages to control air flow direction.
air downwards to balance the room temperature especially for floor.
Step3 Step4
Step2
Cooling
Step5
Step1
098 / 099
INDOOR UNITS _ CONSOLE _ SPECIFICATION
CONSOLE CONSOLE
ARNU07GQAA4 / ARNU09GQAA4 ARNU12GQAA4 / ARNU15GQAA4
INDOOR
UNITS
Model Unit ARNU07GQAA4 ARNU09GQAA4 Model Unit ARNU12GQAA4 ARNU15GQAA4
CONSOLE
Cooling Capacity kW 2.2 2.8 Cooling Capacity kW 3.6 4.5
Heating Capacity kW 2.5 3.2 Heating Capacity kW 4.0 5.0
Power Input Power Input
Nominal W 15 / 12 / 10 15 / 12 / 10 Nominal W 18 / 15 / 13 24 / 19 / 17
(H / M / L) (H / M / L)
Exterior Color Morning Fog Morning Fog Exterior Color Morning Fog Morning Fog
RAL Code RAL 9001 RAL 9001 RAL Code RAL 9001 RAL 9001
Dimensions Body mm 700 x 600 x 210 700 x 600 x 210 Dimensions Body mm 700 x 600 x 210 700 x 600 x 210
(W x H x D) Shipping mm 775 x 662 x 284 775 x 662 x 284 (W x H x D) Shipping mm 775 x 662 x 284 775 x 662 x 284
Type Turbo fan Turbo fan Type Turbo fan Turbo fan
Motor Output x Number W x No. 48 x 1 48 x 1 Motor Output x Number W x No. 48 x 1 48 x 1
Fan Fan
Air Flow Rate (H / M / L) m³/min 6.7 / 5.9 / 4.8 6.7 / 5.9 / 4.8 Air Flow Rate (H / M / L) m³/min 7.5 / 5.9 / 4.8 8.7 / 6.7 / 5.9
Motor Type BLDC BLDC Motor Type BLDC BLDC
Air Filter Pre Filter Pre Filter Air Filter Pre Filter Pre Filter
Liquid Side mm (inch) Ø6.35 (1/4) Ø6.35 (1/4) Liquid Side mm (inch) Ø6.35 (1/4) Ø6.35 (1/4)
Pipe Pipe
Gas Side mm (inch) Ø12.7 (1/2) Ø12.7 (1/2) Gas Side mm (inch) Ø12.7 (1/2) Ø12.7 (1/2)
Connections Connections
Drain Pipe (Internal Dia.) mm (inch) Ø12 (15/32) Ø12 (15/32) Drain Pipe (Internal Dia.) mm (inch) Ø12 (15/32) Ø12 (15/32)
Weight Body kg 14.0 14.0 Weight Body kg 14.0 14.0
Sound Pressure Levels (H / M / L) dB(A) 37 / 34 / 28 37 / 34 / 28 Sound Pressure Levels (H / M / L) dB(A) 39 / 34 / 28 42 / 37 / 31
Sound Power Levels (H / M / L) dB(A) 53 / 50 / 44 53 / 50 / 44 Sound Power Levels (H / M / L) dB(A) 56 / 50 / 44 58 / 53 / 50
Power Supply Ø, V, Hz 1, 220-240, 50 1, 220-240, 50 Power Supply Ø, V, Hz 1, 220-240, 50 1, 220-240, 50
Communication Cable mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C Communication Cable mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C
Note : 1. Performance tested under EN14511 Note : 1. Performance tested under EN14511
2. Capacities are based on the following conditions. 2. Capacities are based on the following conditions.
- Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero
- Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero
3. Due to our policy of innovation, some specifications may be changed without notification. 3. Due to our policy of innovation, some specifications may be changed without notification.
Accessories Accessories
Chassis ARNU07GQAA4 ARNU09GQAA4 Chassis ARNU12GQAA4 ARNU15GQAA4
Drain Pump - Drain Pump -
Cassette Cover - Cassette Cover -
Refrigerant Leakage Detector PRLDNVS0 Refrigerant Leakage Detector PRLDNVS0
EEV Kit PRGK024A0 EEV Kit PRGK024A0
Independent Power Module PRIP0 Independent Power Module PRIP0
Robot Cleaner - Robot Cleaner -
Pre Filter (Washable) ○ Pre Filter (Washable) ○
Ion Generator ○ Ion Generator ○
CO2 Sensor - CO2 Sensor -
Ventilation Kit - Ventilation Kit -
IR Receiver - IR Receiver -
Zone Controller - Zone Controller -
PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible), PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible),
Dry Contact (with additional accessory) Dry Contact (with additional accessory)
PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus) PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus)
External Input (1 point) ○ External Input (1 point) ○
Wi-Fi PWFMDD200 Wi-Fi PWFMDD200
100 / 101
INDOOR UNITS _ COMPATIBILITY INDOOR UNITS _ FEATURE FUNCTIONS
INDOOR
NEW
PQRCH- PDRYCB300 For Modbus
UNITS
PREMTA000A PREMTBB10 PREMTB100 PREMTBB01 PREMTB001 PQRCVCLOQ PQRCVC0QW PQRCHCA0Q PWLSSB21H Contact Contact
CA0QW PDRYCB500
PREMTA000B (H/P) PDRYCB000 PDRYCB400 NEW
PDRYCB320
Model Name
ARNU-A4
ARNU-B4
○ ○ ○ ○ ○ ○ ○ ○ ○ ○ PREMTA000
PREMTB100 PREMTB001 PQRCVCL0Q PQRCHCA0Q NEW
4 Way PREMTA000A PWFMDD200
PREMTBB10 PREMTBB01 PQRCVCL0QW PQRCHCA0QW PWLSSB21H (H/P)
PREMTA000B
Temperature Setting ○ ○ ○ ○ ○ ○ ○
ARNU-A4 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
Round CST Mode Change ○ ○ ○ ○ - ○ ○
Auto Swing ○ ○ ○ ○ ○ ○
ARNU-A4 ○ ○ ○ ○ ○ △ ○ ○ ○ ○ Vane Control
Basic ○ ○ ○ ○ ○ ○ ○
High Sensible (Louver Angle)
E.S.P
Ceiling ○ ○ ○ ○ ○ - -
(External Static Pressure)
Concealed ARNU-A4 ○ ○ ○ ○ ○ △ ○ ○ ○ ○
Duct Electric Failure
High / Mid Statics ○ ○ ○ ○ ○ - ○
Compensation
Advanced Lock
(mode, set point, set point Advanced Lock Advanced Lock - - - - -
Console ARNU-A4 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ range, on/off Lock)
Advanced
Filter Sign ○ ○ ○ - - - -
ARNU-A4
Wall Energy Management 2) ○ ○ ○ - - - -
Mounted
ARNU-C4 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
ARNU-N4
Dual Set Point ○ ○ - - - - -
Human Detection - ○ - - - - -
HYDRO
KIT 1)
ARNH-A4 - - - - - - ○ - ○ -
Temp, Humidity
○ ○ - - - - -
Compensation
Energy
Recovery
Wi-Fi AP mode setting ○ ○ ○ ○ ○ ○ -
Ventilator ○ ○ ○ - - - ○ - - ○
Operation Status LED ○ ○ ○ ○ ○ - -
Ventilation
Energy Recovery Wireless Remote Controller
○3) - ○3) ○3) ○3) - -
Ventilator with Receiver
DX coil
○ ○ ○ - - - ○ - - ○
ETC Display 5 inch Color 4.3 inch Color 4.3 inch mono 2.6 inch mono 2.6 inch mono 2 inch mono -
Size (W x H x D, mm) 137 x 121 x 16.5 120 x 120 x 16 120 x 120 x 16 64 x 120 x 15 64 x 120 x 15 51 x 153 x 26 -
AHU Communication Kit ○ ○ ○ - - △ - - - -
Black Light Control for
○ ○ - - - - -
Screen Saver
※ ○ : Compatible, △ : Need wired remote controller / IR receiver, - : Not compatible ※ ○ : Applied, - : Not Applied
1) It has a separate remote controller. 1) It might not be indicated or operated at the partial product.
2) Centralized control (PACEZA000 / PACS5A000 / PACP5A000 / PLNWKB000) and PDI (PQNUD1S40 / PPWRDB000) should be installed for this function.
3) For ceiling type duct.
Note
- Indoor unit should have functions requested by the controller.
- If you need more detail, please refer to the manual of product. (http://partner.lge.com: Home> Doc.Library> Manual)
102 / 103
HOT WATER
SOLUTION
HOT WATER
SOLUTION
HYDRO KIT
104 / 105
HOT WATER SOLUTION _ HYDRO KIT HOT WATER SOLUTION _ HYDRO KIT _ KEY FEATURES
Pressure
Water
HOT WATER
- Floor Heating : Medium Temp. HYDRO KIT (1ea)
SOLUTION
- Sanitary Hot Water : High Temp. HYDRO KIT (2ea), Sanitary Hot Water
Tanks R410A
- Electricity Cost : Average Cost in EU
R134A
- Gas Cost : Average Cost in EU Stage 1
Hot Water Heating Cooling - Oil Cost : Average Cost in EU Stage 2
Air
Initial Costs Annual Operating Costs
Enthalpy
HYDRO KIT
25,000 100% 90% 95% 25,000 229%
Radiant Heating / Cooling Fan Coil Unit Heating / Cooling Hot Water / Cold Water
20,000
15,000
20,000
15,000 171%
Various Applications
100% Applicable to a variety of facilities including hospitals,
Radiator 10,000 10,000
5,000 5,000
residences and resorts that need floor heating and
Gas Boiler Oil Boiler Gas Boiler Oil Boiler domestic hot water supply.
FCU
Floor heating LCC
50,000
Oil boiler
Gas boiler
40,000
30,000
Combination
20,000 Dormitory Hotel Office Restaurant
10,000
1 2 3 4 5 6 7 8 9 10 (Year)
Hot water+ Radiant heating HR unit (Cooling & Hot water) Thermal Storage System Energy Savings through Fitness Hospital Factory Residential
Heat Recovery
Energy costs can be minimized by reusing the wasted
HYDRO KIT
Domestic
Hot Water Tank 100
100%
Absorbed heat from indoor space is used for making hot water. Office Application
76% Hot water can be supplied
Air Heat Transfer
Hot water conditioning 60 at all times in the office by
HYDRO KIT HR Unit
supply cooling the HR unit to
MULTI V 5 40 30%
On Average
pump
Hot water Heat
Absorption
warm up the sanitary tank,
High temperature using waste energy.
MULTI V 5 Domestic
20 HYDRO KIT
(Heat Recovery) Hot Water Tank
Oil Gas Hot Water Supply Cooling
Boiler Boiler
MULTI V
Outdoor Unit Floor heating
(Water Cooled) Middle temperature
106 / 107
HOT WATER SOLUTION _ HYDRO KIT _ SPECIFICATION
HOT WATER
SOLUTION
Cooling Capacity kW 12.3 28.0 Heating Capacity kW 13.8 25.2
Heating Capacity kW 13.8 31.5 Power Input Nominal1) W 2,300 5,000
Power Input Nominal1) W 10 10 Exterior Color Morning Gray Morning Gray
Exterior Color Morning Gray Morning Gray RAL Code RAL 7030 RAL 7030
RAL Code RAL 7030 RAL 7030 Dimensions Body mm 520 x 1,080 x 330 520 x 1,080 x 330
Dimensions Body mm 520 x 631 x 330 520 x 631 x 330 (W x H x D) Shipping mm 682 x 1,168 x 423 682 x 1,168 x 423
(W x H x D) Shipping mm 677 x 687 x 418 677 x 687 x 418 Liquid Side mm (inch) Ø9.52 (3/8) Ø9.52 (3/8)
Pipe
HYDRO KIT
Liquid Side mm (inch) Ø9.52 (3/8) Ø9.52 (3/8) Gas Side mm (inch) Ø15.88 (5/8) Ø19.05 (3/4)
Pipe Connections
Gas Side mm (inch) Ø15.88 (5/8) Ø22.2 (7/8) Drain Pipe (Internal Dia.) A (inch) 25A (Male PT 1) 25A (Male PT 1)
Connections
Drain Pipe (Internal Dia.) A (inch) 25A (Male PT 1) 25A (Male PT 1) Water Pipe Inlet A (inch) 25A (Male PT 1) 25A (Male PT 1)
Water Pipe Inlet A (inch) 25A (Male PT 1) 25A (Male PT 1) Connections Outlet A (inch) 25A (Male PT 1) 25A (Male PT 1)
Connections Outlet A (inch) 25A (Male PT 1) 25A (Male PT 1) Weight Body kg 87.0 91.0
Weight Body kg 29.2 33.7 Sound Pressure Levels (H / M / L) dB(A) 43 46
Sound Pressure Levels (H / M / L) dB(A) 26 26 Power Supply Ø, V, Hz 1, 220-240, 50 1, 220-240, 50
Power Supply Ø, V, Hz 1, 220-240, 50 1, 220-240, 50 Communication Cable mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C
Communication Cable mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1) Nominal : Performance tested under EN14511
Note : 1. Capacities are based on the following conditions :
1) Nominal : Performance tested under EN14511
- Heating : Indoor 20°C (68°F) DB / 15°C (59°F) WB, Outdoor 7°C (44.6°F) DB / 6°C (42.8°F) WB, Water Inlet 55°C (131°F) / Outlet 65°C (149°F)
Note : 1. Capacities are based on the following conditions :
2. Piping Length : Interconnected Pipe Length = 7.5m
- Cooling : Indoor 27°C (80.6°F) DB / 19° C (66.2°F) WB, Outdoor 35°C (95°F) DB / 24°C (75.2°F) WB, Water Inlet 23°C (73.4°F) / Outlet 18°C (64.4°F)
3. Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
- Heating : Indoor 20°C (68°F) DB / 15°C (59°F) WB, Outdoor 7°C (44.6°F) DB / 6°C (42.8°F) WB, Water Inlet 30°C (86°F) / Outlet 35°C (95°F)
4. MULTI V S 4HP (ARUN040GSS0, ARUN040LSS0) cannot be connected to HYDRO KIT.
2. Piping Length : Interconnected Pipe Length = 7.5m
5. MULTI V Water S cannot be connected to HYDRO KIT.
3. Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
4. MULTI V S 4HP (ARUN040GSS0, ARUN040LSS0) cannot be connected to HYDRO KIT.
5. MULTI V Water S cannot be connected to HYDRO KIT.
6. Anti freezing liquid should be added under 10°C (outdoor temp.) during cooling mode.
Accessories Accessories
Chassis ARNH04GK2A4 ARNH10GK2A4 Chassis ARNH04GK3A4 ARNH08GK3A4
Drain Pump - Drain Pump -
Cassette Cover - Cassette Cover -
Refrigerant Leakage Detector PRLDNVS0 Refrigerant Leakage Detector PRLDNVS0
EEV Kit - EEV Kit -
Independent Power Module ○ Independent Power Module ○
Robot Cleaner - Robot Cleaner -
Pre Filter (Washable) - Pre Filter (Washable) -
Ion Generator - Ion Generator -
CO2 Sensor - CO2 Sensor -
Ventilation Kit - Ventilation Kit -
IR Receiver - IR Receiver -
Zone Controller - Zone Controller -
PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible) PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible)
Dry Contact (with additional accessory) Dry Contact (with additional accessory)
PDRYCB320 (Universal input) PDRYCB320 (Universal input)
External Input (1 point) ○ External Input (1 point) ○
Wi-Fi PWFMDD200 Wi-Fi PWFMDD200
108 / 109
VENTILATION
SOLUTIONS
VENTILATION
SOLUTIONS
ERV
110 / 111
VENTILATION SOLUTIONS _ ERV VENTILATION SOLUTIONS _ ERV _ KEY FEATURES
HIGH EFFICIENCY
High Efficiency Heat Exchanger CO2 Auto Operation
ENERGY RECOVERY Efficiency and comfort is ensured through the high-efficiency
energy recovery central core which recovers energy from
LG ERV reduces energy loss with auto fan speed control
following CO2 level
VENTILATION (ERV)
Fine CO2 level
the indoor air and transfers it to the fresh incoming air High occupancy Low occupancy CO2 level
without mixing the air stream. (high CO2 level) (low CO2 level) Fan speed
Air Filter
Low
Exchanger Air
Supply Air
4% Energy Saving
(Annually)
Extra
high high
Outdoor Air Indoor Air
9 o’clock 10 11 12 13 14 15 16 17
※ This function is operated with ‘Night Time Free Cooling’ on remote controller. (with MULTI V only)
※ Energy saving ratio can be differed by weather condition.
※ Test Condition - Office (49,000ft2) / Occupancy : 30 / Area : London, UK
- ERV (1000 CMH) + MULTI V IV (12HP) Unit Combination
- Other conditions are subject to BREEAM.
VENTILATION
SOLUTIONS
Compulsory Exhaust System Seasonal Auto Operation
The exhausting system using high static and sirocco fan LG ERV senses outdoor temperature and operates
removes contaminants effectively from indoor air. Supply automatically following weather condition.
and exhaust air flows are completely separated in the total High temp. Natural ventilation
Heat recovery LG ERV heat recovery mode
heat exchanger, LG ERV can filter out the impurities before mode LG ERV bypass mode
supplying outdoor air and make indoor air fresh and healthy.
ERV
Proper temp.
Bypass mode 5% Energy Saving
(Annually)
Exchanger Air Supply Air
Exchanger Damper
Low temp.
Air Heat recovery
Return
Air mode
Supply Month Jan. Feb. Mar. Apr. May. Jun. Jul. Aug. Sep. Oct. Nov. Dec.
Air
Outdoor Heat recovery mode Bypass mode
Indoor Air Air
Outdoor Air
Indoor Outdoor Indoor Outdoor
NECESSITY OF ERV outdoors and cool outdoor air can be brought indoors for
energy savings.
Delay Operation
Afternoon Night Morning When the air conditioner and ERV are switched on simultaneously,
Indoor temp. Outdoor temp.(winter) delay operation can reduce unnecessary heating and cooling
Energy Recovery Ventilation (ERV)
22°C -5°C
energy loss by slowing down automatic ERV operation.
Operation Delay operation
Set Temp. Operation starts Operation air conditioner simultaneously. Operation starts with air conditioner.
C
16 ° ERV makes inside cooler Inside Temp.
with bypass mode like Outside Temp. ON Energy consumption Fine CO2 level
natural ventilation
OFF 2%
Energy Saving (Annually)
ON
CO2 level
Natural Ventilation
Office time
Outdoor temp.
-5°C
Indoor temp.
22°C
-5°C Inside is getting
higher in the night
2% Energy Saving
(Annually) starts
112 / 113
VENTILATION SOLUTIONS _ ERV _ KEY FEATURES
Visible
Main display Further information • Indoor CO2 level Exhausting and Supplying
If the CO2 level is above 900ppm in CO2 level and room condition are • Alarm for filter change / Remained time to change filters Fast Ventilation Mode Simultaneously
the room, the red mark is on. displayed continuously.
Monitoring CO2
CO2 1,215 ppm
Group Control
VENTILATION
Exhaust
SOLUTIONS
comfort level Heating
20.5° Fan
※ The remote controller screen image CO2 1 wired remote controller up to 16 ERV (Including air Supply
CO2
may change. 1215 ppm SEVERE Fan
※ Applicable to only Standard III, Premium
conditioner). It is convenient for large common space
remote controller. such as lobby.
Several units combination
CO2 Concentration Control 16 units group control is available with 1 remote controller.
Using CO2 sensor, LG ERV controls exhaust air flow automatically
ERV
to keep indoor air fresh under settled CO2 concentration. Good looking interior External Static Pressure Control Total Air Conditioning Solution
The high static pressure fan can control the air volume LG ERV DX can be used as a Total Air Conditioning Solution.
depending on the length of the duct. It is also easy to It can control condition of incoming air with the DX coil and
CO2 Sensor
RS3 Remote
control the pressure level by using the remote controller humidifier for making comfortable indoor air.
(AHCS 100H0)
(Internal type : Default) Controller for a more flexible duct installation and easier testing. In the summer, LG ERV DX controls the air indoors by cooling
Conventional New and dehumidifying incoming air. In winter, it can provide warm
Air
CO2
(ppm) Controller & installation cost saving Volume air by heating and humidifying the incoming air.
Heat Exchange DX Coil Humidification
Windows Windows Windows Windows
Closed Open Closed Open H
2,500
M
L Exhaust Supply
Air Air
1,000
LG ERV durability is increased through bacteria-resistant material and controlled individually. External Static Pressure (mmAq)
of heat exchanger and corrosion protection coating. It prevents - This function can be operated when the system
shortening product life due to corrosion and mold and supplies is connected with 1 remote controller. Easy Cleaning and Filter Change Interlocking with MULTI V
high quality air to inside by minimizing the bacteria. Filter can be conveniently changed and cleaned. LG ERV DX can be interlocked with MULTI V.
Others LG ERV It can be controlled individually by a wired remote
Remote
Inside ERV Inside ERV Controller controller connected to MULTI V indoor units.
Corrosion
occurrence Indoor Units
Corrosion
protection coating MAX. 16
+ Finish insulator
ERV Unit Remove Side Panel
Outdoor unit
ERV DX
114 / 115
VENTILATION SOLUTIONS _ ERV _ SPECIFICATION
ERV ERV
LZ-H025GBA4 / LZ-H035GBA4 LZ-H080GBA4 / LZ-H100GBA4
LZ-H050GBA4 LZ-H150GBA4 / LZ-H200GBA4
VENTILATION
SOLUTIONS
Pa 100 / 70 / 50 150 / 130 / 100 150 / 100 / 50 Pa 200 / 110 / 60 160 / 90 / 50 200 / 110 / 60 160 / 90 / 50
External Static Pressure SH / H / L External Static Pressure SH / H / L
ERV Mode (inWTR) (0.40 / 0.28 / 0.20) (0.60 / 0.52 / 0.40) (0.60 / 0.40 / 0.20) ERV Mode (inWTR) (0.80 / 0.44 / 0.24) (0.64 / 0.36 / 0.20) (0.80 / 0.44 / 0.24) (0.64 / 0.36 / 0.20)
Temperature Exchange Temperature Exchange
SH / H / L % 80 / 80 / 83 75 / 75 / 77 78 / 78 / 79 SH / H / L % 79 / 79 / 82 77 / 77 / 78 79 / 79 / 82 77 / 77 / 78
Efficiency Efficiency
Enthalpy Exchange Heating (SH / H / L) % 70 / 70 / 72 68 / 68 / 70 73 / 73 / 75 Enthalpy Exchange Heating (SH / H / L) % 72 / 72 / 74 70 / 70 / 72 72 / 72 / 74 70 / 70 / 72
Efficiency Cooling (SH / H / L) % 66 / 66 / 68 63 / 63 / 65 66 / 66 / 69 Efficiency Cooling (SH / H / L) % 63 / 63 / 66 59 / 59 / 63 63 / 63 / 66 59 / 59 / 63
Noise Level Noise Level
SH / H / L dB(A) 29 / 28 / 24 32 / 30 / 27 34 / 32 / 25 SH / H / L dB(A) 40 / 37 / 31 41 / 38 / 32 43 / 40 / 34 44 / 41 / 35
(Sound Level, 1.5m) (Sound Level, 1.5m)
ERV
Step - SUPER-HIGH / HIGH / LOW Step - SUPER-HIGH / HIGH / LOW
Current SH / H / L Amps 0.70 / 0.60 / 0.42 1.10 / 0.95 / 0.60 1.92 / 1.58 / 0.79 Current SH / H / L Amps 2.77 / 2.16 / 1.44 3.41 / 2.90 / 1.76 5.60 / 5.40 / 2.90 6.80 / 5.90 / 3.60
Power Input SH / H / L W 97 / 78 / 52 180 / 163 / 88 240 / 220 / 90 Power Input SH / H / L W 390 / 280 / 187 480 / 385 / 210 780 / 540 / 377 960 / 770 / 420
CMH 250 / 250 / 150 350 / 350 / 210 500 / 500 / 320 CMH 800 / 800 / 660 1,000 / 1,000 / 800 1,500 / 1,500 / 1,200 2,000 / 2,000 / 1,600
Bypass Mode Air Flow SH / H / L Bypass Mode Air Flow SH / H / L
(CFM) (147 / 147 / 88) (206 / 206 / 123) (294 / 294 / 124) (CFM) (471 / 471 / 388) (589 / 589 / 471) (883 / 883 / 706) (1,177 / 1,177 / 942)
Pa 100 / 70 / 50 150 / 130 / 100 150 / 100 / 50 Pa 200 / 110 / 60 160 / 90 / 50 200 / 110 / 60 160 / 90 / 50
External Static Pressure SH / H / L External Static Pressure SH / H / L
(inWTR) (0.40 / 0.28 / 0.20) (0.60 / 0.52 / 0.40) (0.60 / 0.40 / 0.20) (inWTR) (0.80 / 0.44 / 0.24) (0.64 / 0.36 / 0.20) (0.80 / 0.44 / 0.24) (0.64 / 0.36 / 0.20)
Noise Level Noise Level
SH / H / L dB(A) 29 / 29 / 25 32 / 30 / 27 35 / 33 / 25 SH / H / L dB(A) 41 / 38 / 32 41 / 39 / 33 44 / 41 / 35 44 / 42 / 36
(Sound Level, 1.5m) (Sound Level, 1.5m)
Heat Exchanger Type - Air to air cross flow heat exchange Heat Exchanger Type - Air to air cross flow heat exchange
Net Weight kg 44 44 44 Net Weight kg 62 140
Dimension WxHxD mm 988 x 273 x 1,014 988 x 273 x 1,014 988 x 273 x 1,014 Dimension WxHxD mm 1,062 x 365 x 1,140 1,313 x 738 x 1,140
Qty EA 4 Qty EA 4 4+2
Duct Work Duct Work
Size (Ø) mm Ø200 Size (Ø) mm Ø250 Ø250 + Ø350
Qty EA 1 Qty EA 1 2
Supply Air Fan Supply Air Fan
Type - Direct-Drive (Sirocco Fan) Type - Direct-Drive (Sirocco Fan)
Qty EA 1 Qty EA 1 2
Exhaust Air Fan Exhaust Air Fan
Type - Direct-Drive (Sirocco Fan) Type - Direct-Drive (Sirocco Fan)
Qty EA 2 2 Qty EA 2 4
Filters (Default) Type - Cleanable fibrous fleeces Filters (Default) Type - Cleanable fibrous fleeces
Size (W x H x D) mm 855 x 10 x 160 855 x 6 x 230 Size (W x H x D) mm 1,056 x 6 x 212.5
Model - AHFT035H0 AHFT050H0 Model - AHFT100H0
Qty EA 2 2 Qty EA 2 4
Filters (Optional) Filters (Optional)
Type - F7 F7 Type - F7
Size (W x H x D) mm 423.5 x 132 x 25 425 x 194 x 25 Size (W x H x D) mm 520 x 192 x 25
Dry Contact PDRYCB000 Dry Contact PDRYCB000
Note : 1. ERV mode : Total Heat Recovery Ventilation mode Note : 1. ERV mode : Total Heat Recovery Ventilation mode
2. Refer to dimensional drawings. 2. Refer to dimensional drawings.
3. Noise level : 3. Noise level :
- The operating conditions are assumed to be standard. - The operating conditions are assumed to be standard.
- Sound measured at 1.5m below the center the body. - Sound measured at 1.5m below the center the body.
- Sound level will vary depending on a range of factors such as the construction (acoustic absorption coefficient) of particular room in which the equipment is installed. - Sound level will vary depending on a range of factors such as the construction (acoustic absorption coefficient) of particular room in which the equipment is installed.
- The sound level at the air discharge port is about 8 dB(A) higher than the unit's operating sound. - The sound level at the air discharge port is about 8 dB(A) higher than the unit’s operating sound.
4. Temperature and Enthalpy Exchange Efficiency at cooling Indoor Temperature : 26.5°C DB, 64.5% RH, Outdoor Temperature : 34.5°C DB, 75% RH 4. Temperature and Enthalpy Exchange Efficiency at cooling Indoor Temperature : 26.5°C DB, 64.5% RH, Outdoor Temperature : 34.5°C DB, 75% RH
5. Temperature and Enthalpy Exchange Efficiency at heating Indoor Temperature : 20.5°C DB, 59.5% RH, Outdoor Temperature : 5°C DB, 65% RH 5. Temperature and Enthalpy Exchange Efficiency at heating Indoor Temperature : 20.5°C DB, 59.5% RH, Outdoor Temperature : 5°C DB, 65% RH
6. Temperature Exchange efficiency is tested at heating condition. 6. Temperature Exchange efficiency is tested at heating condition.
116 / 117
VENTILATION SOLUTIONS _ ERV _ SPECIFICATION
VENTILATION
Bypass Mode (SH / H / L) CMH 500 / 500 / 440 800 / 800 / 640 1,000 / 1,000 / 820 Bypass Mode (SH / H / L) CMH 500 / 500 / 440 800 / 800 / 640 1,000 / 1,000 / 820
SOLUTIONS
Fan External Static Pressure (SH / H / L) Pa 160 / 120 / 100 140 / 90 / 70 110 / 70 / 60 Fan External Static Pressure (SH / H / L) Pa 180 / 150 / 110 170 / 120 / 80 150 / 100 / 70
System Natural Evaporating Type System -
Humidifier Amount kg/h 2.70 4.00 5.40 Humidifier Amount kg/h -
Pressure Feed Water Mpa 0.02 ~ 0.49 Pressure Feed Water Mpa -
Heat Exchange Mode (SH / H / L) dB(A) 38 / 36 / 33 39 / 37 / 34 40 / 38 / 35 Heat Exchange Mode (SH / H / L) dB(A) 39 / 37 / 35 41 / 38 / 36 41 / 39 / 36
Sound Pressure Sound Pressure
Bypass Mode (SH / H / L) dB(A) 39 / 37 / 34 40 / 38 / 35 40 / 38 / 35 Bypass Mode (SH / H / L) dB(A) 39 / 37 / 35 41 / 38 / 36 41 / 39 / 36
Refrigerant R410A Refrigerant R410A
Power Supply Ø, V, Hz 1, 220-240, 50 / 60 Power Supply Ø, V, Hz 1, 220-240, 50 / 60
ERV
Power Input Heat Exchange Mode (SH / H / L) kW 0.25 / 0.20 / 0.15 0.42 / 0.35 / 0.25 0.48 / 0.42 / 0.27 Power Input Heat Exchange Mode (SH / H / L) kW 0.25 / 0.20 / 0.15 0.42 / 0.35 / 0.25 0.48 / 0.42 / 0.27
(Nominal) Bypass Mode (SH / H / L) kW 0.25 / 0.20 / 0.15 0.42 / 0.35 / 0.25 0.48 / 0.42 / 0.27 (Nominal) Bypass Mode (SH / H / L) kW 0.25 / 0.20 / 0.15 0.42 / 0.35 / 0.25 0.48 / 0.42 / 0.27
Nominal Running Heat Exchange Mode (SH / H / L) A 1.5 / 1.3 / 1.0 2.5 / 2.0 / 1.5 3.6 / 3.2 / 2.3 Nominal Running Heat Exchange Mode (SH / H / L) A 1.5 / 1.3 / 1.0 2.5 / 2.0 / 1.5 3.6 / 3.2 / 2.3
Current (RLA) Bypass Mode (SH / H / L) A 1.5 / 1.3 / 1.0 2.5 / 2.0 / 1.5 3.6 / 3.2 / 2.3 Current (RLA) Bypass Mode (SH / H / L) A 1.5 / 1.3 / 1.0 2.5 / 2.0 / 1.5 3.6 / 3.2 / 2.3
Heat exchange system Air to air cross flow total heat (Sensible + Latent heat) exchange Heat exchange system Air to air cross flow total heat (Sensible + Latent heat) exchange
Heat exchange element Specially processed non-flammable paper Heat exchange element Specially processed non-flammable paper
Air Filter Multidirectional fibrous fleeces Air Filter Multidirectional fibrous fleeces
Dimensions WxHxD mm 1,667 x 365 x 1,140 Dimensions WxHxD mm 1,667 x 365 x 1,140
Net Weight kg 105 Net Weight kg 98
Liquid mm Ø6.35 Liquid mm Ø6.35
Gas mm Ø12.7 Gas mm Ø12.7
Piping Connection Piping Connection
Water mm Ø6.35 Water mm -
Drain Pipe (Internal Dia.) mm (inch) Ø25 (1) Drain Pipe (Internal Dia.) mm (inch) Ø25 (1)
Connection Duct Diameter mm Ø250 Connection Duct Diameter mm Ø250
Note : 1. Cooling Capacity Test condition - Indoor temperature : 27°C DB, 19°C WB / Outdoor temperature : 35°C DB Note : 1. Cooling Capacity Test condition - Indoor temperature : 27°C DB, 19°C WB / Outdoor temperature : 35°C DB
2. Heating Capacity Test condition - Indoor temperature : 20°C DB / Outdoor temperature : 7°C DB, 6°C WB 2. Heating Capacity Test condition - Indoor temperature : 20°C DB / Outdoor temperature : 7°C DB, 6°C WB
3. Humidifying capacity is based on the following conditions - Indoor temperature : 20°C DB, 15°C WB / Outdoor temperature : 7°C DB, 6°C WB 3. Humidifying capacity is based on the following conditions - Indoor temperature : 20°C DB, 15°C WB / Outdoor temperature : 7°C DB, 6°C WB
4. Cooling and heating capacities are based on the following conditions. : Fan is based on High and Super-high. 4. Cooling and heating capacities are based on the following conditions. : Fan is based on High and Super-high.
5. The operating sound measured at the point 1.5 m below the center of the unit is converted to that measured at an anechoic chamber. 5. The operating sound measured at the point 1.5 m below the center of the unit is converted to that measured at an anechoic chamber.
6. The specifications, designs and information here are subject to change without notice. 6. The specifications, designs and information here are subject to change without notice.
Accessories Accessories
Chassis LZ-H050GXH4 LZ-H080GXH4 LZ-H100GXH4 Chassis LZ-H050GXN4 LZ-H080GXN4 LZ-H100GXN4
Drain Pump - Drain Pump -
Cassette Cover - Cassette Cover -
Refrigerant Leakage Detector PRLDNVS0 Refrigerant Leakage Detector PRLDNVS0
EEV Kit - EEV Kit -
Independent Power Module - Independent Power Module -
Robot Cleaner - Robot Cleaner -
Pre Filter (Washable) - Pre Filter (Washable) -
Ion Generator - Ion Generator -
CO2 Sensor AHCS100H0 CO2 Sensor AHCS100H0
Ventilation Kit - Ventilation Kit -
IR Receiver - IR Receiver -
Zone Controller - Zone Controller -
PDRYCB000 (1 point contact) PDRYCB000 (1 point contact)
Dry Contact (with additional accessory) Dry Contact (with additional accessory)
PDRYCB500 (Modbus) PDRYCB500 (Modbus)
External Input (1 point) ○ External Input (1 point) ○
Wi-Fi - Wi-Fi -
118 / 119
CONTROL
SOLUTIONS
INDIVIDUAL CONTROL
CENTRALIZED CONTROL
INTEGRATION DEVICE
120 / 121
CONTROL SOLUTIONS
LG CONTROL SOLUTIONS
MULTI V 5 offers a diverse range of effective control solutions that satisfy specific needs of each building and its user scene.
These control systems are equipped with user-friendly interface, flexible interlocking environment, energy management and smart
individual controller for optimized controlling conditions and smart building management.
HOTEL OFFICE
• Energy Management
• External Device
Power Distribution Solution Smart Individual Control Solution Small Central Control Solution
Integration Solution
122 / 123
CONTROL SOLUTIONS _ INDIVIDUAL CONTROL
FEATURE FUNCTIONS
INDIVIDUAL Controller Name
Premium
Wired Remote Controller
CONTROL
Model Name
PREMTA000
PREMTB100 PREMTB001 PQRCVCL0Q PQRCHCA0Q NEW
PREMTA000A PWFMDD200
PREMTBB10 PREMTBB01 PQRCVCL0QW PQRCHCA0QW PWLSSB21H (H/P)
PREMTA000B
On / Off ○ ○ ○ ○ ○ ○ ○
Temperature Setting ○ ○ ○ ○ ○ ○ ○
Mode Change ○ ○ ○ ○ - ○ ○
Auto Swing ○ ○ ○ ○ ○ ○
Vane Control
○ ○ ○ ○ ○ ○ ○
Basic (Louver Angle)
E.S.P
○ ○ ○ ○ ○ - -
(External Static Pressure)
Electric Failure
○ ○ ○ ○ ○ - ○
Compensation
Schedule / Timer Weekly - Yearly Weekly - Yearly Weekly - - Sleep / On / Off Weekly
SOLUTIONS
CONTROL
Additional Mode Setting 1)
○ ○ ○ - - - -
Time Display ○ ○ ○ - - ○ -
Humid. Display ○ ○ - - - - -
Advanced Lock
(Mode, Set point, Set point Advanced Lock Advanced Lock - - - - -
range, On / Off Lock)
INDIVIDUAL CONTROL
Filter Sign ○ ○ ○ - - - -
Advanced
Energy Management 2) ○ ○ ○ - - - -
Human Detection - ○ - - - - -
Temp, Humidity
○ ○ - - - - -
Compensation
ETC Display 5 inch Color 4.3 inch Color 4.3 inch mono 2.6 inch mono 2.6 inch mono 2 inch mono -
Size (W x H x D, mm) 137 x 121 x 16.5 120 x 120 x 16 120 x 120 x 16 64 x 120 x 15 64 x 120 x 15 51 x 153 x 26 -
124 / 125
CONTROL SOLUTIONS _ INDIVIDUAL CONTROL
SOLUTIONS
※ ○ : Applied, - : Not Applied
- Instantaneous power monitor
CONTROL
Temperature
1) It might not be indicated or operated at the partial product. - With 2 set points control function, indoor unit manages
- Energy consumption check 2) This function is available for duct type.
3) This function requires PDI (PQNUD1S40 / PPWRDB000) to be installed. room temperature automatically.
(Power consumption, operation time) Note : 1. Indoor unit needs to have functions requested by the controller. Cooling set point
2. 2 set points control works normally with MULTI V Heat Recovery and Single Split for Unoccupied Cooling
- Temp. Setback timer, time limit control Heat Pump. But in case of MULTI V Heat Pump, It may not work properly. Setback for energy savings and comfort Cooling Set Point
- Target setting (ODU capacity, Instantaneous power) - In the user's absence, the room temperature will remain for Occupied
Occupied Unoccupied
• Group control between two set points rather than switching off providing Heating Set Point
for Occupied
- Up to 16 Indoor units can be controlled with one quick comfort when the mode is changed to occupied.
INDIVIDUAL CONTROL
Heating Set Point
Heating
remote control ※ This function is for Heat Recovery system or Single heat pump. for Unoccupied
Otherwise it is not guaranteed. Cooling Heating
• External device On / Off (1 point)
Time
- Customized interlocking control with indoor unit is Arrive at a room Leave a room
possible without dry contact Thermo-off
• 2 set points control Indoor temperature
Comfort Level
Schedule Function
Simple Schedule Status Exception Day settings
Standard III remote controller Possible to set up exceptional
Touch Button provides clock type daily schedule. date on regular schedule.
Energy Contents
Error History
126 / 127
CONTROL SOLUTIONS _ INDIVIDUAL CONTROL
SOLUTIONS
- 5 inch color LCD Note : 1. Indoor unit needs to have functions requested by the controller.
CONTROL
2. 2 set points control works normally with MULT V Heat Recovery and Single Split Heat
• Energy saving functions Pump. But in case of MULTI V Heat Pump, It may not work properly.
- Instantaneous power monitor A simple way to control office or hotel systems in a compact design.
- Energy consumption check
(Power consumption, operation time) Model Name PQRCVCL0QW / PQRCHCA0QW /
PQRCVCL0Q PQRCHCA0Q
- Temp. Setback timer, Time limit control On / Off ○ ○
- Target setting (ODU capacity, Instantaneous power…etc) Fan Speed Control ○ ○
INDIVIDUAL CONTROL
Temperature Setting ○ ○
• Group control Cooling / Heating / Auto /
Mode Change -
- Up to 16 Indoor units can be controlled with one remote control Dehumidification / Fan
Auto Swing ○ ○
• 2 set points control Vane Control (Louver direction) ○ ○
- Increase convenience and comfort E.S.P (External Static Pressure) ○ ○
Electric Failure Compensation ○ ○
- Auto changeover, Setback (Home leave) PQRCVCL0QW (White) / PQRCHCA0QW (White) / Child Lock ○ ○
PQRCVCL0Q (Black) PQRCHCA0Q (Black) Indoor Temperature Display ○ ○
Wireless Remote Controller
Easy Energy Management Receiver
○ 1) ○ 1)
Full Touch
Screen
- Check the operation hour or electricity usage
- Comparison of usage compared to last year
Features & Benefits Size (W x H x D, mm)
Blacklight
70 x 121 x 16
○
70 x 121 x 16
○
- Set the target usage and time • Small remote control with minimal functionality ※ ○ : Applied, - : Not Applied
1) For ceiling type ducted unit
Note : Indoor unit needs to have functions requested by the controller.
Easy Scheduling
- Daily, Weekly, Yearly schedule function
- Schedule pattern setting
- Auto changeover switching the operation Cooling Model Name PWLSSB21H (H/P)
Upper
mode automatically Temperature limit On / Off ○
- Setback (Home Leave) Changing status by Lower
Auto Changeover Setback Fan Speed Control ○ 1)
occupied / unoccupied Temperature limit Temperature Setting ○
Heating
Mode Change Cooling / Heating / Auto / Dehumidification / Fan
* This function is only for Heat Recovery system
and Single heat pump. Time Plasma Purification / Energy-Saving Cooling /
Leave For Home Leave For Home Additional Mode Setting
Robot Cleaning / Auto Dry
Group Control Auto Swing ○
Indoor unit 1 Indoor unit 2 Indoor unit 3 Vane Control (Louver direction) ○
- Max. 16 Indoor units by one remote controller. NEW
1 Master
1 Slave Slave
Reservation Sleep / On / Off
Time Display ○
Red (12V)
Yellow (Sig)
Black (GND)
Yellow (Sig)
Black (GND)
Yellow (Sig)
Black (GND) PWLSSB21H (H/P) Indoor Temperature Display ○
Sleep Mode Auto Max. 7 hours
2 2 Features & Benefits Size (W x H x D, mm) 51.4 x 153 x 26
Master ※ ○ : Applied, - : Not Applied
• Easy to use while moving • Main functions are available 1) For some products, you can use “slow” fan speed function.
128 / 129
CONTROL SOLUTIONS _ INDIVIDUAL CONTROL
LG Wi-Fi MODEM
Control LG air conditioners by using internet devices as Android or iOS smartphones. LG ThinQTM Connectivity
Model Name PWFMDD200
LG ThinQ
TM
Size (W x H x D, mm) 48 x 68 x 14
Interfaceable Products MULTI V Indoor unit 3)
Connection Type Indoor unit 1:1
Communication Frequency 2.4 GHz ➋
Wireless Standards IEEE 802.11b/g/n
LG ThinQTM (Android v4.1(Jellybean) or higher, iPhone iOS
Mobile Application
9.0 or higher)
PWFMDD200 Optional Extension Cable PWYREW000 (10m extension)
1) Vane Control may not be possible according to the type of Indoor unit. ➊ ➊ ➌
2) LG Centralized controller and PDI installation is required for this function.
Features & Benefits 3) For the compatibility with Indoor unit, please contact regional LG office.
Note : 1. Functionality may be different according to each IDU model.
2. User interface of application shall be revised for its design and contents improvement.
• User can enjoy anytime, anywhere access with Wi-Fi 3. Application is optimized for smartphone use, so it may not be well functioning
equipped device through LG's ThinQTM mobile app. with tablet devices. Internet
Service Provider
• This allows the user to access the unit remotely to Wireless AP
switch unit on or off before or after leaving the vicinity. (Router)
• LG’s exclusive Home Appliances control app (LG ThinQTM)
is available Connection (Pairing) Order
• Simple operation for various functions ➊ Make LG account on LG ThinQTM and select the Router that will be used
- On / Off ➋ Insert passwords of selected router and set AP (Access Point) by LG remote controller
- Operation mode ➌ Confirm the pairing between Wi-Fi Modem and Router
- Current/Set temperature
- Fan speed
SOLUTIONS
- Vane control 1)
CONTROL
- Reservation (Sleep, Weekly On / Off) ThinQTM Mobile App
- Energy monitoring 2)
- Filter management Simple operation for various functions
Controlling Reservation Energy
- Error check & Monitoring Monitoring On/Off, Current Temp, Mode, Set Temp Vane Control
INDIVIDUAL CONTROL
Overview
Wi-Fi
Modem ThinQTM Server
USB Wire
Day Night
Easy Management
LG ThinQTM
Reservation Energy Monitoring Smart Diagnosis Filter Management
※ Search “LG ThinQTM” on Google market or Appstore then download the app.
※ Internet service with Wi-Fi connection has to be available.
Control panel
USB cable Wi-Fi modem
※ Each indoor unit has a Wi-Fi modem installation location inside the product, and it can be installed by exposure if necessary.
130 / 131
CONTROL SOLUTIONS _ CENTRALIZED CONTROL
SOLUTIONS
Set Back - ○ ○ 4) ○ 4) ○ 4) ○
CONTROL
Additional
2 Set - ○ ○ ○ ○ 4) ○
Function
Change Alarm - Filter Filter Filter Filter Filter
Indoor Unit Lock - ○ ○ ○ ○ 4) -
Cycle - - ○ ○ ○ 4) ○
Air Purification Function - - ○ ○ - ○
CENTRALIZED CONTROL
Schedule ○ ○ ○ 4) ○ 4) ○ 4) ○
132 / 133
CONTROL SOLUTIONS _ CENTRALIZED CONTROL
AC EZ TOUCH
Smart management with 5 inch touch screen for small site. Energy Mode Schedule
When using energy mode function, operation mode changes Schedule control allows user to set the events in advance
Model Name PACEZA000 from cooling to fan or heating to off mode by force. to maximize system performance. Also, by blocking
Size (W x H x D, mm) 137 x 121 x 25 (It is available only for operating indoor unit) unnecessary operation, it prevents a waste of energy.
Interfaceable Products MULTI V / ERV / ERV DX / HYDRO KIT / THERMA V
Maximum number of units 64
Individual / Group Control On & Off / Mode / Temperature / Fan speed
Individual Controller Lock Temperature / Mode / Fan speed / All
Error Check ○
Slave Mode (Interlocking with
○
PACEZA000 higher level controller)
Schedule Weekly / Monthly / Yearly / Exception day
Remote Access By client S/W
Features & Benefits Emergency Stop & Alarm
○
Display
• User-friendly control with iconographic interface
Power Consumption
○
• Total 200 schedule events Monitoring (with PDI)
• Energy saving mode Auto Changeover / Setback ○ Alarm Indicator Group / Individual Control
• Energy monitoring (with PDI) Temperature Limit ○ It shows errors and alarm information. Users can respond User can control each indoor unit individually or by group
Operation History Error record immediately according to alarm indicator therefore HVAC by simply clicking each unit on control screen.
• 2 set point function (Upper / Lower temperature setting)
ODU Low Noise 1) ○
• Temperature set points range limit system is monitored consistently.
Daylight Saving Time ○
• Remote controller lock (All, Temp, Mode, Fan Speed)
External IO Port DI 1
• Operation history
IPv6 Support ○
• Clean or change filter alert
※ ○ : Applied, - : Not Applied
• Emergency stop 1) It is only available in some products.
SOLUTIONS
CONTROL
Overview
IDU
...
CENTRALIZED CONTROL
PC Internet AC EZ TOUCH
...
IDU
AC EZ
Easy to manage up to 32 indoor units, including ERV with simple interface.
* IPv6 supported
Features & Benefits
• 32 indoor units control
• Weekly Schedule
• Individual / Group Control
Internet Appropriate PI 485 should be • MULTI V 5 • MULTI V • MULTI V S • MULTI SPLIT • ERV
used according to PDB • MULTI V IV WATER IV • SINGLE SPLIT
* Fix Public IP is mandatory. • MULTI V III • MULTI V
* Router’s Configuration of NAT is mandatory. Open port 80 & 9300. • MULTI V II WATER II
134 / 135
CONTROL SOLUTIONS _ CENTRALIZED CONTROL
AC SMART 5
10-inch touch screen with HTML5 GUI (Graphic User Interface) for easy control. Building Management System (BMS) Integration Advanced Network Accessibility
Without additional device, AC Smart 5 provides BACnet IP & Modbus TCP inter- AC Smart 5 reflects the state of the art of network technology trend. IPv6
Model Name PACS5A000 face for BMS integration as well as its own management function. (Internet Protocol version 6), which is the most recent version of the Internet
Size (W x H x D, mm) 253.2 x 167.7 x 28.9 Protocol, provides accessibility to the IPv6 compatible network environment.
MULTI V / ERV / ERV DX / HYDRO KIT / In addition, HTML5 allows you to easily control LG HVAC system on a variety
Interfaceable Products
THERMA V / AHU kit / LG Chiller 1) of platforms (PC, Mobile, Tablet), at any time and from any location, not just
Maximum number of units 128 on the touch screen.
Individual / Group Control On & Off / Mode / Temperature / Fan speed BACnet over IP BMS
Individual Controller Lock Temperature / Mode / Fan speed / All
Comfort Cooling / ODU Low Noise / ODU Defrost Mode /
Advanced Function Setting and
Comfort Level display / CO2 Level display (for ERV /
Display 2)
ERV DX) / Night Time Free Cooling (for ERV / ERV DX)
Error Check ○
PACS5A000 Slave Mode (Interlocking with
○
higher level controller) IPv6
Schedule Weekly / Monthly / Yearly / Exception day Network
Features & Benefits Web Access ○
Emergency Stop & Alarm
○
• The central controller allows control of the LG Display
Power Consumption
HVAC system to various platforms. Monitoring (with PDI)
○ HTML5 web design
(Touch screen, PC, Smartphone, Tablet) Auto Changeover / Setback ○
Temperature Limit ○
- DI : 2 / DO : 2 Operation Time Limit ○
- Max. 128 IDU control Visual Navigation ○
Operation Trend ○
- BACnet IP/Modbus TCP
Interlock Control ○ Energy Management Visualized Control
- Schedule Virtual Group Control ○
The energy navigation function allows the air conditioner’s operational energy Visual navigation enables controlling and monitoring the unit on floor plan
- Map view (Visual navigation) ODU Capacity Control ○
usage to be manged monthly, weekly and yearly. By analyzing present energy view for the intuitive management.
Energy Navigation (with PDI) ○
- Time limit control / Auto change over Daylight Saving Time ○
consumption and comparing with the plan, overuse of system operational costs
- Energy monitoring External IO Port DI 2 / DO 2 can be prevented.
BMS Integration 3) BACnet IP / Modbus TCP
- History / Operation trend
IPv6 Support ○
SOLUTIONS
- Interlock with 3rd party equipment
CONTROL
※ ○ : Applied, - : Not Applied
(ACS IO, ACU IO Module is needed) 1) Chiller Option Kit (PCHLLN000) is required
2) It is only available in some products
- Multi level grouping 3) For the detail point list, please refer to the installation manual
- Emergency stop & alarm
- Error alarm by e-mail
- Air quality monitoring
- Air purification function control
CENTRALIZED CONTROL
Overview
IDU
Internet AC Smart 5
...
PC
Multi Level Group Composition Interlocking with 3rd party equipment
User can make frequent and multi level group to control and monitor the device AC Smart 5 can make operation scenario with 3rd party equipment by ACS IO
...
easily. Module. Control coverage is expanded. (Air conditioner only → Sensors, Fans,
Pumps, Switches…)
Smartphone
ERV LG SAC
ODU
OR OR
Tablet Chiller AHU Air Water HYDRO KIT IDUs
ACS IO Option kit AHU Controller AC Smart 5 cooled cooled
3rd party interlocking Chiller AHU Comm. kit 3rd party interlocking
Sensor Facility Sensor Facility
...
Sensor
Screw Invert Scroll
Emergency Lighting Valve Fan Expansion
Control coverage
* Fix Public IP is mandatory. Temp. Lighting
* Router’s Configuration of NAT is mandatory. Open port 80 & 9300. ACS IO
136 / 137
CONTROL SOLUTIONS _ CENTRALIZED CONTROL
SOLUTIONS
- Total Accumulate Power
CONTROL
※ ○ : Applied, - : Not Applied
(ACS IO, ACU IO Module is needed) 1) Chiller Option Kit (PCHLLN000) is required.
※ ○ : Applied, - : Not Applied
2) It is only available in some products.
- Multi level grouping 3) For the detail point list, please refer to the installation manual.
CENTRALIZED CONTROL
CH5 BMS system
CH1 ~ 4 Indoor unit : Max. 64 units (Air conditioner & Ventilation) / Indoor address : 00 ~ FF
Overview Internet ACP 5 IDU
* Master
1)
PC
...
Internet
AC Smart 5
* Slave • MULTI V 5 • MULTI V • MULTI V S • MULTI SPLIT • ERV • AHU (Control Kit)
• MULTI V IV WATER IV • SINGLE SPLIT
Smartphone ... • MULTI V III • MULTI V
Backup operation • MULTI V II WATER II
* Fix Public IP is mandatory. Appropriate PI 485 should be used according to PDB (Product Data Book)
OR OR ERV * Router’s Configuration of NAT is mandatory. Open port 80 & 9300.
Chiller 1) Assignment of public IP address is required to access central controller through internet.
Tablet ACS IO Option kit AHU Controller
Comm. kit
PI 485
Motion Temp. CO2 Cooling Pump Centrifugal Absorption
tower
Etc. PI 485 converts LG air conditioner’s protocol to the RS485 protocol for the central controller.
IPv6
Network PHNFP14A0
HTML5 web design
* Fix Public IP is mandatory. * Router’s Configuration of NAT is mandatory. Open port 80 & 9300.
138 / 139
CONTROL SOLUTIONS _ CENTRALIZED CONTROL
AC MANAGER 5
Multiple ACP and AC Smart integration solution to manage multi sites up to 8,192 units as a single system. Stand-alone
Integrated with S/W program and Hardware platform, it is
Model Name PACM5A000
convenient to install since users no longer need to install
Size (W x H x D, mm) 270 x 155 x 65
program with lock-key on PC.
MULTI V / ERV / ERV DX / HYDRO KIT /
Interfaceable Products
THERMA V / AHU kit / LG Chiller 1)
Maximum number of units 8,192 (supports 32 ACP 5 or AC Smart 5)
Individual / Group Control On & Off / Mode / Temperature / Fan speed
Individual Controller Lock Temperature / Mode / Fan speed / All
Error Check ○ Up to 8,192 Connections for Indoor Units Max. IDU 256 EA
...
...
Temperature Limit ○
• Schedule Operation Time Limit ○
Max. IDU 256 EA
• Map view (Visual Navigation) Visual Navigation ○ ...
• Time limit control / Auto change over Operation Trend ○
• Energy monitoring / Navigation Interlock Control ○
• History / Operation trend Virtual Group Control ○
• Emergency stop & alarm ODU Capacity Control ○ Advanced Network Accessibility & User Friendly GUI (Reddot award)
Energy Navigation (with PDI) ○
• Error alarm by E-mail As an advanced central controller, AC Manager 5 offers flexible
• Multi language ※ ○ : Applied, - : Not Applied
interface for each user by assessing the device screen and
1) Chiller Option Kit (PCHLLN000) is required.
(Eng, Ita, Spa, Por, Rus, Fra, Ger, Tur, Pol, Chi, Kor) Note : AC Manager 5 requires ACP 5 or AC Smart 5.
automatically customizing the layout to provide the most
SOLUTIONS
• Air quality monitoring optimized interface.
CONTROL
• Air purification function control
Overview
AC Manager 5 ACP 5 ODU / IDU & ERV
AHU
PC Comm.kit Energy Navigation & Energy Usage Trend
CENTRALIZED CONTROL
Energy navigation is the function to set the target usage
Internet
amount to limit the monthly power consumption and to
Chiller & AHU
control so that the total accumulated power consumption
Chiller Option kit AHU Controller
does not exceed the target usage amount. It performs
Mobile
total of 7 control levels with the estimated / actual usage
amount exceeding ratio compared to the monthly target
3rd party Device
usage amount. For the control method, there are indoor unit
Compressor Capacity IDU operation IDU operation
operation ratio, outdoor unit capacity control, and indoor Control Ratio Control level
Tablet
ACS IO Module unit operation control.
AC Manager 5
AC Manager 5 Control tower Multi Level Group Composition
ACP 5 ACP 5 AC Smart 5 User can make frequent and multi level group to control and
monitor the device easily.
140 / 141
CONTROL SOLUTIONS _ CENTRALIZED CONTROL
- Applicable for MULTI V 5, MULTI V S, ERV, - Power : DC 12V 5 Reserved Pipe In Temp. 1) Sanitary Tank Temp. -99.0 ~ 99.0 [°C] x 10
THERMA V 6 Reserved Pipe Out Temp. 1) Solar Temp. 2) -99.0 ~ 99.0 [°C] x 10
SOLUTIONS
CONTROL
Modbus Gateway Memory Map Installation Scene
Baud Rate : 9,600 bps, Stop Bit : 1 stop bit, Parity : None Parity, Byte size : 8 bits • Single module
Max. 16 indoor units with a single module
CENTRALIZED CONTROL
Coil Register (0 x 01)
Data Bit Modbus RTU
No. Function Register
Air Conditioner ERV / DX ERV HydroKit & THERMA V
1 Operate (On / Off) Operate (On / Off) Operate (On / Off) 0 : Stop / 1 : Run
2 Auto Swing Aircon Operate (On / Off) Hot Water Mode (On / Off) 0 : Disable / 1 : Enable
3 Filter Alarm Release Filter Alarm Release 1) Reserved 0 : Normal / 1 : Alarm Release BMS
4 Lock Remote Controller Lock Remote Controller Lock Remote Controller 0 : UnLock / 1 : Lock
RS485 (LGAP)
5 Lock Operate Mode Lock Operate Mode 1) Reserved 0 : UnLock / 1 : Lock Register = N x 16 + ①
6 Lock Fan Speed Lock Fan Speed 1) Reserved 0 : UnLock / 1 : Lock (N = Indoor Unit Central Address)
142 / 143
CONTROL SOLUTIONS _ INTEGRATION DEVICE
DEVICE
Model Name PQNUD1S40 PPWRDB000
Size (W x H x D, mm) 270 x 155 x 65
Interfaceable Products Air conditioner, ERV DX
Pulse line
ACS Central controller
SOLUTIONS
CONTROL
220 V~
ACP 5
24 V~
INTEGRATION DEVICE
BUS-A BUS-B AC Smart 5
50kW
Measurement
MENU
AC Manager 5 70kW
SELECT
(00) ~ (03)
160kW [00] [01] [02] [03]
ACP 5 50kW
[10] [11] [12] [13]
[ Slave 1]
[ Master ] [20] [21] [22] [23]
AC Smart5 ACP
Note : 1. Power cable and type could be different from this scene depending on the Outdoor unit’s specification.
2. Measured power consumption could be different between PDI and Watt meter.
3. Applicable Central Controller : ACP 5, ACP Lonworks, AC Smart 5, AC Ez Touch
(Combination : we recommend to connect separated watt meter for Outdoor units to have correct power distribution value.)
144 / 145
CONTROL SOLUTIONS _ INTEGRATION DEVICE
Model Name PEXPMB000 ACU.UIO ACU.UO ACU.UI Module Name PEXPMB300 PEXPMB200 PEXPMB100
PACS4B000 Linkable Products PACS5A000, PACP5A000
PACP4B000
Linkable Products Communication
PACS5A000 2 ch. 1) 1 ch. 1 ch.
PACP5A000 RS-485
Communication RS-485 1 ch. Digital Input - - 3 port
Digital Input 3 port Digital Output 2 port 6 port -
Digital Output 3 port Universal Input 2) 4 port - 6 port
I/O
Universal Input 1) 4 port Analog Output 2 port 4 port
PEXPMB000 Analog Output 4 port PEXPMB300 PEXPMB200 PEXPMB100
Value Spec Min. Max.
Value Spec Min. Max. Analog Input DC (Voltage) 0V 10V
NTC 10k 0.68kΩ 177kΩ Analog Output DC (Voltage) 0V 10V
PT 1000 803kΩ 1,573kΩ Binary Input
Digital Input - -
(Non Voltage)
Analog Input Ni 1000 871.7kΩ 1,675.2kΩ
Digital Output Normal Open - 30VDC, 1A
DC (Voltage) 0V 10V
※ ○ : Applied, - : Not Applied
DC (Current) 0mA 20mA
1) 1ch is reserved for internal communication
Analog Output - 0V 10V 2) The type of UI (Universal Input) is selectable among Digital Input and Analog Input
Binary Input
Features & Benefits
Digital Input - -
(Non Voltage)
• Interlocking with 3rd party equipment LG Central controller can make operation scenario with 3rd party equipment by ACU IO Module.
Digital Output Normal open - 30VAC / 30VDC, 2A
• Applicable devices are expanded. (Air conditioner only → Sensors, Fans, Pumps, Switches …)
※ ○ : Applied, - : Not Applied
1) The type of UI (Universal Input) is selectable among Digital Input and Analog Input
SOLUTIONS
CONTROL
• Interlocking with 3rd party equipment LG Central controller can make operation scenario with 3rd party equipment by ACS IO Module.
• Control coverage is expanded. (Air conditioner only → Sensors, Fans, Pumps, Switches …) CHILLER OPTION KIT
LG central controller 5 series with Chiller Option Kit can provide LG chiller remote control and cycle monitoring.
Key Application
LG Central Control LG SAC
INTEGRATION DEVICE
Model Name PCHLLN000
ODU Evaporator status / Compressor status (Scroll, Screw,
Monitoring Points Centrifugal chiller only) / Condenser status /
Generator status (Abs. chiller only)
On / Off ○
Air cooled Water cooled HYDRO KIT IDUs Target Temp. setting ○
AC Manager 5 ACP 5 Mode Change Scroll chiller only
ACS IO Module
3rd party interlocking Schedule ○
Sensor Facility Interfaceable Products Scroll, Screw, Centrifugal, Absorption (LG Only)
PCHLLN000
※ ○ : Applied, - : Not Applied
146 / 147
CONTROL SOLUTIONS _ INTEGRATION DEVICE
DRY CONTACT
Connection between an indoor unit and external devices to control various functions. PDRYCB000
Model Name PDRYCB000 PDRYCB400 PDRYCB300 PDRYCB320 PDRYCB500 Contact Point Input
CN - CC Dry contact
Operation On / Off
Indoor Unit (Contact point linked with 3rd party)
NEW Status
PCB
Error Alarm
CN - CC
SOLUTIONS
CONTROL
Energy Saving - (Select & Fix) - - - Refrigerant leakage detection alarm
DHW On / Off - - ○ ○ -
Control
INTEGRATION DEVICE
Thermo-Off - - ○ ○ - Card key Leakage Detector
AWHP
Oper Mode - - ○ ○ -
Fan Speed - - - - ○
※ Please contact our regional office to have full compatible room controller list
Operation Status ○ ○ ○ ○ ○
Output Error ○ ○ ○ ○ ○
PDRYCB500 <Modbus Communication Function>
Room Temp. - - - - ○
...
- AWHP : 3 series split and monobloc models.
...
2. Compatibility of PDRYCB400 Max. 16 Indoor units per one
- Can use with all types of aircon indoor units after 2010. (Cassette, Ducted, Convertible, Applied PAC, Wall mounted, Console) Modbus master controller
- Can not use with single package models. One to one connection between
- Can not use with AWHP, Hydrokit models. dry contact and indoor unit
3. (Select & Fix) : This function is preset by rotary switch.
CN-CC
Indoor Unit
※ Please contact our regional office to check the compatibility with 3rd party room controller.
148 / 149
CONTROL SOLUTIONS _ INTEGRATION DEVICE
Note : 1 Y type Cable assembly is for connecting indoor unit and long cable.
2 Long Cable assembly is for connecting indoor to indoor.
Key Application Models Applied
• LG indoor units excluding Wall-Mounted Type
Extension cable
SOLUTIONS
CONTROL
Control
box
INTEGRATION DEVICE
Sensor for detecting the room temperature.
Wired Remote
Controller
Low Profile
Button Sensor
PQRSTA0
Main PCB 22.2mm
150 / 151
CONTROL SOLUTIONS _ INTEGRATION DEVICE
SOLUTIONS
CONTROL
Key Application
Wiring Diagram Demand Control Low Noise Operation
Provides variable setting for demand control according to input method to To reduce noise level, control outdoor unit’s fan speed by dry contact input.
reduce power consumption. This function supports 2 types of input signal : AI
(0 ~ 10V, 10 Step) and contact signal (3 Step).
INTEGRATION DEVICE
Ceiling Concealed Duct
Max. 7 dB
1
(dB)
2
3 DDC DDC
CN - ZONE 4 IO Module (Direct Digital Controller) IO Module (Direct Digital Controller) Timer
5
6 Capacity
7 Control with Noise Level or
8 MULTI V WATER IV
or
Contact Signal
(3 Points / 3 Steps) Contact Signal
AC 24V
Range of Operation Rate
ROOM (External) Damper AI 0 ~ 10V : 0%, 40% ~ 100%
THERMOSTAT #1 Or Relay Contact signal (3 steps) : 0%, 40% ~ 80%
MULTI V 5
Zone controller MULTI V 5 ※ 8 HP (22.4kW) model, Sound power level can be changed by outdoor unit operation
ROOM Damper status and low noise operation input signal.
THERMOSTAT #2 Or Relay
Gas Pipe
IO Module
3. Operation Stop 1. Sense the Gas
MULTI V 5
Alarm
Gas Gas
Sensor Sensor
Refrigerant
152 / 153
CONTROL SOLUTIONS _ INTEGRATION DEVICE
PRLK594A0
SOLUTIONS
CONTROL
Specifications
Control Application Kit
Dimensions (mm) IP
Type Model Power Supply Description
W H D Rating
Return / Room air temperature control by DDC or LG
INTEGRATION DEVICE
PAHCMR000 300 300 155 1Ø, 220~240 V, 50/60 Hz IP66
Communication individual / centralized controller.
Kit Discharge air / Supply air temperature control by DDC
Models Applied PAHCMS000 380 300 155 1Ø, 220~240 V, 50/60 Hz IP66
or LG individual / centralized controller
• MULTI V 5 • MULTI V WATER II • MULTI V WATER IV PAHCMM000 162 90 61 DC 12V IP20 Main Controller module
Controller
• MULTI V IV • MULTI V S Module
PAHCMC000 108 90 61 DC 12V IP20 Communication Controller module
• MULTI V WATER S • MUL TI V PLUS II, MULTI V PLUS
Various AHU control functions with multiple DX coils
Control Kit PAHCNM000 500 500 210 1Ø, 220~240 V, 50/60 Hz
(Maximum connectable ODU is 3 units)
154 / 155
CONTROL SOLUTIONS _ INTEGRATION DEVICE
AHU KITS
Communication Kit Single Split Application (Communication Kit & Controller Module)
HIGH ENERGY EFFICIENCY Single Split + Return / Room Air Temperature Control
LG's DX AHU solutions' superior performance provides
a highly efficient heat source system. Temp. Sensors
Comm. Line
Central Comm. Line to ODU
• High energy efficiency inverter system Ref. Pipe
• Large range of expansion application Kit AHU MULTI V 5
TE = Evaporator Temperature
: Max. 168 kW EEV Kit 1) (Liquid Pipe / Gas Pipe)
• Connected to various heat sources TR = Return Air Temperature
TROOM = Room Air Temperature
: MULTI V, MULTI V WATER IV, MULTI V S, SINGLE SPLIT Control Option
TE
1) Maximum connectable EEV capacity for PAHCMR000, PAHCMC000 is 112 kW.
SINGLE SPLIT
MULTI V WATER IV MULTI V S SINGLE SPLIT Centralized Controller 1)
AHU DX Coil
TR
OR / AND
DIVERSE OPTIONS FOR CONTROL
AHU communication kit can be connected to various LG Controller DDC by Contact signal DDC by Modbus ROOM
control systems such as LG individual / central
controller and DDC 1). It can be directly connected to
DDC without separated controller, so DDC can receive TROOM PAHCMR000
DDC
Central Individual (Modbus or Contact signal)
product control and monitor information through Controller Controller DDC DDC
SOLUTIONS
contact signal or Modbus protocol.
CONTROL
AI / DI / DO
signal
• LG Individual / Central controller supported
- LG controller stand alone or combination with DDC Single Split + Discharge Air Temperature Control
• Direct wiring between DDC and AHU communication kit
- Embedded Digital I/O and Analog Input Temp. Sensors
- Modbus RTU protocol supported Comm. Line
INTEGRATION DEVICE
AHU Kit AHU Kit AHU Kit
Central Comm. Line to ODU
1) DDC : Direct Digital Controller
Ref. Pipe
TE = Evaporator Temperature
(Liquid Pipe / Gas Pipe)
TD = Discharge Air Temperature
TROOM = Room Air Temperature
TROOM PAHCMS000
DDC
(Modbus or Contact signal 2))
156 / 157
CONTROL SOLUTIONS _ INTEGRATION DEVICE
AHU KITS
MULTI V Application (Communication Kit & Controller Module)
MULTI V + EEV Kit + IDU + Return / Room Air Temperature Control MULTI V + EEV Kit + Discharge Air Temperature Control
Control Option
TE
Control Option
MULTI V
Centralized Controller TE
AHU DX Coil
TD Centralized Controller
AHU DX Coil
SOLUTIONS
TR
CONTROL
OR / AND
OR / AND
ROOM
ROOM
INTEGRATION DEVICE
TROOM PAHCMR000
DDC
(Modbus or Contact signal)
OR
TROOM PAHCMS000
DDC
OR (Modbus or Contact signal 2))
PAHCMC000 +
PAHCMM000 PAHCMC000
1) Multiple EEV kits can be applicable with multiple DX Coils and PAHCMR000s. 1) Multiple EEV kits can be applicable with multiple DX Coils and PAHCMR000s.
2) In case of applying DDC with contact signal, discharge air temperature should be measured and controlled by DDC. 2) In case of applying DDC with contact signal, discharge air temperature should be measured and controlled by DDC.
Note : For more detail, please refer to the PDB. Note : For more detail, please refer to the PDB.
158 / 159
CONTROL SOLUTIONS _ INTEGRATION DEVICE
AHU KITS
Communication Kit Function Communication Kit Function
Communication with DDC via Contact Signal With LG Control system (Individual & Centralized Controller)
PAHCMS000 PAHCMS000
PAHCMR000 PAHCMR000
Function List (PAHCMM000 + Type Note Function List (PAHCMM000 Note
(PAHCMC000) (PAHCMC000)
PAHCMC000) +PAHCMC000)
Operation On / Off On / Off On / Off Digital Input (Non Voltage) - Operation On/Off On / Off On / Off -
Available operation mode can vary depending on Available operation mode can vary depending on
Operation Mode Cooling / Heating Cooling / Heating Digital Input (Non Voltage) Operation Mode Cooling / Heating / Fan Cooling / Heating / Fan
the settings of Communication Kit the settings of Communication Kit
Return (Room) Air Temperature 2) 16 ~ 30 °C - Analog Input (DC 0 ~ 10 V / 20mA) - Return (Room) Air Temperature 2) 16 ~ 30 °C - -
Control 1)
Discharge air temperature should be controller Standard II : 16 ~ 30 °C
Control 1) Discharge Air Temperature 2) - - -
directly by DDC using 'ODU Capacity Control Discharge Air Temperature 2) - 12 ~ 50 °C Standard III : 12 ~ 50 °C
Central Controllers : 12 ~ 50 °C
Fan Speed 3) - High / Middle / Low Digital Input (Non Voltage) -
To control the AHU fan, dip switch 1-3 'DO type' should be
Forced Thermal On / Off - Digital Input (Non Voltage) - Fan Speed 3) High / Mid / Low High / Mid / Low
set 'On (Fan Speed)' (PAHCMR000)
ODU Capacity - 40 ~ 100% Analog Input (DC 0 ~ 10 V / 20mA) -
Operation On / Off On / Off -
Emergency Stop - Stop / Normal Digital Input (Non Voltage) -
Operation Mode Cooling / Heating / Fan Cooling / Heating / Fan -
Digital Output For PACHMR000, dip sw1-3 DO Type should be ○ ○
Return (Room) Air Temperature -
Operation On / Off On / Off (Max. : DC 30 V / 1 A, set 'Off' (Status), In this case, 'fan speed' cannot
AC 250V / 1 A ) monitored by DO ports Discharge Air Temperature ○ -
Monitor
Operation Mode - - It needs to be checked through control signal Fan Speed High / Middle / Low High / Middle / Low -
Digital Output For PACHMR000, dip sw1-3 DO Type should be Defrost Operation On / Off On / Off Only with Individual Controller
Fan Speed High / Middle / Low High / Middle / Low (Max : DC 30 V / 1 A, set 'On' (Fan Mode) In this case, ‘On/Off, defrost,
AC 250V / 1 A ) error Status' cannot monitored by DO ports Error Alarm Error Code Error Code Error code will be displayed on the screen
Digital Output For PACHMR000, dip sw1-3 DO Type should be Compressor On/Off On / Off On / Off Only with Individual Controller
Monitor
Defrost Operation Defrost / Normal Defrost / Normal (Max. : DC 30 V / 1 A, set ‘Off' (Status), In this case, 'fan speed' cannot
AC 250V / 1 A ) monitored by DO ports ※ ○ : Applied, - : Not Applied
1) Control functions for LG individual and central controller are not available in case of using together with DDC via contact signal.
Digital Output, Relay C contact For PACHMR000, dip sw1-3 DO Type should be 2) The range of setting temperature is different depending on the type of the controllers. And operation may different from setting range.
Error Alarm Error / Normal Error / Normal (Max. : DC 30 V / 1 A, set 'Off' (Status), In this case, 'fan speed' cannot 3) To control fan speeds, DO port of the fan speed status should be connected to the fan control panel.
AC 250V / 1 A ) monitored by DO ports Note : For more detail information, please refer to the product data book.
Digital Output,
Compressor On / Off - On / Off (Max. : DC 30 V / 1 A, -
SOLUTIONS
AC 250V / 1 A )
CONTROL
1) Control functions for LG individual and central controller are not available in case of using together with DDC via contact signal.
2) The range of temp. is differ depending on the type of the controller. Compatibility with LG HVAC Controllers
3) To control fan speeds, DO port of the fan speed status should be connected to the fan control panel.
Note : For more detail information, please refer to the product data book. BMS
Individual Controller Centralized Controller PDI
Gateway
AC Premium
Premium Standard III Standard II AC Ez AC Ez Touch AC Smart 5 ACP 5 Manager 5 1) ACP Lonworks Standard
Controller
INTEGRATION DEVICE
Communication with DDC via Modbus protocol
PAHCMS000
PAHCMR000
Function List (PAHCMM000 Note
(PAHCMC000) +PAHCMC000)
PREMTA000
Operation On/Off On / Off On / Off PREMTB100 PQNUD1S40
Model no. PREMTA000A PREMTB001 PQCSZ250S0 PACEZA000 PACS5A000 PACP5A000 PACM5A000 PLNWKB000
PREMTBB10 PPWRDB000
Operation Mode Cooling / Heating / Fan Cooling / Heating / Fan PREMTA000B
Return (Room) Air Temperature 16 ~ 30 °C - PAHCMR000 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
Discharge Air Temperature 2) - 12 ~ 50 °C Dip SW1-2 Discharge Temp. Control Type should be set 'On' PAHCMS000 - ○ ○ - - ○ ○ ○ - -
Control 1)
Fan Speed 3) High / Middle / Low -
※ ○ : Applied, - : Not Applied
Forced Thermal On/Off - - 1) AC Manager 5 is an integrator, so the installation with AC Smart 5 or ACP 5 is required.
ODU Capacity Control 2) - 40 ~ 100% Dip SW1-2 Discharge Temp. Control Type should be set 'On' Note : 1. Dry contact for indoor unit (PDRYCB000 / 400 / 300 / 500) is not applied.
2. For more details, please refer to the product data book.
Emergency Stop - -
Operation On / Off On / Off
Operation Mode Cooling / Heating / Fan Cooling / Heating / Fan
Return (Room) Air Temperature ○ - Corresponding air temperature sensor connected to AHU
Discharge Air Temperature - ○ Comm. Kit is required
Monitor
Fan Speed High / Middle / Low High / Middle / Low
Defrost Operation Defrost/Normal Defrost/Normal
Error Alarm Error / Normal, Error code Error / Normal, Error code
Compressor On / Off On / Off On / Off
160 / 161
CONTROL SOLUTIONS _ APPLICATION
Lobby Atrium
Integrated management of AHU applied
Air conditioner control in conjunction
to large spaces
with check-in or check out AC Smart 5 Comm. Kit
(Schedule)
SOLUTIONS
of the public areas
CONTROL
AC Smart 5
(Schedule)
APPLICATION
The air conditioner Integrated control of Control with existing Guest safety is Air conditioner control Proportionally distribute Fast problem detection Reduces energy Integrated Chiller and VRF
automatically turns off air conditioner with the hotel thermostat the first priority in conjunction with and manage power and alarms by checking management of AHU integrated control
when guests leave hotel room controller check-in or check out consumption by the tenant operational trends applied to large spaces
WHM
(Watt-Hour Meter) Chiller option
Error C store
Pulse signal kit (S/W)
Over
24°C Cooling
21°C
ACP 5
Power PDI
100 kWh
162 / 163
CONTROL SOLUTIONS _ APPLICATION
Lecture Hall
Control fan speed and air volume
Dry contact
Schedule management according to
academic plan Central controller
(Schedule)
Service Zone
Energy savings based on flexible Maintenance Office
scheduling Central controller Integrated management of distributed
(Schedule)
buildings Central controller
(Multiple management)
Lobby
Centralized management of AHU for Centralized management with multiple
large spaces interfaces Central controller
(HTML5)
Comm. Kit
SOLUTIONS
CONTROL
Design Proposal Design Proposal
Hospital Ward Service Zone Lobby Class Room Lecture Hall Maintenance Office
APPLICATION
Proper airflow Monitor the comfort level External device Energy savings based on Centralized management Automatically save Central controls Schedule management Integrated management Centralized management
management for patients for each hospital ward interlock control flexible scheduling of AHU for large space energy in the absence prevent students from according to academic plan of distributed buildings with multiple interfaces
of students arbitrary control
Relay
• 4.3 inch color LCD • BMS Integration • BMS Integration • Discharge air • 4.3 inch color LCD
• Touch button (BACnet IP, Modbus TCP) (BACnet IP, Modbus TCP) • Touch button
164 / 165
CONTROL SOLUTIONS _ APPLICATION
OFFICE RESIDENTIAL
Office Control Solution Residential Control Solution
Maintenance 0ffice
Energy savings and management
throughout the building Central controller
Home
(Energy Navi.)
Anytime, anywhere air conditioner
control and access
Integrated management of HVAC with Wi-Fi Modem
SOLUTIONS
detection
CONTROL
Wired remote
controller
APPLICATION
Energy savings Integrated Reduce costs by Reasonable power Main equipment Energy savings Control your home air Build a Smart house Use a familiar residential Simple interlocking Stable system
and management management of HVAC replacing BMS distribution to tenants 24 hours back up based on occupancy conditioner anytime, thermostat control by remote control operation when indoor
throughout the building with BMS system management detection anywhere unit power is lost
WHM Human
BMS Protocol Pump Lighting Fan Sensor (Watt-Hour Meter) detection
Pulse signal sensor
Power PDI A B
Fan
BMS System 100 kWh
Forecasting
Radiator
PACS5A000 PLNWKB000 PEXPMB000 PPWRDB000 PACS5A000 PTVSMA0 PWFMDD200 PDRYCB500 PDRYCB300 PREMTB100 PRIP0
AC Smart 5 LonWorks gateway ACS IO Module PDI Standard (2 port) AC Smart 5 Human detection sensor LG Wi-Fi modem Modbus RTU (9,600bps) NEW PDRYCB320 Wired remote controller Independent power module
8 contact point
• BMS Integration • Max. 128 IDU • BMS Integration Function Function • 4.3 inch color LCD • EEV full close function
(BACnet IP, Modbus TCP) (BACnet IP, Modbus TCP) • On / Off • Operation Input • Touch button
• Fan speed • Indoor temperature • Universal Input
• Operation mode • Error alarm • Operation On / Off
• Vane control • Set operation mode • Thermo On / Off
• Reservation • Set temperature • Operation mode
(Sleep, Weekly On / Off) • Set fan speed (Fan / Heat / Cool)
• Error check • Fan speed
PACP5A000 PMBUSB00A PEXPM300 PQNUD1S40 PACP5A000 PREMTB100 (Low / Middle / High)
ACP 5 Modbus RTU gateway PEXPM200 PDI Premium (8 port) ACP 5 Wired remote controller
PEXPM100 Output
• BMS Integration • Max. 128 IDU • BMS Integration • 4.3 inch color LCD • Operation On / Off status
ACU IO Module
(BACnet IP, Modbus TCP) (BACnet IP, Modbus TCP) • Touch button • Error alarm
166 / 167
ACCESSORIES
MECHANICAL ACCESSORIES
PIPING ACCESSORIES
ACCESSORIES
168 / 169
ACCESSORIES _ MECHANICAL ACCESSORIES
Specification
PT-QCHW0 PT-MCGW0 PT-MPGW0 PT-USC Suction Color Weight Dimension (mm)
Model Gloss
Type (RAL) (kg) W H D
Grid White (RAL 9003) - 7.1 950 35 950
PT-AAGW0
PT-AEGW0 Grid White (RAL 9003) - 8.5 950 35 950
PT-AFGW0
Grid White (RAL 9003) - 7.5 950 35 950
• Independent vane operation uses separate motors, making it Possible to control all 1, 2, and 4 vanes independently. Model Image Model name
• The detachable corner design makes it easy to adjust the hanger during installation and to check for leakages in the drain
pipe and refrigerant pipes. Cassette cover installation manual
* Air purifying panel can be used with air purifying kit together for 1 Way, 4 Way panel. Follow the details to install the external cover correctly.
* Human detecting sensor can be used with human detecting sensor for 4 Way panel. Air purification kit • Read the installation manual carefully before installing the cover.PTAHMP0 ○ ○ ○
• To prevent the exterior of the cover from being scratched or become dirty during the
ACCESSORIES
assembly, always put a clean sheet on the floor.
• Always use the screw included in the product. This product is composed of the following components.
(If you use other screws, it can damage the product.)
Compact and Stylish Design The purpose of this external cover is to prevent the
indoor unit from being exposed externally.
• New 4 Way cassette panel adapted unibody shape and matching with into the ceiling. Ceiling Ceiling
8mm
TM model TN model Follow the details to install the external cover correctly.
Indoor unit
266mm
• Read the installation manual carefully before installing the cover.
• To prevent the exterior of the cover from being scratched or become dirty during the
assembly, always put a clean sheet on the floor.
• Always use the screw included in the product. This product is composed of the followin
MECHANICAL ACCESSORIES
TP model (If you use other screws, it can damage the product.)
Unibody
Shape Cassette cover
Cover in case of exposed cassette installation. installation manual
The characteristics of this external cover are as follows.
The purpose of this external cover is to prevent the
1. The height of the cover can be adjusted according to the height of the product.
Cassette
Cassette Thecover cover
purpose installation
of thisinstallation
external cover manual
ismanual
Applied Products
Detach function
to prevent the
TM model
Ceiling
TN model
Cassette
Cassette • Usecover cover
this when install installation
installation
the cassette manual
air conditioner on manual
the ceiling
4 Way Cassette (for chassis TP, TN, TM, TQ, TR)
without any finishing. Indoor unit
266mm
Key Features • Read the installation manual carefully before installing the cover.
Follow
• Read the installation manual carefully before installing
• To prevent the exterior of the cover from 8mm
Follow
assembly,the
• To prevent the
details details
the exteriortosheet to
ofinstall
the
on thethe
cover
the cover.
Ceiling
being scratched or become dirty during the
install thescratched
external cover
floor. external cover correctly.
from being or become dirtycorrectly.
during the
8mm
TPCeiling
model
during
the the (Refer toTN
Indoor unit
This This
1. The height of the
product
topmodel
picture)
is composed
cover product is according
can be adjusted composed of the offollowing
the
to the height
components.
of thefollowing
product. components.
assembly,
(If you use other screws, it can damage the product.)
assembly,
always always put asheet
put a clean cleanon sheet on the floor.
the floor.
TM model
• Cover A, Cover B • Screws
• Covers the side area of cassette • Always
use theuse theincluded
screw included in the product. Ceiling This This product is composed
2. Cover on the piping side can be detached.
product is composed of the offollowing
the following components.
components.
Dimension (mm) Applied Model Capacity (kW)* The
• Always
purpose
(If youThe
of
screw
purpose this
it of
external
in the product.
can this
it canexternal cover is to is
cover prevent
to prevent the the
Suction Color (If you
use usescrews,
other other screws, damage damage the product.)
the product.) • Cover C, Cover D • Installation Manual
Gloss Weight
50mm
Model Type (RAL) (kg) W H D
Single Split MULTI Split MULTI V • Gives elegantindoor
looks unit from
indoor unit from beingbeingexposed exposed externally.
externally.
Indoor unit
266mm
Detach function
Detach function
ACCESSORIES _ MECHANICAL ACCESSORIES
LZ-H100GXN0 / LZ-H050GXH0 refrigerant concentration exceeds 6,000ppm. Rated Voltage (V) DC 5.0 5%
Dimensions (W x H x D, mm) 31 x 44 x 20
LZ-H080GXH0 / LZ-H100GXH0 (The green and red LED lights blink simultaneously.) Weight (g) 22
• Alarm is “on” when refrigerant leaks out more than Detectable Refrigerant R410A
Sensor
6,000ppm for 5 seconds. If it is reduced less than Detected Concentration (ppm) 0 / 6,000 Alarm Off / On
Key Features 6,000ppm for 5 seconds, alarm is “off”.
Operating Temperature Range (°C) -10 ~ 50
Preserved Temperature Range (°C) -40 ~ 60
Specification Dimensions (Unit : mm) • When the alarm of the refrigerant leak detector is switched Average Power Consumption (mA) 35
Connecting
• Applied Model : ERV (Embedded), ERV DX (Option) 69 26.4 on the user must ventilate the room until the alarm is Cable Cable Length (m) 10
Sensor Dimensions of Front Plate (W x H x D, mm) 80 x 110 x 44.6
• Supply voltage : DV12V 5% disabled. Protective
Cover Dimension of Back Plate (W x H x D, mm) 80 x 110 x 6.5
• Output : 0.6 ~ 4.4V (Linear output, 240 ~ 1,760 ppm CO2) • The detector has to be installed inside the room and it
※ This function available for ARU****L**5 and 4 (MULTI V 5, MULTI V IV H/P, H/R model)
• Accuracy : 10% (2 days after installation)
50
Key Application
ACCESSORIES
CO2 (ppm)
MECHANICAL ACCESSORIES
Embedded inside of ERV With ERV
1,000 Refrigerant Leakage Detector has three application methods.
Standard III Wired
Remote Controller 0
ERV with CO2 Concentration Control Case 1) Case 2) Case 3)
Time (min) Stop Operating Main Pipe Closing & Branch Pipe Closing &
(System Termination) Pump Down Continuous Operating
How to Install
1. Remove a screw on the service cover. Pull the service cover fixing bracket(①), then remove the service cover(②). Remove two elements(③) and two air filters(④). Room 1 Room 2 Room 1 Room 2 Room 1 Room 2
※ Airflow can be controlled by concentration of CO2, after setting automatic operation mode at remote controller.
※ Use the screwdriver whose total length is less than 250mm. Accessory Specification (To realize the case 2 application)
172 / 173
ACCESSORIES _ MECHANICAL ACCESSORIES
Applied Products
Applied Products
Indoor Unit Model Chassis Applicable
1 Way Cassette TU ○ MULTI V Indoors (Ceiling Concealed Duct, Floor Standing Units)
TT N/A
2 Way Cassette
TS ○ (~5.6kW)
TR ○
Cassette
TQ ○ (~4.5kW)
Key Features 4 Way Cassette TP N/A Key Features
TN N/A
• Decreasing noise level of MULTI V Indoor units and easy TM - • Designed for wireless control.
installation. BG - • Indication lamps (3 colors) and Self-diagnosis function.
High Sensible BR -
B8 -
High Static B8 -
M1 ○ (~5.6kW)
Duct
Middle Static M2
M3
-
-
Key Application
L1 ○
Low Static L2 -
Note : Do not install both the IR Receiver and Wired Remote Controller. This may cause malfunctions.
L3 -
CE ○
Floor Standing
CF -
Convertible VE ○
V1 -
Ceiling Suspended
V2 -
SJ ○
Etc
Wall Mounted SK ○
SV -
Art Cool SF ○
Console QA ○ Wired Remote
K2 - Controller IR Receiver
HYDRO KIT
K3 -
※ ○ : Applied, - : Not applied, N/A : Not Applicable
Key Application
ACCESSORIES
Wireless Remote
Pipe EEV Kit can be applied for the space which requires quiet Controller
Wire environment and noise sensitive space. (Standard)
Refrigerant flow (Cooling)
Refrigerant flow (Heating)
Outdoor Unit
Operation of Indication Lamps Test Run Mode
① Emergency Operation button : After installing the product, you must run a
C / Box EEV
Turns the indoor unit on or off when Test Run mode. Press the Emergency Operation
MECHANICAL ACCESSORIES
Kit
remote controller is not working. button for 5 seconds, until the LED flickers.
Luxury Hotel Villa ② Signal Detector : Then the indoor unit, duct runs cooling mode
Indoor Unit Receives the signal from remote controller. for 18 minutes, where the setting temperature is
③ Timer lamp (Green) : 18°C and the fan speed is high.
Lights up during the timer operation.
Indoor Unit EEV Kit Outdoor Unit
Indoor Heat Exchanger
④ Hotstart lamp (Orange) :
Electronic
Expansion Valve
Lights up during the pre-heating operation,
Fan M
defrost operation as well as latent heat
COMP 6 5 removal operation in heat mode. Available
M Fan Executive office Meeting room
Heat Exchanger
4 3 only for the heat pump models, not cooling
Note : If you don’t use EEV of same specification, Cooling (Heating) capacity could be decreased. only models.
2 1
⑤ System On / Off lamp (Red) :
Lights up during system controller
Signal Receiver operation.
⑥ Filter Sign lamp (Green) :
How to Install Lights up after 2,400 hours from the time
of first power on operation.
Open Indoor unit’s control box cover.
① Open fully indoor unit’s EEV through vacuum mode of ODU setting. Indoor Unit
② Detach the Indoor unit’s EEV connector from PCB and then push the reset C/Box
button of Outdoor unit’s PCB.
③ After connecting indoor unit’s EEV CONNECTOR, repeat the process Existing
① & ②. Then, connect the EEV CONNECTOR of EEV KIT in PCB of indoor unit. EEV
④ Finally connect the lead wire of the EEV Kit to the indoor unit’s PCB. KIT
EEV
⑤ Assemble the control box cover.
CN-EEV
174 / 175
ACCESSORIES _ MECHANICAL ACCESSORIES
Model Name
Key Features PRARH1
• Independent Power Module is specially designed to close the Indoor EEV when power cut-off.
- Supply Voltage : DC 12V 50% Key Features Applied Products
- Provides two stages of auxiliary heat for indoor unit. 1, 2, 4 Way Ceiling Cassette, High Static Ducted,
- Provides ability to use the two stage auxiliary heater as Low Static Ducted, Ceiling Suspended
IncludedIncluded
Items
Included
ItemsItems
the primary or secondary heating source.
Included Parts Key Application
Model PRIP0 (Others) If the EEV is opened due to power cut off, liquid refrigerant
2. Included
2. 2.
IncludedItems
Included
Included Items
Items
Parts
Included Items
Key Application
Electrical Wiring
2. Included Items
ENGLISH
ENGLISH
ENGLISH
• Harness 1 (1m)
Item
Independent
Screw
Clamp
• Harness 2 (1m)
flows into compressor. It could damage the compressor in Model ModelModel Model PRARH1 PRARH1
PRARH1
PRARH1 3 rdParty Scope
3 rd
Party Scope
(Tie Wrap)
ENGLISH
Power Kit cooling mode. Also condensing might be happened for unclosed
• Harness 3 (1m) PRARH1
Item Auxliary
Item Heater
Item Auxliary Relay
Auxliary
Model
Heater
Item Kit
Heater
Relay Kit Screw
Relay
Auxiliary Kit ScrewScrew
Heater Insulation
Screw InsulationInstallation
Insulation
Insulation Manual
Installation
Installation
Installation ManualManual
Q'ty 1 2 4 • Installation Manual EEV’s indoor unit due to flow of refrigerant. Q·ty Q · t y 1 Item 1
Relay Kit
Auxliary Heater 2
Relay Kit 2 2
Screw 2
Insulation
Manual
1Installation 1
• Insulation (PE) Q·ty 1 2 2 1 Manual RADIATOR
RADIATOR
Q·ty
Q'ty 11 2 2 2 2 1 1
IncludedIncluded Items Items
ItemsIncluded
Electricity Cut-off EEV Valve
Hot Water
2. Included Items
Close Hot Water
2. Included
2. Included
Figure FigureFigure
Items Items
Figure
Figure Included Items
Figure
ENGLISH
External Power supply
ENGLISH
ENGLISH
2. Included Items
- Supply voltage : AC 24V
M4 x10
• PRARH1 applies to High Static Duct, Low Static Duct, 1Way CST, 2Way CST, 4Way CST and Ceiling
PRARS1 PRARS1
ENGLISH
Model ModelModel PRARS1
ACCESSORIES
Suspended types.
Model PRARS1 LG Scope
LG Scope
• PRARH1 applies
• PRARH1 to
• PRARH1 High
applies Static
applies
to High Duct,
to HighLow
Static Static
Static
Duct, LowDuct,
Duct, Low1Way
Static Duct,CST,
Static 2Way
Duct,
1Way CST,CST,
1Way CST,4Way
2Way CST,CST
2Way CST,
4Way and Ceiling
4Way
CST CSTCeiling
and and Ceiling
Item
Item Suspended
Suspended Item
Auxliary
types. Auxliary
SuspendedHeater Heater
Auxliary
Relay Kit
Model
types.
types. Item Relay
Heater Kit
Relay
Auxliary Kit
Heater
Screw Screw PRARS1
Screw Insulation
Insulation
Screw Installation
Installation
Insulation
Installation
Insulation Manual Manual
Installation Manual Indoor Unit
Indoor Unit
(Unit : inch)
(Unit : (Unit
inch) : inch)
CN_PTC
DC12V
DC12V
A
2-19/32
MECHANICAL ACCESSORIES
B
CN_PTC1
A
DUCT / FS / CVT / FAU CST / Console / HYDRO KIT Gen2 Wall Mounted / ARTCOOL Gen4 Wall Mounted ① Turn the power off using circuit breaker.
B
② Disconnect the EEV cable of the indoor unit's PCB
CN_WRITE or CN1
CN_WRITE or CN1
2-19/32
2-19/32
③ Connect the independent power module (CN-EEV/
2-19/32
• PRARS1
• PRARS1 applies applies
• PRARS1
to to Walltomounted
Wallapplies
mounted Wall
and Art and Art
mounted
cool cool
and
types.Arttypes.
cool types. 7-9/32
CN_EEV
CN_EEV CN_EEV LOAD) to the indoor unitʼs EEV, using harness 1.
How to Install (Unit : inch)
CN_WRITE or CN1
3-13/32
7-9/32 14 Auxiliary Heater Relay Kit
7-9/32 7-9/32
2-19/32
CN_EEV / LOAD
2-7/32
CN_EEV / LOAD
CN_EEV / LOAD CN_EEV / LOAD
2 3/16
Harness 1 1-13/32 1-13/321-13/32 6-23/32 6-23/326-23/32
1-7/16
Harness 1 Harness 1 Harness 1
* FS : Floor Standing Aux heater
Aux heater communication
* CVT : Convertible communication lines Aux heater communication lines lines
To Indoor unit’s EEV
* FAU : Fresh Air Intake Unit
2 3/16
To Indoor unit’s EEV
2 3/16
To Indoor unit’s EEV To Indoor unit’s EEV
* CST : Cassette 2 3/16
High Static Ducted 7 Low
9/32 Static Ducted Ceiling Suspended Wall Mounted
1 13/32 6 23/32
3-13/32
3-13/32
3-13/32
2-19/32
2-19/32
2-19/32
2-7/32
2-7/32
2-7/32
Aux heater Installation Manual 5
1-7/16
1-7/16
1-7/16
communication
lines
7 9/32 7 9/32
3 13/32
7 9/32
3 13/32
3 13/32
2 7/32
Installation
2 7/32
Installation Manual 5
1 7/16
1 7/16
1 7/16
Installation Manual 5
176 / 177
ACCESSORIES _ PIPING ACCESSORIES
HEAT RECOVERY
Applied Products
MULTI V 5
MULTI V IV
MULTI V WATER IV
ACCESSORIES
Power Supply Ø, V, Hz
Considering the direction for Indoor 1, 220, 60 1, 220, 60 1, 220, 60 1, 220, 60 1, 220, 60
64 kBtu / Port units and SVC port, connection for
reverse direction makes much easier
PIPING ACCESSORIES
(Unit : mm)
Reduce Noise
Model Liquid High Pressure Low Pressure
dB(A)
46 dB(A) Indoor Unit Reducer
13 dB(A)
33 dB(A)
PRHR023
HR Unit Reducer
Conventional New
178 / 179
ACCESSORIES _ PIPING ACCESSORIES
ARBL057
(7 Branch)
Key Application
Heat Pump System
ARBL104
(4 Branch)
ACCESSORIES
Y Branch for Header for
Indoor Units (2 Pipes) Indoor Units (2 Pipes)
ARBL107
(7 Branch)
Y Branch for Heat Pump
Outdoor Units (2 Pipes)
PIPING ACCESSORIES
Heat Recovery System
ARBL1010
(10 Branch)
Y Branch for
Heat Recovery Units (3 Pipes)
HR Unit
ARBL2010
Y Branch for Heat Recovery (10 Branch)
Outdoor Units (3 Pipes)
Y Branch for
Zoning Control (2 Pipes)
HR Unit
180 / 181
ACCESSORIES _ PIPING ACCESSORIES
PIPING ACCESSORIES
Y Branch pipe for connection of outdoor units.
Specification Specification
Heat Pump Heat Recovery
R410A MULTI V 5, MULTI V IV, MULTI V III, MULTI V WATER IV, MULTI V WATER II R410A MULTI V 5, MULTI V IV Heat Recovery, MULTI V III Heat Recovery, MULTI V WATER IV Heat Recovery,
MULTI V WATER II Heat Recovery
(Unit : mm) (Unit : mm)
LiquidI.D.Pipe
O.D.15.88 19.05 High Pressure Gas Pipe
O.D. 22.2 I.D. 19.05
LiquidI.D.Pipe
O.D.15.88 19.05 Low Pressure GasPressure
High
I.D.22.2 O.D. 28.58 I.D.34.9
Pipe Gas Pipe
O.D. 22.2 I.D. 19.05
LiquidI.D.Pipe
O.D.15.88 19.05 High Pressure Low
I.D.22.2O.D.
O.D.22.2
Gas
Pressure Pipe Gas Pipe
28.58I.D.I.D.34.9
19.05
LiquidI.D.Pipe
O.D.15.88 19.05 High Pressure Low
Gas
O.D. 22.2O.D.I.D.
I.D.22.2
Pressure
Pipe
19.05I.D.34.9
28.58
Gas Pipe
331
314 416
331
314
Low
416 Pressure Gas Pipe
416
Liquid 331 Pipe
314
High Pressure Low 416 Gas
416
Pressure Pipe Gas Pipe Liquid
331 Pipe
314
High Pressure Low
416
Gas
416 Pressure
Pipe Gas Pipe
I.D.15.88 I.D.15.88 I.D.15.88 I.D.15.88 408 I.D.15.88 I.D.15.88 408 I.D.15.88 I.D.15.88 408 I.D.15
408 408 408 408
I.D.28.58 I.D.28.58 I.D.28.58 I.D.28.58 I.D.28.58 I.D.28.58
I.D.28.58 I.D.28.58 I.D.22.2 O.D. 28.58 I.D.34.9 I.D.28.58 I.D.28.58O.D.15.88 I.D. 19.05 I.D.28.58
I.D.22.2O.D.
O.D.22.2 I.D.28.58
28.58I.D.I.D.34.9
19.05 O.D.15.88 I.D. 19.05 I.D.28.58 I.D.22.2
O.D. 22.2O.D.I.D. I.D.28.58
19.05
28.58 I.D.34.9
O.D.15.88 I.D. 19.05 O.D. 22.2 I.D. 19.05 O.D.15.88 I.D. 19.05 O.D. 22.2 I.D. 19.05 331 331
D.19.05 I.D.12.7 I.D.9.52 83 I.D.19.05 I.D.12.7 I.D.9.52 83 416 I.D.19.05 O.D.15.88 314I.D. I.D.12.7
19.05 I.D.9.52 83 416 I.D.19.05 O.D.15.88 314I.D. I.D.12.7
19.05 I.D.9.52 83 416 I.D.19.05
331 111 331 I.D.22.2 O.D. 28.58 I.D.34.9
I.D.22.2 111
111 I.D.22.2O.D.
O.D.22.2
28.58I.D.I.D.34.9
416 19.05
I.D.22.2 111
111
O.D. 416
22.2O.D.
I.D.22.2 I.D. 19.05I.D.34.9
28.58 I.D.22.2111 111
Liquid Pipe High Pressure Gas Pipe Liquid Pipe
408
High Pressure Gas Pipe
ARCNN21 I.D.22.2 I.D.22.2 408 I.D.22.2 408 I.D.22.2
314 I.D.31.8 I.D.34.9 416 314 I.D.31.8 I.D.34.9
I.D.31.8 I.D.34.9 416
I.D.15.88 331 ARCNB21 I.D.15.88 I.D.31.8 I.D.34.9 408
I.D.31.8 I.D.34.9 416
I.D.15.88 331 I.D.15.88 I.D.31.8 I.D.34.9
I.D.31.8 I.D.34.9 408 I.D.15
I.D.28.58 416 I.D.28.58 I.D.28.58 I.D.28.58 I.D.28.58 416 I.D.28.58 I.D.28.58
I.D.15.88 I.D.15.88 408 I.D.15.88 I.D.15.88 408 314 I.D.28.58 416 I.D.28.58 314 I.D.28.58 416
I.D.22.2 O.D.19.05 I.D.22.2 O.D.19.05 408 I.D.22.2 O.D.19.05
I.D.15.88 I.D.15.88 408 I.D.22.2 O.D.19.05
I.D.15.88 I.D.15.88 408 I.D.22
I.D.15
I.D.12.7 I.D.15.88 I.D.28.58 I.D.28.58 I.D.12.7 I.D.15.88I.D.41.3 I.D.38.1 O.D.34.9 I.D.28.58 I.D.28.58 I.D.12.7 I.D.15.88 I.D.41.3 408
I.D.38.1 O.D.34.9 I.D.12.7 I.D.15.88 I.D.41.3 408 O.D.34.9
I.D.38.1
I.D.28.58 I.D.28.58 I.D.19.05 I.D.12.7 I.D.9.52 83 I.D.28.58 I.D.28.58 I.D.19.05 I.D.12.7 I.D.9.52 83 I.D.28.58 I.D.28.58 I.D.19.05
I.D.28.58 111 I.D.28.58 I.D.28.58
I.D.28.58 111 I.D.28.58 I.D.28.58 I.D.28.58 111
I.D.12.7 I.D.9.52 83 I.D.28.58 I.D.12.7 I.D.9.52 83 I.D.22.2 I.D.28.58 I.D.22.2
I.D.28.58 111 I.D.22.2111
I.D.28.58
D.19.05 I.D.19.05 I.D.22.2 I.D.22.2
O.D.12.7 I.D.9.52 O.D.12.7 I.D.31.8
I.D.9.52 I.D.34.9 O.D.12.7
I.D.12.7 I.D.9.52 I.D.9.5283 I.D.31.8 I.D.34.9
I.D.31.8 I.D.34.9 O.D.12.7
I.D.12.7 I.D.9.5283
I.D.9.52
I.D.31.8 I.D.34.9
I.D.31.8 I.D.34.9
70 I.D.22.2 111 70 I.D.19.05
I.D.22.2 70 111 I.D.19.05 70 I.D.19.05
130 I.D.22.2 111 130 I.D.22.2 111 130 I.D.22.2111 111
O.D.15.88 I.D. 19.05 I.D.31.8 I.D.34.9 O.D.15.88 I.D. 19.05 I.D.31.8 I.D.34.9 I.D.22.2 O.D.19.05 I.D.22.2 111 I.D.22.2 O.D.19.05 I.D.22.2 I.D.22
I.D.31.8
I.D.41.3 I.D.34.9
I.D.38.1 O.D.34.9 I.D.31.8
I.D.41.3 I.D.34.9
I.D.38.1 O.D.34.9 I.D.31.8 I.D.34.9
I.D.22.2 O.D.19.05
O.D. 22.2 I.D. 19.05
I.D.22.2 O.D.19.05
O.D. 22.2 I.D. 19.05 I.D.12.7 I.D.15.88 I.D.31.8 I.D.34.9 I.D.12.7 I.D.15.88 I.D.31.8 I.D.41.3
I.D.34.9I.D.38.1 O.D.34.9
331 I.D.12.7 I.D.15.88 O.D.28.58 I.D. 19.05 331 I.D.12.7 I.D.15.88 I.D.28.58 O.D.28.58 I.D. 19.05
I.D.22.2 O.D.19.05 O.D.28.58 I.D. 19.05I.D.28.58 I.D.22.2 O.D.19.05 O.D.28.58 I.D. 19.05 I.D.28.58 I.D.22
I.D.28.58 I.D.28.58
314 I.D.22.2
416 314 I.D.41.3 I.D.38.1 O.D.34.9 I.D.22.2
416 I.D.12.7 I.D.9.52
O.D.12.7 I.D.15.88 I.D.22.2
I.D.41.3 I.D.38.1 O.D.34.9 I.D.9.52
O.D.12.7 I.D.15.88
I.D.12.7 I.D.22.2
I.D.41.3 I.D.38.1 O.D.34.9
O.D.15.88
I.D.15.88 I.D. 19.05
I.D.15.88 I.D.9.52 I.D.28.58 I.D.15.88O.D.15.88 I.D. 19.05
I.D.15.88 I.D.9.52 I.D.22.2 O.D.28.58 I.D.34.9 I.D.28.58
O.D.15.88
70 I.D. 19.05 I.D.22.2 O.D.28.58 I.D.34.9 O.D.15.88
70 I.D. 19.05 I.D.22.2 O.D.28.58 I.D.34.9
O.D.12.7 408 O.D.12.7 130 I.D.28.58 408 130 I.D.28.58 130 I.D.28.58
I.D.28.58 I.D.28.58
70 I.D.28.58 I.D.28.58 70 I.D.28.58 I.D.28.58 O.D.12.7 I.D.9.52 O.D.12.7 I.D.9.52
70 O.D.28.58 I.D. 19.05 70 O.D.28.58 130 I.D. 19.05
D.19.05 I.D.12.7 I.D.9.52 83 I.D.19.05 I.D.12.7 I.D.9.52 83 130 130
O.D.28.58 I.D. 19.05 O.D.28.58 I.D. 19.05 I.D.22.2 I.D.22.2
I.D.22.2 111 I.D.22.2 O.D.28.58 I.D.34.9 I.D.22.2 111
O.D.15.88 I.D. 19.05 I.D.22.2 O.D.28.58 I.D.34.9 O.D.15.88 I.D. 19.05 I.D.22.2 O.D.28.58 I.D.34.9
I.D.31.8 I.D.34.9 I.D.22.2 I.D.31.8 I.D.34.9 I.D.22.2 O.D.28.58 I.D. 19.05 O.D.28.58 I.D. 19.05
O.D.15.88 I.D. 19.05 3 Outdoor Units O.D.15.88 I.D. 19.05 I.D.22.2 3 Outdoor Units I.D.22.2
I.D.22.2 O.D.19.05 I.D.22.2 O.D.19.05 I.D.22.2 O.D.28.58 I.D.34.9 O.D.15.88 I.D. 19.05 I.D.22.2 O.D.28.58 I.D.34.9 O.D.15.88 I.D. 19.05 I.D.22.2 O.D.28.58 I.D.34.9
I.D.12.7 I.D.15.88 I.D.12.7 I.D.15.88 I.D.41.3 O.D.34.9 I.D.41.3 O.D.34.9 I.D.41.3 O.D.34.9
I.D.22.2 O.D.28.58 I.D.34.9 O.D.34.9 I.D.28.58 I.D.22.2 O.D.28.58 I.D.34.9 O.D.34.9 I.D.28.58 O.D.34.9 I.D.28.58
.D.19.05 I.D.12.7 Model I.D.22.2
O.D.19.05 High Pressure Gas PipeI.D.28.58
O.D.19.05 Liquid Pipe
I.D.12.7 O.D.19.05 I.D.22.2 I.D.28.58
Model High Pressure Gas Pipe Liquid Pipe Low Pressure Gas Pipe
I.D.15.88 416 I.D.15.88 416 I.D.22.2 O.D.28.58 I.D.34.9 I.D.22.2 O.D.28.58 I.D.34.9
O.D.12.7 I.D.9.52 O.D.12.7 I.D.9.52
70 408 70 408 O.D.19.05 I.D.12.7 O.D.19.05 I.D.22.2 O.D.19.05 I.D.12.7 O.D.19.05 I.D.22.2 O.D.19.05
334 334 125I.D.28.58 I.D.15.88 416 125 I.D.15.88 416 125 I
I.D.28.58 I.D.28.58 I.D.41.3 O.D.34.9 I.D.28.58 I.D.41.3 O.D.34.9 I.D.41.3 O.D.34.9
281 281 341 341
408 408 341
O.D.34.9 I.D.28.58298 334 O.D.34.9 I.D.28.58
298 334 O.D.34.9 I.D.28.58
298 I.D.28.58
O.D.28.58 I.D. 19.05 O.D.28.58 I.D. 19.05 I.D.28.58 I.D.28.58 I.D.28.58
I.D.22.2 I.D.22.2
O.D.28.58 I.D.34.9 I.D.41.3 O.D.34.9 I.D.22.2 O.D.28.58
I.D.22.2 I.D.34.9 281 I.D.22.2 O.D.28.58 I.D.41.3 O.D.34.9
I.D.34.9 281 I.D.22.2 O.D.28.58 I.D.34.9 I.D.41.3 O.D.34.9
.D.19.05 I.D.12.7 O.D.19.05 I.D.22.2 I.D.22.2 111 O.D.19.05 I.D.12.7 O.D.19.05 I.D.22.2 I.D.22.2
O.D.19.05 111 I.D.12.7 O.D.19.05 I.D.12.7 O.D.19.05
O.D.15.88
I.D.15.88 I.D. 19.05 O.D.15.88
I.D.15.88 I.D. 19.05 O.D.34.9 I.D.28.58 O.D.19.05 I.D.22.2 O.D.34.9 I.D.28.58 O.D.19.05 I.D.22.2 O.D.34.9 I.D.28.58
I.D.31.8 I.D.34.9 416 I.D.31.8
125 I.D.34.9 416 I.D.15.88 416 125 I.D.15.88 416 125 I
408 408 I.D.22.2 408
O.D.28.58 I.D.34.9
I.D.22.2 111 I.D.22.2 408O.D.28.58 I.D.34.9
I.D.22.2 111
334 I.D.19.05 83 I.D.41.3 334 I.D.19.05 83 341 341 341
.22.2 I.D.19.05 I.D.28.58I.D.38.1 O.D.34.9 I.D.28.58 I.D.22.2 I.D.19.05
I.D.41.3 298 I.D.34.9
I.D.41.3
I.D.28.58 I.D.38.1 O.D.34.9O.D.19.05
I.D.28.58 I.D.12.7
334 O.D.19.05 I.D.22.2 I.D.31.8 I.D.34.9
I.D.28.58
I.D.41.3 298 I.D.28.58
I.D.34.9
O.D.19.05 I.D.12.7
334 O.D.19.05 I.D.22.2 I.D.31.8 I.D.34.9
I.D.28.58
I.D.41.3 298 I.D.28.58I.D.34.9
O.D.19.05
281 281 125 111 I.D.15.88 416 125 111 I.D.15.88 416 125 111 I
I.D.22.2 I.D.19.05 281 I.D.19.05 83 I.D.41.3 I.D.38.1 408
O.D.34.9 I.D.22.2 I.D.19.05 281 I.D.19.05 83 I.D.41.3 I.D.38.1 408 O.D.34.9 I.D.22.2 I.D.1
I.D.28.58 341 I.D.28.58 341 341
298 334 I.D.28.58 298 I.D.28.58 334 I.D.28.58 298 I.D.28.58
ACCESSORIES
I.D.22.2 111 I.D.22.2 111 281 I.D.28.58 111 281 I.D.28.58 111
I.D.15.88 I.D.12.7 130 I.D.15.88 I.D.12.7 130 I.D.22.2 I.D.22.2
I.D.31.8 I.D.34.9 I.D.31.8 I.D.34.9 I.D.31.8 I.D.34.9 I.D.31.8 I.D.34.9
I.D.28.58 O.D.22.2 ARCNN31
I.D.19.05 83 I.D.28.58 O.D.22.2 I.D.41.383
I.D.19.05I.D.53.98
I.D.28.58 111
I.D.34.9 ARCNB31
I.D.15.88 I.D.12.783 I.D.41.3 130 I.D.28.58 111
I.D.34.9 I.D.15.88 I.D.12.783 I.D.41.3130 I.D.28.58 111
I.D.34.9
.22.2 I.D.19.05 I.D.41.3 I.D.22.2 I.D. 34.9 O.D.28.58
I.D.38.1 O.D.34.9
O.D.28.58 I.D.34.9I.D.22.2 I.D.22.2 I.D.19.05 I.D. 44.5 O.D.41.3 I.D.41.3 I.D.22.2 I.D. 34.9
I.D.38.1 O.D.34.9
O.D.28.58 O.D.28.58
I.D.22.2 I.D.34.9 I.D.22.2
I.D.19.05 I.D.19.05 I.D.53.98 I.D. 44.5
I.D.41.3 I.D.38.1 O.D.41.3 I.D.22.2
O.D.34.9 111 I.D.22.2 I.D.19.05 I.D.19.05 I.D.53.98
I.D.41.3 I.D.38.1 I.D. 44.5 O.D.41.3
O.D.34.9 I.D.22.2 111 I.D.22.2 I.D.1
.D.19.05 I.D.12.7 O.D.19.05 I.D.22.2 O.D.19.05 I.D.12.7 O.D.19.05 I.D.22.2 I.D.31.8 I.D.34.9 I.D.31.8 I.D.34.9
I.D.15.88 416 I.D.15.88 I.D.41.3 I.D.34.9 416 I.D.28.58 O.D.22.2 I.D.41.3 I.D. 34.9 O.D.28.58
I.D.34.9 I.D.22.2 I.D.28.58 O.D.22.2 I.D.41.3 I.D. 34.9 O.D.28.58I.D.34.9
I.D.22.2 111 I.D.28.58
O.D.15.88 I.D.19.05 I.D.28.58 O.D.15.88 I.D.19.05 111 I.D.28.58 111
408 408 I.D.22.2 I.D.19.05 I.D.19.05 83 I.D.41.3 I.D.38.1 O.D.34.9 I.D.28.58 I.D.22.2 I.D.19.05 I.D.19.05 83 I.D.41.3 I.D.38.1 O.D.34.9 I.D.28.58 I.D.22.2 I.D.1
334 I.D.53.98 I.D.44.5 O.D.41.3
I.D.28.58 I.D.28.58 334 I.D.53.98
I.D.28.58I.D.44.5 O.D.41.3 I.D.28.58
I.D.15.88 I.D.12.7 130 I.D.15.88 I.D.12.7 I.D.22.2 O.D.28.58 I.D.34.9
I.D.28.58 130 O.D.15.88 I.D.19.05 I.D.22.2 O.D.28.58 I.D.34.9
I.D.28.58 O.D.15.88 I.D.19.05 I.D.22.2 O.D.28.58 I.D.34.9
I.D.28.58
281 281 I.D.15.88 I.D.12.7 130 I.D.15.88 I.D.12.7 130
I.D.53.98 I.D. 44.5 O.D.41.3 I.D.53.98I.D.44.5
I.D.53.98 I.D. 44.5 O.D.41.3
O.D.41.3 I.D.28.58 I.D.53.98 I.D.53.98
I.D.44.5 I.D. 44.5 O.D.41.3I.D.28.58
O.D.41.3
I.D.28.58 O.D.22.2 I.D. 34.9 O.D.28.58 I.D.22.2 I.D.28.58 O.D.22.2 I.D. 34.9 O.D.28.58
I.D.28.58 I.D.22.2
O.D.22.2 I.D.28.58 O.D.22.2 I.D.28.58
111 I.D.28.58 111 I.D.15.88 I.D.12.7 I.D.28.58
130 I.D. 34.9 O.D.28.58 I.D.22.2 I.D.15.88 I.D.12.7 I.D.28.58
130 I.D. 34.9 O.D.28.58 I.D.22.2
I.D.22.2 I.D.53.98 I.D. 44.5 O.D.41.3 I.D.22.2 I.D.53.98 I.D. 44.5 O.D.41.3 I.D.53.98 I.D. 44.5 O.D.41.3
O.D.15.88 I.D.19.05 I.D.31.8 I.D.34.9 O.D.15.88 I.D.19.05 I.D.31.8 I.D.34.9
I.D.22.2 O.D.28.58 I.D.34.9 I.D.28.58 O.D.22.2 O.D.15.88 I.D.19.05 I.D.22.2 O.D.28.58
I.D. 34.9 O.D.28.58 I.D.34.9
I.D.22.2 I.D.28.58 O.D.22.2 O.D.15.88 I.D.19.05 I.D.22.2
I.D. 34.9 O.D.28.58
O.D.28.58 I.D.22.2I.D.34.9 I.D.28.58
.22.2 I.D.19.05 I.D.19.05 83 I.D.53.98 I.D.44.5
I.D.38.1 O.D.41.3
I.D.41.3O.D.34.9 O.D.34.9 I.D.22.2 I.D.19.05 I.D.19.05 83 I.D.53.98 I.D.44.5
I.D.38.1 O.D.41.3
I.D.41.3O.D.34.9 O.D.34.9
O.D.19.05 I.D.22.2 I.D.28.58 I.D.41.3 I.D.44.5 O.D.19.05 I.D.22.2 I.D.28.58 I.D.41.3 I.D.44.5 I.D.53.98 I.D.44.5 O.D.41.3 I.D.53.98 I.D.44.5 O.D.41.3
I.D.22.2 O.D.28.58 I.D.34.9 O.D.15.88 I.D.19.05 I.D.22.2 O.D.28.58 I.D.34.9 O.D.15.88 I.D.19.05 I.D.22.2 O.D.28.58 I.D.34.9
334 341 I.D.28.58 334 341 I.D.28.58
PIPING ACCESSORIES
I.D.53.98 I.D.44.5 O.D.41.3 I.D.53.98 I.D.44.5 O.D.41.3
281 298 281 298
I.D.15.88 I.D.12.7 130 I.D.15.88 I.D.12.7 130
I.D.28.58 O.D.22.2 I.D.28.58 O.D.22.2
O.D.19.05 I.D.22.2 I.D.28.58 O.D.34.9 I.D. 34.9 O.D.28.58
I.D.41.3 I.D.44.5I.D.22.2
4 Outdoor Units O.D.19.05 I.D.22.2 I.D.28.58 O.D.34.9 I.D. 34.9 O.D.28.58
I.D.41.3 I.D.44.5I.D.22.2 4 Outdoor Units
.22.2 I.D.19.05 I.D.19.05 83 I.D.22.2 I.D.19.05 I.D.19.05 83
334O.D.15.88 I.D.19.05 I.D.41.3 341 I.D.34.9 111 334O.D.15.88 I.D.19.05 I.D.41.3 341 I.D.34.9 111
281 Model High
I.D.53.98 Pressure
I.D.44.5 298
O.D.41.3 Gas Pipe Liquid
281 Pipe O.D.41.3 I.D.44.5 I.D.53.98 298
I.D.53.98 I.D.44.5 O.D.41.3 O.D.19.05 I.D.22.2 Model
I.D.28.58 High Pressure
O.D.41.3
O.D.34.9 I.D.41.3Gas
I.D.44.5 Pipe
I.D.53.98
I.D.44.5 Liquid
O.D.19.05 Pipe I.D.28.58
I.D.22.2 Low Pressure
O.D.41.3
O.D.34.9 Gas
I.D.44.5I.D.44.5
I.D.41.3 Pipe
I.D.53.98 O
415 334 415
341 334 341 415
I.D.15.88 I.D.12.7 I.D.15.88 I.D.12.7
I.D.31.8 I.D.28.58 O.D.22.2 I.D.31.8 I.D.28.58 O.D.22.2 375 281 375
298 281 298 375
I.D.53.98 I.D.44.5 O.D.41.3 I.D.28.58 I.D.53.98 I.D.44.5 O.D.41.3 I.D.28.58
.22.2 I.D.19.05 I.D.19.05 83 I.D.22.2 I.D.19.05 I.D.19.05 83
O.D.41.3 I.D.44.5 I.D.53.98I.D.41.3 O.D.19.05
I.D.41.3 I.D.34.9 111 I.D.34.9 111 I.D.22.2 I.D.28.58 O.D.41.3
O.D.34.9 I.D.44.5
I.D.41.3 I.D.53.98
I.D.44.5 O.D.19.05 I.D.22.2 I.D.28.58 O.D.34.9
O.D.41.3
I.D.41.3
I.D.44.5I.D.44.5
I.D.53.98 O
415 334 415
341 341 415
O.D.19.05 I.D.22.2 I.D.28.58
O.D.15.88 I.D.19.05 O.D.34.9
I.D.34.9 I.D.41.3
O.D.28.58 I.D.44.5
I.D.22.2 O.D.19.05 I.D.22.2 I.D.28.58
O.D.15.88 I.D.19.05 O.D.41.3 I.D.44.5 I.D.53.98 O.D.34.9 I.D.41.3
134 I.D.34.9 O.D.28.58
I.D.44.5
I.D.22.2I.D.22.2
O.D.19.05
I.D.19.05 I.D.22.2 I.D.28.58
I.D.19.05 83 O.D.34.9 I.D.44.5
O.D.41.3 I.D.41.3 I.D.53.98
I.D.44.5 134 O.D.19.05 334
I.D.22.2 I.D.19.05 I.D.22.2 I.D.28.58
I.D.19.05 83 O.D.41.3
O.D.34.9 I.D.44.5I.D.44.5
I.D.41.3 I.D.53.98 134 O
I.D.22.2 I.D.
I.D.44.48 I.D.53.98 375 I.D.41.3 281 I.D.44.48 375
I.D.41.3 I.D.53.98298 I.D.41.3
I.D.34.9 111 281 298
I.D.41.3I.D.44.48 I.D.53.98 375 I.D.34.9 I.D.41.3
111
334 I.D.15.88 I.D.12.7 341 334 I.D.15.88 I.D.12.7 415 341 415
341 341 415
I.D.31.8 I.D.28.58 281
O.D.22.2 I.D.53.98 I.D.44.5 O.D.41.3 I.D.31.8 I.D.28.58 281
O.D.22.2 I.D.53.98 I.D.44.5 O.D.41.3 334 334
298 I.D.28.58 375 298 I.D.28.58 375
298 298 375
281 281
I.D.15.88 I.D.12.7 I.D.15.88 I.D.12.7
I.D.22.2 I.D.28.58 O.D.22.2 I.D.19.05
I.D.31.8I.D.19.05 83 I.D.22.2
I.D.31.8I.D.19.05
I.D.28.58 O.D.22.2 I.D.19.05 83 I.D.22.2
I.D.31.8I.D.I
I.D.44.48 I.D.53.98 I.D.28.58 134
I.D.41.3 I.D.53.98
I.D.41.3 I.D.44.5
I.D.44.48 I.D.53.98O.D.41.3 I.D.28.58134
I.D.28.58
I.D.41.3
I.D.34.9 111 I.D.53.98 I.D.44.5I.D.53.98
I.D.41.3I.D.44.48 O.D.41.3 I.D.28.58
I.D.34.9 I.D.28.58
I.D.41.3111 134
O.D.15.88 I.D.19.05 I.D.34.9 O.D.28.58 I.D.22.2 O.D.15.88 I.D.19.05 I.D.34.9 O.D.28.58 I.D.22.2
.22.2 I.D.19.05 I.D.19.05 83 I.D.22.2 I.D.19.05 I.D.19.05 83
ARCNN41 I.D.41.3 I.D.34.9 111 I.D.22.2 I.D.41.3I.D.41.3
O.D.28.58 I.D.34.9 134 I.D.34.9
I.D.22.2 I.D.19.05111 ARCNB41
I.D.19.05 83
I.D.41.3I.D.22.2 I.D.41.3
I.D.34.9
O.D.28.58 I.D.34.9 134 I.D.22.2 I.D.19.05 I.D.19.05 83
I.D.41.3I.D.44.48
I.D.22.2 I.D.34.9
O.D.28.58 I.D.41.3
I.D.34.9 134 I.D.22.2 I.D.
I.D.44.48 I.D.53.98 I.D.44.48 I.D.53.98 111 I.D.53.98 111
O.D.15.88
I.D.15.88I.D.19.05
I.D.12.7 I.D.34.9 O.D.28.58 I.D.22.2 O.D.15.88
I.D.15.88I.D.19.05
I.D.12.7 I.D.34.9 O.D.28.58 I.D.22.2
I.D.28.58 I.D.31.8 I.D.28.58 O.D.22.2 I.D.53.98 I.D.44.5 O.D.41.3 I.D.28.58
I.D.28.58 I.D.31.8 I.D.28.58 O.D.22.2 I.D.53.98 I.D.44.5 O.D.41.3 I.D.28.58I.D.28.58 I.D.31.8 I
I.D.15.88 I.D.12.7 I.D.15.88 I.D.12.7 I.D.15.88 I.D.12.7 I.D.15.88 I.D.12.7
I.D.31.8 I.D.28.58 O.D.22.2 I.D.53.98 I.D.44.5 O.D.41.3 I.D.28.58 I.D.31.8 I.D.28.58 O.D.22.2 I.D.53.98 I.D.44.5 O.D.41.3 I.D.31.8I.D.28.58
I.D.28.58 O.D.22.2 I.D.31.8 I.D.28.58 O.D.22.2 I.D.31.8 I
I.D.22.2 O.D.28.58 I.D.34.9 I.D.28.58 I.D.53.98I.D.22.2
I.D.44.5 O.D.28.58
O.D.41.3 I.D.34.9
I.D.28.58
I.D.28.58 I.D.53.98 I.D.44.5 O.D.41.3
I.D.22.2 I.D.28.58
O.D.28.58 I.D.28.58
I.D.34.9
O.D.15.88 I.D.19.05 I.D.34.9 O.D.28.58 I.D.22.2 O.D.15.88 I.D.19.05 I.D.34.9 O.D.28.58 I.D.22.2
O.D.15.88 I.D.19.05 I.D.34.9 O.D.28.58 I.D.22.2 O.D.15.88 I.D.19.05 I.D.22.2 O.D.28.58 I.D.34.9 I.D.34.9 O.D.28.58 I.D.22.2 O.D.15.88 I.D.19.05
I.D.22.2 O.D.28.58 I.D.34.9
O.D.15.88 I.D.19.05
I.D.22.2 O.D.28.58 I.D.34.9
I.D.34.9 O.D.28.58 I.D.22.2 I.D.34.9 O.D.28.58 I.D.22.2
182 / 183
ACCESSORIES _ PIPING ACCESSORIES
PIPING ACCESSORIES
Y Branch pipe for connection of outdoor units.
Specification Specification
Heat Pump, Heat Recovery Zone Control Heat Recovery
R410A MULTI V 5, MULTI V IV, MULTI V III, MULTI V PLUS II, MULTI V PLUS, MULTI V S, MULTI V MINI, R410A MULTI V 5, MULTI V IV Heat Recovery, MULTI V III Heat Recovery, MULTI V WATER IV Heat Recovery,
MULTI V SPACE II, MULTI V WATER IV, MULTI V WATER S, MULTI V WATER II MULTI V WATER II Heat Recovery
(Unit : mm) (Unit : mm)
Model Gas Pipe Liquid Pipe Model High Pressure Gas Pipe Liquid Pipe Low Pressure Gas Pipe
I.D15.88 I.D6.35
ARBLN01621
ARBLB01621 I.D6.35 I.D15.88
I.D12.7
I.D25.4
I.D9.52 I.D9.52 I.D6.35 I.D22.2 I.D19.05 I.D15.88 I.D19.05
I.D12.7 I.D12.7
O.D19.05
ARBLN03321 I.D28.58
I.D15.88 I.D12.7
I.D12.7
I.D19.05 I.D25.4
ARBLB03321 I.D12.7 I.D12.7
I.D9.52 I.D6.35
I.D28.58 O.D19.05
I.D25.4 O.D19.05
O.D19.05 I.D12.7 I.D15.88 I.D12.7
I.D 22.2 I.D 22.2 I.D9.52 I.D6.35
I.D19.05
I.D12.7
I.D25.4 O.D19.05
O.D19.05
I.D 22.2 I.D 22.2
I.D12.7 I.D12.7
I.D12.7 I.D12.7 I.D19.05 I.D31.8
ARBLN07121 ARBLB07121
ACCESSORIES
I.D31.8 I.D19.05
I.D34.9
I.D34.9 I.D41.3 I.D38.1 I.D28.58
I.D34.9
I.D34.9 I.D41.3 I.D38.1 I.D28.58
I.D28.58
I.D38.1
PIPING ACCESSORIES
I.D28.58
ARBLN14521 I.D41.3 O.D34.9
I.D34.9 I.D22.2 I.D38.1
I.D41.3
O.D38.1 I.D38.1
ARBLB14521 I.D41.3 O.D34.9
I.D34.9 I.D22.2
I.D41.3
O.D38.1 I.D38.1
Model High Pressure Gas Pipe Liquid Pipe Low Pressure Gas Pipe
184 / 185
ACCESSORIES _ PIPING ACCESSORIES
Max. 450
Key Application
ACCESSORIES
Manifold Ceiling Mounted Cassette Flexible Hose
250 (4 Way, 1 Way) Make a Loop Form
Ceiling Concealed Duct
(with Drain Pump)
Capillary Assembly
(Unit : mm)
PIPING ACCESSORIES
Specification
* Fault Detect & Diagnosis
Model Length Quantity
PHDHA05T 500mm 30EA
PHDHA07T 700mm 30EA
PHDHA05B 500mm 5EA
186 / 187
ACCESSORIES _ PIPING ACCESSORIES
STOPPER VALVES
"A"
9.52 : 19.05
3.0 m Room 1
Key Features
9.52 : 19.05 Closed State
Pin (Closed) Pin (Open)
• This unit can be applied for the additional indoor unit’s installation. 3.0 m
• This unit can be applied for each indoor unit’s service. In case of installation of stopper valve,
Stopper Valves
9.52 : 15.88In case of installation of additional
flare part should be facing towards indoor unit, SVC valve should be in Room 2
10.0 m
additional indoor unit. closed state
ID 19.05 • In case of installation of additional indoor unit, refrigerant of used indoor unit must be discharged. (Room 3 & Room 4)
ID 15.88 ID 22.2 ID 22.2 ID 19.05 ID 15.88
PRVT780 • If stopper valve is already installed, you can install additional indoor unit without refrigerant loss from the entire system.
• After installation of additional indoor unit, you just need refrigerant charging for “A” section.
• Then, open the Stopper Valve.
ACCESSORIES
Input Output (Indoor unit) Cut inlet side of the connector, and weld In case of the installation of additional
ID 28.58 ID 28.58
the pipe indoor unit, outlet side connector should
be cut according to installation pipe.
PRVT980
9.52 : 19.05
PIPING ACCESSORIES
3.0 m
9.52 : 15.88
Pin (Closed)
Pin (Closed)
Pin (Open)
Pin (Open) 3.0 m
Room 2
1.Cut
Cutinletthe
sideinlet
of the connector,
ofside weldweld In case
of theandand Ifofinstalling
2.case the installation of additional
additional indoor 3.case
When installingof astopper
stopper
Cut inlet side the connector, In of the installation of additional In of installation
In case valve,valve,
of installation of stopper
4. installation
In case of
valve,
When installing anadditional
of additional
In case of installation of additional
the the
pipepipe indoor unit,unit,
indoor outlet sideside
outlet connector should
connector should
connector, and weld the pipe. be cut units, the
according to outlet side
installation connec-
pipe. the
flare flare
part
flare part
should
part be should
facing
should be facing
betowards
facing towards indoor unit, indoor
SVC
indoor unit,
valve
unit, SVC thebe
should
valve SVC
in be
should valve
in
be cut according to installation pipe. additional indoor unit. closed state
tor should be cut according to towards additional indoor unit.
additional indoor unit. closed stateshould be in closed state. Room 3
installation pipe.
-When -When
welding,welding,
service service
valve shoud
valvebe wrapped
shoud by wet by
be wrapped cloth.
wet cloth.
※ When welding, service valve should be wrapped by wet cloth. Room 4
Pin (Closed)
Pin (Closed) Pin (Open)
Pin (Open)
In case of installation
In case of stopper
of installation valve,
of stopper valve, In case of installation
In case of additional
of installation of additional
flareflare
partpart
should be facing
should towards
be facing towards indoor unit,unit,
indoor SVCSVCvalve should
valve be in
should be in
additional indoor unit.
additional indoor unit. closed state
closed state
-When welding,
-When service
welding, valve
service shoud
valve be wrapped
shoud by wet
be wrapped cloth.
by wet cloth. 188 / 189