You are on page 1of 54

2020 - 2021

LG BECON
HVAC SOLUTION GUIDE

LG BECON HVAC SOLUTION GUIDE


2020 - 2021

LG Electronics Distributed by
http: / / www.lg.com
http: / / partner.lge.com

Copyright © 2020 LG Electronics. All rights reserved.


WHY LG BECON HVAC SOLUTION

BENEFITS OF
LG BECON HVAC SOLUTION

Benefits for Benefits for


Building Owners Consultants
Efficient Management & Cost Reduction Versatile Solutions
- Fault Detection Diagnosis enables easy maintenance - Air-Cooled, Water-Cooled, Heating, and
- Requires no extra manpower for regular Air Handing Unit interlocking solutions
maintenance
- With diverse control systems, maintenance cost is
Professional Design Support
minimized
- LATS (LG Air conditioner Technical Solution) for
Reliability at Every Stage draft energy estimation, model selection, HVAC
- Ultimate Inverter Compressor developed and design and 3D designing
manufactured in Korea - CFD Analysis to ensure suitable solutions and
- Corrosion resistant Ocean Black Fin for harsh prevent malfunctions
conditions operation - Energy simulation offered to find the optimal
- Smart Oil management (Auto Oil balancing and solution
Active Oil return) decreases compressor damage
Optimized Convenience with HVAC Design
Customized Comfort and Solution - Flexible and longer piping length facilitates
- Compatible option between Heat pump and Heat HVAC designing process
recovery system is possible - Meets any type of customer requirements of
diverse environment, design conditions, and
building applications

Benefits for Benefits for


Developers & Construction Companies End-users

Green Solutions Minimizing your Operation Costs


- Optimized for LEED / BREEAM certification - Excellent cost savings through energy saving solutions
- Renewable energy solution provided through :E
 nergy Management, Schedule Control,
geothermal application Time Limit, Group Control

Maximizing Space Utilization Smart Management


- Large capacity in compact size enhances space - Intuitive control and monitoring provides a more
utilization comfortable environment with smart management
functions.
Smart Building Solutions - Air purify solution keeps providing clean air
- Seamless integration with current Building :A
 ir Purify Control, Air Quality Level, Visual Navigation,
Management Systems Operation Trend, Comfort Level Display
- Wi-Fi control available for anytime, anywhere
Expandability
access (via the 'LG ThinQ' mobile app)
- Without additional device, AC Smart 5 /
- Energy management and control according to
ACP 5 provides BACnet IP & Modbus TCP
usage and planning is possible with LG’s centralized
interface for BMS integration as well as its own
control solution
management function
- Interlocking with 3rd party equipment

002 / 003
WHY LG BECON HVAC SOLUTION

The perfect choice for innovative building management


LG BECON HVAC SOLUTION
Innovative building management solution in your hands.
Our optimized solutions provide integrated control for customers configuration of various equipment in building and
intuitive interface to maximize efficiency of operations.

SMART MANAGEMENT

ENERGY SMART EASY Standard III Premium Wi-Fi Modem


SAVING MANAGEMENT EXPANDABILITY Remote Controller Remote Controller (with LG ThinQ)

EASY EXPANDABILITY

ENERGY SAVING

Modbus Gateway ACP LonWorks Dry Contact

PDI AC Smart 5

ACP 5 ACS IO Module ACU IO Module

AC Manager 5 AC Ez Touch

004 / 005
WHY LG BECON HVAC SOLUTION

KEY BENEFITS

Energy Saving
LG BECON HVAC SOLUTION prevents energy waste through energy reduction solutions optimized for a variety of business
environments, providing excellent cost reduction.

Energy Management
Capacity Control
(Usage Graph & Navigation)

Time Limit Pre-Cooling and Heating


ENERGY
SAVING

Smart Management
Comfort and convenience play a major factor in the effectiveness of an HVAC Control Solution. We provides smart management with
control and monitoring, as well as a more pleasant environment through an air purify solution anytime anywhere.

Environment Display
Air Purify Solution
(Temperature, Humidity, CO2, Air Quality Level)

User Friendly Interface Visual Navigation


SMART
MANAGEMENT

IPv6 Network
Operation Trend View & Energy Report
(HTML5)

Easy Expandability
Integrated management of LG HVAC Control Solution links operations of LG Air conditioners with external systems for expanded coverage.
The embedded BMS enables direct connection with other systems without any additional BMS gateways to enable communication.
Units' operations (on / off, air flow adjustment, Etc) can be configured through triggers such as Air quality, humidity, CO2, and room
occupancy sensors. Also, 3rd Party Thermostat controllers are connectable with LG HVAC System.

BMS Protocol Embedded Interlocking with 3rd Party Equipment

EASY
EXPANDABILITY

006 / 007
WHY LG BECON HVAC SOLUTION

VARIOUS
INTEGRATED SOLUTIONS

Retail AC Ez Touch, PDI


Customized operation maintains the comfort of retail space
Hospitality Dry Contact
Meeting diverse needs

Power Consumption Distribution Solution Energy Management Solution Refrigerant Leak Detection Solution Interlocking Solution Using Dry Contact
In case of shared power consumption in a building, a solution to distribute the Since HVAC systems use a significant portion of any building’s total amount of Real-time refrigerant leak detection ensures a safe environment. 3rd party thermostats can be used to control LG Air conditioners in a room by
power consumption amount per tenant might be necessary. Electricity charges can energy, the energy saving functions of a controller can make a big difference. When refrigerant concentration exceeds 6,000ppm for 5 seconds, using a multi point dry contact. The dry contact enables basic control of air
be billed to each tenant by using output from the LG Power Distribution Indicator The energy navigation function enables you to set target values for energy the indoor unit will stop operation and alert users with a buzzer or light switch conditioners as well as making it possible to report the status and any errors
(PDI). An administrator is able to check the power usage for each space and consumption over a certain period of time. In addition, to achieve that value, the (Dry contact option). impacting the indoor unit. The Standard III remote control has a DO port. With
date as needed. If the PDI is used in conjunction with an LG central controller, the administrator can set the energy saving logic in 7 steps and predict the expected this DO port, it is possible to interlock the indoor unit with 3rd party devices such
results can be exported to Excel. usage relative to the target value. Active self-management enables energy savings as lighting, a fan, or a radiator, based on things like operation mode or current
through out the building. temperature. The indoor unit can be interlocked with various types of input
WHM
(Watt Meter) ➌ Stops Operation such as card key-tag, door sensor, human detection sensor etc. so that the air
Pulse Signal (Option : ring alarm) conditioner is automatically operated. In addition, the dry contact option settings
enable operation of air conditioner to maintain proper temperature when the
70% occupant is absent. This solution makes sure that the room does not overheat or
become too cold when unoccupied so that energy cost can be saved.

Power 100 kWh PDI Compressor Capacity IDU Operation IDU Operation ➋ Senses
Control Ratio Control Level Refrigerant
Leakage
B Office C Office
20 kWh Target
30 kWh
A Office D Office ➊ Refrigerant
Forecasting Leakage
30 kWh 20 kWh
Refrigerant
leakage
detection

008 / 009
WHY LG BECON HVAC SOLUTION

VARIOUS
INTEGRATED SOLUTIONS

Residential Standard III, Wi-Fi Modem


Creating a comfortable home
Office AC Smart 5
Supporting efficiency with flexibility

Easy Control Air Purify Solution Integration Solution with BMS Energy Management Solution
Wired remote controller is easy for usage. Anywhere! Anytime! Control IDU with Wi-Fi Modem through LG ThinQ. There are many BMS protocols used for the control of buildings’ various systems Since HVAC systems use a significant portion of any building’s total amount of
such as HVAC, lighting, power and security. LG has a wide range of gateway energy, the energy saving functions of a controller can make a big difference.
Convenient Air Quality Level Monitoring products for different protocols such as BACnet, Modbus, and LonWorks. The energy navigation function enables you to set target values for energy
• Flexible display • Easily Check Air Quality Status
- Dual display with air conditioner.
In addition, LG gateways include Stand-alone central control capability to act as a consumption over a certain period of time. In addition, to achieve that value, the
- PM10
- Zoom selected directory to - PM2.5
back-up controller of the BMS if needed. administrator can set the energy saving logic in 7 steps and predict the expected
increase legibility. - PM1.0 usage relative to the target value. Active self-management enables energy savings
Small / Medium size building Medium / Large size building
Visible - Graph View of measurement through out the building.
• Indoor CO2 level, Air Purify history Day, Week, Month, Year
Easy quality level, Humidity IDU ~ 64 : ACP LonWorks
LG ThinQ
• Navigation buttons, easy to use. • Alarm for filter change /
• Easy installation setting Remained time to change filters Air Purify Control
• Air Purify Set / Clear
IDU ~ 128 : AC Smart 5
(BACnet IP / Modbus TCP) 70%
Purification IDU ~ 64 : Modbus RTU
Energy Management IDU ~ 256 : ACP 5
(BACnet IP / Modbus TCP) Compressor Capacity IDU Operation IDU Operation
Mobile Remote Control Control Ratio Control Level
Users can check power consumption and • Using a Wi-Fi modem, control BMS System
running time report. (Weekly, Monthly, Yearly) and monitor air purify from your Target
Various energy managing settings such as LG ThinQ App. BMS Protocol
energy target setting, alarm pop-up indication, - Temp. / Mode / Fan / Air Flow Forecasting
and so on
time limit control and home leave operation are
available for efficient management.
* Wi-Fi modem (PWFMDD200) is an accessory.

010 / 011
WHY LG BECON HVAC SOLUTION

VARIOUS
INTEGRATED SOLUTIONS

Education AC Manager 5
Large capacity in compact size enhances space utilization
Public Facility AHU Comm.Kit
Suitable for large public facilities through group control

Total Control of Any Device Air Purify Total Solution Air Handling Unit (AHU) Solution Interlocking Solution by Using ACS IO Module
In order to manage multiple spaces and multiple buildings, the administrators Total management of air purify creates clean school environment for everyday. AHU is a suitable solution for cooling and heating in large space. With an LG AHU It is costly to introduce a BMS system to control multiple devices or systems in a
should be able to control systems from wherever they are. The LG central Using LG central controller, you can check the air condition of multiple zones at Comm.Kit (for both return air / supply air control) connected to the DX coil of the small building. With the ACS / ACU IO Module, various IO contact points
controller can be controlled from any web browser that supports HTML5. once and improve the overall air quality through simple control. AHU, LG VRF system can be applied to deliver conditioned air. (DI, DO, UI, AO) can be interlocked and integrated, while control is possible from
Now through the implementation of HTML5, the interface will look great and the LG central controller. This enables an efficient management of lighting, pumps
Air Quality Information
perform well on any device. - Air Quality Level Monitoring
and other devices in the building in conjunction with the HVAC system.
MULTI V 5
Air Purify Control Outdoor Unit
- Set / Clear

Saving Engineering Cost


Pump Lighting Fan Sensor
Strengthen
Maintenance Efficiency
EEV Signal
Air Quality Level Monitoring Air Purify Control View Air Quality Trends
System Air Conditioner
Communication ACS IO Module
Kit
EEV Kit
Send out Indoor Unit
Commercial Air Purifier
Air Purify
Ref. pipe (Liquid)
Ref. pipe (Gas) AC Smart (ACP)
• Daily (per hour),
Management office Library Main administration building Good • Easy setting of Air Purify Period (30 days) shows trends Communication
PC Tablet Mobile function (Set / Clear) AHU
• Excel output / easy to manage

012 / 013
LINE UP

LG BECON HVAC SOLUTION


LINE UP

Individual Control Centralized Control Centralized Control Integration Device

Wired Remote Controller Indoor Unit


Wireless Remote
Display Platform Gateway Facility Integrator Outdoor Unit AHU Kit
Controller
Standard Simple Dry Contact Control Accessory

Standard III (White) AC Ez ACP 5 ACP LonWorks PDI IO Module


Group Control Wire Communication Kit
(Power Distribution Indicator) (Input / Output Module)

PREMTB100 PQRCVCL0QW PWLSSB21H (Heat Pump) PQCSZ250S0 PACP5A000 PLNWKB000 Premium (8 ports) PQNUD1S40 Simple Dry Contact PZCWRCG3 For MULTI V IV, 5 Return / Room Air Control
PWLSSB21C (Cooling Only) (Indoor Unit ~ 32) (Indoor Unit ~ 256) (Indoor Unit ~ 64) Standard (2 ports) PPWRDB000 PDRYCB000 PVDSMN000 PAHCMR000
BACnet IP / Modbus TCP

Standard III (Black) Wi-Fi Modem AC Ez Touch AC Manager 5 Modbus RTU gateway ACS IO Module Variable Water Flow
Remote Temperature Sensor
(Input / Output Module) Control Kit

PREMTBB10 PQRCVCL0Q For Indoor Unit PACEZA000 PACM5A000 PMBUSB00A PEXPMB000 Dry Contact for Thermostat PQRSTA0 For MULTI V WATER IV Discharge / Supply Air Control
PWFMDD200 (Indoor Unit ~ 64) (Indoor Unit ~ 8,192) PDRYCB300 PWFCKN000 PAHCMS000

Standard II (White) AC Smart 5 PI485 Chiller Option Kit Zone Controller Low Ambient Kit Controller Module

PREMTB001 PQRCHCA0QW PACS5A000 For Indoor Unit (ERV) PCHLLN000 Dry Contact for Thermostat 4 Zones by thermostat For MULTI V IV, 5 Main Module
(Simple for Hotel) (Indoor Unit ~ 128) PHNFP14A0 (For using universal input) ABZCA PRVC2 PAHCMM000
BACnet IP / Modbus TCP PDRYCB320

Standard II (Black) ACU IO Module


Cool / Heat Selector
UIO

PREMTBB01 PQRCHCA0Q For Outdoor Unit


(Simple for Hotel) (SINGLE / MULTI / THERMA V) PEXPMB300 2 Points Dry Contact (For Setback) PRDSBM Communication Module
PMNFP14A1 PDRYCB400 PAHCMC000

Premium
UO Control Kit

PREMTA000
PREMTA000A PEXPMB200 For Modbus PAHCNM000
PREMTA000B PDRYCB500 (Max. 3 Outdoor Units)

UI Water Communication Module

PEXPMB100 PAHCMW000

EEV Kit
(Electronic Expansion Valve)

PRLK048A0 ( ~ 28 kW) PRLK396A0 PRLK594A0


PRLK096A0 ( ~ 56 kW) ( ~ 112 kW) ( ~ 168kW)

014 / 015
ARCHITECTURE

CONTROL SYSTEM LG BECON HVAC SOLUTION offers a diverse range of effective control solutions that satisfy specific needs of each building
and its user scene. These control systems are equipped with user-friendly interface, flexible interlocking environment,

ARCHITECTURE energy management and smart individual controller for optimized controlling conditions and smart building management

Integrated Controller Central Controller Central Controller Power Distribution Indicator CONTROLLER FOR INDOOR UNIT
(Medium / Large) (Small)

Individual Controller Dry Contact


AC Manager 5 ACP 5 AC Ez Touch PDI
Internet Internet Internet Wired R / C

PACM5A000 PACP5A000 PACEZA000


PDI Premium
BACnet IP / Modbus TCP PQNUD1S40 (8 ports) Card Key
AC Ez
PREMTA000
PDI Standard
PPWRDB000 (2 ports) PDRYCB000

PROPOSAL
CASE
AC Smart 5
PQCSZ250S0
Internet
PREMTB100
Motion
IO Module for
Sensor
Central Controller
PACS5A000
BACnet IP / Modbus TCP ACS IO Module

IO Module PDRYCB400
PREMTB001
Light

Thermostat
PEXPMB000
Pump

ACU IO Module PQRCVCL0QW (W)


PQRCHCL0QW (W)
BMS Gateway PVDSMN000 * For Hotel

Fan PDRYCB300
Wireless R / C (For thermostat 3rd party
ACP LonWorks G / W
via contact signal) Home
Internet Controller
PEXPMB100
PEXPMB200 PI485
PEXPMB300 Etc

PLNWKB000

Controller for AHU

PWLSSB21H (Heat Pump) PDRYCB320


PWLSSB21C (Cooling Only) Dry contact for Thermostat
Multi
PMNFP14A1 (For using universal input)
Split
BMS (For outdoor unit)
Building Protocol Modbus RTU G / W Wi-Fi Modem

Management AHU Comm.Kit AHU Control Kit


System
Single
AHU Comm.Kit AHU Control Kit Split
PMBUSB00A
PAHCMR000
(Return Air temp. control) PHNFP14A0 PDRYCB500
PAHCNM000 (For indoor unit) ERV (For thermostat
PWFMDD200
PAHCMS000 via Modbus RTU)
(Supply Air temp. control)

016 / 017
CONTENTS

LG BECON
HVAC
SOLUTION

INDIVIDUAL CONTROL
020 - 035

CENTRALIZED CONTROL

PROPOSAL
036 - 057

CASE
INTEGRATION DEVICE
058 - 094

PROPOSAL CASE
095 - 101

018 / 019
INDIVIDUAL CONTROL

INDIVIDUAL
CONTROL
FEATURE FUNCTIONS

Wired Remote Controller Wireless


Controller Name Wi-Fi
Remote
Modem
Premium Standard III Standard II Simple Simple (Hotel) Controller

Model Name

PREMTA000
PREMTB100 PREMTB001 PQRCVCL0QW PQRCHCA0QW PWLSSB21H (H / P)
PREMTA000A PWFMDD200
PREMTBB10 PREMTBB01 PQRCVCL0Q PQRCHCA0Q PWLSSB21C (C / O)
PREMTA000B

On / Off ○ ○ ○ ○ ○ ○ ○

Fan Speed Control ○ ○ ○ ○ ○ ○ ○

Temperature Setting ○ ○ ○ ○ ○ ○ ○

Mode ○ ○ ○ ○ - ○ ○

Auto Swing ○ ○ ○ ○ ○ ○

Vane Control
○ ○ ○ ○ ○ ○ ○
(Louver Angle)

Basic E.S.P
○ ○ ○ ○ ○ - -
(External Static Pressure)

Electric Failure
○ ○ ○ ○ ○ - ○
Compensation

Indoor Temperature Display ○ ○ ○ ○ ○ ○

All Button Lock


○ ○ ○ ○ ○ - -
(Child Lock)

Schedule / Timer Weekly - Yearly Weekly - Yearly Weekly - - Sleep / On / Off Weekly

Wi-Fi AP Mode Setting ○ ○ ○ ○ ○ ○ -

Additional Mode Setting 1) ○ ○ ○ - - - -

Time Display ○ ○ ○ - - ○ -

Humidity Display ○ ○ - - - - -

Advanced Lock
(Mode, Set point, Set point Advanced Lock Advanced Lock - - - - -
range, On / Off Lock)

Filter Sign ○ ○ ○ - - - -

Energy Management 2) ○ ○ ○ - - - -
Advanced
Dual Set Point ○ ○ - - - - -

Human Detection - ○ - - - - -

Temp, Humidity
○ ○ - - - - -
Compensation

Air Purify Control - ○ - - - ○ ○

Air Quality Level - ○ - - - - ○

Dual Vane (6 Airflows mode) - ○ - - - ○ ○

Operation Status LED ○ ○ ○ ○ ○ - -

Wireless Remote Controller


○ 3) - ○ 3) ○ 3) ○ 3) - -
Receiver

INDIVIDUAL
ETC Display 5 inch Color 4.3 inch Color 4.3 inch mono 2.6 inch mono 2.6 inch mono 2 inch mono -

Size (W x H x D, mm) 137 x 121 x 16.5 120 x 120 x 16 120 x 120 x 16 64 x 120 x 15 64 x 120 x 15 51 x 153 x 26 -

Black Light Control for


○ ○ - - - - -
Screen Saver

CONTROL ※ ○ : Applied, - : Not Applied


1) It might not be indicated or operated at the partial product.
2) Centralized control (PACEZA000 / PACS5A000 / PACP5A000 / PLNWKB000) and PDI (PQNUD1S40 / PPWRDB000) should be installed for this function.
3) For ceiling type duct
Note : 1. Indoor unit should have functions requested by the controller.
2. If you need more detail, please refer to the manual of product. (http://partner.lge.com : Home > Doc.Library > Manual)

020 / 021
STANDARD III STANDARD III
WIRED REMOTE CONTROLLER WIRED REMOTE
PREMTB100 (White), PREMTBB10 (Black)

4.3” COLORED SCREEN


CONTROLLER Size (W x H x D, mm) : 120 x 120 x 16

WITH MODERN DESIGN

NEW COMFORT
MODERN DESIGN & RELIABILITY
(Air Purify)

CONVENIENCE ENERGY
MANAGEMENT

SCHEDULE INTERLOCKING

Design Comfort & Air Purification Energy Contents Advanced Functions


- 4.3 inch color LCD / Intuitive GUI - CO2 level monitoring (For ERV) - Power consumption monitoring - Comfort cooling setting
- Seamless design / Touch button - Air quality level monitoring - Operation time monitoring - Smart Load Control setting
- Humidity sensor embedded - Air purify control - Temperature setback - Outdoor unit low noise setting
- Time limit control - Defrost noise setting
- ODU capacity control
- Schedule functions
INDIVIDUAL CONTROL

STANDARD III

INDIVIDUAL
CONTROL
WIRED REMOTE CONTROLLER

PREMTB100 (White) / PREMTBB10 (Black)

4.3 inch colored screen with modern design

Model Name PREMTB100 / PREMTBB10


On / Off ○
Fan Speed Control ○
Temperature Setting ○
Mode Cool / Heat / Dry / Fan / Auto
Touch Button
Additional Mode Setting 1) Energy-Saving Cooling / Robot Cleaning / Heater / Humidification / Comfort Cooling
Auto Swing ○
Vane Control (Louver direction) ○
E.S.P (External Static Pressure) 2) ○
Reservation Simple / Sleep / On & Off timer / Weekly / Yearly / Holiday
Time Display ○
Electric Failure Compensation ○
Lock All / On & Off / Mode / Set temperature range
Cool Heat Dry Fan Auto Filter Sign ○ (Remain time + Alarm)
Check Energy Usage 3) / Check Operation Time / Target Setting (Energy, Operation Time) / Time Limit Operation / Alarm
Energy Management
Popup / Initialization Usage Data
Operation Status LED ○
Air Purify Control 4) ○
Air Quality Level 4) ○
Indoor Temperature Display ○
Indoor Humidity Display ○
Human Detection ○
Display 4.3 inch TFT color LCD (480 x 272)
Size (W x H x D, mm) 120 x 120 x 16
Black Light for Screen Saver ○
Home Leave 2 set points control

※ ○ : Applied, - : Not Applied


Comfort Level Energy Contents Error History 1) The function is available in some product. (Refer to the product data Book).
2) This function is available for duct type.
3) This function requires PDI (PQNUD1S40 / PPWRDB000) to be installed.
4) This function is available for indoor units that provide corresponding function.
Note : 1. Indoor unit needs to have functions requested by the controller.
2. 2
 set points control works normally with MULTI V Heat Recovery and Single Split Heat Pump. But in case of MULTI V Heat Pump, It may not work properly.

• PROVIDES OPTIMIZED CONTROL PERFORMANCE IN


ANY BUSINESS ENVIRONMENT EXCELLENT USABILITY
WITH MODERN DESIGN & EASY INTERFACE

022 / 023 024 / 025


INDIVIDUAL CONTROL

STANDARD III

INDIVIDUAL
CONTROL
WIRED REMOTE CONTROLLER Features & Benefits

Air Quality Level Display Energy Savings

Easy check for indoor air quality Energy Management


· PM10 / PM2.5 / PM1.0 · Status / Monitoring - Energy Monitoring & Alarm
Real-time and day / week / month / year energy usage
‘Good’ ‘Moderate’ ‘Unhealthy’ ‘Poor’
monitoring is possible. In addition, it can set target for
energy usage and operation time, and alarm will be
13 79 149 258 displayed when exceeded. Instantaneous Power Check Energy Usage Target Setting
10 34 74 257
※ PDI (PQNUD1S40 / PPWRDB000) is required.
8 33 73 256

Time Limit Control


- Monitoring the unit’s continuous running time.
And prevent the wasting energy by turning the unit off
automatically.

Classification Good Moderate Unhealthy Poor


* PM10 (㎍ / m3) 0 ~ 54 55 ~ 154 155 ~ 254 255 ~
* PM2.5 (㎍ / m3) 0 ~ 12 13 ~ 35 36 ~ 55 56 ~
* PM1.0 (㎍ / m3) 0 ~ 12 13 ~ 35 36 ~ 55 56 ~

Note : Display color may change depending on the region / country.


This function is available for indoor units that provide corresponding function.
* PM (Particulate matter)
Schedule Function
- PM10 : Coarse Particulate matter / PM2.5 : Fine Particulate matter / PM1.0 : Ultra Fine Particulate matter
- PM designated as a carcinogen as like an asbestos, widely known as carcinogen.
If the dust diameter is under 10 micrometers, it is PM10. And under 2.5 micrometers, it’s PM2.5. Simple Schedule Status Exception Day Settings
Standard III remote controller provides clock type daily schedule. Possible to set up exceptional date on regular schedule.
Environment Display
Displaying environment information for the more user comfort
Temperature / Humidity / Comfort level / CO2 concentration

External Device On / Off


External Equipment Control Customized Interlocking Control
Dual Set Point User can control the external equipment through additional User can create a automatic control pattern.
contact signal output. For example controlling the external heater switches on
Auto changeover for convenience Temperature Thermo-off Indoor temperature when temperature drops below or rises above
- Indoor unit will keep the indoor temperature within the a certain temperature.
Cooling set point
range of dual set point by automatically switch the unit for Unoccupied Cooling
operation. Cooling Set Point
for Occupied
Setback for energy savings and comfort Heating Set Point
Occupied Unoccupied
for Occupied
- In the user's absence, the room temperature will remain Heating
Heating Set Point
between two set points rather than switching off providing for Unoccupied
Cooling Heating
quick comfort when the mode is changed to occupied. Time
※ This function is for Heat Recovery system or Single heat pump. Otherwise it is not guaranteed. Arrive at a room Leave a room

026 / 027
INDIVIDUAL CONTROL

PREMIUM

INDIVIDUAL
CONTROL
WIRED REMOTE CONTROLLER Features & Benefits

Easy Energy Management Easy Scheduling


Full Touch
Screen
- Check the operation hour or electricity usage - Daily, Weekly, Yearly schedule function
- Comparison of usage compared to last year - Schedule pattern setting
- Set the target usage and time - Schedule copy

PREMTA000 1) / PREMTA000A 2) / PREMTA000B 3)

5 inch full touch screen with a premium design


Dual Set Point

- Auto changeover switching the operation mode Temperature

automatically
Cooling
- Setback (Leave Home) Changing status by occupied / Upper
* Supported languages list
Temperature
1) English / Portuguese / Spanish / French unoccupied limit
2) English / Italian / Russian / Chinese Setback
* This function is only for Heat Recovery system and Single heat pump.
3) English / German / Polish / Czech Auto Changeover
Lower
Temperature
Model Name PREMTA000 / PREMTA000A / PREMTA000B limit
Heating
On / Off ○
Fan Speed Control ○
Time
Temperature Setting ○ Arrive at Home Leave Home
Mode
Additional Mode Setting 1)
Cool / Heat / Dry / Fan / Auto
Energy-Saving Cooling / Robot Cleaning / Heater / Humidification
Group Control
Auto Swing ○
Vane Control (Louver direction) ○
- Max. 16 Indoor units by one remote controller
E.S.P (External Static Pressure) 2) ○
Reservation Simple / Sleep / On / Off / Weekly / Yearly / Holiday
Time Display ○
Indoor unit 1 Indoor unit 2 Indoor unit 3
Electric Failure Compensation ○
Child Lock ○
Master Slave Slave
Filter Sign ○ (Remain time + Alarm) 1 1
Check Energy Usage 3) / Check Operation Time / Target Setting (Energy, Operation Time)
Energy Management
/ Time Limit Operation / Alarm Popup / Initialization Usage Data
Red (12V)
Operation Status LED ○ Yellow (Sig)
Yellow (Sig) Yellow (Sig)
Black (GND) Black (GND)
Indoor Temperature Display ○ Black (GND)

Wireless Remote Controller Receiver ○ 4)


Display 5 Inch TFT color LCD (480 x 272)
Size (W x H x D, mm) 137 x 121 x 16.5
Black Light for Screen Saver ○
Home Leave 2 Set Points Control 2 2
※ ○ : Applied, - : Not Applied
1) It might not be indicated or operated at the partial product. Master
2) This function is available for duct type.
3) This function requires PDI (PQNUD1S40 / PPWRDB000) to be installed.
4) For ceiling type ducted unit
Note : 1. Indoor unit needs to have functions requested by the controller
2. 2 set points control works normally with MULT V Heat Recovery and Single Split Heat Pump. But in case of MULTI V Heat Pump, It may not work properly

028 / 029
INDIVIDUAL CONTROL

STANDARD II WIRED SIMPLE WIRED

INDIVIDUAL
CONTROL
REMOTE CONTROLLER REMOTE CONTROLLER

PREMTB001(White) / PREMTBB01(Black) PQRCVCL0QW (White) / PQRCVCL0Q (Black)


PQRCHCA0QW (White) / PQRCHCA0Q (Black)
Providing easy control of one or a group of indoor units with various functions.

A simple way to control office or hotel systems Model Name


PQRCVCL0QW / PQRCHCA0QW /
PQRCVCL0Q PQRCHCA0Q
in a compact design.
On / Off ○ ○
Fan Speed Control ○ ○
Temperature Setting ○ ○
Cool / Heat / Dry / Fan /
Mode -
Auto
Auto Swing ○ ○
Vane Control
○ ○
(Louver direction)
E.S.P
○ ○
(External Static Pressure)
Electric Failure
○ ○
Compensation
Child Lock ○ ○
Indoor Temperature
Features & Benefits Display
○ ○
Wireless Remote
• Wired remote controller that can implement various functions such as scheduling or filter alert. Controller Receiver
○ 1) ○ 1)
Size (W x H x D, mm) 70 x 121 x 16 70 x 121 x 16
Features & Benefits
Black Light ○ ○
• Small remote control with minimal functionality. ※ ○ : Applied, - : Not Applied
Model Name PREMTB001 / PREMTBB01 1) For ceiling type ducted unit
On / Off ○ Note : Indoor unit needs to have functions requested by the controller.

Fan Speed Control ○


Temperature Setting ○
Mode Cool / Heat / Dry / Fan / Auto
Additional Mode Setting Energy-Saving Cooling / Robot Cleaning / Heater / Humidification
Auto Swing
Vane Control (Louver direction)

○ WIRELESS
E.S.P (External Static Pressure) ○
Reservation
Time Display
Simple / Sleep / On / Off / Weekly / Holiday

REMOTE CONTROLLER
Electric Failure Compensation ○
Child Lock ○
Filter Sign ○ (Remain time + Alarm)
Operation Status LED
Indoor Temperature Display


PWLSSB21H (Heat Pump), PWLSSB21C (Cooling Only)
Wireless Remote Controller Receiver ○ 1)
Size (W x H x D, mm) 120 x 120 x 16
Black Light ○
Handy and portable wireless type Model Name PWLSSB21H (H / P), PWLSSB21C (C / O)
Power Consumption Monitoring ○ 2) On / Off ○
Check Model Information ○ Fan Speed Control ○ 1)
Temperature Setting ○
※ ○ : Applied, - : Not Applied Mode Cool / Heat / Dry / Fan / Auto
1) For ceiling type ducted unit Additional Mode Plasma Purification / Energy-Saving Cooling /
2) This function requires PDI (PQNUD1S40 / PPWRDB000) to be installed. Setting Robot Cleaning / Auto Dry
Note : Indoor unit needs to have functions requested by the controller. Auto Swing ○
Vane Control

(Louver direction)
Reservation Sleep / On / Off
Time Display ○
Indoor Temperature

Display
Sleep Mode Auto Max. 7 hours
Size (W x H x D, mm) 51.4 x 153 x 26
Features & Benefits ※ ○ : Applied, - : Not Applied
1) For some products, you can use “slow” fan speed function.
• Easy to use while moving.
• Main functions are available.

030 / 031
INDIVIDUAL CONTROL

INDIVIDUAL
CONTROL
WI-FI MODEM

PWFMDD200

Control conditioners by using internet devices as Android or iOS smartphones.

Features & Benefits


Wi-Fi • User can enjoy anytime, anywhere access with Wi-Fi equipped device through LG's ThinQ mobile app.
Modem • This allows the user to access the unit remotely to switch unit on or off before or after leaving the vicinity.
• LG’s exclusive Home Appliances control app (LG ThinQ) is available.
• Simple operation for various functions.
- On / Off - Reservation (Sleep, Weekly On / Off)
USB - Operation Mode - Energy Monitoring 2)
Wire - Current / Set Temperature - Filter Management
- Fan Speed - Error Check
- Vane Control 1) - Air Purify 3)

Model Name PWFMDD200


Size (W x H x D, mm) 48 x 68 x 14
Interfaceable Products System Air Conditioner 3)
Connection Type Indoor unit 1:1
Note : 1. Functionality may be different according to each IDU model.
Communication
2.4 GHz 2. User interface of application shall be revised for its design and contents
Frequency
improvement.
Wireless Standards IEEE 802.11b / g / n
LG ThinQ 3. Application is optimized for smartphone use, so it may not be well
LG ThinQ (Android v4.1(Jellybean) or higher, functioning with tablet devices.
Mobile Application
iPhone iOS 9.0 or higher) 1) Vane Control may not be possible according to the type of Indoor unit.
Optional Extension 2) LG Centralized controller and PDI installation is required for this function.
PWYREW000 (10m extension)
Cable 3) For the compatibility with Indoor unit, please contact regional LG office.

Installation Scene

Control box

Indoor unit PCB

Control panel
USB cable Wi-Fi modem
※ Search “LG ThinQ” on Google play or Appstore then download the app.
※ Internet service with Wi-Fi connection has to be available.
※ The Wi-Fi communication distance and reliability may be vary due to the type of Wi-Fi router and the installation environment, Please refer to the manual.

032 / 033
INDIVIDUAL CONTROL

INDIVIDUAL
CONTROL
WI-FI MODEM

LG ThinQ Connectivity LG ThinQ Mobile App

Connection (Pairing) Order Simple operation for various functions


➊ Make LG account on LG ThinQ (Application) and login. On, Off, Current Temp., Mode, Set Temp.
➋ Select the installed product and set AP (Access Point) mode by wired / wireless remote controller.
➌ Select the Wi-Fi networkv that will be used and insert the passwords.
➍ Product registration progress is completed.
* 5GHz networks may not be supported.

4 LG ThinQ
3

Internet <Day> <Night>


Service Provider
Vane Control Air Purify

2
1

Easy Management
Reservation Energy Monitoring Smart Diagnosis Filter Management

034 / 035
CENTRALIZED CONTROL

FEATURE FUNCTIONS

CENTRALIZED
CONTROL
Controller Name AC Ez AC Ez Touch AC Smart 5 6) ACP 5 6) ACP LonWorks AC Manager 5 7)

Model Name

PQCSZ250S0 PACEZA000 PACS5A000 PACP5A000 PLNWKB000 PACM5A000


DO - - 2 4 2 -
DI - 1 2 10 2 -
IDUs 32 64 128 256 64 8,192
ERV 32 64 128 256 64 8,192
Product Max. A / C + ERV 32 64 128 256 64 8,192
Connectable
No. AHU - - 16 16 16 5) 16 x 32
Chiller - - 5 Optional 4) 10 Optional 4) - 10 x 32
Commercial Air Purifier 1) - - 64 128 - 128 x 32
Air Conditioner ○ 3) ○ ○ ○ ○ ○
Ventilation (ERV / ERV DX) ○ 4) ○ ○ ○ ○ ○
Heating - ○ ○ ○ ○ ○
Compatibility AHU - - ○ ○ ○ ○
Chiller - - ○ 5) ○ 5) - ○
Commercial Air Purifier 1) - - ○ 5) ○ 5) - ○
ACS IO - - ○ 5) ○ 5) ○ 5) ○
Add Drawing - - ○ 5) ○ 5) ○ 5) ○
Group Management - ○ ○ 5) ○ 5) ○ 5) ○
Auto Changer Over - ○ ○ 5) ○ 5) ○ 5) ○
Set Back - ○ ○ 5) ○ 5) ○ 5) ○
Additional
Dual Setpoint - ○ ○ ○ ○ 5) ○
Function
Change Alarm - Filter Filter Filter Filter Filter
Indoor Unit Lock ○ 8) ○ ○ ○ ○ 5) -
Cycle Monitoring - - ○ ○ ○ 5) ○
Air Purify - ○ 5) ○ 5) ○ 5) - ○
Schedule ○ ○ ○ 5)
○ 5) ○ 5) ○
Peak Priority Control - ○ ○ ○ ○ 5) ○
Auto Control Outdoor Unit Capacity Control - - ○ 5) ○ 5) ○ 5) ○
Control Time limit control - - ○ 5) ○ 5) ○ 5) ○
Interlocking - - ○ 5) ○ 5) ○ 5) ○
Energy Navigation - - ○ 5) ○ 5) - ○
Power - ○ ○ ○ ○ 5) ○
Energy Gas - - ○ ○ ○ 5) ○
Report Run time - - ○ 5) ○ 5) ○ 5) ○
Save to PC / USB (Excel) - - PC / USB 5) PC PC PC
Trend Reporting - - - - - ○
Report (Control / Error) - Error ○ 5) ○ 5) ○ 5) ○
History Send Email - - ○ 5) ○ 5) ○ 5) ○
Save to PC / USB (Excel) - - PC / USB 2) PC 2) ○ 5) PC 2)
Summer Time - ○ ○ 5) ○ 5) ○ 5) ○
Outdoor Unit Oil-Return Operation - - ○ 5) ○ 5) ○ 5) -
etc
User Authority - Password ○ 5) ○ 5) ○ 5) ○

CENTRALIZED
PC Access - ○ ○ 5) ○ 5) ○ 5) ○

※ ○ : Applied, - : Not Applied


1) The Commercial Air purifier must additionally install PI485(PHNFP14A0).
2) Save to PC / USB function will be available from 2021.

CONTROL
3) Except for some feature (Individual lock, Limit temp., etc.)
4) Except for some feature (User mode, additional function, etc.)
5) This function is not applied for BMS points.
6) Without additional device, ACP 5 and AC Smart 5 provide BACnet IP and Modbus TCP interface for BMS.
7) ACP 5 or AC Smart 5 is required.
8) Hard Lock

036 / 037
CENTRALIZED CONTROL

AC EZ TOUCH
Features & Benefits

CENTRALIZED
CONTROL
PC Access
PC
Users can control each space efficiently through PC access.

IDU
...

Internet Internet
AC EZ TOUCH
IDU * IPv6 supported
...
- Fixed Public IP is recommended. If not, router’s configuration of NAT is required.
- Open port 80 & 9300

ERV Energy Statistics (with PDI) Energy Mode

PACEZA000 Statistics of operational status (Time, Power consumption) When using energy mode function, operation Modes from
are provided to help make intelligent system operation cooling to fan or heating to off mode by force.
decisions. (It is available only for operating indoor unit)
Smart management with 5 inch touch screen for small site.

Model Name PACEZA000


Size (W x H x D, mm) 137 x 121 x 25
Interfaceable Products MULTI V / ERV / ERV DX / Hydro Kit / THERMA V
Maximum number of units 64
Individual / Group Control On & Off / Mode / Temperature / Fan speed
Individual Controller Lock
Error Check
Temperature / Mode / Fan speed / All

Air Purify Control & Monitoring
Slave Mode

(Interlocking with higher level controller)
Schedule Weekly / Monthly / Yearly / Exception day
Remote Access By client S / W
Emergency Stop & Alarm Display ○
Power Consumption Monitoring (with PDI) ○
Auto Changeover / Setback ○
Temperature Limit ○
Operation History Error record
ODU Low Noise 1) ○
Daylight Saving Time ○
External IO Port DI 1
IPv6 Support ○
Air Purify Control ○
Air Quality Level ○

※ ○ : Applied, - : Not Applied


1) It is only available in some products.

038 / 039
CENTRALIZED CONTROL

AC EZ TOUCH AC EZ

CENTRALIZED
CONTROL
Alarm Indicator

It shows errors and alarm information. Users can respond


immediately according to alarm indicator therefore HVAC
system is monitored consistently.

Schedule • MULTI V 5 • MULTI V • MULTI V S • MULTI SPLIT • ERV


• MULTI V IV WATER IV • SINGLE SPLIT
• MULTI V III • MULTI V
Schedule control allows user to set the events in advance
• MULTI V II WATER II
to maximize system performance. Also, by blocking
unnecessary operation, it prevents a waste of energy. Appropriate PI485 should be used according to PDB.

PQCSZ250S0

Easy to manage up to 32 indoor units, including ERV with simple interface.

Features & Benefits


• 32 indoor units control
• Weekly Schedule

Group / Individual Control • Individual / Group Control

User can control each indoor unit individually or by group by


simply clicking each unit on control screen. Model Name PQCSZ250S0
Size (W x H x D, mm) 190 x 120 x 20
Interfaceable Products MULTI V / ERV / ERV DX
Display LED / LCD Display
Power DC 12V
Maximum number of units 32
Individual / Group Control On & Off / Mode / Temperature / Fan speed
Individual Controller Lock All
Error Check ○
Slave Mode (Interlocking with higher level controller) ○
Schedule Weekly

※ ○ : Applied, - : Not Applied

040 / 041
AC SMART 5
10” WITH HTML5 GUI
AC SMART 5 PACS5A000
Size (W x H x D, mm) : 253.2 x 167.7 x 28.9

TOUCH SCREEN
FOR EASY CONTROL
Lobby

MAX. 128 ENERGY


IDU CONTROL MONITORING
Lobby

Lobby

SCHEDULE AIR PURIFY

MAP VIEW MULTI LEVEL


(Visual navigation) GROUPING

MENU BAR STATUS VIEWING CONTROL MENU


CENTRALIZED CONTROL

AC SMART 5

CENTRALIZED
CONTROL
PC SMARTPHONE TABLET PACS5A000

10-inch touch screen with HTML5 GUI (Graphic User Interface) for easy control.

BMS

INTERNET

AC SMART 5

Model Name PACS5A000


Size (W x H x D, mm) 253.2 x 167.7 x 28.9
MULTI V / ERV / ERV DX / Hydro kit /
Interfaceable Products THERMA V / AHU Kit / LG Chiller 1) / Commercial Air Purifier
rd
3 party interlocking Maximum number of units 128
CH1 CH2 Individual / Group Control On & Off / Mode / Temperature / Fan speed
Facility Sensor ODU & IDU Commercial
Air Purifier Individual Controller Lock Temperature / Mode / Fan speed / All
Comfort Cooling / ODU Low Noise / ODU Defrost Mode / Comfort Level display /
Advanced Function Setting and Display 2) CO2 Level display (for ERV / ERV DX) / Night Time Free Cooling (for ERV / ERV DX)

Motion Temp. CO2 Error Check ○


ACS IO Multi V Slave Mode (Interlocking with higher level controller) ○
Cooling tower Pump Therma V
Etc. Schedule Weekly / Monthly / Yearly / Exception day
Web Access ○
Emergency Stop & Alarm Display ○
ACU IO
Power Consumption Monitoring (with PDI) ○
Valve Fan Emergency Lighting Multi / Single
Auto Changeover / Setback ○
Temperature Limit ○
Chiller ERV
Operation Time Limit ○
Visual Navigation ○
Operation Trend ○
Air Purify Control ○
Chiller
Centrifugal Absorption Screw Invert Air Quality Level ○
Option Kit
Scroll
Interlock Control ○

OR Virtual Group Control ○


ODU Capacity Control ○
Energy Navigation (with PDI) ○
Daylight Saving Time ○
AHU AHU
External IO Port DI 2 / DO 2
Comm.Kit
(For Supply / BMS Integration 3) BACnet IP / Modbus TCP
Discharge Air Control)
IPv6 Support ○

※ ○ : Applied, - : Not Applied


Comm.Kit 1) Chiller Option Kit (PCHLLN000) is required.
(For Return /
2) It is only available in some products.
Room Air Control)
Control Kit 3) For the detail point list, please refer to the installation manual.
• THE CENTRAL CONTROLLER ALLOWS CONTROL OF THE
According to CH1 setting, normal ODU can be connected to CH1.
LG HVAC SYSTEM TO VARIOUS PLATFORMS (Flexible wiring design with 2 ports)
(Touch screen, PC, Smartphone, Tablet) Appropriate PI485 should be used according to PDB (Product Data Book).
For details, refer to the product PDB or manual.
042 / 043 044 / 045
CENTRALIZED CONTROL

AC SMART 5
Features & Benefits

CENTRALIZED
CONTROL
Air Purify Total Solution Energy Management

Air Purify Control The energy navigation function allows the air conditioner’s
Air Purify operational energy usage to be manged monthly, weekly
and yearly. By analyzing present energy consumption and
comparing with the plan, overuse of system operational
- Easy setting of Air Purify
costs can be prevented.
function (Set / Clear)

Air Quality Level Monitoring

Good
* The Commercial Air purifier must additionally install PI485(PHNFP14A0).
System Air Conditioner Commercial Air Purifier
Building Management System (BMS) Integration

Without additional device, AC Smart 5 provides BACnet IP


Advanced Network Accessibility BACnet over IP BMS
& Modbus TCP interface for BMS integration as well as its
own management function.
AC Smart 5 reflects the state of the art of network
technology trend. IPv6 (Internet Protocol version 6), which
is the most recent version of the Internet Protocol provides IPv6
accessibility to the IPv6 compatible network environment. Network
In addition, HTML5 allows you to easily control LG HVAC
system on a variety of platforms (PC, Mobile, Tablet), at any HTML5 web design
time and from any location, not just on the touch screen.

Interlocking with 3rd Party Equipment


Visualized Control Multi Level Group Composition AC Smart 5 can make operation scenario with 3rd party LG SAC

equipment by ACS IO Module. Control coverage is expanded. ODU

Visual navigation enables controlling and monitoring the unit User can make frequent and multi level group to control and (Air conditioner only → Sensors, Fans, Pumps, Switches…)
on floor plan view for the intuitive management. monitor the device easily. Air Water Hydro Kit IDUs
AC Smart 5 cooled cooled

Building West

Classroom 3rd party interlocking


Floor #1 Sensor Facility
East

West
Temp. CO2 Cooling Emergency
Floor #2 tower
Facilities
Occupancy
Faculty Valve Fan

...
Floor #1
Sensor
East Expansion
West Control Coverage
Floor #2
Temp. Lighting
ACS IO

046 / 047
CENTRALIZED CONTROL

ACP 5

CENTRALIZED
CONTROL
PC SMARTPHONE TABLET PACP5A000

Advanced solution for BMS integration up to 256 units via BACnet and Modbus protocol as well as
its own smart management function with web server interface.
BMS
Model Name PACP5A000
Size (W x H x D, mm) 270 x 155 x 65
INTERNET MULTI V / ERV / ERV DX / Hydro kit /
Interfaceable Products THERMA V / AHU Kit / LG Chiller 1) / Commercial Air Purifier
Maximum number of units 256
Individual / Group Control On & Off / Mode / Temperature / Fan speed
Individual Controller Lock Temperature / Mode / Fan speed / All
Comfort Cooling / ODU Low Noise / ODU Defrost Mode / Comfort Level
Advanced Function Setting
ACP 5 and Display 2)
display / CO2 Level display (for ERV / ERV DX)
/ Night Time Free Cooling (for ERV / ERV DX)
Error Check ○
Schedule Weekly / Monthly / Yearly / Exception day
CH 5 ~ 6 CH1 ~ 4 Web Access ○
Emergency Stop & Alarm ○
Display
OR OR Power Consumption Monitoring ○
(with PDI)
Auto Changeover / Setback ○
AHU Chiller ACS IO Comm.Kit
rd Temperature Limit ○
Controller Option Kit 3 party interlocking
Operation Time Limit ○
AHU Chiller Facility IDU ERV Commercial Air AHU Visual Navigation ○
Purifier Operation Trend ○
Air Purify Control ○
Air Quality Level ○
Interlock Control ○
Centrifugal Cooling Tower Pump
Virtual Group Control ○
ODU Capacity Control ○
Energy Navigation (with PDI) ○
Daylight Saving Time ○
External IO Port DI 10 / DO 4
Absorption Valve Fan
BMS Integration 3) BACnet IP / Modbus TCP
IPv6 Support ○
Sensor
※ ○ : Applied, - : Not Applied
1) Chiller Option Kit (PCHLLN000) is required.
2) It is only available in some products.
Screw Motion Temp. CO2 3) For the detail point list, please refer to the installation manual.

Etc.
Integrated Management
The Commercial Air Purifier can be used with LG central controller to monitor and control.

Invert Scroll Emergency Lighting


LG VRF
SYSTEMS

Advanced Network Accessibility Energy Navigation BACnet IP & Modbus TCP Air Purify Control / Internet
Monitoring
BACnet over IP BMS

IPv6
ACP 5
Network
Commercial
HTML5 web design Air Purifier

Good
* Fix Public IP is mandatory.
* Router’s Configuration of NAT is mandatory. Open port 80 & 9300.

048 / 049
CENTRALIZED CONTROL

AC MANAGER 5

CENTRALIZED
CONTROL
PC SMARTPHONE TABLET PACM5A000

Multiple ACP and AC Smart integration solution to manage multi sites up to 8,192 units as
a single system.

INTERNET

AC MANAGER 5

Max.
or 32
ACP 5 AC SMART 5
Model Name PACM5A000
Size (W x H x D, mm) 270 x 155 x 65
Interfaceable Products MULTI V / ERV / ERV DX / Hydro kit / THERMA V / AHU Kit / LG Chiller 1) / Commercial Air Purifier
ODU / IDU & ERV Chiller & AHU 3 party Device
rd
Commercial Air Purifier
Maximum number of units 8,192 (Supports 32 ACP 5 or AC Smart 5)
Individual / Group Control On & Off / Mode / Temperature / Fan speed
Individual Controller Lock Temperature / Mode / Fan speed / All
Chiller AHU Error Check ○
Option Kit Controller ACS IO Module
Schedule Weekly / Monthly / Yearly / Exception day
Web Access ○
Emergency Alarm Display ○
Power Consumption Monitoring (with PDI) ○
Centrifugal Cooling Tower Pump
Auto Changeover / Setback ○
Temperature Limit ○
Operation Time Limit ○
Absorption Valve Fan Visual Navigation ○
Operation Trend ○
Air Purify Control ○
Air Quality Level ○
Screw Motion Temp. CO2 Interlock Control ○
Virtual Group Control ○
ODU Capacity Control ○
AHU Energy Navigation (with PDI) ○
Comm.Kit
Invert Scroll Emergency Lighting
※ ○ : Applied, - : Not Applied
1) Chiller Option Kit (PCHLLN000) is required for ACP 5 or AC Smart 5.
Note : AC Manager 5 required for ACP 5 or AC Smart 5

Max.
AC Manager 5 Control tower AC Manager 5 32
ACP 5 ACP 5 AC Smart 5

050 / 051
CENTRALIZED CONTROL

AC MANAGER 5
Features & Benefits

CENTRALIZED
CONTROL
Up to 8,192 Connections for Indoor Units Advanced Network Accessibility & User Friendly GUI

Administrators can easily and conveniently manage a variety Max. IDU 256 EA As an advanced central controller, AC Manager 5 offers
of LG HVAC equipment. Also, it is available to manage many ... flexible interface for each user by assessing the device
buildings or areas at one place via AC Manager 5. screen and automatically customizing the layout to provide
Max. IDU 128 EA
the most optimized interface.
...

...

...
Max. IDU 256 EA

...

Smart Air Purify Solution Energy Navigation & Energy Usage Graph

Total management of air purify function creates clean environment for everyday. Energy navigation is the function to set the target usage
amount to limit the monthly power consumption and to
Air Quality Multi Status view Air Quality Summary Widget control so that the total accumulated power consumption

Air Quality Level Air Quality Level


does not exceed the target usage amount. It performs
total of 7 control levels with the estimated / actual usage
Good Good amount exceeding ratio compared to the monthly target
Average Air Quality Average Air Quality
Good Moderate Good Moderate usage amount. For the control method, there are indoor unit
Unhealthy Poor Unhealthy Poor operation ratio, outdoor unit capacity control, and indoor Compressor Capacity IDU Operation IDU Operation
unit operation control. Control Ratio Control Level
No. Name Group Fine dust Status
1 AIR PURIFIER_1F New 96 Good
- Average Value
2 AIR PURIFIER_1E New 95 Good
- View by Device 3 AIR PURIFIER_1D New 94 Good

(Name, Air Quality value, Status) 4

5
AIR PURIFIER_1C

AC_01
New

New
93

93
Good

Poor
Peak Control Multi Level Group Composition
6 AIR PURIFIER_1B New 92 Moderate

7 AIR PURIFIER_1A New 91 Poor

8 AIR PURIFIER_19 New 90 Moderate This function can reduce electricity use. There are two User can make frequent and multi level group to control and
9 AC_02 New 90 Poor
kinds of control logic. Energy saving effect by indoor unit monitor the device easily.
10 AIR PURIFIER_18 New 89 Moderate

11 AIR PURIFIER_17 New 88 Poor operation rate control. Load management effect by outdoor
unit capacity control.
Building West

Air Purify Control View Air Quality Trends Classroom

Operation ratio (IDUs) Control ODU Capacity Control Floor #1

Air Purify Send out East


9 Step Operation Rate (%)
[ 0, 40, 45, 50, 60, 70, 80, 90, 100 ] West
Indoor unit Priority Control
gradually stop depending on Floor #2
importance of room.
Facilities

Faculty
Robby  Office  VIP room Compressor Hz Control
Floor #1

- Easy setting of Air Purify function (Set / Clear) East

West
- Daily (per hour), period (30 days) shows trends
Floor #2
- Excel output / easy to manage

052 / 053
CENTRALIZED CONTROL

ACP LONWORKS GATEWAY PI485

CENTRALIZED
CONTROL
PLNWKB000 PI485 converts LG Air conditioners protocol to the RS485 protocol for the central controller.

LonWorks easily link LG Air conditioners Control Monitoring


and other existing building systems. On / Off Command On / Off PMNFP14A1
By including ACP control function, the Operation Mode Setting Operation Mode

controlling continues even when error occurs Lock Lock


Temperature Temperature
with BMS.
Fan Level Fan Level
Fan Direction Auto Fan Direction Auto
Mode Lock Mode Lock • Power : Single phase AC 220V 50 / 60Hz
Fan Level Lock Fan Level Lock
• 1 for Each Outdoor Unit
Temperature Lock Temperature Lock
- MULTI V MINI (ARUN40GS2A / ARUV40GS2A Only needs PI485)
Temperature Lower Limit Temperature Lower Limit
- SINGLE SPLIT - MULTI SPLIT - THERMA V
Temperature Higher Limit Temperature Higher Limit
Peak Convert Cycle Peak Convert Cycle
Peak Setting Peak Setting
Temperature Unit Temperature Unit
Features & Benefits
Total Temperature Lock -
• Connect to use LonWorks protocol Total On / Off -
and LG Air conditioner protocol. Total Temperature -
• Process ability (Max. connection) : Indoor unit - Product Type
64EA, AHU Control Kit : Max. 16EA - Product Address
• Self installation verification using internet - Current Temperature
(Web Server Included) - Diagnosis of communication - Alarm
status on LG Air conditioner network - Power

• It offers a variety of functions as ACP which allows -


-
Error Code
Peak Current Operating Percent
PHNFP14A0
the customer to efficiently control various types of
equipment from the customer’s own Integration. - Total Accumulate Power

※ ○ : Applied, - : Not Applied

• Power : C
 onnected with the Indoor Units
• 1 for Each Indoor Unit
- Indoor Unit (ERV)

BMS system

Lighting Energy Management HVAC Touch Screen

CH5
CH1 ~ 4 Indoor unit : Max. 64 units (Air conditioner & Ventilation) / Indoor address : 00 ~ FF

* Master
1)

Internet

AC Smart 5
* Slave • MULTI V 5 • MULTI V • MULTI V S • MULTI SPLIT • ERV • AHU (Control Kit)
• MULTI V IV WATER IV • SINGLE SPLIT
• MULTI V III • MULTI V
Backup Operation • MULTI V II WATER II

1) Assignment of public IP address is required to access central controller through internet. Appropriate PI485 should be used according to PDB (Product Data Book).

054 / 055
CENTRALIZED CONTROL

MODBUS RTU GATEWAY

CENTRALIZED
CONTROL
PMBUSB00A Modbus Gateway Memory Map
Baud Rate : 9,600 bps, Stop Bit : 1 stop bit, Parity : None Parity, Byte size : 8 bits

Providing Modbus RTU connection between LG Air conditioners and BMS. Coil Register (0 x 01)
Data Bit
No. Function Register
Features & Benefits Air Conditioner ERV / DX ERV Hydro Kit & THERMA V
• Function 1 Operate (On / Off) Operate (On / Off) Operate (On / Off) 0 : Stop / 1 : Run

- Modbus RTU communication with Modbus master controller 2 Auto Swing Aircon Operate (On / Off) Hot Water Mode (On / Off) 0 : Disable / 1 : Enable
3 Filter Alarm Release Filter Alarm Release 1) Reserved 0 : Normal / 1 : Alarm Release
- Modbus RTU slave (RS485) / 9,600 bps
4 Lock Remote Controller Lock Remote Controller Lock Remote Controller 0 : UnLock / 1 : Lock
- Applicable for MULTI V 5, MULTI V S, ERV, Heating 5 Lock Operate Mode Lock Operate Mode 1) Reserved 0 : UnLock / 1 : Lock Register = N X 16 + ①
- Size (W x H x D, mm) : 53.6 x 89.7 x 60.7 6 Lock Fan Speed Lock Fan Speed 1) Reserved 0 : UnLock / 1 : Lock (N = Indoor Unit Central Address)

- Max. 16 IDUs with single module / Max. 64 IDUs with 4 modules 7 Lock Target Temp. Lock Target Temp. 1) Reserved 0 : UnLock / 1 : Lock
8 Lock IDU Address Lock IDU Address 1) Reserved 0 : UnLock / 1 : Lock
- Power : DC 12V
9 Reserved Quick Ventilate Reserved 0 : Disable / 1 : Enable
10 Reserved Energy Save Reserved 0 : Disable / 1 : Enable

1) : This register value is applied ‘DX Ventilator’ ONLY.

Discrete Register (0 x 02)


Installation Scene Data Bit
No. Function Register
Air Conditioner ERV / DX ERV Hydro Kit & THERMA V
• Single Module
1 Connected IDU Connected IDU Connected IDU 0 : Disconnected / 1 : Connected
Max. 16 indoor units with a single module 2 Alarm Alarm Alarm 0 : Normal / 1 : Alarm
• 0 : Normal / 1 : Alarm Hydro Kit Register = N X 16 + ①
3 Filter Alarm Filter Alarm 1) Hot Water Only 2)
• 0 : Normal / 1 : Hot Water Only (N = Indoor Unit Central Address)
4 Reserved Reserved Target Temp. Select 0 : Air / 1 : Water
Modbus 5 Reserved Reserved Error Division 2) 0 : CH type error / 1 : BC type error

1) : This register value is applied ‘DX Ventilator’ ONLY.


2) : This register value is applied ‘Hydro Kit’ ONLY.

Holding Register (0 x 03)


BMS RS485 (LGAP 1))
Data Bit
No. Function Register
Air Conditioner ERV / DX ERV Hydro Kit & THERMA V
• 0 : Cooling, 1 : Dehumidifying,
2 : Fan, 3 : Auto, 4 : Heating Hydro Kit
1 Operate Mode Operate Mode Connected IDU (Middle Temp. DHW) / AWHP
• 0 : Cooling, 3 : Auto, 4 : Heating
Hydro Kit (High Temp. DHW)
2 Fan Speed Fan Speed Target Temp. DHW 2) 1 : Low, 2 : Mid, 3 : High, 4 : Auto Register = N X 20 + ①
(N = Indoor Unit Central Address)
3 Target Temp. Target Temp. 1) Target Temp. 2) 16.0 ~ 30.0 [°C] x 10
• Multiple Module 4 Target Temp. Limit (Upper) Target Temp. Limit 1) (Upper) Reserved 16.0 ~ 30.0 [°C] x 10
5 Target Temp. Limit (Lower) Target Temp. Limit 1) (Lower) Reserved 16.0 ~ 30.0 [°C] x 10
Max. 64 indoor units with 4 modules in one Modbus communication line 6 Reserved Vent. Operate Mode Reserved 0 : HEX, 1 : Auto, 2 : Normal

Modbus RS485 (LGAP 1)) 1) : This register value is applied ‘DX Ventilator’ ONLY.
2) : This value range can be between 0 ~ 127 [°C]. And it would be limited by upper & lower value according to the setting of remote controller.

Input Register (0 x 04)


Data Bit
No. Function Register
Air Conditioner ERV / DX ERV Hydro Kit & THERMA V
BMS 1 Error Code Error Code Error Code
0 ~ 255
※ Please refer to the product error table.
2 Room Temp. RA Temp. Room Temp. -99.0 ~ 99.0 [°C] x 10
3 Pipe In Temp. OA Temp. 1) Water Inlet Temp. -99.0 ~ 99.0 [°C] x 10 Register = N X 20 + ①
(N = Indoor Unit Central Address)
4 Pipe Out Temp. SA Temp. 1) Water Outlet Temp. -99.0 ~ 99.0 [°C] x 10
5 Reserved Pipe In Temp. 1) Sanitary Tank Temp. -99.0 ~ 99.0 [°C] x 10
Max. 16 outdoor units in
6 Reserved Pipe Out Temp. 1) Solar Temp. 2) -99.0 ~ 99.0 [°C] x 10
one RS485 (LGAP) line
Note : LGAP is LG Protocol. 1) : This register value is applied ‘DX Ventilator’ ONLY.
2) : This register value is applied ‘AWHP’ ONLY.

056 / 057
INTEGRATION DEVICE

INTEGRATION
DEVICE
INTEGRATION
DEVICE
058 / 059
INDIVIDUAL
CONTROL
PDI PDI
(POWER DISTRIBUTION INDICATOR) (POWER DISTRIBUTION INDICATOR) PQNUD1S40 (Premium, 8 ports)
30 kWh PPWRDB000 (Standard, 2 ports)
C Shop
20 kWh Size (W x H x D, mm) : 270 x 155 x 65
PDI SHOWS DISTRIBUTED B Shop
POWER CONSUMPTION OF 30 kWh
A Shop
UP TO 128 INDOOR UNITS
CONNECT TO PULSE TYPE WHM
WHM
(Watt-Hour Meter)

MAX. 128 ENERGY


IDUS MONITORING
Pulse Signal

100 kWh EHP


GAS
20 kWh
D Shop
Power
PDI
ENABLES EHP / GAS ELECTRICITY / GAS
CONSUMPTION DISTRIBUTION

STATUS LCD CONNECT TO


CENTRAL CONTROLLER
ACP 5

POWER SUPPLY PDI


AC Smart 5

PDI SHOWS
DISTRIBUTED POWER CONSUMPTION
OF UP TO 128 INDOOR UNITS.
INTEGRATION DEVICE

PDI
(POWER DISTRIBUTION INDICATOR)

30 kWh PQNUD1S40 (Premium, 8 ports)


C Shop PPWRDB000 (Standard, 2 ports)
20 kWh
B Shop

INTEGRATION
30 kWh PDI shows distributed power consumption of up to 128 indoor units.

DEVICE
A Shop Pulse Line
ACS Central Controller

220 V ~
ACP 5
24 V ~

PDI Power Source RS485

Features & Benefits


BUS-A BUS-B AC Smart 5
• Enables total and indoor power consumption monitoring.
• With LG central control connectivity, energy monitoring, energy savings operations and target usage setting functions are enabled.
• Enables gas consumption and electricity distribution.

Model Name PQNUD1S40 PPWRDB000


Size (W x H x D, mm) 270 x 155 x 65
Interfaceable Products Air conditioner, ERV DX
EHP : 8 Watt meter EHP : 2 Watt meter
Maximum Number of Power Meters
MENU
GHP : 4 Watt meter / 4 Gas meter GHP : 1 Watt meter / 1 Gas meter
50kW
Maximum Number of
SELECT
MULTI V : 128
Measurement Indoor Units

20 kWh Data Backup When Power Outage ○


MENU

AC Manager 5 70kW
(00) ~ (03)
SELECT
Power Input PDI : AC 24V, Transformer : AC 220V
D Shop 160kW [00] [01] [02] [03]
※ ○ : Applied, - : Not Applied
ACP 5 50kW
[10] [11] [12] [13]
[ Slave 1]
[ Master ] [20] [21] [22] [23]
AC Smart 5 ACP

Graphing [30] [31] [32] [33]

Note : 1. Power cable and type could be different from this scene depending on the Outdoor unit’s specification.
2. Measured power consumption could be different between PDI and Watt meter.
3. Applicable Central Controller : ACP 5, ACP LonWorks, AC Smart 5, AC Ez Touch
(Combination : we recommend to connect separated watt meter for Outdoor units to have correct power distribution value)

ENABLES TOTAL AND


INDOOR POWER
CONSUMPTION MONITORING

060 / 061 062 / 063


INTEGRATION DEVICE

ACS IO MODULE

PEXPMB000

AC Manager 5 This module can be connected with ACP 5 or AC Smart 5 controller if additional I / O points
such as DI / DO and AI / AO for 3rd party devices control and monitoring are needed.

INTEGRATION
DEVICE
LG Central Control

ACP 5 AC Smart 5

ACS IO Module
Features & Benefits
LG SAC
• Interlocking with 3rd party equipment LG Central controller can make operation scenario with 3rd party equipment by ACS IO Module.
ODU • Control coverage is expanded. (Air conditioner only → Sensors, Fans, Pumps, Switches …)

Air Cooled Water Cooled Hydro Kit IDUs


Model Name PEXPMB000
Linkable Products PACS5A000, PACP5A000
3rd party interlocking Communication RS-485 1 ch
Digital Input 3 ports
Sensor Sensor Facility
Digital Output 3 ports
I/O
Universal Input 1) 4 ports
Analog Output 4 ports

Temp. CO2 Occupancy Emergency Lighting Cooling Emergency Valve Fan


Tower
Value Spec Min. Max.
Expansion Control coverage
NTC 10k 0.68kΩ 177kΩ

※ DI : Digital Input, DO : Digital Output, UI : Universal Input, AO : Analog Output / Please contact our regional office to have connectable relay specification for analog output PT 1000 803Ω 1,573Ω
Analog Input Ni 1000 871.7Ω 1,675.2Ω
DC (Voltage) 0V 10V

Case. 1 Case. 2 DC (Current) 0mA 20mA


Analog Output - 0V 10V
Parking Lot Ventilation Auxiliary Heater Digital Input Binary Input (Non Voltage) - -
Turning on ventilator when CO2 Level is high Turning on aux. heater when outside temp. is very low
Digital Output Normal open - 30VAC / 30VDC, 2A

※ ○ : Applied, - : Not Applied


Exhaust fan Outside Temp. sensor
1) The type of UI (Universal Input) is selectable among Digital Input and Analog Input.

ACP 5 ACS IO Module

ACP 5 ACS IO Module

Boiler control signal -10 °C

CO2 Sensor House

Supply Fan
Boiler

064 / 065
INTEGRATION DEVICE

ACU IO MODULE CHILLER OPTION KIT

PEXPMB300 / PEXPMB200 / PEXPMB100 PCHLLN000

This module can be connected with ACP 5 or AC Smart 5 controller if additional I / O points LG central controller 5 series with Chiller Option Kit can provide LG chiller remote control
such as UIO / UI / UO for 3rd party devices control and monitoring are needed. and cycle monitoring.

INTEGRATION
DEVICE
ACU.UIO ACU.UO ACU.UI

PEXPMB300 PEXPMB200 PEXPMB100 Model Name PCHLLN000


Evaporator status / Compressor status (Scroll, Screw, Centrifugal chiller only) / Condenser status /
Monitoring Points Generator status (Abs. chiller only)

Features & Benefits On / Off ○


Target Temp. setting ○
• Interlocking with 3rd party equipment LG Central controller can make operation scenario with 3rd party equipment by ACU IO Module.
Mode Scroll chiller only
• Applicable devices are expanded. (Air conditioner only → Sensors, Fans, Pumps, Switches …) Schedule ○
Interfaceable Products Scroll, Screw, Centrifugal, Absorption (LG Only)

※ ○ : Applied, - : Not Applied


Module Name PEXPMB300 PEXPMB200 PEXPMB100
Linkable Products PACS5A000, PACP5A000
Communication RS-485 2 ch 1) 1 ch 1 ch
Digital Input - - 3 ports
Digital Output
Universal Input 2)
2 ports
4 ports
6 ports
-
-
6 ports
Installation Scene Cycle Display Example
Analog Output 2 ports 4 ports

• Chiller Option Kit installation of ACP, AC Smart should be Turbo Chiller Cycle information

Value Spec Min. Max. conducted by a specialized installation service engineer. View all Evaporator Compressor Condenser

Analog Input DC (Voltage) 0V 10V • Chiller Option Kit installation can be achieved with a SD Card.
Analog Output DC (Voltage) 0V 10V • The SD Card can install Chiller Option Kit in one ACP, AC
Binary Input
Digital Input (Non Voltage)
- - Smart. Insert the SD Card in the ACP, AC Smart.
Digital Output Normal Open - 30VDC, 1A If a backup SD Card is inserted, replace it with a Chiller
※ ○ : Applied, - : Not Applied Option Kit SD Card.
1) 1 ch is reserved for internal communication.
2) The type of UI (Universal Input) is selectable among Digital Input and Analog Input. Mode COOL Evaporator water out temperature 30.3 °C

Operation ON Motor current 6A

Evaporator

Flow amount ON Saturation temperature 23.2 °C

Water in temperature 20 °C Pressure 2.01 kgf / cm2

Water out temperature 30.3 °C - -

066 / 067
INTEGRATION DEVICE

DRY CONTACT

PDRYCB000 PDRYCB500

Simple Dry Contact (1 input) Dry Contact for Modbus


3rd Party Controller

INTEGRATION
Modbus RTU Communication
Dry Contact

DEVICE
(Contact point linked with 3rd Party)

Indoor Unit Modbus Controller

...
Master

...
Interlocking Device
Contact Point Input
Max. 16 Indoor units per one
Modbus master controller
Indoor Unit
Operation On / Off PCB
Indoor Unit One to one connection between
Status
PCB dry contact and indoor unit
Error Alarm Key Lighting Fire Alarm Timer Motion Door Check CN - CC Indoor Unit
CN - CC Switch Sensor Detect Sensor Sensor
※ Please contact our regional office to check the compatibility with 3rd party room controller.

Specification

Connection between an indoor unit and external devices to control various functions.
PDRYCB400
Model Name PDRYCB000 PDRYCB400 PDRYCB300 PDRYCB320* PDRYCB500

Dry Contact for 2 Input

Window Sensor

Case ○ ○ ○ ○ ○
Input Port 1 2 8 8 -
Card key Universal Input port - - - 1 -
Contact Point Input 1
Comm. Protocol - - - - Modbus RTU
Contact Point Input 2 Refrigerant Leakage Detection Alarm Power AC 220V Connect to Indoor unit PCB (CN_CC) : DC 12V
Indoor Unit
PCB Operation On / Off On / Off ○ ○ ○ ○ ○
Status
Operation Mode - ○ ○ ○ ○
Error Alarm
CN - CC Leakage Alarm
Set Temp. - (Select & Fix) (Select & Fix) (Select & Fix) ○
IDU Fan Speed - - ○ ○ ○
Thermo-Off - (Select & Fix) ○ ○ -
Card key Leakage Detector Energy Saving - (Select & Fix) - - -
Lock / Unlock - (Select & Fix) - - -
On / Off ○ - ○ ○ -
DHW On / Off - - ○ ○ -
Control
Thermo-Off - - ○ ○ -
Heating
PDRYCB300 / PDRYCB320* Operation Mode
Silent Mode
-
-
-
-




-
-
Emergency Mode - - ○ ○ -
On / Off ○ - - - ○
Dry Contact for Thermostat Operation Mode - - - - ○
ERV Aircon Mode - - - - ○
Additional Mode - - - - ○
Fan Speed - - - - ○
Operation Status ○ ○ ○ ○ ○
Output Error ○ ○ ○ ○ ○
Room Temp. - - - - ○
Target temperature setting* (0 ~ 10V)
Operation On / Off ※ ○ : Applied, - : Not Applied
Thermo On / Off Note : 1. Compatibility of PDRYCB300 / PDRYCB320 2. Compatibility of PDRYCB400
Indoor Unit Operation Mode (Fan / Heat / Cool) - Can use with all types of aircon indoor units after 2010. - Can use with all types of air conditioner indoor units after 2010.
PCB (Cassette, Ducted, Convertible, Applied PAC, Wall mounted, Console) (Cassette, Ducted, Convertible, Applied PAC, Wall mounted, Console)
Fan Speed (Low / Middle / High)
Room controller - Can use with new single package AK-W model after 2020. 1Q - Can use with new single package AK-W model after 2020. 1Q
Operation On / Off Status
CN - CC (The previous version Single package is not compatible) (The previous version Single package is not compatible)
Error Alarm
- Heating : 3 series AWHP split and Monobloc models - Can not use with AWHP, Hydro Kit models.
* Available only for PDRYCB320 ※ Please contact our regional office to have full compatible room controller list. 4 generation Hydro Kit 3. (Select & Fix) : This function is preset by rotary switch.

068 / 069
INTEGRATION DEVICE

REMOTE
GROUP CONTROL WIRE
TEMPERATURE SENSOR

PZCWRCG3 PQRSTA0

Cables used to connect a wired remote controller up to 16 indoor units. Sensor for detecting the room temperature.

INTEGRATION
DEVICE
2
1

Features & Benefits


Model Name PZCWRCG3
• It detects the exact room temperature instead of indoor unit’s air temperature sensor.
1 Y-type Cable 0.25m Length
• Applied to Ceiling Mounted Cassette, Ceiling Concealed Duct, THERMA V and Hydro Kit.
2 Long Cable 9.6m Length
• Extension cable (15m) is included.

Installation Scene Installation Scene


1. Wire to the control box in the indoor unit by removing the 2. Cut the extension cable to the appropriate length and
existing thermistor and connect the extension cable its connect the screw terminal of the remote sensor.
place.
Indoor 1 MAIN PCB

Indoor 1 Indoor 2 Indoor 3


Indoor terminal block Indoor terminal block Indoor terminal block
Indoor Unit
RED (12V)
YL (SIGNAL) YL (SIGNAL)
YL (SIGNAL)
BK (GND) BK (GND)
Extension Cable
BK (GND)

Note : 1 Y type Cable assembly is for connecting indoor unit and long cable.
2 Long Cable assembly is for connecting indoor to indoor.

Remote Wired Remote


Temperature Sensor Controller
Main PCB

Extension Cable
CN-ROOM Connector

070 / 071
INTEGRATION DEVICE

ZONE CONTROLLER IO MODULE

ABZCA PVDSMN000

Controls air conditioning in up to 4 zones by external thermostat. Interface module between the outdoor unit of system air conditioner and the external device.

INTEGRATION
Features & Benefits Features

DEVICE
• Controls different zones (up to 4 zones) by external Function
thermostat (AC 24V) • Demand control
• Maintain proper air volume of each zone • Low noise operation
• Auto variation of dampers • Output outdoor or indoor unit operation status
• Auto control of fan speed and On / Off operation • Output error status

Description
• IO Module is communication interface module for connection between MULTI V 5 and external IO
(Input / Output Module) devices.

Installation Scene Models Applied


• MULTI V IV, 5
Ceiling Concealed Duct
• MULTI V WATER IV
Ceiling Concealed Duct • MULTI V S
Note : IO Module is not compatible for MULTI V III and MULTI V S R32.

CN - ZONE

AC 24V Part Description


ROOM(External)
THERMOSTAT #1 Damper or Relay 1) Digital Input Part (DI : Dry Contact Input)
• Demand control by contact input (3 Step)
Zone Controller
ROOM Damper or Relay
• Low Noise Operation input
THERMOSTAT #2
• Priority Setting input : Setting the priority of demand control command (Capacity control for external signal from DDC vs
Peak control by LG Central controller)
ROOM
THERMOSTAT #3 Damper or Relay
- Open : External signal has priority to central controller (Default)
- Close : Central controller has priority to external signal
ROOM
THERMOSTAT #4 Damper or Relay

2) Analog Input Part (AI : DC 0 ~ 10V)


• Demand control by analog input (10 Step)
ROOM1 ROOM2
Indoor Unit
(Duct Type) Thermostat Thermostat 3) Digital Output Part (DO : AC 250V, Max. 1A)
• Error status relay output
• Operation status relay output
• Valve control

Thermostat Thermostat

Zone Control ROOM3 ROOM4


sub PCB ※ THERMOSTAT is a Field Supply.

072 / 073
INTEGRATION DEVICE

VARIABLE WATER FLOW


IO MODULE
CONTROL KIT

ODU Capacity Control PWFCKN000 (MULTI V WATER IV)

Provides variable settings for ODU Capacity Control according to input method to reduce the power consumption. Accessory for controlling the water flow.
IO Module supports 2 types of input signal : Analog Inputs (0 ~ 10V, 10 steps) and contact signals (3 steps)

INTEGRATION
Features

DEVICE
DDC
IO Module (Direct Digital Controller)
Function
Capacity
or Control with • Water pump or valve control (0 ~ 10V)
• Minimum output voltage setting available
Contact Signal
• Operation, error output (AC 250V, Max. 1A)
(3 Points / 3 Steps) • Dry contact input and analog output for demand control
MULTI V 5 MULTI V WATER IV
Range of Operation Rate • Digital output for operation, error status (AC 250V, Max. 1A)
AI 0 ~ 10V : 0%, 40% ~ 100%
Contact signal (3 steps) : 0%, 40% ~ 80%
Description
• Water flow consumption reduction
• Pump electricity consumption reduction

Low Noise Operation • Including IO Module (Dry contact input, Analog input / output, Digital output)
: Using Dry contact and variable water flow control function simultaneously.

To reduce noise level, control outdoor unit’s fan speed by dry contact input.

DDC Installation Scene


IO Module (Direct Digital Controller) Timer
(dB) • Flow Control Valve : Regulates the flow or pressure of a fluid, normally responding to signals generated by independent devices.
or
• Flow Meter : Measures mass flow rate of a fluid traveling through a tube.
(The mass flow rate is the mass of the fluid traveling past a fixed point per unit time.)
MULTI V 5 Noise Level Contact Signal • Pressure Sensor : Measures the pressure.

Cooling Tower
※ 8 HP (22.4kW) model, Sound power level can be changed by outdoor unit operation status and low noise operation input signal.
Inverter Pump

0 ~ 10V (Analog output)

Refrigerant Leakage Detection with Pump-down Flow


Control Water Flow Line
Valve Signal Line

Cooling Tower
Pump / Cooling Tower
For safety, IO module closes refrigerant valve when Pump-down operation. Controller
Variable Water Flow Control Valve
Inverter Pump

⑥ Close Valve
Liquid Pipe Valve

Gas Pipe Valve 0 ~ 10V


(Analog output)
IO Module

MULTI V 5 Flow
③ Indoor Unit Stop Control
⑤ Outdoor Unit Stop Valve Pressure
& Pump-down
Sensor
④ Buzzer Alarm
Variable Water Flow Control Valve

Dry Contact

Remote Refrigerant
controller Detector ② Error Display ① Leak Detect
From Water Source

※ If the concentration of the refrigerant in the air exceeds 6,000 ppm more than 5 seconds, the function will be activated.
Inverter Pump
(Refer to operation sequence which written in red, 1~6)

074 / 075
INTEGRATION DEVICE

LOW AMBIENT KIT COOL / HEAT SELECTOR

PRVC2 PRDSBM

External integration module for cooling operation with -25 °C low ambient temperature. Cooling only, heating only, and fan mode can be selected.

INTEGRATION
Features Features

DEVICE
• Indoor unit mode control without central controller.
Function
• Select operation mode : Cooling, Heating, Fan mode
• 25 °C Low ambient cooling operation by Low ambient kit and hood with damper
• Mode lock for cooling & heating mixing error-proof during the change of season.
(Analog output 0 ~ 10V)
• Demand control
• Low noise operation
• Output outdoor or indoor unit operation status (AC 250V, Max. 1A)
• Output error status (AC 250V, Max. 1A)
Models Applied
Description • MULTI V 5 • MULTI V WATER II • MULTI V WATER IV
• Low ambient kit supports -25 °C cooling operation by making stable condensing • MULTI V IV • MULTI V S
pressure with reducing air flow rate from hood and damper control given 0 ~ 10V • MULTI V WATER S • MUL TI V PLUS II, MULTI V PLUS
Models Applied proportional to condensing pressure.
• MULTI V 5 • Low ambient kit provides IO Module function.
• External snow hood and air damper are required for this item.
• Transformer and terminal block are included. Fan Mode Mode

Installation Scene Cooling Heating


only only
Reference : Air Damper

AC 220V

Damper Damper
Transformer Actuator Actuator
MULTI V 5 Main PCB

Installation Scene
<Outdoor Main PCB >
Push Button
Terminal Block
• Connect Terminals (1, 2, GND) on the back side of the outdoor dry
DC 0 ~ 10V Insert wire method contact to terminals (1, 2, GND) of outdoor as shown below.
Control Signal

IO Module AC / DC 24V
Push arrow direction

Low Ambient Kit

Note
1. Damper Actuator can accept only DC 24V power input. Insert wire to
2. Do not input AC power. Otherwise it will cause a serious damage. • Communication line length can be maximum 300m, use
Field wiring connector
Communication line as thick 1.25mm.
3. The IO Module can control maximum three actuators. Connected wiring
4. Case of one valve, the slave signal connector must not use.
5. The power (AC / DC 24V) and signal (DC 0 ~ 10V) line is recommended by AWG22 (1/32 in, (0.644 mm), 0.016 Ω / ft (0.053 Ω / m)).

076 / 077
INTEGRATION DEVICE

AHU KIT

A solution to connect LG’s high efficiency system to the DX coil of an air handling unit for the Communication Kit
maximum energy savings.

COMMUNICATION KIT CONTROL KIT EEV KIT


High Energy Efficiency

INTEGRATION
LG's DX AHU solutions' superior performance provides a highly efficient heat source system.

DEVICE
• High energy efficiency inverter system
• Large range of expansion application Kit : Max. 168 kW EEV Kit 1)
• Connected to various heat sources : MULTI V, MULTI V WATER, MULTI V S, SINGLE SPLIT
1) Maximum connectable EEV capacity for PAHCMR000, PAHCMC000 is 112 kW.
PAHCMR000 PAHCMS000 PAHCNM000 PRLK048A0
PRLK096A0

CONTROLLER MODULE

PRLK396A0 MULTI V 5

PAHCMM000 PAHCMC000
AHU
+

MULTI V WATER IV MULTI V S SINGLE SPLIT


PRLK594A0

Specifications
Control Application Kit Diverse Options for Control
Dimensions (mm) IP
Type Model Power Supply Description AHU communication kit can be connected to various control systems such as LG individual / central controller and DDC 1).
W H D Rating
It can be directly connected to DDC without separated controller, so DDC can receive product control and monitor
Return / Room air temperature control by DDC or LG
PAHCMR000 300 300 155 1Ø, 220 ~ 240 V, 50 / 60 Hz IP66
individual / centralized controller.
Communication information through contact signal or Modbus protocol.
Kit Discharge air / Supply air temperature control by DDC
PAHCMS000 380 300 155 1Ø, 220 ~ 240 V, 50 / 60 Hz IP66
or LG individual / centralized controller

PAHCMM000 162 90 61 DC 12V IP20 Main Controller module • LG Individual / Central controller supported LG Controller DDC by Contact Signal DDC by Modbus
Controller
Module - LG controller stand alone or combination with DDC
PAHCMC000 108 90 61 DC 12V IP20 Communication Controller module
• Direct wiring between DDC and
Various AHU control functions with multiple DX coils
Control Kit PAHCNM000 500 500 210 1Ø, 220 ~ 240 V, 50 / 60 Hz
(Maximum connectable ODU is 3 units) AHU communication kit Central Individual
Controller Controller DDC DDC
- Embedded Digital I / O and Analog Input
- Modbus RTU protocol supported AI / DI / DO
Expansion Application Kit signal
1) DDC : Direct Digital Controller

Dimensions (mm) Pipe Diameter (mm)


Type Model Capacity Index Range
W H D Liquid

PRLK048A0 217 404 83 12.7 3.6 ~ 28 kW


AHU Comm.Kit AHU Comm.Kit AHU Comm.Kit
PRLK096A0 217 404 83 12.7 28.1 ~ 56 kW
EEV Kit
PRLK396A0 349.5 345.5 180 19.05 56.1 ~ 112 kW

PRLK594A0 409.5 345.5 180 19.05 112.1 ~ 168 kW

078 / 079
INTEGRATION DEVICE

AHU KIT

Communication Kit Communication Kit & Controller Module

Expandable System Design Single Split Application

INTEGRATION
LG AHU system can be a suitable solution for various sites due to its application flexibility and wide range of line up with Single Split + Return / Room Air Temperature Control

DEVICE
large capacity models. According to the required capacity, a single or multiple module combination is possible due to the AHU
communication kit's modular design.
Temp. Sensors
• Multiple module combination for large capacity AHU Comm. Line
Central Comm. Line to ODU
Ref. Pipe

TE = Evaporator Temperature
(Liquid Pipe / Gas Pipe)
TR = Return Air Temperature
TROOM = Room Air Temperature

DDC
Control Option
TE

SINGLE SPLIT 1)
Centralized Controller
Discharge Air control Return Air control Return Air control Return Air control
AHU DX Coil

TR

OR / AND

ROOM

TROOM PAHCMR000
DDC
OR (Modbus or Contact signal 2))

PAHCMC000

1) PI485 (PMNFP14A1) is required for centralized controller.


2) In case of applying DDC with contact signal, discharge air temperature should be measured and controlled by DDC.
Note : For more detail, please refer to the PDB.

080 / 081
INTEGRATION DEVICE

AHU KIT

Communication Kit & Controller Module Communication Kit & Controller Module

Single Split Application MULTI V Application

INTEGRATION
Single Split + Discharge Air Temperature Control MULTI V + EEV Kit + IDU + Return / Room Air Temperature Control

DEVICE
Temp. Sensors Temp. Sensors
Comm. Line Comm. Line
Central Comm. Line to ODU Central Comm. Line to ODU
Ref. Pipe Ref. Pipe

TE = Evaporator Temperature TE = Evaporator Temperature


(Liquid Pipe / Gas Pipe) (Liquid Pipe / Gas Pipe) IDUs
TR = Return Air Temperature TR = Return Air Temperature
TROOM = Room Air Temperature TROOM = Room Air Temperature

EEV Kit 1)
Control Option
TE

SINGLE SPLIT 1)
TD Centralized Controller
Control Option
AHU DX Coil TE
MULTI V
Centralized Controller

AHU DX Coil

OR / AND

TR
ROOM
OR / AND

PAHCMS000 ROOM
TROOM DDC
OR (Modbus or Contact signal 2))

+
TROOM PAHCMR000
PAHCMM000 PAHCMC000 DDC
(Modbus or Contact signal 2))
OR
1) PI485 (PMNFP14A1) is required for centralized controller.
2) In case of applying DDC with contact signal, discharge air temperature should be measured and controlled by DDC.
Note : For more detail, please refer to the PDB.
PAHCMC000

1) Multiple EEV kits can be applicable with multiple DX Coils and PAHCMR000s.
2) In case of applying DDC with contact signal, discharge air temperature should be measured and controlled by DDC.
Note : For more detail, please refer to the PDB.

082 / 083
INTEGRATION DEVICE

AHU KIT

Communication Kit & Controller Module Communication Kit Function


Communication with DDC via Contact Signal
MULTI V Application PAHCMR000 PAHCMS000
Function List (PAHCMM000 + Type Note
(PAHCMC000)

INTEGRATION
PAHCMC000)
MULTI V + EEV Kit + Discharge Air Temperature Control Operation On / Off On / Off On / Off Digital Input (Non Voltage) -

DEVICE
Available operation mode can vary depending on
Operation Mode Cooling / Heating Cooling / Heating Digital Input (Non Voltage)
the settings of Communication Kit
Analog Input
Return (Room) Air Temperature 2) 16 ~ 30 °C - -
(DC 0 ~ 10 V / 20mA)
Temp. Sensors Discharge air temperature should be controller
Control 1) Discharge Air Temperature 2) - - -
Comm. Line directly by DDC using 'ODU Capacity Control
Central Comm. Line to ODU Fan Speed 3) - High / Middle / Low Digital Input (Non Voltage) -
Ref. Pipe Forced Thermal On / Off - Digital Input (Non Voltage) -
Comm. Line between modules Analog Input
ODU Capacity - 10 ~ 100% -
(DC 0 ~ 10 V / 20mA)
TE = Evaporator Temperature
Emergency Stop - Stop / Normal Digital Input (Non Voltage) -
(Liquid Pipe / Gas Pipe)
TD = Discharge Air Temperature Digital Output For PACHMR000, dip sw1-3 DO Type
Operation On / Off On / Off (Max. : DC 30 V / 1 A, should be set 'Off' (Status), In this case, '
TROOM = Room Air Temperature AC 250V / 1 A ) fan speed' cannot be monitored by DO ports
Operation Mode - - - It needs to be checked through control signal
Digital Output For PACHMR000, dip sw1-3 DO Type should be
MULTI V Fan Speed High / Middle / Low High / Middle / Low (Max. : DC 30 V / 1 A, set 'On' (Fan Mode) In this case, ‘On / Off, defrost,
AC 250V / 1 A ) error Status' cannot be monitored by DO ports
Monitor Digital Output
Defrost Operation Defrost / Normal Defrost / Normal (Max. : DC 30 V / 1 A,
EEV Kit 1) AC 250V / 1 A ) For PACHMR000, dip sw1-3 DO type
should be set 'OFF' (Status), In this case,
Digital Output, Relay C contact 'fan speed' cannot be monitored by DO ports
Error Alarm Error / Normal Error / Normal (Max. : DC 30 V / 1 A,
AC 250V / 1 A )
Digital Output,
Control Option Compressor On / Off - On / Off (Max. : DC 30 V / 1 A, -
TE AC 250V / 1 A )

1) Control functions for LG individual and central controller are not available in case of using together with DDC via contact signal.
TD Centralized Controller
2) The range of temp. is differ depending on the type of the controller.
3) To control fan speeds, DO port of the fan speed status should be connected to the fan control panel.
AHU DX Coil
Note : For more detail information, please refer to the product data book.

Communication with DDC via Modbus protocol


OR / AND PAHCMR000 PAHCMS000
Function List Note
(PAHCMC000) (PAHCMM000 + PAHCMC000)
Operation On / Off On / Off On / Off
ROOM Operation Mode Cooling / Heating / Fan Cooling / Heating / Fan
Return (Room) Air Temperature 16 ~ 30 °C -
Dip SW1-2 Discharge Temp. Control Type should be
Discharge Air Temperature 2) - ○
Control 1) set 'On' Standard II : 16 ~ 30 °C Standard III 4) : 12 ~ 50 °C
PAHCMS000 Fan Speed 3) High / Middle / Low -
TROOM DDC
OR (Modbus or Contact signal 2)) Forced Thermal On / Off - -
ODU Capacity Control 2) - 10 ~ 100% Dip SW1-2 Discharge Temp. Control Type should be set 'On'
+ - -
Emergency Stop
PAHCMM000 PAHCMC000 Operation On / Off On / Off
Operation Mode Cooling / Heating / Fan Cooling / Heating / Fan
1) Multiple EEV kits can be applicable with multiple DX Coils and PAHCMR000s. Return (Room) Air Temperature ○ - Corresponding air temperature sensor
2) In case of applying DDC with contact signal, discharge air temperature should be measured and controlled by DDC. connected to AHU Comm.Kit is required
Discharge Air Temperature - ○
Note : For more detail, please refer to the PDB. Monitor
Fan Speed High / Middle / Low High / Middle / Low
Defrost Operation Defrost / Normal Defrost / Normal
Error Alarm Error / Normal, Error code Error / Normal, Error code
Compressor On / Off On / Off On / Off

※ ○ : Applied, - : Not Applied


1) Control functions for LG individual and central controller are not available in case of using together with DDC via contact signal.
2) In case of PAHCMS000, control type between “Discharge Air Temperature” and “ODU Capacity Control” is selectable.
3) To control fan speeds, DO port of the fan speed status should be connected to the fan control panel.
4) Standard III wired remote controller after version 2.10.5a.
Note : For the Modbus memory map and more detail information, please refer to the product data book.

084 / 085
INTEGRATION DEVICE

AHU KIT

Communication Kit Function Outdoor Unit Compatibility


With LG Control System (Individual & Centralized Controller) For Small Size Application (~ 15kW) - Single Split
PAHCMS000
PAHCMR000 UUA1 UUB1 UUC1 UUD1 / UUD3
Function List (PAHCMM000 Note Type Model
(PAHCMC000)

INTEGRATION
+ PAHCMC000) (2.5 ~ 5.0 kW) 1) (5.0 ~ 8.0 kW) 1) (7.1 ~ 10.0 kW) 1) (10.0 ~ 15.0 kW) 1)
Operation On / Off On / Off On / Off -

DEVICE
PAHCMR000
- ○ ○ ○
Available operation mode can vary depending on Communication Kit (PAHCMC000)
Operation Mode Cooling / Heating / Fan Cooling / Heating / Fan
the settings of Communication Kit (Controller Module) PAHCMS000
Return (Room) Air Temperature 2) 16 ~ 30 °C - - - ○ ○ ○
(PAHCMM000 + PAHCMC000)
Control 1)
Standard II : 16 ~ 30 °C
○ Control Kit PAHCNM000 - - - -
Discharge Air Temperature 2) - Standard III 4) : 12 ~ 50 °C
Central Controllers : 12 ~ 50 °C
1) When connecting to Single Split outdoor unit, please check the compatibility to the regional sales office.
To control the AHU fan, dip switch 1-3 'DO type'
Fan Speed 3) High / Mid / Low High / Mid / Low
should be set 'On (Fan Speed)' (PAHCMR000)
Operation On / Off On / Off -
Operation Mode Cooling / Heating / Fan Cooling / Heating / Fan -
Return (Room) Air Temperature ○ - - For Medium-Large Size Application (~ 672 kW) - MULTI V
Standard II : 11 ~ 39.5 °C
Discharge Air Temperature ○ Standard III 4) : 0 ~ 100.0 °C MULTI V MULTI V WATER
Monitor Central : -50.0 ~ 100.0 °C Type Model
5 Ⅳ Ⅲ S Ⅳ Ⅱ
Fan Speed High / Middle / Low High / Middle / Low -
Defrost Operation On / Off On / Off Only with Individual Controller PAHCMR000
○ ○ ○ ○ ○ ○
Communication Kit (PAHCMC000)
Error Alarm Error Code Error Code Error code will be displayed on the screen
(Controller Module) PAHCMS000
Compressor On / Off On / Off On / Off Only with Individual Controller ○ ○ ○ ○ ○ ○
(PAHCMM000 + PAHCMC000)
※ ○ : Applied, - : Not Applied Control Kit PAHCNM000 ○ ○ ○ ○ ○ ○
1) Control functions for LG individual and central controller are not available in case of using together with DDC via contact signal.
2) The range of setting temperature is different depending on the type of the controllers. And operation may different from setting range.
3) To control fan speeds, DO port of the fan speed status should be connected to the fan control panel.
4) Standard III wired remote controller after version 2.10.5a.
Note : For more detail information, please refer to the product data book.

EEV Kit Compatibility


AHU Application Kits
Capacity index (kW) Connection by ODU system
(Maximum connectable EEV Kits)
Compatibility with LG HVAC Controllers EEV Kit
Model PAHCMS000 MULTI V
BMS PAHCMR000
Individual Controller Centralized Controller PDI Min. Max. (PAHCMM000 + PAHCNM000 Single Split
Gateway (PAHCMC000) Heat
PAHCMC000) Heat Pump Recovery
AC ACP Premium
Premium Standard III Standard II AC Ez AC Ez Touch AC Smart 5 ACP 5 Manager 5 1) LonWorks Standard PRLK048A0 3.6 28 ○ (1) ○ (1) ○ (6) ○ ○ -
Controller ○
PRLK096A0 28.1 56 ○ (1) ○ (1) ○ (6) ○ -
(Max. 33.7 kW)

PRLK396A0 56.1 112 ○ (1) ○ (1) ○ (6) ○ - -

PRLK594A0 112.1 168 - ○ (1) ○ (3) ○ - -


PREMTA000
PREMTB100 PQNUD1S40
Model no. PREMTA000A PREMTB001 PQCSZ250S0 PACEZA000 PACS5A000 PACP5A000 PACM5A000 PLNWKB000 ※ O : Applied, - : Not applied
PREMTBB10 PPWRDB000
PREMTA000B
Note 1. Table of the outdoor unit compatibility is based on European regional model.
PAHCMR000 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ 2. When connecting outdoor units in other areas, please check whether they are compatible or not.
PAHCMS000 - ○ 2) ○ - - ○ ○ ○ - - 3. Expansion application kit compatibility is based on capacity index of the system, it may changed according to system design condition.

※ ○ : Applied, - : Not Applied


1) AC Manager 5 is an integrator, so the installation with AC Smart 5 or ACP 5 is required.
2) Set temperature range of this model shall be extended April, 2020.
Note : 1. Dry contact for indoor unit (PDRYCB000 / 400 / 300 / 500) is not applied.
2. For more details, please refer to the product data book.

086 / 087
INTEGRATION DEVICE

WATER COMMUNICATION
AHU KIT
MODULE

Control Kit PAHCMW000


Field Supplied Item
This module is intended to connect 3rd party plate heat exchanger to
List Required Specification Apply Location
LG outdoor unit with the ability to control water temperature from

INTEGRATION
- Power : AC 24 V
- Output signal : DC 0 ~ 10 V
3rd party DDC or LG remote controller.

DEVICE
Temperature / Humidity Sensor Supply air duct, Return air duct, Outdoor air duct
- Temperature range : -40 °C ~ 70 °C
- Humidity range : 0 ~ 95 % RH
- Power : AC 24 V
Temperature Sensor - Output signal : DC 0 ~ 10 V Supply air duct, Return air duct, Mixed air duct
- Temperature range : -50 °C ~ 50 °C
- Power : AC 24 V
- Input / output signal : DC 0 ~ 10 V
Damper Actuator - Torque : 15 N·m Outdoor air damper, Exhaust air damper, Mixed damper
- Operation time : 150 s
- Rotation Angle : 90˚
- Power : AC 24 V
Overview
- Output signal : DC 0 ~ 10 V
Filter Differential Pressure Sensor - Range: 0 ~ 1,000 Pa Filter Interlocking with 3rd parties can make various solution with LG MULTI V outdoor unit.
- Switch type : Relay open / close
- Power : AC 24 V 1. EEV
Static Pressure Sensor - Output signal : DC 0 ~ 10 V Supply air duct
- Range : 0 ~ 1,000 Pa 2. Solenoid Valve (NC)
- Power : AC 24 V 3. Non-Return Valve
CO2 Sensor - Output signal : DC 0 ~ 10 V Return air duct
- Range : 0 ~ 2,000 ppm 4. FS : Flow Switch
- Power : AC 24 V 5. TT : DHW Temperature Transmitter
Smoke Detector Return air duct
- Type : Contact

Various Control with Control Kit – Multiple MULTI V + EEV Kits


Air handling unit (3rd party) 3rd Party DDC
EA OA EEV Kit MULTI V (ODU) Modbus
RA SA
RTU / DI+AI Water LG
Temperature Sensor
- Return Air, Supply Air (Essential)
Communication Remote
- Mixed Air Module Controller
Temp. & Humidity Sensor
- Return Air / Supply Air / Outdoor Air EEV Kit
MULTI V (ODU)
Damper Actuator
- Exhaust Air / Outdoor Air / Mixed Air

Differential Pressure Switch


4
Valve for Humidifier FS
Control Kit

CO2 Sensor 3 5
1 Water Side DHW
Refrigerant Side M TT
Smoke Detector Tank
2
Fan
- Supply / Return

Heat
Connection Pipe Exchanger
AHU HMI Communication Line
Thermistor (Pipe Temp.) • 3rd party solenoid, non-return valve, heat exchanger, flow switch and DHW temperature transmitter (Optional) must be purchased separately. (Field supplied items)
Signal (On / Off, DC 0~10V)

088 / 089
INTEGRATION DEVICE

WATER COMMUNICATION
MODULE

Features & Benefits Installation Scene with Contact Connection


Interlocking with 3rd parties can make various solution with LG MULTI V outdoor unit. Contact signal + DHW Only Setting
Contents Connection Port Function

INTEGRATION
CH1 (A+ / B-) Module Comm. Port Communication Port Modbus
RS485

DEVICE
CH2 (A+ / B-) IDU Comm. Port Communication with MULTI V Outdoor
UI1 Flow Switch Flow Switch Input by 3rd party Water side
UNIVERSAL INPUT UI2 0 ~ 10V Set Temp. Target Temp. Setting
DHW On / Off Water Inlet (5m)
(Cooling / Heating Setting) UI3 Cooling Thermostat Signal Thermostat Cooling Signal
UI4 Heating Thermostat Signal Thermostat Heating Signal
3rd Party Water Outlet (5m)
UI1 Flow Switch Flow Switch Input by 3rd party Set Temp. (0 ~ 10V)
Controller
UNIVERSAL INPUT UI2 0-10V Set Temp. Target Temp. Setting
DHW Temperature Measured Water Temp. Input Error / Normal
(DHW Only) UI3 Dry Contact
Transmitter 0 ~ 10V by 3rd party 0 ~ 10 V sensor
UI4 DHW Thermostat Signal DHW Heating Signal (Option) Flow Switch (Field Supply)
Defrost /
RI1 Water Inlet Sensor PHEX Water Inlet Sensor LG Central Controller (Option) DHW Temp. Sensor
NTC Normal
RI2 Water Outlet Sensor PHEX Water Outlet Sensor (0 ~ 10V)
REMO +12V / SIG / GND LG Remote Controller -
SINGLE Reserved - - Filed Supply
DO1 Defrost / Mode Output for defrost signal and / or cool mode Standard III Remote
DIGITAL OUTPUT DO2 Pump Output signal for pump on / off Controller (Option) Ref. side
DO3 Bypass Output signal for PHEX Bypass Valve
LGAP
RI3 Thermistor Pipe In PHEX Ref. Inlet Pipe Sensor
NTC
RI4 Thermistor Pipe Out PHEX Ref. Outlet Pipe Sensor
EEV +12V / 1 / 2 / 3 / 4 Expansion Valve EEV Control

CH2 UI1 UI2 UI3 UI4 RI1 RI2

Compatibility & Accessory MULTI V


CN-CC

EEV (LG MODEL) LG Controllers


DO1 DO2 DO3 RI3 RI4 EEV
Individual
Capacity (kW) Controller Centralized Controller
Model PAHCMW000 Dry Contact
Controller Heating
Min. Max. AC EZ Touch AC smart 5
Standard Ⅲ
PAEEVC000 3.6 28 HP / HR PREMTW101 PACEZA000 PACS5A000 PDRYCB000
PRLK048A0 3.6 28 HP / HR Pipe Out (5m)
PRLK096A0 28.1 56 HP
Bypass Pipe In (5m)
Note : Water communication module can accept plate heat exchangers from 3, 6 to On / Off
112 kW for combination with MULTI V Outdoor units.

3rd Party Solenoid


Valve (By Pass)
Specification for Field supply item + Non-Return Valve

• The 3rd party can select the for best usable version Filed Supply
EEV kit
Solenoid valve for Bypass Flow switch
Capacity
• The nominal flow and cut of flow can be calculated using
Kv Value of
(kW) solenoid and the values below.
EEV type System Pipe size
Non-Return
Min. Max. Valve
Controller Nominal Flow Flow switch Cut off
PAEEVC000
3.6 28 HP / HR 0.95 3 / 8" / 9.52mm L / min*kW 3.29 1.23
PRLK048A0
28 56 PRLK096A0 HP 1.9 1 / 2" / 12.7mm * Example : ODU nominal Cooling Capacity 28 kW,
28 x 3.29 = 92.12 L / min. nominal flow,
28 x 1.23 = 34.44 L / min. flow switch cut off

090 / 091
INTEGRATION DEVICE

WATER COMMUNICATION
MODULE

Installation Scene with Contact Connection Installation Scene with Modbus / LG Control (Optional) Connection
Contact signal + Heating / Cooling Setting Modbus + DHW Only Setting

INTEGRATION
DEVICE
Water Side
Water Side
Pump
Heating On / Off Water Inlet (5m)
Cooling On / Off Modbus Water Outlet (5m)
3rd Party 3rd Party
Set Temp. (0 ~ 10V) Water Inlet (5m)
Controller Controller
Error / Normal Water Outlet (5m)
Dry Contact
Flow Switch (Field Supply)
(Option)
Defrost /
LG Central Controller (Option) LG Central Controller (Option) DHW Temp. Sensor
Normal Flow Switch (Field Supply) (0 ~ 10V)

Filed Supply
Standard III Remote Standard III Remote
Controller (Option) Controller (Option) Ref. Side
LGAP LGAP

Ref. Side
CH2 UI1 UI2 UI3 UI4 RI1 RI2 CH1 CH2 UI1 UI2 UI3 UI4 RI1 RI2

MULTI V MULTI V
CN-CC

DO1 DO2 DO3 RI3 RI4 EEV DO1 DO2 DO3 RI3 RI4 EEV

Pump On / Off
Pipe Out (5m) Pipe Out (5m)

Bypass Pipe In (5m) Bypass Pipe In (5m)


On / Off On / Off

3rd Party Solenoid 3rd Party Solenoid


Valve (By Pass) Valve (By Pass)
+ Non-Return Valve + Non-Return Valve

Filed Supply Filed Supply


EEV kit
EEV kit
※ In case of Contact control, LG controllers can only support monitoring functions.

092 / 093
INTEGRATION DEVICE PROPOSAL CASE

WATER COMMUNICATION
MODULE

Installation Scene with Modbus / LG Control (Optional) Connection 


Modbus + Heating / Cooling Setting

INTEGRATION
DEVICE
Water Side

Pump

3rd Party Modbus


Water Inlet (5m)
Controller
Water Outlet (5m)

LG Central Controller (Option) Flow Switch (Field Supply)

Standard III Remote


Controller (Option)
LGAP

Ref. side
CH1 CH2 UI1 UI2 UI3 UI4 RI1 RI2

MULTI V

DO1 DO2 DO3 RI3 RI4 EEV

Pump On / Off
Pipe Out (5m)

Bypass Pipe In (5m)


On / Off

3rd Party Solenoid


Valve (By Pass)
+ Non-Return Valve

Filed Supply
EEV kit

PROPOSAL
CASE
094 / 095
PROPOSAL CASE

HOTEL SHOPPING MALL


CONTROL SOLUTION CONTROL SOLUTION

Guest Room Retail


Air conditioner automatically switches Proportionally distribute and manage
off when guests depart the power consumption by tenants

Integrated control of air conditioner


Real-time system issue detection and alert
with the hotel room controller

Air conditioner can be controlled with


existing hotel thermostat Maintenance Office
Reduces energy by checking
Prioritizes guest safety with refrigerant operational trends
leak detection

PROPOSAL
CASE
Reception Atrium

Air conditioner control in conjunction Integrated management of AHU applied to large spaces
with check-in or check out

Public Areas Chiller and VRF integrated control


Centralized management of the public areas

Design Proposal Design Proposal


Guest Room Lobby Retail Maintenance Office Atrium

The air conditioner Integrated control of Control with existing Guest safety is Air conditioner control Proportionally distribute Fast problem detection Reduces energy Integrated Chiller and VRF
automatically turns off air conditioner with the hotel thermostat the first priority in conjunction with and manage power and alarms by checking management of AHU integrated control
when guests leave hotel room controller check-in or check out consumption by the tenant operational trends applied to large spaces
WHM
(Watt-Hour Meter) Chiller Option
Error C store
Pulse signal Kit (S / W)
Over
24 °C Cooling

21 °C
ACP 5

Power PDI
100 kWh

PDRYCB400 PDRYCB500 PDRYCB300 PRLDNVS0 PACS5A000 PPWRDB000 PACS5A000 PAHCMR000 PCHLLN000


2 contact point Modbus RTU (9,600bps) PDRYCB320* Refrigerant leakage detector AC Smart 5 PDI Standard (2 ports) AC Smart 5 AHU Comm.Kit Chiller Option Kit
8 contact point
Input Function • 6,000ppm • BMS Integration • Max. 128 IDU • BMS Integration • Return air
• Operation On / Off • Operation Input (BACnet IP, Modbus TCP) (BACnet IP, Modbus TCP)
• Indoor temperature • Universal Input*
Output • Error alarm • Operation On / Off
• Operation On / Off status • Set run mode • Thermo On / Off PACP5A000 PACS5A000
• Error alarm • Set temperature • Operation mode ACP 5 AC Smart 5
• Set fan speed (Fan / Heat / Cool)
• Fan speed
(Low / Middle / High)
PREMTB100 PACP5A000 PQNUD1S40 PACP5A000 PAHCMS000
Wired remote controller ACP 5 PDI Premium (8 ports) ACP 5 AHU Comm.Kit
Output
• Operation On / Off status • 4.3 inch color LCD • BMS Integration • Max. 128 IDU • BMS Integration • Discharge air
• Error alarm • Touch button (BACnet IP, Modbus TCP) (BACnet IP, Modbus TCP)

* Available from April 2020

096 / 097
PROPOSAL CASE

HOSPITAL ACADEMIC INSTITUTION


CONTROL SOLUTION CONTROL SOLUTION

Hospital Ward Class Room


Automatically save energy in the
Proper airflow management for patients
absence of students

Central controls prevent students from


Monitor the comfort level for each hospital ward
arbitrary control

Control fan speed and air volume


Lecture Hall
Schedule management according to
academic plan
Service Zone

PROPOSAL
Energy savings based on flexible Maintenance Office

CASE
scheduling
Integrated management of distributed buildings

Lobby
Centralized management of AHU for
Centralized management with multiple interfaces
large spaces

Design Proposal Design Proposal


Hospital Ward Service Zone Lobby Class Room Lecture Hall Maintenance Office

Proper airflow Monitor the comfort level External device Energy savings based on Centralized management Automatically save Central controls Schedule management Integrated management Centralized management
management for patients for each hospital ward interlock control flexible scheduling of AHU for large space energy in the absence prevent students from according to academic plan of distributed buildings with multiple interfaces
of students arbitrary control

Relay

PTVSMA0 PACS5A000 PDRYCB400 PACS5A000 PAHCMR000 PTVSMA0


Human detection sensor AC Smart 5 2 contact point AC Smart 5 AHU Comm.Kit Human detection sensor

• BMS Integration Input • BMS Integration • Return air


(BACnet IP, Modbus TCP) • Operation On / Off (BACnet IP, Modbus TCP)

Output PACS5A000 PACP5A000 PACM5A000


• Operation On / Off status AC Smart 5 ACP 5 AC Manager 5
• Error alarm
• BMS Integration • BMS Integration
(BACnet IP, Modbus TCP) (BACnet IP, Modbus TCP)
PREMTB100 PACP5A000 PACP5A000 PAHCMS000 PREMTB100
Wired remote controller ACP 5 ACP 5 AHU Comm.Kit Wired remote controller

• 4.3 inch color LCD • BMS Integration • BMS Integration • Discharge air • 4.3 inch color LCD
• Touch button (BACnet IP, Modbus TCP) (BACnet IP, Modbus TCP) • Touch button

098 / 099
PROPOSAL CASE

OFFICE RESIDENTIAL
CONTROL SOLUTION CONTROL SOLUTION

Maintenance 0ffice Home


Anytime, anywhere air conditioner
Energy savings and management throughout the building
control and access

Integrated management of HVAC with BMS system Integrate systems for smart connectivity throughout

Reduce costs by replacing BMS


Bed Room

Office Room Use a familiar residential thermostat

PROPOSAL
Reasonable power distribution to
tenants

CASE
Simple interlocking control by remote control
Server Room
24-hour backup management
Apartment / Residence
Meeting Room
Energy savings based on occupancy Stable system operation
detection

Design Proposal Design Proposal


Maintenance Office Office Room Server Room Meeting Room Home Bed Room Apartment

Energy savings Integrated Reduce costs by Reasonable power Main equipment Energy savings Control your home air Build a Smart house Use a familiar residential Simple interlocking Stable system
and management management of HVAC replacing BMS distribution to tenants 24 hours back up based on occupancy conditioner anytime, thermostat control by remote control operation when indoor
throughout the building with BMS system management detection anywhere unit power is lost

WHM Human
BMS Protocol Pump Lighting Fan Sensor (Watt-Hour Meter) detection
Pulse signal sensor

Target Error Lighting

Power PDI A B
Fan
BMS System 100 kWh
Forecasting

Radiator

PACS5A000 PLNWKB000 PEXPMB000 PPWRDB000 PACS5A000 PTVSMA0 PWFMDD200 PDRYCB500 PDRYCB300 PREMTB100 PRIP0
AC Smart 5 LonWorks gateway ACS IO Module PDI Standard (2 ports) AC Smart 5 Human detection sensor Wi-Fi modem Modbus RTU (9,600bps) PDRYCB320* Wired remote controller Independent power module
8 contact point
• BMS Integration • Max. 128 IDU • BMS Integration Function Function • 4.3 inch color LCD • EEV full close function
(BACnet IP, Modbus TCP) (BACnet IP, Modbus TCP) • On / Off • Operation Input • Touch button
• Fan speed • Indoor temperature • Universal Input*
• Operation mode • Error alarm • Operation On / Off
• Vane control • Set operation mode • Thermo On / Off
• Reservation • Set temperature • Operation mode
(Sleep, Weekly On / Off) • Set fan speed (Fan / Heat / Cool)
• Error check • Fan speed
PACP5A000 PMBUSB00A PEXPM300 PQNUD1S40 PACP5A000 PREMTB100 (Low / Middle / High)
ACP 5 Modbus RTU gateway PEXPM200 PDI Premium (8 ports) ACP 5 Wired remote controller
PEXPM100 Output
• BMS Integration • Max. 128 IDU • BMS Integration • 4.3 inch color LCD • Operation On / Off status
ACU IO Module
(BACnet IP, Modbus TCP) (BACnet IP, Modbus TCP) • Touch button • Error alarm
* Available from April 2020

100 / 101
CONTROL SYSTEM ARCHITECTURE STICKER

LG BECON HVAC SOLUTION offers a diverse range of effective control solutions that satisfy specific needs
CONTROL SYSTEM of each building and its user scene. These control systems are equipped with user-friendly interface, flexible
ARCHITECTURE
interlocking environment, energy management and smart individual controller for optimized controlling
conditions and smart building management
Integrated Controller Central Controller Central Controller Power Distribution Indicator CONTROLLER FOR INDOOR UNIT
(Medium / Large) (Small)
Individual Controller Dry Contact
AC Manager 5 ACP 5 AC Ez Touch PDI
Internet Internet Internet Wired R / C
PACM5A000 PACP5A000 PACEZA000
PDI Premium
BACnet IP / Modbus TCP PQNUD1S40 (8 Ports) Card Key
AC Ez
PREMTA000
PDI Standard
PPWRDB000 (2 Ports) PDRYCB000
AC Smart 5
PQCSZ250S0
Internet
PREMTB100
Motion
IO Module for Sensor
Central Controller
PACS5A000
ACS IO Module
BACnet IP / Modbus TCP
IO Module PDRYCB400
PREMTB001
Light
Thermostat
PEXPMB000
Pump
ACU IO Module PQRCVCL0QW(W)
PQRCHCL0QW(W)*
BMS Gateway PVDSMN000 * For Hotel
Fan PDRYCB300
Wireless R / C (For thermostat 3rd party
ACP LonWorks G / W
via contact signal) Home
Internet PEXPMB100 Controller
PEXPMB200 PI485
PEXPMB300 Etc
PLNWKB000
Controller for AHU
PWLSSB21H (Heat Pump) PDRYCB320
PWLSSB21C (Cooling Only) Dry contact for Thermostat
PMNFP14A1 Multi (For using universal input)
(For outdoor unit) Split
BMS
Building Protocol Modbus RTU G / W Wi-Fi Modem
Management AHU Comm.Kit AHU Control Kit
System
Single
AHU Comm.Kit AHU Control Kit Split
PMBUSB00A
PAHCMR000
(Return Air temp. control) PHNFP14A0 PDRYCB500
PAHCNM000 (For indoor unit) ERV (For thermostat
PWFMDD200
PAHCMS000 via Modbus RTU)
(Supply Air temp. control)
MEMO
PRODUCT LINE-UP STICKER

Individual Control

Standard III (White) Standard III (Black) Standard II (White) Standard II (Black) Simple

Simple for hotel Premium Wi-Fi Modem Wireless Remote Controller

Centralized Control

AC Ez AC Ez Touch ACP 5 AC Smart 5 Modbus RTU gateway

ACP LonWorks AC Manager 5 PI485 PI485

스티커 용지 후면
Integration Device

Remote
Group
PDI ACS IO Module Temperature
Chiller Option Kit ACU IO Module Control Wire
(Power Distribution Indicator) (Input / Output Module) Sensor

2 Points Dry Contact Zone Cool / Heat


Simple Dry Contact Dry Contact for Thermostat For Modbus Controller Selector
(For Setback)

IO Module Variable Water Flow


Low Ambient Kit Water Communication Module Control Kit
(Input / Output Module) Control Kit

Communication Kit Communication Kit Controller Module Controller Module EEV Kit
Return / Room Air control Discharge / Supply Air control Main module Communication module (Electronic Expansion Valve)

Download PDF file from the path below.


[http://partner.lge.com] Home>Doc.Library>Product>Control(BECON)>Catalogue & Leaflet
MEMO

스티커 용지 후면

You might also like