You are on page 1of 94

2021

2021

L G AI R
SOLUTION

LG Electronics Distributed by
SINGAPORE
http://www.lg.com
http://partner.lge.com

Copyright 2021 LG Electronics. All rights reserved.


024 - 025 104 - 105
OUTDOOR HOT WATER
UNITS SOLUTION
MULTI V 5 (Heat Pump) 038 HYDRO KIT 106

MULTI V S (Cooling Only) 052

110 - 111 120 - 121


VENTILATION CONTROL
SOLUTIONS SOLUTIONS
ERV 112 INDIVIDUAL CONTROL 124

CENTRALIZED CONTROL 132

INTEGRATION DEVICE 144

054 - 055
168 - 169
INDOOR
ACCESSORIES
UNITS
MECHANICAL ACCESSORIES 170
WALL MOUNTED 056
INDEX

PIPING ACCESSORIES 178


CEILING MOUNTED CASSETTE 062

CEILING MOUNTED ROUND CASSETTE 078

CEILING CONCEALED DUCT 082

CEILING SUSPENDED 094

CONSOLE 098

002 / 003
10 ADVANTAGES
OF MULTI V

5 SMART
CONTROLS 6 BUSINESS
SUPPORT
MULTI V responds to diverse building - Engineering Tools & Support
environments with LG ThinQ -based
TM
- LG Air Conditioning Academy
AI control and individual/central - Asia Regional HQ
integrated control solutions.

1 ULTIMATE
EFFICIENCY 3 SUPERIOR
DURABILITY 4 DESIGN
FLEXIBILITY
Ultimate Energy Saving with LG’s exclusive “Black Fin” Flexible Installation with
Dual Sensing Control. heat exchanger is designed
to perform even in corrosive
Environments.
Large Capacity Outdoor Unit.

MULTI V 5 enables easy type


change-over to suit the purpose
7 DIVERSE
PRODUCT
LINE UP
9
MADE IN
10
BRAND
of any building.
Hydrophilic film
LG offers a specialized product
KOREA RELIABILITY
Acryl + Epoxy +
Melamine resin lineup suited for various
business environments, perfectly LG MULTI V line-up emphasizing Global production sites facilitate
Humidity Temperature Aluminum fin
responding to the unique high quality and durability with world-class customer service.
conditions no matter the use case. Korea made products.

2
Certified protection

INNOVATIVE
TECHNOLOGIES
8 DIVERSE
INTEGRATED
SOLUTION
MULTI V 5 Integrated solution optimized for
- Ultimate Inverter Compressor ※ Verification of corrosion resistance performance various business environments,
- Declared by TUV Rheinland
- Biomimetics Technology Fan - Test Method B of ISO21207 including hot water, AHU, BMS,
- Test condition : Salt contaminated condition
+ severe industrial/traffic and EMS.
environment

Scroll Compressor

004 / 005
WHY LG MULTI V

MULTI V BRAND HISTORY INFRASTRUCTURE IN ASIA

2017 ~

・ Dual Sensing Control


2013 ・ Ultimate Inverter
Compressor
・ One Unified Platform
・ Active Refrigerant
2010 Heat pump & Heat
Control
recovery
・ Variable Heat Exchanger LG Singapore Air Conditioning Academy LG Whisen Park
・ Ocean Black Fin
Circuit
・ High Pressure Oil Return LG Singapore, as affiliate of managing several countries which LG Air conditioning Academy is a key infrastructure for the
・ Smart Load Control
2008 ・ Vapor Injection contain Bangladesh, Sri Lanka, Nepal, and other insular area company’s Total Climate Control business. HVAC business differs
・ Smart Oil Return like Maldives, Papua New Guinea, Fiji, runs LG air conditioning from ordinary air conditioning businesses in that as a B2B sector,
・ Continuous Heating
・ Vapor Injection academy. LG academy is supposed of LG showroom which LG the three elements of sales, installation and service must come
・ Ø7.0 Wide louver (Advanced) home appliance and air conditioning projects are displayed together to create good results.
2006 ・ LGDC Inverter and LG practice room which we instruct LG HVAC product
knowledge and software as well by using directly with LG
displayed materials.
・ Heat Recovery
・ Ø7.0 Corrugate
・ Fuzzy Algorithm
・ AC Inverter
・ R410A

Since the time when LG launched Korea’s first residential air MULTI V’s wide range of VRF solutions satisfies various building
conditioner in 1968, the company has worked to continuously types and sizes. MULTI V S’s size discharge was designed Germany
Canada
UK Poland
enhance its technological innovation and reliability. As a for small to mid-sized buildings while MULTI V Water is a Russia

result of sustained improvement, LG VRF launched the first water-cooled VRF solution with variable water flow control Italy Hungary
Korea
USA
France
generation of MULTI V in 2006 and achieved significant technology. Kazakhstan
China
development. With the best-in-class compressor technology
and innovation applied to every part and control solution, In 2017, the ultimate VRF solution was introduced with MULTI V 5. Jordan

MULTI V has evolved to be on of the world’s most efficient This generation has fully improved its technological potential
and reliable VRF solutions. with the powerful and reliable yet economical Ultimate Inverter GF
Vietnam
Panama
Thailand
Compressor, effective corrosion resistance with the Ocean India

The first and second generations of MULTI V boasted inverter Black Fin coating and enlarged fans. Dual Sensing Control Philippines

Nigeria
technology and non-ozone depleting technology, while MULTI V III was offers the most pleasant indoor environment while minimizing Singapore
Colombia

produced with cutting edge tech like oil return with HiPORTM unnecessary energy loss by sensing both temperature and
and double compression features with mid-pressure refrigerant humidity to efficiently manage cooling, heating and part load. Kenya
Indonesia

allowed by Vapor Injection. The innovative technologies of


MULTI V’s fourth generation brought about product leadership MULTI V 5 has been designed for the ultimate efficiency, Hub
in efficiency. Its smart load control adjusts with the outdoor performance, flexibility, comfort and control, ensuring the most Brazil

Regional
temperature, while optimizing refrigeration management and pleasant indoor experience.
South Africa
heat exchange for both cooling and heating.
Local
Australia

Branch

006 / 007
WHY LG MULTI V

ENGINEERING TOOLS & SUPPORT


From planning to service & maintenance and then to de-construction, an architectural project goes through many stages from 01 Draft Energy Estimation
the beginning to the end of its lifecycle. Along those stages, various engineering tools are applied to solve the diverse issues
happening in each stage, with the most optimal solution possible. Given the usage of such tools, buildings are effectively LATS Energy
designed, built, supervised, and maintained throughout their lifecycle. LATS Energy is a program developed by LG to estimate energy consumption and
Dedicated to provide the best HVAC engineering support, LG Electronics Air Solution Business Unit offers several engineering analyze the life cycle cost of LG commercial air conditioning systems during a
tools and solutions focused on HVAC, during the overall lifecycle of a building, related to the three categories. Among them, the project's early stages.
LATS* Program series has been developed to offer the best tool for LG HVAC systems, providing our customers with a solution
that allows for faster, easier and more accurate model selection, draft energy estimations and more.
* LATS : LG Air-conditioner Technical Solution
02 Building Energy Modeling
eQuest, EnergyPro, Trace700 and More
These are certified commercial programs which assess the HVAC system efficiency
and building’s annual energy savings for building standards or certifications,
like LEED. LG HQ supports these programs for the project stages of Design
Development and Construction Design wherein the overall designing is finished.

03 Model Selection
I II III LATS HVAC
LATS HVAC is a model selection program that accurately and quickly selects
Energy Estimation Model Selection Installation the most suitable LG commercial air conditioning systems for each design. In
addition to model selection, faster estimation on refrigerant piping diameter and
& Energy Modeling & Design Environment
additional refrigerant is possible, along with auto printing of reports.
Simulation

04 Design
LATS CAD
01 Planning LATS CAD enables faster and more accurate 2D design of LG commercial air
conditioning systems. It also enables modules for quotation and installation
LATS review that minimize inherent problems during installation and commissioning.
Energy
※ AutoCAD program is required.

02 Schematic Design LATS REVIT


LATS REVIT allows BIM users to have an attractive 3D design of LG commercial
LATS air conditioning systems with embedded calculations for refrigerant and efficiency
HVAC features.
※ AutoCAD Revit program is required.

03 Design Development
Energy
Modeling LATS CAD
- eQUEST Ⓡ
- TRNSYS
LATS REVIT
05 Environment Simulation
CFD CFD Analysis
04 Construction Design - FLUENT
CFD Analysis is applied in areas of estimating : indoor airflow and temperature
distribution while operating VRF products, outdoor airflow distribution, and
noise level. By running a simulation before construction, engineers estimate
possible issues and find optimal solutions for malfunctions that could occur after
construction.
05 Construction

06 Service & Maintenance


LGMV
LGMV offers real-time MULTI V cycle monitoring. During start-up, LGMV can
06 Service & Maintenance LGMV
check for normal operation as well as troubleshoot any errors. Also it helps to
find causes of errors and solve the problem faster.

008 / 009
WHY LG MULTI V

BENEFITS OF LG MULTI V

Benefits for Benefits for


Building Owners Consultants
Efficient Management & Cost Reduction Versatile Solutions
- Fault Detection Diagnosis enables easy maintenance - Air-cooled, Water-cooled, Heating, and Air Handing
- Requires no extra manpower for regular Unit interlocking solutions
maintenance
- With diverse control systems, maintenance cost is
Professional Design Support
minimized
- LATS (LG Air-conditioner Technical Solution) for
Reliability at Every Stage draft energy estimation, model selection, HVAC
- Ultimate Inverter Compressor developed and design and 3D designing
manufactured in Korea - CFD Analysis to ensure suitable solutions and
- Corrosion resistant Ocean Black Fin for harsh prevent malfunctions
conditions operation - Energy simulation offered to find the optimal
- Smart Oil management (Auto Oil Balancing and solution
Active Oil return) decreases compressor damage
Optimized Convenience with HVAC Design
Customized Comfort and Solution - Flexible and longer piping length facilitates
- Compatible option between Heat pump and Heat HVAC designing process
recovery system is possible - Meets any type of customer requirements of
diverse environment, design conditions, and
building applications

Benefits for Benefits for


Developers & Construction Companies End-users

Green Solutions Cost Saving Operation


- Optimized for LEED/BREEAM certification - High efficiency guaranteed throughout product
- Renewable energy solution provided through line-up
geothermal application - Up to 31% cost savings with MULTI V's Smart
Load Control*
Maximizing Space Utilization
- Large capacity in compact size enhances space
utilization Comfort Cooling & Heating
- Smart Load Control maximizes indoor comfort level
- Dual Sensing Control offers pleasant and
Smart Building Solutions comfortable cooling and heating environment
- Seamless integration with current Building - Duration time of Continuous Heating is 11%
Management Systems longer than previous model**
- Wi-Fi control available for anytime, anywhere
access (via the 'LG ThinQTM' mobile app) Convenient Functions
- Energy management and control according to - Low-noise operation provides a pleasant
usage and planning is possible with LG’s centralized environment
control solution

* Dual Smart Load Control ESEER based, below 50% humidity, model ARUM260LTE5
** LG internal test result

010 / 011
WHY LG MULTI V

APPLICATION SOLUTIONS

Office Residential
Supporting efficiency with flexibility Creating a comfortable home

High Rise Office Building Small to Medium sized Office Building Condominium Apartments

• MULTI V WATER IV • High Static Duct • Variable water flow • MULTI V 5 HR • Low static duct
• MULTI V 5 / S • 4 Way CST** • PDI • MULTI V 5 • 1 Way CST • PDI
• DX AHU • PDI* control kit • HYDRO KIT • 3rd party controller RTU gateway

The MULTI V series revitalizes the workspace by providing fresh air at all times. LG's intelligent control solutions add comfort MULTI V 5 HR/HP with various IDU enables optimal solution, providing comfort to every space through individual zone
to any space. control and hot water solution.

Commercial Hospitality
Maximizing business, minimizing cost Meeting diverse needs

Shopping Mall Retail Quick Service Restaurant (QSR)

• MULTI V • Convertible • MULTI V • HYDRO KIT


• MULTI V 5 • DX AHU • MULTI V 5 • DX AHU • HYDRO KIT • Low Static Duct • Remote control • Refrigerant leak detector
• ERV • ERV • 4 Way CST

The highly efficient, energy saving MULTI V 5 and MULTI V reduces operation costs, and provides comfort that suits any The diverse applications that can be applied to MULTI V 5 helps bring just the right solution to a sophisticated hotel business.
purpose and any space, helping to invest the extra space and expense to your business.

* PDI : Power Distribution Indicator ** CST : Cassette

012 / 013
WHY LG MULTI V

DIVERSE INTEGRATED SOLUTION DIVERSE INTEGRATED SOLUTION


Hot Water Solution Refrigerant Leak Detection Solution Energy Management Solution Interlocking Solution
Water heating costs can be reduced with a heat pump, which provides Real-time refrigerant leak detection ensures a safe environment. Since HVAC systems use a significant portion of any building’s total by Using ACU Module
higher efficiency than a boiler system. The HYDRO KIT can be connected When refrigerant concentration exceeds 6,000ppm for 5 seconds, amount of energy, the energy saving functions of a controller can make a
It is costly to introduce a BMS system to control multiple devices or
to MULTI V 5, providing temperatures up to 80°C. Energy savings can be the indoor unit will stop operation and alert users with a buzzer or big difference. The energy navigation function enables you to set target
systems in a small building. With the ACU module, various IO contact
maximized with the combination of the HYDRO KIT and the MULTI V 5 light switch (Dry contact option). values for energy consumption over a certain period of time. In addition,
points (DI, DO, UI, AO) can be interlocked and integrated, while control
Heat Recovery system. to achieve that value, the administrator can set the energy saving logic
is possible from the LG central controller. This enables an efficient
in 7 steps and predict the expected usage relative to the target value.
ROOM management of lighting, pumps and other devices in the building in
Indoor Unit Active self-management enables energy savings through out the building.
Buzzer Alarm conjunction with the HVAC system.
Card Key
MULTI V 5
Outdoor Unit Saving Engineering Cost
Cooling I/O Module
70% Pump Lighting Fan Sensor
Strengthen
Maintenance Efficiency
HR Unit Compressor Capacity IDU Operation IDU Operation
Ball Valve Control Ratio Control Level
ACS IO Module
(Field supply)
MULTI V 5
Outdoor Unit
Refrigerant Remote
Detector Controller
Target
AC Smart (ACP)
※ Regulation : EN378, BREEAM, ASHRAE Std. 15 & 34
Forecasting
HYDRO KIT Heating Hot Water

Power Consumption Distribution Solution Interlocking Solution Using Dry Contact


Air Handling Unit (AHU) Solution In case of shared power consumption in a building, a solution to 3rd party thermostats can be used to control LG air conditioners in a
distribute the power consumption amount per tenant might be room by using a multi point dry contact. The dry contact enables basic
AHU is a suitable solution for cooling and heating in large space. necessary. Electricity charges can be billed to each tenant by using control of air conditioners as well as making it possible to report the
With an LG AHU Comm. Kit (for both return air / supply air control) output from the LG Power Distributor Indicator (PDI). An administrator status and any errors impacting the indoor unit.
connected to the DX coil of the AHU, LG VRF system can be applied to is able to check the power usage for each space and date as needed. Integration Solution with BMS The Standard III remote control has a DO port. With this DO port, it
deliver conditioned air. If the PDI is used in conjunction with an LG central controller, the results
There are many BMS protocols used for the control of buildings’ various is possible to interlock the indoor unit with 3rd party devices such as
can be exported to Excel.
MULTI V 5 B Office systems such as HVAC, lighting, power and security. LG has a wide lighting, a fan, or a radiator, based on things like operation mode or
Outdoor Unit 20 kWh
WHM range of gateway products for different protocols such as BACnet, current temperature.
C Office
(Watt Meter)
Pulse Signal 30 kWh D Office Modbus, and LonWorks. In addition, LG gateways include Stand-alone The indoor unit can be interlocked with various types of input such as
A Office
20 kWh central control capability to act as a back-up controller of the BMS if
30 kWh card key-tag, door sensor, human detection sensor etc. so that the air
needed. conditioner is automatically operated. In addition, the dry contact
option settings enable operation of air conditioner to maintain proper
Small - Medium size building Medium - Large size building temperature when the occupant is absent. This solution makes sure
Power PDI
100 kWh that the room does not overheat or become too cold when unoccupied
IDU ~64 : ACP LonWorks so that energy cost can be saved.

Total Control of Any Device IDU 16~64 : Modbus RTU


IDU ~128 : AC Smart 5
(BACnet IP/Modbus TCP)
EEV Signal In order to manage multiple spaces and multiple buildings,
the administrators should be able to control systems from wherever
Communication they are. The LG central controller can be controlled from any web IDU ~256 : ACP 5
Kit Indoor Unit browser that supports HTML5. Now through the implementation of (BACnet IP/Modbus TCP)
EEV Kit
HTML5, the interface will look great and perform well on any device.

BMS Protocol
BMS System

Ref. pipe (Liquid)


Ref. pipe (Gas)
Communication

AHU

Management office Library Main administration building


PC Tablet Mobile

014 / 015
LINE-UP

OUTDOOR UNITS LINE-UP


Unit : HP / ● 380V, 3Ø

Features Appearance 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90 92 94 96 .... 104

● ● ●

● ● ● ● ● ● ●

HEAT PUMP
• Dual Sensing Control
• Large capacity ODU (Up to 26HP) ● ● ● ● ● ●
• Continuous Heating
• Black Fin heat exchanger
• Heat pump function
● ● ● ● ● ● ● ●
• For large space, high rise building and
individual control building

● ● ● ● ● ● ● ● ● ● ● ●

● ● ● ● ● ● ● ● ● ● ● ●

OUTDOOR UNITS LINE-UP


Features Appearance 3 4 5 6 8 10 12 14 16 18 20

○ ○ ○

• Space saving
• Flexible design applications
- Slim, light, and broad range (3 to 6HP)
- Large number of connectable indoor units
(Up to 20 Units)
• For small / medium building ○

016 / 017
LINE-UP

INDOOR UNITS LINE-UP INDOOR UNITS FEATURE OVERVIEW


Thermo Thermo Static Pressure 1 Point Auto
kW 1.5 2.2 2.8 3.6 4.5 5.6 6.2 7.1 8.2 9.0 10.6 12.3 14.1 15.8 17.5 22.4 28.0 Occupied /
Model Refrigerant On / Off On / Off 11 Step Control External Filter Sign Restart
Energy 2 Set Unoccupied Group Test Run Test Run Auto Wi-Fi
Information Leakage Range Range (Only for Ceiling Input (Remaining Function
Monitoring Point Scheduling Control (Cooling) (Heating) Addressing Ready
Monitoring Detection Setting Setting Concealed (On / Off Time) Disable /
Type Btu/h 5k 7k 9k 12k 15k 18k 21k 24k 28k 30k 36k 42k 48k 54k 60k 76k 96k Function
(Cooling) (Heating) Duct Type) Control) Enable

4th generation
Wall Standard ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●
Mounted

4 Way Cassette
● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●
(570 x 570)

4 Way Cassette
● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●
(840 x 840)

4 Way Cassette High Sensible


4th generation (840 x 840) ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●
Ceiling
Mounted
Cassette
Round Ceiling Cassette ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●

2 Way Cassette ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●

1 Way Cassette ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●

High Statics ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●

4th generation
Ceiling
Mid Static ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●
Concealed
Duct

Low Statics ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●

4th generation
● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●
Fresh Air Intake

4th generation
● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●
Ceiling Suspended

4th generation
● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●
Console

4th generation
Floor Standing
Floor ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●
with Case
Standing

Low Temperature ● ● ● ● ● ● ● ● ● ● ● ● ● ●
4th generation
HYDRO KIT
High Temperature ● ● ● ● ● ● ● ● ● ● ● ● ●

4th generation with Humidifier ● ● ● ● ● ● ● ● ● ● ●


Energy
Recovery
Ventilator
with DX Coil without Humidifier ● ● ● ● ● ● ● ● ● ● ●

※ If 4th generation indoor units are connected to MULTI V WATER S, several functions are not available.
※ If 4th generation indoor units are combined to 2nd generation indoor units, several functions are not available.
More detailed information, refer to the "MULTI V Indoor units Compatibility Table"

018 / 019
LINE-UP

LG HVAC CONTROL LINE-UP


INDIVIDUAL CONTROL CENTRALIZED CONTROL CENTRALIZED CONTROL INTEGRATION DEVICE
Wired Remote Controller Wireless Remote Indoor Unit
Display Platform Gateway Facility Integrator Outdoor Unit AHU Kit
Standard Simple Controller Dry Contact Control Accessory
PDI IO Module
Standard III (White) NEW
AC Ez ACP 5 ACP LonWorks (Power Distribution Indicator) Group Control Wire (Input / Output Module) Communication Kit

PREMTB100 PQRCVCL0QW PWLSSB21H (H/P) PQCSZ250S0 PACP5A000 PLNWKB000 Premium (8 port) Simple Dry Contact PZCWRCG3 For MULTI V 5 Return / Room Air control
(Indoor Unit ~32) (Indoor Unit ~256) (Indoor Unit ~64) PQNUD1S40 PDRYCB000 PVDSMN000 PAHCMR000
BACnet IP / Standard (2 port)
Modbus TCP PPWRDB000
Wi-Fi Controller
ACS IO Module Variable Water Flow
Standard III (Black) LG Wi-Fi Modem AC Ez Touch AC Manager 5 Modbus RTU Gateway (Input / Output Module) Remote Temperature Sensor Control kit

PREMTBB10 PQRCVCL0Q For Indoor Unit PACEZA000 PACM5A000 PMBUSB00A PEXPMB000 Dry Contact for Thermostat PQRSTA0 For MULTI V WATER IV Discharge / Supply Air control
PWFMDD200 (Indoor Unit ~64) (Indoor Unit ~8,192) PDRYCB300 PWFCKN000 PAHCMS000

Low Profile Remote


Standard II (White) AC Smart 5 PI-485 Chiller Option Kit Temperature Button Sensor Low Ambient Kit Controller Module

PREMTB001 PQRCHCA0QW PACS5A000 For Indoor Unit (ERV) PCHLLN000 Dry contact for Thermostat ZRTBS01 For MULTI V IV, 5 Main module
(Simple for Hotel) (Indoor Unit ~128) PHNFP14A0 (For using universal input) PRVC2 NEW
PAHCMM000
BACnet IP / NEW
PDRYCB320
Modbus TCP
ACU IO Module

Standard II (Black) UIO Zone Controller Cool / Heat Selector

PREMTBB01 PQRCHCA0Q PEXPMB300 2 Points Dry Contact (For Setback) 4 Zones by PRDSBM Communication module
(Simple for Hotel) PDRYCB400 thermostat ABZCA NEW
PAHCMC000

Premium
EEV Kit
UO Water Communication Module (Electronic Expansion Valve)

PREMTA000 PEXPMB200 For Modbus NEW


PAHCMW000 PRLK048A0 (3 - 10 HP)
PREMTA000A PDRYCB500 PRLK096A0 (12 - 20 HP)
PREMTA000B PRLK396A0 (20 - 40 HP)
PRLK594A0 (40 - 60 HP)

UI

PEXPMB100

020 / 021
OUTDOOR
UNITS

MULTI V 5 (HEAT PUMP)


MUTLI V S (COOLING ONLY)

024 / 025
OUTDOOR UNITS _ MULTI V 5 _ KEY FEATURES

INNOVATIVE TECHNOLOGIES INNOVATIVE TECHNOLOGIES

OUTDOOR
UNITS
Dual Sensing Smart Load Control (SLC) Energy Savings with Dual Sensing Control Comfort Cooling Intelligent Defrost
Enhanced energy saving & increased indoor comfort (Temperature & Humidity) Increased indoor comfort & enhanced operating efficiency Increased heating run-hours
Cooling loads vary according to both temperature and humidity. Case study First reference use Indoor Unit (IDU) is operating in a season when MULTI V has provided an intelligent defrost algorithm and settings
With Dual Sensing SLC, work exerted to meet the load depends its load is less than the design load, the comfort cooling algorithm based on current outdoor ambient temperature. With the addition

MULTI V 5
Weather characteristics of Warsaw, Poland
on both temperature and humidity. As a result, less capacity will be controls the indoor unit’s coil superheat, thus raising the discharged of the outdoor air humidity sensor, MULTI V 5 Intelligent Defrost just
The portion of cooling operation hours at low humidity condition (Below
required in lower humidity conditions. air temperature as the space temperature is approaching set point. got smarter.
50% RH) is big. The cooling load of this condition is less than the load at
MULTI V 5’s comfort control algorithm monitors the outdoor air MULTI V 5 computes the current ambient air dew point temperature
It influences the VRF system main processor’s decision on where to standard (50 ~ 70% RH) or high (over 70% RH) humidity condition even in
temperature and humidity conditions. When changing weather - the temperature at which frost will form on the outdoor unit coil in
set the system’s target high or low system pressure values. the same outdoor air temperature. MULTI V 5 raises the evaporating Temp
up at low load (Low humidity) condition to enable energy saving and prevent conditions are deteriorating and there is a high potential the indoor during winter operation. MULTI V 5 makes continuous adjustments to
over-cooling which can happen when the system is controlled only by using unit’s load will remain stable or may increase, comfort cooling delays the refrigeration cycle's operating parameters to keep the outdoor coil
Smart Load Control responds to : outdoor air Temp. or abandons raising the target superheat as the room temperature surface temperature above actual dew point which can be calculated
1) Outdoor ambient dry bulb temperature approaches set-point. When changing weather conditions are
Warsaw weather in Summer by using dry bulb Temp and relative humidity. When the refrigeration
2) Outdoor ambient relative humidity (when enabled) favorable to raising target superheat, target superheat is moderated. cycle's operating parameters can be adjusted no further without
90%
Cooling Indoor Units - adjusts target low pressure sacrificing heating comfort, further adjustment is stopped and frost is
80% High Humidity
Raises the target low pressure value as cooling load falls and/or ambient temperature falls.
Lowers the target low pressure value as cooling load rises and/or ambient temperature rises.
70% ~ 100% What are the benefits? allowed to build on the coil, therefore activating defrost.

Relative Humidity
70%
Heating Indoor Units - adjusts target high pressure Mid Humidity Dual Increased indoor comfort
60% SLC Sensing
Lowers the target high pressure as heating load falls and/or ambient temperature rises. 50% ~ 70%
SLC If comfort cooling is turned off, and the temperature of the leaving air is not What are the benefits?
Raises the target high pressure as heating load rises and/or ambient temperature falls. 50%
raised, when the fan speed is reduced to low speed, there is a potential that
Low Humidity The Intelligent Defrost algorithm increases the VRF system’s heating run-hours
40% 0% ~ 50% occupants located directly under a cassette IDU or supply air registers could
What are the benefits? feel cold air falling on them resulting in a lower overall comfort experience.
and reduces the number of defrost cycles required to maintain optimum
30% heating performance irrelevant of the mode and method of defrost selected.
Enhanced energy savings With comfort cooling turned on, the discharged air temperature is controlled.
20%
When the IDU controller reduces the fan speed, the potential for cold air falling
- Cooling Mode 23°C 25°C 27°C 29°C 31°C 33°C 35°C
on occupants located under the cassette IDU or supply air registers is reduced.
By raising the target low pressure during off-peak cooling operation, the Source : Outdoor Air Temperature
https://energyplus.net/weather
compressor lift is reduced. This slows compressor’s speed which leads to a
Time Portion of Relative Humidity in Summer
Enhanced operating efficiency
decrease in compressor’s power consumption.
(Warsaw, Poland) Raising superheat reduces refrigerant volume flowing through the coil.
- Heating Mode
RH (%) Portion As flow decreases, demand on the compressor decreases and the Conventional
By lowering the target high pressure during off-peak heating operation, the
compressor speed will be reduced, thus saving energy. Defrost
compressor lift is reduced. This slows compressor’s speed which leads to a 70% ~ 100% 8%

decrease in compressor’s power consumption. 50% ~ 70% 45%


Previous Model Frost
0% ~ 50% 47% accumulation begins
Increased indoor comfort Coil
Surface (°C)
Smart Load Control uses one (or two) sensors to measure changing outdoor
weather conditions and prepares the VRF system for operation under
the revised weather conditions before changing conditions impact indoor
Energy Consumption in Cooling Season Repeated on & off
Comfort &
Continuous Cooling
When we compared the energy consumption between SLC (Outdoor air Dew Frost accumulation
comfort. Point (°C)
Temp sensing only) and Dual sensing SLC (Outdoor air Temp and humidity
Cooling load according to Cooling load according to
temperature change humidity change sensing), Dual sensing SLC control can save 6% more energy compared to
SLC. So dual sensing control is more efficient than SLC.
Cooling Load

Cooling Load

Cooling Mode Fan Mode Cooling Mode

EER ※ Indoor unit set up available with Standard III Remote Controller.
MULTI V 5 SLC
MULTI V 5 Dual Sensing SLC 9.4 9.4
9.2
9.0 Preventing cold draft & repeated turn On / Off
8.1 8.6
25°C 30°C 35°C Temperature 40% 60% 80% Relative 7.9
Humidity Improved Indoor Comfort
Latent heat load Sensible heat load 6.9 6.9
※ Constant indoor temp condition 6.0
Indoor temp
Cooling Load
Previous Cooling Capacity LG Intelligent Defrost /
For low temperature, Adjusting capacity Smart Heating
lower load and
to meet load Frost
Actually 31°C ~ 29 ~ 31°C 27 ~ 29°C 25 ~ 27°C 23 ~ 25°C Not cool accumulation begins
capacity are required External Load zone Coil
Required
Cooling
Outdoor Air Temperature Surface (°C)
Internal Load
Capacity
※ This energy simulation was performed in LG internally based on 16HP model.
Temperature & Humidity
Evaporation Temperature
Low Humidity
Power Consumption in Cooling Season
Dew
SLC
Yearly Power Input (kWh) - ODU Point (°C)
Lower load and Comfort
OAT MV4 (Fixed) MV5 SLC MV5 Dual SLC zone Set
capacity need High Humidity Additional Time
temperature
higher evaporation 31 ~ 17 15 13 Spent Heating
Outdoor
temperature Standard Temperature (°C) 29 ~ 31 91 73 62
(Non SLC)
Low Temperature High Temperature 27 ~ 29 183 136 124

Efficiency 25 ~ 27 243 170 165


Too cool
Low Humidity
23 ~ 25 155 110 109 zone ※ Increased heating operation time per day : Up to 17%
SLC
Total 690 (137%) 503 (100%) 474 (94%)
• LG Internal Test result,
Higher evaporation • Test condition (MULTI V 5 vs MULTI V IV, 22HP)
High Humidity
temperature results 6% more energy saving
in higher efficiency
Standard compared to SLC Previous Model Time - Outdoor : 2/1°C, Indoor : 20/15°C
(Non SLC) Outdoor
Temperature (°C)
- Humidity : 83%, Dew Point : -0.5°C
Low Temperature High Temperature

026 / 027
OUTDOOR UNITS _ MULTI V 5 _ KEY FEATURES

INNOVATIVE TECHNOLOGIES INNOVATIVE TECHNOLOGIES

OUTDOOR
UNITS
Variable Path Heat Exchanger Active Refrigerant Control HiPORTM Sub-cooling & Vapor Injection
Optimized system efficiency & continuous heating Stable operation & sustaining most efficient operation Advanced compressor reliability & efficiency Increased heating performance
MULTI V 5 outdoor units (ODU) are manufactured with horizontally The accumulator in the outdoor unit has a storage tank mounted HiPOR™ is an LG trademark that stands for High Pressure Oil Return. MULTI V 5 is equipped with advanced sub-cooler and vapor injection
split ODU coil consisting of two independent circuit sections. inside known as the receiver tank. The receiver tank is equipped It consists of an oil separator, oil drain line between the separator and the control system. The sub-cooler algorithm sub-cools liquid refrigerant

MULTI V 5
Each half of the coil is independently controlled. with inlet and outlet valves that are electronically opened and compressor. HiPOR™ technology enables oil to return directly into the just enough so that it can travel to the farthest IDU in the system
This split coil feature makes it possible for MULTI V 5 to provide closed. Refrigerant is being passed between the accumulator compressor, instead of returning through the refrigerant suction pipe. operating in cooling mode without changing state. During low
continuous heating during defrost. The split coil and valve and the receiver tank on a continuous basis. MULTI V 5 active This prevents energy waste when oil flows between the separator ambient operation down to -25°C (Heating mode), the sub-cooler
arrangement also makes it possible for the MULTI V 5 to change refrigerant control algorithm goal is to minimize the amount of and the compressor. Because the operating pressure in the chamber provides medium temperature refrigerant gas to the compressor’s
the flow path of refrigerant through one of the two coils only, or refrigerant in circulation. The lower the volume in circulation the containing the oil sump of the compressor and the pressure in the oil vapor injection system. When injected into the compression
through both coils in either a series or parallel arrangement. lower the cost to move it around the system and the higher the separator are nearly equal, there is no loss in compressor efficiency. chamber, system mass flow increases which stabilizes the system’s
Based on system pressures, ambient temperature conditions, and stability of the refrigeration cycle. It accomplishes this by constantly suction pressure. In all cases the vapor injection increases the
monitoring the system operating pressures and temperatures and What are the benefits? compressors cycle efficiency and reduces operating cost.
mode of operation, the system controller may modify the selected
a variety of other vital control metrics of the refrigeration cycle. Maximizes reliability and efficiency of the compressor.
path at any time.
When the cycle is out of balance, an adjustment in the amount of Non HiPOR™ HiPOR™ What are the benefits?
circulating refrigerant occurs. Compressor
1 Refrigerant Provides stable refrigeration cycle operation over a wide range of outdoor
What are the benefits? 3 ambient operating conditions.
4
Optimizes system efficiency regardless of operating modes as ambient weather Increases compressor efficiency when compared to systems without vapor
conditions change. What are the benefits? Efficiency Increase
Up to 33%
injection technology.
Customizes the used area of the outdoor unit’s heat exchange surface.
Widens the ambient temperature range at which stable operation occurs. 2

Oil Technology Mechanism


Low ambient cooling and / or light building load Sustains most efficient system operation regardless of outdoor weather 5

conditions, operating mode, or building load.


• Half active High-pressure
Non HiPOR™ HiPOR™
• Lower idle Low pressure High pressure Oil Low pressure High pressure Oil Low-pressure
Cooling Heating Part Load refrigerant Compressor refrigerant Separator refrigerant Compressor refrigerant Separator
1 2 3 4 1 2 3 4

Amount of refrigerant
Full load cooling in receiver
• Upper & lower active 5 Energy loss in suction gas No energy loss in suction gas 5

• Series circuited • LG Internal Test result,


• High velocity refrigerant flow • Test condition - 15Hz Rating Condition : TC = 37.9°C, Te : 7.2°C

Heating - all conditions Smart Oil Management Mid-pressure


(Vapor injection port)
• Upper & Lower active Energy saving, enhanced heating & increased compressor reliability
• Parallel circuited
• Low velocity refrigerant flow MULTI V 5 performs oil return when needed under normal operating
IDU (Heating)
conditions. An oil level sensor is provided in every LG VRF compressor.
If the sensor indicates the compressor oil level is low, the main system
Efficiency
processor is notified that an oil return cycle is necessary. Oil balancing
EEV
Heating cycle occurs every hour and does not hinder system performance.
It balances the oil level deposit between both compressors in multi- High temp
discharge
compressor frames. Older VRF technology protects compressors from
Cooling Non-receiver tank
oil loss based on timed oil return logic because there was no way to
Fixed refrigerant amount Control optimized Refrigerant amount
Maximized efficiency know if the oil level in any one compressor was low. LG’s unique oil level MID-stage Injection
SC
Series Half Active Parallel measuring sensor actively monitors the oil level in each compressor. HEX
Low temp
Efficiency
Continuous Heating
What are the benefits? suction

Fixed refrigerant type Energy savings : fewer oil return cycles eliminate unnecessary energy
Heating performance
consumption.
Increases system heating run-time during winter operation.
Heating ODU Coil
efficiency 3% Increases compressor reliability.

Part load Heating Performance Smart Oil Return


efficiency 10%
On Heating supply On Performance Comparison
Heating performance
Heating Heating Heating

Oil Oil
Non heating Non heating Non-Vapor Injection
Time
27%
Timed oil return logic (Non-oil Sensor) Oil Level Sensor Oil
Effect of partial defrost
Increased heating operation time per day Auto Oil Balancing Up to
: Up to 12% -25°C
• LG Internal Test result,
Cooling
efficiency • Test condition
- without oil level sensor : -25 -20 -15 -10 -5 0 7 11 15
Time Active Refrigerant Control
Non-Partial defrost Refrigerant quantity (kg) every 8 hour oil recovery operation Oil Outdoor temp(°C)
- with oil level sensor : ※ Improved heating performance by 27%.
non oil recovery operation ※ Comparison tested on 10HP model.
Oil Level Sensor

028 / 029
OUTDOOR UNITS _ MULTI V 5 _ KEY FEATURES

INNOVATIVE TECHNOLOGIES DESIGN FLEXIBILITY

OUTDOOR
UNITS
Corrosion Resistance Black Fin Biomimetic Fan One Unified Model Flexible Installation with
Improved durability Maximized performance Heat pump / Heat recovery with one platform Large Capacity Outdoor Units
The black coating with enhanced epoxy resin is applied on the heat The fans in MULTI V 5's outdoor unit have been upgraded to feature LG MULTI V 5 satisfies users’ various needs with just one platform. More flexible design potential & space saving
exchanger for strong protection from various corrosive external a moire pattern similar to that of a clam shell's exterior that help with Heat Pump System works for the sites where either cooling or heating

MULTI V 5
Large capacity outdoor units of MULTI V 5 minimize installation
conditions such as salt contamination and air pollution. noise reduction. At the same time, unlike the fans installed in previous operation is needed, while Heat Recovery System fits perfectly to the
space that spares valuable floor space and significantly decreases
Moreover, the hydrophilic film keeps water from accumulating products that generate separation of flow due to absence of tubercles, sites wherein both the cooling and heating operations are simultaneously
total installed weight. This gives users more flexible design potential
on the heat exchanger’s fin, minimizing moisture buildup and the bumpy back design inspired by the bumps on the humpback needed or locations installed with Hot Water Solution to provide hot
and better use of the saved space.
eventually making it even more corrosion resistant. whale’s flipper is applied as the tubercles on the back side of the fans, water and heating via radiators.
LG Corrosion Resistance solution passed ISO 21207 accelerated increasing wind power by reducing flacking. In addition to the biomimetic 12.25m2
corrosion test conducted by an independent test organization technology-based fans, extended shroud of MULTI V 5 allows more high
and the result has been certified by prestigious global certification static pressure and helps fans to blow higher air volume for efficient
organization, TUV. operation. With wider air guide, discharged air current is stabilized and What are the benefits?
Previous Model
noise level is reduced. MULTI V 5 allows the building previously installed with Heat Pump system to
23%
What are the benefits? switch to the Heat Recovery system (by adding HR boxes and a third pipe) 9.42m2 Reduction
for changing purpose of the building or remodeling reasons via simple piping
This improvement in durability prolongs the product’s lifespan and lowers both What are the benefits?
construction.
the operational and maintenance costs. Based on the biomimetic technology, the fans of MULTI V 5 increased air
flow rate by 10% in comparison to previous model and reduced its power
Heat Pump System
consumption up to 20% when compared with the fan blade design on
MULTI V IV. This eventually results in maximized performance with large capacity. 23% 15%
Reduction Reduction

12.25m2 9.42m2 3,640kg 3,100kg

Previous Model Previous Model

※ Verification of corrosion resistance performance Foot print area Product weight


- Declared by TUV Rheinland
Humpback ※ Comparison basis : 1 Rows of outdoor units 728kW (72.8kW x 10sets) installation case
- Test Method B of ISO21207
Whale Design
- Test condition : Salt contaminated condition
+ severe industrial/traffic
environment(NO2 / SO2)
Clam Shell
Pattern
Slave 1 Master
Outdoor unit Outdoor unit
Wider Operation Range
2 pipes Able to operate at extreme conditions
Hydrophilic film (Water flow)
The Hydrophilic coating minimizes moisture Liquid Pipe
With improved inverter cooling technology, sub-cooling and vapor
buildup on the fin. Gas Pipe injection, MULTI V 5 offers an extended range of heating and cooling
Acryl + Epoxy + Melamine resin operations. It can perform normal heating operations at temperatures
(Corrosion resistant) Indoor unit
as low as -25°C. Cooling operations function at temperatures as low as
The Black coating provides strong protection

Changeover
from corrosion.
-15°C or as high as 48°C making it an adequate solution for specialized

Type
Aluminum fin areas like technical rooms. Moreover, MULTI V 5’s cycle technology
with enhanced durability enables optimal cooling performance at high
temperature that increases up to 48°C.
SST (Salt Spray Test)
Heat Recovery System Outdoor air temp (°C WB)
Test Process Test Result
(5% Area of defects compared to initial)
18°C
15°C
1,950 hr
Process
1,000 hr
1) repeated
Fog
(35°C, 24hr)
95%

Test process is conducted according to ISO 9227. Gold Fin Black Fin
1) Salty water concentration : NaCl aqueous solution (5%) 100% copper material to -20°C
Air flow rate Power consumption
prevent corrosion & refrigerant -25°C
leakage m3/min W 10°C 15°C 20°C 27°C

Heating Indoor air temp(°C DB)


CCT (Cyclic Corrosion Test) Heat Recovery Unit

Test Process Test Result


(5% Area of defects compared to initial) 320 1,500 Outdoor air temp (°C DB)
20%
1,300 hr
10% Slave 1 Master 48°C
290 Outdoor unit Outdoor unit
3 pipes 43°C
500 hr
Fog1) Wet2) 1,200
(35°C, 2hr)
Dry
(70°C, 2hr) (50°C, 2hr)
160%
Previous Model

Process Gold Fin Black Fin

repeated 100% copper material to Indoor unit -10°C


prevent corrosion & refrigerant
※ Test process is conducted according to ISO 14933. leakage Liquid Pipe -15°C
1) Salty water concentration : NaCl aqueous solution (5%) High Pressure Gas Pipe 10°C 14°C 25°C 27°C
Previous Model Previous Fan Design
※ Dry condition changed : 60°C, 4hr → 70°C, 2hr Cooling Indoor air temp (°C WB)
Low Pressure Gas Pipe
2) Deionized water
※ Comparison based on 20HP model ※ Comparison based on air volume of 290m3/min HR unit

030 / 031
Multi V 5 Outdoor Units

OUTDOOR UNITS _ MULTI V 5 _ KEY FEATURES 10. Sound


OUTDOOR UNITS _Levels
MULTI V 5 _ TECHNICAL DATA

USER-FRIENDLY CONTROL 10.1 Sound Pressure Level


Multi
MultiVV
55

OUTDOOR
Outdoor
Outdoor
Units
Units
Position of Sound Pressure Level Measuring Cooling / Heating Operation

UNITS
9.9.Operation
OperationLimits
Limits
Note
Low-Noise Operation Simple Test Run via LGMV Cooling
Cooling
Cooling / Heating
/ Heating
Operation
Operation Heating
For noise sensitive environment Increased overall efficiency in installation • Data is valid at free field condition
• Data
50°C is valid at nominal operating 20°Ccondition
48°C
Unlike the previous model which enables Low-Noise Operation To make sure that the product functions properly, conducting a test run • Sound level will vary depending on
18°C
15°C a range of
45°C
only during night after judgment time, the Low-Noise Operation of is recommended. For previous product, professional engineer who is well- factors such as the construction(acoustic

Outdoor Temperature (°C WB)

MULTI V 5
Outdoor Temperature (°C DB)
40°C
1m
MULTI V 5 can function regardless of the time at the noise sensitive aware of more than 40 different functional settings and more than 200 absorption coefficient) of particular
10°C room in

Range for warming up operation


Range for continuous operation

Range for continuous operation


35°C

Range for pull down operation


areas. When used, the speed of the outdoor unit fans is restricted error codes had to check main parts in order to make sure that the test which
30°C
the equipment is installed
5°C
during normal operation. run had succeeded. With Mobile LGMV of MULTI V 5, fast and accurate 1m
• Sound
25°C
level can be increased in static
auto test run can be executed and the professional installer running the pressure
20°C
mode or used air guide.0°C
Previous Model test can receive test results via email, which shortens installation hours • Data is valid at free field condition.
15°C -5°C
and increases overall efficiency in installation processes. • Data is valid at nominal operating condition.
• Sound level will vary depending on a range of factors such as the
10°C Unit:dB(A)
-10°C
Previous Model absorption coefficient) of particular room
construction (Acoustic Cooinling 5°C
Heating
ARequipment
UM080LisTinstalled.
E5 58.0 59.0
-15°C
which the 0°C

• Sound level can be increased in static pressure mode or used air guide.
ARUM100LTE5 58.0 59.0 -20°C
-5°C
Load
-10°C
ARUM120LTE5 59.0 60.0 -25°C
-15°C
ARUM140LTE5 60.0 10°C 14°C 15°C 20°C 25°C 27°C 30°C61.0 10°C 15°C 20°C 25°C27°C 30°C
Sound level Off Outdoor Units Function
ARUM160LTE5 60.5 Indoor Temperature (°C WB) 61.5 Indoor Temperature (°C DB)
Category Functions MULTI V 5 Note
Note
(Judgment time) Low-noise operation time ARUM180LTE5 61.0 1. 1.
These
These figures
figures
assume
assume thethefollowing
following
operating
operating6conditions:
2.0
conditions:
Variable Path of Outdoor Unit HEX ○ Note
ARUM20HiPOR 0LTETM5(High Pressure Oil Return) ○
62.0 Equivalent
Equivalent
Level
Level
piping
piping
difference:0m
difference:0m
length:7.5m
length:7.5m
1. These figures assume the following operating 6 4.5conditions :
Equivalent piping length : 7.5m
On ARUM22Humidity
Key Refrigerant 0LTE5Sensor ○ 64.5
2. 2.
Range
Range of pull
of pull
down
Level difference : 0m
downoperation:
operation: 65.5
Components If the
If the
relative
relative
humidity
humidity is too
is too
high,
high,
cooling
cooling
capacity
capacity
cancan
be be
decreased
decreased
by by
thethe
sensible
sensible
heat
heat
reduction.
reduction.
2. Range of pull down operation :
6:00 12:00 13:00 18:00 21:00 0:00 6:00 ARUM24Corrosion
0LTE5 Resistance Black Fin ○ 65.0 If the relative humidity is too high, cooling 67capacity
.0 can be decreased by the sensible heat
Highest Start End
outdoor temp ARUM26Oil 0LSensor
TE5 ○ 65.0 reduction.
67.0
3. Warming up operation means that the outdoor unit operates to reach the range
ARUM22Dual 1LTSensing
E5 ○ 61.5 of continuous operating, however it may6not 2.5operate continuously due to safety or
Low Noise Operation ○ protection logic.
ARUM241LTE5 62.0 63.0
High Static Mode of Outdoor Unit Fan ○
ARUM26Partial 1LTEDefrosting
5 ○
6 2.5 63.5
Multi
Multi V 5V 5 Outdoor Units
ARUM28Auto 0LTDust
E5 Removal of Outdoor Unit 62.8 63.8 Outdoor Units

○ 9. Operation
Simultaneous
9. Operation Limits Limits
Cooling / Heating Operation
ARUM30(Fan
Useful Function 0LTreverse
E5 rotation) 63.1 64.1
Indoor Cooling Comfort Mode Based Simultaneous
Cooling Cooling / Heating Operation
ARUM32Outdoor 0LTE5Temperature ○ 63.8 Simultaneous Cooling / Heating
65.8Heating
Operation

ARUM34Smart 0LTELoad
5 Control (SLC) 65.6 30°C
66.6 20°C
Load (Changing indoor discharge air ○
ARUM36temperature
0LTE5 according to load) 66.0 67.8
ARUM38Outdoor 0LTE5Unit Control Refer to Humidity ○ 66.2 68.0 16°C
25°C 675675

Outdoor Temperature (°C WB)


Outdoor Temperature (°C DB)
15°C
Sound level Scheduled setting available ARUM400LTE5 Defrost / Deicing ○ 66.3 20°C 68.1

Range for continuous operation

Range for pull down operation


High Pressure Switch ○
ARUM420LTE5 66.5 68.2 10°C

Range for warming up operation

Range for continuous operation


15°C
Phase Protection ○
Low-noise Low-noise Reliability
ARUM44Restart 0LTE5 Delay (3-minutes) ○
66.8 68.9
10°C
Wi-Fi MV Module
operation operation
ARUM46Self 0LTDiagnosis
E5 ○ 67.8 69.3 5°C
On Off On
ARUM48Soft 0LTStart
E5 ○ 68.0
5°C
70.0
6:00 12:00 18:00 6:00 ARUM50Test 0LTRun
E5Function ○ 67.0 0°C 68.6 0°C
Start End Start End
ARUM520LTE(Simple
AC Ez 5 Controller) 67.1
PQCSZ250S0
-5°C 68.7
AC Ez Touch PACEZA000
Indoor setting available ARUM540LTE5 67.2 68.8 -5°C
AC Smart IV PACS4B000 -10°C
ARUM56AC
Central Controller
0LSmart
TE5 5 PACS5A000
67.4 69.5
ARUM58ACP 0LT(Advanced
E5 Control Platform) IV 68.3
PACP4B000
-15°C
10°C 14°C 15°C 20°C
69.8 -10°C
25°C 27°C 30°C
ARUM60ACP 0LT(Advanced
E5 Control Platform) 5 PACP5A00068.5 70.4 10°C 15°C 20°C 25°C27°C 30°C

ARUM62AC 0LManager
TE5 5 PACM5A00068.6 Note
Note
Indoor Temperature (°C WB) 70.5 Indoor Temperature (°C DB)

ARUM64ACP
BNU (Building 0LTLonworks
E5 PLNWKB000
68.7 1. 1. These
These
Note
figures
figures
Equivalent
assume
assume
piping
thethe following
following
length:7.5m
operating
operating 7conditions:
0.6
conditions:
Network Unit) ACP BACnet PQNFB17C0 Equivalent piping length:7.5m
ARUM660LTE5 68.8 1. These
Level figures
difference:0m
Level difference:0m assume the following 70.6 conditions :
operating
Cycle Monitoring Diagnosis Installation Smart Management Refrigerant Charging Kit PRAC1 2. 2.
Range
Equivalent
Range of pull
of pull
piping
down
down
length : 7.5m
operation:
operation:
InstallationARUM68Variable0LTE5Water Flow Valve Control Kit - 69.0
IfLevel
If the the
relative
difference
relative humidity
humidity
: 0m
is toois too high,
high, cooling
cooling 7can
capacity 1.can
capacity 1be be decreased
decreased by the
by the sensible
sensible heatheat reduction.
reduction.
2. Range of pull down operation :
PDI (Power A R U M 7 0 0LTE5
Standard PPWRDB00069.6 If the relative humidity is too high, cooling 71capacity
.3 can be decreased by the sensible heat
LGMV reduction.
DistributionAIndicator)
RUM72Premium0LTE5 PQNUD1S4069.8 71.8
Cool / Heat AR UM740LTE5
Selector PRDSBM 69.1 70.9
Low Ambient Kit PRVC2
ARUM760LTE5 69.2 70.9
IO Module (ODU Dry Contact) PVDSMN000
Cycle Monitoring LGMV PRCTIL0
Device Mobile LGMV PLGMVW100 677

※ ○ : Applied, - : Not Applied

676676

032 / 033
OUTDOOR UNITS _ MULTI V 5 _ Q&A

MULTI V 5 Q&A MULTI V 5 Q&A

Q1 What are the differences between MULTI V IV and MULTI V 5? Q3 How does MULTI V 5 operate when humidity reference of the dual sensing SLC is that of the outdoor?
A1 Category MULTI V IV H/P (ARUN***LTE4) MULTI V 5 H/P & H/R (ARUM***LTE5) A3 During dual sensing SLC, outdoor unit changes target pressure of the system referring to temperature and humidity in cooling mode.

MULTI V 5
- When the humidity of outdoor side is higher than that of indoor side, outdoor unit will lower target pressure to remove humidity, thus
Vapor Injection ◯ ◯
outdoor unit will consume more energy and indoor will be more cooled compared to SLC operation but more efficiency than normal operation.
HiPORTM ◯ ◯

Smart Oil Control (Oil Level Sensor) ◯ ◯


Outdoor humidity is higher than indoor unit Evaporation temperature & efficiency
Active Refrigerant Control ◯ ◯ Outdoor unit will consume more energy Dual Sensing SLC (RH 70%↑)
Variable Heat Exchanger Circuit ◯ ◯ Relative Humidity >70%

Continuous Heating ◯ ◯ Discharge


SLC under the high humidity condition
Temperature
Smart Load Control ◯ ◯ (˚C)

Dual sensing (Humidity Sensor) - ◯


Normal operation (non -SLC)
Comfort Cooling ◯ ◯
20°C 25°C 30°C 35°C
Ocean Black Fin - ◯ Discharge air will be more cold than normal or
SLC operation Efficiency SLC under the high humidity condition
(%)
Maximum Capacity (1 Unit / 4 Unit) 20 HP / 80 HP 26 HP / 96 HP

Height Difference (ODU ~ IDU / IDU ~ IDU) 110m / 40m 110m / 40m
Normal operation (non -SLC)
Cooling Operating Range (OAT, °CDB) -10 ~ 43 -15 ~ 48
20°C 25°C 30°C 35°C
Heating Operating Range (OAT, °CWB) -25 ~ 18 -25 ~ 18

1 Unit 50 ~ 200% 50 ~ 200% - When the humidity of outdoor side is lower than that of indoor side, outdoor unit will rise target pressure to save energy and keep
Combination ratio of
2 Unit 50 ~ 160% 50 ~ 160% comfort, but indoor humidity will be less removed compared to normal operation.
IDU
3 or 4 Units 50 ~ 130% 50 ~ 130%
Outdoor humidity is lower than indoor unit Evaporation temperature & efficiency
※ ○ : Applied, - : Not Applied
Outdoor unit will consume less energy Dual Sensing SLC (Low Humidity)
30%< Relative Humidity<50%

Discharge SLC under the low humidity condition


Q2 Can MULTI V 5 ODU be connected with the 2 series indoor unit? Temperature
(°C)
A2 Yes, MULTI V 5 ODU can be connected with the 2 series indoor unit. In this case, the ODU DIP Switch No.3 should be “OFF” which is
default setting. Refer to the below table. Normal operation (non -SLC)

ODU IDU Compatibility ODU DIP Switch No. 3 If dip switch setting is not correct Ref. 20°C 25°C 30°C 35°C
Discharge air will be less cold than normal or
SLC operation. Efficiency SLC under the low humidity condition
Can not communicate between Indoor (%)
Must be OFF
Gen. 2 (ARNU*2) ◯ & Outdoor unit
(factory default)
(System will not be operated)

Normal operation (non -SLC)


When Dip Switch No.3 is OFF, 20°C 25°C 30°C 35°C
MULTI V IV Must be ON to enable
Gen. 4 (ARNU*4) ◯ System can be operated, but
MULTI V 5 gen. 4 functions
some function of Gen. 4 is not available
To maximize comfort and energy efficiency, the outdoor unit's humidity sensing can be turned off or a standard remote control can be
When Dip Switch No.3 is ON, installed to sense indoor humidity.
Must be OFF Can not communicate between Gen. Some functions of
Gen. 2 + Gen. 4 ◯
(factory default) 2 Indoor & Outdoor unit (Gen 2 units are not Gen.4 are not available
operated), only Gen 4 Units are operated. Sensing point SLC Setting
CASE 1. Dual Sensing SLC with Outdoor humidity sensor in ODU Setting
※ ○ : Applied, - : Not Applied Outdoor humidity
by humidity sensor (ODU) DIP-SW01

ODU dip switch setting procedure (No.3) 7-Segment

ODU main PCB dip switch is all “OFF” at default state SW04C (X : cancel) Setting summary
SW03C (▶: forward) DIP-SW01 #5 On
(1) Check and make sure that all connected indoor units are 4 series. (ARNU******4.) SW02C (◀ : backward) Func > Fn14 >
(2) Change Dip switch No. 3 from OFF → ON Off, op1 ~ op3
SW01C (●: Confirm/
(3) Push the reset button. Automatic Addressing)
SW01D (reset)
Dip Switch 7 Segment
Indoor humidity CASE 2. Dual Sensing SLC with Indoor humidity sensor in New Standard
ON ON R/C setting (PREMTB100)

Setting summary
Reset Function>
button Smart Load Control>
Off, op1 ~ op3
1 2 3 4 5 6 7 1 2 3 4 5 6 7
1 2 3 4 5 6 7 1 2 3 4 5 6 7
※ User can turn off humidity control in ODU Setting (humidity reference)
<Setting summary> ODU DIP-SW01 #5 On > Func > Fn16 > Off

034 / 035
OUTDOOR UNITS _ MULTI V 5 _ Q&A

MULTI V 5 Q&A MULTI V 5 Q&A

Q4 What is the principle and accuracy of humidity sensor? Other Questions


A4 Total Tolerance (%) = Sensor measurement tolerance (%) + Location of sensor tolerance (%) Item Question Answer

MULTI V 5
Upper electrode
The capacitive measurement principle established and proved itself as a standard in the past. Thin-film polymer
For this principle, the sensor element is built out of a capacitor. The dielectric is a polymer Lower electrode
Fan The static pressure of MULTI V 5 is max. 8 mmAq as MULTI V IV?? Yes, the static pressure of MULTI V 5 is the same as MULTI V IV.
which absorbs or releases water proportional to the relative environmental humidity, and thus Glass substrate

changes the capacitance of the capacitor. This change in capacitance can be measured by an
electronic circuit. For humidity sensors with CMOSensⓇ technology, a “micro-machined” finger
electrode system with different protective and polymer cover layers forms the capacitance for Is the limitation of Compressor max. Hz applied No, the limitation of comp Hz is not applied for default.
Compressor
the sensor chip, and, in addition to providing the sensor property, simultaneously protects the by the capacity of outdoor unit? But, it can be set by option for limitation of max. Hz (or current).
sensor from interference in ways previously not achieved.

Model Humidity Sensor of Outdoor Humidity Sensor of R/Controller


The optimal middle pressure for vapor injection is 1.2 PS*.
VI In case of vapor injection, how much is the middle pressure?
Size (mm) 3 x 3 x 1.1 2.5 x 2.5 x 0.9 *PS : Suction pressure of compressor.

Supply voltage range 2.1 to 3.6 V 2.4 to 5.5 V

RH operating range 0 ~ 100% RH 0 ~ 100% RH By how much is heating capacity increased


VI Generally, the heating capacity is increased up to 15 ~ 20%.
by vapor injection?
T operating range -40 to +125°C (-40 to +257°F) -40 to +125°C (-40 to +257°F)

RH response time 8 sec (tau 63%) 8 sec (tau 63%)

Humidity
Where is Indoor Humidity sensor? It is placed inside of the RS3 remote controller.
Sensor

Remote Does remote controller show the humidity information (Status) as Yes. It shows the current humidity information on screen.
Q5 What is difference in refrigerant piping connection between heat pump and heat recovery? Controller well? (for RS3 Only) But has no function to control the humidity.
A5 From MULTI V 5, Low pressure gas pipe in heat pump operation changes to high pressure gas pipe in heat recovery operation
due to internal cycle. So for heat pump cycle, no. 1, 3 pipe should be connected and for heat recovery operation, No. 1, 2, 3 pipe is
connected. (For the heat pump operation, DO NOT connect No.2 pipe)
Remote Is it possible to connect the local humidity sensor with Remote No. All of RS3 remote controller can not be connected
Controller controller (RS3)? with local humidity sensor.

Heat Recovery Installation Heat Pump Installation

SLC Does dual sensing SLC function control the humidity ratio? No. There is no control of humidity ratio.
Close Close

Close Is SLC fully used on Eurovent? Isn’t humidity fixed


Close SLC Eurovent (RH 47%) and AHRI (RH 51%) have fixed humidity test condition.
1 Close 2 3 1 2 3 for the test? What about AHRI?
Close
High Pressure

Comfort cooling need super heating controlled and Comfort heating need sub
Low Pressure

Comfort
Liquid pipe

Liquid pipe

Why is not the comfort heating applied in product? cooling controlled. In case of controlling EEV for sub cooling, noise and stable
Gas pipe

Gas pipe

Gas pipe

Cooling
operation may be affected and critical.

Reducer for Gas Pipe

8HP 9.52 19.05 15.88 8HP 9.52 No Use 19.05 15.88 19.05 Does the IDU – Central controller direct connection for
Installation No, it is not possible.
10HP 9.52 22.2 19.05 10HP 9.52 No Use 22.2 communication cable is possible? (Flat connection)
19.05 22.2

20HP 15.88 28.58 22.2 20HP 15.88 No Use 28.58 22.2 28.58

※ For using as Heat Pump, Reducer for Gas pipe should be used.
Reducer is included in outdoor unit.

036 / 037
1,000m
HEAT PUMP TOTAL PIPING LENGTH 225m
Longest Piping Length

- Air Cooled VRF Heat Pump

between ODU ~ IDU

MULTI V 5
Height Difference
- 22.4kW ~ 268.8kW (Cooling capacity based)
- 3Ø, 380 ~ 415V, 50Hz

110m
- Top discharge outdoor unit

TOTAL PIPING LENGTH

between IDU ~ IDU


Height Difference
40m
How does it work?
Dual Sensing

Energy savings

Partial Defrost
Reliability

Designed
Design
For
For
The Ultimate Low noise
The Ultimate

Advanced performance

038 / 039
OUTDOOR UNITS _ MULTI V 5 _ SPECIFICATION

MULTI V 5 HEAT PUMP MULTI V 5 HEAT PUMP

OUTDOOR
UNITS
ARUN080LTE5 / ARUN100LTE5 ARUN160LTE5 / ARUN180LTE5
ARUN120LTE5 / ARUN140LTE5 ARUN200LTE5 / ARUN220LTE5

MULTI V 5
HP 8 10 12 14 HP 16 18 20 22

Combination Unit ARUN080LTE5 ARUN100LTE5 ARUN120LTE5 ARUN140LTE5 Combination Unit ARUN160LTE5 ARUN180LTE5 ARUN200LTE5 ARUN220LTE5
Model Name Model Name
Independent Unit ARUN080LTE5 ARUN100LTE5 ARUN120LTE5 ARUN140LTE5 Independent Unit ARUN160LTE5 ARUN180LTE5 ARUN200LTE5 ARUN220LTE5
kW 22.4 28.0 33.6 39.2 kW 44.8 50.4 56.0 61.6
Cooling (Rated) Cooling (Rated)
Btu/h 76,400 95,500 114,600 133,800 Btu/h 152,900 172,000 191,100 210,200
Capacity Capacity
kW 25.2 31.5 37.8 44.1 kW 50.4 56.7 63.0 69.3
Heating (Rated) Heating (Rated)
Btu/h 86,000 107,500 129,000 150,500 Btu/h 172,000 193,500 215,000 236,500
Cooling (Rated) kW 4.59 5.70 7.91 9.12 Cooling (Rated) kW 10.80 10.96 12.31 14.84
Input Input
Heating (Rated) kW 4.74 5.78 8.06 9.78 Heating (Rated) kW 11.59 12.06 15.52 17.54
EER (Rated) 4.88 4.91 4.25 4.30 EER (Rated) 4.15 4.60 4.55 4.15
COP (Rated) 5.32 5.45 4.69 4.51 COP (Rated) 4.35 4.70 4.06 3.95
Power Factor Rated - 0.93 0.93 0.93 0.93 Power Factor Rated - 0.93 0.93 0.93 0.93
Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray
Exterior Exterior
RAL code NL503K / NA507K NL503K / NA507K NL503K / NA507K NL503K / NA507K RAL code NL503K / NA507K NL503K / NA507K NL503K / NA507K NL503K / NA507K
Heat Exchanger Wide Louver Plus Wide Louver Plus Wide Louver Plus Wide Louver Plus Heat Exchanger Wide Louver Plus Wide Louver Plus Wide Louver Plus Wide Louver Plus
Compressor Motor Output x Number W x No. 5,300 x 1 5,300 x 1 5,300 x 1 5,300 x 1 Compressor Motor Output x Number W x No. 5,300 x 1 5,300 x 1 + 4,200 x 1 5,300 x 2 5,300 x 2
Type Propeller fan Propeller fan Propeller fan Propeller fan Type Propeller fan Propeller fan Propeller fan Propeller fan
Motor Output x Number W 1,200 x 1 1,200 x 1 1,200 x 1 900 x 2 Motor Output x Number W 900 x 2 900 x 2 900 x 2 900 x 2
m3/min 240 x 1 240 x 1 240 x 1 320 x 1 m3/min 320 x 1 320 x 1 320 x 1 320 x 1
Air Flow Rate (High) Air Flow Rate (High)
Fan ft3/min 8,476 x 1 8,476 x 1 8,476 x 1 11,301 x 1 Fan ft3/min 11,301 x 1 11,301 x 1 11,301 x 1 11,301 x 1
External Static Pressure (Max, Pa) 80 80 80 80 External Static Pressure (Max, Pa) 80 80 80 80
Drive DC INVERTER DC INVERTER DC INVERTER DC INVERTER Drive DC INVERTER DC INVERTER DC INVERTER DC INVERTER
Discharge Side / Top TOP TOP TOP TOP Discharge Side / Top TOP TOP TOP TOP
Pipe Liquid Pipe mm (inch) 9.52 (3/8) 9.52 (3/8) 12.7 (1/2) 12.7 (1/2) Pipe Liquid Pipe mm (inch) 12.7 (1/2) 15.88 (5/8) 15.88 (5/8) 15.88 (5/8)
Connections Gas Pipe mm (inch) 19.05 (3/4) 22.2 (7/8) 28.58 (1-1/8) 28.58 (1-1/8) Connections Gas Pipe mm (inch) 28.58 (1-1/8) 28.58 (1-1/8) 28.58 (1-1/8) 28.58 (1-1/8)
Dimensions (W x H x D) mm x No. (930 x 1,690 x 760) x 1 (930 x 1,690 x 760) x 1 (930 x 1,690 x 760) x 1 (1,240 x 1,690 x 760) x 1 Dimensions (W x H x D) mm x No. (1,240 x 1,690 x 760) x 1 (1,240 x 1,690 x 760) x 1 (1,240 x 1,690 x 760) x 1 (1,240 x 1,690 x 760) x 1
kg 188 x 1 188 x 1 188 x 1 220 x 1 kg 220 x 1 260 x 1 274 x 1 274 x 1
Net Weight Net Weight
lbs 448 x 1 448 x 1 448 x 1 507 x 1 lbs 507 x 1 595 x 1 635 x 1 635 x 1
Sound Cooling dB(A) 58.0 58.0 59.0 60.0 Sound Cooling dB(A) 60.5 61.0 62.0 64.5
Pressure Level Heating dB(A) 59.0 59.0 60.0 61.0 Pressure Level Heating dB(A) 61.5 62.0 64.5 65.5
Sound Cooling dB(A) 78.0 78.0 79.0 82.0 Sound Cooling dB(A) 83.0 85.0 86.0 86.0
Power Level Heating dB(A) 79.0 79.0 80.0 84.0 Power Level Heating dB(A) 85.0 86.0 87.0 88.0
mm2 x No. mm2 x No.
Communication Cable 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C Communication Cable 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C
(VCTF-SB) (VCTF-SB)
Refrigerant name R410A R410A R410A R410A Refrigerant name R410A R410A R410A R410A
Precharged Amount kg 10.0 10.0 10.0 13.0 Precharged Amount kg 13.0 13.0 14.0 14.0
Refrigerant in factory lbs 22.0 22.0 22.0 28.7 Refrigerant in factory lbs 28.7 28.7 30.9 30.9
t-CO2eq 20.9 20.9 20.9 27.1 t-CO2eq 27.1 27.1 29.2 29.2
Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50
Power Supply Ø, V, Hz Power Supply Ø, V, Hz
3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60
Number of maximum connectable indoor units 13 (20) 16 (25) 20 (30) 23 (35) Number of maximum connectable indoor units 26 (40) 29 (45) 32 (50) 35 (56)

Note Note
1. Due to our policy of innovation some specifications may be changed without notification. 1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical work and design. 2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Power factor could vary less than ±1% according to the operating conditions. 3. Power factor could vary less than ±1% according to the operating conditions.
4. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard. 4. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard. Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard.
Therefore, these values can be increased owing to ambient conditions during operation. Therefore, these values can be increased owing to ambient conditions during operation.
5. Performances are based on the following conditions : 5. Performances are based on the following conditions :
*Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB *Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
*Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB *Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is Zero. Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is Zero.
6. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination. 6. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination.
The recommended ratio is 130%. The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases. (R410A, GWP(Global warming potential) = 2087.5) 7. This product contains Fluorinated greenhouse gases. (R410A, GWP(Global warming potential) = 2087.5)

040 / 041
OUTDOOR UNITS _ MULTI V 5 _ SPECIFICATION

MULTI V 5 HEAT PUMP MULTI V 5 HEAT PUMP

OUTDOOR
UNITS
ARUN240LTE5 / ARUN260LTE5
ARUN261LTE5 / ARUN280LTE5
ARUN300LTE5 / ARUN320LTE5

MULTI V 5
HP 24 26

HP 26' 28 30 32
Combination Unit ARUN261LTE5 ARUN280LTE5 ARUN300LTE5 ARUN320LTE5
Model Name ARUN140LTE5 ARUN160LTE5 ARUN180LTE5 ARUN200LTE5
Independent Unit
ARUN120LTE5 ARUN120LTE5 ARUN120LTE5 ARUN120LTE5
kW 72.8 78.4 84.0 89.6
Combination Unit ARUN240LTE5 ARUN260LTE5 Cooling (Rated)
Model Name Btu/h 248,400 267,500 286,600 305,700
Independent Unit ARUN240LTE5 ARUN260LTE5 Capacity
kW 81.9 88.2 94.5 100.8
kW 67.2 72.8 Heating (Rated)
Cooling (Rated) Btu/h 279,500 301,000 322,500 344,000
Btu/h 229,300 248,400 Cooling (Rated) kW 17.02 18.70 18.86 20.21
Capacity Input
kW 74.3 74.3 Heating (Rated) kW 17.84 19.65 20.12 23.58
Heating (Rated)
Btu/h 253,400 253,400 EER (Rated) 4.28 4.19 4.45 4.43
Cooling (Rated) kW 16.76 19.41 COP (Rated) 4.59 4.49 4.70 4.28
Input
Heating (Rated) kW 18.85 19.49 Power Factor Rated - 0.93 0.93 0.93 0.93
EER (Rated) 4.01 3.75 Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray
COP (Rated) 3.94 3.81 Exterior
RAL code NL503K / NA507K NL503K / NA507K NL503K / NA507K NL503K / NA507K
Power Factor Rated - 0.93 0.93 Heat Exchanger Wide Louver Plus Wide Louver Plus Wide Louver Plus Wide Louver Plus
Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray Compressor Motor Output x Number W x No. 5,300 x 2 5,300 x 2 (5,300 x 2) + (4,200 x 1) (5,300 x 2) + (4,200 x 1)
Exterior
RAL code NL503K / NA507K NL503K / NA507K Type Propeller fan Propeller fan Propeller fan Propeller fan
Heat Exchanger Wide Louver Plus Wide Louver Plus Motor Output x Number W (900 x 2) + (1,200 x 1) (900 x 2) + (1,200 x 1) (900 x 2) + (1,200 x 1) (900 x 2) + (1,200 x 1)
Compressor Motor Output x Number W x No. 5,300 x 2 5,300 x 2 m3/min (320 x 1) + (240 x 1) (320 x 1) + (240 x 1) (320 x 1) + (240 x 1) (320 x 1) + (240 x 1)
Type Propeller fan Propeller fan Air Flow Rate (High)
Fan ft3/min (11,301 x 1) + (8,476 x 1) (11,301 x 1) + (8,476 x 1) (11,301 x 1) + (8,476 x 1) (11,301 x 1) + (8,476 x 1)
Motor Output x Number W 900 x 2 900 x 2 External Static Pressure (Max, Pa) 80 80 80 80
m3/min 320 x 1 320 x 1 Drive DC INVERTER DC INVERTER DC INVERTER DC INVERTER
Air Flow Rate (High)
Fan ft /min
3
11,301 x 1 11,301 x 1 Discharge Side / Top TOP TOP TOP TOP
External Static Pressure (Max, Pa) 80 80 Liquid Pipe mm (inch) 19.05 (3/4) 19.05 (3/4) 19.05 (3/4) 19.05 (3/4)
Pipe
Drive DC INVERTER DC INVERTER Connections Gas Pipe mm (inch) 34.9 (1-3/8) 34.9 (1-3/8) 34.9 (1-3/8) 34.9 (1-3/8)
Discharge Side / Top TOP TOP (1,240 x 1,690 x 760) x 1 (1,240 x 1,690 x 760) x 1 (1,240 x 1,690 x 760) x 1 (1,240 x 1,690 x 760) x 1
Dimensions (W x H x D) mm x No.
Pipe Liquid Pipe mm (inch) 15.88 (5/8) 19.05 (3/4) + (930 x 1,690 x 760) x 1 + (930 x 1,690 x 760) x 1 + (930 x 1,690 x 760) x 1 + (930 x 1,690 x 760) x 1
Connections Gas Pipe mm (inch) 34.9 (1-3/8) 34.9 (1-3/8) kg (220 x 1) + (188 x 1) (220 x 1) + (188 x 1) (260 x 1) + (188 x 1) (274 x 1) + (188 x 1)
Net Weight
Dimensions (W x H x D) mm x No. (1,240 x 1,690 x 760) x 1 (1,240 x 1,690 x 760) x 1 lbs (507 x 1) + (448 x 1) (507 x 1) + (448 x 1) (595 x 1) + (448 x 1) (635 x 1) + (448 x 1)
kg 276 x 1 276 x 1 Sound Cooling dB(A) 62.5 62.8 63.1 63.8
Net Weight Pressure Level Heating
lbs 639 x 1 639 x 1 dB(A) 63.5 63.8 64.1 65.8
Sound Cooling dB(A) 65.0 65.0 Sound Cooling dB(A) 83.8 84.5 86.0 86.8
Pressure Level Heating dB(A) 67.0 67.0 Power Level Heating dB(A) 85.5 86.2 87.0 87.8
Sound Cooling dB(A) 88.0 88.0 mm2 x No.
Communication Cable 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C
Power Level (VCTF-SB)
Heating dB(A) 90.0 90.0
Refrigerant name R410A R410A R410A R410A
mm x No.2
Communication Cable 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C kg 13.0 + 10.0 13.0 + 10.0 13.0 + 10.0 14.0 + 10.0
(VCTF-SB) Precharged Amount
Refrigerant name R410A R410A Refrigerant in factory lbs 28.7 + 22.0 28.7 + 22.0 28.7 + 22.0 30.9 + 22.0
Precharged Amount kg 16.0 16.0 t-CO2eq 48.0 48.0 48.0 50.1
Refrigerant in factory lbs 35.3 35.3 Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
t-CO2eq 33.4 33.4 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50
Power Supply Ø, V, Hz
Control Electronic Expansion Valve Electronic Expansion Valve 3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60
3, 380-415, 50 3, 380-415, 50 Number of maximum connectable indoor units 42 (52) 45 (56) 49 (60) 52 (64)
Power Supply Ø, V, Hz
3, 380, 60 3, 380, 60
Number of maximum connectable indoor units 39 (61) 42 (64)

Note Note
1. Due to our policy of innovation some specifications may be changed without notification. 1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical work and design. 2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Power factor could vary less than ±1% according to the operating conditions. 3. Power factor could vary less than ±1% according to the operating conditions.
4. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard. 4. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard. Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard.
Therefore, these values can be increased owing to ambient conditions during operation. Therefore, these values can be increased owing to ambient conditions during operation.
5. Performances are based on the following conditions : 5. Performances are based on the following conditions :
*Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB *Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
*Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB *Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is Zero. Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is Zero.
6. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination. 6. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination.
The recommended ratio is 130%. The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases. (R410A, GWP(Global warming potential) = 2087.5) 7. This product contains Fluorinated greenhouse gases. (R410A, GWP(Global warming potential) = 2087.5)

042 / 043
OUTDOOR UNITS _ MULTI V 5 _ SPECIFICATION

MULTI V 5 HEAT PUMP MULTI V 5 HEAT PUMP

OUTDOOR
UNITS
ARUN340LTE5 / ARUN360LTE5 ARUN420LTE5 / ARUN440LTE5
ARUN380LTE5 / ARUN400LTE5 ARUN460LTE5 / ARUN480LTE5

MULTI V 5
HP 34 36 38 40 HP 42 44 46 48
Combination Unit ARUN340LTE5 ARUN360LTE5 ARUN380LTE5 ARUN400LTE5 Combination Unit ARUN420LTE5 ARUN440LTE5 ARUN460LTE5 ARUN480LTE5
Model Name ARUN220LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 Model Name ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5
Independent Unit Independent Unit
ARUN120LTE5 ARUN120LTE5 ARUN140LTE5 ARUN160LTE5 ARUN180LTE5 ARUN200LTE5 ARUN220LTE5 ARUN240LTE5
kW 95.2 100.8 106.4 112.0 kW 117.6 123.2 128.8 134.4
Cooling (Rated) Cooling (Rated)
Btu/h 324,800 343,900 363,100 382,200 Btu/h 401,300 420,400 439,500 458,600
Capacity Capacity
kW 107.1 112.1 118.4 124.7 kW 131.0 137.3 143.6 148.5
Heating (Rated) Heating (Rated)
Btu/h 365,500 382,400 403,900 425,400 Btu/h 446,900 468,400 489,900 506,800
Cooling (Rated) kW 22.75 24.66 25.87 27.55 Cooling (Rated) kW 27.71 29.07 31.60 33.52
Input Input
Heating (Rated) kW 25.60 26.91 28.62 30.43 Heating (Rated) kW 30.91 34.36 36.39 37.69
EER (Rated) 4.18 4.09 4.11 4.06 EER (Rated) 4.24 4.24 4.08 4.01
COP (Rated) 4.18 4.16 4.13 4.10 COP (Rated) 4.24 3.99 3.94 3.94
Power Factor Rated - 0.93 0.93 0.93 0.93 Power Factor Rated - 0.93 0.93 0.93 0.93
Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray
Exterior Exterior
RAL code NL503K / NA507K NL503K / NA507K NL503K / NA507K NL503K / NA507K RAL code NL503K / NA507K NL503K / NA507K NL503K / NA507K NL503K / NA507K
Heat Exchanger Wide Louver Plus Wide Louver Plus Wide Louver Plus Wide Louver Plus Heat Exchanger Wide Louver Plus Wide Louver Plus Wide Louver Plus Wide Louver Plus
Compressor Motor Output x Number W x No. 5,300 x 3 5,300 x 3 5,300 x 3 5,300 x 3 Compressor Motor Output x Number W x No. (5,300 x 3) + (4,200 x 1) 5,300 x 4 5,300 x 4 5,300 x 4
Type Propeller fan Propeller fan Propeller fan Propeller fan Type Propeller fan Propeller fan Propeller fan Propeller fan
Motor Output x Number W (900 x 2) + (1,200 x 1) (900 x 2) + (1,200 x 1) 900 x 4 900 x 4 Motor Output x Number W 900 x 4 900 x 4 900 x 4 900 x 4
m3/min (320 x 1) + (240 x 1) (320 x 1) + (240 x 1) 320 x 2 320 x 2 m3/min 320 x 2 320 x 2 320 x 2 320 x 2
Air Flow Rate (High) Air Flow Rate (High)
Fan ft3/min (11,301 x 1) + (8,476 x 1) (11,301 x 1) + (8,476 x 1) 11,301 x 2 11,301 x 2 Fan ft3/min 11,301 x 2 11,301 x 2 11,301 x 2 11,301 x 2
External Static Pressure (Max, Pa) 80 80 80 80 External Static Pressure (Max, Pa) 80 80 80 80
Drive DC INVERTER DC INVERTER DC INVERTER DC INVERTER Drive DC INVERTER DC INVERTER DC INVERTER DC INVERTER
Discharge Side / Top TOP TOP TOP TOP Discharge Side / Top TOP TOP TOP TOP
Pipe Liquid Pipe mm (inch) 19.05 (3/4) 19.05 (3/4) 19.05 (3/4) 19.05 (3/4) Pipe Liquid Pipe mm (inch) 19.05 (3/4) 19.05 (3/4) 19.05 (3/4) 19.05 (3/4)
Connections Gas Pipe mm (inch) 34.9 (1-3/8) 41.3 (1-5/8) 41.3 (1-5/8) 41.3 (1-5/8) Connections Gas Pipe mm (inch) 41.3 (1-5/8) 41.3 (1-5/8) 41.3 (1-5/8) 41.3 (1-5/8)
(1,240 x 1,690 x 760) x 1 (1,240 x 1,690 x 760) x 1 Dimensions (W x H x D) mm x No. (1,240 x1,690 x 760) x 2 (1,240 x1,690 x 760) x 2 (1,240 x1,690 x 760) x 2 (1,240 x1,690 x 760) x 2
Dimensions (W x H x D) mm x No. (1,240 x1,690 x 760) x 2 (1,240 x1,690 x 760) x 2
+ (930 x 1,690 x 760) x 1 + (930 x 1,690 x 760) x 1
kg (276 x 1) + (260 x 1) (276 x 1) + (274 x 1) (276 x 1) + (274 x 1) 276 x 2
kg (274 x 1) + (188 x 1) (276 x 1) + (188 x 1) (276 x 1) + (220 x 1) (276 x 1) + (220 x 1) Net Weight
Net Weight lbs (639 x 1) + (595 x 1) (639 x 1) + (635 x 1) (639 x 1) + (635 x 1) 639 x 2
lbs (635 x 1) + (448 x 1) (639 x 1) + (448 x 1) (639 x 1) + (507 x 1) (639 x 1) + (507 x 1)
Sound Cooling dB(A) 66.5 66.8 67.8 68.0
Sound Cooling dB(A) 65.6 66.0 66.2 66.3 Pressure Level Heating dB(A) 68.2 68.9 69.3 70.0
Pressure Level Heating dB(A) 66.6 67.8 68.0 68.1
Sound Cooling dB(A) 89.8 90.1 90.1 91.0
Sound Cooling dB(A) 86.8 88.5 89.0 89.2 Power Level Heating dB(A) 91.5 91.8 92.1 93.0
Power Level Heating dB(A) 88.6 90.4 91.0 91.2
mm2 x No.
mm x No.
2 Communication Cable 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C
Communication Cable 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C (VCTF-SB)
(VCTF-SB)
Refrigerant name R410A R410A R410A R410A
Refrigerant name R410A R410A R410A R410A
Precharged Amount kg 16.0 + 13.0 16.0 + 14.0 16.0 + 14.0 16.0 + 16.0
Precharged Amount kg 14.0 + 10.0 16.0 + 10.0 16.0 + 13.0 16.0 + 13.0 in factory
Refrigerant lbs 35.3 + 28.7 35.3 + 30.9 35.3 + 30.9 35.3 + 35.3
Refrigerant in factory lbs 30.9 + 22.0 35.3 + 22.0 35.3 + 28.7 35.3 + 28.7
t-CO2eq 60.5 62.6 62.6 66.8
t-CO2eq 50.1 54.3 60.5 60.5
Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50
3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 Power Supply Ø, V, Hz
Power Supply Ø, V, Hz 3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60
3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60
Number of maximum connectable indoor units 64 64 64 64
Number of maximum connectable indoor units 55 (64) 58 (64) 61 (64) 64

Note Note
1. Due to our policy of innovation some specifications may be changed without notification. 1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical work and design. 2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Power factor could vary less than ±1% according to the operating conditions. 3. Power factor could vary less than ±1% according to the operating conditions.
4. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard. 4. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard. Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard.
Therefore, these values can be increased owing to ambient conditions during operation. Therefore, these values can be increased owing to ambient conditions during operation.
5. Performances are based on the following conditions : 5. Performances are based on the following conditions :
*Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB *Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
*Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB *Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is Zero. Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is Zero.
6. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination. 6. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination.
The recommended ratio is 130%. The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases. (R410A, GWP(Global warming potential) = 2087.5) 7. This product contains Fluorinated greenhouse gases. (R410A, GWP(Global warming potential) = 2087.5)

044 / 045
OUTDOOR UNITS _ MULTI V 5 _ SPECIFICATION

MULTI V 5 HEAT PUMP MULTI V 5 HEAT PUMP

OUTDOOR
UNITS
ARUN500LTE5 / ARUN520LTE5 ARUN580LTE5 / ARUN600LTE5
ARUN540LTE5 / ARUN560LTE5 ARUN620LTE5 / ARUN640LTE5

MULTI V 5
HP 50 52 54 56 HP 58 60 62 64
Combination Unit ARUN500LTE5 ARUN520LTE5 ARUN540LTE5 ARUN560LTE5 Combination Unit ARUN580LTE5 ARUN600LTE5 ARUN620LTE5 ARUN640LTE5
Model Name ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5
Model Name
Independent Unit ARUN140LTE5 ARUN160LTE5 ARUN180LTE5 ARUN200LTE5 Independent Unit ARUN220LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5
ARUN120LTE5 ARUN120LTE5 ARUN120LTE5 ARUN120LTE5 ARUN120LTE5 ARUN120LTE5 ARUN140LTE5 ARUN160LTE5
kW 140.0 145.6 151.2 156.8 kW 162.4 168.0 173.6 179.2
Cooling (Rated) Cooling (Rated)
Btu/h 477,700 496,800 515,900 535,000 Btu/h 554,100 573,200 592,400 611,500
Capacity Capacity
kW 156.2 162.5 168.8 175.1 kW 181.4 186.3 192.6 198.9
Heating (Rated) Heating (Rated)
Btu/h 532,900 554,400 575,900 597,400 Btu/h 618,900 635,800 657,300 678,800
Cooling (Rated) kW 33.78 35.46 35.62 36.97 Cooling (Rated) kW 39.51 41.42 42.63 44.31
Input Input
Heating (Rated) kW 36.68 38.49 38.97 42.42 Heating (Rated) kW 44.45 45.75 47.47 49.28
EER (Rated) 4.14 4.11 4.24 4.24 EER (Rated) 4.11 4.06 4.07 4.04
COP (Rated) 4.26 4.22 4.33 4.13 COP (Rated) 4.08 4.07 4.06 4.04
Power Factor Rated - 0.93 0.93 0.93 0.93 Power Factor Rated - 0.93 0.93 0.93 0.93
Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray
Exterior Exterior
RAL code NL503K / NA507K NL503K / NA507K NL503K / NA507K NL503K / NA507K RAL code NL503K / NA507K NL503K / NA507K NL503K / NA507K NL503K / NA507K
Heat Exchanger Wide Louver Plus Wide Louver Plus Wide Louver Plus Wide Louver Plus Heat Exchanger Wide Louver Plus Wide Louver Plus Wide Louver Plus Wide Louver Plus
Compressor Motor Output x Number W x No. 5,300 x 4 5,300 x 4 (5,300 x 4) + (4,200 x 1) 5,300 x 5 Compressor Motor Output x Number W x No. 5,300 x 5 5,300 x 5 5,300 x 5 5,300 x 5
Type Propeller fan Propeller fan Propeller fan Propeller fan Type Propeller fan Propeller fan Propeller fan Propeller fan
Motor Output x Number W (900 x 4) + (1,200 x 1) (900 x 4) + (1,200 x 1) (900 x 4) + (1,200 x 1) (900 x 4) + (1,200 x 1) Motor Output x Number W (900 x 4) + (1,200 x 1) (900 x 4) + (1,200 x 1) 900 x 6 900 x 6
m3/min (320 x 2) + (240 x 1) (320 x 2) + (240 x 1) (320 x 2) + (240 x 1) (320 x 2) + (240 x 1) m3/min (320 x 2) + (240 x 1) (320 x 2) + (240 x 1) 320 x 3 320 x 3
Air Flow Rate (High) Air Flow Rate (High)
Fan ft3/min (11,301 x 2) + (8,476 x 1) (11,301 x 2) + (8,476 x 1) (11,301 x 2) + (8,476 x 1) (11,301 x 2) + (8,476 x 1) Fan ft3/min (11,301 x 2) + (8,476 x 1) (11,301 x 2) + (8,476 x 1) 11,301 x 3 11,301 x 3
External Static Pressure (Max, Pa) 80 80 80 80 External Static Pressure (Max, Pa) 80 80 80 80
Drive DC INVERTER DC INVERTER DC INVERTER DC INVERTER Drive DC INVERTER DC INVERTER DC INVERTER DC INVERTER
Discharge Side / Top TOP TOP TOP TOP Discharge Side / Top TOP TOP TOP TOP
Pipe Liquid Pipe mm (inch) 19.05 (3/4) 19.05 (3/4) 19.05 (3/4) 19.05 (3/4) Pipe Liquid Pipe mm (inch) 19.05 (3/4) 19.05 (3/4) 22.2 (7/8) 22.2 (7/8)
Connections Gas Pipe mm (inch) 41.3 (1-5/8) 41.3 (1-5/8) 41.3 (1-5/8) 41.3 (1-5/8) Connections Gas Pipe mm (inch) 41.3 (1-5/8) 41.3 (1-5/8) 44.5 (1-3/4) 44.5 (1-3/4)
(1,240 x 1,690 x 760) x 2 (1,240 x 1,690 x 760) x 2 (1,240 x 1,690 x 760) x 2 (1,240 x 1,690 x 760) x 2 (1,240 x 1,690 x 760) x 2 (1,240 x 1,690 x 760) x 2
Dimensions (W x H x D) mm x No. Dimensions (W x H x D) mm x No. (1,240 x1,690 x 760) x 3 (1,240 x1,690 x 760) x 3
+ (930 x 1,690 x 760) x 1 + (930 x 1,690 x 760) x 1 + (930 x 1,690 x 760) x 1 + (930 x 1,690 x 760) x 1 + (930 x 1,690 x 760) x 1 + (930 x 1,690 x 760) x 1
(276 x 1) + (220 x 1) + (276 x 1) + (220 x 1) + (276 x 1) + (260 x 1) + (276 x 1) + (274 x 1) + (276 x 1) + (274 x 1) +
kg kg (276 x 2) + (188 x 1) (276 x 2) + (220 x 1) (276 x 2) + (220 x 1)
(188 x 1) (188 x 1) (188 x 1) (188 x 1) (188 x 1)
Net Weight Net Weight
(639 x 1) + (507 x 1) + (639 x 1) + (507 x 1) + (639 x 1) + (595 x 1) + (639 x 1) + (635 x 1) + (639 x 1) + (635 x 1) +
lbs lbs (639 x 2) + (448 x 1) (639 x 2) + (507 x 1) (639 x 2) + (507 x 1)
(448 x 1) (448 x 1) (448 x 1) (448 x 1) (448 x 1)
Sound Cooling dB(A) 67.0 67.1 67.2 67.4 Sound Cooling dB(A) 68.3 68.5 68.6 68.7
Pressure Level Heating dB(A) 68.6 68.7 68.8 69.5 Pressure Level Heating dB(A) 69.8 70.4 70.5 70.6
Sound Cooling dB(A) 89.4 89.6 90.1 90.4 Sound Cooling dB(A) 90.4 91.3 91.5 91.6
Power Level Heating dB(A) 91.3 91.5 91.8 92.0 Power Level Heating dB(A) 92.4 93.2 93.5 93.6
mm2 x No. mm2 x No.
Communication Cable 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C Communication Cable 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C
(VCTF-SB) (VCTF-SB)
Refrigerant name R410A R410A R410A R410A Refrigerant name R410A R410A R410A R410A
Precharged Amount kg 16.0 + 13.0 + 10.0 16.0 + 13.0 + 10.0 16.0 + 13.0 + 10.0 16.0 + 14.0 + 10.0 Precharged Amount kg 16.0 + 14.0 + 10.0 16.0 + 16.0 + 10.0 16.0 + 16.0 + 13.0 16.0 + 16.0 + 13.0
Refrigerant in factory lbs 35.3 + 28.7 + 22.0 35.3 + 28.7 + 22.0 35.3 + 28.7 + 22.0 35.3 + 30.9 + 22.0 Refrigerant in factory lbs 35.3 + 30.9 + 22.0 35.3 + 35.3 + 22.0 35.3 + 35.3 + 28.7 35.3 + 35.3 + 28.7
t-CO2eq 81.4 81.4 81.4 83.5 t-CO2eq 83.5 87.7 93.9 93.9
Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50
Power Supply Ø, V, Hz Power Supply Ø, V, Hz
3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60
Number of maximum connectable indoor units 64 64 64 64 Number of maximum connectable indoor units 64 64 64 64

Note Note
1. Due to our policy of innovation some specifications may be changed without notification. 1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical work and design. 2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Power factor could vary less than ±1% according to the operating conditions. 3. Power factor could vary less than ±1% according to the operating conditions.
4. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard. 4. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard. Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard.
Therefore, these values can be increased owing to ambient conditions during operation. Therefore, these values can be increased owing to ambient conditions during operation.
5. Performances are based on the following conditions : 5. Performances are based on the following conditions :
*Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB *Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
*Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB *Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is Zero. Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is Zero.
6. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination. 6. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination.
The recommended ratio is 130%. The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases. (R410A, GWP(Global warming potential) = 2087.5) 7. This product contains Fluorinated greenhouse gases. (R410A, GWP(Global warming potential) = 2087.5)

046 / 047
OUTDOOR UNITS _ MULTI V 5 _ SPECIFICATION

MULTI V 5 HEAT PUMP MULTI V 5 HEAT PUMP

OUTDOOR
UNITS
ARUN660LTE5 / ARUN680LTE5 ARUN740LTE5 / ARUN760LTE5
ARUN700LTE5 / ARUN720LTE5 ARUN780LTE5 / ARUN800LTE5

MULTI V 5
HP 66 68 70 72 HP 74 76 78 80
Combination Unit ARUN660LTE5 ARUN680LTE5 ARUN700LTE5 ARUN720LTE5 Combination Unit ARUN740LTE5 ARUN760LTE5 ARUN780LTE5 ARUN800LTE5
Model Name ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5
Independent Unit ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 Model Name ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5
Independent Unit
ARUN180LTE5 ARUN200LTE5 ARUN220LTE5 ARUN240LTE5 ARUN140LTE5 ARUN160LTE5 ARUN180LTE5 ARUN200LTE5
kW 184.8 190.4 196.0 201.6 ARUN120LTE5 ARUN120LTE5 ARUN120LTE5 ARUN120LTE5
Cooling (Rated) kW 207.2 212.8 218.4 224.0
Btu/h 630,600 649,700 668,800 687,900 Cooling (Rated)
Capacity Btu/h 707,000 726,100 745,200 764,300
kW 205.2 211.5 217.8 222.8 Capacity
Heating (Rated) kW 230.4 236.7 243.0 249.3
Btu/h 700,300 721,800 743,300 760,200 Heating (Rated)
Cooling (Rated) kW 44.47 45.82 48.36 50.27 Btu/h 786,300 807,800 829,300 850,800
Input Cooling (Rated) kW 50.54 52.22 52.38 53.73
Heating (Rated) kW 49.76 53.21 55.24 56.54 Input
EER (Rated) 4.16 4.16 4.05 4.01 Heating (Rated) kW 55.53 57.34 57.82 61.27

COP (Rated) 4.12 3.97 3.94 3.94 EER (Rated) 4.10 4.08 4.17 4.17

Power Factor Rated - 0.93 0.93 0.93 0.93 COP (Rated) 4.15 4.13 4.20 4.07

Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Power Factor Rated - 0.93 0.93 0.93 0.93
Exterior Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray
RAL code NL503K / NA507K NL503K / NA507K NL503K / NA507K NL503K / NA507K Exterior
Heat Exchanger Wide Louver Plus Wide Louver Plus Wide Louver Plus Wide Louver Plus RAL code NL503K / NA507K NL503K / NA507K NL503K / NA507K NL503K / NA507K

Compressor Motor Output x Number W x No. (5,300 x 5) + (4,200 x 1) 5,300 x 6 5,300 x 6 5,300 x 6 Heat Exchanger Wide Louver Plus Wide Louver Plus Wide Louver Plus Wide Louver Plus

Type Propeller fan Propeller fan Propeller fan Propeller fan Compressor Motor Output x Number W x No. 5,300 x 6 5,300 x 6 (5,300 x 6) + (4,200 x 1) 5,300 x 7

Motor Output x Number W 900 x 6 900 x 6 900 x 6 900 x 6 Type Propeller fan Propeller fan Propeller fan Propeller fan

m3/min 320 x 3 320 x 3 320 x 3 320 x 3 Motor Output x Number W (900 x 6) + (1,200 x 1) (900 x 6) + (1,200 x 1) (900 x 6) + (1,200 x 1) (900 x 6) + (1,200 x 1)
Air Flow Rate (High) m3/min (320 x 3) + (240 x 1) (320 x 3) + (240 x 1) (320 x 3) + (240 x 1) (320 x 3) + (240 x 1)
Fan ft /min
3
11,301 x 3 11,301 x 3 11,301 x 3 11,301 x 3 Air Flow Rate (High)
External Static Pressure (Max, Pa) 80 80 80 80 Fan ft3/min (11,301 x 3) + (8,476 x 1) (11,301 x 3) + (8,476 x 1) (11,301 x 3) + (8,476 x 1) (11,301 x 3) + (8,476 x 1)

Drive DC INVERTER DC INVERTER DC INVERTER DC INVERTER External Static Pressure (Max, Pa) 80 80 80 80

Discharge Side / Top TOP TOP TOP TOP Drive DC INVERTER DC INVERTER DC INVERTER DC INVERTER

Liquid Pipe mm (inch) 22.2 (7/8) 22.2 (7/8) 22.2 (7/8) 22.2 (7/8) Discharge Side / Top TOP TOP TOP TOP
Pipe
Connections Gas Pipe mm (inch) 53.98 (2-1/8) 53.98 (2-1/8) 53.98 (2-1/8) 53.98 (2-1/8) Pipe Liquid Pipe mm (inch) 22.2 (7/8) 22.2 (7/8) 22.2 (7/8) 22.2 (7/8)
Connections Gas Pipe mm (inch) 53.98 (2-1/8) 53.98 (2-1/8) 53.98 (2-1/8) 53.98 (2-1/8)
Dimensions (W x H x D) mm x No. (1,240 x1,690 x 760) x 3 (1,240 x1,690 x 760) x 3 (1,240 x1,690 x 760) x 3 (1,240 x1,690 x 760) x 3
(1,240 x 1,690 x 760) x 3 (1,240 x 1,690 x 760) x 3 (1,240 x 1,690 x 760) x 3 (1,240 x 1,690 x 760) x 3
kg (276 x 2) + (260 x 1) (276 x 2) + (274 x 1) (276 x 2) + (274 x 1) 276 x 3 Dimensions (W x H x D) mm x No.
Net Weight + (930 x 1,690 x 760) x 1 + (930 x 1,690 x 760) x 1 + (930 x 1,690 x 760) x 1 + (930 x 1,690 x 760) x 1
lbs (639 x 2) + (595 x 1) (639 x 2) + (635 x 1) (639 x 2) + (635 x 1) 639 x 3 kg (276 x 2) + (220 x 1) + (188 x 1) (276 x 2) + (220 x 1) + (188 x 1) (276 x 2) + (260 x 1) + (188 x 1) (276 x 2) + (274 x 1) + (188 x 1)
Cooling dB(A) 68.8 69.0 69.6 69.8 Net Weight
Sound lbs (639 x 2) + (507 x 1) + (448 x 1) (639 x 2) + (507 x 1) + (448 x 1) (639 x 2) + (595 x 1) + (448 x 1) (639 x 2) + (635 x 1) + (448 x 1)
Pressure Level Heating dB(A) 70.6 71.1 71.3 71.8
Sound Cooling dB(A) 69.1 69.2 69.2 69.4
Sound Cooling dB(A) 92.0 92.2 92.2 92.8 Pressure Level Heating dB(A) 70.9 70.9 71.0 71.4
Power Level Heating dB(A) 93.8 94.0 94.2 94.8
Sound Cooling dB(A) 91.8 91.9 92.2 92.4
mm x No.2
Power Level
Communication Cable 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C Heating dB(A) 93.7 93.8 94.0 94.2
(VCTF-SB)
mm2 x No.
Refrigerant name R410A R410A R410A R410A Communication Cable 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C
(VCTF-SB)
Precharged Amount kg 16.0 + 16.0 + 13.0 16.0 + 16.0 + 14.0 16.0 + 16.0 + 14.0 16.0 + 16.0 + 16.0 Refrigerant name R410A R410A R410A R410A
Refrigerant in factory lbs 35.3 + 35.3 + 28.7 35.3 + 35.3 + 30.9 35.3 + 35.3 + 30.9 35.3 + 35.3 + 35.3
Precharged Amount kg 16.0 + 16.0 + 13.0 + 10.0 16.0 + 16.0 + 13.0 + 10.0 16.0 + 16.0 + 13.0 + 10.0 16.0 + 16.0 + 14.0 + 10.0
t-CO2eq 93.9 96.0 96.0 100.2 Refrigerant in factory lbs 35.3 + 35.3 + 28.7 + 22.0 35.3 + 35.3 + 28.7 + 22.0 35.3 + 35.3 + 28.7 + 22.0 35.3 + 35.3 + 30.9 + 22.0
Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve t-CO2eq 114.8 114.8 114.8 116.9
3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
Power Supply Ø, V, Hz
3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50
Number of maximum connectable indoor units 64 64 64 64 Power Supply Ø, V, Hz
3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60
Number of maximum connectable indoor units 64 64 64 64

Note Note
1. Due to our policy of innovation some specifications may be changed without notification. 1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical work and design. 2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Power factor could vary less than ±1% according to the operating conditions. 3. Power factor could vary less than ±1% according to the operating conditions.
4. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard. 4. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard. Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard.
Therefore, these values can be increased owing to ambient conditions during operation. Therefore, these values can be increased owing to ambient conditions during operation.
5. Performances are based on the following conditions : 5. Performances are based on the following conditions :
*Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB *Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
*Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB *Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is Zero. Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is Zero.
6. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination. 6. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination.
The recommended ratio is 130%. The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases. (R410A, GWP(Global warming potential) = 2087.5) 7. This product contains Fluorinated greenhouse gases. (R410A, GWP(Global warming potential) = 2087.5)

048 / 049
OUTDOOR UNITS _ MULTI V 5 _ SPECIFICATION

MULTI V 5 HEAT PUMP MULTI V 5 HEAT PUMP

OUTDOOR
UNITS
ARUN900LTE5 / ARUN920LTE5
ARUN820LTE5 / ARUN840LTE5
ARUN940LTE5 / ARUN960LTE5
ARUN860LTE5 / ARUN880LTE5

MULTI V 5
HP 82 84 86 88 HP 92 94
Combination Unit ARUN820LTE5 ARUN840LTE5 ARUN860LTE5 ARUN880LTE5 Combination Unit ARUN920LTE5 ARUN940LTE5
ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5
Model Name ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 Model Name ARUN240LTE5 ARUN240LTE5
Independent Unit Independent Unit
ARUN220LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5 ARUN240LTE5
ARUN120LTE5 ARUN120LTE5 ARUN140LTE5 ARUN160LTE5 ARUN200LTE5 ARUN220LTE5
kW 229.6 235.2 240.8 246.4 kW 257.6 263.2
Cooling (Rated) Cooling (Rated)
Btu/h 783,400 802,500 821,700 840,800 Btu/h 879,000 898,100
Capacity Capacity
kW 255.6 260.6 266.9 273.2 kW 285.8 292.1
Heating (Rated) Heating (Rated)
Btu/h 872,300 889,200 910,700 932,200 Btu/h 975,200 996,700
Cooling (Rated) kW 56.27 58.18 59.39 61.07 Cooling (Rated) kW 62.58 65.12
Input Input
Heating (Rated) kW 63.30 64.60 66.32 68.13 Heating (Rated) kW 72.06 74.08
EER (Rated) 4.08 4.04 4.05 4.03 EER (Rated) 4.12 4.04
COP (Rated) 4.04 4.03 4.02 4.01 COP (Rated) 3.97 3.94
Power Factor Rated - 0.93 0.93 0.93 0.93 Power Factor Rated - 0.93 0.93
Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray
Exterior Exterior
RAL code NL503K / NA507K NL503K / NA507K NL503K / NA507K NL503K / NA507K RAL code NL503K / NA507K NL503K / NA507K
Heat Exchanger Wide Louver Plus Wide Louver Plus Wide Louver Plus Wide Louver Plus Heat Exchanger Wide Louver Plus Wide Louver Plus
Compressor Motor Output x Number W x No. 5,300 x 7 5,300 x 7 5,300 x 7 5,300 x 7 Compressor Motor Output x Number W x No. 5,300 x 8 5,300 x 8
Type Propeller fan Propeller fan Propeller fan Propeller fan Type Propeller fan Propeller fan
Motor Output x Number W (900 x 6) + (1,200 x 1) (900 x 6) + (1,200 x 1) 900 x 8 900 x 8 Motor Output x Number W 900 x 8 900 x 8
m3/min (320 x 3) + (240 x 1) (320 x 3) + (240 x 1) 320 x 4 320 x 4 m3/min 320 x 4 320 x 4
Air Flow Rate (High) Air Flow Rate (High)
Fan ft3/min (11,301 x 3) + (8,476 x 1) (11,301 x 3) + (8,476 x 1) 11,301 x 4 11,301 x 4 Fan ft3/min 11,301 x 4 11,301 x 4
External Static Pressure (Max, Pa) 80 80 80 80 External Static Pressure (Max, Pa) 80 80
Drive DC INVERTER DC INVERTER DC INVERTER DC INVERTER Drive DC INVERTER DC INVERTER
Discharge Side / Top TOP TOP TOP TOP Discharge Side / Top TOP TOP
Pipe Liquid Pipe mm (inch) 22.2 (7/8) 22.2 (7/8) 22.2 (7/8) 22.2 (7/8) Pipe Liquid Pipe mm (inch) 22.2 (7/8) 22.2 (7/8)
Connections Gas Pipe mm (inch) 53.98 (2-1/8) 53.98 (2-1/8) 53.98 (2-1/8) 53.98 (2-1/8) Connections Gas Pipe mm (inch) 53.98 (2-1/8) 53.98 (2-1/8)
(1,240 x 1,690 x 760) x 3 (1,240 x 1,690 x 760) x 3 Dimensions (W x H x D) mm x No. (1,240 x1,690 x 760) x 4 (1,240 x1,690 x 760) x 4
Dimensions (W x H x D) mm x No. (1,240 x1,690 x 760) x 4 (1,240 x1,690 x 760) x 4
+ (930 x 1,690 x 760) x 1 + (930 x 1,690 x 760) x 1
kg (276 x 3) + (274 x 1) (276 x 3) + (274 x 1)
kg (276 x 2) + (274 x 1) + (188 x 1) (276 x 3) + (188 x 1) (276 x 3) + (188 x 1) (276 x 3) + (220 x 1) Net Weight
Net Weight lbs (639 x 3) + (635 x 1) (639 x 3) + (635 x 1)
lbs (639 x 2) + (635 x 1) + (448 x 1) (639 x 3) + (448 x 1) (639 x 3) + (507 x 1) (639 x 3) + (507 x 1)
Sound Cooling dB(A) 70.4 70.9
Sound Cooling dB(A) 70.0 70.1 70.2 70.3 Pressure Level Heating dB(A) 72.5 72.7
Pressure Level Heating dB(A) 71.6 72.1 72.1 72.2
Sound Cooling dB(A) 93.6 93.6
Sound Cooling dB(A) 92.4 92.9 93.1 93.2 Power Level Heating dB(A) 95.4 95.6
Power Level Heating dB(A) 94.4 94.9 95.1 95.2
mm2 x No.
mm2 x No. Communication Cable 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C
Communication Cable 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C (VCTF-SB)
(VCTF-SB)
Refrigerant name R410A R410A
Refrigerant name R410A R410A R410A R410A
Precharged Amount kg 16.0 + 16.0 + 16.0 + 14.0 16.0 + 16.0 + 16.0 + 14.0
Precharged Amount kg 16.0 + 16.0 + 14.0 + 10.0 16.0 + 16.0 + 16.0 + 10.0 16.0 + 16.0 + 16.0 + 13.0 16.0 + 16.0 + 16.0 + 13.0 in factory
Refrigerant lbs 35.3 + 35.3 + 35.3 + 30.9 35.3 + 35.3 + 35.3 + 30.9
Refrigerant in factory lbs 35.3 + 35.3 + 30.9 + 22.0 35.3 + 35.3 + 35.3 + 22.0 35.3 + 35.3 + 35.3 + 28.7 35.3 + 35.3 + 35.3 + 28.7
t-CO2eq 129.4 129.4
t-CO2eq 116.9 121.1 127.3 127.3
Control Electronic Expansion Valve Electronic Expansion Valve
Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
3, 380-415, 50 3, 380-415, 50
3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50 Power Supply Ø, V, Hz
Power Supply Ø, V, Hz 3, 380, 60 3, 380, 60
3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60
Number of maximum connectable indoor units 64 64
Number of maximum connectable indoor units 64 64 64 64

Note Note
1. Due to our policy of innovation some specifications may be changed without notification. 1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical work and design. 2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Power factor could vary less than ±1% according to the operating conditions. 3. Power factor could vary less than ±1% according to the operating conditions.
4. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard. 4. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard. Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard.
Therefore, these values can be increased owing to ambient conditions during operation. Therefore, these values can be increased owing to ambient conditions during operation.
5. Performances are based on the following conditions : 5. Performances are based on the following conditions :
*Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB *Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
*Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB *Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is Zero. Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is Zero.
6. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination. 6. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination.
The recommended ratio is 130%. The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases. (R410A, GWP(Global warming potential) = 2087.5) 7. This product contains Fluorinated greenhouse gases. (R410A, GWP(Global warming potential) = 2087.5)

050 / 051
OUTDOOR UNITS _ MULTI V 5 _ SPECIFICATION

MULTI V S COOLING ONLY NOTE

OUTDOOR
UNITS
ARUV030GSD0 / ARUV040GSD0
ARUV050GSD5 / ARUV060GSD5

MULTI V 5
HP 3 4 5 6

Model Name Combination Unit ARUV030GSD0 ARUV040GSD0 ARUV050GSD0 ARUV060GSD0


kW 9.2 11.0 14.5 17.0
Cooling kcal/h 7,911 9,458 12,470 14,620
Btu/h 31,400 37,600 49,500 58,000
Capacity (Rated)
kW - - - -
Heating kcal/h - - - -
Btu/h - - - -
Cooling kW 2.10 2.75 3.85 4.00
Input (Rated)
Heating kW - - - -
Power Factor Rated - 1 1 1 1
Casing Color Warm Gray Warm Gray Warm Gray Warm Gray
Heat Exchanger Wide Louver Plus Wide Louver Plus Gold fin Gold fin
Hermetic Motor Hermetic Motor Hermetic Motor Hermetic Motor
Type
Compressor Compressor Compressor Compressor
Piston Displacement cm3/rev 24 24 44.2 44.2
Number of Revolution rev/min 6,600 6,600
Compressor Motor Output x Number W x No. 2,137 x 1 2,137 x 1 4,000 x 1 4,000 x 1
Starting Method DC Inverter Starting DC Inverter Starting DC Inverter Starting DC Inverter Starting
Oil Type FVC68D (PVE) FVC68D (PVE) FVC68D (PVE) FVC68D (PVE)
Oil Charge 900 900 1,300 1,300
Type Axial Flow Fan Axial Flow Fan Axial Flow Fan Axial Flow Fan
Motor Output x Number W 124.0 x 1 124.0 x 1 124.0 x 1 124.0 x 1
m3/min 60 60 60 90
Fan Air Flow Rate (High)
ft3/min 2,118 2,118 2,118 3,178
Drive DC INVERTER DC INVERTER DC INVERTER DC INVERTER
Discharge Side / Top Side Side Side Side
Liquid mm (inch) 9.52 (3/8) 9.52 (3/8) 9.52 (3/8) 9.52 (3/8)
Pipe Connections
Gas mm (inch) 15.88 (5/8) 15.88 (5/8) 15.88 (5/8) 19.05 (3/4)
mm 950 x 834 x 330 950 x 834 x 330 950 x 834 x 330 950 x 1,170 x 330
Dimensions (W x H x D)
inch 37-13/32 x 32-27/32 x 13 37-13/32 x 32-27/32 x 13 37-13/32 x 32-27/32 x 13 37-13/32 x 46-1/16 x 13
kg 59 59 66 79
Net Weight
lbs 130 130 146 174
Cooling dB(A) 50 50 51 52
Sound Pressure Level
Heating dB(A) - - - -
Sound Power Level dB(A) - - - -
High pressure sensor / High pressure sensor /
High pressure protection - Low pressure sensor Low pressure sensor
High pressure switch High pressure switch
Over-heat protection Over-heat protection Over-heat protection / Over-heat protection
Protection Devices Compressor / Fan - / Fan driver overload / Fan driver overload Fan driver overload / Fan driver overload
protector protector protector protector
Over-heat protection / Over-heat protection / Over-heat protection / Over-heat protection /
Inverter -
Over-current protection Over-current protection Over-current protection Over-current protection
mm2 x No.
Communication Cable 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C
(VCTF-SB)
Refrigerant name R410A R410A R410A R410A
kg 1.4 1.4 1.4 2.3
Refrigerant Precharged Amount
lbs 3.1 3.1 3.1 5.1
Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
Power Supply Ø, V, Hz 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50
Number of maximum connectable indoor units 5 6 8 9

052 / 053
INDOOR

INDOOR
UNITS
UNITS

WALL MOUNTED

CEILING MOUNTED CASSETTE

CEILING MOUNTED ROUND CASSETTE

CEILING CONCEALED DUCT

FRESH AIR INTAKE

CEILING SUSPENDED

CONSOLE

054 / 055
INDOOR UNITS _ WALL MOUNTED INDOOR UNITS _ WALL MOUNTED _ KEY FEATURES

SMART
Wi-Fi Control
WALL MOUNTED Anytime, anywhere access to the unit with Android & iOS-based smartphones.

LG ThinQTM

INDOOR
UNITS
Search “LG ThinQTM” on Google market or the App Store to download the app.
LG ThinQTM

Integrated Home Appliances Control Access your air conditioner anytime and from anywhere
Control / Monitor all your LG appliances from one place. With a Wi-Fi equipped device and LG’s exclusive control app, LG ThinQTM.

WALL MOUNTED
Easy Registration and Log-in
Follow the easy set-up steps that will activate LG ThinQTM’s user-friendly features. Wi-Fi Connectivity
Each user can set and save temperature and fan speed preferences in the
LG ThinQTM app. If a household has more than one indoor unit, separate
temperature settings can be set for each.

Multiple Devices

Features & Benefits Key Applications * Wi-Fi modem (Option) is necessary for this function

• 6 Different discharge angles can be programmed via the remote controller. • Retail • Hotel
• Easily detachable full surface cover helps to clean the air conditioner. • Restaurant • Multi-family Residence Simple operation for various functions
• Drain pipe can be easily hidden from sight. • Office ※ Can be controlled by multiple users, but not simultaneously.

Multi-Control
Wall Mounted Standard
Smart Wi-Fi ○
Energy Efficiency Energy Display ○
Fast Cooling & Jet Cool ○ On/Off, Current Temp Mode, Set Temp Vane Control
Heating Auto Swing (Up & Down) ○

Ionizer Straight forward Management
~7.1kW Only
Health Pre Filter ○
Auto Cleaning ○
Sleep Mode ○
Timer (On / Off) ○
Comfort Timer (Weekly) ○
Two Thermistor Control ○
Group Control ○
Reservation Energy Smart Filter
※ ○: Applied, - : Not applied Monitoring Diagnosis Management

056 / 057
INDOOR UNITS _ WALL MOUNTED _ KEY FEATURES

FRESH AIR FAST COOLING & HEATING COMFORT


Ionizer PLUS Cleans Filter with Regular Airflow Auto Swing Scheduled Operation
The comprehensive auto cleaning function prevents the formation of bacteria
The powerful Ionizer protects you from bad odors and Cool air extends to the entire room regardless of where You can set the daily temperature, fan speed, the operation
and mold on the heat exchanger.
ilizes Over Escherichia
3 Million coliIons)
and Staphylococcus in the surface with over the unit is situated. mode and automatic On / Off time for two weeks.
3 million ions to sterilize to make a safer, and cleaner
particles by infusing the air passing through the air conditioner with over 3 millions ions. How It Works
※ Specifications may vary for each model. It will keep running on that time until canceled by the user.
environment. ※ This function is for wired remote controller only.
6-Step Vane,
6-Step Vane Control
Control up
upto
to70°
70° 5-Step Louver, Control upisto 55°

INDOOR
※ Wired remote controller need to be separately purchased.
※ Specifications may vary for each model.

UNITS
※ Depending on the experimental conditions.
H
H H
H
The
Thevertical vane,
vertical which
vane, moves
which up andup
moves down,
andhas 6 different
down, has 6settings including
different full-auto swing.
settings The louver, which sways left and right, has 5 different settings including full auto-swing.
H H
O- including full-auto swing.
H+ Sterilization and Deodorization (Utilizes Over 3 Million Ions) Schedule 1 Schedule 2
O- Ionizer PLUS reduces E.coli and Staphylococcus in the surface with over Setting temperature : 19°C Setting temperature : 21°C
By dehumidifying, (Some models are by Operation time : 09:00 ~ 12:00 Operation time : 13:00 ~ 18:00
H+ 3 million ions.
O- dehumidifying and ionizing), the auto cleaning
function prevents potentially harmful substances

WALL MOUNTED
1
from forming on the surface of the heat exchanger.
How It Works Up & Down 2
rmful Substances OH Radical Production Chemical Reaction Complete Sterilization
NqjfsxQnqyjw|nym]jlzqfwLnwņt| 70° 3
harmful particles Ion Cluster OH Surrounding
radicles inactivate OH
harmful 4
Radicalsubstances OH radicles
Chemical Reaction bond with H particles inThe
Sterilization thecomprehensive
air Hauto
2O molecules are produced
cleaning function prevents the formation of bacteria and mold on the heat exchanger, providing a more pleasant and comfortable environment. Heating 5
Generation
Ions are released
Harmful Substances Production
H- and O- bond to How It Works
OH radicles inactivate OH radicles bond H2O molecules are
6
into air
2
harmful particles harmful substances with H particles
H H
produced How It Works ※ Angle can be different from each model and working mode. 9:00 12:00 13:00 18:00
NqjfsxQnqyjw|nym]jlzqfwLnwņt|
H
H H
H

Sterilization Performance Evaluations 6-Step Vane, Control up to 70°


The comprehensive auto cleaning function prevents the formation of bacteria and mold on the heat exchanger, providing a more pleasant and comfortable environment. Control
5-Step up toControl
Louver, 110° up to 55°
The vertical vane, which moves up and down, has 6 different settings including full-auto swing.
TheLouver
louver, can
whichbesways left and right, hasto5 extend
differentleft
settings
and including full auto-swing.
Sterilize Bacteria E.coli over 99.9% in 30 min. and staphylococcus over
The indoor environment remains odorless By preventing pollution of the heat 110 degrees.
adjusted manually right swing to
Two Thermistors Control
99.6% in 60min. ※ Test Conditions : with the advanced deodorizing function. exchanger caused by various germs and The indoor temperature can be checked using the
Space : 52m3 Chamber (measuring
By eliminating the humidity and bacteriabacteria,
left in the performance and lifespan
The indoor environment of the with
remains odorless air the By preventing the polluting of the heat exchangerMjsjŅy
Survival Rate Virus Bacteria (%)

100
2 H
H H with the specimen in the
Hcenter of test chamber)
air conditioner, the auto cleaning function removes advanced LMWLWZQbQVON]VK\QWV
conditioner can be increased over 10 years. by various germs and bacteria, the cooling performance thermistors in the remote controller as well as from the
H H all substances that might be harmful to human body. and longevity ofthe air conditioner remains unchanged
80 Temperature & Humidity : Normal even after 10 years of usage.
4 Way Swing indoor unit. There may be a significant difference between
60 Pain Point Bacteria E.coli
Bacteria : E coil colon bacillus,
Staphylococcus Aureus NjwynŅhfyj
MjsjŅy ceiling and floor air temperature. Two thermistors can
4 Way Swing disperses cool air quickly and effectively in multiple directions to each corner of a room.
99.9% Tested by Intertek Auto cleaning
40
D/CtitwxywjslymijhwjfxjnsHBrnszyjx Air conditioners with
Sanitization
vanes that only move up and
By eliminating
staphylococcus
down are Removes
the humidity and bacteria left in the
Auto Harmful
TheCleaning
indoor Particles
Tsyjwyjp0ajwnŅhfyntsNjwynk~nslLsyngfhyjwnfq
environment
provides remains odorless
clean withpreventing
air by the By preventing the polluting
bacteria, mold of the
andheat exchanger
odors that Left & Right optimize indoor air temperature for a more comfortable
20 unable to suitably cool all areas of aairroom.
conditioner, the auto cleaning function removes
Auto Cleaning LMWLWZQbQVON]VK\QWV
advancedprovides clean air by eliminating bacteria, moldbyand
various
odorsgerms andotherwise
that can bacteria, the cooling performance
accumulate in an indoor unit.
30 min.
99.9%
LstitwtkxywjslymD or less indicates that there is odor but no sense
all substances that might be harmful to human body.
Sanitization
Function of Plasmaster Ionizer+ / Ionizer
can otherwise accumulate in an indoor unit. and longevity ofthe air conditioner remains unchanged
even after 10 years of usage.
110° environment.
Heating /
of displeasure
0 (degree of odor permissible).
MjsjŅy Cooling
d and bacteria growing on 15 30 45 60 Time (min)
※ Angle can be different from each model and working mode.
he heat exchanger is wet. Removes Harmful Particles
2.1
Odor
odor strength decrease
Autoin 60 minutes
Cleaning provides clean air by eliminating bacteria, mold and odors that can otherwise accumulate in an indoor unit. Easy and Simple Control Indoor Unit
1 2 3 4
Strength
An odor of measured as 2 European odor units (ouE/m³) or less Thermistor
Airflow direction can be changed
indicates that the level of odor falls within permissible limits.
by LG ThinQTM Wi-Fi app.
Normal Odor Strength 1 2 3 4
wjzx Offensive
odor MjsjŅy Bacteria Elimination Odor Elimination Mold Elimination
substance
Offensive
sensitivity odor
4 Way Swing
substance
Mountain
smell
Indoor life
smell
Bathroom
smell
Food waste
smell
How It Works
sensitivity Mountain Indoor life Bathroom Food waste 4 Way Swing disperses cool air quickly and effectively in multiple directions to each corner of a room.
smell smell smell smell Up / Down Swing
and down are Odor strength Light Moderate Strong Very Strong NqjfsxQnqyjw|nym]jlzqfwLnwņt| Remote Controller
level Thermistor
Odor strength level Light Moderate Strong Very Strong The comprehensive auto cleaning function prevents the formation of bacteria and mold on the heat exchanger, providing a more pleasant and comfortable environment.
Bacteria
Bacteria Elimination Odor Odor
Elimination MoldMold
Elimination Jet Cool
1.5 3.6 Prevention Elimination Elimination
LG air conditioners provide optimized high-speed airflow,
Odor strength reduce 3.6 1.5 / The Odor floating in the room as well as curtain and clothes. which can cool rooms faster while delivering cool air evenly Group Control
60
me(min)
ZitwxywjslymwjizhjE/HC/G&_mjZitwņtfynslnsymjwttrfx|jqqfxhzwyfnsfsihqtymjx/
※ Test conditions : in every direction. Group control by new remote controller (PREMTB100 /
Space: 8m3 Chamber
Temperature & Humidify : Normal ※ Specifications may vary for each model.
Tested by Intertek ※ Depending on the experimental conditions. PREMTBB10) has more functions than previous model.
Installation One Click “Jet Mode”
Auto Cleaning Installation Support
By eliminating the humidity and bacteria left in the The indoor environment remains odorless with the
Clip
air conditioner, the auto cleaning function removes advanced LMWLWZQbQVON]VK\QWV
By preventing
Reduces thetemperature
the polluting of theof
heat exchanger air to 18°C for 30 minutes with
outflowing
by various germs and bacteria, the cooling performance
The unit has a self-cleaning function that dries the heat all substances that might be harmful to human body. justlongevity
and one click.
ofthe air conditioner remains unchanged
A support clip creates adequate space between the wall and the unit for even after 10 years of usage.
exchanger before sterilizing the interior. easier installation.
MjsjŅy
Cooling / Heating Dehumidification
Removes Harmful Particles Fan only operating Setting temp.
Pain Point 25°
Auto Cleaning provides clean air by eliminating bacteria, mold and odors that can otherwise accumulate in an indoor unit.
The main cause of odor within air conditioners is mold and bacteria
growing on the heat exchanger. These germs can spread when the heat Standard Operation
exchanger is wet.
ng on
wet. More Powerful Performance In Case of Group Control
By reducing the second vortex, which
decreases airflow within the air outlet,
and enlarging the fan size, the amount of
167mm
air flow is increased to 13 CMM.

Low Magnitude of High


Velocity
Bacteria Elimination Odor Elimination Mold Elimination

058 / 059
INDOOR UNITS _ WALL MOUNTED _ SPECIFICATION

STANDARD STANDARD
ARNU05GSJN4 / ARNU07GSJN4 ARNU18GSK*4 / ARNU24GSK*4
ARNU09GSJN4 / ARNU12GSJN4 ARNU30GSVA4 / ARNU36GSVA4
ARNU15GSJN4

INDOOR
UNITS
Model Unit ARNU05GSJN4 ARNU07GSJN4 ARNU09GSJN4 ARNU12GSJN4 ARNU15GSJN4 Model Unit ARNU18GSK*4 ARNU24GSK*4 ARNU30GSVA4 ARNU36GSVA4

WALL MOUNTED
Cooling Capacity kW 1.6 2.2 2.8 3.6 4.5 Cooling Capacity kW 5.6 7.1 8.8 10.4
Heating Capacity kW 1.8 2.5 3.2 4.0 5.0 Heating Capacity kW 6.3 7.5 9.4 10.8
Power Input Power Input
Nominal W 11 / 10 / 9 12 / 11 / 9 13 / 12 / 9 15 / 13 / 11 23 / 18 / 11 Nominal W 32 / 26 / 16 39 / 26 / 16 54 / 43 / 31 85 / 51 / 36
(H / M / L) (H / M / L)
Exterior Color White White White White White Exterior Color White White White White
RAL Code RAL 9016 RAL 9016 RAL 9016 RAL 9016 RAL 9016 RAL Code RAL 9016 RAL 9016 RAL 9016 RAL 9016
Dimensions Body mm 818 x 316 x 189 818 x 316 x 189 818 x 316 x 189 818 x 316 x 189 818 x 316 x 189 Dimensions Body mm 975 x 354 x 209 975 x 354 x 209 1,190 x 346 x 265 1,190 x 346 x 265
(W x H x D) Shipping mm 892 x 381 x 249 892 x 381 x 249 892 x 381 x 249 892 x 381 x 249 892 x 381 x 249 (W x H x D) Shipping mm 1,063 x 420 x 274 1,063 x 420 x 274 1,265 x 432 x 335 1,265 x 432 x 335
Type Cross Flow Fan Cross Flow Fan Cross Flow Fan Cross Flow Fan Cross Flow Fan Type Cross Flow Fan Cross Flow Fan Cross Flow Fan Cross Flow Fan
Motor Output x Number W x No. 30 x 1 30 x 1 30 x 1 30 x 1 30 x 1 Motor Output x Number W x No. 58 x 1 58 x 1 113 x 1 113 x 1
Fan Fan
Air Flow Rate (H / M / L) m³/min 6.8 / 6.5 / 5.9 7.2 / 6.8 / 5.9 7.8 / 7.2 / 5.9 8.5 / 7.8 / 6.8 10.5 / 9.5 / 6.8 Air Flow Rate (H / M / L) m³/min 14.0 / 12.0 / 10.5 15.2 / 12.7 / 10.5 23.0 / 20.0 / 17.0 26.0 / 23.0 / 19.0
Motor Type BLDC BLDC BLDC BLDC BLDC Motor Type BLDC BLDC BLDC BLDC
Air Filter Pre Filter Pre Filter Pre Filter Pre Filter Pre Filter Air Filter Pre Filter Pre Filter Pre Filter Pre Filter
Liquid Side mm (inch) Ø6.35 (1/4) Ø6.35 (1/4) Ø6.35 (1/4) Ø6.35 (1/4) Ø6.35 (1/4) Liquid Side mm (inch) Ø6.35 (1/4) Ø9.52 (3/8) Ø9.52 (3/8) Ø9.52 (3/8)
Pipe Pipe
Gas Side mm (inch) Ø12.7 (1/2) Ø12.7 (1/2) Ø12.7 (1/2) Ø12.7 (1/2) Ø12.7 (1/2) Gas Side mm (inch) Ø12.7 (1/2) Ø15.88 (5/8) Ø15.88 (5/8) Ø15.88 (5/8)
Connections Connections
Drain Pipe (Internal Dia.) mm (inch) Ø16 (5/8) Ø16 (5/8) Ø16 (5/8) Ø16 (5/8) Ø16 (5/8) Drain Pipe (Internal Dia.) mm (inch) Ø16 (5/8) Ø16 (5/8) Ø16 (5/8) Ø16 (5/8)
Weight Body kg 8.4 8.4 8.4 8.4 8.4 Weight Body kg 12.2 12.2 16.6 16.6
Sound Pressure Levels (H / M / L) dB(A) 30 / 29 / 28 32 / 30 / 28 34 / 32 / 28 37 / 34 / 30 42 / 39 / 32 Sound Pressure Levels (H / M / L) dB(A) 43 / 39 / 34 46 / 41 / 34 49 / 44 / 42 52 / 47 / 43
Sound Power Levels (H / M / L) dB(A) 54 / 53 / 52 54 / 53 / 52 55 / 54 / 52 55 / 54 / 53 58 / 56 / 54 Sound Power Levels (H / M / L) dB(A) 63 / 57 / 54 65 / 60 / 54
Power Supply Ø, V, Hz 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 Power Supply Ø, V, Hz 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50
Communication Cable mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C Communication Cable mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C
Note : 1. Performance tested under EN14511 * : N or C can be applied which has little bit different shape of panel.
2. Capacities are based on the following conditions. Note : 1. Performance tested under EN14511
- Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero 2. Capacities are based on the following conditions.
- Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero
3. Due to our policy of innovation, some specifications may be changed without notification. - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero
3. Due to our policy of innovation, some specifications may be changed without notification.

Accessories Accessories
Chassis ARNU05GSJN4 ARNU07GSJN4 ARNU09GSJN4 ARNU12GSJN4 ARNU15GSJN4 Chassis ARNU18GSK*4 ARNU24GSK*4 ARNU30GSVA4 ARNU36GSVA4
Drain Pump - Drain Pump - -
Cassette Cover - Cassette Cover - -
Refrigerant Leakage Detector PRLDNVS0 Refrigerant Leakage Detector PRLDNVS0 PRLDNVS0
EEV Kit PRGK024A0 EEV Kit PRGK024A0 -
Independent Power Module PRIP0 Independent Power Module PRIP0 PRIP0
Robot Cleaner - Robot Cleaner - -
Pre Filter (Washable) ○ Pre Filter (Washable) ○ ○
Ion Generator ○ Ion Generator ○ -
CO2 Sensor - CO2 Sensor - -
Ventilation Kit - Ventilation Kit - -
IR Receiver - IR Receiver - -
Zone Controller - Zone Controller - -
PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible), PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible),
Dry Contact (with additional accessory) Dry Contact (with additional accessory)
PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus) PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus)
External Input (1 point) ○ External Input (1 point) ○ ○
Wi-Fi ○ Wi-Fi ○ PWFMDD200

※ ○ : Applied, - : Not applied ※ ○ : Applied, - : Not applied


Option : Refer to model name in table Option : Refer to model name in table

060 / 061
INDOOR UNITS _ CEILING MOUNTED CASSETTE INDOOR UNITS _ CEILING MOUNTED CASSETTE _ KEY FEATURES

NEW DESIGN
4 Way Air Flow with New Design Wide Design
CEILING MOUNTED New Excellent Technology (NET) certifies new 4 Way dual vane
design that promotes comfortable and convenient airflow.
Bigger inlet and outlet make faster cooling / heating airflow.

CASSETTE

INDOOR
UNITS
4 Way
Dual Vane Increased Inlet Area

Normal 4 Way

CEILING MOUNTED CASSETTE


x2

Dual Vane 4 Way

*New types wind


Normal Dual Vane Full 3D Turbo Fan
Full 3D Turbo fan decreases air resistance,
so it makes High Efficient and reduces noise level.
Indirect
Wind Turbo fan

Direct
Wind

Full 3D Turbo fan


*6 Airflows mode Power consumption 13W ↓, Noise 3dB(A) ↓

Fast and Quick Fresh and Natural Auto Vane Control


Power Mode Up / Down Swing Smart Mode

Improved outlet flow rate

5m
Features & Benefits Key Applications
Indirect cooling & Heating Suitable for High Ceiling Provide high concentration
High Efficiency Heat Exchanger (HEX)
• New Dual Vane 4 Way cassette allows comfortable air flow. • Retail Ø5 High Density Heat Exchanger increases cooling
• Full 3D Turbo fan decreases air resistance, providing high air flow and Indirect Wind Direct Wind Refresh Mode
• School / heating efficiency by 10%.
low sound levels. • Office
Normal Ø7 HEX
• Hotel
Brighter Color
• Dormitory Color enhancement allows cassette to blend in to most
• Restaurant interior ceiling spaces. 20mm

Cassette 4 Way 2 Way 1 Way Normal Ivory Dual Vane White


Smart Wi-Fi ○ ○ ○ Tube Column 12 Column
Energy Efficiency Human Detect Sensor ○ - - 12 Column
Fin per Inch 21
Drain Pump ○ ○ ○
Sleep Mode ○ ○ ○
High Efficient Ø5 HEX
Timer (On / Off) ○ ○ ○
Comfort
Timer (Weekly) ○ ○ ○
Two Thermistor Control ○ ○ ○
Group Control ○ ○ ○ 14mm

Tube Column 18 Column


18 Column Fin per Inch 22

062 / 063
INDOOR UNITS _ CEILING MOUNTED CASSETTE _ KEY FEATURES

SMART SMART INSTALLATION


Ceiling to Floor Temperature Sensing High-performance Air purification Real-time Air Quality Monitoring Minimized Height
With a special sensor that sense both ceiling and floor Air cleaning function provides fresh, filtered air. Wi-Fi functionality for anytime, anywhere indoor unit With a height of 132mm, the LG 1 Way cassette is the ideal
temperature, Dual Vane 4 Way cassette provides comfort air. control and air cleaning status display. solution for limited-space installations.

IDU Temperature ① Smart indicator (Air quality) ② Remote controller

INDOOR
Real-time indoor air quality status Fine dust concentration & air quality

UNITS
displayed on indoor unit status displayed on remote control
132mm

Calculate Room Good Bad


Temperature

CEILING MOUNTED CASSETTE


Normal Very Bad

Size Comparison (Unit : mm)


③ Mobile
Floor Temperature A Company B Company LG
Anytime, anywhere access to check
& control air status via mobile
1 Way
※ Available only for products with floor temperature sensor.. 215 230 132
Cassette

Human-detection Air Flow


Human detection provides users with direct or indirect air Flexible Installation
flow preferences. 1 Way cassette doesn’t require the inspection access hole,
so that simple installation is possible.
Indirect comfort Direct cooling
Dual Elevating Grille
Grille automatically detaches and re-attaches with 4 touchpoints 1 Way cassette Duct
Provides air flow that blows away
from user for comfort.
Provides air flow that blows directly
onto user for cooling. Convenient & Powerful 4-Step for enhanced stability & convenient filter management.
Duct
Air purification
It captures 99% of microfine dust (PM1.0) Normal 4 way Smart Dual Vane IDU
Besides, Easy-to-maintain system with washable filters
Inspection hole

No touch Direct airflow


Indirect airflow 4m
2°C
Comfort Cooler

Installation Standard
① Horizontal Sensor ② Check Close grille ① Detect Obstacle ③ Set Stop Point
② Horizontal Sensor ④ Check Close grille
Human Detection for Optimized Air
purification Deodorization filter Phase 4 I Deodorizes
Efficiency kit
LG ThinQTM Connectivity
Indoor unit senses human presence to switch on or off for Anytime anywhere access to indoor units with LG ThinQTM

300 or more
Phase 3 I Captures microfine dust
maximum power savings of 54%. PM1.0 Filter mobile app. Ceiling
Ceiling Board
Dust electrification Ceiling Board
Operation On Turning Off Turning On

300 or less
On Off On
Phase 2 I Dust Electrification 500 or

or more
500 or

1,000
more more

4,000 or less
Above 2,500
Pre-filter
PM1.0
Sensor
Phase 1 I Captures fine dust
Unit : mm

Air
In office Absence In office purification
Floor
panel
Learning time for
↑2°C, running
Power saving Max. 54%
25min Power saving
Manageable set time Power saving
(If set time 30min) ① Monitoring Air status ② Mobile Remote Control
30min/60min/90min Smart Easy to check indoor air status Remote control by using mobile phone
indicator • Ultra Fine / Extra Fine / Fine Dust • Control Mode / Temperature
Absence → Turn off after 30min (Set turn off)
• Day / Week /Month / Yearly / Air flow etc.
Learning time for Absence Cycle Management
5min Dust ③ Display Power Consumption
Pre-filter Ultra Fine Dust Kit Deodorizing Filter Check power consumption of A/C
※ Smart Dual Vane Indoor Unit ‘20 Line up. Electrification
※ Data Based on actual test of LG, single product 2 hours measurement result. • Check energy display
Easy removable 6 months /
(Cooling 26 °C, strong wind) Washable Dry in sunlight • Set target energy consumption level
pre-filter Washable

064 / 065
INDOOR UNITS _ CEILING MOUNTED CASSETTE _ SPECIFICATION

DUAL VANE 4 Way CASSETTE (840 X 840) DUAL VANE 4 Way CASSETTE (840 X 840)
ARNU24GTBB4 / ARNU28GTBB4 ARNU36GTAB4 / ARNU42GTAB4
ARNU30GTBB4 ARNU48GTAB4

INDOOR
UNITS
Model Unit ARNU24GTBB4 ARNU28GTBB4 ARNU30GTBB4 Model Unit ARNU36GTAB4 ARNU42GTAB4 ARNU48GTAB4

CEILING MOUNTED CASSETTE


Cooling Capacity kW 7.1 8.2 9.0 Cooling Capacity kW 10.6 12.3 14.1
Heating Capacity kW 8.0 9.2 10.0 Heating Capacity kW 11.9 13.8 15.9
Power Input Power Input
Nominal W 32 / 27 / 20 37 / 30 / 22 48 / 36 / 25 Nominal W 69 / 49 / 37 97 / 69 / 49 110 / 76 / 61
(H / M / L) (H / M / L)
Dimensions Body mm 840 x 204 x 840 840 x 204 x 840 840 x 204 x 840 Dimensions Body mm 840 x 288 x 840 840 x 288 x 840 840 x 288 x 840
(W x H x D) Shipping mm 922 x 276 x 917 922 x 276 x 917 922 x 276 x 917 (W x H x D) Shipping mm 922 x 360 x 917 922 x 360 x 917 922 x 360 x 917
Type Full 3D Turbo Fan Full 3D Turbo Fan Full 3D Turbo Fan Type Full 3D Turbo Fan Full 3D Turbo Fan Full 3D Turbo Fan
Motor Output x Number W x No. 51 x 1 51 x 1 51 x 1 Motor Output x Number W x No. 135 x 1 135 x 1 135 x 1
Fan Fan
Air Flow Rate (H / M / L) m3/min 18 / 17 / 15 19 / 17 / 15 21 / 19 / 16 Air Flow Rate (H / M / L) m3/min 29 / 26 / 22 33 / 29 / 26 34 / 30 / 28
Motor Type BLDC BLDC BLDC Motor Type BLDC BLDC BLDC
Air Filter Pre Filter Pre Filter Pre Filter Air Filter Pre Filter Pre Filter Pre Filter
Liquid Side mm (inch) Ø9.52 (3/8) Ø9.52 (3/8) Ø9.52 (3/8) Liquid Side mm (inch) Ø9.52 (3/8) Ø9.52 (3/8) Ø9.52 (3/8)
Pipe Pipe
Gas Side mm (inch) Ø15.88 (5/8) Ø15.88 (5/8) Ø15.88 (5/8) Gas Side mm (inch) Ø15.88 (5/8) Ø15.88 (5/8) Ø15.88 (5/8)
Connections Connections
Drain Pipe (Internal Dia.) mm (inch) Ø25 (1) Ø25 (1) Ø25 (1) Drain Pipe (Internal Dia.) mm (inch) Ø25 (1) Ø25 (1) Ø25 (1)
Weight Body kg 21 21 21 Weight Body kg 26 26 26
Sound Pressure Level (H / M / L) dB(A) 36 / 34 / 31 39 / 35 / 34 40 / 36 / 33 Sound Pressure Level (H / M / L) dB(A) 42 / 39 / 36 44 / 41 / 39 46 / 43 / 41
Sound Power Level (H / M / L) dB(A) 46 / 44 / 42 50 / 46 / 43 53 / 50 / 45 Sound Power Level (H / M / L) dB(A) 54 / 51 / 47 56 / 53 / 49 58 / 54 / 53
Power Supply Ø, V, Hz 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 Power Supply Ø, V, Hz 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50
Communication Cable mm2 x No. 1.25 x 2C 1.25 x 2C 1.25 x 2C Communication Cable mm2 x No. 1.25 x 2C 1.25 x 2C 1.25 x 2C
PT-AAGW0 PT-AAGW0 PT-AAGW0 PT-AAGW0 PT-AAGW0 PT-AAGW0
Model Name PT-AFGW0 PT-AFGW0 PT-AFGW0 Model Name PT-AFGW0 PT-AFGW0 PT-AFGW0
PT-AEGW0 PT-AEGW0 PT-AEGW0 PT-AEGW0 PT-AEGW0 PT-AEGW0
Decoration Exterior Color White White White Decoration Exterior Color White White White
Panel Panel
RAL Code RAL 9003 RAL 9003 RAL 9003 RAL Code RAL 9003 RAL 9003 RAL 9003
(Accessory) (Accessory)
Net Dimensions Net Dimensions
mm 950 x 35 x 950 950 x 35 x 950 950 x 35 x 950 mm 950 x 35 x 950 950 x 35 x 950 950 x 35 x 950
(W x H x D) (W x H x D)
Net Weight kg 7.1 / 7.5 / 8.5 7.1 / 7.5 / 8.5 7.1 / 7.5 / 8.5 Net Weight kg 7.1 / 7.5 / 8.5 7.1 / 7.5 / 8.5 7.1 / 7.5 / 8.5

Note : 1. Performance tested under EN14511 Note : 1. Performance tested under EN14511
2. Capacities are based on the following conditions. 2. Capacities are based on the following conditions.
- Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero
- Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero
3. Due to our policy of innovation, some specifications may be changed without notification. 3. Due to our policy of innovation, some specifications may be changed without notification.

Accessories Accessories
Chassis ARNU24GTBB4 ARNU28GTBB4 ARNU30GTBB4 Chassis ARNU36GTAB4 ARNU42GTAB4 ARNU48GTAB4
Drain Pump ○ Drain Pump ○
Cassette Cover PTDCA Cassette Cover PTDCA
Refrigerant Leakage Detector PRLDNVS0 Refrigerant Leakage Detector PRLDNVS0
EEV Kit - EEV Kit -
Independent Power Module PRIP0 Independent Power Module PRIP0
Robot Cleaner - Robot Cleaner -
Pre Filter (Washable) ○ Pre Filter (Washable) ○
Ion Generator - Ion Generator -
CO2 Sensor - CO2 Sensor -
Ventilation Kit - Ventilation Kit -
IR Receiver - IR Receiver -
Zone Controller - Zone Controller -
PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible), PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible),
Dry Contact (with additional accessory) Dry Contact (with additional accessory)
PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus) PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus)
External Input (1 Point) ○ External Input (1 Point) ○
Wi-Fi PWFMDD200 Wi-Fi PWFMDD200
Human detection sensor PTVSAA0 Human detection sensor PTVSAA0
Floor Temperature Sensor PT-AFGW0 :○ Floor Temperature Sensor PT-AFGW0 : ○
Air cleaning kit PT-AFGW0 : PTAHMP0 Air cleaning kit PT-AFGW0 : PTAHMP0
Elevation Grille PT-AEGW0 :○ Elevation Grille PT-AEGW0 : ○

066 / 067
INDOOR UNITS _ CEILING MOUNTED CASSETTE _ SPECIFICATION

DUAL VANE 4 Way CASSETTE (840 X 840) HIGH SENSIBLE DUAL VANE 4 Way CASSETTE (840 X 840) HIGH SENSIBLE
ARNU07GTAA4 / ARNU09GTAA4 ARNU24GTAA4 / ARNU28GTAA4
ARNU12GTAA4 / ARNU15GTAA4 ARNU36GTAA4 / ARNU42GTAA4
ARNU18GTAA4 ARNU48GTAA4

INDOOR
UNITS
Model Unit ARNU07GTAA4 ARNU09GTAA4 ARNU12GTAA4 ARNU15GTAA4 ARNU18GTAA4 Model Unit ARNU24GTAA4 ARNU28GTAA4 ARNU36GTAA4 ARNU42GTAA4 ARNU48GTAA4

CEILING MOUNTED CASSETTE


Cooling Capacity kW 2.2 2.8 3.6 4.5 5.6 Cooling Capacity kW 7.1 8.2 10.6 12.3 14.1
Heating Capacity kW 2.5 3.2 4.0 5.0 6.3 Heating Capacity kW 8.0 9.2 11.9 13.8 15.9
Power Input Power Input
Nominal W 23 / 16 / 11 25 / 18 / 11 26 / 19 / 13 29 / 20 / 15 31 / 23 / 16 Nominal W 35 / 29 / 20 40 / 31 / 25 65 / 43 / 31 86 / 65 / 43 100 / 67 / 53
(H / M / L) (H / M / L)
Dimensions Body mm 840 x 288 x 840 840 x 288 x 840 840 x 288 x 840 840 x 288 x 840 840 x 288 x 840 Dimensions Body mm 840 x 288 x 840 840 x 288 x 840 840 x 288 x 840 840 x 288 x 840 840 x 288 x 840
(W x H x D) Shipping mm 922 x 360 x 917 922 x 360 x 917 922 x 360 x 917 922 x 360 x 917 922 x 360 x 917 (W x H x D) Shipping mm 922 x 360 x 917 922 x 360 x 917 922 x 360 x 917 922 x 360 x 917 922 x 360 x 917
Type Full 3D Turbo Fan Full 3D Turbo Fan Full 3D Turbo Fan Full 3D Turbo Fan Full 3D Turbo Fan Type Full 3D Turbo Fan Full 3D Turbo Fan Full 3D Turbo Fan Full 3D Turbo Fan Full 3D Turbo Fan
Motor Output x Number W x No. 166 x 1 166 x 1 166 x 1 166 x 1 166 x 1 Motor Output x Number W x No. 166 x 1 166 x 1 166 x 1 166 x 1 166 x 1
Fan Running Current A 0.23 0.25 0.25 0.27 0.28 Fan Running Current A 0.38 0.46 0.60 0.80 0.88
Air Flow Rate (H / M / L) m3/min 19 / 16 / 13 19 / 16 / 13 20 / 17 / 15 20 / 17 / 15 21 / 19 / 16 Air Flow Rate (H / M / L) m3/min 23 / 21 / 19 24 / 22 / 20 28 / 24 / 21 31 / 28 / 24 33 / 28 / 26
Motor Type BLDC BLDC BLDC BLDC BLDC Motor Type BLDC BLDC BLDC BLDC BLDC
Air Filter Pre Filter Pre Filter Pre Filter Pre Filter Pre Filter Air Filter Pre Filter Pre Filter Pre Filter Pre Filter Pre Filter
Liquid Side mm (inch) Ø9.52 (3/8) Ø9.52 (3/8) Ø9.52 (3/8) Ø9.52 (3/8) Ø9.52 (3/8) Liquid Side mm (inch) Ø9.52 (3/8) Ø9.52 (3/8) Ø9.52 (3/8) Ø9.52 (3/8) Ø9.52 (3/8)
Pipe Pipe
Gas Side mm (inch) Ø15.88 (5/8) Ø15.88 (5/8) Ø15.88 (5/8) Ø15.88 (5/8) Ø15.88 (5/8) Gas Side mm (inch) Ø15.88 (5/8) Ø15.88 (5/8) Ø15.88 (5/8) Ø15.88 (5/8) Ø15.88 (5/8)
Connections Connections
Drain Pipe (Internal Dia.) mm (inch) Ø25 (1) Ø25 (1) Ø25 (1) Ø25 (1) Ø25 (1) Drain Pipe (Internal Dia.) mm (inch) Ø25 (1) Ø25 (1) Ø25 (1) Ø25 (1) Ø25 (1)
Weight Body kg 26 26 26 26 26 Weight Body kg 26 26 26 26 26
Sound Pressure Level (H / M / L) dB(A) 32 / 30 / 26 33 / 30 / 26 34 / 31 / 27 34 / 32 / 29 35 / 32 / 30 Sound Pressure Level (H / M / L) dB(A) 39 / 36 / 33 40 / 37 / 34 42 / 39 / 35 46 / 42 / 39 47 / 43 / 41
Sound Power Level (H / M / L) dB(A) 41 / 38 / 34 42 / 39 / 34 42 / 40 / 36 43 / 40 / 37 44 / 41 / 38 Sound Power Level (H / M / L) dB(A) 47 / 45 / 42 48 / 46 / 42 51 / 48 / 44 54 / 51 / 48 56 / 52 / 50
Power Supply Ø, V, Hz 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 Power Supply Ø, V, Hz 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50
Communication Cable mm2 x No. 1.25 x 2C 1.25 x 2C 1.25 x 2C 1.25 x 2C 1.25 x 2C Communication Cable mm2 x No. 1.25 x 2C 1.25 x 2C 1.25 x 2C 1.25 x 2C 1.25 x 2C
Exterior Color White White White White White PT-AAGW0 PT-AAGW0 PT-AAGW0 PT-AAGW0 PT-AAGW0
Model Name PT-AFGW0 PT-AFGW0 PT-AFGW0 PT-AFGW0 PT-AFGW0
Decoration RAL Code RAL 9003 RAL 9003 RAL 9003 RAL 9003 RAL 9003 PT-AEGW0 PT-AEGW0 PT-AEGW0 PT-AEGW0 PT-AEGW0
Panel Net Dimensions
(Accessory) mm 950 x 35 x 950 950 x 35 x 950 950 x 35 x 950 950 x 35 x 950 950 x 35 x 950 Decoration Exterior Color White White White White White
(W x H x D) Panel
Net Weight kg 7.1 / 7.5 / 8.5 7.1 / 7.5 / 8.5 7.1 / 7.5 / 8.5 7.1 / 7.5 / 8.5 7.1 / 7.5 / 8.5 RAL Code RAL 9003 RAL 9003 RAL 9003 RAL 9003 RAL 9003
(Accessory)
Net Dimensions
mm 950 x 35 x 950 950 x 35 x 950 950 x 35 x 950 950 x 35 x 950 950 x 35 x 950
Note : 1. Performance tested under EN14511 (W x H x D)
2. Capacities are based on the following conditions. Net Weight kg 7.1 / 7.5 / 8.5 7.1 / 7.5 / 8.5 7.1 / 7.5 / 8.5 7.1 / 7.5 / 8.5 7.1 / 7.5 / 8.5
- Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero
- Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero Note : 1. Performance tested under EN14511
3. Due to our policy of innovation, some specifications may be changed without notification. 2. Capacities are based on the following conditions.
- Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero
- Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero
3. Due to our policy of innovation, some specifications may be changed without notification.

Accessories Accessories
Chassis ARNU07GTAA4 ARNU09GTAA4 ARNU12GTAA4 ARNU15GTAA4 ARNU18GTAA4 Chassis ARNU24GTAA4 ARNU28GTAA4 ARNU36GTAA4 ARNU42GTAA4 ARNU48GTAA4
Drain Pump ○ Drain Pump ○
Cassette Cover PTDCA Cassette Cover PTDCA
Refrigerant Leakage Detector PRLDNVS0 Refrigerant Leakage Detector PRLDNVS0
EEV Kit - EEV Kit -
Independent Power Module PRIP0 Independent Power Module PRIP0
Robot Cleaner - Robot Cleaner -
Pre Filter (Washable) ○ Pre Filter (Washable) ○
Ion Generator - Ion Generator -
CO2 Sensor - CO2 Sensor -
Ventilation Kit - Ventilation Kit -
IR Receiver - IR Receiver -
Zone Controller - Zone Controller -
PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible), PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible),
Dry Contact (with additional accessory) Dry Contact (with additional accessory)
PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus) PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus)
External Input (1 Point) ○ External Input (1 Point) ○
Wi-Fi PWFMDD200 Wi-Fi PWFMDD200
Human detection sensor PTVSAA0 Human detection sensor PTVSAA0
Floor Temperature Sensor PT-AFGW0 : ○ Floor Temperature Sensor PT-AFGW0 : ○
Air cleaning kit PT-AFGW0 : PTAHMP0 Air cleaning kit PT-AFGW0 : PTAHMP0
Elevation Grille PT-AEGW0 : ○ Elevation Grille PT-AEGW0 : ○

068 / 069
INDOOR UNITS _ CEILING MOUNTED CASSETTE _ SPECIFICATION

4 Way CASSETTE (570 X 570) 4 Way CASSETTE (570 X 570)


ARNU05GTRB4 / ARNU07GTRB4 ARNU15GTQB4 / ARNU18GTQB4
ARNU09GTRB4 / ARNU12GTRB4 ARNU21GTQB4

INDOOR
UNITS
Model Unit ARNU05GTRB4 ARNU07GTRB4 ARNU09GTRB4 ARNU12GTRB4 Model Unit ARNU15GTQB4 ARNU18GTQB4 ARNU21GTQB4

CEILING MOUNTED CASSETTE


Cooling Capacity kW 1.6 2.2 2.8 3.6 Cooling Capacity kW 4.5 5.6 6.0
Heating Capacity kW 1.8 2.5 3.2 4.0 Heating Capacity kW 5.0 6.3 6.8
Power Input Power Input
Nominal W 13 / 12 / 11 13 / 12 / 11 14 / 13 / 12 17 / 15 / 13 Nominal W 24 / 21 / 18 25 / 22 / 19 28 / 23 / 20
(H / M / L) (H / M / L)
Dimensions Body mm 570 x 214 x 570 570 x 214 x 570 570 x 214 x 570 570 x 214 x 570 Dimensions Body mm 570 x 256 x 570 570 x 256 x 570 570 x 256 x 570
(W x H x D) Shipping mm 667 x 285 x 646 667 x 285 x 646 667 x 285 x 646 667 x 285 x 646 (W x H x D) Shipping mm 667 x 327 x 646 667 x 327 x 646 667 x 327 x 646
Type Turbo Fan Turbo Fan Turbo Fan Turbo Fan Type Turbo Fan Turbo Fan Turbo Fan
Motor Output x Number W x No. 43 x 1 43 x 1 43 x 1 43 x 1 Motor Output x Number W x No. 43 x 1 43 x 1 43 x 1
Fan Fan
Air Flow Rate (H / M / L) m³/min 7.5 / 7.0 / 6.6 7.5 / 7.0 / 6.6 8.0 / 7.5 / 7.1 8.7 / 8.0 / 7.0 Air Flow Rate (H / M / L) m³/min 11.0 / 10.0 / 9.3 11.2 / 11.0 / 10.0 12.0 / 11.1 / 9.4
Motor Type BLDC BLDC BLDC BLDC Motor Type BLDC BLDC BLDC
Air Filter Pre Filter Pre Filter Pre Filter Pre Filter Air Filter Pre Filter Pre Filter Pre Filter
Liquid Side mm (inch) Ø6.35 (1/4) Ø6.35 (1/4) Ø6.35 (1/4) Ø6.35 (1/4) Liquid Side mm (inch) Ø6.35 (1/4) Ø6.35 (1/4) Ø9.52 (3/8)
Pipe Pipe
Gas Side mm (inch) Ø12.7 (1/2) Ø12.7 (1/2) Ø12.7 (1/2) Ø12.7 (1/2) Gas Side mm (inch) Ø12.7 (1/2) Ø12.7 (1/2) Ø15.88 (5/8)
Connections Connections
Drain Pipe (Internal Dia.) mm (inch) Ø25 (1) Ø25 (1) Ø25 (1) Ø25 (1) Drain Pipe (Internal Dia.) mm (inch) Ø25 (1) Ø25 (1) Ø25 (1)
Weight Body kg 12.6 12.6 13.7 13.7 Weight Body kg 15.0 15.0 15.0
Sound Pressure Levels (H / M / L) dB(A) 29 / 27 / 26 29 / 27 / 26 30 / 29 / 27 32 / 30 / 27 Sound Pressure Levels (H / M / L) dB(A) 36 / 34 / 32 37 / 35 / 34 40 / 38 / 34
Sound Power Levels (H / M / L) dB(A) 45 / 43 / 42 45 / 43 / 42 46 / 43 / 42 48 / 46 / 43 Sound Power Levels (H / M / L) dB(A) 50 / 48 / 46 51 / 50 / 46 53 / 51 / 46
Power Supply Ø, V, Hz 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 Power Supply Ø, V, Hz 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50
Communication Cable mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C Communication Cable mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C
Model Name PT-QCHW0 PT-QCHW0 PT-QCHW0 PT-QCHW0 Model Name PT-QCHW0 PT-QCHW0 PT-QCHW0
Exterior Color Morning Fog Morning Fog Morning Fog Morning Fog Exterior Color Morning Fog Morning Fog Morning Fog
Decoration Decoration
Panel RAL Code RAL 9001 RAL 9001 RAL 9001 RAL 9001 Panel RAL Code RAL 9001 RAL 9001 RAL 9001
(Accessory) Net Dimensions mm
700 x 22 x700 700 x 22 x700 700 x 22 x700 700 x 22 x700 (Accessory) Net Dimensions mm
700 x 22 x700 700 x 22 x700 700 x 22 x700
(W x H x D) 620 x 20 x 620 620 x 20 x 620 620 x 20 x 620 620 x 20 x 620 (W x H x D) 620 x 20 x 620 620 x 20 x 620 620 x 20 x 620
Net Weight kg 3.0 / 3.0 3.0 / 3.0 3.0 / 3.0 3.0 / 3.0 Net Weight kg 3.0 / 3.0 3.0 / 3.0 3.0 / 3.0

Note : 1. Performance tested under EN14511 Note : 1. Performance tested under EN14511
2. Capacities are based on the following conditions. 2. Capacities are based on the following conditions.
- Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero
- Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero
3. Due to our policy of innovation, some specifications may be changed without notification. 3. Due to our policy of innovation, some specifications may be changed without notification.

Accessories Accessories
Chassis ARNU05GTRB4 ARNU07GTRB4 ARNU09GTRB4 ARNU12GTRB4 Chassis ARNU15GTQB4 ARNU18GTQB4 ARNU21GTQB4
Drain Pump ○ Drain Pump ○
Cassette Cover PTDCQ Cassette Cover PTDCQ
Refrigerant Leakage Detector PRLDNVS0 Refrigerant Leakage Detector PRLDNVS0
EEV Kit PRGK024A0 (~4.5kW) EEV Kit PRGK024A0 (~4.5kW)
Independent Power Module PRIP0 Independent Power Module PRIP0
Robot Cleaner - Robot Cleaner -
Pre Filter (Washable) ○ Pre Filter (Washable) ○
Ion Generator - Ion Generator -
CO2 Sensor - CO2 Sensor -
Ventilation Kit PTVK430 Ventilation Kit PTVK430
IR Receiver - IR Receiver -
Zone Controller - Zone Controller -
PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible), PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible),
Dry Contact (with additional accessory) Dry Contact (with additional accessory)
PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus) PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus)
External Input (1 point) ○ External Input (1 point) ○
Wi-Fi PWFMDD200 Wi-Fi PWFMDD200
※ ○ : Applied, - : Not applied ※ ○ : Applied, - : Not applied
Option : Refer to model name in table Option : Refer to model name in table

070 / 071
INDOOR UNITS _ CEILING MOUNTED CASSETTE _ SPECIFICATION

4 Way CASSETTE (840 X 840) 4 Way CASSETTE (840 X 840)


ARNU24GTPA4 / ARNU28GTPA4 ARNU42GTMA4 / ARNU48GTMA4
ARNU30GTPA4 / ARNU36GTNA4 ARNU54GTMA4

INDOOR
UNITS
Model Unit ARNU24GTPA4 ARNU28GTPA4 ARNU30GTPA4 ARNU36GTNA4 Model Unit ARNU42GTMA4 ARNU48GTMA4 ARNU54GTMA4

CEILING MOUNTED CASSETTE


Cooling Capacity kW 7.1 8.2 9.0 10.6 Cooling Capacity kW 12.3 14.1 15.8
Heating Capacity kW 8.0 9.2 10.0 11.9 Heating Capacity kW 13.8 15.9 18.0
Power Input Power Input
Nominal W 18 / 16 / 14 20 / 17 / 15 26 / 24 / 21 70 / 53 / 43 Nominal W 86 / 78 / 69 89 / 84 / 78 98 / 92 / 78
(H / M / L) (H / M / L)
Dimensions Body mm 840 x 204 x 840 840 x 204 x 840 840 x 204 x 840 840 x 246 x 840 Dimensions Body mm 840 x 288 x 840 840 x 288 x 840 840 x 288 x 840
(W x H x D) Shipping mm 950 x 35 x 950 950 x 35 x 950 950 x 35 x 950 950 x 35 x 950 (W x H x D) Shipping mm 950 x 35 x 950 950 x 35 x 950 950 x 35 x 950
Type Turbo Fan Turbo Fan Turbo Fan Turbo Fan Type Turbo Fan Turbo Fan Turbo Fan
Motor Output x Number W x No. 30 x 1 30 x 1 30 x 1 135 x 1 Motor Output x Number W x No. 135 x 1 135 x 1 135 x 1
Fan Fan
Air Flow Rate (H / M / L) m³/min 17.0 / 15.0 / 13.0 19.0 / 16.0 / 14.0 24.3 / 22.8 / 19.5 25 / 21 / 19 Air Flow Rate (H / M / L) m³/min 30 / 27 / 24 31 / 29 / 27 34 / 32 / 27
Motor Type BLDC BLDC BLDC BLDC Motor Type BLDC BLDC BLDC
Air Filter Pre Filter Pre Filter Pre Filter Pre Filter Air Filter Pre Filter Pre Filter Pre Filter
Liquid Side mm (inch) Ø9.52 (3/8) Ø9.52 (3/8) Ø9.52 (3/8) Ø9.52 (3/8) Liquid Side mm (inch) Ø9.52 (3/8) Ø9.52 (3/8) Ø9.52 (3/8)
Pipe Pipe
Gas Side mm (inch) Ø15.88 (5/8) Ø15.88 (5/8) Ø15.88 (5/8) Ø15.88 (5/8) Gas Side mm (inch) Ø15.88 (5/8) Ø15.88 (5/8) Ø15.88 (5/8)
Connections Connections
Drain Pipe (Internal Dia.) mm (inch) 25 (1) 25 (1) 25 (1) 25 (1) Drain Pipe (Internal Dia.) mm (inch) 25 (1) 25 (1) 25 (1)
Weight Body kg 20.8 (45.8) 20.8 (45.8) 20.8 (45.8) 23.5 (51.8) Weight Body kg 25.6 (56.4) 25.6 (56.4) 26.5 (58.4)
Sound Pressure Levels (H / M / L) dB(A) 36 / 34 / 31 39 / 35 / 33 40 / 36 / 33 43 / 40 / 37 Sound Pressure Levels (H / M / L) dB(A) 44 / 41 / 38 46 / 43 / 41 50 / 48 / 44
Sound Power Levels (H / M / L) dB(A) 46 / 44 / 43 52 / 46 / 44 58 / 57 / 54 56 / 53 / 51 Sound Power Levels (H / M / L) dB(A) 58 / 55 / 50 60 / 56 / 55 60 / 58 / 55
Power Supply Ø, V, Hz 1, 220-230-240, 50/60 1, 220-230-240, 50/60 1, 220-230-240, 50/60 1, 220-230-240, 50/60 Power Supply Ø, V, Hz 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50
Communication Cable mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C Communication Cable mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C
PT-MCGW0 PT-MCGW0 PT-MCGW0 PT-MCGW0 PT-MCGW0 PT-MCGW0 PT-MCGW0
Model Name Model Name
PT-MPGW0 PT-MPGW0 PT-MPGW0 PT-MPGW0 PT-MPGW0 PT-MPGW0 PT-MPGW0
Decoration Exterior Color Morning Fog Morning Fog Morning Fog Morning Fog Decoration Exterior Color Morning Fog Morning Fog Morning Fog
Panel RAL Code RAL 9001 RAL 9001 RAL 9001 RAL 9001 Panel RAL Code RAL 9001 RAL 9001 RAL 9001
(Accessory) Net Dimensions 950 x 25 x 950 950 x 25 x 950 950 x 25 x 950 950 x 25 x 950 (Accessory) Net Dimensions 950 x 25 x 950 950 x 25 x 950 950 x 25 x 950
mm mm
(W x H x D) 950 x 35 x 950 950 x 35 x 950 950 x 35 x 950 950 x 35 x 950 (W x H x D) 950 x 35 x 950 950 x 35 x 950 950 x 35 x 950
Net Weight kg 5.0 / 6.3 5.0 / 6.3 5.0 / 6.3 5.0 / 6.3 Net Weight kg 5.0 / 6.3 5.0 / 6.3 5.0 / 6.3
Note : 1. Performance tested under EN14511 Note : 1. Performance tested under EN14511
2. Capacities are based on the following conditions. 2. Capacities are based on the following conditions.
- Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero
- Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero
3. Due to our policy of innovation, some specifications may be changed without notification. 3. Due to our policy of innovation, some specifications may be changed without notification.

Accessories Accessories
Chassis ARNU24GTPA4 ARNU28GTPA4 ARNU30GTPA4 ARNU36GTNA4 Chassis ARNU42GTMA4 ARNU48GTMA4 ARNU54GTMA4
Drain Pump ○ Drain Pump ○
Cassette Cover PTDCM Cassette Cover PTDCM
Refrigerant Leakage Detector PRLDNVS0 Refrigerant Leakage Detector PRLDNVS0
EEV Kit - EEV Kit -
Independent Power Module PRIP0 Independent Power Module PRIP0
Robot Cleaner - Robot Cleaner -
Pre Filter (Washable) ○ Pre Filter (Washable) ○
Ion Generator - Ion Generator -
CO2 Sensor - CO2 Sensor -
Ventilation Kit PTVK430 Ventilation Kit PTVK430
IR Receiver - IR Receiver -
Zone Controller - Zone Controller -
PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible), PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible),
Dry Contact (with additional accessory) Dry Contact (with additional accessory)
PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus) PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus)
External Input (1 point) ○ External Input (1 point) ○
Wi-Fi PWFMDD200 Wi-Fi PWFMDD200

※ ○ : Applied, - : Not applied ※ ○ : Applied, - : Not applied


Option : Refer to model name in table Option : Refer to model name in table

072 / 073
INDOOR UNITS _ CEILING MOUNTED CASSETTE _ SPECIFICATION

2 Way CASSETTE 2 Way CASSETTE


ARNU09GTSA4 / ARNU12GTSA4 ARNU18GTSA4 / ARNU24GTSA4

INDOOR
UNITS
Model Unit ARNU09GTSA4 ARNU12GTSA4 Model Unit ARNU18GTSA4 ARNU24GTSA4

CEILING MOUNTED CASSETTE


Cooling Capacity kW 2.8 3.6 Cooling Capacity kW 5.6 7.1
Heating Capacity kW 3.2 4.0 Heating Capacity kW 6.3 8.0
Power Input Power Input
Nominal W 16 / 14 / 11 18 / 14 / 11 Nominal W 19 / 16 / 14 31 / 22 / 14
(H / M / L) (H / M / L)
Dimensions Body mm 830 x 225 x 600 830 x 225 x 600 Dimensions Body mm 830 x 225 x 600 830 x 225 x 600
(W x H x D) Shipping mm 1,055 x 290 x 682 1,055 x 290 x 682 (W x H x D) Shipping mm 1,055 x 290 x 682 1,055 x 290 x 682
Type Turbo Fan Turbo Fan Type Turbo Fan Turbo Fan
Motor Output x Number W x No. 37 x 1 37 x 1 Motor Output x Number W x No. 37 x 1 37 x 1
Fan Fan
Air Flow Rate (H / M / L) m³/min 10.8 / 9.8 / 9.1 11.1 / 10.3 / 9.1 Air Flow Rate (H / M / L) m³/min 11.8 / 10.8 / 9.8 14.5 / 12.4 / 10.3
Motor Type BLDC BLDC Motor Type BLDC BLDC
Air Filter Pre Filter Pre Filter Air Filter Pre Filter Pre Filter
Liquid Side mm (inch) Ø6.35 (1/4) Ø6.35 (1/4) Liquid Side mm (inch) Ø6.35 (1/4) Ø9.52 (3/8)
Pipe Pipe
Gas Side mm (inch) Ø12.7 (1/2) Ø12.7 (1/2) Gas Side mm (inch) Ø12.7 (1/2) Ø15.88 (5/8)
Connections Connections
Drain Pipe (Internal Dia.) mm (inch) 25 (1) 25 (1) Drain Pipe (Internal Dia.) mm (inch) 25 (1) 25 (1)
Weight Body kg 18.1 18.1 Weight Body kg 18.1 18.1
Sound Pressure Levels (H / M / L) dB(A) 33 / 31 / 29 34 / 32 / 29 Sound Pressure Levels (H / M / L) dB(A) 35 / 33 / 31 40 / 37 / 33
Sound Power Levels (H / M / L) dB(A) 42 / 40 / 38 43 / 41 / 39 Sound Power Levels (H / M / L) dB(A) 44 / 42 / 40 48 / 45 / 40
Power Supply Ø, V, Hz 1, 220-230-240, 50/60 1, 220-230-240, 50/60 Power Supply Ø, V, Hz 1, 220-230-240, 50/60 1, 220-230-240, 50/60
Communication Cable mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C Communication Cable mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C
Model Name PT-USC PT-USC Model Name PT-USC PT-USC
Exterior Color Morning Fog Morning Fog Exterior Color Morning Fog Morning Fog
Decoration Decoration
Panel RAL Code RAL 9001 RAL 9001 Panel RAL Code RAL 9001 RAL 9001
(Accessory) Net Dimensions (Accessory) Net Dimensions mm 1,100 x 28 x 690 1,100 x 28 x 690
mm 1,100 x 28 x 690 1,100 x 28 x 690 (W x H x D)
(W x H x D)
Net Weight kg 4.65 4.65 Net Weight kg 4.65 4.65

Note : 1. Performance tested under EN14511 Note : 1. Performance tested under EN14511
2. Capacities are based on the following conditions. 2. Capacities are based on the following conditions.
- Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero
- Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero
3. Due to our policy of innovation, some specifications may be changed without notification. 3. Due to our policy of innovation, some specifications may be changed without notification.

Accessories Accessories
Chassis ARNU09GTSA4 ARNU12GTSA4 Chassis ARNU18GTSA4 ARNU24GTSA4
Drain Pump ○ Drain Pump ○
Cassette Cover - Cassette Cover -
Refrigerant Leakage Detector PRLDNVS0 Refrigerant Leakage Detector PRLDNVS0
EEV Kit PRGK024A0 (~5.6kW) EEV Kit PRGK024A0 (~5.6kW)
Independent Power Module PRIP0 Independent Power Module PRIP0
Robot Cleaner - Robot Cleaner -
Pre Filter (Washable) ○ Pre Filter (Washable) ○
Ion Generator - Ion Generator -
CO2 Sensor - CO2 Sensor -
Ventilation Kit - Ventilation Kit -
IR Receiver - IR Receiver -
Zone Controller - Zone Controller -
PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible), PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible),
Dry Contact (with additional accessory) Dry Contact (with additional accessory)
PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus) PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus)
External Input (1 point) ○ External Input (1 point) ○
Wi-Fi PWFMDD200 Wi-Fi PWFMDD200

※ ○ : Applied, - : Not applied ※ ○ : Applied, - : Not applied


Option : Refer to model name in table Option : Refer to model name in table

074 / 075
INDOOR UNITS _ CEILING MOUNTED CASSETTE _ SPECIFICATION

1 Way CASSETTE 1 Way CASSETTE


ARNU07GTUB4 / ARNU09GTUB4 ARNU18GTTB4 / ARNU24GTTB4
ARNU12GTUB4

INDOOR
UNITS
Model Unit ARNU07GTUB4 ARNU09GTUB4 ARNU12GTUB4 Model Unit ARNU18GTTB4 ARNU24GTTB4

CEILING MOUNTED CASSETTE


Cooling Capacity kW 2.2 2.8 3.6 Cooling Capacity kW 5.6 7.1
Heating Capacity kW 2.5 3.2 4.0 Heating Capacity kW 6.3 7.1
Power Input Power Input
Nominal W 20 / 18 / 16 22 / 20 / 18 24 / 22 / 20 Nominal W 38 / 28 / 24 51 / 33 / 26
(H / M / L) (H / M / L)
Dimensions Body mm 860 x 132 x 450 860 x 132 x 450 860 x 132 x 450 Dimensions Body mm 1,180 x 132 x 450 1,180 x 132 x 450
(W x H x D) Shipping mm 1,129 x 259 x 538 1,129 x 259 x 538 1,129 x 259 x 538 (W x H x D) Shipping mm 1,499 x 259 x 538 1,499 x 259 x 538
Type Cross Flow Fan Cross Flow Fan Cross Flow Fan Type Cross Flow Fan Cross Flow Fan
Motor Output x Number W x No. 30 x 1 30 x 1 30 x 1 Motor Output x Number W x No. 30 x 1 30 x 1
Fan Fan
Air Flow Rate (H / M / L) m³/min 8.2 / 7.3 / 6.4 9.2 / 8.6 / 8.2 10.0 / 9.2 / 8.2 Air Flow Rate (H / M / L) m³/min 13.3 / 12.1 / 10.9 14.6 / 13.3 / 11.5
Motor Type BLDC BLDC BLDC Motor Type BLDC BLDC
Air Filter Pre Filter Pre Filter Pre Filter Air Filter Pre Filter Pre Filter
Liquid Side mm (inch) Ø6.35 (1/4) Ø6.35 (1/4) Ø6.35 (1/4) Liquid Side mm (inch) Ø6.35 (1/4) Ø9.52 (3/8)
Pipe Pipe
Gas Side mm (inch) Ø12.7 (1/2) Ø12.7 (1/2) Ø12.7 (1/2) Gas Side mm (inch) Ø12.7 (1/2) Ø15.88 (5/8)
Connections Connections
Drain Pipe (Internal Dia.) mm (inch) Ø25 (1) Ø25 (1) Ø25 (1) Drain Pipe (Internal Dia.) mm (inch) Ø25 (1) Ø25 (1)
Weight Body kg 13.6 13.6 13.6 Weight Body kg 15.6 15.6
Sound Pressure Levels (H / M / L) dB(A) 32 / 29 / 25 35 / 34 / 32 38 / 35 / 32 Sound Pressure Levels (H / M / L) dB(A) 40 / 37 / 35 43 / 40 / 36
Sound Power Levels (H / M / L) dB(A) 47 / 44 / 41 50 / 48 / 47 52 / 50 / 47 Sound Power Levels (H / M / L) dB(A) 56 / 51 / 48 59 / 53 / 50
Power Supply Ø, V, Hz 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 Power Supply Ø, V, Hz 1, 220-240, 50 1, 220-240, 50
Communication Cable mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C Communication Cable mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C
Model Name PT-UAHW0, PT-UPHG0 PT-UAHW0, PT-UPHG0 PT-UAHW0, PT-UPHG0 Model Name PT-TAHW0, PT-TPHG0 PT-TAHW0, PT-TPHG0
Exterior Color Noble White Noble White Noble White Exterior Color Noble White Noble White
Decoration Decoration
Panel RAL Code RAL 9003 RAL 9003 RAL 9003 Panel RAL Code RAL 9003 RAL 9003
(Accessory) Net Dimensions mm 1,100 x 34 x 500 1,100 x 34 x 500 1,100 x 34 x 500 (Accessory) Net Dimensions mm 1,420 x 34 x 500 1,420 x 34 x 500
(W x H x D) (W x H x D)
Net Weight kg 3.3 / 4.1 3.3 / 4.1 3.3 / 4.1 Net Weight kg 5.5 / 6.5 5.5 / 6.5

Note : 1. Performance tested under EN14511 Note : 1. Performance tested under EN14511
2. Capacities are based on the following conditions. 2. Capacities are based on the following conditions.
- Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero
- Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero
3. Due to our policy of innovation, some specifications may be changed without notification. 3. Due to our policy of innovation, some specifications may be changed without notification.

Accessories Accessories
Chassis ARNU07GTUB4 ARNU09GTUB4 ARNU12GTUB4 Chassis ARNU18GTTB4 ARNU24GTTB4
Drain Pump ○ Drain Pump ○
Cassette Cover - Cassette Cover -
Refrigerant Leakage Detector PRLDNVS0 Refrigerant Leakage Detector PRLDNVS0
EEV Kit PRGK024A0 EEV Kit -
Independent Power Module PRIP0 Independent Power Module PRIP0
Robot Cleaner - Robot Cleaner -
Pre Filter (Washable) ○ Pre Filter (Washable) ○
Ion Generator - Ion Generator -
CO2 Sensor - CO2 Sensor -
Ventilation Kit - Ventilation Kit -
IR Receiver - IR Receiver -
Zone Controller - Zone Controller -
PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible), PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible),
Dry Contact (with additional accessory) Dry Contact (with additional accessory)
PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus) PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus)
External Input (1 point) ○ External Input (1 point) ○
Wi-Fi PWFMDD200 Wi-Fi PWFMDD200

※ ○ : Applied, - : Not applied ※ ○ : Applied, - : Not applied


Option : Refer to model name in table Option : Refer to model name in table

076 / 077
INDOOR UNITS _ CEILING MOUNTED ROUND CASSETTE INDOOR UNITS _ CEILING MOUNTED ROUND CASSETTE _ KEY FEATURES

NEW DESIGN
Slim and Compact design Visible air flow
CEILING MOUNTED Reduce the height of the body by 15% save space and
maximize the openness of the interior space.
With crystal vein for 6-step precision control, you can send
cool / heated air wherever you want.

ROUND CASSETTE Other Brand LG Round Cassette Other Brand LG Round Cassette

INDOOR
UNITS
384mm
330mm

CEILING MOUNTED ROUND CASSETTE


15% less body height makes
room more higher Crystal Vein
※ Product : 48 kBtu
Wind direction Wind direction
control ❶ ❷ ❸ control ❶ ❷ ❸ ❹ ❺ ❻

Minimal exposure design Powerful and Quiet air flow


Pipes are brought together in one place to minimize exposure. 3D fan increases airflow by 5% and noise reduction
Hanger covers hide installations to add a clean look. technology makes a quieter, more comfortable space.

Other Brand LG Round Cassette Full 3D Fan, Air flow rate 5% ↑ Full 3D Fan, Low noise

Talking
❶ Drain Pipe Library 50 dB(A) Office
40 dB(A) 55 dB(A)
LG Vacuum
Round CST Cleaner
39 dB(A) 70 dB(A)
Previous New
(4 Way) (Round) ※ 48 kBtu, Low flow rate

❷ Refrigerant Pipe ❶ Piping in One Direction Only

❸ Exposed Hanger ❷ Hanger Cover Normal communication Library Noise level 40 dB(A)
Noise level 50 dB(A)

Features & Benefits Key Applications


• Luxury round design can make a luxurious space with a round design • Retail Perfect round air flow 30% Faster in cooling
considering side view. • Restaurant Perfect round flow without blind spots. Larger airflow rate, cooling rate is faster than 30%.
• Perfect round air flow without blind spots. • Office
Other Brand LG Round Cassette
• Hotel

Cassette Round
Smart Wi-Fi ○
Energy Efficiency Human Detect Sensor - Other Brand LG Round Cassette
Drain Pump ○
Sleep Mode ○
Timer (On / Off) ○
Comfort
Timer (Weekly) ○
Two Thermistor Control ○
Group Control ○ Set temperature reach time 18 minutes Set temperature reach time 12 minutes
(Height 1.1m) (Height 1.1m)

※ Based on test results from LG chamber, this image is designed to help customers
understand. Experimental environment: height 3.2m, 48 kBtu, cooling mode,
3 Way airflow with blind spot. Perfect circular airflow without blind spots. high flow rate, horizontal air flow direction

078 / 079
INDOOR UNITS _ CEILING MOUNTED ROUND CASSETTE _ SPECIFICATION

ROUND CEILING CASSETTE


ARNU24GTYA4 / ARNU36GTYA4
ARNU48GTYA4

INDOOR
UNITS
Model Unit ARNU24GTYA4 ARNU36GTYA4 ARNU48GTYA4

CEILING MOUNTED ROUND CASSETTE


Cooling Capacity kW 7.1 10.6 14.1
Heating Capacity kW 8.0 11.9 15.9
Power Input
Nominal W 44 / 36 / 29 63 / 47 / 36 98 / 70 / 44
(H / M / L)
Dimensions Body mm 1,050 x 330 x 1,050 1,050 x 330 x 1,050 1,050 x 330 x 1,050
(W x H x D) Shipping mm 1,137 x 395 x 1,132 1,137 x 395 x 1,132 1,137 x 395 x 1,132
Type 3D Turbo Fan 3D Turbo Fan 3D Turbo Fan
Motor Output x Number W x No. 157 x 1 157 x 1 157 x 1
Fan
Air Flow Rate (H / M / L) m3/min 22 / 21 / 19 27 / 24 / 21 32 / 28 / 23
Motor Type BLDC BLDC BLDC
Air Filter Long life Long life Long life
Liquid Side mm (inch) Ø9.52 (3/8) Ø9.52 (3/8) Ø9.52 (3/8)
Pipe
Gas Side mm (inch) Ø15.88 (5/8) Ø15.88 (5/8) Ø15.88 (5/8)
Connections
Drain Pipe (Internal Dia.) mm (inch) Ø25 (1) Ø25 (1) Ø25 (1)
Weight Body kg 30 30 30
Sound Pressure Level (H / M / L) dB(A) 39 / 37 / 34 43 / 39 / 37 47 / 44 / 39
Sound Power Level (H / M / L) dB(A) 48 / 46 / 43 52 / 48 / 46 56 / 53 / 48
Power Supply Ø, V, Hz 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50
Communication Cable mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C

Note : 1. Performance tested under EN14511


2. Capacities are based on the following conditions.
- Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero
- Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero
3. Due to our policy of innovation, some specifications may be changed without notification.

Accessories
Chassis ARNU24GTYA4 ARNU36GTYA4 ARNU48GTYA4
Drain Pump ○
Cassette Cover -
Refrigerant Leakage Detector PRLDNVS0
EEV Kit -
Independent Power Module PRIP0
Robot Cleaner -
Pre Filter (Washable) ○
Ion Generator -
CO2 Sensor -
Ventilation Kit -
IR Receiver -
Zone Controller -
PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible),
Dry Contact (with additional accessory)
PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus)
External Input (1 Point) ○
Wi-Fi PWFMDD200
Human detection sensor -
Floor Temperature Sensor -
Air cleaning kit -
Elevation Grille -

※ ○ : Applied, - : Not applied


Option : Refer to model name in table

080 / 081
INDOOR UNITS _ CEILING CONCEALED DUCT INDOOR UNITS _ CEILING CONCEALED DUCT _ KEY FEATURES

SMART ENERGY EFFICIENCY


Wi-Fi Control External Static Pressure (ESP) Control
CEILING Anytime, anywhere access with LG ThinQTM mobile app. User has easy access to air volume selection via remote
controller using the ESP control function.

CONCEALED DUCT LG ThinQTM


Search “LG ThinQTM” on Google market or Appstore then
The BLDC motor can control fan speed and air volume.
No additional accessories are necessary to control air flow.

INDOOR
download the app.

UNITS
LG ThinQTM
E.S.P. E.S.P.
Control Control

Comfort Cooling / Comfort Cooling /


Wi-Fi Heating Heating

CEILING CONCEALED DUCT


Static Pressure 11- Step Control
Depending on the installation environment, LG's ceiling
concealed duct controls the static pressure with 11steps
to provide maximized comfort to any environment.

LG ThinQTM Conventional New

1 step
Static Pressure
Low Setting
* Wi-Fi modem (Option) is necessary for this function

Easy Registration and Log-in 11 steps

Follow the easy set-up steps that will activate LG ThinQ ’s user-friendly features.
TM Static Pressure
Power Setting

Energy Monitoring
Accumulated electric energy of the indoor unit can be
identified with wired remote control, as well as with
the central controller. This function is an advantage for
energy management.

Features & Benefits Key Applications


Install Scene Apply for multistory building
• Easy and flexible duct adjusts air volume with External Static Pressure (ESP) • Office 100kWh
control function. • Hotel
Watt PDI
• Minimalist visibility (Hidden within ceiling) to blend seamlessly into any interior • Retail Meter
• Residential building Total Power
Input

Premium Wired Total accumulated


Remote Controller electric energy 20kWh
Simple operation for various functions 595kWh

Duct High Middle Low 50kWh


Smart Wi-Fi ○ ○ ○
Energy Efficiency E.S.P Control ○ ○ ○ Standard Wired Total accumulated
Drain Pump ○ ○ ○ Remote Controller electric energy 30kWh
Timer (On / Off) ○ ○ ○ 3,977kWh

Comfort Timer (Weekly) ○ ○ ○


On/Off, Current Temp Mode, Set Temp Vane Control ※ Outdoor unit's accumulated electric energy / using rate of individual indoor unit + indoor
Two Thermistor Control ○ ○ ○ unit's accumulated electric energy is displayed in wired remote controller, only when
Group Control ○ ○ ○ central controller, digital integrating electricity meter and PDI are installed and PDI,
outdoor unit and indoor unit are connected with power wire. Only total accumulated
※ ○ : Applied, - : Not applied electric energy is displayed in standard wired remote controller. In premium wired remote
controller, that are displayed into week / month / year.

082 / 083
INDOOR UNITS _ CEILING CONCEALED DUCT _ KEY FEATURES

COMFORT
Multiple Room Operation Minimized Height
Using a spiral duct (Embedded or flexible type) and New mid-static ducts provide ideal solution for installation
stream chamber, it is possible to operate cooling / heating in limited space.
for several rooms simultaneously.

270mm

INDOOR
UNITS
8 / 10kW 12.5kW
380
mm
298
mm

CEILING CONCEALED DUCT


270 270
mm mm

Conventional New Conventional New

Filter Alert Two Thermistors Control


The alarm is activated when the filter needs to be The indoor temperature can be checked using the thermistors
cleaned, and the time remaining for cleaning is displayed in the remote controller as well as from the indoor unit.
on the screen. There may be a significant difference between ceiling and
floor air temperature. Two thermistors can optimize indoor air
Remain Time Until Indoor Filter Cleaning + Alarm
temperature for a more comfortable environment.

Indoor Unit Thermistor


Standard Wired
Remote Controller

Remain time until indoor filter cleaning 2,400hr.

Premium Wired
Remote Controller
Remote Controller Thermistor
Remain time until indoor filter cleaning 1,729hr.

1 Point External Input (On / Off Control)


Flexible Installation (Low Static Duct Only) Indoor unit can be controlled by external devices without
The low static duct allows the air intake at the rear or dry contact, so customer can save cost of installation.
bottom under specific installation conditions.
Connection between an indoor unit and external devices directly
Not Necessary
Air intake at the rear or bottom
Motion Detector
Sensor

Not Necessary
for Dry Contact

Cost Savings

Key Tag

※ In case of needing more functions beside on / off control, a dry contact is required
to be installed.

084 / 085
INDOOR UNITS _ CEILING CONCEALED DUCT _ SPECIFICATION

MID STATIC HIGH STATIC


ARNU07GM1A4 / ARNU09GM1A4 ARNU28GM2A4 / ARNU36GM2A4
ARNU12GM1A4 / ARNU15GM1A4 ARNU42GM2A4 / ARNU48GM3A4
ARNU18GM1A4 / ARNU24GM1A4 ARNU54GM3A4

INDOOR
UNITS
Model Unit ARNU07GM1A4 ARNU09GM1A4 ARNU12GM1A4 ARNU15GM1A4 ARNU18GM1A4 ARNU24GM1A4 Model Unit ARNU28GM2A4 ARNU36GM2A4 ARNU42GM2A4 ARNU48GM3A4 ARNU54GM3A4

CEILING CONCEALED DUCT


Cooling Capacity kW 2.2 2.8 3.6 4.5 5.6 7.1 Cooling Capacity kW 8.2 10.6 12.3 14.1 15.8
Heating Capacity kW 2.5 3.2 4.0 5.0 6.3 8.0 Heating Capacity kW 9.2 11.9 13.8 15.9 18.0
Power Input Power Input
Nominal W 39 / 30 / 25 40 / 32 / 26 46 / 38 / 31 67 / 53 / 46 85 / 63 / 55 91 / 74 / 58 Nominal W 123 / 81 / 57 184 / 123 / 81 231 / 162 / 111 172 / 105 / 65 260 / 215 / 172
(H / M / L) (H / M / L)
Dimensions Body mm 900 x 270 x 700 900 x 270 x 700 900 x 270 x 700 900 x 270 x 700 900 x 270 x 700 900 x 270 x 700 Dimensions Body mm 1,250 x 270 x 700 1,250 x 270 x 700 1,250 x 270 x 700 1,250 x 360 x 700 1,250 x 360 x 700
(W x H x D) Shipping mm 1,100 x 338 x 773 1,100 x 338 x 773 1,100 x 338 x 773 1,100 x 338 x 773 1,100 x 338 x 773 1,100 x 338 x 773 (W x H x D) Shipping mm 1,450 x 338 x 773 1,450 x 338 x 773 1,450 x 338 x 773 1,450 x 428 x 773 1,450 x 428 x 773
Type Sirocco Fan Sirocco Fan Sirocco Fan Sirocco Fan Sirocco Fan Sirocco Fan Type Sirocco Fan Sirocco Fan Sirocco Fan Sirocco Fan Sirocco Fan
Motor Output x Number W x No. 136 x 1 136 x 1 136 x 1 136 x 1 136 x 1 136 x 1 Motor Output x Number W x No. 350 x 1 350 x 1 350 x 1 350 x 1 350 x 1
Air Flow Rate (H / M / L) m³/min 9.0 / 7.5 / 6.0 9.5 / 7.5 / 6.0 11.0 / 9.0 / 7.0 16.0 / 12.0 / 9.0 17.0 / 14.5 / 12.0 19.0 / 16.0 / 14.0 Air Flow Rate (H / M / L) m³/min 28.0 / 24.0 / 21.0 32.0 / 28.0 / 24.0 38.0 / 33.0 / 28.0 40.0 / 34.0 / 28.0 50.0 / 45.0 / 40.0
External Static Pressure External Static Pressure
mmAq (Pa) 6 (59) 6 (59) 6 (59) 6 (59) 6 (59) 6 (59) mmAq (Pa) 6 (59) 6 (59) 6 (59) 6 (59) 6 (59)
Fan (High Mode) Fan (High Mode)
Air Flow Rate (H / M / L) Air Flow Rate (H / M / L)
m³/min 9.0 / 7.5 / 6.0 9.5 / 7.5 / 6.0 11.0 / 9.0 / 7.0 16.0 / 12.0 / 9.0 17.0 / 14.5 / 12.0 19.0 / 16.0 / 14.0 m³/min 28.0 / 24.0 / 21.0 32.0 / 28.0 / 24.0 38.0 / 33.0 / 28.0 40.0 / 34.0 / 28.0 50.0 / 45.0 / 40.0
(Standard Mode) (Standard Mode)
External Static Pressure External Static Pressure
mmAq (Pa) 2.5 (25) 2.5 (25) 2.5 (25) 2.5 (25) 2.5 (25) 2.5 (25) mmAq (Pa) 5 (49) 5 (49) 5 (49) 5 (49) 5 (49)
(Standard Mode) (Standard Mode)
Motor Type BLDC BLDC BLDC BLDC BLDC BLDC Motor Type BLDC BLDC BLDC BLDC BLDC
Air Filter Pre Filter Pre Filter Pre Filter Pre Filter Pre Filter Pre Filter Air Filter Pre Filter Pre Filter Pre Filter Pre Filter Pre Filter
Liquid Side mm (inch) Ø6.35 (1/4) Ø6.35 (1/4) Ø6.35 (1/4) Ø6.35 (1/4) Ø6.35 (1/4) Ø9.52 (3/8) Liquid Side mm (inch) Ø9.52 (3/8) Ø9.52 (3/8) Ø9.52 (3/8) Ø9.52 (3/8) Ø9.52 (3/8)
Pipe Pipe
Gas Side mm (inch) Ø12.7 (1/2) Ø12.7 (1/2) Ø12.7 (1/2) Ø12.7 (1/2) Ø12.7 (1/2) Ø15.88 (5/8) Gas Side mm (inch) Ø15.88 (5/8) Ø15.88 (5/8) Ø15.88 (5/8) Ø15.88 (5/8) Ø19.05 (3/4)
Connections Connections
Drain Pipe (Internal Dia.) mm (inch) 25 (1) 25 (1) Ø25 (1) Ø25 (1) Ø25 (1) Ø25 (1) Drain Pipe (Internal Dia.) mm (inch) Ø25 (1) Ø25 (1) Ø25 (1) Ø25 (1) Ø25 (1)
Weight Body kg 25.5 25.5 25.5 25.5 25.5 26.5 Weight Body kg 38.0 38.0 39.5 44.0 44.0
Sound Pressure Levels (H / M / L) dB(A) 26 / 24 / 23 27 / 25 / 23 27 / 25 / 23 30 / 27 / 23 31 / 28 / 25 32 / 29 / 26 Sound Pressure Levels (H / M / L) dB(A) 36 / 34 / 33 37 / 36 / 34 38 / 37 / 36 39 / 37 / 35 42 / 40 / 39
Sound Power Levels (H / M / L) dB(A) 55 / 54 / 51 55 / 54 / 52 56 / 54 / 52 59 / 57 / 55 59 / 57 / 55 59 / 58 / 56 Sound Power Levels (H / M / L) dB(A) 59 / 57 / 55 60 / 59 / 57 62 / 61 / 60 63 / 60 / 59 65 / 64 / 62
Power Supply Ø, V, Hz 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 Power Supply Ø, V, Hz 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50
Communication Cable mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C Communication Cable mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C
Note : 1. Performance tested under EN14511 Note : 1. Performance tested under EN14511
2. Capacities are based on the following conditions. 2. Capacities are based on the following conditions.
- Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero
- Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero
3. Due to our policy of innovation, some specifications may be changed without notification. 3. Due to our policy of innovation, some specifications may be changed without notification.

Accessories Accessories
Chassis ARNU07GM1A4 ARNU09GM1A4 ARNU12GM1A4 ARNU15GM1A4 ARNU18GM1A4 ARNU24GM1A4 Chassis ARNU28GM2A4 ARNU36GM2A4 ARNU42GM2A4 ARNU48GM3A4 ARNU54GM3A4
Drain Pump ○ Drain Pump ○
Cassette Cover - Cassette Cover -
Refrigerant Leakage Detector PRLDNVS0 Refrigerant Leakage Detector PRLDNVS0
EEV Kit PRGK024A0 (~5.6kW) EEV Kit -
Independent Power Module PRIP0 Independent Power Module PRIP0
Robot Cleaner - Robot Cleaner -
Pre Filter (Washable) ○ Pre Filter (Washable) ○
Ion Generator - Ion Generator -
CO2 Sensor - CO2 Sensor -
Ventilation Kit - Ventilation Kit -
IR Receiver PWLRVN000 IR Receiver PWLRVN000
Zone Controller ABZCA Zone Controller ABZCA
PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible), PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible),
Dry Contact (with additional accessory) Dry Contact (with additional accessory)
PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus) PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus)
External Input (1 point) ○ External Input (1 point) ○
Wi-Fi PWFMDD200 Wi-Fi PWFMDD200

※ ○ : Applied, - : Not applied ※ ○ : Applied, - : Not applied


Option : Refer to model name in table Option : Refer to model name in table

086 / 087
INDOOR UNITS _ CEILING CONCEALED DUCT _ SPECIFICATION

HIGH STATIC LOW STATIC


ARNU76GB8A4 / ARNU96GB8A4 ARNU05GL1G4 / ARNU07GL1G4
ARNU09GL1G4

INDOOR
UNITS
Model Unit ARNU76GB8A4 ARNU96GB8A4 Model Unit ARNU05GL1G4 ARNU07GL1G4 ARNU09GL1G4

CEILING CONCEALED DUCT


Cooling Capacity kW 22.4 28.0 Cooling Capacity kW 1.7 2.2 2.8
Heating Capacity kW 25.2 31.5 Heating Capacity kW 1.9 2.5 3.2
Power Input Power Input
Nominal W 765 / 500 / 500 800 / 750 / 750 Nominal W 29 / 26 / 24 31 / 28 / 24 39 / 29 / 24
(H / M / L) (H / M / L)
Dimensions Body mm 1,562 x 460 x 688 1,562 x 460 x 688 Dimensions Body mm 700 x 190 x 700 700 x 190 x 700 700 x 190 x 700
(W x H x D) Shipping mm 1,806 x 537 x 825 1,806 x 537 x 825 (W x H x D) Shipping mm 862 x 255 x 781 862 x 255 x 781 862 x 255 x 781
Type Sirocco Fan Sirocco Fan Type Sirocco Fan Sirocco Fan Sirocco Fan
Motor Output x Number W x No. 375 x 2 375 x 2 Motor Output x Number W x No. 19 x 1 19 x 1 19 x 1
Air Flow Rate (H / M / L) Air Flow Rate (H / M / L)
m³/min 60.0 / 50.0 / 50.0 72.0 / 64.0 / 64.0 m³/min 6.7 / 6.2 / 5.5 7.5 / 6.5 / 5.5 9.0 / 7.0 / 5.5
(High Mode-Factory Set) (High Mode-Factory Set)
External Static Pressure External Static Pressure
Fan mmAq (Pa) 22 (216) 22 (216) Fan mmAq (Pa) 2.54 (25) 2.54 (25) 2.54 (25)
(High Mode) (High Mode)
Air Flow Rate (H / M / L) Air Flow Rate (H / M / L)
m³/min 64.0 / 50.0 / 50.0 76.0 / 64.0 / 64.0 m³/min 6.7 / 6.2 / 5.5 7.5 / 6.5 / 5.5 9.0 / 7.0 / 5.5
(Standard Mode) (Standard Mode)
External Static Pressure External Static Pressure
mmAq (Pa) 15 (147) 15 (147) mmAq (Pa) 0 (0) 0 (0) 0 (0)
(Standard Mode) (Standard Mode)
Motor Type BLDC BLDC Motor Type BLDC BLDC BLDC
Air Filter Pre Filter Pre Filter Air Filter Pre Filter Pre Filter Pre Filter
Liquid Side mm (inch) Ø9.52 (3/8) Ø9.52 (3/8) Liquid Side mm (inch) Ø6.35 (1/4) Ø6.35 (1/4) Ø6.35 (1/4)
Pipe Pipe
Gas Side mm (inch) Ø19.05 (3/4) Ø22.2 (7/8) Gas Side mm (inch) Ø12.7 (1/2) Ø12.7 (1/2) Ø12.7 (1/2)
Connections Connections
Drain Pipe (Internal Dia.) mm (inch) Ø25 (1) Ø25 (1) Drain Pipe (Internal Dia.) mm (inch) Ø25 (1) Ø25 (1) Ø25 (1)
Weight Body kg 87.0 87.0 Weight Body kg 17.5 17.5 17.5

Sound Pressure Levels (H / M / L) dB(A) 45 / 41 / 40 47 / 42 / 41 Sound Pressure Levels (H / M / L) dB(A) 25 / 24 / 22 26 / 24 / 22 28 / 25 / 22
Sound Power Levels (H / M / L) dB(A) 70 / 68 / 68 72 / 69 / 68 Sound Power Levels (H / M / L) dB(A) 48 / 46 / 45 50 / 47 / 45 53 / 49 / 45
Power Supply Ø, V, Hz 1, 220-240, 50 1, 220-240, 50 Power Supply Ø, V, Hz 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50
Communication Cable mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C Communication Cable mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C

Note : 1. Performance tested under EN14511 Note : 1. Performance tested under EN14511
2. Capacities are based on the following conditions. 2. Capacities are based on the following conditions.
- Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero
- Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero
3. Due to our policy of innovation, some specifications may be changed without notification. 3. Due to our policy of innovation, some specifications may be changed without notification.

Accessories Accessories
Chassis ARNU76GB8A4 ARNU96GB8A4 Chassis ARNU05GL1G4 ARNU07GL1G4 ARNU09GL1G4
Drain Pump ○ Drain Pump ○
Cassette Cover - Cassette Cover -
Refrigerant Leakage Detector PRLDNVS0 Refrigerant Leakage Detector PRLDNVS0
EEV Kit ○ EEV Kit PRGK024A0
Independent Power Module PRIP0 Independent Power Module PRIP0
Robot Cleaner - Robot Cleaner -
Pre Filter (Washable) ○ Pre Filter (Washable) ○
Ion Generator - Ion Generator -
CO2 Sensor - CO2 Sensor -
Ventilation Kit - Ventilation Kit -
IR Receiver PWLRVN000 IR Receiver PWLRVN000
Zone Controller ABZCA Zone Controller ABZCA
PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible), PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible),
Dry Contact (with additional accessory) Dry Contact (with additional accessory)
PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus) PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus)
External Input (1 point) ○ External Input (1 point) ○
Wi-Fi PWFMDD200 Wi-Fi PWFMDD200

※ ○ : Applied, - : Not applied ※ ○ : Applied, - : Not applied


Option : Refer to model name in table Option : Refer to model name in table

088 / 089
INDOOR UNITS _ CEILING CONCEALED DUCT _ SPECIFICATION

LOW STATIC LOW STATIC


ARNU12GL2G4 / ARNU15GL2G4 ARNU21GL3G4 / ARNU24GL3G4
ARNU18GL2G4

INDOOR
UNITS
Model Unit ARNU12GL2G4 ARNU15GL2G4 ARNU18GL2G4 Model Unit ARNU21GL3G4 ARNU24GL3G4

CEILING CONCEALED DUCT


Cooling Capacity kW 3.6 4.5 5.6 Cooling Capacity kW 6.2 7.1
Heating Capacity kW 4.0 5.0 6.3 Heating Capacity kW 7.0 8.0
Power Input Power Input
Nominal W 41 / 34 / 29 56 / 41 / 34 71 / 56 / 41 Nominal W 72 / 53 / 48 103 / 63 / 48
(H / M / L) (H / M / L)
Dimensions Body mm 900 x 190 x 700 900 x 190 x 700 900 x 190 x 700 Dimensions Body mm 1,100 x 190 x 700 1,100 x 190 x 700
(W x H x D) Shipping mm 1,062 x 255 x 781 1,062 x 255 x 781 1,062 x 255 x 781 (W x H x D) Shipping mm 1,262 x 255 x 781 1,262 x 255 x 781
Type Sirocco Fan Sirocco Fan Sirocco Fan Type Sirocco Fan Sirocco Fan
Motor Output x Number W x No. 19 x 1, 5 x 1 19 x 1, 5 x 1 19 x 1, 5 x 1 Motor Output x Number W x No. 19 x 2 19 x 2
Air Flow Rate (H / M / L) Air Flow Rate (H / M / L)
m³/min 10.0 / 8.5 / 7.0 12.5 / 10.0 / 8.5 15.0 / 12.5 / 10.0 m³/min 17.5 / 14.0 / 12.0 20.0 / 16.0 / 12.0
(High Mode-Factory Set) (High Mode-Factory Set)
External Static Pressure External Static Pressure
Fan mmAq (Pa) 2.54 (25) 2.54 (25) 2.54 (25) Fan mmAq (Pa) 2.54 (25) 2.54 (25)
(High Mode) (High Mode)
Air Flow Rate (H / M / L) Air Flow Rate (H / M / L)
m³/min 10.0 / 8.5 / 7.0 12.5 / 10.0 / 8.5 15.0 / 12.5 / 10.0 m³/min 17.5 / 14.0 / 12.0 20.0 / 16.0 / 12.0
(Standard Mode) (Standard Mode)
External Static Pressure External Static Pressure
mmAq (Pa) 0 (0) 0 (0) 0 (0) mmAq (Pa) 0 (0) 0 (0)
(Standard Mode) (Standard Mode)
Motor Type BLDC BLDC BLDC Motor Type BLDC BLDC
Air Filter Pre Filter Pre Filter Pre Filter Air Filter Pre Filter Pre Filter
Liquid Side mm (inch) Ø6.35 (1/4) Ø6.35 (1/4) Ø6.35 (1/4) Liquid Side mm (inch) Ø9.52 (3/8) Ø9.52 (3/8)
Pipe Pipe
Gas Side mm (inch) Ø12.7 (1/2) Ø12.7 (1/2) Ø12.7 (1/2) Gas Side mm (inch) Ø15.88 (5/8) Ø15.88 (5/8)
Connections Connections
Drain Pipe (Internal Dia.) mm (inch) Ø25 (1) Ø25 (1) Ø25 (1) Drain Pipe (Internal Dia.) mm (inch) Ø25 (1) Ø25 (1)
Weight Body kg 23.0 23.0 23.0 Weight Body kg 27.0 27.0
Sound Pressure Levels (H / M / L) dB(A) 30 / 27 / 25 33 / 30 / 28 35 / 32 / 29 Sound Pressure Levels (H / M / L) dB(A) 35 / 29 / 28 36 / 33 / 28
Sound Power Levels (H / M / L) dB(A) 50 / 47 / 46 54 / 51 / 47 56 / 54 / 51 Sound Power Levels (H / M / L) dB(A) 59 / 55 / 54 63 / 59 / 55
Power Supply Ø, V, Hz 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 Power Supply Ø, V, Hz 1, 220-240, 50 1, 220-240, 50
Communication Cable mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C Communication Cable mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C

Note : 1. Performance tested under EN14511 Note : 1. Performance tested under EN14511
2. Capacities are based on the following conditions. 2. Capacities are based on the following conditions.
- Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero
- Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero
3. Due to our policy of innovation, some specifications may be changed without notification. 3. Due to our policy of innovation, some specifications may be changed without notification.

Accessories Accessories
Chassis ARNU12GL2G4 ARNU15GL2G4 ARNU18GL2G4 Chassis ARNU21GL3G4 ARNU24GL3G4
Drain Pump ○ Drain Pump ○
Cassette Cover - Cassette Cover -
Refrigerant Leakage Detector PRLDNVS0 Refrigerant Leakage Detector PRLDNVS0
EEV Kit - EEV Kit PRGK024A0
Independent Power Module PRIP0 Independent Power Module PRIP0
Robot Cleaner - Robot Cleaner -
Pre Filter (Washable) ○ Pre Filter (Washable) ○
Ion Generator - Ion Generator -
CO2 Sensor - CO2 Sensor -
Ventilation Kit - Ventilation Kit -
IR Receiver PWLRVN000 IR Receiver PWLRVN000
Zone Controller ABZCA Zone Controller ABZCA
PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible), PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible),
Dry Contact (with additional accessory) Dry Contact (with additional accessory)
PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus) PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus)
External Input (1 point) ○ External Input (1 point) ○
Wi-Fi PWFMDD200 Wi-Fi PWFMDD200
※ ○ : Applied, - : Not applied ※ ○ : Applied, - : Not applied
Option : Refer to model name in table Option : Refer to model name in table

090 / 091
INDOOR UNITS _ FRESH AIR INTAKE INDOOR UNITS _ FRESH AIR INTAKE _ SPECIFICATION

FRESH AIR INTAKE FRESH AIR INTAKE


Fresh Outdoor Air Supply ARNU76GB8Z4 / ARNU96GB8Z4

The LG Fresh Air Intake Unit (FAU) is the alternative solution for ventilation, which supplies the fresh outdoor
air indoors as well as being able to cool and heat air inside simultaneously. It means the indoor space can have
positive air pressure consistently, which can block cold, hot or contaminated air from outside.

INDOOR
UNITS
This allows the indoor space to have consistent positive air pressure blocking cold.

Fresh Air Intake

100%
Outdoor Air Indoor Unit Diffuser Indoor Unit Diffuser Indoor Unit Diffuser Model Unit ARNU76GB8Z4 ARNU96GB8Z4

FRESH AIR INTAKE


Cooling Capacity kW 22.4 28.0
Heating Capacity kW 21.4 26.7
Air Conditioning
Power Input
Air Conditioning + Nominal W 230 / 200 / 200 360 / 230 / 230
(H / M / L)
Outdoor Air Supply
Dimensions Body mm 1,562 x 460 x 688 1,562 x 460 x 688
(W x H x D) Shipping mm 1,806 x 537 x 825 1,806 x 537 x 825
Type Sirocco Fan Sirocco Fan
Motor Output x Number W x No. 375 x 1 375 x 1
MULTI V 5 Outdoor Unit
Air Flow Rate (H / M / L)
Fan m³/min 23.7 / 13.2 / 13.2 35.7 / 23.7 / 23.7
(High Mode-Factory Set)
External Static Pressure mmAq (Pa) 22 (216) 22 (216)
Motor Type BLDC BLDC
Economic Operation Air Filter Long Life Filter Long Life Filter
Natural outdoor air is utilized as seasons change for cost efficiency. Liquid Side mm (inch) Ø9.52 (3/8) Ø9.52 (3/8)
Pipe
Gas Side mm (inch) Ø19.05 (3/4) Ø22.2 (7/8)
Connections
Spring Season Autumn Season Drain Pipe (Internal Dia.) mm (inch) Ø25 (1) Ø25 (1)
Fresh Air Intake Fresh Air Intake Weight Body kg 73.0 73.0
Sound Pressure Levels (H / M / L) dB(A) 45 / 43 / 43 47 / 45 / 45
Sound Power Levels (H / M / L) dB(A) 70 / 67 / 67 72 / 70 / 70
Indoor Unit Diffuser Indoor Unit Diffuser Power Supply Ø, V, Hz 1, 220-240, 50 1, 220-240, 50
OFF OFF Communication Cable mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C
Note : 1. Performance tested under EN14511
Warm Air Cool Air 2. Capacities are based on the following conditions.
+ + - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero
- Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero
Outdoor Air Supply Outdoor Air Supply
3. Due to our policy of innovation, some specifications may be changed without notification.

CAUTION
MULTI V 5 Outdoor Unit MULTI V 5 Outdoor Unit 1. Operation range (Cooling : 5°C ~ 43°C, Heating : -5°C ~ 43°C) 2. Installation of exhaust fan is recommended for a sealed room. 3. Indoor Unit Connection
No Connection Condition Combination
Fresh air intake units only 1) The total capacity of fresh air intake unit should be 50 ~ 100% of outdoor unit.
1
are connected with outdoor units 2) The max. quantity of fresh air intake is 4 units.

Installation Scene 2
Mixture connection with
general indoor unit and fresh intake units
1) The total capacity of indoor units (Standard Indoor Unit + Fresh Air Intake Unit) should be 50 ~ 100% of outdoor unit.
2) The total capacity of fresh air intake unit should be less than 30% of the total capacity of indoor units.

Min. 2m

Accessories
1/30 Slope Chassis ARNU76GB8Z4 ARNU96GB8Z4
Outlet Air Drain Pump ○
Cassette Cover -
Refrigerant Leakage Detector PRLDNVS0
EEV Kit -
Independent Power Module PRIP0
Robot Cleaner -
Exhaust Air
Pre Filter (Washable) ○
Ion Generator -
Inlet Hood Intake Air Duct Fresh Air Intake Unit CO2 Sensor -
Exhaust Fan Door Ventilation Kit -
IR Receiver PWLRVN000
Zone Controller -
PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible),
Dry Contact (with additional accessory)
PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus)
External Input (1 point) ○
Wi-Fi PWFMDD200
※ ○ : Applied, - : Not applied
Option : Refer to model name in table

092 / 093
INDOOR UNITS _ CEILING SUSPENDED INDOOR UNITS _ CEILING SUSPENDED _ KEY FEATURES

SMART COMFORT(CEILING SUSPENDED)


Wi-Fi Control Differentiated Design
CEILING SUSPENDED Access your air conditioner anytime and from anywhere. Modern elegance design with V-shape and
black vane is appropriate for any commercial space.
LG ThinQTM
It received iF Design Award.
Search “LG ThinQTM” on Google market or Appstore then
LG ThinQTM download the app.

INDOOR
UNITS
LG ThinQTM
Wi-Fi

CEILING SUSPENDED
Easy Registration and Log-in
Follow the easy set-up steps that will Powerful Cooling & Heating
activate LG ThinQTM’s impressive feature. High ceiling mode provides powerful cooling and heating up to
4.2m in height from floor, 15m away from ceiling.

* Wi-Fi modem (Option) is necessary


for this function

COMFORT(CONSOLE)
One Touch & 2 Piece Filter
Flexible Easy in / out filter structure as well as a simplified two-piece
The ceiling and floor models can be installed either on the filter, which slides out for easy cleaning and maintenance.
ceiling or on the floor.

Features & Benefits Key Applications


Air flow Direction Control One Touch Filter

• Modern design with V-shape and black vane • Retail Vertical air flow direction can be adjusted using remote controller,
• Powerful air speed and volume can reach up to 15m • Shop and horizontal Air flow direction can be adjusted manually.
• Restaurant Two Thermistors Control
Users can purchase a wired remote controller that includes
a second thermistor, allowing for temperature checks from
Horizontal Vertical
100 °
93 ° multiple locations.
Ceilings Ceiling & Floor Convertible Ceiling Suspended
Smart Wi-Fi ○ ○ 80 °
Close 63 ° Close
Fast Cooling & Heating Jet Cool ○ ○
Cooling Heating
Sleep mode ○ ○ Two
Thermistors

Comfort
Timer (On / Off)
Timer (Weekly)




Filter Change Alarm Indoor Unit
Remote
Controller Thermistor
The filter change alarm informs you when the unit has been
Two thermistor control
Group control




operating for 2,400 hours. 15M
15M
Thermistor

※ ○ : Applied, - : Not applied

One Touch Filter Velocity in Stn Frame


Contour 1
2,000e+001
Filter Change Alarm
ANSYS
R15.0

1,800e+001
1,600e+001
1,400e+001
1,200e+001
1,000e+001
8,000e+000
094 / 095
6,000e+000
4,000e+000
2,000e+000
Velocity in Stn Frame 0,000e+000 ANSYS
Contour 1 [m s^-1] R15. 0
2,000e+00 1
1,800e+00 1
1,600e+00 1
INDOOR UNITS _ CEILING SUSPENDED _ SPECIFICATION

CEILING SUSPENDED CEILING SUSPENDED


ARNU18GV1A4 / ARNU24GV1A4 ARNU36GV2A4 / ARNU48GV2A4

INDOOR
UNITS
Model Unit ARNU18GV1A4 ARNU24GV1A4 Model Unit ARNU36GV2A4 ARNU48GV2A4

CEILING SUSPENDED
Cooling Capacity kW 5.6 7.1 Cooling Capacity kW 10.6 14.1
Heating Capacity kW 6.3 8.0 Heating Capacity kW 11.9 15.9
Power Input Power Input
Nominal W 23 / 20 / 17 25 / 21 / 17 Nominal W 84 / 77 / 66 91 / 79 / 66
(H / M / L) (H / M / L)
Exterior Color Morning Fog Morning Fog Exterior Color Morning Fog Morning Fog
RAL Code RAL 9001 RAL 9001 RAL Code RAL 9001 RAL 9001
Dimensions Body mm 1,200 x 235 x 690 1,200 x 235 x 690 Dimensions Body mm 1,600 x 235 x 690 1,600 x 235 x 690
(W x H x D) Shipping mm 1,315 x 320 x 772 1,315 x 320 x 772 (W x H x D) Shipping mm 1,715 x 320 x 772 1,715 x 320 x 772
Type Cross Flow Fan Cross Flow Fan Type Cross Flow Fan Cross Flow Fan
Motor Output x Number W x No. 85.9 x 1 85.9 x 1 Motor Output x Number W x No. 125 x 1 125 x 1
Fan Fan
Air Flow Rate (H / M / L) m³/min 13.5 / 12.5 / 12.0 14.0 / 13.0 / 12.0 Air Flow Rate (H / M / L) m³/min 27.0 / 24.0 / 20.0 29.0 / 24.0 / 20.0
Motor Type BLDC BLDC Motor Type BLDC BLDC
Air Filter Pre Filter Pre Filter Air Filter Pre Filter Pre Filter
Liquid Side mm (inch) Ø6.35 (1/4) Ø9.52 (3/8) Liquid Side mm (inch) Ø9.52 (3/8) Ø9.52 (3/8)
Pipe Pipe
Gas Side mm (inch) Ø12.7 (1/2) Ø15.88 (5/8) Gas Side mm (inch) Ø15.88 (5/8) Ø15.88 (5/8)
Connections Connections
Drain Pipe (Internal Dia.) mm (inch) Ø16 (5/8) Ø16 (5/8) Drain Pipe (Internal Dia.) mm (inch) Ø16 (5/8) Ø16 (5/8)
Weight Body kg 29.0 29.0 Weight Body kg 37.0 37.0
Sound Pressure Levels (H / M / L) dB(A) 36 / 34 / 33 37 / 35 / 33 Sound Pressure Levels (H / M / L) dB(A) 48 / 46 / 44 49 / 47 / 44
Sound Power Levels (H / M / L) dB(A) 61 / 59 / 56 62 / 59 / 56 Sound Power Levels (H / M / L) dB(A) 68 / 66 / 64 68 / 67 / 66
Power Supply Ø, V, Hz 1, 220-240, 50 1, 220-240, 50 Power Supply Ø, V, Hz 1, 220-240, 50 1, 220-240, 50
Communication Cable mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C Communication Cable mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C

Note : 1. Performance tested under EN14511 Note : 1. Performance tested under EN14511
2. Capacities are based on the following conditions. 2. Capacities are based on the following conditions.
- Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero
- Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero
3. Due to our policy of innovation, some specifications may be changed without notification. 3. Due to our policy of innovation, some specifications may be changed without notification.

Accessories Accessories
Chassis ARNU18GV1A4 ARNU24GV1A4 Chassis ARNU36GV2A4 ARNU48GV2A4
Drain Pump - Drain Pump -
Cassette Cover - Cassette Cover -
Refrigerant Leakage Detector PRLDNVS0 Refrigerant Leakage Detector PRLDNVS0
EEV Kit - EEV Kit -
Independent Power Module PRIP0 Independent Power Module PRIP0
Robot Cleaner - Robot Cleaner -
Pre Filter (Washable) ○ Pre Filter (Washable) ○
Ion Generator - Ion Generator -
CO2 Sensor - CO2 Sensor -
Ventilation Kit - Ventilation Kit -
IR Receiver - IR Receiver -
Zone Controller - Zone Controller -
PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible), PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible),
Dry Contact (with additional accessory) Dry Contact (with additional accessory)
PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus) PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus)
External Input (1 point) ○ External Input (1 point) ○
Wi-Fi PWFMDD200 Wi-Fi PWFMDD200

※ ○ : Applied, - : Not Applied ※ ○ : Applied, - : Not Applied


Option : Refer to model name in table Option : Refer to model name in table

096 / 097
INDOOR UNITS _ CONSOLE INDOOR UNITS _ CONSOLE _ KEY FEATURES

SMART COMFORT
Wi-Fi Control Cold Draft Protection
CONSOLE Access your air conditioner anytime and from anywhere. The console protects cold draft from windows to provide
comfortable environment.
LG ThinQTM
Without Console
Search “LG ThinQTM” on Google market or Appstore then
download the app.

INDOOR
LG ThinQTM

UNITS
Wi-Fi
LG ThinQTM

CONSOLE
Without Console

* Wi-Fi modem (Option) is necessary for this function

COMFORT
Air Flow Direction Change
During the cooling operation, the vane adjusts upwards to direct the 5-Step Vane Control
air flow towards the ceiling. When heating, the vane directs the warm There are 5 different stages to control air flow direction.
air downwards to balance the room temperature especially for floor.
Step3 Step4
Step2
Cooling
Step5

Step1

6 Way Flexible Piping


It is possible to install and connect the outdoor unit in
Features & Benefits Key Applications Heating (Normal) 6 different ways. (Right Side, Right Back, Right Floor,
Left Side, Left Back, Left Floor)
• 6 Way flexible piping • Residential building
• Cold draft window protection • Hotel
• Condensation protection • Historical building

Floor standing Console


Smart Wi-Fi ○
Energy Efficiency Jet Cool -
Health Ionizer ○
Fast Cooling & Heating Jet Cool ○ Heating (Option)
Sleep Mode ○
Timer (On / Off) ○
Comfort Timer (Weekly) ○
Two Thermistor Control ○
Group Control ○
※ ○ : Applied, - : Not applied

098 / 099
INDOOR UNITS _ CONSOLE _ SPECIFICATION

CONSOLE CONSOLE
ARNU07GQAA4 / ARNU09GQAA4 ARNU12GQAA4 / ARNU15GQAA4

INDOOR
UNITS
Model Unit ARNU07GQAA4 ARNU09GQAA4 Model Unit ARNU12GQAA4 ARNU15GQAA4

CONSOLE
Cooling Capacity kW 2.2 2.8 Cooling Capacity kW 3.6 4.5
Heating Capacity kW 2.5 3.2 Heating Capacity kW 4.0 5.0
Power Input Power Input
Nominal W 15 / 12 / 10 15 / 12 / 10 Nominal W 18 / 15 / 13 24 / 19 / 17
(H / M / L) (H / M / L)
Exterior Color Morning Fog Morning Fog Exterior Color Morning Fog Morning Fog
RAL Code RAL 9001 RAL 9001 RAL Code RAL 9001 RAL 9001
Dimensions Body mm 700 x 600 x 210 700 x 600 x 210 Dimensions Body mm 700 x 600 x 210 700 x 600 x 210
(W x H x D) Shipping mm 775 x 662 x 284 775 x 662 x 284 (W x H x D) Shipping mm 775 x 662 x 284 775 x 662 x 284
Type Turbo fan Turbo fan Type Turbo fan Turbo fan
Motor Output x Number W x No. 48 x 1 48 x 1 Motor Output x Number W x No. 48 x 1 48 x 1
Fan Fan
Air Flow Rate (H / M / L) m³/min 6.7 / 5.9 / 4.8 6.7 / 5.9 / 4.8 Air Flow Rate (H / M / L) m³/min 7.5 / 5.9 / 4.8 8.7 / 6.7 / 5.9
Motor Type BLDC BLDC Motor Type BLDC BLDC
Air Filter Pre Filter Pre Filter Air Filter Pre Filter Pre Filter
Liquid Side mm (inch) Ø6.35 (1/4) Ø6.35 (1/4) Liquid Side mm (inch) Ø6.35 (1/4) Ø6.35 (1/4)
Pipe Pipe
Gas Side mm (inch) Ø12.7 (1/2) Ø12.7 (1/2) Gas Side mm (inch) Ø12.7 (1/2) Ø12.7 (1/2)
Connections Connections
Drain Pipe (Internal Dia.) mm (inch) Ø12 (15/32) Ø12 (15/32) Drain Pipe (Internal Dia.) mm (inch) Ø12 (15/32) Ø12 (15/32)
Weight Body kg 14.0 14.0 Weight Body kg 14.0 14.0
Sound Pressure Levels (H / M / L) dB(A) 37 / 34 / 28 37 / 34 / 28 Sound Pressure Levels (H / M / L) dB(A) 39 / 34 / 28 42 / 37 / 31
Sound Power Levels (H / M / L) dB(A) 53 / 50 / 44 53 / 50 / 44 Sound Power Levels (H / M / L) dB(A) 56 / 50 / 44 58 / 53 / 50
Power Supply Ø, V, Hz 1, 220-240, 50 1, 220-240, 50 Power Supply Ø, V, Hz 1, 220-240, 50 1, 220-240, 50
Communication Cable mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C Communication Cable mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C

Note : 1. Performance tested under EN14511 Note : 1. Performance tested under EN14511
2. Capacities are based on the following conditions. 2. Capacities are based on the following conditions.
- Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero
- Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero
3. Due to our policy of innovation, some specifications may be changed without notification. 3. Due to our policy of innovation, some specifications may be changed without notification.

Accessories Accessories
Chassis ARNU07GQAA4 ARNU09GQAA4 Chassis ARNU12GQAA4 ARNU15GQAA4
Drain Pump - Drain Pump -
Cassette Cover - Cassette Cover -
Refrigerant Leakage Detector PRLDNVS0 Refrigerant Leakage Detector PRLDNVS0
EEV Kit PRGK024A0 EEV Kit PRGK024A0
Independent Power Module PRIP0 Independent Power Module PRIP0
Robot Cleaner - Robot Cleaner -
Pre Filter (Washable) ○ Pre Filter (Washable) ○
Ion Generator ○ Ion Generator ○
CO2 Sensor - CO2 Sensor -
Ventilation Kit - Ventilation Kit -
IR Receiver - IR Receiver -
Zone Controller - Zone Controller -
PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible), PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible),
Dry Contact (with additional accessory) Dry Contact (with additional accessory)
PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus) PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus)
External Input (1 point) ○ External Input (1 point) ○
Wi-Fi PWFMDD200 Wi-Fi PWFMDD200

※ ○ : Applied, - : Not Applied ※ ○ : Applied, - : Not Applied


Option : Refer to model name in table Option : Refer to model name in table

100 / 101
INDOOR UNITS _ COMPATIBILITY INDOOR UNITS _ FEATURE FUNCTIONS

COMPATIBILITY FEATURE FUNCTIONS


Premium Standard III Standard II Simple Simple for Hotel Wireless Dry Contact Wired Remote Controller Wireless
Controller Name Wi-Fi
Remote Modem
Controller Premium Standard III Standard II Simple Simple(Hotel) Controller

Dry Contact for


Product PREMTA000 Simple Dry 2 points Dry Thermostat

INDOOR
NEW
PQRCH- PDRYCB300 For Modbus

UNITS
PREMTA000A PREMTBB10 PREMTB100 PREMTBB01 PREMTB001 PQRCVCLOQ PQRCVC0QW PQRCHCA0Q PWLSSB21H Contact Contact
CA0QW PDRYCB500
PREMTA000B (H/P) PDRYCB000 PDRYCB400 NEW
PDRYCB320
Model Name

ARNU-A4
ARNU-B4
○ ○ ○ ○ ○ ○ ○ ○ ○ ○ PREMTA000
PREMTB100 PREMTB001 PQRCVCL0Q PQRCHCA0Q NEW
4 Way PREMTA000A PWFMDD200
PREMTBB10 PREMTBB01 PQRCVCL0QW PQRCHCA0QW PWLSSB21H (H/P)
PREMTA000B

COMPATIBILITY / FEATURE FUNCTIONS


Ceiling
ARNU-B4 On / Off ○ ○ ○ ○ ○ ○ ○
Mounted
ARNU-C4
○ ○ ○ ○ ○ ○ ○ ○ ○ ○
Cassette
2 Way / 1 Way Fan Speed Control ○ ○ ○ ○ ○ ○ ○

Temperature Setting ○ ○ ○ ○ ○ ○ ○
ARNU-A4 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
Round CST Mode Change ○ ○ ○ ○ - ○ ○

Auto Swing ○ ○ ○ ○ ○ ○
ARNU-A4 ○ ○ ○ ○ ○ △ ○ ○ ○ ○ Vane Control
Basic ○ ○ ○ ○ ○ ○ ○
High Sensible (Louver Angle)

E.S.P
Ceiling ○ ○ ○ ○ ○ - -
(External Static Pressure)
Concealed ARNU-A4 ○ ○ ○ ○ ○ △ ○ ○ ○ ○
Duct Electric Failure
High / Mid Statics ○ ○ ○ ○ ○ - ○
Compensation

Indoor Temperature Display ○ ○ ○ ○ ○ ○


ARNU-G4 ○ ○ ○ ○ ○ △ ○ ○ ○ ○
Low Statics
ALL Button Lock
○ ○ ○ ○ ○ - -
(Child Lock)
FAU
Schedule / Timer Weekly - Yearly Weekly - Yearly Weekly - - Sleep / On / Off Weekly
(Fresh Air ARNU-Z4 ○ ○ ○ ○ ○ △ ○ ○ ○ ○
intake)
Additional Mode Setting 1) ○ ○ ○ - - - -
MULTI V

Convertible Time Display ○ ○ ○ - - ○ -


& Ceiling ARNU-A4 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
Suspended Humid. Display ○ ○ - - - - -

Advanced Lock
(mode, set point, set point Advanced Lock Advanced Lock - - - - -
Console ARNU-A4 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ range, on/off Lock)
Advanced
Filter Sign ○ ○ ○ - - - -
ARNU-A4
Wall Energy Management 2) ○ ○ ○ - - - -
Mounted
ARNU-C4 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
ARNU-N4
Dual Set Point ○ ○ - - - - -

Human Detection - ○ - - - - -
HYDRO
KIT 1)
ARNH-A4 - - - - - - ○ - ○ -
Temp, Humidity
○ ○ - - - - -
Compensation
Energy
Recovery
Wi-Fi AP mode setting ○ ○ ○ ○ ○ ○ -
Ventilator ○ ○ ○ - - - ○ - - ○
Operation Status LED ○ ○ ○ ○ ○ - -
Ventilation
Energy Recovery Wireless Remote Controller
○3) - ○3) ○3) ○3) - -
Ventilator with Receiver
DX coil
○ ○ ○ - - - ○ - - ○
ETC Display 5 inch Color 4.3 inch Color 4.3 inch mono 2.6 inch mono 2.6 inch mono 2 inch mono -

Size (W x H x D, mm) 137 x 121 x 16.5 120 x 120 x 16 120 x 120 x 16 64 x 120 x 15 64 x 120 x 15 51 x 153 x 26 -
AHU Communication Kit ○ ○ ○ - - △ - - - -
Black Light Control for
○ ○ - - - - -
Screen Saver

※ ○ : Compatible, △ : Need wired remote controller / IR receiver, - : Not compatible ※ ○ : Applied, - : Not Applied
1) It has a separate remote controller. 1) It might not be indicated or operated at the partial product.
2) Centralized control (PACEZA000 / PACS5A000 / PACP5A000 / PLNWKB000) and PDI (PQNUD1S40 / PPWRDB000) should be installed for this function.
3) For ceiling type duct.
Note
- Indoor unit should have functions requested by the controller.
- If you need more detail, please refer to the manual of product. (http://partner.lge.com: Home> Doc.Library> Manual)

102 / 103
HOT WATER
SOLUTION

HOT WATER
SOLUTION
HYDRO KIT

104 / 105
HOT WATER SOLUTION _ HYDRO KIT HOT WATER SOLUTION _ HYDRO KIT _ KEY FEATURES

HYDRO KIT EFFICIENCY


Cost Savings with High Efficiency High Temperature HYDRO KIT
Features & Benefits Key Applications Equivalent installation cost of traditional boiler with reduced Cycle Diagram
• Lower operation cost compared to fossil fuel-based systems such as boilers. • Where Hot Water is needed such as domestic Hot Water, operational costs.
Outdoor Unit High Temperature HYDRO KIT Heating
• More energy saving through MULTI V heat recovery system. In-floor or radiant heat. Where cold water is needed such as 1st Proposal MULTI V 5 HYDRO KIT
Refrigerant - Refrigerant -
by Hot Water
(Air Conditioning + Hot Water Supply + Floor Heating) Refrigerant Water
Fan coil unit and chilled beam. 2nd Proposal MULTI V 5 Air-Conditioning + Gas Boiler
Air-Refrigerant

(Hot Water Supply + Floor Heating)


3rd Proposal MULTI V 5 Air-Conditioning + Oil Boiler AIR
50°C 80°C
(Hot Water Supply + Floor Heating)
Analysis Conditions
- Building Type : Dormitory, Flats
- Cooling / Floor Heating / Sanitary Hot Water for 10 years High Temperature Technology
- Cooling : MULTI V IV Indoor Unit

Pressure
Water

HOT WATER
- Floor Heating : Medium Temp. HYDRO KIT (1ea)

SOLUTION
- Sanitary Hot Water : High Temp. HYDRO KIT (2ea), Sanitary Hot Water
Tanks R410A
- Electricity Cost : Average Cost in EU
R134A
- Gas Cost : Average Cost in EU Stage 1
Hot Water Heating Cooling - Oil Cost : Average Cost in EU Stage 2
Air
Initial Costs Annual Operating Costs
Enthalpy

HYDRO KIT
25,000 100% 90% 95% 25,000 229%

Radiant Heating / Cooling Fan Coil Unit Heating / Cooling Hot Water / Cold Water
20,000

15,000
20,000

15,000 171%
Various Applications
100% Applicable to a variety of facilities including hospitals,
Radiator 10,000 10,000

5,000 5,000
residences and resorts that need floor heating and
Gas Boiler Oil Boiler Gas Boiler Oil Boiler domestic hot water supply.
FCU
Floor heating LCC
50,000
Oil boiler
Gas boiler
40,000

30,000
Combination
20,000 Dormitory Hotel Office Restaurant

10,000
1 2 3 4 5 6 7 8 9 10 (Year)

Thermal Storage Tank

Hot water+ Radiant heating HR unit (Cooling & Hot water) Thermal Storage System Energy Savings through Fitness Hospital Factory Residential

Heat Recovery
Energy costs can be minimized by reusing the wasted

CONVENIENCE heat from indoor units. Hotel Application


Constant simultaneous
Conventional
Absorbed heat is released to outdoor air. cooling and heating operating
Total Solution Eco-friendly Solution during summer to provide hot
Heat Transfer water by using wasted heat
Total solution provided with heat pump, air conditioning Green energy solution through the reduction of CO2 Heat
Released
(Cooling by refrigerant and cold water / heating by emissions. energy from indoor cooling
pump
refrigerant hot water) and domestic hot water supply. Hot water Heat
Absorption
process.
Conventional System
CO2 Emissions
Refrigerant piping Water piping Conventional Boiler Domestic
(%) Hot Water Tank
HR Unit Hot Water Supply Cooling
Indoor Unit 120

HYDRO KIT
Domestic
Hot Water Tank 100
100%
Absorbed heat from indoor space is used for making hot water. Office Application
76% Hot water can be supplied
Air Heat Transfer
Hot water conditioning 60 at all times in the office by
HYDRO KIT HR Unit
supply cooling the HR unit to
MULTI V 5 40 30%
On Average
pump
Hot water Heat
Absorption
warm up the sanitary tank,
High temperature using waste energy.
MULTI V 5 Domestic
20 HYDRO KIT
(Heat Recovery) Hot Water Tank
Oil Gas Hot Water Supply Cooling
Boiler Boiler
MULTI V
Outdoor Unit Floor heating
(Water Cooled) Middle temperature

106 / 107
HOT WATER SOLUTION _ HYDRO KIT _ SPECIFICATION

HYDRO KIT HYDRO KIT


ARNH04GK2A4 / ARNH10GK2A4 ARNH04GK3A4 / ARNH08GK3A4

Model Unit ARNH04GK2A4 ARNH10GK2A4 Model Unit ARNH04GK3A4 ARNH08GK3A4

HOT WATER
SOLUTION
Cooling Capacity kW 12.3 28.0 Heating Capacity kW 13.8 25.2
Heating Capacity kW 13.8 31.5 Power Input Nominal1) W 2,300 5,000
Power Input Nominal1) W 10 10 Exterior Color Morning Gray Morning Gray
Exterior Color Morning Gray Morning Gray RAL Code RAL 7030 RAL 7030
RAL Code RAL 7030 RAL 7030 Dimensions Body mm 520 x 1,080 x 330 520 x 1,080 x 330
Dimensions Body mm 520 x 631 x 330 520 x 631 x 330 (W x H x D) Shipping mm 682 x 1,168 x 423 682 x 1,168 x 423
(W x H x D) Shipping mm 677 x 687 x 418 677 x 687 x 418 Liquid Side mm (inch) Ø9.52 (3/8) Ø9.52 (3/8)
Pipe

HYDRO KIT
Liquid Side mm (inch) Ø9.52 (3/8) Ø9.52 (3/8) Gas Side mm (inch) Ø15.88 (5/8) Ø19.05 (3/4)
Pipe Connections
Gas Side mm (inch) Ø15.88 (5/8) Ø22.2 (7/8) Drain Pipe (Internal Dia.) A (inch) 25A (Male PT 1) 25A (Male PT 1)
Connections
Drain Pipe (Internal Dia.) A (inch) 25A (Male PT 1) 25A (Male PT 1) Water Pipe Inlet A (inch) 25A (Male PT 1) 25A (Male PT 1)
Water Pipe Inlet A (inch) 25A (Male PT 1) 25A (Male PT 1) Connections Outlet A (inch) 25A (Male PT 1) 25A (Male PT 1)
Connections Outlet A (inch) 25A (Male PT 1) 25A (Male PT 1) Weight Body kg 87.0 91.0
Weight Body kg 29.2 33.7 Sound Pressure Levels (H / M / L) dB(A) 43 46
Sound Pressure Levels (H / M / L) dB(A) 26 26 Power Supply Ø, V, Hz 1, 220-240, 50 1, 220-240, 50
Power Supply Ø, V, Hz 1, 220-240, 50 1, 220-240, 50 Communication Cable mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C
Communication Cable mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1) Nominal : Performance tested under EN14511
Note : 1. Capacities are based on the following conditions :
1) Nominal : Performance tested under EN14511
- Heating : Indoor 20°C (68°F) DB / 15°C (59°F) WB, Outdoor 7°C (44.6°F) DB / 6°C (42.8°F) WB, Water Inlet 55°C (131°F) / Outlet 65°C (149°F)
Note : 1. Capacities are based on the following conditions :
2. Piping Length : Interconnected Pipe Length = 7.5m
- Cooling : Indoor 27°C (80.6°F) DB / 19° C (66.2°F) WB, Outdoor 35°C (95°F) DB / 24°C (75.2°F) WB, Water Inlet 23°C (73.4°F) / Outlet 18°C (64.4°F)
3. Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
- Heating : Indoor 20°C (68°F) DB / 15°C (59°F) WB, Outdoor 7°C (44.6°F) DB / 6°C (42.8°F) WB, Water Inlet 30°C (86°F) / Outlet 35°C (95°F)
4. MULTI V S 4HP (ARUN040GSS0, ARUN040LSS0) cannot be connected to HYDRO KIT.
2. Piping Length : Interconnected Pipe Length = 7.5m
5. MULTI V Water S cannot be connected to HYDRO KIT.
3. Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
4. MULTI V S 4HP (ARUN040GSS0, ARUN040LSS0) cannot be connected to HYDRO KIT.
5. MULTI V Water S cannot be connected to HYDRO KIT.
6. Anti freezing liquid should be added under 10°C (outdoor temp.) during cooling mode.

Accessories Accessories
Chassis ARNH04GK2A4 ARNH10GK2A4 Chassis ARNH04GK3A4 ARNH08GK3A4
Drain Pump - Drain Pump -
Cassette Cover - Cassette Cover -
Refrigerant Leakage Detector PRLDNVS0 Refrigerant Leakage Detector PRLDNVS0
EEV Kit - EEV Kit -
Independent Power Module ○ Independent Power Module ○
Robot Cleaner - Robot Cleaner -
Pre Filter (Washable) - Pre Filter (Washable) -
Ion Generator - Ion Generator -
CO2 Sensor - CO2 Sensor -
Ventilation Kit - Ventilation Kit -
IR Receiver - IR Receiver -
Zone Controller - Zone Controller -
PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible) PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible)
Dry Contact (with additional accessory) Dry Contact (with additional accessory)
PDRYCB320 (Universal input) PDRYCB320 (Universal input)
External Input (1 point) ○ External Input (1 point) ○
Wi-Fi PWFMDD200 Wi-Fi PWFMDD200

※ ○ : Applied, - : Not applied ※ ○ : Applied, - : Not applied


Option : Refer to model name in table Option : Refer to model name in table

108 / 109
VENTILATION
SOLUTIONS

VENTILATION
SOLUTIONS
ERV

110 / 111
VENTILATION SOLUTIONS _ ERV VENTILATION SOLUTIONS _ ERV _ KEY FEATURES

HIGH EFFICIENCY
High Efficiency Heat Exchanger CO2 Auto Operation
ENERGY RECOVERY Efficiency and comfort is ensured through the high-efficiency
energy recovery central core which recovers energy from
LG ERV reduces energy loss with auto fan speed control
following CO2 level

VENTILATION (ERV)
Fine CO2 level
the indoor air and transfers it to the fresh incoming air High occupancy Low occupancy CO2 level
without mixing the air stream. (high CO2 level) (low CO2 level) Fan speed

- Reduce power consumption


for ventilation
- Reduce cooling, heating
energy loss by ventilation

Air Filter
Low
Exchanger Air
Supply Air
4% Energy Saving
(Annually)
Extra
high high
Outdoor Air Indoor Air

9 o’clock 10 11 12 13 14 15 16 17
※ This function is operated with ‘Night Time Free Cooling’ on remote controller. (with MULTI V only)
※ Energy saving ratio can be differed by weather condition.
※ Test Condition - Office (49,000ft2) / Occupancy : 30 / Area : London, UK
- ERV (1000 CMH) + MULTI V IV (12HP) Unit Combination
- Other conditions are subject to BREEAM.

VENTILATION
SOLUTIONS
Compulsory Exhaust System Seasonal Auto Operation
The exhausting system using high static and sirocco fan LG ERV senses outdoor temperature and operates
removes contaminants effectively from indoor air. Supply automatically following weather condition.
and exhaust air flows are completely separated in the total High temp. Natural ventilation
Heat recovery LG ERV heat recovery mode
heat exchanger, LG ERV can filter out the impurities before mode LG ERV bypass mode
supplying outdoor air and make indoor air fresh and healthy.

ERV
Proper temp.
Bypass mode 5% Energy Saving
(Annually)
Exchanger Air Supply Air
Exchanger Damper
Low temp.
Air Heat recovery
Return
Air mode

Supply Month Jan. Feb. Mar. Apr. May. Jun. Jul. Aug. Sep. Oct. Nov. Dec.
Air
Outdoor Heat recovery mode Bypass mode
Indoor Air Air
Outdoor Air
Indoor Outdoor Indoor Outdoor

Outdoors Indoors Total Heat Exchanger Automatic


Change
Damper Damper
Heat Exchanger Heat Exchanger
※ This function is operated with ‘Auto’ mode by wired remote control.
※ Energy saving ratio can be differed by weather condition.
※ Test Condition: - Office (49,000ft2) / Occupancy : 30 / Area : London, UK
Night Time Free Cooling - ERV (1,000 CMH) + MULTI V IV (12HP) Unit Combination
- Other conditions are subject to BREEAM.
During summer nights, indoor heat can be discharged

NECESSITY OF ERV outdoors and cool outdoor air can be brought indoors for
energy savings.
Delay Operation
Afternoon Night Morning When the air conditioner and ERV are switched on simultaneously,
Indoor temp. Outdoor temp.(winter) delay operation can reduce unnecessary heating and cooling
Energy Recovery Ventilation (ERV)
22°C -5°C
energy loss by slowing down automatic ERV operation.
Operation Delay operation
Set Temp. Operation starts Operation air conditioner simultaneously. Operation starts with air conditioner.
C
16 ° ERV makes inside cooler Inside Temp.
with bypass mode like Outside Temp. ON Energy consumption Fine CO2 level
natural ventilation
OFF 2%
Energy Saving (Annually)
ON
CO2 level

Natural Ventilation

Office time
Outdoor temp.
-5°C
Indoor temp.
22°C
-5°C Inside is getting
higher in the night
2% Energy Saving
(Annually) starts

24% Indoor temp Outdoor temp


because of business
machines.
Operation
time
Comfort air + Energy Saving 22°C -5°C ※ This function is operated with ‘Night Time Free Cooling’ on remote controller. (with MULTI V only)
Demand Cooling only Demand Cooling & Ventilation
Compare to natural ventilation ※ Energy saving ratio can be differed by weather condition.
Energy Saving ※ This function is operated with ‘Night Time Free Cooling’ on remote controller. (with MULTI V only)
Heat exchanger collects wasted ※ Test Condition ※ Energy saving ratio can be differed by weather condition.
Natural Ventilation loss - Office (49,000ft2) / Occupancy : 30 / Area : London, UK ※ Test Condition - Office (49,000ft2) / Occupancy : 30 / Area : London, UK
energy while ventilating. heat energy. - ERV (1000 CMH) + MULTI V IV (12HP) Unit Combination - ERV (1,000 CMH) + MULTI V IV (12HP) Unit Combination
- Other conditions are subject to BREEAM. - Other conditions are subject to BREEAM.

112 / 113
VENTILATION SOLUTIONS _ ERV _ KEY FEATURES

COMFORT & RELIABILITY CONVENIENCE CONVENIENCE


CO2 Level Monitoring Easy Control Fast Ventilation Mode Providing Cool & Warm Fresh Air
CO2 sensor senses CO2 level in the room. Users can monitor Wired remote controller is easy for usage. Fast ventilation mode prevents the spread of contaminants During the summer, ERV DX can transform outdoor
CO2 level on new wired remote controller, and ERV controls under negative indoor pressure and makes indoor air fresh warm air into cool air for indoors and it can prevent cold
the fan speed automatically following the level. and comfortable quickly. drafts during the winter by supplying warm air.
Only Exhausting
CO2 Level Visualization
CO2 sensor senses indoor CO2 level and displays it on new wired remote controller. Convenient
• Flexible display
- Dual display with air conditioner.
- Zoom selected directory to increase legibility.
Exhausting operation causes Cooling
negative indoor air pressure,
and cannot fully ventilate.
Easy
• Navigation buttons, easy to use.
• Easy installation setting

Visible
Main display Further information • Indoor CO2 level Exhausting and Supplying
If the CO2 level is above 900ppm in CO2 level and room condition are • Alarm for filter change / Remained time to change filters Fast Ventilation Mode Simultaneously
the room, the red mark is on. displayed continuously.
Monitoring CO2
CO2 1,215 ppm

Group Control

VENTILATION
Exhaust

SOLUTIONS
comfort level Heating
20.5° Fan
※ The remote controller screen image CO2 1 wired remote controller up to 16 ERV (Including air Supply
CO2
may change. 1215 ppm SEVERE Fan
※ Applicable to only Standard III, Premium
conditioner). It is convenient for large common space
remote controller. such as lobby.
Several units combination
CO2 Concentration Control 16 units group control is available with 1 remote controller.
Using CO2 sensor, LG ERV controls exhaust air flow automatically

ERV
to keep indoor air fresh under settled CO2 concentration. Good looking interior External Static Pressure Control Total Air Conditioning Solution
The high static pressure fan can control the air volume LG ERV DX can be used as a Total Air Conditioning Solution.
depending on the length of the duct. It is also easy to It can control condition of incoming air with the DX coil and
CO2 Sensor
RS3 Remote
control the pressure level by using the remote controller humidifier for making comfortable indoor air.
(AHCS 100H0)
(Internal type : Default) Controller for a more flexible duct installation and easier testing. In the summer, LG ERV DX controls the air indoors by cooling
Conventional New and dehumidifying incoming air. In winter, it can provide warm
Air
CO2
(ppm) Controller & installation cost saving Volume air by heating and humidifying the incoming air.
Heat Exchange DX Coil Humidification
Windows Windows Windows Windows
Closed Open Closed Open H
2,500
M
L Exhaust Supply
Air Air
1,000

0 ERV with CO2 H


Concentration Control M
L
Time (min)

Interlocking with Air Conditioning System Outdoor Return


High Durability - LG ERV can be interlocked with air conditioners Air Air

LG ERV durability is increased through bacteria-resistant material and controlled individually. External Static Pressure (mmAq)

of heat exchanger and corrosion protection coating. It prevents - This function can be operated when the system
shortening product life due to corrosion and mold and supplies is connected with 1 remote controller. Easy Cleaning and Filter Change Interlocking with MULTI V
high quality air to inside by minimizing the bacteria. Filter can be conveniently changed and cleaned. LG ERV DX can be interlocked with MULTI V.
Others LG ERV It can be controlled individually by a wired remote
Remote
Inside ERV Inside ERV Controller controller connected to MULTI V indoor units.
Corrosion
occurrence Indoor Units
Corrosion
protection coating MAX. 16
+ Finish insulator
ERV Unit Remove Side Panel

Heat exchanger and filter Heat exchanger

Outdoor unit
ERV DX

Change Filter Remove Heat Exchanger


Breading mold Bacteria-resistant

114 / 115
VENTILATION SOLUTIONS _ ERV _ SPECIFICATION

ERV ERV
LZ-H025GBA4 / LZ-H035GBA4 LZ-H080GBA4 / LZ-H100GBA4
LZ-H050GBA4 LZ-H150GBA4 / LZ-H200GBA4

Model LZ-H025GBA4 LZ-H035GBA4 LZ-H050GBA4 Model LZ-H080GBA4 LZ-H100GBA4 LZ-H150GBA4 LZ-H200GBA4


CMH CMH
Nominal Capacity 250 (147) 350 (206) 500 (294) Nominal Capacity 800 (471) 1,000 (589) 1,500 (883) 2,000 (1,177)
(CFM) (CFM)
Power Supply Ø, V, Hz 1, 220-240, 50 / 60 Power Supply Ø, V, Hz 1, 220-240, 50 / 60
Step - SUPER-HIGH / HIGH / LOW Step - SUPER-HIGH / HIGH / LOW
Current SH / H / L Amps 0.70 / 0.60 / 0.42 1.10 / 0.95 / 0.60 1.92 / 1.58 / 0.79 Current SH / H / L Amps 2.77 / 2.16 / 1.44 3.41 / 2.90 / 1.76 5.60 / 5.40 / 2.90 6.80 / 5.90 / 3.60
Power Input SH / H / L W 97 / 78 / 52 180 / 163 / 88 240 / 220 / 90 Power Input SH / H / L W 390 / 280 / 187 480 / 385 / 210 780 / 540 / 377 960 / 770 / 420
CMH 250 / 250 / 150 350 / 350 / 210 500 / 500 / 320 CMH 800 / 800 / 660 1,000 / 1,000 / 800 1,500 / 1,500 / 1,200 2,000 / 2,000 / 1,600
Air Flow SH / H / L Air Flow SH / H / L
(CFM) (147 / 147 / 88) (206 / 206 / 123) (294 / 294 / 124) (CFM) (471 / 471 / 388) (589 / 589 / 471) (883 / 883 / 706) (1,177 / 1,177 / 942)

VENTILATION
SOLUTIONS
Pa 100 / 70 / 50 150 / 130 / 100 150 / 100 / 50 Pa 200 / 110 / 60 160 / 90 / 50 200 / 110 / 60 160 / 90 / 50
External Static Pressure SH / H / L External Static Pressure SH / H / L
ERV Mode (inWTR) (0.40 / 0.28 / 0.20) (0.60 / 0.52 / 0.40) (0.60 / 0.40 / 0.20) ERV Mode (inWTR) (0.80 / 0.44 / 0.24) (0.64 / 0.36 / 0.20) (0.80 / 0.44 / 0.24) (0.64 / 0.36 / 0.20)
Temperature Exchange Temperature Exchange
SH / H / L % 80 / 80 / 83 75 / 75 / 77 78 / 78 / 79 SH / H / L % 79 / 79 / 82 77 / 77 / 78 79 / 79 / 82 77 / 77 / 78
Efficiency Efficiency
Enthalpy Exchange Heating (SH / H / L) % 70 / 70 / 72 68 / 68 / 70 73 / 73 / 75 Enthalpy Exchange Heating (SH / H / L) % 72 / 72 / 74 70 / 70 / 72 72 / 72 / 74 70 / 70 / 72
Efficiency Cooling (SH / H / L) % 66 / 66 / 68 63 / 63 / 65 66 / 66 / 69 Efficiency Cooling (SH / H / L) % 63 / 63 / 66 59 / 59 / 63 63 / 63 / 66 59 / 59 / 63
Noise Level Noise Level
SH / H / L dB(A) 29 / 28 / 24 32 / 30 / 27 34 / 32 / 25 SH / H / L dB(A) 40 / 37 / 31 41 / 38 / 32 43 / 40 / 34 44 / 41 / 35
(Sound Level, 1.5m) (Sound Level, 1.5m)

ERV
Step - SUPER-HIGH / HIGH / LOW Step - SUPER-HIGH / HIGH / LOW
Current SH / H / L Amps 0.70 / 0.60 / 0.42 1.10 / 0.95 / 0.60 1.92 / 1.58 / 0.79 Current SH / H / L Amps 2.77 / 2.16 / 1.44 3.41 / 2.90 / 1.76 5.60 / 5.40 / 2.90 6.80 / 5.90 / 3.60
Power Input SH / H / L W 97 / 78 / 52 180 / 163 / 88 240 / 220 / 90 Power Input SH / H / L W 390 / 280 / 187 480 / 385 / 210 780 / 540 / 377 960 / 770 / 420
CMH 250 / 250 / 150 350 / 350 / 210 500 / 500 / 320 CMH 800 / 800 / 660 1,000 / 1,000 / 800 1,500 / 1,500 / 1,200 2,000 / 2,000 / 1,600
Bypass Mode Air Flow SH / H / L Bypass Mode Air Flow SH / H / L
(CFM) (147 / 147 / 88) (206 / 206 / 123) (294 / 294 / 124) (CFM) (471 / 471 / 388) (589 / 589 / 471) (883 / 883 / 706) (1,177 / 1,177 / 942)
Pa 100 / 70 / 50 150 / 130 / 100 150 / 100 / 50 Pa 200 / 110 / 60 160 / 90 / 50 200 / 110 / 60 160 / 90 / 50
External Static Pressure SH / H / L External Static Pressure SH / H / L
(inWTR) (0.40 / 0.28 / 0.20) (0.60 / 0.52 / 0.40) (0.60 / 0.40 / 0.20) (inWTR) (0.80 / 0.44 / 0.24) (0.64 / 0.36 / 0.20) (0.80 / 0.44 / 0.24) (0.64 / 0.36 / 0.20)
Noise Level Noise Level
SH / H / L dB(A) 29 / 29 / 25 32 / 30 / 27 35 / 33 / 25 SH / H / L dB(A) 41 / 38 / 32 41 / 39 / 33 44 / 41 / 35 44 / 42 / 36
(Sound Level, 1.5m) (Sound Level, 1.5m)
Heat Exchanger Type - Air to air cross flow heat exchange Heat Exchanger Type - Air to air cross flow heat exchange
Net Weight kg 44 44 44 Net Weight kg 62 140
Dimension WxHxD mm 988 x 273 x 1,014 988 x 273 x 1,014 988 x 273 x 1,014 Dimension WxHxD mm 1,062 x 365 x 1,140 1,313 x 738 x 1,140
Qty EA 4 Qty EA 4 4+2
Duct Work Duct Work
Size (Ø) mm Ø200 Size (Ø) mm Ø250 Ø250 + Ø350
Qty EA 1 Qty EA 1 2
Supply Air Fan Supply Air Fan
Type - Direct-Drive (Sirocco Fan) Type - Direct-Drive (Sirocco Fan)
Qty EA 1 Qty EA 1 2
Exhaust Air Fan Exhaust Air Fan
Type - Direct-Drive (Sirocco Fan) Type - Direct-Drive (Sirocco Fan)
Qty EA 2 2 Qty EA 2 4
Filters (Default) Type - Cleanable fibrous fleeces Filters (Default) Type - Cleanable fibrous fleeces
Size (W x H x D) mm 855 x 10 x 160 855 x 6 x 230 Size (W x H x D) mm 1,056 x 6 x 212.5
Model - AHFT035H0 AHFT050H0 Model - AHFT100H0
Qty EA 2 2 Qty EA 2 4
Filters (Optional) Filters (Optional)
Type - F7 F7 Type - F7
Size (W x H x D) mm 423.5 x 132 x 25 425 x 194 x 25 Size (W x H x D) mm 520 x 192 x 25
Dry Contact PDRYCB000 Dry Contact PDRYCB000

Note : 1. ERV mode : Total Heat Recovery Ventilation mode Note : 1. ERV mode : Total Heat Recovery Ventilation mode
2. Refer to dimensional drawings. 2. Refer to dimensional drawings.
3. Noise level : 3. Noise level :
- The operating conditions are assumed to be standard. - The operating conditions are assumed to be standard.
- Sound measured at 1.5m below the center the body. - Sound measured at 1.5m below the center the body.
- Sound level will vary depending on a range of factors such as the construction (acoustic absorption coefficient) of particular room in which the equipment is installed. - Sound level will vary depending on a range of factors such as the construction (acoustic absorption coefficient) of particular room in which the equipment is installed.
- The sound level at the air discharge port is about 8 dB(A) higher than the unit's operating sound. - The sound level at the air discharge port is about 8 dB(A) higher than the unit’s operating sound.
4. Temperature and Enthalpy Exchange Efficiency at cooling Indoor Temperature : 26.5°C DB, 64.5% RH, Outdoor Temperature : 34.5°C DB, 75% RH 4. Temperature and Enthalpy Exchange Efficiency at cooling Indoor Temperature : 26.5°C DB, 64.5% RH, Outdoor Temperature : 34.5°C DB, 75% RH
5. Temperature and Enthalpy Exchange Efficiency at heating Indoor Temperature : 20.5°C DB, 59.5% RH, Outdoor Temperature : 5°C DB, 65% RH 5. Temperature and Enthalpy Exchange Efficiency at heating Indoor Temperature : 20.5°C DB, 59.5% RH, Outdoor Temperature : 5°C DB, 65% RH
6. Temperature Exchange efficiency is tested at heating condition. 6. Temperature Exchange efficiency is tested at heating condition.

116 / 117
VENTILATION SOLUTIONS _ ERV _ SPECIFICATION

ERV WITH DX COIL ERV WITH DX COIL


LZ-H050GXH4 / LZ-H080GXH4 LZ-H050GXN4 / LZ-H080GXN4
LZ-H100GXH4 LZ-H100GXN4

Model LZ-H050GXH4 LZ-H080GXH4 LZ-H100GXH4 Model LZ-H050GXN4 LZ-H080GXN4 LZ-H100GXN4


Fresh Air Cooling kW 4.93 7.46 9.12 Fresh Air Cooling kW 4.93 7.46 9.12
Conditioning Load Heating kW 6.73 9.80 11.72 Conditioning Load Heating kW 6.73 9.80 11.72
Temperature Temperature
Exchange SH / H / L % 86 / 86 / 87 80 / 80 / 81 76 / 76 / 78 Exchange SH / H / L % 86 / 86 / 87 80 / 80 / 81 76 / 76 / 78
Efficiency Efficiency
Enthalpy Exchange Cooling (SH / H / L) % 61 / 61 / 63 50 / 50 / 53 45 / 45 / 50 Enthalpy Exchange Cooling (SH / H / L) % 61 / 61 / 63 50 / 50 / 53 45 / 45 / 50
Efficiency Heating (SH / H / L) % 76 / 76 / 77 67 / 67 / 69 64 / 64 / 66 Efficiency Heating (SH / H / L) % 76 / 76 / 77 67 / 67 / 69 64 / 64 / 66
Operation Range Outdoor air Temperature °C -15 ~ 45 -15 ~ 45 -15 ~ 45 Operation Range Outdoor air Temperature °C -15 ~ 45 -15 ~ 45 -15 ~ 45
Heat Exchange Mode (SH / H / L) CMH 500 / 500 / 440 800 / 800 / 640 1,000 / 1,000 / 820 Heat Exchange Mode (SH / H / L) CMH 500 / 500 / 440 800 / 800 / 640 1,000 / 1,000 / 820
Air Flow Rate Air Flow Rate

VENTILATION
Bypass Mode (SH / H / L) CMH 500 / 500 / 440 800 / 800 / 640 1,000 / 1,000 / 820 Bypass Mode (SH / H / L) CMH 500 / 500 / 440 800 / 800 / 640 1,000 / 1,000 / 820

SOLUTIONS
Fan External Static Pressure (SH / H / L) Pa 160 / 120 / 100 140 / 90 / 70 110 / 70 / 60 Fan External Static Pressure (SH / H / L) Pa 180 / 150 / 110 170 / 120 / 80 150 / 100 / 70
System Natural Evaporating Type System -
Humidifier Amount kg/h 2.70 4.00 5.40 Humidifier Amount kg/h -
Pressure Feed Water Mpa 0.02 ~ 0.49 Pressure Feed Water Mpa -
Heat Exchange Mode (SH / H / L) dB(A) 38 / 36 / 33 39 / 37 / 34 40 / 38 / 35 Heat Exchange Mode (SH / H / L) dB(A) 39 / 37 / 35 41 / 38 / 36 41 / 39 / 36
Sound Pressure Sound Pressure
Bypass Mode (SH / H / L) dB(A) 39 / 37 / 34 40 / 38 / 35 40 / 38 / 35 Bypass Mode (SH / H / L) dB(A) 39 / 37 / 35 41 / 38 / 36 41 / 39 / 36
Refrigerant R410A Refrigerant R410A
Power Supply Ø, V, Hz 1, 220-240, 50 / 60 Power Supply Ø, V, Hz 1, 220-240, 50 / 60

ERV
Power Input Heat Exchange Mode (SH / H / L) kW 0.25 / 0.20 / 0.15 0.42 / 0.35 / 0.25 0.48 / 0.42 / 0.27 Power Input Heat Exchange Mode (SH / H / L) kW 0.25 / 0.20 / 0.15 0.42 / 0.35 / 0.25 0.48 / 0.42 / 0.27
(Nominal) Bypass Mode (SH / H / L) kW 0.25 / 0.20 / 0.15 0.42 / 0.35 / 0.25 0.48 / 0.42 / 0.27 (Nominal) Bypass Mode (SH / H / L) kW 0.25 / 0.20 / 0.15 0.42 / 0.35 / 0.25 0.48 / 0.42 / 0.27
Nominal Running Heat Exchange Mode (SH / H / L) A 1.5 / 1.3 / 1.0 2.5 / 2.0 / 1.5 3.6 / 3.2 / 2.3 Nominal Running Heat Exchange Mode (SH / H / L) A 1.5 / 1.3 / 1.0 2.5 / 2.0 / 1.5 3.6 / 3.2 / 2.3
Current (RLA) Bypass Mode (SH / H / L) A 1.5 / 1.3 / 1.0 2.5 / 2.0 / 1.5 3.6 / 3.2 / 2.3 Current (RLA) Bypass Mode (SH / H / L) A 1.5 / 1.3 / 1.0 2.5 / 2.0 / 1.5 3.6 / 3.2 / 2.3
Heat exchange system Air to air cross flow total heat (Sensible + Latent heat) exchange Heat exchange system Air to air cross flow total heat (Sensible + Latent heat) exchange
Heat exchange element Specially processed non-flammable paper Heat exchange element Specially processed non-flammable paper
Air Filter Multidirectional fibrous fleeces Air Filter Multidirectional fibrous fleeces
Dimensions WxHxD mm 1,667 x 365 x 1,140 Dimensions WxHxD mm 1,667 x 365 x 1,140
Net Weight kg 105 Net Weight kg 98
Liquid mm Ø6.35 Liquid mm Ø6.35
Gas mm Ø12.7 Gas mm Ø12.7
Piping Connection Piping Connection
Water mm Ø6.35 Water mm -
Drain Pipe (Internal Dia.) mm (inch) Ø25 (1) Drain Pipe (Internal Dia.) mm (inch) Ø25 (1)
Connection Duct Diameter mm Ø250 Connection Duct Diameter mm Ø250
Note : 1. Cooling Capacity Test condition - Indoor temperature : 27°C DB, 19°C WB / Outdoor temperature : 35°C DB Note : 1. Cooling Capacity Test condition - Indoor temperature : 27°C DB, 19°C WB / Outdoor temperature : 35°C DB
2. Heating Capacity Test condition - Indoor temperature : 20°C DB / Outdoor temperature : 7°C DB, 6°C WB 2. Heating Capacity Test condition - Indoor temperature : 20°C DB / Outdoor temperature : 7°C DB, 6°C WB
3. Humidifying capacity is based on the following conditions - Indoor temperature : 20°C DB, 15°C WB / Outdoor temperature : 7°C DB, 6°C WB 3. Humidifying capacity is based on the following conditions - Indoor temperature : 20°C DB, 15°C WB / Outdoor temperature : 7°C DB, 6°C WB
4. Cooling and heating capacities are based on the following conditions. : Fan is based on High and Super-high. 4. Cooling and heating capacities are based on the following conditions. : Fan is based on High and Super-high.
5. The operating sound measured at the point 1.5 m below the center of the unit is converted to that measured at an anechoic chamber. 5. The operating sound measured at the point 1.5 m below the center of the unit is converted to that measured at an anechoic chamber.
6. The specifications, designs and information here are subject to change without notice. 6. The specifications, designs and information here are subject to change without notice.

Accessories Accessories
Chassis LZ-H050GXH4 LZ-H080GXH4 LZ-H100GXH4 Chassis LZ-H050GXN4 LZ-H080GXN4 LZ-H100GXN4
Drain Pump - Drain Pump -
Cassette Cover - Cassette Cover -
Refrigerant Leakage Detector PRLDNVS0 Refrigerant Leakage Detector PRLDNVS0
EEV Kit - EEV Kit -
Independent Power Module - Independent Power Module -
Robot Cleaner - Robot Cleaner -
Pre Filter (Washable) - Pre Filter (Washable) -
Ion Generator - Ion Generator -
CO2 Sensor AHCS100H0 CO2 Sensor AHCS100H0
Ventilation Kit - Ventilation Kit -
IR Receiver - IR Receiver -
Zone Controller - Zone Controller -
PDRYCB000 (1 point contact) PDRYCB000 (1 point contact)
Dry Contact (with additional accessory) Dry Contact (with additional accessory)
PDRYCB500 (Modbus) PDRYCB500 (Modbus)
External Input (1 point) ○ External Input (1 point) ○
Wi-Fi - Wi-Fi -

※ ○ : Applied, - : Not applied ※ ○ : Applied, - : Not applied


Option : Refer to model name in table Option : Refer to model name in table

118 / 119
CONTROL
SOLUTIONS

INDIVIDUAL CONTROL

CENTRALIZED CONTROL

INTEGRATION DEVICE

120 / 121
CONTROL SOLUTIONS

LG CONTROL SOLUTIONS
MULTI V 5 offers a diverse range of effective control solutions that satisfy specific needs of each building and its user scene.
These control systems are equipped with user-friendly interface, flexible interlocking environment, energy management and smart
individual controller for optimized controlling conditions and smart building management.

HOTEL OFFICE

Hotel Room Solution Central Control Solution

3rd Party BMS Cloud System

• Energy Management

• External Device

Lighting Pump Fan CO2 Temp.


Sensor Sensor

APARTMENT RESIDENTIAL SMALL BUILDING

Power Distribution Solution Smart Individual Control Solution Small Central Control Solution

Integration Solution
122 / 123
CONTROL SOLUTIONS _ INDIVIDUAL CONTROL

FEATURE FUNCTIONS
INDIVIDUAL Controller Name
Premium
Wired Remote Controller

Standard III Standard II Simple Simple(Hotel)


Wireless
Remote
Controller
Wi-Fi
Controller

CONTROL
Model Name

PREMTA000
PREMTB100 PREMTB001 PQRCVCL0Q PQRCHCA0Q NEW
PREMTA000A PWFMDD200
PREMTBB10 PREMTBB01 PQRCVCL0QW PQRCHCA0QW PWLSSB21H (H/P)
PREMTA000B

On / Off ○ ○ ○ ○ ○ ○ ○

Fan Speed Control ○ ○ ○ ○ ○ ○ ○

Temperature Setting ○ ○ ○ ○ ○ ○ ○

Mode Change ○ ○ ○ ○ - ○ ○

Auto Swing ○ ○ ○ ○ ○ ○

Vane Control
○ ○ ○ ○ ○ ○ ○
Basic (Louver Angle)

E.S.P
○ ○ ○ ○ ○ - -
(External Static Pressure)

Electric Failure
○ ○ ○ ○ ○ - ○
Compensation

Indoor Temperature Display ○ ○ ○ ○ ○ ○

ALL Button Lock


○ ○ ○ ○ ○ - -
(Child Lock)

Schedule / Timer Weekly - Yearly Weekly - Yearly Weekly - - Sleep / On / Off Weekly

SOLUTIONS
CONTROL
Additional Mode Setting 1)
○ ○ ○ - - - -

Time Display ○ ○ ○ - - ○ -

Humid. Display ○ ○ - - - - -

Advanced Lock
(Mode, Set point, Set point Advanced Lock Advanced Lock - - - - -
range, On / Off Lock)

INDIVIDUAL CONTROL
Filter Sign ○ ○ ○ - - - -
Advanced
Energy Management 2) ○ ○ ○ - - - -

Dual Set Point ○ ○ - - - - -

Human Detection - ○ - - - - -

Temp, Humidity
○ ○ - - - - -
Compensation

Wi-Fi AP Mode Setting ○ ○ ○ ○ ○ ○ -

Air Purification Function - ○ - - - - -

Operation Status LED ○ ○ ○ ○ ○ - -

Wireless Remote Controller


○ 3)
- ○ 3)
○ 3)
○ 3)
- -
Receiver

ETC Display 5 inch Color 4.3 inch Color 4.3 inch mono 2.6 inch mono 2.6 inch mono 2 inch mono -

Size (W x H x D, mm) 137 x 121 x 16.5 120 x 120 x 16 120 x 120 x 16 64 x 120 x 15 64 x 120 x 15 51 x 153 x 26 -

Black Light Control for


○ ○ - - - - -
Screen Saver

※ ○ : Applied, - : Not Applied


1) It might not be indicated or operated at the partial product.
2) Centralized control (PACEZA000 / PACS5A000 / PACP5A000 / PLNWKB000) and PDI (PQNUD1S40 / PPWRDB000) should be installed for this function.
3) For ceiling type duct
Note : 1. Indoor unit should have functions requested by the controller.
2. If you need more detail, please refer to the manual of product. (http://partner.lge.com : Home> Doc.Library> Manual)

124 / 125
CONTROL SOLUTIONS _ INDIVIDUAL CONTROL

STANDARD III WIRED REMOTE CONTROLLER


4.3 inch colored screen with modern design Energy Savings
Energy Management
Model Name PREMTB100 / PREMTBB10
- Energy Monitoring & Alarm
On / Off ○
Fan Speed Control ○
Real-time and day / week / month / year energy usage
Temperature Setting ○ monitoring is possible. In addition, it can set target for
Mode Change Cooling / Heating / Auto / Dehumidification / Fan energy usage and operation time, and alarm will be
Energy-Saving Cooling / Robot Cleaning / Heater /
Additional Mode Setting 1)
Humidification / Comfort Cooling
displayed when exceeded.
Instantaneous Power Check Energy Usage Target Setting
Auto Swing ○ ※ PDI (PQNUD1S40 / PPWRDB000) is required.
Vane Control (Louver direction) ○
PREMTB100 (White) PREMTBB10 (Black) E.S.P

(External Static Pressure) 2)
Reservation Simple / Sleep / On & Off timer / Weekly / Yearly / Holiday Time Limit Control
Time Display ○ - The time-limit operation controls product by amount of
Features & Benefits Electric Failure Compensation ○
time. By setting the device operation time in advance,
Lock All / On & Off / Mode / Set temperature range
• The optimized controller for MULTI V 5 Filter Sign ○ (Remain time + Alarm) users can control for how long a device works and have
- Humidity sensor embedded Check Energy Usage 3) / Check Operation Time / Target Setting it stop automatically.
Energy Management (Energy, Operation Time) / Time Limit Operation / Alarm Popup
- Comfort cooling setting / Initialization Usage Data
- Smart Load Control setting Operation Status LED ○
Indoor Temperature Display ○
- Outdoor unit low noise setting
Indoor Humidity Display ○
- Defrost mode setting Human Detection ○
• New modern design & easy interface Display 4.3 inch TFT color LCD (480 x 272)
- Seamless design / Touch button Size (W x H x D, mm) 120 x 120 x 16
- 4.3 inch color LCD / Intuitive GUI Black light for Screen saver
Home Leave

2 set points control
2 Set Points Control
• Energy saving functions
Auto Changeover for convenience

SOLUTIONS
※ ○ : Applied, - : Not Applied
- Instantaneous power monitor

CONTROL
Temperature
1) It might not be indicated or operated at the partial product. - With 2 set points control function, indoor unit manages
- Energy consumption check 2) This function is available for duct type.
3) This function requires PDI (PQNUD1S40 / PPWRDB000) to be installed. room temperature automatically.
(Power consumption, operation time) Note : 1. Indoor unit needs to have functions requested by the controller. Cooling set point
2. 2 set points control works normally with MULTI V Heat Recovery and Single Split for Unoccupied Cooling
- Temp. Setback timer, time limit control Heat Pump. But in case of MULTI V Heat Pump, It may not work properly. Setback for energy savings and comfort Cooling Set Point
- Target setting (ODU capacity, Instantaneous power) - In the user's absence, the room temperature will remain for Occupied
Occupied Unoccupied
• Group control between two set points rather than switching off providing Heating Set Point
for Occupied
- Up to 16 Indoor units can be controlled with one quick comfort when the mode is changed to occupied.

INDIVIDUAL CONTROL
Heating Set Point
Heating
remote control ※ This function is for Heat Recovery system or Single heat pump. for Unoccupied
Otherwise it is not guaranteed. Cooling Heating
• External device On / Off (1 point)
Time
- Customized interlocking control with indoor unit is Arrive at a room Leave a room
possible without dry contact Thermo-off
• 2 set points control Indoor temperature

- Increase convenience and comfort


- Auto changeover, Setback (Home leave)
• Air Purification External Device On / Off
- Air Quality Monitoring
- Air Purification function Control External Equipment Control Customized Interlocking Control
User can turn the external User can create a control scenario
equipment off or on through where the external heater
contact point output. switches on when temperature
drops below or rises above a
certain temperature.

Comfort Level
Schedule Function
Simple Schedule Status Exception Day settings
Standard III remote controller Possible to set up exceptional
Touch Button provides clock type daily schedule. date on regular schedule.

Energy Contents

Cool Heat Dry Fan Auto

Error History

126 / 127
CONTROL SOLUTIONS _ INDIVIDUAL CONTROL

PREMIUM WIRED REMOTE CONTROLLER STANDARD II WIRED REMOTE CONTROLLER


5 inch full touch screen with a premium design. Providing easy control of one or a group of indoor units with various functions.

Model Name PREMTA000 / PREMTA000A / PREMTA000B Model Name PREMTB001 / PREMTBB01


On / Off ○ On / Off ○
Fan Speed Control ○ Fan Speed Control ○
Temperature Setting ○ Temperature Setting ○
Mode Change Cooling / Heating / Auto / Dehumidification / Fan Mode Change Cooling / Heating / Auto / Dehumidification / Fan
Energy-Saving Cooling / Robot Cleaning / Heater / Energy-Saving Cooling /
Additional Mode Setting 1) Additional Mode Setting
Humidification Robot Cleaning / Heater / Humidification
Auto Swing ○ Auto Swing ○
Vane Control (Louver direction) ○ Vane Control (Louver direction) ○
E.S.P E.S.P (External Static Pressure) ○
○ Reservation Simple / Sleep / On / Off / Weekly / Holiday
PREMTA000 1) / PREMTA000A 2) / PREMTA000B 3) (External Static Pressure) 2) PREMTB001 (White) PREMTBB01 (Black) Time Display ○
Reservation Simple / Sleep / On / Off / Weekly / Yearly / Holiday
1) English / Portuguese / Spanish / French Electric Failure Compensation ○
2) English / Italian / Russian / Chinese Time Display ○
3) English / German / Polish / Czech Electric Failure Compensation
Child Lock


Features & Benefits Child Lock
Filter Sign

○ (Remain time + Alarm)
Operation Status LED ○
Filter Sign ○ (Remain time + Alarm) • Wired remote controller that can implement various Indoor Temperature Display ○
Features & Benefits Energy Management
Check Energy Usage 3) / Check Operation Time / Target
Setting (Energy, Operation Time) / Time Limit Opera- functions such as scheduling or filter alert. Wireless Remote Controller
○ 1)
tion / Alarm Popup / Initialization Usage Data Receiver
• Full Touch screen Operation Status LED ○ Size (W x H x D, mm) 120 x 120 x 16
Blacklight ○
• The optimized controller for MULTI V 5 Indoor Temperature Display ○
Power Consumption Monitoring ○ 2)
Wireless Remote Controller
- Comfort cooling setting Receiver
○ 4) Check Model Information ○
- Smart Load Control setting Display 5 Inch TFT color LCD (480 x 272) ※ ○ : Applied, - : Not Applied
Size (W x H x D, mm) 137 x 121 x 16.5 1) For ceiling type ducted unit
- Outdoor unit low noise setting Black Light for Screen Saver ○ 2) This function requires PDI (PQNUD1S40 / PPWRDB000) to be installed.
Note : Indoor unit needs to have functions requested by the controller.
- Defrost mode setting Home Leave 2 Set Points Control
• Design with user’s convenience ※ ○ : Applied, - : Not Applied
1) It might not be indicated or operated at the partial product.
- Intuitive GUI 2) This function is available for duct type.

SIMPLE WIRED REMOTE CONTROLLER


- Main display simple mode 3) This function requires PDI (PQNUD1S40 / PPWRDB000) to be installed.
4) For ceiling type ducted unit.

SOLUTIONS
- 5 inch color LCD Note : 1. Indoor unit needs to have functions requested by the controller.

CONTROL
2. 2 set points control works normally with MULT V Heat Recovery and Single Split Heat
• Energy saving functions Pump. But in case of MULTI V Heat Pump, It may not work properly.
- Instantaneous power monitor A simple way to control office or hotel systems in a compact design.
- Energy consumption check
(Power consumption, operation time) Model Name PQRCVCL0QW / PQRCHCA0QW /
PQRCVCL0Q PQRCHCA0Q
- Temp. Setback timer, Time limit control On / Off ○ ○
- Target setting (ODU capacity, Instantaneous power…etc) Fan Speed Control ○ ○

INDIVIDUAL CONTROL
Temperature Setting ○ ○
• Group control Cooling / Heating / Auto /
Mode Change -
- Up to 16 Indoor units can be controlled with one remote control Dehumidification / Fan
Auto Swing ○ ○
• 2 set points control Vane Control (Louver direction) ○ ○
- Increase convenience and comfort E.S.P (External Static Pressure) ○ ○
Electric Failure Compensation ○ ○
- Auto changeover, Setback (Home leave) PQRCVCL0QW (White) / PQRCHCA0QW (White) / Child Lock ○ ○
PQRCVCL0Q (Black) PQRCHCA0Q (Black) Indoor Temperature Display ○ ○
Wireless Remote Controller
Easy Energy Management Receiver
○ 1) ○ 1)
Full Touch
Screen
- Check the operation hour or electricity usage
- Comparison of usage compared to last year
Features & Benefits Size (W x H x D, mm)
Blacklight
70 x 121 x 16

70 x 121 x 16

- Set the target usage and time • Small remote control with minimal functionality ※ ○ : Applied, - : Not Applied
1) For ceiling type ducted unit
Note : Indoor unit needs to have functions requested by the controller.
Easy Scheduling
- Daily, Weekly, Yearly schedule function
- Schedule pattern setting

WIRELESS REMOTE CONTROLLER


- Schedule copy

2 Set points Control Temperature

- Auto changeover switching the operation Cooling Model Name PWLSSB21H (H/P)
Upper
mode automatically Temperature limit On / Off ○
- Setback (Home Leave) Changing status by Lower
Auto Changeover Setback Fan Speed Control ○ 1)
occupied / unoccupied Temperature limit Temperature Setting ○
Heating
Mode Change Cooling / Heating / Auto / Dehumidification / Fan
* This function is only for Heat Recovery system
and Single heat pump. Time Plasma Purification / Energy-Saving Cooling /
Leave For Home Leave For Home Additional Mode Setting
Robot Cleaning / Auto Dry
Group Control Auto Swing ○
Indoor unit 1 Indoor unit 2 Indoor unit 3 Vane Control (Louver direction) ○
- Max. 16 Indoor units by one remote controller. NEW
1 Master
1 Slave Slave
Reservation Sleep / On / Off
Time Display ○
Red (12V)
Yellow (Sig)
Black (GND)
Yellow (Sig)
Black (GND)
Yellow (Sig)
Black (GND) PWLSSB21H (H/P) Indoor Temperature Display ○
Sleep Mode Auto Max. 7 hours
2 2 Features & Benefits Size (W x H x D, mm) 51.4 x 153 x 26
Master ※ ○ : Applied, - : Not Applied
• Easy to use while moving • Main functions are available 1) For some products, you can use “slow” fan speed function.

128 / 129
CONTROL SOLUTIONS _ INDIVIDUAL CONTROL

LG Wi-Fi MODEM
Control LG air conditioners by using internet devices as Android or iOS smartphones. LG ThinQTM Connectivity
Model Name PWFMDD200
LG ThinQ
TM
Size (W x H x D, mm) 48 x 68 x 14
Interfaceable Products MULTI V Indoor unit 3)
Connection Type Indoor unit 1:1
Communication Frequency 2.4 GHz ➋
Wireless Standards IEEE 802.11b/g/n
LG ThinQTM (Android v4.1(Jellybean) or higher, iPhone iOS
Mobile Application
9.0 or higher)
PWFMDD200 Optional Extension Cable PWYREW000 (10m extension)

1) Vane Control may not be possible according to the type of Indoor unit. ➊ ➊ ➌
2) LG Centralized controller and PDI installation is required for this function.
Features & Benefits 3) For the compatibility with Indoor unit, please contact regional LG office.
Note : 1. Functionality may be different according to each IDU model.
2. User interface of application shall be revised for its design and contents improvement.
• User can enjoy anytime, anywhere access with Wi-Fi 3. Application is optimized for smartphone use, so it may not be well functioning
equipped device through LG's ThinQTM mobile app. with tablet devices. Internet
Service Provider
• This allows the user to access the unit remotely to Wireless AP
switch unit on or off before or after leaving the vicinity. (Router)
• LG’s exclusive Home Appliances control app (LG ThinQTM)
is available Connection (Pairing) Order
• Simple operation for various functions ➊ Make LG account on LG ThinQTM and select the Router that will be used
- On / Off ➋ Insert passwords of selected router and set AP (Access Point) by LG remote controller
- Operation mode ➌ Confirm the pairing between Wi-Fi Modem and Router
- Current/Set temperature
- Fan speed

SOLUTIONS
- Vane control 1)

CONTROL
- Reservation (Sleep, Weekly On / Off) ThinQTM Mobile App
- Energy monitoring 2)
- Filter management Simple operation for various functions
Controlling Reservation Energy
- Error check & Monitoring Monitoring On/Off, Current Temp, Mode, Set Temp Vane Control

INDIVIDUAL CONTROL
Overview

Wi-Fi
Modem ThinQTM Server

USB Wire

Day Night

Easy Management
LG ThinQTM
Reservation Energy Monitoring Smart Diagnosis Filter Management
※ Search “LG ThinQTM” on Google market or Appstore then download the app.
※ Internet service with Wi-Fi connection has to be available.

Installation Scene Control box

Indoor unit PCB

Control panel
USB cable Wi-Fi modem

※ Each indoor unit has a Wi-Fi modem installation location inside the product, and it can be installed by exposure if necessary.

130 / 131
CONTROL SOLUTIONS _ CENTRALIZED CONTROL

CENTRALIZED CONTROLLER FEATURE LIST


CENTRALIZED Controller Name AC Ez AC Ez Touch AC Smart 5 5) ACP 5 5) ACP Lonworks AC Manager 5 3)

CONTROL Model Name

PQCSZ250S0 PACEZA000 PACS5A000 PACP5A000 PLNWKB000 PACM5A000


DO - - 2 4 2 -
DI - 1 2 10 2 -
IDUs 32 64 128 256 64 8,192
Product ERV 32 64 128 256 64 8,192
Max.
Connectable A/C + ERV 32 64 128 256 64 8,192
No.
AHU - - 16 16 16 4)
16 x 32
Chiller - - 5 Optional 2) 10 Optional 2) - 10 x 32
Air Conditioner ○ 1) ○ ○ ○ ○ ○
Ventilation (ERV / ERV DX) ○ 2) ○ ○ ○ ○ ○
Heating - ○ ○ ○ ○ ○
Compatibility
AHU - - ○ ○ ○ ○
Chiller - - ○ 4) ○ 4) - ○
ACS IO - - ○ 4)
○ 4)
○ 4)

Add Drawing - - ○ 4) ○ 4) ○ 4) ○
Group Management - - ○ 4) ○ 4) ○ 4) ○
Auto Changer Over - ○ ○ 4) ○ 4) ○ 4) ○

SOLUTIONS
Set Back - ○ ○ 4) ○ 4) ○ 4) ○

CONTROL
Additional
2 Set - ○ ○ ○ ○ 4) ○
Function
Change Alarm - Filter Filter Filter Filter Filter
Indoor Unit Lock - ○ ○ ○ ○ 4) -
Cycle - - ○ ○ ○ 4) ○
Air Purification Function - - ○ ○ - ○

CENTRALIZED CONTROL
Schedule ○ ○ ○ 4) ○ 4) ○ 4) ○

Peak Priority Control - ○ ○ ○ ○ 4) ○


Control Outdoor Unit Capacity Control - - ○ 4) ○ 4) ○ 4) ○
Auto Control
Time limit control - - ○ 4) ○ 4) ○ 4) ○
Interlocking - - ○ 4)
○ 4)
○ 4)

Energy Navigation - - ○ 4) ○ 4) - ○
Power - ○ ○ ○ ○ 4) ○
Gas - - ○ ○ ○ 4) ○
Energy
Run time - - ○ 4) ○ 4) ○ 4) ○
Report
Email - - - - ○ 4) -
PC / USB - - ○ 4) PC PC PC
Trend Reporting - - - - - ○
Report (Control / Error) - Error ○ 4) ○ 4) ○ 4) ○
History Send Email - - ○ 4) ○ 4) ○ 4) ○
Save to PC / USB 6)
- - - - ○ 4) -
Summer Time - ○ ○ 4) ○ 4) ○ 4) ○
Outdoor Unit Oil-Return Operation - - ○ 4) ○ 4) ○ 4) -
etc
User Authority - Password ○ 4) ○ 4) ○ 4) ○
PC Access - ○ ○ 4) ○ 4) ○ 4) ○

※ ○ : Applied, - : Not Applied


1) Except for some feature (individual lock, limit, temp., etc.)
2) Except for some feature (user mode, additional function, etc.)
3) ACP 5 or AC Smart 5 is required.
4) This function is possible to use in Web Only. (BMS Point is not applied.)
5) Without additional device, ACP 5 and AC Smart 5 provide BACnet IP and Modbus TCP interface for BMS.
6) Save to PC / USB function will be available from 4Q 2020.

132 / 133
CONTROL SOLUTIONS _ CENTRALIZED CONTROL

AC EZ TOUCH
Smart management with 5 inch touch screen for small site. Energy Mode Schedule
When using energy mode function, operation mode changes Schedule control allows user to set the events in advance
Model Name PACEZA000 from cooling to fan or heating to off mode by force. to maximize system performance. Also, by blocking
Size (W x H x D, mm) 137 x 121 x 25 (It is available only for operating indoor unit) unnecessary operation, it prevents a waste of energy.
Interfaceable Products MULTI V / ERV / ERV DX / HYDRO KIT / THERMA V
Maximum number of units 64
Individual / Group Control On & Off / Mode / Temperature / Fan speed
Individual Controller Lock Temperature / Mode / Fan speed / All
Error Check ○
Slave Mode (Interlocking with

PACEZA000 higher level controller)
Schedule Weekly / Monthly / Yearly / Exception day
Remote Access By client S/W
Features & Benefits Emergency Stop & Alarm

Display
• User-friendly control with iconographic interface
Power Consumption

• Total 200 schedule events Monitoring (with PDI)
• Energy saving mode Auto Changeover / Setback ○ Alarm Indicator Group / Individual Control
• Energy monitoring (with PDI) Temperature Limit ○ It shows errors and alarm information. Users can respond User can control each indoor unit individually or by group
Operation History Error record immediately according to alarm indicator therefore HVAC by simply clicking each unit on control screen.
• 2 set point function (Upper / Lower temperature setting)
ODU Low Noise 1) ○
• Temperature set points range limit system is monitored consistently.
Daylight Saving Time ○
• Remote controller lock (All, Temp, Mode, Fan Speed)
External IO Port DI 1
• Operation history
IPv6 Support ○
• Clean or change filter alert
※ ○ : Applied, - : Not Applied
• Emergency stop 1) It is only available in some products.

SOLUTIONS
CONTROL
Overview

IDU
...

CENTRALIZED CONTROL
PC Internet AC EZ TOUCH

...
IDU
AC EZ
Easy to manage up to 32 indoor units, including ERV with simple interface.

ERV Model Name PQCSZ250S0


Size (W x H x D, mm) 190 x 120 x 20
Interfaceable Products MULTI V / ERV / ERV DX
Display LED / LCD Display
Feature Power DC 12V
Maximum number of units 32
PC Access Energy Statistics (with PDI)
Individual / Group Control On & Off / Mode / Temperature / Fan speed
Users can control each space efficiently through PC access. Statistics of operational status (Time, Power consumption)
Individual Controller Lock All
are provided to help make intelligent system operation PQCSZ250S0 Error Check ○
decisions. Slave Mode (Interlocking with

higher level controller)
Schedule Weekly

※ ○ : Applied, - : Not Applied

* IPv6 supported
Features & Benefits
• 32 indoor units control
• Weekly Schedule
• Individual / Group Control
Internet Appropriate PI 485 should be • MULTI V 5 • MULTI V • MULTI V S • MULTI SPLIT • ERV
used according to PDB • MULTI V IV WATER IV • SINGLE SPLIT
* Fix Public IP is mandatory. • MULTI V III • MULTI V
* Router’s Configuration of NAT is mandatory. Open port 80 & 9300. • MULTI V II WATER II

134 / 135
CONTROL SOLUTIONS _ CENTRALIZED CONTROL

AC SMART 5
10-inch touch screen with HTML5 GUI (Graphic User Interface) for easy control. Building Management System (BMS) Integration Advanced Network Accessibility
Without additional device, AC Smart 5 provides BACnet IP & Modbus TCP inter- AC Smart 5 reflects the state of the art of network technology trend. IPv6
Model Name PACS5A000 face for BMS integration as well as its own management function. (Internet Protocol version 6), which is the most recent version of the Internet
Size (W x H x D, mm) 253.2 x 167.7 x 28.9 Protocol, provides accessibility to the IPv6 compatible network environment.
MULTI V / ERV / ERV DX / HYDRO KIT / In addition, HTML5 allows you to easily control LG HVAC system on a variety
Interfaceable Products
THERMA V / AHU kit / LG Chiller 1) of platforms (PC, Mobile, Tablet), at any time and from any location, not just
Maximum number of units 128 on the touch screen.
Individual / Group Control On & Off / Mode / Temperature / Fan speed BACnet over IP BMS
Individual Controller Lock Temperature / Mode / Fan speed / All
Comfort Cooling / ODU Low Noise / ODU Defrost Mode /
Advanced Function Setting and
Comfort Level display / CO2 Level display (for ERV /
Display 2)
ERV DX) / Night Time Free Cooling (for ERV / ERV DX)
Error Check ○
PACS5A000 Slave Mode (Interlocking with

higher level controller) IPv6
Schedule Weekly / Monthly / Yearly / Exception day Network
Features & Benefits Web Access ○
Emergency Stop & Alarm

• The central controller allows control of the LG Display
Power Consumption
HVAC system to various platforms. Monitoring (with PDI)
○ HTML5 web design
(Touch screen, PC, Smartphone, Tablet) Auto Changeover / Setback ○
Temperature Limit ○
- DI : 2 / DO : 2 Operation Time Limit ○
- Max. 128 IDU control Visual Navigation ○
Operation Trend ○
- BACnet IP/Modbus TCP
Interlock Control ○ Energy Management Visualized Control
- Schedule Virtual Group Control ○
The energy navigation function allows the air conditioner’s operational energy Visual navigation enables controlling and monitoring the unit on floor plan
- Map view (Visual navigation) ODU Capacity Control ○
usage to be manged monthly, weekly and yearly. By analyzing present energy view for the intuitive management.
Energy Navigation (with PDI) ○
- Time limit control / Auto change over Daylight Saving Time ○
consumption and comparing with the plan, overuse of system operational costs
- Energy monitoring External IO Port DI 2 / DO 2 can be prevented.
BMS Integration 3) BACnet IP / Modbus TCP
- History / Operation trend
IPv6 Support ○

SOLUTIONS
- Interlock with 3rd party equipment

CONTROL
※ ○ : Applied, - : Not Applied
(ACS IO, ACU IO Module is needed) 1) Chiller Option Kit (PCHLLN000) is required
2) It is only available in some products
- Multi level grouping 3) For the detail point list, please refer to the installation manual
- Emergency stop & alarm
- Error alarm by e-mail
- Air quality monitoring
- Air purification function control

CENTRALIZED CONTROL
Overview
IDU
Internet AC Smart 5

...
PC
Multi Level Group Composition Interlocking with 3rd party equipment
User can make frequent and multi level group to control and monitor the device AC Smart 5 can make operation scenario with 3rd party equipment by ACS IO
...
easily. Module. Control coverage is expanded. (Air conditioner only → Sensors, Fans,
Pumps, Switches…)
Smartphone
ERV LG SAC
ODU

OR OR
Tablet Chiller AHU Air Water HYDRO KIT IDUs
ACS IO Option kit AHU Controller AC Smart 5 cooled cooled

3rd party interlocking Chiller AHU Comm. kit 3rd party interlocking
Sensor Facility Sensor Facility

Temp. CO2 Cooling Emergency


Motion Temp. CO2 Cooling Pump Centrifugal Absorption tower
tower
Etc. Occupancy
Valve Fan

...
Sensor
Screw Invert Scroll
Emergency Lighting Valve Fan Expansion
Control coverage
* Fix Public IP is mandatory. Temp. Lighting
* Router’s Configuration of NAT is mandatory. Open port 80 & 9300. ACS IO

136 / 137
CONTROL SOLUTIONS _ CENTRALIZED CONTROL

ACP 5 ACP LONWORKS GATEWAY


Advanced solution for BMS integration up to 256 units via BACnet and Modbus protocol as well as its own smart Lonworks easily link LG air conditioners and other existing building systems. By including ACP control function,
management function with web server interface. the controlling continues even when error occurs with BMS.

Model Name PACP5A000 Control Monitoring


Size (W x H x D, mm) 270 x 155 x 65 On / Off Command On / Off
MULTI V / ERV / ERV DX / HYDRO KIT / Operation Mode Setting Operation Mode
Interfaceable Products
THERMA V / AHU kit / LG Chiller 1)
Maximum number of units 256 Lock Lock
Individual / Group Control On & Off / Mode / Temperature / Fan speed Temperature Temperature
Individual Controller Lock Temperature / Mode / Fan speed / All Fan Level Fan Level
Comfort Cooling / ODU Low Noise / ODU Defrost Mode / Fan Direction Auto Fan Direction Auto
Advanced Function Setting and
Comfort Level display / CO2 Level display (for ERV / ERV DX) /
Display 2) Mode Lock Mode Lock
Night Time Free Cooling (for ERV / ERV DX)
Error Check ○ Fan Level Lock Fan Level Lock
PACP5A000 Schedule Weekly / Monthly / Yearly / Exception day
PLNWKB000
Temperature Lock Temperature Lock
Web Access ○ Temperature Lower Limit Temperature Lower Limit
Emergency Stop & Alarm
Features & Benefits Display
○ Features & Benefits Temperature Higher Limit Temperature Higher Limit
Power Consumption Peak Convert Cycle Peak Convert Cycle

• The central controller allows control of the LG HVAC Monitoring (with PDI) • Connect to use Lonworks protocol and LG air Peak Setting Peak Setting
Auto Changeover / Setback ○
system by various platforms. (PC, Smartphone, Tablet) Temperature Limit ○
conditioner protocol. Temperature Unit Temperature Unit
Total Temperature Lock -
- DI :10 / DO : 4 Operation Time Limit ○ • Process ability (Max. connection) : Indoor unit
Visual Navigation ○ Total On / Off -
- Max. 256 IDU control 64EA, AHU Control Kit : Max. 16EA
Operation Trend ○ Total Temperature -
- BACnet IP/Modbus TCP Interlock Control ○ • Self installation verification using internet - Product Type
- Schedule Virtual Group Control ○ (Web Server Included) - Diagnosis of communication - Product Address
ODU Capacity Control ○
- Map view (Visual navigation) Energy Navigation (with PDI) ○
status on LG Air-conditioner network - Current Temperature
- Alarm
- Time limit control / Auto change over Daylight Saving Time ○ • It offers a variety of functions as ACP which allows
External IO Port DI 10 / DO 4 - Power
- Energy monitoring the customer to efficiently control various types of - Error Code
BMS Integration 3) BACnet IP / Modbus TCP
- History / Operation trend IPv6 Support ○ equipment from the customer’s own Integration. - Peak Current Operating Percent
- Interlock with 3rd party equipment

SOLUTIONS
- Total Accumulate Power

CONTROL
※ ○ : Applied, - : Not Applied
(ACS IO, ACU IO Module is needed) 1) Chiller Option Kit (PCHLLN000) is required.
※ ○ : Applied, - : Not Applied
2) It is only available in some products.
- Multi level grouping 3) For the detail point list, please refer to the installation manual.

- Emergency stop & alarm Overview


- Error alarm by e-mail
- Air quality monitoring
- Air purification function control Lighting control Remote checking Utility control

CENTRALIZED CONTROL
CH5 BMS system
CH1 ~ 4 Indoor unit : Max. 64 units (Air conditioner & Ventilation) / Indoor address : 00 ~ FF
Overview Internet ACP 5 IDU
* Master
1)
PC
...
Internet

AC Smart 5
* Slave • MULTI V 5 • MULTI V • MULTI V S • MULTI SPLIT • ERV • AHU (Control Kit)
• MULTI V IV WATER IV • SINGLE SPLIT
Smartphone ... • MULTI V III • MULTI V
Backup operation • MULTI V II WATER II

* Fix Public IP is mandatory. Appropriate PI 485 should be used according to PDB (Product Data Book)
OR OR ERV * Router’s Configuration of NAT is mandatory. Open port 80 & 9300.
Chiller 1) Assignment of public IP address is required to access central controller through internet.
Tablet ACS IO Option kit AHU Controller

3rd party interlocking Chiller AHU


AHU
Sensor Facility

Comm. kit
PI 485
Motion Temp. CO2 Cooling Pump Centrifugal Absorption
tower
Etc. PI 485 converts LG air conditioner’s protocol to the RS485 protocol for the central controller.

Screw Invert Scroll • Power : Connected with the


Emergency Lighting Valve Fan
Indoor Units
Multi level group / • 1 for Each Indoor Unit
Advanced Network Accessibility Energy Navigation BACnet IP & Modbus TCP Special control group - Indoor Unit (ERV)
BACnet over IP BMS

IPv6
Network PHNFP14A0
HTML5 web design
* Fix Public IP is mandatory. * Router’s Configuration of NAT is mandatory. Open port 80 & 9300.
138 / 139
CONTROL SOLUTIONS _ CENTRALIZED CONTROL

AC MANAGER 5
Multiple ACP and AC Smart integration solution to manage multi sites up to 8,192 units as a single system. Stand-alone
Integrated with S/W program and Hardware platform, it is
Model Name PACM5A000
convenient to install since users no longer need to install
Size (W x H x D, mm) 270 x 155 x 65
program with lock-key on PC.
MULTI V / ERV / ERV DX / HYDRO KIT /
Interfaceable Products
THERMA V / AHU kit / LG Chiller 1)
Maximum number of units 8,192 (supports 32 ACP 5 or AC Smart 5)
Individual / Group Control On & Off / Mode / Temperature / Fan speed
Individual Controller Lock Temperature / Mode / Fan speed / All
Error Check ○ Up to 8,192 Connections for Indoor Units Max. IDU 256 EA

PACM5A000 Schedule Weekly / Monthly / Yearly / Exception day


Administrators can easily and conveniently manage a ...
Web Access ○
Emergency Alarm Display ○
variety of LG HVAC equipment. Also, it is available to Max. IDU 128 EA
Features & Benefits Power Consumption manage many buildings or areas at one place via AC
○ ...
• Console Type : No needs software installation and lock-key
Monitoring (with PDI) Manager 5.
Auto Changeover / Setback ○
• Max. 8,192 IDU Control

...

...
Temperature Limit ○
• Schedule Operation Time Limit ○
Max. IDU 256 EA
• Map view (Visual Navigation) Visual Navigation ○ ...
• Time limit control / Auto change over Operation Trend ○
• Energy monitoring / Navigation Interlock Control ○
• History / Operation trend Virtual Group Control ○

• Emergency stop & alarm ODU Capacity Control ○ Advanced Network Accessibility & User Friendly GUI (Reddot award)
Energy Navigation (with PDI) ○
• Error alarm by E-mail As an advanced central controller, AC Manager 5 offers flexible
• Multi language ※ ○ : Applied, - : Not Applied
interface for each user by assessing the device screen and
1) Chiller Option Kit (PCHLLN000) is required.
(Eng, Ita, Spa, Por, Rus, Fra, Ger, Tur, Pol, Chi, Kor) Note : AC Manager 5 requires ACP 5 or AC Smart 5.
automatically customizing the layout to provide the most

SOLUTIONS
• Air quality monitoring optimized interface.

CONTROL
• Air purification function control

Overview
AC Manager 5 ACP 5 ODU / IDU & ERV
AHU
PC Comm.kit Energy Navigation & Energy Usage Trend

CENTRALIZED CONTROL
Energy navigation is the function to set the target usage
Internet
amount to limit the monthly power consumption and to
Chiller & AHU
control so that the total accumulated power consumption
Chiller Option kit AHU Controller
does not exceed the target usage amount. It performs
Mobile
total of 7 control levels with the estimated / actual usage
amount exceeding ratio compared to the monthly target
3rd party Device
usage amount. For the control method, there are indoor unit
Compressor Capacity IDU operation IDU operation
operation ratio, outdoor unit capacity control, and indoor Control Ratio Control level
Tablet
ACS IO Module unit operation control.

AC Smart 5 ODU / IDU, ERV, Chiller, AHU, 3rd party Device


Operation ratio (IDUs) Control ODU Capacity Control
Peak Control
※ Fix Public IP is mandatory. 9 Step Operation rate (%)
※ Router’s Configuration of NAT is mandatory. Open port 80 & 9300.
This function can reduce electricity use. There are two kinds [ 0, 40, 45, 50, 60, 70, 80, 90, 100 ]
Indoor unit Priority Control
of control logic. Energy saving effect by indoor unit operation gradually stop depending on
importance of room.
rate control. Load management effect by outdoor unit capacity
control.
Robby < Office < VIP room Compressor Hz Control

AC Manager 5
AC Manager 5 Control tower Multi Level Group Composition
ACP 5 ACP 5 AC Smart 5 User can make frequent and multi level group to control and
monitor the device easily.

140 / 141
CONTROL SOLUTIONS _ CENTRALIZED CONTROL

MODBUS RTU GATEWAY MODBUS RTU GATEWAY


Providing Modbus RTU connection between LG Air conditioners and BMS. Holding Register (0 x 03)
Data Bit
No. Function Register
Air Conditioner ERV / DX ERV HYDROKIT & THERMA V
0 : Cooling, 1 : Dehumidifying,
2 : Fan, 3 : Auto, 4 : Heating Hydrokit
1 Operate Mode Operate Mode Connected IDU (Middle Temp. DHW) / AWHP
– 0 : Cooling, 3 : Auto, 4 : Heating
Hydrokit (High Temp. DHW)
2 Fan Speed Fan Speed Target Temp. DHW 2) 1 : Low, 2 : Mid, 3 : High, 4 : Auto Register = N x 20 + ①
(N = Indoor Unit Central Address)
3 Target Temp. Target Temp. 1) Target Temp. 2) 16.0 ~ 30.0 [°C] x 10
4 Target Temp. Limit (Upper) Target Temp. Limit 1) (Upper) Reserved 16.0 ~ 30.0 [°C] x 10
5 Target Temp. Limit (Lower) Target Temp. Limit 1) (Lower) Reserved 16.0 ~ 30.0 [°C] x 10
6 Reserved Vent. Operate Mode Reserved 0 : HEX, 1 : Auto, 2 : Normal

1) This register value is applied ‘DX Ventilator’ ONLY.


2) This value range can be between 0 ~ 127 [°C]. And it would be limited by upper & lower value according to the setting of remote controller.

PMBUSB00A Input Register (0 x 04)


Data Bit
Features & Benefits No.
Air Conditioner ERV / DX ERV HYDROKIT & THERMA V
Function Register

• Function 1 Error Code Error Code Error Code


0 ~ 255 ※ Please refer to the
product error table.
- MODBUS RTU communication with MODBUS - Size (W x H x D) : 53.6 x 89.7 x 60.7
2 Room Temp. RA Temp. Room Temp. -99.0 ~ 99.0 [°C] x 10
master controller - Max. 16 IDUs with single module
3 Pipe In Temp. OA Temp. 1) Water Inlet Temp. -99.0 ~ 99.0 [°C] x 10 Register = N x 20 + ①
- MODBUS RTU slave (RS485) / 9,600 bps / Max. 64 IDUs with 4 modules 4 Pipe Out Temp. SA Temp. 1) Water Outlet Temp. -99.0 ~ 99.0 [°C] x 10
(N = Indoor Unit Central Address)

- Applicable for MULTI V 5, MULTI V S, ERV, - Power : DC 12V 5 Reserved Pipe In Temp. 1) Sanitary Tank Temp. -99.0 ~ 99.0 [°C] x 10
THERMA V 6 Reserved Pipe Out Temp. 1) Solar Temp. 2) -99.0 ~ 99.0 [°C] x 10

1) This register value is applied ‘DX Ventilator’ ONLY.


2) This register value is applied ‘AWHP’ ONLY.

SOLUTIONS
CONTROL
Modbus Gateway Memory Map Installation Scene
Baud Rate : 9,600 bps, Stop Bit : 1 stop bit, Parity : None Parity, Byte size : 8 bits • Single module
Max. 16 indoor units with a single module

CENTRALIZED CONTROL
Coil Register (0 x 01)
Data Bit Modbus RTU
No. Function Register
Air Conditioner ERV / DX ERV HydroKit & THERMA V
1 Operate (On / Off) Operate (On / Off) Operate (On / Off) 0 : Stop / 1 : Run
2 Auto Swing Aircon Operate (On / Off) Hot Water Mode (On / Off) 0 : Disable / 1 : Enable
3 Filter Alarm Release Filter Alarm Release 1) Reserved 0 : Normal / 1 : Alarm Release BMS
4 Lock Remote Controller Lock Remote Controller Lock Remote Controller 0 : UnLock / 1 : Lock
RS485 (LGAP)

5 Lock Operate Mode Lock Operate Mode 1) Reserved 0 : UnLock / 1 : Lock Register = N x 16 + ①
6 Lock Fan Speed Lock Fan Speed 1) Reserved 0 : UnLock / 1 : Lock (N = Indoor Unit Central Address)

7 Lock Target Temp. Lock Target Temp. 1) Reserved 0 : UnLock / 1 : Lock


8 Lock IDU Address Lock IDU Address 1) Reserved 0 : UnLock / 1 : Lock
9 Reserved Quick Ventilate Reserved 0 : Disable / 1 : Enable
10 Reserved EnergySave Reserved 0 : Disable / 1 : Enable

1)This register value is applied ‘DX Ventilator’ ONLY.


• Multiple module
Max. 64 indoor units with 4 modules in one Modbus communication line
Modbus RTU
Discrete Register (0 x 02)
Data Bit
No. Function Register
Air Conditioner ERV / DX ERV HydroKit & THERMA V
1 Connected IDU Connected IDU Connected IDU 0 : Disconnected / 1 : Connected
2 Alarm Alarm Alarm 0 : Normal / 1 : Alarm
BMS
0 : Normal / 1 : Alarm Hydrokit Register = N x 16 + ① RS485 (LGAP)
3 Filter Alarm Filter Alarm 1)
Hot Water Only 2)
– 0 : Normal / 1 : Hot Water Only (N = Indoor Unit Central Address)
4 Reserved Reserved Target Temp Select 0 : Air / 1 : Water
5 Reserved Reserved Error Division 2) 0 : CH type error / 1 : BC type error Max. 16 outdoor units in
1) This register value is applied ‘DX Ventilator’ ONLY.
one RS485 (LGAP) line
2) This register value is applied ‘Hydrokit’ ONLY.

142 / 143
CONTROL SOLUTIONS _ INTEGRATION DEVICE

PDI (POWER DISTRIBUTION INDICATOR)


INTEGRATION PDI shows distributed power consumption of up to 128 indoor units.

DEVICE
Model Name PQNUD1S40 PPWRDB000
Size (W x H x D, mm) 270 x 155 x 65
Interfaceable Products Air conditioner, ERV DX

Maximum Number of EHP : 8 Watt meter EHP : 2 Watt meter


GHP : 4 Watt meter GHP : 1 Watt meter
Power Meters / 4 Gas meter / 1 Gas meter
Maximum Number of
MULTI V : 128
Indoor Units
Data Backup
PQNUD1S40 (Premium, 8 port) when Power Outage

PPWRDB000 (Standard, 2 port) Power Input PDI : AC 24V, Transformer : AC 220V


※ ○ : Applied, - : Not Applied
Features & Benefits
• Enables total and indoor power consumption monitoring
• With LG central control connectivity, energy monitoring, energy savings operations and target usage setting functions are enabled
• Enables gas consumption and electricity distribution

Pulse line
ACS Central controller

SOLUTIONS
CONTROL
220 V~
ACP 5
24 V~

PDI power source RS485

INTEGRATION DEVICE
BUS-A BUS-B AC Smart 5

50kW

Measurement
MENU

AC Manager 5 70kW
SELECT
(00) ~ (03)
160kW [00] [01] [02] [03]

ACP 5 50kW
[10] [11] [12] [13]
[ Slave 1]
[ Master ] [20] [21] [22] [23]
AC Smart5 ACP

Graphing [30] [31] [32] [33]

Note : 1. Power cable and type could be different from this scene depending on the Outdoor unit’s specification.
2. Measured power consumption could be different between PDI and Watt meter.
3. Applicable Central Controller : ACP 5, ACP Lonworks, AC Smart 5, AC Ez Touch
(Combination : we recommend to connect separated watt meter for Outdoor units to have correct power distribution value.)

144 / 145
CONTROL SOLUTIONS _ INTEGRATION DEVICE

ACS IO MODULE ACU IO MODULE


This module can be connected with ACP 5 or AC Smart 5 controller if additional I/O points such as DI/DO and This module can be connected with ACP 5 or AC Smart 5 controller if additional I/O points such as UIO / UI / UO
AI/AO for 3rd party devices control and monitoring are needed. for 3rd party devices control and monitoring are needed.

Model Name PEXPMB000 ACU.UIO ACU.UO ACU.UI Module Name PEXPMB300 PEXPMB200 PEXPMB100
PACS4B000 Linkable Products PACS5A000, PACP5A000
PACP4B000
Linkable Products Communication
PACS5A000 2 ch. 1) 1 ch. 1 ch.
PACP5A000 RS-485
Communication RS-485 1 ch. Digital Input - - 3 port
Digital Input 3 port Digital Output 2 port 6 port -
Digital Output 3 port Universal Input 2) 4 port - 6 port
I/O
Universal Input 1) 4 port Analog Output 2 port 4 port
PEXPMB000 Analog Output 4 port PEXPMB300 PEXPMB200 PEXPMB100
Value Spec Min. Max.
Value Spec Min. Max. Analog Input DC (Voltage) 0V 10V
NTC 10k 0.68kΩ 177kΩ Analog Output DC (Voltage) 0V 10V
PT 1000 803kΩ 1,573kΩ Binary Input
Digital Input - -
(Non Voltage)
Analog Input Ni 1000 871.7kΩ 1,675.2kΩ
Digital Output Normal Open - 30VDC, 1A
DC (Voltage) 0V 10V
※ ○ : Applied, - : Not Applied
DC (Current) 0mA 20mA
1) 1ch is reserved for internal communication
Analog Output - 0V 10V 2) The type of UI (Universal Input) is selectable among Digital Input and Analog Input
Binary Input
Features & Benefits
Digital Input - -
(Non Voltage)
• Interlocking with 3rd party equipment LG Central controller can make operation scenario with 3rd party equipment by ACU IO Module.
Digital Output Normal open - 30VAC / 30VDC, 2A
• Applicable devices are expanded. (Air conditioner only → Sensors, Fans, Pumps, Switches …)
※ ○ : Applied, - : Not Applied
1) The type of UI (Universal Input) is selectable among Digital Input and Analog Input

Features & Benefits

SOLUTIONS
CONTROL
• Interlocking with 3rd party equipment LG Central controller can make operation scenario with 3rd party equipment by ACS IO Module.
• Control coverage is expanded. (Air conditioner only → Sensors, Fans, Pumps, Switches …) CHILLER OPTION KIT
LG central controller 5 series with Chiller Option Kit can provide LG chiller remote control and cycle monitoring.
Key Application
LG Central Control LG SAC

INTEGRATION DEVICE
Model Name PCHLLN000
ODU Evaporator status / Compressor status (Scroll, Screw,
Monitoring Points Centrifugal chiller only) / Condenser status /
Generator status (Abs. chiller only)
On / Off ○
Air cooled Water cooled HYDRO KIT IDUs Target Temp. setting ○
AC Manager 5 ACP 5 Mode Change Scroll chiller only
ACS IO Module
3rd party interlocking Schedule ○
Sensor Facility Interfaceable Products Scroll, Screw, Centrifugal, Absorption (LG Only)
PCHLLN000
※ ○ : Applied, - : Not Applied

AC Smart 5 Temp. CO2 Occupancy Cooling Emergency Valve


tower
Fan Cycle Display Example Installation Scene
Sensor • Chiller Option Kit installation of LG HVAC Solution product
...

should be conducted by a specialized installation service


Expansion engineer.
Control coverage
• Chiller Option Kit installation can be achieved with a SD Card.
Temp. Lighting
• The SD Card can install Chiller Option Kit in one LG HVAC
Solution product.
* DI : Digital Input, DO : Digital Output, UI : Universal Input, AO : Analog Output / Please contact our regional office to have connectable relay specification for analog output.

Insert the SD Card in the LG HVAC Solution product. If a backup


SD Card is inserted, replace it with a Chiller Option Kit SD Card.

146 / 147
CONTROL SOLUTIONS _ INTEGRATION DEVICE

DRY CONTACT
Connection between an indoor unit and external devices to control various functions. PDRYCB000
Model Name PDRYCB000 PDRYCB400 PDRYCB300 PDRYCB320 PDRYCB500 Contact Point Input
CN - CC Dry contact
Operation On / Off
Indoor Unit (Contact point linked with 3rd party)
NEW Status
PCB
Error Alarm
CN - CC

Case ○ ○ ○ ○ ○ Key Lighting Fire Alarm Timer Motion Door Check


Switch Sensor Detect Sensor Sensor
Input Port 1 2 8 8 - System Structure

Universal Input port - - - 1 -

Comm. Protocol - - - - Modbus RTU


PDRYCB400
Power AC 220V Connect to Indoor unit PCB (CN_CC)
2 inputs interworking
Contact Point Input 1
On / Off ○ ○ ○ ○ ○
Contact Point Input 2 CN - CC
Indoor Unit
PCB Operation On / Off
Oper Mode - ○ ○ ○ ○
Status
Error Alarm Window Sensor
Set Temp. - (Select & Fix) (Select & Fix) (Select & Fix) ○ CN - CC

Aircon Fan Speed - - ○ ○ ○


Card key
Thermo-Off - (Select & Fix) ○ ○ -

SOLUTIONS
CONTROL
Energy Saving - (Select & Fix) - - - Refrigerant leakage detection alarm

Lock/Unlock - (Select & Fix) - - -


CN - CC

On / Off ○ - ○ ○ - Leakage Alarm

DHW On / Off - - ○ ○ -
Control

INTEGRATION DEVICE
Thermo-Off - - ○ ○ - Card key Leakage Detector
AWHP
Oper Mode - - ○ ○ -

Silent Mode - - ○ ○ - PDRYCB300 / PDRYCB320


Emergency Mode - - ○ ○ - Target temperature setting (0 ~ 10V)
Operation On / Off CN - CC
On / Off ○ - - - ○ Thermo On / Off
Indoor Unit Operation Mode (Fan / Heat / Cool)
Oper Mode - - - - ○ PCB
Fan Speed (Low / Middle / High) Control Module
Vent Aircon Mode - - - - ○ Operation On / Off Status
CN - CC
Error Alarm
Additional Mode - - - - ○

Fan Speed - - - - ○
※ Please contact our regional office to have full compatible room controller list

Operation Status ○ ○ ○ ○ ○

Output Error ○ ○ ○ ○ ○
PDRYCB500 <Modbus Communication Function>
Room Temp. - - - - ○

※ ○ : Applied, - : Not Applied CN-CC


Note : 1. Compatibility of PDRYCB300 / PDRYCB320
- Can use with all types of aircon indoor units after 2010. (Cassette, Ducted, Convertible, Applied PAC, Wall mounted, Console)
- Can not use with Single package models. Indoor Unit Modbus Master Controller

...
- AWHP : 3 series split and monobloc models.

...
2. Compatibility of PDRYCB400 Max. 16 Indoor units per one
- Can use with all types of aircon indoor units after 2010. (Cassette, Ducted, Convertible, Applied PAC, Wall mounted, Console) Modbus master controller
- Can not use with single package models. One to one connection between
- Can not use with AWHP, Hydrokit models. dry contact and indoor unit
3. (Select & Fix) : This function is preset by rotary switch.
CN-CC

Indoor Unit

※ Please contact our regional office to check the compatibility with 3rd party room controller.

148 / 149
CONTROL SOLUTIONS _ INTEGRATION DEVICE

GROUP CONTROL WIRE LOW PROFILE REMOTE TEMPERATURE BUTTON SENSOR


Cables used to connect a wired remote controller up to 16 indoor units. Allows for easy and discreet installation as well as connection to an indoor unit.

Model Name PZCWRCG3 Model Name ZRTBS01


Y-type Cable 0.25m Length Operation Range -40 °C to 85 °C (0 to 100%RH, Non-condensing)

Long Cable 9.6m Length Sensing Element Thermistor


Sensing Element Accuracy 0.2 °C (0 to 70 °C)
Material Etched Teflon
Wire Leads Length 15m
Thickness 0.33mm2
Mounting 10mm hole, push in plastic sheath with peel off tape strip
PZCWRCG3 ZRTBS01 Enclosure Material Ratings Plastic, NEMA 1, UL94

Installation Scene Indoor 1 MAIN PCB

Indoor 1 Indoor 2 Indoor 3 Features & Benefits


Indoor terminal block Indoor terminal block Indoor terminal block
• Ideal for locations where aesthetics are as important as the temperature measurement.
RED (12V) • Inconspicuous wall sensor that mounts easily by pushing through a 10mm hole and secured with a peel off tape strip.
YL (SIGNAL) YL (SIGNAL)
YL (SIGNAL)
BK (GND) BK (GND)
BK (GND) • Small flush sensor mounting.
• Accurate direct air measurement.
• Paintable with latex or oil base.

Note : 1 Y type Cable assembly is for connecting indoor unit and long cable.
2 Long Cable assembly is for connecting indoor to indoor.
Key Application Models Applied
• LG indoor units excluding Wall-Mounted Type
Extension cable

SOLUTIONS
CONTROL
Control
box

REMOTE TEMPERATURE SENSOR

INTEGRATION DEVICE
Sensor for detecting the room temperature.
Wired Remote
Controller
Low Profile
Button Sensor

Installation Scene Drawing


Adhesive Ring

PQRSTA0
Main PCB 22.2mm

Features & Benefits Indoor Unit


9mm
1.6mm
• It detects the exact room temperature instead of indoor unit’s air temperature sensor.
15.2mm
• Applied to Ceiling Mounted Cassette, Ceiling Concealed Duct, THERMA V and HYDRO KIT.
• Extension cable (15m) is included.

Installation Scene Extension Cable Main PCB


CN-ROOM
1. Wire to the control box in the indoor unit by
removing the existing thermistor and connect Low Profile Remote
CN-ROOM Connector
Temperature Button Sensor
the extension cable its place.
Indoor Unit
2. Cut the extension cable to the appropriate
length and connect the screw terminal of the
Remote Wired Remote
remote sensor. Temperature Sensor Controller

150 / 151
CONTROL SOLUTIONS _ INTEGRATION DEVICE

ZONE CONTROLLER IO MODULE


Controls air conditioning in up to 4 zones by external thermostat. Interface module between system air conditioner’s outdoor unit and external device.

ROOM1 ROOM2 Models Applied


Indoor Unit
Thermostat Thermostat
(Duct Type) • MULTI V 5 • MULTI V WATER IV
• MULTI V S
Part Description

1) Digital Input Part (DI : Dry Contact Input)


• Demand control by contact input (3 Step)
ABZCA PVDSMN000 • Low Noise Operation input
• Priority Setting input : Setting the priority of demand control command
(Capacity control for external signal from DDC vs Peak control by LG
Features & Benefits Thermostat Thermostat
Features Central controller)
- Open : External signal has priority to central controller (Default)
• Controls different zones (up to 4 zones) by external Function - Close : Central controller has priority to external signal
Zone Control ROOM3 ROOM4
thermostat (AC 24V) sub PCB • Demand control
2) Analog Input Part (AI : DC 0 ~ 10V)
• Maintain proper air volume of each zone • Low noise operation
• Demand control by analog input (10 Step)
• Auto variation of dampers • Output outdoor or indoor unit operation status
• Auto control of fan speed and On / Off operation • Output error status 3) Digital Output Part (DO : AC 250V, Max. 1A)
• Error status relay output
• Operation status relay output
Description • Valve control
• IO Module is communication interface module for
connection between MULTI V 5 and external IO
Models Applied (Input / Output Module) devices.
• Ceiling Concealed Duct (Refer to Product Data Book for applicable models) Note : IO Module is not compatible for MULTI V III

SOLUTIONS
CONTROL
Key Application
Wiring Diagram Demand Control Low Noise Operation
Provides variable setting for demand control according to input method to To reduce noise level, control outdoor unit’s fan speed by dry contact input.
reduce power consumption. This function supports 2 types of input signal : AI
(0 ~ 10V, 10 Step) and contact signal (3 Step).

INTEGRATION DEVICE
Ceiling Concealed Duct
Max. 7 dB
1
(dB)
2
3 DDC DDC
CN - ZONE 4 IO Module (Direct Digital Controller) IO Module (Direct Digital Controller) Timer
5
6 Capacity
7 Control with Noise Level or
8 MULTI V WATER IV
or
Contact Signal
(3 Points / 3 Steps) Contact Signal
AC 24V
Range of Operation Rate
ROOM (External) Damper AI 0 ~ 10V : 0%, 40% ~ 100%
THERMOSTAT #1 Or Relay Contact signal (3 steps) : 0%, 40% ~ 80%
MULTI V 5

Zone controller MULTI V 5 ※ 8 HP (22.4kW) model, Sound power level can be changed by outdoor unit operation
ROOM Damper status and low noise operation input signal.
THERMOSTAT #2 Or Relay

ROOM Damper Refrigerant Leakage detection with Pump-down


THERMOSTAT #3 Or Relay
For safety, IO module close refrigerant valve when Pump-down operation.

ROOM Damper 2. Valve Close


THERMOSTAT #4 Or Relay Liquid Pipe

Gas Pipe

IO Module
3. Operation Stop 1. Sense the Gas
MULTI V 5
Alarm
Gas Gas
Sensor Sensor
Refrigerant

152 / 153
CONTROL SOLUTIONS _ INTEGRATION DEVICE

COOL / HEAT SELECTOR AHU KITS


Cooling only, heating only, and fan mode can be selected. A solution to connect LG’s high efficiency system to the DX coil of an air handling unit for the maximum energy savings.
NEW
COMMUNICATION KIT CONTROL KIT EEV KIT

PAHCMR000 PAHCMS000 PAHCMM000 PRLK048A0


PRDSBM
PRLK096A0
NEW
Features CONTROLLER MODULE NEW

• Indoor unit mode control without central controller


• Select operation mode : Cooling, Heating, Fan mode
• Mode lock for cooling & heating mixing error-proof during the change of season
PRLK396A0
Fan Mode Mode Change

PAHCMM000 PAHCMC000 NEW


Cooling Heating
only only +

PRLK594A0

SOLUTIONS
CONTROL
Specifications
Control Application Kit
Dimensions (mm) IP
Type Model Power Supply Description
W H D Rating
Return / Room air temperature control by DDC or LG

INTEGRATION DEVICE
PAHCMR000 300 300 155 1Ø, 220~240 V, 50/60 Hz IP66
Communication individual / centralized controller.
Kit Discharge air / Supply air temperature control by DDC
Models Applied PAHCMS000 380 300 155 1Ø, 220~240 V, 50/60 Hz IP66
or LG individual / centralized controller

• MULTI V 5 • MULTI V WATER II • MULTI V WATER IV PAHCMM000 162 90 61 DC 12V IP20 Main Controller module
Controller
• MULTI V IV • MULTI V S Module
PAHCMC000 108 90 61 DC 12V IP20 Communication Controller module
• MULTI V WATER S • MUL TI V PLUS II, MULTI V PLUS
Various AHU control functions with multiple DX coils
Control Kit PAHCNM000 500 500 210 1Ø, 220~240 V, 50/60 Hz
(Maximum connectable ODU is 3 units)

Wiring Diagram Expansion Application Kit


Dimensions (mm) Pipe Diameter (mm)
Type Model Capacity Index Range
W H D Liquid
<Outdoor Main PCB >
PRLK048A0 217 404 83 12.7 3.6 ~ 28 kW
Push Button
• Connect Terminals (1, 2, GND) on the back side of the outdoor dry PRLK096A0 217 404 83 12.7 28.1 ~ 56 kW
Insert wire method contact to terminals (1, 2, GND) of outdoor as shown below. EEV Kit
PRLK396A0 349.5 345.5 180 19.05 56.1 ~ 112 kW

PRLK594A0 409.5 345.5 180 19.05 112.1 ~ 168 kW


Push arrow direction

Insert wire to * Communication line length can be maximum 300m, use


Field wiring connector Communication line as thick 1.25mm.
Connected wiring

154 / 155
CONTROL SOLUTIONS _ INTEGRATION DEVICE

AHU KITS
Communication Kit Single Split Application (Communication Kit & Controller Module)
HIGH ENERGY EFFICIENCY Single Split + Return / Room Air Temperature Control
LG's DX AHU solutions' superior performance provides
a highly efficient heat source system. Temp. Sensors
Comm. Line
Central Comm. Line to ODU
• High energy efficiency inverter system Ref. Pipe
• Large range of expansion application Kit AHU MULTI V 5
TE = Evaporator Temperature
: Max. 168 kW EEV Kit 1) (Liquid Pipe / Gas Pipe)
• Connected to various heat sources TR = Return Air Temperature
TROOM = Room Air Temperature
: MULTI V, MULTI V WATER IV, MULTI V S, SINGLE SPLIT Control Option
TE
1) Maximum connectable EEV capacity for PAHCMR000, PAHCMC000 is 112 kW.
SINGLE SPLIT
MULTI V WATER IV MULTI V S SINGLE SPLIT Centralized Controller 1)

AHU DX Coil

TR

OR / AND
DIVERSE OPTIONS FOR CONTROL
AHU communication kit can be connected to various LG Controller DDC by Contact signal DDC by Modbus ROOM
control systems such as LG individual / central
controller and DDC 1). It can be directly connected to
DDC without separated controller, so DDC can receive TROOM PAHCMR000
DDC
Central Individual (Modbus or Contact signal)
product control and monitor information through Controller Controller DDC DDC

SOLUTIONS
contact signal or Modbus protocol.

CONTROL
AI / DI / DO
signal
• LG Individual / Central controller supported
- LG controller stand alone or combination with DDC Single Split + Discharge Air Temperature Control
• Direct wiring between DDC and AHU communication kit
- Embedded Digital I/O and Analog Input Temp. Sensors
- Modbus RTU protocol supported Comm. Line

INTEGRATION DEVICE
AHU Kit AHU Kit AHU Kit
Central Comm. Line to ODU
1) DDC : Direct Digital Controller
Ref. Pipe

TE = Evaporator Temperature
(Liquid Pipe / Gas Pipe)
TD = Discharge Air Temperature
TROOM = Room Air Temperature

EXPANDABLE SYSTEM DESIGN Control Option


TE
LG AHU system can be a suitable solution for
various sites due to its application flexibility and SINGLE SPLIT
Centralized Controller 1)
TD
wide range of line up with large capacity models.
AHU DX Coil
According to the required capacity, a single or multiple
module combination is possible due to the AHU
communication kit's modular design.
Discharge Air control Return Air control Return Air control Return Air control OR / AND
• Multiple module combination for large capacity AHU
ROOM

TROOM PAHCMS000
DDC
(Modbus or Contact signal 2))

1) PI485 (PMNFP14A1) is required for centralized controller.


2) In case of applying DDC with contact signal, discharge air temperature should be measured and controlled by DDC.
Note : For more detail, please refer to the PDB.

156 / 157
CONTROL SOLUTIONS _ INTEGRATION DEVICE

AHU KITS
MULTI V Application (Communication Kit & Controller Module)
MULTI V + EEV Kit + IDU + Return / Room Air Temperature Control MULTI V + EEV Kit + Discharge Air Temperature Control

Temp. Sensors Temp. Sensors


Comm. Line Comm. Line
Central Comm. Line to ODU Central Comm. Line to ODU
Ref. Pipe Ref. Pipe
TE = Evaporator Temperature Comm. Line between modules
(Liquid Pipe / Gas Pipe) TE = Evaporator Temperature
TR = Return Air Temperature (Liquid Pipe / Gas Pipe)
TROOM = Room Air Temperature TD = Discharge Air Temperature
TROOM = Room Air Temperature

EEV Kit 1) MULTI V

Control Option
TE
Control Option
MULTI V
Centralized Controller TE
AHU DX Coil
TD Centralized Controller

AHU DX Coil

SOLUTIONS
TR

CONTROL
OR / AND

OR / AND
ROOM

ROOM

INTEGRATION DEVICE
TROOM PAHCMR000
DDC
(Modbus or Contact signal)
OR
TROOM PAHCMS000
DDC
OR (Modbus or Contact signal 2))
PAHCMC000 +

PAHCMM000 PAHCMC000

1) Multiple EEV kits can be applicable with multiple DX Coils and PAHCMR000s. 1) Multiple EEV kits can be applicable with multiple DX Coils and PAHCMR000s.
2) In case of applying DDC with contact signal, discharge air temperature should be measured and controlled by DDC. 2) In case of applying DDC with contact signal, discharge air temperature should be measured and controlled by DDC.
Note : For more detail, please refer to the PDB. Note : For more detail, please refer to the PDB.

158 / 159
CONTROL SOLUTIONS _ INTEGRATION DEVICE

AHU KITS
Communication Kit Function Communication Kit Function
Communication with DDC via Contact Signal With LG Control system (Individual & Centralized Controller)
PAHCMS000 PAHCMS000
PAHCMR000 PAHCMR000
Function List (PAHCMM000 + Type Note Function List (PAHCMM000 Note
(PAHCMC000) (PAHCMC000)
PAHCMC000) +PAHCMC000)
Operation On / Off On / Off On / Off Digital Input (Non Voltage) - Operation On/Off On / Off On / Off -
Available operation mode can vary depending on Available operation mode can vary depending on
Operation Mode Cooling / Heating Cooling / Heating Digital Input (Non Voltage) Operation Mode Cooling / Heating / Fan Cooling / Heating / Fan
the settings of Communication Kit the settings of Communication Kit
Return (Room) Air Temperature 2) 16 ~ 30 °C - Analog Input (DC 0 ~ 10 V / 20mA) - Return (Room) Air Temperature 2) 16 ~ 30 °C - -
Control 1)
Discharge air temperature should be controller Standard II : 16 ~ 30 °C
Control 1) Discharge Air Temperature 2) - - -
directly by DDC using 'ODU Capacity Control Discharge Air Temperature 2) - 12 ~ 50 °C Standard III : 12 ~ 50 °C
Central Controllers : 12 ~ 50 °C
Fan Speed 3) - High / Middle / Low Digital Input (Non Voltage) -
To control the AHU fan, dip switch 1-3 'DO type' should be
Forced Thermal On / Off - Digital Input (Non Voltage) - Fan Speed 3) High / Mid / Low High / Mid / Low
set 'On (Fan Speed)' (PAHCMR000)
ODU Capacity - 40 ~ 100% Analog Input (DC 0 ~ 10 V / 20mA) -
Operation On / Off On / Off -
Emergency Stop - Stop / Normal Digital Input (Non Voltage) -
Operation Mode Cooling / Heating / Fan Cooling / Heating / Fan -
Digital Output For PACHMR000, dip sw1-3 DO Type should be ○ ○
Return (Room) Air Temperature -
Operation On / Off On / Off (Max. : DC 30 V / 1 A, set 'Off' (Status), In this case, 'fan speed' cannot
AC 250V / 1 A ) monitored by DO ports Discharge Air Temperature ○ -
Monitor
Operation Mode - - It needs to be checked through control signal Fan Speed High / Middle / Low High / Middle / Low -
Digital Output For PACHMR000, dip sw1-3 DO Type should be Defrost Operation On / Off On / Off Only with Individual Controller
Fan Speed High / Middle / Low High / Middle / Low (Max : DC 30 V / 1 A, set 'On' (Fan Mode) In this case, ‘On/Off, defrost,
AC 250V / 1 A ) error Status' cannot monitored by DO ports Error Alarm Error Code Error Code Error code will be displayed on the screen

Digital Output For PACHMR000, dip sw1-3 DO Type should be Compressor On/Off On / Off On / Off Only with Individual Controller
Monitor
Defrost Operation Defrost / Normal Defrost / Normal (Max. : DC 30 V / 1 A, set ‘Off' (Status), In this case, 'fan speed' cannot
AC 250V / 1 A ) monitored by DO ports ※ ○ : Applied, - : Not Applied
1) Control functions for LG individual and central controller are not available in case of using together with DDC via contact signal.
Digital Output, Relay C contact For PACHMR000, dip sw1-3 DO Type should be 2) The range of setting temperature is different depending on the type of the controllers. And operation may different from setting range.
Error Alarm Error / Normal Error / Normal (Max. : DC 30 V / 1 A, set 'Off' (Status), In this case, 'fan speed' cannot 3) To control fan speeds, DO port of the fan speed status should be connected to the fan control panel.
AC 250V / 1 A ) monitored by DO ports Note : For more detail information, please refer to the product data book.
Digital Output,
Compressor On / Off - On / Off (Max. : DC 30 V / 1 A, -

SOLUTIONS
AC 250V / 1 A )

CONTROL
1) Control functions for LG individual and central controller are not available in case of using together with DDC via contact signal.
2) The range of temp. is differ depending on the type of the controller. Compatibility with LG HVAC Controllers
3) To control fan speeds, DO port of the fan speed status should be connected to the fan control panel.
Note : For more detail information, please refer to the product data book. BMS
Individual Controller Centralized Controller PDI
Gateway
AC Premium
Premium Standard III Standard II AC Ez AC Ez Touch AC Smart 5 ACP 5 Manager 5 1) ACP Lonworks Standard
Controller

INTEGRATION DEVICE
Communication with DDC via Modbus protocol
PAHCMS000
PAHCMR000
Function List (PAHCMM000 Note
(PAHCMC000) +PAHCMC000)
PREMTA000
Operation On/Off On / Off On / Off PREMTB100 PQNUD1S40
Model no. PREMTA000A PREMTB001 PQCSZ250S0 PACEZA000 PACS5A000 PACP5A000 PACM5A000 PLNWKB000
PREMTBB10 PPWRDB000
Operation Mode Cooling / Heating / Fan Cooling / Heating / Fan PREMTA000B
Return (Room) Air Temperature 16 ~ 30 °C - PAHCMR000 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
Discharge Air Temperature 2) - 12 ~ 50 °C Dip SW1-2 Discharge Temp. Control Type should be set 'On' PAHCMS000 - ○ ○ - - ○ ○ ○ - -
Control 1)
Fan Speed 3) High / Middle / Low -
※ ○ : Applied, - : Not Applied
Forced Thermal On/Off - - 1) AC Manager 5 is an integrator, so the installation with AC Smart 5 or ACP 5 is required.
ODU Capacity Control 2) - 40 ~ 100% Dip SW1-2 Discharge Temp. Control Type should be set 'On' Note : 1. Dry contact for indoor unit (PDRYCB000 / 400 / 300 / 500) is not applied.
2. For more details, please refer to the product data book.
Emergency Stop - -
Operation On / Off On / Off
Operation Mode Cooling / Heating / Fan Cooling / Heating / Fan
Return (Room) Air Temperature ○ - Corresponding air temperature sensor connected to AHU
Discharge Air Temperature - ○ Comm. Kit is required
Monitor
Fan Speed High / Middle / Low High / Middle / Low
Defrost Operation Defrost/Normal Defrost/Normal
Error Alarm Error / Normal, Error code Error / Normal, Error code
Compressor On / Off On / Off On / Off

※ ○ : Applied, - : Not Applied


1) Control functions for LG individual and central controller are not available in case of using together with DDC via contact signal.
2) In case of PAHCMS000, control type between “Discharge Air Temperature” and “ODU Capacity Control” is selectable.
3) To control fan speeds, DO port of the fan speed status should be connected to the fan control panel.
Note : For the Modbus memory map and more detail information, please refer to the product data book.

160 / 161
CONTROL SOLUTIONS _ APPLICATION

HOTEL SHOPPING MALL


Hotel Control Solution Shopping Mall Control Solution

Guest Room Retail


Air conditioner automatically switches Proportionally distribute and manage
off when guests depart the power consumption by tenants
Dry contact PDI

Integrated control of air conditioner Real-time system issue detection


with the hotel room controller and alert Central controller
Dry contact (Operation trend)

Air conditioner can be controlled with


existing hotel thermostat Dry contact Maintenance Office
For thermostat

Reduces energy by checking


Prioritizes guest safety with refrigerant operational trends Central controller
(Operation trend)
leak detection Refrigerant
Leak detector

Lobby Atrium
Integrated management of AHU applied
Air conditioner control in conjunction
to large spaces
with check-in or check out AC Smart 5 Comm. Kit
(Schedule)

Public Areas Chiller and VRF integrated control


Central controller
(Operation trend) Chiller option kit
Centralized management

SOLUTIONS
of the public areas

CONTROL
AC Smart 5
(Schedule)

Design Proposal Design Proposal


Guest Room Lobby / Public Areas Retail Maintenance Office Atrium

APPLICATION
The air conditioner Integrated control of Control with existing Guest safety is Air conditioner control Proportionally distribute Fast problem detection Reduces energy Integrated Chiller and VRF
automatically turns off air conditioner with the hotel thermostat the first priority in conjunction with and manage power and alarms by checking management of AHU integrated control
when guests leave hotel room controller check-in or check out consumption by the tenant operational trends applied to large spaces
WHM
(Watt-Hour Meter) Chiller option
Error C store
Pulse signal kit (S/W)
Over
24°C Cooling

21°C
ACP 5

Power PDI
100 kWh

PDRYCB400 PDRYCB500 PDRYCB300 PRLDNVS0 PACS5A000 PPWRDB000 PACS5A000 PAHCMR000 PCHLLN000


2 contact point Modbus RTU (9,600bps) NEW PDRYCB320 Refrigerant leakage detector AC Smart 5 PDI Standard (2 port) AC Smart 5 AHU Comm. Kit Chiller option kit
8 contact point
Input Function • 6,000ppm • BMS Integration • Max. 128 IDU • BMS Integration • Return air
• Operation On / Off • Operation Input (BACnet IP, Modbus TCP) (BACnet IP, Modbus TCP)
• Indoor temperature • Universal Input
Output • Error alarm • Operation On / Off
• Operation On / Off status • Set run mode • Thermo On / Off PACP5A000 PACS5A000
• Error alarm • Set temperature • Operation mode ACP 5 AC Smart 5
• Set fan speed (Fan / Heat / Cool)
• Fan speed
(Low / Middle / High)
PREMTB100 PACP5A000 PQNUD1S40 PACP5A000 PAHCMS000
Wired remote controller ACP 5 PDI Premium (8 port) ACP 5 AHU Comm. Kit
Output
• Operation On / Off status • 4.3 inch color LCD • BMS Integration • Max. 128 IDU • BMS Integration • Discharge air
• Error alarm • Touch button (BACnet IP, Modbus TCP) (BACnet IP, Modbus TCP)

162 / 163
CONTROL SOLUTIONS _ APPLICATION

HOSPITAL ACADEMIC INSTITUTION


Hospital Control Solution Academic Institution Control Solution

Hospital Ward Class Room


Automatically save energy in the
Proper airflow management for patients absence of students Wired remote
Wired remote controller
controller

Central controls prevent students from


Monitor the comfort level for each
arbitrary control
hospital ward Central controller
Central controller
(Lock)
(Comport level)

Lecture Hall
Control fan speed and air volume
Dry contact
Schedule management according to
academic plan Central controller
(Schedule)

Service Zone
Energy savings based on flexible Maintenance Office
scheduling Central controller Integrated management of distributed
(Schedule)
buildings Central controller
(Multiple management)

Lobby
Centralized management of AHU for Centralized management with multiple
large spaces interfaces Central controller
(HTML5)
Comm. Kit

SOLUTIONS
CONTROL
Design Proposal Design Proposal
Hospital Ward Service Zone Lobby Class Room Lecture Hall Maintenance Office

APPLICATION
Proper airflow Monitor the comfort level External device Energy savings based on Centralized management Automatically save Central controls Schedule management Integrated management Centralized management
management for patients for each hospital ward interlock control flexible scheduling of AHU for large space energy in the absence prevent students from according to academic plan of distributed buildings with multiple interfaces
of students arbitrary control

Relay

PTVSMA0 PACS5A000 PDRYCB400 PACS5A000 PAHCMR000 PTVSMA0


Human detection sensor AC Smart 5 2 contact point AC Smart 5 AHU Comm. Kit Human detection sensor

• BMS Integration Input • BMS Integration • Return air


(BACnet IP, Modbus TCP) • Operation On / Off (BACnet IP, Modbus TCP)

Output PACS5A000 PACP5A000 PACM5A000


• Operation On / Off status AC Smart 5 ACP 5 AC Manager 5
• Error alarm
• BMS Integration • BMS Integration
(BACnet IP, Modbus TCP) (BACnet IP, Modbus TCP)
PREMTB100 PACP5A000 PACP5A000 PAHCMS000 PREMTB100
Wired remote controller ACP 5 ACP 5 AHU Comm. Kit Wired remote controller

• 4.3 inch color LCD • BMS Integration • BMS Integration • Discharge air • 4.3 inch color LCD
• Touch button (BACnet IP, Modbus TCP) (BACnet IP, Modbus TCP) • Touch button

164 / 165
CONTROL SOLUTIONS _ APPLICATION

OFFICE RESIDENTIAL
Office Control Solution Residential Control Solution

Maintenance 0ffice
Energy savings and management
throughout the building Central controller
Home
(Energy Navi.)
Anytime, anywhere air conditioner
control and access
Integrated management of HVAC with Wi-Fi Modem

BMS system Central controller


(BMS Gateway)
Integrate systems
for smart connectivity throughout
Modbus RTU
Reduce costs by replacing BMS
Central controller
(Operation trend) ACS IO Module

Office Room Bed Room


Reasonable power distribution to
Use a familiar residential thermostat
tenants Dry contact
PDI For thermostat

Server Room Simple interlocking control by remote


control Wired remote
controller
24-hour backup management
Central controller
(Backup operation)
Apartment / Residence
Meeting Room
Stable system operation
Independent
Energy savings based on occupancy power module

SOLUTIONS
detection

CONTROL
Wired remote
controller

Design Proposal Design Proposal


Maintenance Office Office Room Server Room Meeting Room Home Bed Room Apartment

APPLICATION
Energy savings Integrated Reduce costs by Reasonable power Main equipment Energy savings Control your home air Build a Smart house Use a familiar residential Simple interlocking Stable system
and management management of HVAC replacing BMS distribution to tenants 24 hours back up based on occupancy conditioner anytime, thermostat control by remote control operation when indoor
throughout the building with BMS system management detection anywhere unit power is lost

WHM Human
BMS Protocol Pump Lighting Fan Sensor (Watt-Hour Meter) detection
Pulse signal sensor

Target Error Lighting

Power PDI A B
Fan
BMS System 100 kWh
Forecasting

Radiator

PACS5A000 PLNWKB000 PEXPMB000 PPWRDB000 PACS5A000 PTVSMA0 PWFMDD200 PDRYCB500 PDRYCB300 PREMTB100 PRIP0
AC Smart 5 LonWorks gateway ACS IO Module PDI Standard (2 port) AC Smart 5 Human detection sensor LG Wi-Fi modem Modbus RTU (9,600bps) NEW PDRYCB320 Wired remote controller Independent power module
8 contact point
• BMS Integration • Max. 128 IDU • BMS Integration Function Function • 4.3 inch color LCD • EEV full close function
(BACnet IP, Modbus TCP) (BACnet IP, Modbus TCP) • On / Off • Operation Input • Touch button
• Fan speed • Indoor temperature • Universal Input
• Operation mode • Error alarm • Operation On / Off
• Vane control • Set operation mode • Thermo On / Off
• Reservation • Set temperature • Operation mode
(Sleep, Weekly On / Off) • Set fan speed (Fan / Heat / Cool)
• Error check • Fan speed
PACP5A000 PMBUSB00A PEXPM300 PQNUD1S40 PACP5A000 PREMTB100 (Low / Middle / High)
ACP 5 Modbus RTU gateway PEXPM200 PDI Premium (8 port) ACP 5 Wired remote controller
PEXPM100 Output
• BMS Integration • Max. 128 IDU • BMS Integration • 4.3 inch color LCD • Operation On / Off status
ACU IO Module
(BACnet IP, Modbus TCP) (BACnet IP, Modbus TCP) • Touch button • Error alarm

166 / 167
ACCESSORIES

MECHANICAL ACCESSORIES

PIPING ACCESSORIES

ACCESSORIES
168 / 169
ACCESSORIES _ MECHANICAL ACCESSORIES

CASSETTE PANEL DUAL VANE CASSETTE PANEL


The Independent Vane Operation makes desired and comfortable air flow. Model Name
PT-AAGW0
Model Name & Applied Products PT-AEGW0
PT-AFGW0
4 Way Cassette 1 Way Cassette (1,100 x 34 x 500) * Air Purifying Kit
(Mini) PT-QCHW0 (Standard) PT-UAHW0 (1 Way) PTAHTP0 Available from ‘Oct 2020
(Standard) PT-MCGW0 (Air purification) PT-UPHG0 (4 Way) PTAHMP0
(Air purification) PT-MPGW0 Key Features
1 Way Cassette (1,420 x 34 x 500) * Human detection Sensor
Function
2 Way Cassette (Standard) PT-TAHW0 (4 Way) PTVSMA0 Model Floor Temperature Human detection
Dual Vane Wi-Fi Air Purification Elevating Grille
(Standard) PT-USC (Air purification) PT-TPHG0 Sensor sensor
○ Optional X X X Optional
PT-AAGW0
PT-AEGW0 ○ Optional X X ○ Optional
PT-AFGW0
○ Optional ○ Optional X Optional

Specification
PT-QCHW0 PT-MCGW0 PT-MPGW0 PT-USC Suction Color Weight Dimension (mm)
Model Gloss
Type (RAL) (kg) W H D
Grid White (RAL 9003) - 7.1 950 35 950
PT-AAGW0
PT-AEGW0 Grid White (RAL 9003) - 8.5 950 35 950
PT-AFGW0
Grid White (RAL 9003) - 7.5 950 35 950

PT-UAHW0 PT-UPHG0 PT-TAHW0 PT-TPHG0


Air Purification Kit
Key Features Dielectric
Dust collecting filter
Photocatalytic
Deodorizing filter HVPS

• Independent vane operation uses separate motors, making it Possible to control all 1, 2, and 4 vanes independently. Model Image Model name
• The detachable corner design makes it easy to adjust the hanger during installation and to check for leakages in the drain
pipe and refrigerant pipes. Cassette cover installation manual
* Air purifying panel can be used with air purifying kit together for 1 Way, 4 Way panel. Follow the details to install the external cover correctly.
* Human detecting sensor can be used with human detecting sensor for 4 Way panel. Air purification kit • Read the installation manual carefully before installing the cover.PTAHMP0 ○ ○ ○
• To prevent the exterior of the cover from being scratched or become dirty during the

ACCESSORIES
assembly, always put a clean sheet on the floor.
• Always use the screw included in the product. This product is composed of the following components.
(If you use other screws, it can damage the product.)

Compact and Stylish Design The purpose of this external cover is to prevent the
indoor unit from being exposed externally.

Cassette cover installation manual


• Use this when install the cassette air conditioner on the ceiling without any finishing.

• New 4 Way cassette panel adapted unibody shape and matching with into the ceiling. Ceiling Ceiling
8mm

• Panel size is fit into the ceiling tile.


8mm
Indoor unit Indoor unit 266mm
308mm

TM model TN model Follow the details to install the external cover correctly.

CASSETTE COVER 50mm


Ceiling

Indoor unit
266mm
• Read the installation manual carefully before installing the cover.
• To prevent the exterior of the cover from being scratched or become dirty during the
assembly, always put a clean sheet on the floor.
• Always use the screw included in the product. This product is composed of the followin

MECHANICAL ACCESSORIES
TP model (If you use other screws, it can damage the product.)
Unibody
Shape Cassette cover
Cover in case of exposed cassette installation. installation manual
The characteristics of this external cover are as follows.
The purpose of this external cover is to prevent the
1. The height of the cover can be adjusted according to the height of the product.

(No Inlet Line)


(Refer to top picture)
2. Cover on the piping side can be detached. indoor unit from being exposed externally.
Follow the details to install the external cover
• Use this when correctly.
install
Model Name
the cassette air conditioner on the ceiling without any finishing.
• Read the installation manual carefully before installing the cover.
• To prevent the exterior of the cover from being scratched or becomeCeiling
dirty during the
PTDCM / PTDCQ 8mm
Ceiling
assembly, always put a clean sheet on the floor. 8mm
• Always use the screw included in the product.
Indoor unit 308mm This product
Indoor unit
is composed
266mm
of the following components.
(If you use other screws, it can damage the product.)

Cassette
Cassette Thecover cover
purpose installation
of thisinstallation
external cover manual
ismanual
Applied Products
Detach function

to prevent the
TM model

Ceiling
TN model

indoor unit from being exposed externally. 50mm

Cassette
Cassette • Usecover cover
this when install installation
installation
the cassette manual
air conditioner on manual
the ceiling
4 Way Cassette (for chassis TP, TN, TM, TQ, TR)
without any finishing. Indoor unit
266mm

Follow the details to install the external cover correctly.


Follow the details to install the external cover correctly. P/No.:3828A20128R

Key Features • Read the installation manual carefully before installing the cover.

Follow
• Read the installation manual carefully before installing
• To prevent the exterior of the cover from 8mm
Follow
assembly,the
• To prevent the
details details
the exteriortosheet to
ofinstall
the
on thethe
cover
the cover.
Ceiling
being scratched or become dirty during the
install thescratched
external cover
floor. external cover correctly.
from being or become dirtycorrectly.
during the
8mm
TPCeiling
model

The characteristics Included Parts


of this
266mm external cover are as follows.

Specification Read •the


• Always
• Specially designed for indoor unit
• (If
To you
Read
use
always put a clean
assembly, always put a clean sheet on the floor. Indoor unit
thescrew
the installation
installation manual
included manual
in thecarefully
carefully product.
• Always use the screw included in the product.
• use
To
prevent other
prevent
the screws,
the
exterior of itthe
exteriorcan damage
of
cover thefrom the
cover
before installing
before installing
product.)
from
being being scratched
scratched or
the cover.
the cover.
or
become become
dirty dirty
during
308mm

during
the the (Refer toTN
Indoor unit
This This
1. The height of the
product
topmodel
picture)
is composed
cover product is according
can be adjusted composed of the offollowing
the
to the height
components.
of thefollowing
product. components.
assembly,
(If you use other screws, it can damage the product.)
assembly,
always always put asheet
put a clean cleanon sheet on the floor.
the floor.
TM model
• Cover A, Cover B • Screws
• Covers the side area of cassette • Always
use theuse theincluded
screw included in the product. Ceiling This This product is composed
2. Cover on the piping side can be detached.
product is composed of the offollowing
the following components.
components.
Dimension (mm) Applied Model Capacity (kW)* The
• Always
purpose
(If youThe
of
screw
purpose this
it of
external
in the product.
can this
it canexternal cover is to is
cover prevent
to prevent the the
Suction Color (If you
use usescrews,
other other screws, damage damage the product.)
the product.) • Cover C, Cover D • Installation Manual
Gloss Weight
50mm
Model Type (RAL) (kg) W H D
Single Split MULTI Split MULTI V • Gives elegantindoor
looks unit from
indoor unit from beingbeingexposed exposed externally.
externally.
Indoor unit
266mm

R32 R410A R32 R410A R410A The The


purpose
• Use this purpose
when oftheexternal
ofinstall
this this
install the cassette
• Use this when external
air cover
air conditioner
cassette
on cover
the ceilingis
isonto
conditioner to prevent
theprevent
without
ceiling
any finishing.the
the
without any finishing.
• Light weightindoor indoor unit from
unitCeiling
from beingbeingexposed exposed externally.
externally.
TP model
Ceiling
PT-QCHW0 Grill Morning Fog (RAL 9001) - 3.0 620 35 620 2.5 ~ 5.0 2.5 ~ 5.0 1.5 ~ 5.3 1.5 ~ 5.3 1.6 ~ 6.2 • Use thisinstallCeiling
whenthe
install the cassette air conditioner on the without
ceiling without
Ceiling
any finishing.
The characteristics of this external cover are as follows.
8mm
8mm• Use this when cassette air conditioner on the
8mmceiling any finishing.
8mm 266mm
Indoor unit 308mm Indoor unit 266mm
Indoor unit Indoor unit
PT-MCHW0 Grill Morning Fog (RAL 9001) - 6.3 950 35 950 6.8 ~ 14.6 6.8 ~ 14.6 6.7 - 7.1 ~ 15.8 Ceiling Ceiling
308mm
1. The height of the cover canCeiling
Ceiling
be adjusted according to the height of the product.
4 Way
PT-UQC Grill Morning Fog (RAL 9001) - 3.0 700 22 700 2.5 ~ 5.0 2.5 ~ 5.0 - 1.5 ~ 5.3 1.6 ~ 6.2 Specification 8mm 8mm TM model
TMIndoor
model
Indoor unit unit 308mm
2.
(Refer to
8mm top picture)
8mm
TN model
Cover on the piping
308mm sideTN
Indoor can
unit
model
be unit
Indoor detached.266mm 266mm Detach function
Ceiling
Ceiling
PT-UQC Grill Morning Fog (RAL 9001) - 5.6 950 25 950 6.8 ~ 14.6 6.8 ~ 14.6 - 6.7 7.1 ~ 15.8 50mm TM model
TM model TN model
TN model
50mm
Weight
266mm (kg) Dimensions (mm) Cover A (4 units) Cover B (4 units) Screw (32 units)
2 Way PT-USC Grill Morning Fog (RAL 9001) - 4.7 1,100 28 690 - - - - 2.8 ~ 7.1 Indoor unitCeiling 266mm
Model Front Panel
Ceiling
Indoor unit
50mm 50mm
TP model
NET Gross W H D
PT-UUC Grill Noble White (RAL 9003) ○ 4.6 1,100 34 500 - - - - 2.2 ~ 3.6 TP model
Indoor unit
266mm 266mm
Indoor unit
TP / TN of this
The characteristics
PT-UMC / characteristics 5.9external 8.8cover1,157 are as 1,157
follows. 268
PT-UUC1 Grill Noble White (RAL 9003) - 4.4 1,100 34 500 - - 2.6 ~ 3.5 2.6 ~ 3.5 - PTDCM The of this external cover are as follows.
PT-UMC1 theTP
1. The heightTPofmodel model
cover can be adjusted according to the height of the product.
1. The heightTMof the cover can 5.9 8.8 to the
be adjusted according 1,157
height of the1,157
product. 310
1 Way PT-UTC Grill Noble White (RAL 9003) ○ 5.5 1,420 34 500 - - - - 5.6 ~ 7.1 (Refer to top picture)
The The
2. Cover
characteristics
characteristics
on the piping side can of
(Refer to top picture) of external
this this external
be detached. covercover are
are as as follows.
follows. Detach function
2. Cover on the piping side can be detached.
TR 5.0 7.2 907 907 268
PT-UUD Panel Noble White (RAL 9003) ○ 4.6 1,100 34 500 - - - - 2.2 ~ 3.6 1. Theof
1. The height height of thecan
the cover cover
be can be adjusted
adjusted according
according to theof
to the height height of the product.
the product.
PTDCQ PT-UQC (Refer
(Refer to to top picture)
top picture)
PT-UTD Panel Noble White (RAL 9003) ○ 5.5 1,420 34 500 - - - - 5.6 ~ 7.1 2.on
2. Cover Cover
the pipingTQ
on theside
piping
canside
be can 5.0
be detached.
detached. 7.2 907 907 310 Cover C (4 units) Cover D (4 units) Installation Manual
P/No.:3828A20128R
* Based on cooling capacity ※ ○ : Applied, - : Not applied
170 / 171

Detach function
Detach function
ACCESSORIES _ MECHANICAL ACCESSORIES

CO2 SENSOR REFRIGERANT LEAKAGE DETECTOR


CO2 sensor in ventilation system. R410A refrigerant leakage detector ensures room safety.

Model Name Model Name


AHCS100H0 PRLDNVS0

Applied Products Applied Products


LZ-H025GBA4 MULTI V 5
LZ-H035GBA5 / LZ-H050GBA5 MULTI V IV Heat Pump & Heat Recovery
LZ-H080GBA5 / LZ-H100GBA5 MULTI V WATER IV
LZ-H150GBA5 / LZ-H200GBA5

Applicable Products Key Features Specification


LZ-H050GXN0 / LZ-H080GXN0 • This detector senses refrigerant leakage when the Parts Specification

LZ-H100GXN0 / LZ-H050GXH0 refrigerant concentration exceeds 6,000ppm. Rated Voltage (V) DC 5.0 5%
Dimensions (W x H x D, mm) 31 x 44 x 20
LZ-H080GXH0 / LZ-H100GXH0 (The green and red LED lights blink simultaneously.) Weight (g) 22
• Alarm is “on” when refrigerant leaks out more than Detectable Refrigerant R410A
Sensor
6,000ppm for 5 seconds. If it is reduced less than Detected Concentration (ppm) 0 / 6,000 Alarm Off / On
Key Features 6,000ppm for 5 seconds, alarm is “off”.
Operating Temperature Range (°C) -10 ~ 50
Preserved Temperature Range (°C) -40 ~ 60
Specification Dimensions (Unit : mm) • When the alarm of the refrigerant leak detector is switched Average Power Consumption (mA) 35
Connecting
• Applied Model : ERV (Embedded), ERV DX (Option) 69 26.4 on the user must ventilate the room until the alarm is Cable Cable Length (m) 10
Sensor Dimensions of Front Plate (W x H x D, mm) 80 x 110 x 44.6
• Supply voltage : DV12V 5% disabled. Protective
Cover Dimension of Back Plate (W x H x D, mm) 80 x 110 x 6.5
• Output : 0.6 ~ 4.4V (Linear output, 240 ~ 1,760 ppm CO2) • The detector has to be installed inside the room and it
※ This function available for ARU****L**5 and 4 (MULTI V 5, MULTI V IV H/P, H/R model)
• Accuracy : 10% (2 days after installation)
50

should be installed 300 ~ 500mm above the floor.


Description
• The product is especially designed to detect CO2.
Included Parts
• This model requires Standard III Wired Remote Controller for display.

Key Application

ACCESSORIES
CO2 (ppm)

Sensor Connecting Cable Sensor Protective Cover


Windows Windows Windows Windows
Closed Open Closed Open
2,500

CO2 Sensor (AHCS100H0)


Without ERV Key Application

MECHANICAL ACCESSORIES
Embedded inside of ERV With ERV
1,000 Refrigerant Leakage Detector has three application methods.
Standard III Wired
Remote Controller 0
ERV with CO2 Concentration Control Case 1) Case 2) Case 3)
Time (min) Stop Operating Main Pipe Closing & Branch Pipe Closing &
(System Termination) Pump Down Continuous Operating

How to Install
1. Remove a screw on the service cover. Pull the service cover fixing bracket(①), then remove the service cover(②). Remove two elements(③) and two air filters(④). Room 1 Room 2 Room 1 Room 2 Room 1 Room 2

2. Install the sensor with two screws.


3. Remove a screw, then remove the right side of element rail(⑤).
4. Press the holder(⑥) into the hole to fix the CO2 sensor cable(⑦).
5. Connect the wire terminal to the CN-CO2 port of PCB. Room 3 Room 4 Room 3 Room 4 Room 3 Room 4

※ Airflow can be controlled by concentration of CO2, after setting automatic operation mode at remote controller.
※ Use the screwdriver whose total length is less than 250mm. Accessory Specification (To realize the case 2 application)

Screw1 Screw2 [Optional / Field Supply]


I/O Module PRLDNVS0 [Optional / Field Supply] PDRYCB400 Buzzer alarm [Field Supply] Central Control Devices
PVDSMN000 (Refrigerant Automatic (Dry contact) for central control room Buzzer alarm for room
leak detector) Ball Valve1) (Direct connection ~ DC 30V, ~ 1A)
Screw ※ Necessary accessory 1) Please contact to subsidiary to get

1 2 3 4 5 6 the recommended specification.


(LG Electronic don’t provide this accessory)

172 / 173
ACCESSORIES _ MECHANICAL ACCESSORIES

EEV KIT (FOR INDOOR UNIT) IR RECEIVER


MULTI V EEV KIT is specially designed to reduce noise and make comfort environment. IR RECEIVER can be connected to ceiling concealed duct and floor standing unit which the customer wants to control
by wireless remote controller.
Model Name Model Name
PRGK024A0 PWLRVN000

Applied Products
Applied Products
Indoor Unit Model Chassis Applicable
1 Way Cassette TU ○ MULTI V Indoors (Ceiling Concealed Duct, Floor Standing Units)
TT N/A
2 Way Cassette
TS ○ (~5.6kW)
TR ○
Cassette
TQ ○ (~4.5kW)
Key Features 4 Way Cassette TP N/A Key Features
TN N/A
• Decreasing noise level of MULTI V Indoor units and easy TM - • Designed for wireless control.
installation. BG - • Indication lamps (3 colors) and Self-diagnosis function.
High Sensible BR -
B8 -
High Static B8 -
M1 ○ (~5.6kW)
Duct
Middle Static M2
M3
-
-
Key Application
L1 ○
Low Static L2 -
Note : Do not install both the IR Receiver and Wired Remote Controller. This may cause malfunctions.
L3 -
CE ○
Floor Standing
CF -
Convertible VE ○
V1 -
Ceiling Suspended
V2 -
SJ ○
Etc
Wall Mounted SK ○
SV -
Art Cool SF ○
Console QA ○ Wired Remote
K2 - Controller IR Receiver
HYDRO KIT
K3 -
※ ○ : Applied, - : Not applied, N/A : Not Applicable

Key Application

ACCESSORIES
Wireless Remote
Pipe EEV Kit can be applied for the space which requires quiet Controller
Wire environment and noise sensitive space. (Standard)
Refrigerant flow (Cooling)
Refrigerant flow (Heating)
Outdoor Unit
Operation of Indication Lamps Test Run Mode
① Emergency Operation button : After installing the product, you must run a
C / Box EEV
Turns the indoor unit on or off when Test Run mode. Press the Emergency Operation

MECHANICAL ACCESSORIES
Kit
remote controller is not working. button for 5 seconds, until the LED flickers.
Luxury Hotel Villa ② Signal Detector : Then the indoor unit, duct runs cooling mode
Indoor Unit Receives the signal from remote controller. for 18 minutes, where the setting temperature is
③ Timer lamp (Green) : 18°C and the fan speed is high.
Lights up during the timer operation.
Indoor Unit EEV Kit Outdoor Unit
Indoor Heat Exchanger
④ Hotstart lamp (Orange) :
Electronic
Expansion Valve
Lights up during the pre-heating operation,
Fan M
defrost operation as well as latent heat
COMP 6 5 removal operation in heat mode. Available
M Fan Executive office Meeting room
Heat Exchanger
4 3 only for the heat pump models, not cooling
Note : If you don’t use EEV of same specification, Cooling (Heating) capacity could be decreased. only models.
2 1
⑤ System On / Off lamp (Red) :
Lights up during system controller
Signal Receiver operation.
⑥ Filter Sign lamp (Green) :
How to Install Lights up after 2,400 hours from the time
of first power on operation.
Open Indoor unit’s control box cover.
① Open fully indoor unit’s EEV through vacuum mode of ODU setting. Indoor Unit
② Detach the Indoor unit’s EEV connector from PCB and then push the reset C/Box
button of Outdoor unit’s PCB.
③ After connecting indoor unit’s EEV CONNECTOR, repeat the process Existing
① & ②. Then, connect the EEV CONNECTOR of EEV KIT in PCB of indoor unit. EEV
④ Finally connect the lead wire of the EEV Kit to the indoor unit’s PCB. KIT
EEV
⑤ Assemble the control box cover.
CN-EEV

174 / 175
ACCESSORIES _ MECHANICAL ACCESSORIES

INDEPENDENT POWER MODULE AUXILIARY HEATER RELAY KIT


It closes EEV in indoor unit when power cut. Providing an efficient way to add auxiliary heat.

Model Name Model Name


PRIP0 PRARS1

Applied Products Applied Products


MULTI V Indoor Units Wall Mounted, Art Cool Mirror, Art Cool Gallery

Model Name
Key Features PRARH1
• Independent Power Module is specially designed to close the Indoor EEV when power cut-off.
- Supply Voltage : DC 12V 50% Key Features Applied Products
- Provides two stages of auxiliary heat for indoor unit. 1, 2, 4 Way Ceiling Cassette, High Static Ducted,
- Provides ability to use the two stage auxiliary heater as Low Static Ducted, Ceiling Suspended
IncludedIncluded
Items
Included
ItemsItems
the primary or secondary heating source.
Included Parts Key Application
Model PRIP0 (Others) If the EEV is opened due to power cut off, liquid refrigerant
2. Included
2. 2.
IncludedItems
Included
Included Items
Items
Parts
Included Items
Key Application
Electrical Wiring

2. Included Items

ENGLISH

ENGLISH
ENGLISH
• Harness 1 (1m)
Item
Independent
Screw
Clamp
• Harness 2 (1m)
flows into compressor. It could damage the compressor in Model ModelModel Model PRARH1 PRARH1
PRARH1
PRARH1 3 rdParty Scope
3 rd
Party Scope
(Tie Wrap)

ENGLISH
Power Kit cooling mode. Also condensing might be happened for unclosed
• Harness 3 (1m) PRARH1
Item Auxliary
Item Heater
Item Auxliary Relay
Auxliary
Model
Heater
Item Kit
Heater
Relay Kit Screw
Relay
Auxiliary Kit ScrewScrew
Heater Insulation
Screw InsulationInstallation
Insulation
Insulation Manual
Installation
Installation
Installation ManualManual
Q'ty 1 2 4 • Installation Manual EEV’s indoor unit due to flow of refrigerant. Q·ty Q · t y 1 Item 1
Relay Kit
Auxliary Heater 2
Relay Kit 2 2
Screw 2
Insulation
Manual
1Installation 1
• Insulation (PE) Q·ty 1 2 2 1 Manual RADIATOR
RADIATOR
Q·ty
Q'ty 11 2 2 2 2 1 1
IncludedIncluded Items Items
ItemsIncluded
Electricity Cut-off EEV Valve
Hot Water

2. Included Items
Close Hot Water

2. Included
2. Included
Figure FigureFigure
Items Items
Figure
Figure Included Items
Figure

ENGLISH
External Power supply

ENGLISH
ENGLISH
2. Included Items
- Supply voltage : AC 24V
M4 x10
• PRARH1 applies to High Static Duct, Low Static Duct, 1Way CST, 2Way CST, 4Way CST and Ceiling
PRARS1 PRARS1

ENGLISH
Model ModelModel PRARS1

ACCESSORIES
Suspended types.
Model PRARS1 LG Scope
LG Scope
• PRARH1 applies
• PRARH1 to
• PRARH1 High
applies Static
applies
to High Duct,
to HighLow
Static Static
Static
Duct, LowDuct,
Duct, Low1Way
Static Duct,CST,
Static 2Way
Duct,
1Way CST,CST,
1Way CST,4Way
2Way CST,CST
2Way CST,
4Way and Ceiling
4Way
CST CSTCeiling
and and Ceiling
Item
Item Suspended
Suspended Item
Auxliary
types. Auxliary
SuspendedHeater Heater
Auxliary
Relay Kit
Model
types.
types. Item Relay
Heater Kit
Relay
Auxliary Kit
Heater
Screw Screw PRARS1
Screw Insulation
Insulation
Screw Installation
Installation
Insulation
Installation
Insulation Manual Manual
Installation Manual Indoor Unit
Indoor Unit

Relay Kit Manual


Q·ty Q·ty Q·ty 1 Item 1 1 Heater Relay
Auxliary 2 Kit 2 2 2
Screw 2Insulation
2 1
Installation1(Unit
Manual 1
: inch)
Q·ty
Q'ty 11 22 2 2 1 1

(Unit : inch)
(Unit : (Unit
inch) : inch)
CN_PTC

DC12V
DC12V

How to Install Figure FigureFigure Figure Auxiliary Relay


Auxiliary Kit
Relay Kit
Figure

A
2-19/32

MECHANICAL ACCESSORIES
B
CN_PTC1

A
DUCT / FS / CVT / FAU CST / Console / HYDRO KIT Gen2 Wall Mounted / ARTCOOL Gen4 Wall Mounted ① Turn the power off using circuit breaker.

B
② Disconnect the EEV cable of the indoor unit's PCB
CN_WRITE or CN1
CN_WRITE or CN1

(CN-EEV) • PRARS1 applies to Wall mounted and Art cool types.

2-19/32

2-19/32
③ Connect the independent power module (CN-EEV/

2-19/32
• PRARS1
• PRARS1 applies applies
• PRARS1
to to Walltomounted
Wallapplies
mounted Wall
and Art and Art
mounted
cool cool
and
types.Arttypes.
cool types. 7-9/32
CN_EEV
CN_EEV CN_EEV LOAD) to the indoor unitʼs EEV, using harness 1.
How to Install (Unit : inch)
CN_WRITE or CN1

CN_EEV Harness 2 1-13/32 6-23/32


CN_WRITE or CN1

Harness 2 EEV EEV


Harness 3
EEV ④ Connect the independent power module (CN-EEV/
EEV Harness 3 Harness 4
MAIN) to the indoor unitʼs PCB (CN-EEV/CN-
CN_EEV / MAIN CN_EEV / MAIN
CN_EEV / MAIN
(Unit : inch)
(Unit : inch) (Unit : inch)
CN_EEV / MAIN WRITE), using harness 2 or 3.
⑤ Supply the power. Model : PREMBTB100

3-13/32
7-9/32 14 Auxiliary Heater Relay Kit
7-9/32 7-9/32

2-19/32
CN_EEV / LOAD

2-7/32
CN_EEV / LOAD
CN_EEV / LOAD CN_EEV / LOAD

2 3/16
Harness 1 1-13/32 1-13/321-13/32 6-23/32 6-23/326-23/32

1-7/16
Harness 1 Harness 1 Harness 1
* FS : Floor Standing Aux heater
Aux heater communication
* CVT : Convertible communication lines Aux heater communication lines lines
To Indoor unit’s EEV
* FAU : Fresh Air Intake Unit

2 3/16
To Indoor unit’s EEV

2 3/16
To Indoor unit’s EEV To Indoor unit’s EEV
* CST : Cassette 2 3/16
High Static Ducted 7 Low
9/32 Static Ducted Ceiling Suspended Wall Mounted
1 13/32 6 23/32
3-13/32

3-13/32
3-13/32
2-19/32

2-19/32
2-19/32
2-7/32

2-7/32
2-7/32
Aux heater Installation Manual 5
1-7/16

1-7/16
1-7/16

communication
lines
7 9/32 7 9/32
3 13/32
7 9/32

1 13/32 1 13/321 13/32 2 7/32 6 23/32 6 23/326 23/32


1 7/16

Aux heater Aux heater


communication communication lines
lines

1 Way Cassette 2 Way Cassette 4 Way Cassette


3 13/32

3 13/32
3 13/32

2 7/32

Installation Manual 5 Manual 5


2 7/32

Installation
2 7/32

Installation Manual 5
1 7/16

1 7/16
1 7/16

Installation Manual 5
176 / 177
ACCESSORIES _ PIPING ACCESSORIES

HEAT RECOVERY

Model Name Included Parts


PRHR023 (2 Branch Unit) • HR unit (1EA)
PRHR033 (3 Branch Unit) • Hanging bolts M10 or M8 (4EA)
PRHR043 (4 Branch Unit) • Nut M8 or M10 (8EA)
PRHR063 (6 Branch Unit) • Washers M10 (8EA)
PRHR083 (8 Branch Unit) • Reducers

Applied Products
MULTI V 5
MULTI V IV
MULTI V WATER IV

Key Features Specification


• Max. 64 indoor units can be connected. (Max. 8 indoor units per branch) Model PRHR023 PRHR033 PRHR043 PRHR063 PRHR083
• It is easy to install due to the automatic search algorithm for piping detection. Number of Branch EA 2 3 4 6 8
• Subcooling cycle in HR unit makes the system efficiency maximum. Maximum Connectable Capacity of Indoor Units
kW 17.5 / 35 17.5 / 52.5 17.5 / 69.5 17.5 / 69.5 17.5 / 69.5
(Per branch / unit)
Maximum Number of Connectable Indoor Units Per Branch EA 8 8 8 8 8
Connection Capacity Flexible Connection Nominal Input
Cooling kW 0.040 0.040 0.040 0.076 0.076
Maximum number of connectable indoor units : Series connection can be installed without pipes crossing. Heating kW 0.038 0.038 0.038 0.072 0.072
64 IDUs / HR unit (in case of 8 ports model) Net. Weight kg 18.5 20.3 22.0 28.3 31.8
New Dimensions (W x H x D) mm 786 x 218 x 657 786 x 218 x 657 786 x 218 x 657 1,113 x 218 x 657 1,113 x 218 x 657
8 Ports Liquid mm (inch) 9.52 (3/8) 9.52 (3/8) 9.52 (3/8) 9.52 (3/8) 9.52 (3/8)
Indoor Unit
Gas mm (inch) 15.88 (5/8) 15.88 (5/8) 15.88 (5/8) 15.88 (5/8) 15.88 (5/8)
Piping
Liquid mm (inch) 9.52 (3/8) 12.7 (1/2) 15.88 (5/8) 15.88 (5/8) 15.88 (5/8)
Connections
Outdoor Unit Low Pressure mm (inch) 22.2 (7/8) 28.58 (11/8) 28.58 (11/8) 28.58 (11/8) 28.58 (11/8)
High Pressure mm (inch) 19.05 (3/4) 22.2 (7/8) 22.2 (7/8) 22.2 (7/8) 22.2 (7/8)
1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50

ACCESSORIES
Power Supply Ø, V, Hz
Considering the direction for Indoor 1, 220, 60 1, 220, 60 1, 220, 60 1, 220, 60 1, 220, 60
64 kBtu / Port units and SVC port, connection for
reverse direction makes much easier

Max. 230 kBtu

Reducers for Indoor Unit and HR Unit

PIPING ACCESSORIES
(Unit : mm)
Reduce Noise
Model Liquid High Pressure Low Pressure

dB(A)
46 dB(A) Indoor Unit Reducer
13 dB(A)
33 dB(A)

PRHR023

HR Unit Reducer
Conventional New

Test Condition (ISO Standard) PRHR033


- Temp. : (Cooling) 27°C DB / 19°C WB, 35°C DB / 24°C WB PRHR043
PRHR063
(Heating) 20°C DB / 15°C WB, 7°C DB / 6°C WB
PRHR083
- Operating : cooling → heating switching operation

178 / 179
ACCESSORIES _ PIPING ACCESSORIES

Y BRANCH AND HEADER BRANCH


For refrigerant distribution of indoor units.

Model Name Specification


Refer to specifications
Header Branch
R410A
Applied Products
(Unit : mm)
MULTI V 5
Model Gas Pipe Liquid Pipe
MULTI V IV
MULTI V III, MULTI V PLUS II, MULTI V PLUS
MULTI V S
Key Features MULTI V WATER IV ARBL054
• Various Y Branch pipe of different capacities make MULTI V MULTI V WATER II (4 Branch)
installation much easier. MULTI V WATER S
• Y Branch and header branch for both gas and liquid are provided.
• Insulation material is also provided for covering the branches.

ARBL057
(7 Branch)

Key Application
Heat Pump System
ARBL104
(4 Branch)

ACCESSORIES
Y Branch for Header for
Indoor Units (2 Pipes) Indoor Units (2 Pipes)

ARBL107
(7 Branch)
Y Branch for Heat Pump
Outdoor Units (2 Pipes)

PIPING ACCESSORIES
Heat Recovery System
ARBL1010
(10 Branch)

Y Branch for
Heat Recovery Units (3 Pipes)

HR Unit
ARBL2010
Y Branch for Heat Recovery (10 Branch)
Outdoor Units (3 Pipes)

Y Branch for
Zoning Control (2 Pipes)

HR Unit

180 / 181
ACCESSORIES _ PIPING ACCESSORIES

PIPING ACCESSORIES
Y Branch pipe for connection of outdoor units.

Specification Specification
Heat Pump Heat Recovery
R410A MULTI V 5, MULTI V IV, MULTI V III, MULTI V WATER IV, MULTI V WATER II R410A MULTI V 5, MULTI V IV Heat Recovery, MULTI V III Heat Recovery, MULTI V WATER IV Heat Recovery,
MULTI V WATER II Heat Recovery
(Unit : mm) (Unit : mm)

2 Outdoor Units 2 Outdoor Units


Liquid Pipe High Pressure Gas Pipe Liquid Pipe High Pressure Gas Pipe
Model High Pressure Gas Pipe Liquid Pipe Low Pressure Gas Pipe Liquid Pipe
Model High Pressure
Low Gas
Pressure
High Pressure GasPipe
Pipe Gas Pipe Liquid Pipe
Liquid Pipe High Pressure Low
GasPressure
Low PressurePipe
Gas Pipe Gas Pipe

LiquidI.D.Pipe
O.D.15.88 19.05 High Pressure Gas Pipe
O.D. 22.2 I.D. 19.05
LiquidI.D.Pipe
O.D.15.88 19.05 Low Pressure GasPressure
High
I.D.22.2 O.D. 28.58 I.D.34.9
Pipe Gas Pipe
O.D. 22.2 I.D. 19.05
LiquidI.D.Pipe
O.D.15.88 19.05 High Pressure Low
I.D.22.2O.D.
O.D.22.2
Gas
Pressure Pipe Gas Pipe
28.58I.D.I.D.34.9
19.05
LiquidI.D.Pipe
O.D.15.88 19.05 High Pressure Low
Gas
O.D. 22.2O.D.I.D.
I.D.22.2
Pressure
Pipe
19.05I.D.34.9
28.58
Gas Pipe
331
314 416
331
314
Low
416 Pressure Gas Pipe
416
Liquid 331 Pipe
314
High Pressure Low 416 Gas
416
Pressure Pipe Gas Pipe Liquid
331 Pipe
314
High Pressure Low
416
Gas
416 Pressure
Pipe Gas Pipe
I.D.15.88 I.D.15.88 I.D.15.88 I.D.15.88 408 I.D.15.88 I.D.15.88 408 I.D.15.88 I.D.15.88 408 I.D.15
408 408 408 408
I.D.28.58 I.D.28.58 I.D.28.58 I.D.28.58 I.D.28.58 I.D.28.58
I.D.28.58 I.D.28.58 I.D.22.2 O.D. 28.58 I.D.34.9 I.D.28.58 I.D.28.58O.D.15.88 I.D. 19.05 I.D.28.58
I.D.22.2O.D.
O.D.22.2 I.D.28.58
28.58I.D.I.D.34.9
19.05 O.D.15.88 I.D. 19.05 I.D.28.58 I.D.22.2
O.D. 22.2O.D.I.D. I.D.28.58
19.05
28.58 I.D.34.9
O.D.15.88 I.D. 19.05 O.D. 22.2 I.D. 19.05 O.D.15.88 I.D. 19.05 O.D. 22.2 I.D. 19.05 331 331
D.19.05 I.D.12.7 I.D.9.52 83 I.D.19.05 I.D.12.7 I.D.9.52 83 416 I.D.19.05 O.D.15.88 314I.D. I.D.12.7
19.05 I.D.9.52 83 416 I.D.19.05 O.D.15.88 314I.D. I.D.12.7
19.05 I.D.9.52 83 416 I.D.19.05
331 111 331 I.D.22.2 O.D. 28.58 I.D.34.9
I.D.22.2 111
111 I.D.22.2O.D.
O.D.22.2
28.58I.D.I.D.34.9
416 19.05
I.D.22.2 111
111
O.D. 416
22.2O.D.
I.D.22.2 I.D. 19.05I.D.34.9
28.58 I.D.22.2111 111
Liquid Pipe High Pressure Gas Pipe Liquid Pipe
408
High Pressure Gas Pipe
ARCNN21 I.D.22.2 I.D.22.2 408 I.D.22.2 408 I.D.22.2
314 I.D.31.8 I.D.34.9 416 314 I.D.31.8 I.D.34.9
I.D.31.8 I.D.34.9 416
I.D.15.88 331 ARCNB21 I.D.15.88 I.D.31.8 I.D.34.9 408
I.D.31.8 I.D.34.9 416
I.D.15.88 331 I.D.15.88 I.D.31.8 I.D.34.9
I.D.31.8 I.D.34.9 408 I.D.15
I.D.28.58 416 I.D.28.58 I.D.28.58 I.D.28.58 I.D.28.58 416 I.D.28.58 I.D.28.58
I.D.15.88 I.D.15.88 408 I.D.15.88 I.D.15.88 408 314 I.D.28.58 416 I.D.28.58 314 I.D.28.58 416
I.D.22.2 O.D.19.05 I.D.22.2 O.D.19.05 408 I.D.22.2 O.D.19.05
I.D.15.88 I.D.15.88 408 I.D.22.2 O.D.19.05
I.D.15.88 I.D.15.88 408 I.D.22
I.D.15
I.D.12.7 I.D.15.88 I.D.28.58 I.D.28.58 I.D.12.7 I.D.15.88I.D.41.3 I.D.38.1 O.D.34.9 I.D.28.58 I.D.28.58 I.D.12.7 I.D.15.88 I.D.41.3 408
I.D.38.1 O.D.34.9 I.D.12.7 I.D.15.88 I.D.41.3 408 O.D.34.9
I.D.38.1
I.D.28.58 I.D.28.58 I.D.19.05 I.D.12.7 I.D.9.52 83 I.D.28.58 I.D.28.58 I.D.19.05 I.D.12.7 I.D.9.52 83 I.D.28.58 I.D.28.58 I.D.19.05
I.D.28.58 111 I.D.28.58 I.D.28.58
I.D.28.58 111 I.D.28.58 I.D.28.58 I.D.28.58 111
I.D.12.7 I.D.9.52 83 I.D.28.58 I.D.12.7 I.D.9.52 83 I.D.22.2 I.D.28.58 I.D.22.2
I.D.28.58 111 I.D.22.2111
I.D.28.58
D.19.05 I.D.19.05 I.D.22.2 I.D.22.2
O.D.12.7 I.D.9.52 O.D.12.7 I.D.31.8
I.D.9.52 I.D.34.9 O.D.12.7
I.D.12.7 I.D.9.52 I.D.9.5283 I.D.31.8 I.D.34.9
I.D.31.8 I.D.34.9 O.D.12.7
I.D.12.7 I.D.9.5283
I.D.9.52
I.D.31.8 I.D.34.9
I.D.31.8 I.D.34.9
70 I.D.22.2 111 70 I.D.19.05
I.D.22.2 70 111 I.D.19.05 70 I.D.19.05
130 I.D.22.2 111 130 I.D.22.2 111 130 I.D.22.2111 111
O.D.15.88 I.D. 19.05 I.D.31.8 I.D.34.9 O.D.15.88 I.D. 19.05 I.D.31.8 I.D.34.9 I.D.22.2 O.D.19.05 I.D.22.2 111 I.D.22.2 O.D.19.05 I.D.22.2 I.D.22
I.D.31.8
I.D.41.3 I.D.34.9
I.D.38.1 O.D.34.9 I.D.31.8
I.D.41.3 I.D.34.9
I.D.38.1 O.D.34.9 I.D.31.8 I.D.34.9
I.D.22.2 O.D.19.05
O.D. 22.2 I.D. 19.05
I.D.22.2 O.D.19.05
O.D. 22.2 I.D. 19.05 I.D.12.7 I.D.15.88 I.D.31.8 I.D.34.9 I.D.12.7 I.D.15.88 I.D.31.8 I.D.41.3
I.D.34.9I.D.38.1 O.D.34.9
331 I.D.12.7 I.D.15.88 O.D.28.58 I.D. 19.05 331 I.D.12.7 I.D.15.88 I.D.28.58 O.D.28.58 I.D. 19.05
I.D.22.2 O.D.19.05 O.D.28.58 I.D. 19.05I.D.28.58 I.D.22.2 O.D.19.05 O.D.28.58 I.D. 19.05 I.D.28.58 I.D.22
I.D.28.58 I.D.28.58
314 I.D.22.2
416 314 I.D.41.3 I.D.38.1 O.D.34.9 I.D.22.2
416 I.D.12.7 I.D.9.52
O.D.12.7 I.D.15.88 I.D.22.2
I.D.41.3 I.D.38.1 O.D.34.9 I.D.9.52
O.D.12.7 I.D.15.88
I.D.12.7 I.D.22.2
I.D.41.3 I.D.38.1 O.D.34.9
O.D.15.88
I.D.15.88 I.D. 19.05
I.D.15.88 I.D.9.52 I.D.28.58 I.D.15.88O.D.15.88 I.D. 19.05
I.D.15.88 I.D.9.52 I.D.22.2 O.D.28.58 I.D.34.9 I.D.28.58
O.D.15.88
70 I.D. 19.05 I.D.22.2 O.D.28.58 I.D.34.9 O.D.15.88
70 I.D. 19.05 I.D.22.2 O.D.28.58 I.D.34.9
O.D.12.7 408 O.D.12.7 130 I.D.28.58 408 130 I.D.28.58 130 I.D.28.58
I.D.28.58 I.D.28.58
70 I.D.28.58 I.D.28.58 70 I.D.28.58 I.D.28.58 O.D.12.7 I.D.9.52 O.D.12.7 I.D.9.52
70 O.D.28.58 I.D. 19.05 70 O.D.28.58 130 I.D. 19.05
D.19.05 I.D.12.7 I.D.9.52 83 I.D.19.05 I.D.12.7 I.D.9.52 83 130 130
O.D.28.58 I.D. 19.05 O.D.28.58 I.D. 19.05 I.D.22.2 I.D.22.2
I.D.22.2 111 I.D.22.2 O.D.28.58 I.D.34.9 I.D.22.2 111
O.D.15.88 I.D. 19.05 I.D.22.2 O.D.28.58 I.D.34.9 O.D.15.88 I.D. 19.05 I.D.22.2 O.D.28.58 I.D.34.9
I.D.31.8 I.D.34.9 I.D.22.2 I.D.31.8 I.D.34.9 I.D.22.2 O.D.28.58 I.D. 19.05 O.D.28.58 I.D. 19.05
O.D.15.88 I.D. 19.05 3 Outdoor Units O.D.15.88 I.D. 19.05 I.D.22.2 3 Outdoor Units I.D.22.2
I.D.22.2 O.D.19.05 I.D.22.2 O.D.19.05 I.D.22.2 O.D.28.58 I.D.34.9 O.D.15.88 I.D. 19.05 I.D.22.2 O.D.28.58 I.D.34.9 O.D.15.88 I.D. 19.05 I.D.22.2 O.D.28.58 I.D.34.9
I.D.12.7 I.D.15.88 I.D.12.7 I.D.15.88 I.D.41.3 O.D.34.9 I.D.41.3 O.D.34.9 I.D.41.3 O.D.34.9
I.D.22.2 O.D.28.58 I.D.34.9 O.D.34.9 I.D.28.58 I.D.22.2 O.D.28.58 I.D.34.9 O.D.34.9 I.D.28.58 O.D.34.9 I.D.28.58
.D.19.05 I.D.12.7 Model I.D.22.2
O.D.19.05 High Pressure Gas PipeI.D.28.58
O.D.19.05 Liquid Pipe
I.D.12.7 O.D.19.05 I.D.22.2 I.D.28.58
Model High Pressure Gas Pipe Liquid Pipe Low Pressure Gas Pipe
I.D.15.88 416 I.D.15.88 416 I.D.22.2 O.D.28.58 I.D.34.9 I.D.22.2 O.D.28.58 I.D.34.9
O.D.12.7 I.D.9.52 O.D.12.7 I.D.9.52
70 408 70 408 O.D.19.05 I.D.12.7 O.D.19.05 I.D.22.2 O.D.19.05 I.D.12.7 O.D.19.05 I.D.22.2 O.D.19.05
334 334 125I.D.28.58 I.D.15.88 416 125 I.D.15.88 416 125 I
I.D.28.58 I.D.28.58 I.D.41.3 O.D.34.9 I.D.28.58 I.D.41.3 O.D.34.9 I.D.41.3 O.D.34.9
281 281 341 341
408 408 341
O.D.34.9 I.D.28.58298 334 O.D.34.9 I.D.28.58
298 334 O.D.34.9 I.D.28.58
298 I.D.28.58
O.D.28.58 I.D. 19.05 O.D.28.58 I.D. 19.05 I.D.28.58 I.D.28.58 I.D.28.58
I.D.22.2 I.D.22.2
O.D.28.58 I.D.34.9 I.D.41.3 O.D.34.9 I.D.22.2 O.D.28.58
I.D.22.2 I.D.34.9 281 I.D.22.2 O.D.28.58 I.D.41.3 O.D.34.9
I.D.34.9 281 I.D.22.2 O.D.28.58 I.D.34.9 I.D.41.3 O.D.34.9
.D.19.05 I.D.12.7 O.D.19.05 I.D.22.2 I.D.22.2 111 O.D.19.05 I.D.12.7 O.D.19.05 I.D.22.2 I.D.22.2
O.D.19.05 111 I.D.12.7 O.D.19.05 I.D.12.7 O.D.19.05
O.D.15.88
I.D.15.88 I.D. 19.05 O.D.15.88
I.D.15.88 I.D. 19.05 O.D.34.9 I.D.28.58 O.D.19.05 I.D.22.2 O.D.34.9 I.D.28.58 O.D.19.05 I.D.22.2 O.D.34.9 I.D.28.58
I.D.31.8 I.D.34.9 416 I.D.31.8
125 I.D.34.9 416 I.D.15.88 416 125 I.D.15.88 416 125 I
408 408 I.D.22.2 408
O.D.28.58 I.D.34.9
I.D.22.2 111 I.D.22.2 408O.D.28.58 I.D.34.9
I.D.22.2 111
334 I.D.19.05 83 I.D.41.3 334 I.D.19.05 83 341 341 341
.22.2 I.D.19.05 I.D.28.58I.D.38.1 O.D.34.9 I.D.28.58 I.D.22.2 I.D.19.05
I.D.41.3 298 I.D.34.9
I.D.41.3
I.D.28.58 I.D.38.1 O.D.34.9O.D.19.05
I.D.28.58 I.D.12.7
334 O.D.19.05 I.D.22.2 I.D.31.8 I.D.34.9
I.D.28.58
I.D.41.3 298 I.D.28.58
I.D.34.9
O.D.19.05 I.D.12.7
334 O.D.19.05 I.D.22.2 I.D.31.8 I.D.34.9
I.D.28.58
I.D.41.3 298 I.D.28.58I.D.34.9
O.D.19.05
281 281 125 111 I.D.15.88 416 125 111 I.D.15.88 416 125 111 I
I.D.22.2 I.D.19.05 281 I.D.19.05 83 I.D.41.3 I.D.38.1 408
O.D.34.9 I.D.22.2 I.D.19.05 281 I.D.19.05 83 I.D.41.3 I.D.38.1 408 O.D.34.9 I.D.22.2 I.D.1
I.D.28.58 341 I.D.28.58 341 341
298 334 I.D.28.58 298 I.D.28.58 334 I.D.28.58 298 I.D.28.58

ACCESSORIES
I.D.22.2 111 I.D.22.2 111 281 I.D.28.58 111 281 I.D.28.58 111
I.D.15.88 I.D.12.7 130 I.D.15.88 I.D.12.7 130 I.D.22.2 I.D.22.2
I.D.31.8 I.D.34.9 I.D.31.8 I.D.34.9 I.D.31.8 I.D.34.9 I.D.31.8 I.D.34.9
I.D.28.58 O.D.22.2 ARCNN31
I.D.19.05 83 I.D.28.58 O.D.22.2 I.D.41.383
I.D.19.05I.D.53.98
I.D.28.58 111
I.D.34.9 ARCNB31
I.D.15.88 I.D.12.783 I.D.41.3 130 I.D.28.58 111
I.D.34.9 I.D.15.88 I.D.12.783 I.D.41.3130 I.D.28.58 111
I.D.34.9
.22.2 I.D.19.05 I.D.41.3 I.D.22.2 I.D. 34.9 O.D.28.58
I.D.38.1 O.D.34.9
O.D.28.58 I.D.34.9I.D.22.2 I.D.22.2 I.D.19.05 I.D. 44.5 O.D.41.3 I.D.41.3 I.D.22.2 I.D. 34.9
I.D.38.1 O.D.34.9
O.D.28.58 O.D.28.58
I.D.22.2 I.D.34.9 I.D.22.2
I.D.19.05 I.D.19.05 I.D.53.98 I.D. 44.5
I.D.41.3 I.D.38.1 O.D.41.3 I.D.22.2
O.D.34.9 111 I.D.22.2 I.D.19.05 I.D.19.05 I.D.53.98
I.D.41.3 I.D.38.1 I.D. 44.5 O.D.41.3
O.D.34.9 I.D.22.2 111 I.D.22.2 I.D.1
.D.19.05 I.D.12.7 O.D.19.05 I.D.22.2 O.D.19.05 I.D.12.7 O.D.19.05 I.D.22.2 I.D.31.8 I.D.34.9 I.D.31.8 I.D.34.9
I.D.15.88 416 I.D.15.88 I.D.41.3 I.D.34.9 416 I.D.28.58 O.D.22.2 I.D.41.3 I.D. 34.9 O.D.28.58
I.D.34.9 I.D.22.2 I.D.28.58 O.D.22.2 I.D.41.3 I.D. 34.9 O.D.28.58I.D.34.9
I.D.22.2 111 I.D.28.58
O.D.15.88 I.D.19.05 I.D.28.58 O.D.15.88 I.D.19.05 111 I.D.28.58 111
408 408 I.D.22.2 I.D.19.05 I.D.19.05 83 I.D.41.3 I.D.38.1 O.D.34.9 I.D.28.58 I.D.22.2 I.D.19.05 I.D.19.05 83 I.D.41.3 I.D.38.1 O.D.34.9 I.D.28.58 I.D.22.2 I.D.1
334 I.D.53.98 I.D.44.5 O.D.41.3
I.D.28.58 I.D.28.58 334 I.D.53.98
I.D.28.58I.D.44.5 O.D.41.3 I.D.28.58
I.D.15.88 I.D.12.7 130 I.D.15.88 I.D.12.7 I.D.22.2 O.D.28.58 I.D.34.9
I.D.28.58 130 O.D.15.88 I.D.19.05 I.D.22.2 O.D.28.58 I.D.34.9
I.D.28.58 O.D.15.88 I.D.19.05 I.D.22.2 O.D.28.58 I.D.34.9
I.D.28.58
281 281 I.D.15.88 I.D.12.7 130 I.D.15.88 I.D.12.7 130
I.D.53.98 I.D. 44.5 O.D.41.3 I.D.53.98I.D.44.5
I.D.53.98 I.D. 44.5 O.D.41.3
O.D.41.3 I.D.28.58 I.D.53.98 I.D.53.98
I.D.44.5 I.D. 44.5 O.D.41.3I.D.28.58
O.D.41.3
I.D.28.58 O.D.22.2 I.D. 34.9 O.D.28.58 I.D.22.2 I.D.28.58 O.D.22.2 I.D. 34.9 O.D.28.58
I.D.28.58 I.D.22.2
O.D.22.2 I.D.28.58 O.D.22.2 I.D.28.58
111 I.D.28.58 111 I.D.15.88 I.D.12.7 I.D.28.58
130 I.D. 34.9 O.D.28.58 I.D.22.2 I.D.15.88 I.D.12.7 I.D.28.58
130 I.D. 34.9 O.D.28.58 I.D.22.2
I.D.22.2 I.D.53.98 I.D. 44.5 O.D.41.3 I.D.22.2 I.D.53.98 I.D. 44.5 O.D.41.3 I.D.53.98 I.D. 44.5 O.D.41.3
O.D.15.88 I.D.19.05 I.D.31.8 I.D.34.9 O.D.15.88 I.D.19.05 I.D.31.8 I.D.34.9
I.D.22.2 O.D.28.58 I.D.34.9 I.D.28.58 O.D.22.2 O.D.15.88 I.D.19.05 I.D.22.2 O.D.28.58
I.D. 34.9 O.D.28.58 I.D.34.9
I.D.22.2 I.D.28.58 O.D.22.2 O.D.15.88 I.D.19.05 I.D.22.2
I.D. 34.9 O.D.28.58
O.D.28.58 I.D.22.2I.D.34.9 I.D.28.58
.22.2 I.D.19.05 I.D.19.05 83 I.D.53.98 I.D.44.5
I.D.38.1 O.D.41.3
I.D.41.3O.D.34.9 O.D.34.9 I.D.22.2 I.D.19.05 I.D.19.05 83 I.D.53.98 I.D.44.5
I.D.38.1 O.D.41.3
I.D.41.3O.D.34.9 O.D.34.9
O.D.19.05 I.D.22.2 I.D.28.58 I.D.41.3 I.D.44.5 O.D.19.05 I.D.22.2 I.D.28.58 I.D.41.3 I.D.44.5 I.D.53.98 I.D.44.5 O.D.41.3 I.D.53.98 I.D.44.5 O.D.41.3
I.D.22.2 O.D.28.58 I.D.34.9 O.D.15.88 I.D.19.05 I.D.22.2 O.D.28.58 I.D.34.9 O.D.15.88 I.D.19.05 I.D.22.2 O.D.28.58 I.D.34.9
334 341 I.D.28.58 334 341 I.D.28.58

PIPING ACCESSORIES
I.D.53.98 I.D.44.5 O.D.41.3 I.D.53.98 I.D.44.5 O.D.41.3
281 298 281 298
I.D.15.88 I.D.12.7 130 I.D.15.88 I.D.12.7 130
I.D.28.58 O.D.22.2 I.D.28.58 O.D.22.2
O.D.19.05 I.D.22.2 I.D.28.58 O.D.34.9 I.D. 34.9 O.D.28.58
I.D.41.3 I.D.44.5I.D.22.2
4 Outdoor Units O.D.19.05 I.D.22.2 I.D.28.58 O.D.34.9 I.D. 34.9 O.D.28.58
I.D.41.3 I.D.44.5I.D.22.2 4 Outdoor Units
.22.2 I.D.19.05 I.D.19.05 83 I.D.22.2 I.D.19.05 I.D.19.05 83
334O.D.15.88 I.D.19.05 I.D.41.3 341 I.D.34.9 111 334O.D.15.88 I.D.19.05 I.D.41.3 341 I.D.34.9 111
281 Model High
I.D.53.98 Pressure
I.D.44.5 298
O.D.41.3 Gas Pipe Liquid
281 Pipe O.D.41.3 I.D.44.5 I.D.53.98 298
I.D.53.98 I.D.44.5 O.D.41.3 O.D.19.05 I.D.22.2 Model
I.D.28.58 High Pressure
O.D.41.3
O.D.34.9 I.D.41.3Gas
I.D.44.5 Pipe
I.D.53.98
I.D.44.5 Liquid
O.D.19.05 Pipe I.D.28.58
I.D.22.2 Low Pressure
O.D.41.3
O.D.34.9 Gas
I.D.44.5I.D.44.5
I.D.41.3 Pipe
I.D.53.98 O
415 334 415
341 334 341 415
I.D.15.88 I.D.12.7 I.D.15.88 I.D.12.7
I.D.31.8 I.D.28.58 O.D.22.2 I.D.31.8 I.D.28.58 O.D.22.2 375 281 375
298 281 298 375
I.D.53.98 I.D.44.5 O.D.41.3 I.D.28.58 I.D.53.98 I.D.44.5 O.D.41.3 I.D.28.58
.22.2 I.D.19.05 I.D.19.05 83 I.D.22.2 I.D.19.05 I.D.19.05 83
O.D.41.3 I.D.44.5 I.D.53.98I.D.41.3 O.D.19.05
I.D.41.3 I.D.34.9 111 I.D.34.9 111 I.D.22.2 I.D.28.58 O.D.41.3
O.D.34.9 I.D.44.5
I.D.41.3 I.D.53.98
I.D.44.5 O.D.19.05 I.D.22.2 I.D.28.58 O.D.34.9
O.D.41.3
I.D.41.3
I.D.44.5I.D.44.5
I.D.53.98 O
415 334 415
341 341 415
O.D.19.05 I.D.22.2 I.D.28.58
O.D.15.88 I.D.19.05 O.D.34.9
I.D.34.9 I.D.41.3
O.D.28.58 I.D.44.5
I.D.22.2 O.D.19.05 I.D.22.2 I.D.28.58
O.D.15.88 I.D.19.05 O.D.41.3 I.D.44.5 I.D.53.98 O.D.34.9 I.D.41.3
134 I.D.34.9 O.D.28.58
I.D.44.5
I.D.22.2I.D.22.2
O.D.19.05
I.D.19.05 I.D.22.2 I.D.28.58
I.D.19.05 83 O.D.34.9 I.D.44.5
O.D.41.3 I.D.41.3 I.D.53.98
I.D.44.5 134 O.D.19.05 334
I.D.22.2 I.D.19.05 I.D.22.2 I.D.28.58
I.D.19.05 83 O.D.41.3
O.D.34.9 I.D.44.5I.D.44.5
I.D.41.3 I.D.53.98 134 O
I.D.22.2 I.D.
I.D.44.48 I.D.53.98 375 I.D.41.3 281 I.D.44.48 375
I.D.41.3 I.D.53.98298 I.D.41.3
I.D.34.9 111 281 298
I.D.41.3I.D.44.48 I.D.53.98 375 I.D.34.9 I.D.41.3
111
334 I.D.15.88 I.D.12.7 341 334 I.D.15.88 I.D.12.7 415 341 415
341 341 415
I.D.31.8 I.D.28.58 281
O.D.22.2 I.D.53.98 I.D.44.5 O.D.41.3 I.D.31.8 I.D.28.58 281
O.D.22.2 I.D.53.98 I.D.44.5 O.D.41.3 334 334
298 I.D.28.58 375 298 I.D.28.58 375
298 298 375
281 281
I.D.15.88 I.D.12.7 I.D.15.88 I.D.12.7
I.D.22.2 I.D.28.58 O.D.22.2 I.D.19.05
I.D.31.8I.D.19.05 83 I.D.22.2
I.D.31.8I.D.19.05
I.D.28.58 O.D.22.2 I.D.19.05 83 I.D.22.2
I.D.31.8I.D.I
I.D.44.48 I.D.53.98 I.D.28.58 134
I.D.41.3 I.D.53.98
I.D.41.3 I.D.44.5
I.D.44.48 I.D.53.98O.D.41.3 I.D.28.58134
I.D.28.58
I.D.41.3
I.D.34.9 111 I.D.53.98 I.D.44.5I.D.53.98
I.D.41.3I.D.44.48 O.D.41.3 I.D.28.58
I.D.34.9 I.D.28.58
I.D.41.3111 134
O.D.15.88 I.D.19.05 I.D.34.9 O.D.28.58 I.D.22.2 O.D.15.88 I.D.19.05 I.D.34.9 O.D.28.58 I.D.22.2
.22.2 I.D.19.05 I.D.19.05 83 I.D.22.2 I.D.19.05 I.D.19.05 83
ARCNN41 I.D.41.3 I.D.34.9 111 I.D.22.2 I.D.41.3I.D.41.3
O.D.28.58 I.D.34.9 134 I.D.34.9
I.D.22.2 I.D.19.05111 ARCNB41
I.D.19.05 83
I.D.41.3I.D.22.2 I.D.41.3
I.D.34.9
O.D.28.58 I.D.34.9 134 I.D.22.2 I.D.19.05 I.D.19.05 83
I.D.41.3I.D.44.48
I.D.22.2 I.D.34.9
O.D.28.58 I.D.41.3
I.D.34.9 134 I.D.22.2 I.D.
I.D.44.48 I.D.53.98 I.D.44.48 I.D.53.98 111 I.D.53.98 111
O.D.15.88
I.D.15.88I.D.19.05
I.D.12.7 I.D.34.9 O.D.28.58 I.D.22.2 O.D.15.88
I.D.15.88I.D.19.05
I.D.12.7 I.D.34.9 O.D.28.58 I.D.22.2
I.D.28.58 I.D.31.8 I.D.28.58 O.D.22.2 I.D.53.98 I.D.44.5 O.D.41.3 I.D.28.58
I.D.28.58 I.D.31.8 I.D.28.58 O.D.22.2 I.D.53.98 I.D.44.5 O.D.41.3 I.D.28.58I.D.28.58 I.D.31.8 I
I.D.15.88 I.D.12.7 I.D.15.88 I.D.12.7 I.D.15.88 I.D.12.7 I.D.15.88 I.D.12.7
I.D.31.8 I.D.28.58 O.D.22.2 I.D.53.98 I.D.44.5 O.D.41.3 I.D.28.58 I.D.31.8 I.D.28.58 O.D.22.2 I.D.53.98 I.D.44.5 O.D.41.3 I.D.31.8I.D.28.58
I.D.28.58 O.D.22.2 I.D.31.8 I.D.28.58 O.D.22.2 I.D.31.8 I
I.D.22.2 O.D.28.58 I.D.34.9 I.D.28.58 I.D.53.98I.D.22.2
I.D.44.5 O.D.28.58
O.D.41.3 I.D.34.9
I.D.28.58
I.D.28.58 I.D.53.98 I.D.44.5 O.D.41.3
I.D.22.2 I.D.28.58
O.D.28.58 I.D.28.58
I.D.34.9
O.D.15.88 I.D.19.05 I.D.34.9 O.D.28.58 I.D.22.2 O.D.15.88 I.D.19.05 I.D.34.9 O.D.28.58 I.D.22.2
O.D.15.88 I.D.19.05 I.D.34.9 O.D.28.58 I.D.22.2 O.D.15.88 I.D.19.05 I.D.22.2 O.D.28.58 I.D.34.9 I.D.34.9 O.D.28.58 I.D.22.2 O.D.15.88 I.D.19.05
I.D.22.2 O.D.28.58 I.D.34.9
O.D.15.88 I.D.19.05
I.D.22.2 O.D.28.58 I.D.34.9
I.D.34.9 O.D.28.58 I.D.22.2 I.D.34.9 O.D.28.58 I.D.22.2

182 / 183
ACCESSORIES _ PIPING ACCESSORIES

PIPING ACCESSORIES
Y Branch pipe for connection of outdoor units.

Specification Specification
Heat Pump, Heat Recovery Zone Control Heat Recovery
R410A MULTI V 5, MULTI V IV, MULTI V III, MULTI V PLUS II, MULTI V PLUS, MULTI V S, MULTI V MINI, R410A MULTI V 5, MULTI V IV Heat Recovery, MULTI V III Heat Recovery, MULTI V WATER IV Heat Recovery,
MULTI V SPACE II, MULTI V WATER IV, MULTI V WATER S, MULTI V WATER II MULTI V WATER II Heat Recovery
(Unit : mm) (Unit : mm)

Model Gas Pipe Liquid Pipe Model High Pressure Gas Pipe Liquid Pipe Low Pressure Gas Pipe

I.D12.7 I.D15.88 I.D15.88


I.D9.52 I.D9.52 I.D6.35
I.D12.7 I.D15.88
I.D9.52 I.D9.52 I.D6.35

I.D15.88 I.D6.35
ARBLN01621
ARBLB01621 I.D6.35 I.D15.88

I.D12.7 I.D15.88 I.D. 9.52 I.D6.35 I.D12.7


I.D19.05 I.D12.7 I.D15.88
I.D. 9.52 I.D6.35 I.D19.05
O.D9.52 I.D12.7
O.D15.88 O.D9.52 O.D15.88

I.D22.2 I.D19.05 I.D15.88 I.D19.05


I.D9.52 I.D9.52 I.D6.35

I.D12.7
I.D25.4
I.D9.52 I.D9.52 I.D6.35 I.D22.2 I.D19.05 I.D15.88 I.D19.05
I.D12.7 I.D12.7
O.D19.05
ARBLN03321 I.D28.58
I.D15.88 I.D12.7
I.D12.7
I.D19.05 I.D25.4
ARBLB03321 I.D12.7 I.D12.7

I.D9.52 I.D6.35
I.D28.58 O.D19.05
I.D25.4 O.D19.05
O.D19.05 I.D12.7 I.D15.88 I.D12.7
I.D 22.2 I.D 22.2 I.D9.52 I.D6.35
I.D19.05
I.D12.7

I.D25.4 O.D19.05
O.D19.05
I.D 22.2 I.D 22.2

Model Gas Pipe Liquid Pipe


I.D19.05
I.D19.05
I.D19.05 I.D19.05 I.D12.7 I.D15.88 I.D15.88 I.D12.7 I.D28.58 I.D22.2 I.D15.88
I.D28.58 I.D22.2 I.D15.88 I.D12.7 I.D15.88 I.D15.88 I.D12.7

I.D12.7 I.D12.7
I.D12.7 I.D12.7 I.D19.05 I.D31.8
ARBLN07121 ARBLB07121

ACCESSORIES
I.D31.8 I.D19.05

I.D15.88 I.D19.05 I.D19.05 I.D15.88


I.D19.05 I.D15.88 I.D15.88 I.D19.05
O.D12.7 I.D6.35
O.D12.7 I.D6.35
I.D31.8 O.D22.2 I.D9.52 I.D31.8 O.D22.2
I.D9.52
I.D34.9 I.D28.58 O.D19.05 I.D28.58 I.D9.52 I.D9.52
I.D34.9 I.D28.58 O.D19.05 I.D28.58
O.D31.8 I.D22.2 O.D12.7 O.D12.7 O.D31.8 I.D22.2

I.D34.9
I.D34.9 I.D41.3 I.D38.1 I.D28.58
I.D34.9
I.D34.9 I.D41.3 I.D38.1 I.D28.58
I.D28.58
I.D38.1

PIPING ACCESSORIES
I.D28.58
ARBLN14521 I.D41.3 O.D34.9
I.D34.9 I.D22.2 I.D38.1

I.D41.3
O.D38.1 I.D38.1
ARBLB14521 I.D41.3 O.D34.9
I.D34.9 I.D22.2

I.D41.3
O.D38.1 I.D38.1

I.D12.7 O.D28.58 I.D19.05


O.D22.2 I.D15.88
O.D15.88 I.D22.2
I.D19.05
I.D15.88 I.D12.7 O.D28.58 I.D19.05
O.D22.2
I.D19.05 O.D15.88 I.D22.2

Model Gas Pipe Liquid Pipe

Model High Pressure Gas Pipe Liquid Pipe Low Pressure Gas Pipe

I.D34.9 I.D34.9 I.D.44.48


I.D.41.3 I.D38.1 I.D28.58 I.D.53.98 I.D41.3 I.D38.1
2 I.D.25.4
I.D25.4 I.D22.2 I.D.22.2 I.D.19.05 2
1
I.D28.58 2 I.D.44.48
I.D38.1
ARBLN23220 I.D34.9 I.D22.2 125 I.D.44.48 I.D41.3 I.D38.1 134
I.D.25.4
471 I.D.22.2 I.D.19.05 96 420
3 3
517
490
346 3
ARBLB23220 I.D19.05 379 I.D.34.9 I.D31.8
O.D22.2 I.D15.88 I.D.53.98 I.D.25.4 I.D.22.2
O.D38.1 I.D41.3 O.D34.9 I.D38.1 O.D.38.1 I.D.28.58 O.D.44.48
O.D.28.58
3 2 3 I.D41.3 I.D19.52 2 2
I.D.15.88 X2 X2 3
O.D.19.05 I.D.12.7 O.D12.7 I.D6.35 3 3
120 90 130
175 100 115
2 3 X2 3
I.D12.7 O.D28.58 I.D22.2 I.D12.7 I.D.19.05 I.D.15.88
3 110 110
2 I.D19.05 3 3
O.D15.88
O.D15.88 O.D.22. 2
70 120
70 120

184 / 185
ACCESSORIES _ PIPING ACCESSORIES

REFRIGERANT CHARGING KIT DRAIN HOSE


Recharging refrigerant after a pump down or when refrigerant is either insufficient or excessive. Easy drain installation.

Model Name Model Name


PRAC1 PHDHA05T
PHDHA07T
Applied Products PHDHA05B
MULTI V 5
PHDHA07B
MULTI V IV Heat Pump
MULTI V IV Heat Recovery Applied Products
MULTI V III Heat Pump MULTI V Indoor units
MULTI V III Heat Recovery
MULTI V PLUS II
MULTI V SYNC II

How to Use Key Features


• Arrange manifold, capillary assembly, refrigerant vessel and scale. • It reduces the installation time by over 40% with elbow-less drain hose.
• Connect manifold to the gas pipe service valve of outdoor unit as shown in the figure. • Drain pump covers maximum 700mm high, featuring easy piping installation.
• Connect manifold and capillary tube. Use designated capillary assembly only.
If designated capillary assembly isn’t used, the system may get damaged.
• Connect capillary and refrigerant vessel.
• Purge hose and manifold.
• After “568” is displayed, open the valve and charge the refrigerant. Key Application
• Ceiling Mounted Cassette and Ceiling Concealed Duct. (Refer to PDB for applicable model)

Max. 450
Key Application

ACCESSORIES
Manifold Ceiling Mounted Cassette Flexible Hose
250 (4 Way, 1 Way) Make a Loop Form
Ceiling Concealed Duct
(with Drain Pump)
Capillary Assembly
(Unit : mm)

PIPING ACCESSORIES
Specification
* Fault Detect & Diagnosis
Model Length Quantity
PHDHA05T 500mm 30EA
PHDHA07T 700mm 30EA
PHDHA05B 500mm 5EA

Refrigerant PHDHA07B 700mm 5EA

186 / 187
ACCESSORIES _ PIPING ACCESSORIES

STOPPER VALVES

Model Name Application


PRVT120 (Under 12.7mm) (Room 3 & 4 : in useCut/ Room
inlet side1of&the
2 :connector,
need to and
install
weldindoor units)
In case of the installation of additional
PMVT780 (Under 22.2mm) the pipe indoor unit, outlet side connector should
be cut according to installation pipe.
PMVT980 (Under 28.58mm)

"A"

9.52 : 19.05

3.0 m Room 1
Key Features
9.52 : 19.05 Closed State
Pin (Closed) Pin (Open)
• This unit can be applied for the additional indoor unit’s installation. 3.0 m
• This unit can be applied for each indoor unit’s service. In case of installation of stopper valve,
Stopper Valves
9.52 : 15.88In case of installation of additional
flare part should be facing towards indoor unit, SVC valve should be in Room 2
10.0 m
additional indoor unit. closed state

-When welding, service valve shoud be wrapped by wet cloth.


Specification 9.52 : 15.88
5.0 m
Model Specification Room 3

Input Output (Indoor unit)


6.35 : 12.7
ID 6.35 OD 9.52 ID 12.7 ID 12.7 ID 6.35
3.0 m
PRVT120
Room 4

Input Output (Indoor unit)

ID 19.05 • In case of installation of additional indoor unit, refrigerant of used indoor unit must be discharged. (Room 3 & Room 4)
ID 15.88 ID 22.2 ID 22.2 ID 19.05 ID 15.88
PRVT780 • If stopper valve is already installed, you can install additional indoor unit without refrigerant loss from the entire system.
• After installation of additional indoor unit, you just need refrigerant charging for “A” section.
• Then, open the Stopper Valve.

ACCESSORIES
Input Output (Indoor unit) Cut inlet side of the connector, and weld In case of the installation of additional
ID 28.58 ID 28.58
the pipe indoor unit, outlet side connector should
be cut according to installation pipe.
PRVT980

Open / Close Port


Charge Port

9.52 : 19.05

PIPING ACCESSORIES
3.0 m

9.52 : 19.05 Pin (Closed) Open State


Pin (Open)
Cut inletCut
sideinlet
of the In case of the installation of additional 3.0 m Stopper Valves
sideconnector, and weldand weld
of the connector, In case of the installation of additional
the pipethe pipe indoor unit, outlet
indoor unit,side connector
outlet should should
side connector In case of installation of9.52 : 15.88
stopper valve, In case of installation of additional
be cut according to installation pipe.
be cut according to installation pipe. flare part should be facing towards indoor unit, SVC valve should be in
How to Install additional indoor unit. 10.0 m closed state
6.35 : 12.7
3.0 m
-When welding, service valve shoud be wrapped by wet cloth. Room 1

9.52 : 15.88
Pin (Closed)
Pin (Closed)
Pin (Open)
Pin (Open) 3.0 m
Room 2
1.Cut
Cutinletthe
sideinlet
of the connector,
ofside weldweld In case
of theandand Ifofinstalling
2.case the installation of additional
additional indoor 3.case
When installingof astopper
stopper
Cut inlet side the connector, In of the installation of additional In of installation
In case valve,valve,
of installation of stopper
4. installation
In case of
valve,
When installing anadditional
of additional
In case of installation of additional
the the
pipepipe indoor unit,unit,
indoor outlet sideside
outlet connector should
connector should
connector, and weld the pipe. be cut units, the
according to outlet side
installation connec-
pipe. the
flare flare
part
flare part
should
part be should
facing
should be facing
betowards
facing towards indoor unit, indoor
SVC
indoor unit,
valve
unit, SVC thebe
should
valve SVC
in be
should valve
in
be cut according to installation pipe. additional indoor unit. closed state
tor should be cut according to towards additional indoor unit.
additional indoor unit. closed stateshould be in closed state. Room 3
installation pipe.
-When -When
welding,welding,
service service
valve shoud
valvebe wrapped
shoud by wet by
be wrapped cloth.
wet cloth.
※ When welding, service valve should be wrapped by wet cloth. Room 4

Pin (Closed)
Pin (Closed) Pin (Open)
Pin (Open)

In case of installation
In case of stopper
of installation valve,
of stopper valve, In case of installation
In case of additional
of installation of additional
flareflare
partpart
should be facing
should towards
be facing towards indoor unit,unit,
indoor SVCSVCvalve should
valve be in
should be in
additional indoor unit.
additional indoor unit. closed state
closed state

-When welding,
-When service
welding, valve
service shoud
valve be wrapped
shoud by wet
be wrapped cloth.
by wet cloth. 188 / 189