PLUMBING LEGEND AND ABBREVIATIONS PLUMBING DEMOLITION NOTES PLUMBING GENERAL NOTES

PLUMBING PIPE DESIGNATIONS ABBREVIATIONS PLUMBING/PIPING SYMBOLS


1. THE CONTRACTOR SHALL THOROUGHLY EXAMINE THE SITE PRIOR TO (THESE NOTES APPLY TO ALL PLUMBING DRAWINGS)
SUBMITTING A BID. DUE TO THE NATURE OF THIS PROJECT AND THE STATE
F FIRE PROTECTION PIPING AD AREA DRAIN GATE VALVE OF THE EXISTING BUILDING, IT IS IMPOSSIBLE TO COMPLETELY RELATE THE A. ALL WORK SHALL COMPLY WITH THE LATEST ADOPTED STATE AND LOCAL
SCOPE OF THE DEMOLITION REQUIRED TO THE CONTRACTOR THROUGH CODES, AS WELL AS FEDERAL, STATE, AND MUNICIPAL REGULATIONS.
POTABLE COLD WATER PIPING AFF ABOVE FINISHED FLOOR GLOBE VALVE THE CONTRACT DOCUMENTS. FAILURE TO VISIT THE SITE WILL NOT
RELIEVE THE CONTRACTOR OF DEMOLITION RESPONSIBILITIES UNDER THIS
CONTRACT. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE AND THE WORK REQUIRED CONSISTS OF PERFORMING ALL LABOR AND
110° POTABLE HOT WATER 110%%127F PIPING AFG ABOVE FINISHED GRADE PLUG VALVE B.
COORDINATE THE EXACT CONTENT OF DEMOLITION NECESSARY TO FURNISHING ALL MATERIALS, FIXTURES AND EQUIPMENT REQUIRED TO
PROVIDE A RENOVATED AND UPGRADED SPACE AND TO FACILITATE NEW PROVIDE A COMPLETE INSTALLATION OF ALL PLUMBING SYSTEMS AS
120° POTABLE HOT WATER 120%%127F PIPING BFF BELOW FINISHED FLOOR WORK.
OS & Y PATTERN GATE VALVE INDICATED IN THE CONTRACT DOCUMENTS. IT SHALL FURTHER INCLUDE
140° POTABLE HOT WATER 140%%127F PIPING BFG BELOW FINISHED GRADE FURNISHING AND INSTALLING ALL ASSOCIATED ITEMS REQUIRED FOR THE
BALL VALVE PROPER OPERATION OF ALL PLUMBING SYSTEMS INCLUDING BUT NOT
2. INFORMATION REGARDING THE EXISTING CONDITIONS WAS GATHERED
LIMITED TO ELECTRICAL, CONTROL AND HYRDONIC SYSTEM DEVICES.
110°C POTABLE HOT WATER RECIRC. 110%%127F PIPING BFP BACKFLOW PREVENTER FROM THE ALL AVAILABLE EXISTING DRAWINGS, SURVEY AND
BALANCING VALVE CORRESPONDENCE WITH UTILITY, STAFF AND MUNICIPAL PERSONNEL.
120°C POTABLE HOT WATER RECIRC. 120%%127F PIPING CA COMPRESSED AIR THERE ARE NO GUARANTEES AS TO THE ACCURACY OF THIS INFORMATION
CHECK VALVE AND IT IS OFFERED FOR INFORMATION ONLY. C. DRAWINGS ARE DIAGRAMMATIC, CONTAINING INFORMATION TO A DEGREE
140°C POTABLE HOT WATER RECIRC. 140%%127F PIPING CD CONDENSATE DRAIN OF DETAIL CONSISTENT WITH THEIR SCALE AND ADEQUATE TO CONVEY
THE DESIGN INTENT. THE CONTRACTOR IS RESPONSIBLE FOR
BUTTERFLY VALVE 3. VERIFY EXISTING LOCATIONS OF EQUIPMENT, PIPING AND SYSTEM
G NATURAL GAS PIPING CO CLEANOUT VERIFICATION OF ALL FIELD DIMENSIONS, LOCATIONS AND CONDITIONS
COMPONENTS PRIOR TO DEMOLITION. IF EXISTING CONDITIONS ARE
PRIOR TO THE PURCHASE OF ANY MATERIALS AND COMMENCEMENT OF
DIFFERENT THAN WHAT IS INDICATED ON THE CONTRACT DOCUMENTS, THE
SANITARY SEWER PIPING (ABOVE FLOOR/GRADE) CW COLD WATER WORK. NOTIFY THE ARCHITECT OF ALL DISCREPANCIES THAT WILL
GAS COCK CONTRACTOR SHALL NOTIFY THE ARCHITECT PRIOR TO PROCEEDING
AFFECT THE WORK FOR RESOLUTION.
WITH WORK.
SANITARY SEWER PIPING (BELOW FLOOR/GRADE) DCBFP DOUBLE CHECK BACKFLOW PREVENTER
HOSE BIBB
D. EQUIPMENT AND MATERIAL SHOWN ON DRAWINGS ARE BASED ON
4. MINIMIZE DISTURBANCE AND/OR DAMAGE TO EXISTING FINISHED SURFACES
ST STORM SEWER PIPING (ABOVE FLOOR/GRADE) DWG DRAWING MANUFACTURER'S PUBLISHED DATA, AND ARE, IN THE DESIGNER'S
HOSE BIBB AND FINISHES. WHERE DEMOLITION OF PLUMBING SYSTEM COMPONENTS
PROFESSIONAL OPINION, REPRESENTATIVE OF TYPICAL SIZES. ALL
DAMAGES EXISTING SURFACE TO REMAIN, RESTORE THOSE SURFACES TO
ST STORM SEWER PIPING (BELOW FLOOR/GRADE) (E) EXISTING EQUIPMENT AND MATERIAL PROVIDED SHALL FIT WITHIN THE SPACE
THE SAME CONDITION AS THE ADJACENT SURFACES. RESTORATION MUST
PROVIDED. ALL EQUIPMENT, FIXTURES, AND SERVICEABLE DEVICES SHALL
SILLCOCK BE PERFORMED BY WORKMEN SKILLED IN PERFORMING SUCH WORK. ALL
RD ROOF DRAIN PIPING (ABOVE FLOOR/GRADE) EC ELECTRICAL CONTRACTOR BE INSTALLED WITH ACCESS AND CLEARANCE FOR MAINTENANCE.
FIRE AND SMOKE RATINGS SHALL BE RETAINED AS PART OF THE REPAIRS
COORDINATE WITH THE GENERAL CONTRACTOR AND OTHER TRADES TO
AND PATCH/SEAL HOLES WEATHERTIGHT WHERE REQUIRED. ALL PATCHES
PRESSURE REDUCING VALVE PROVIDE THIS ACCESS AND CLEARANCE. INSTALL ALL EQUIPMENT AND
RD ROOF DRAIN PIPING (BELOW FLOOR/GRADE) EWT ENTERING WATER TEMPERATURE AND REPAIRS SHALL BE SUBJECT TO REVIEW AND APPROVAL OF THE
MATERIALS PER MANUFACTURER'S INSTRUCTIONS.
ARCHITECT.
GW GREASE WASTE PIPING EWC ELECTRIC WATER COOLER TEMPERATURE CONTROL VALVE 2 WAY
E. IF EQUIPMENT, FIXTURES, AND MATERIAL, OTHER THAN THAT SCHEDULED
SANITARY VENT PIPING F FIRE 5. ALL AREAS OF EGRESS SHALL BE KEPT OPEN AND FREE FROM DEBRIS OR SPECIFIED, IS APPROVED AND PROVIDED, IT IS THE RESPONSIBILITY
TEMPERATURE CONTROL VALVE 3 WAY AT ALL TIMES. OF THE CONTRACTOR TO COORDINATE AND PROVIDE REVISED UTILITIES
CD CONDENSATE DRAIN PIPING FD FLOOR DRAIN AND SERVICE CONNECTIONS AND VERIFY THE SPACE ALOTTED FOR
6. DO NOT REMOVE ITEMS SUPPORTING OTHER ITEMS WITHOUT PROVIDING ADEQUECY AND CLEARANCE REQUIREMENTS. THIS INCLUDES BUT IS NOT
SOG SAND/OIL/GAS WASTE PIPING FLR FLOOR T&P RELIEF VALVE TEMPORARY OR PERMANENT SUPPORT AS REQUIRED. SEE DRAWINGS LIMITED TO REVISED POWER, WATER, CONTROLS, HYDRONICS, WASTE
FOR AREAS AND EXTENT OF DEMOLITION. PROPERLY SUPPORT ALL DRAINS, FUEL FLUES AND VENT REQUIREMENTS.
S EXISTING ITEMS TO REMAIN. CONTRACTOR SHALL BE RESPONSIBLE FOR
FOS FUEL OIL SUPPLY PIPING FM FORCED MAIN SOLENOID VALVE PROVIDING REQUIRED SUPPORTS FOR AFFECTED ITEMS. COORDINATE ALL LOCATIONS AND SIZES OF STRUCTURAL FLOOR AND
F.
FOR FUEL OIL RETURN PIPING FO FUEL OIL AV WALL PENETRATIONS WITH THE GENERAL CONTRACTOR AND PROVIDE
7. VERIFY EXTENT OF PIPING, EQUIPMENT, COMPONENTS AND CONTROLS TO CODE REQUIRED SEALS AT ALL FIRE RATED WALL, CEILING, ROOF AND
AUTOMATIC AIR VENT BE RETAINED OR REUSED PRIOR TO THE DEMOLITION OF SPECIFIC FLOOR PENETRATIONS.
FOV FUEL OIL VENT PIPING FOR FUEL OIL RETURN
SYSTEM. PROTECT ITEMS WHICH ARE TO BE REUSED ON SITE TO MINIMIZE
UG UN INTERRUPTABLE GAS PIPING FOS FUEL OIL SUPPLY BACKFLOW PREVENTER POST CONSTRUCTION REPAIRS. ANY ITEMS WHICH ARE DAMAGED SHALL ACCESS DOORS AND/OR PANELS SHALL BE PROVIDED AT ALL
G.
BE THE RESPONSIBILITY OF THE CONTRACTOR AND SHALL BE REPAIRED MAINTENANCE AND SERVICE LOCATIONS FOR CONCEALED CONTROL
IN LINE PUMP OR REPLACED AT NO ADDITIONAL COST TO THE CONTRACT. DEVICES, VALVES AND PLUMBING EQUIPMENT/DEVICES. UNLESS A SIZE IS
IG INTERRUPTABLE GAS PIPING FOV FUEL OIL VENT
SPECIFICALLY NOTED, PANELS SHALL BE SIZED TO SERVICE
CA COMPRESSED AIR PIPING G GAS STRAINER W/ BLOWOFF VALVE EQUIPMENT/DEVICE. DOORS AND PANELS SHALL HAVE THE SAME FIRE
8. REMOVE EQUIPMENT OWNER WISHES TO RETAIN AND DELIVER TO THE RATING AS THE WALL OR CEILING IN WHICH THEY ARE INSTALLED. ACCESS
EWC ELECTRIC WATER COOLER CHILLED WATER PIPING GC GENERAL CONTRACTOR LOCATION DESIGNATED BY THE OWNER. REMOVE PROMPTLY FROM SITE DOORS AND/OR PANELS ARE NOT REQUIRED WHERE ADJUSTMENT,
TEMPERATURE & PRESSURE TEST PLUG ALL MATERIALS AND EQUIPMENT INDICATED FOR REMOVAL WHICH ARE NOT MAINTENANCE AND REPLACEMENT ARE POSSIBLE THROUGH LAY IN
SPECIFIED FOR REUSE, STORAGE, OR RETAINED BY OWNER. SUSPENDED CEILING.
NP NON POTABLE COLD WATER GCO GRADE CLEANOUT T
TEMPERATURE SENSOR
GPH GALLONS PER HOUR 9. VERIFY ALL EXISTING STRUCTURAL CONDITIONS AND NOTIFY STRUCTURAL H. INSTALL SHUT OFF VALVES AT EACH FIXTURE. INSTALL BRANCH SHUTOFF
ENGINEER FOR APPROVAL PRIOR TO PENETRATING EXISTING BUILDING VALVES WHERE INDICATED ON PLANS. LOCATE AND ORIENT VALVE
GPM GALLONS PER MINUTE VACUUM BREAKER STRUCTURAL SYSTEMS. OPERATORS FOR EASE OF ACCESS AND FULL LIMITS OF OPERATION.

GW GREASE WASTE 10. NO DEMOLITION SHALL OCCUR WHICH LEAVES THE BUILDING INTERIOR
WITHOUT WEATHER PROTECTION. ALL DEMOLITION OF EXTERIOR OF I. INSULATION AND VAPOR BARRIER SHALL BE PROVIDED ON ALL PIPING
HW HOT WATER THERMOMETER EXTERIOR SURFACES SHALL BE FOLLOWED IMMEDIATELY BY PROTECTIVE AND/OR EQUIPMENT SUBJECT TO HEAT LOSS, CONDENSATION, OR
CONSTRUCTION. CONTRACTORS SHALL PROVIDE AND INSTALL CONSTITUTING A POTENTIAL BURN HAZARD.
P TEMPORARY PROTECTION IN ALL OPENINGS WHERE WINDOWS AND
HWC HOT WATER RECIRC. PRESSURE SWITCH EXTERIOR DOORS HAVE BEEN REMOVED.
J. INSULATION SHALL NOT BE CRUSHED OR COMPRESSED THROUGH
IG INTERRUPTABLE GAS F INTERFERENCE WITH SYSTEMS INSTALLED BY OTHER TRADES OR BUILDING
FLOW SWITCH 11. THE INTENT OF THE DEMOLITION ON THIS PROJECT IS THE COMPLETE CONSTRUCTION.
IW INDIRECT WASTE REMOVAL OF ALL INTERIOR AND EXTERIOR PLUMBING SYSTEMS, EXCEPT
WHERE NOTED. AFTER THE DEMOLITION OF AN AREA, THE ONLY EXISTING K. INSTALL PLUMBING AND PIPING HIGH POINTS AS TIGHT AS POSSIBLE TO THE
ITEM THAT SHOULD REMAIN IS PIPING IN (E) MASONRY WALLS AND BELOW BUILDING STRUCTURE TO ALLOW PROPER PITCH AND MAXIMIZE CEILING
LAV LAVATORY PRESSURE GAUGE W/ GAUGE COCK
(E) FLOOR SLABS. REMAINING PIPING IN THESE LOCATIONS SHALL BE HEIGHT.
PATCHED OVER AND NOT VISIBLE NOR REUSABLE. NO PIPING SHALL
LWT LEAVING WATER TEMPERATURE EXPANSION JOINT REMAIN IN CEILING SPACES. L. PROVIDE AIR VENTS AT PIPING HIGH POINTS AND DRAINS AT LOW POINTS IN
MC MECHANICAL CONTRACTOR MAINS.
FLEXIBLE PIPE CONNECTION 12. THE PLUMBING CONTRACTOR SHALL REFER TO ALL SECTIONS AND
(N) NEW DRAWINGS OF THE CONTRACT DOCUMENTS FOR DEMOLITION OF PLUMBING M. ALL PIPING SHALL BE INSTALLED IN SUCH A MANNER AS TO AVOID
PIPING RISER SYSTEM COMPONENTS INCLUDED IN THE PLUMBING CONTRACT. NOTIFY THE FREEZING. ALL WATER PIPING SHALL BE INSTALLED BELOW ATTIC
ARCHITECT OF ALL DISCREPANCIES OR QUESTIONS PERTAINING TO EXTENT INSULATION AND NO PIPING SHALL BE INSTALLED WITHIN EXTERIOR WALLS.
NIC NOT IN CONTRACT
PIPE DROP OF WORK PRIOR TO BIDDING. THE INSTALLATION OF PLUMBING SYSTEMS SHALL IN NO WAY CRUSH OR
COMPROMISE BUILDING INSULATION AND ALL BELOWGRADE WATER PIPING
NTS NOT TO SCALE PIPE ANCHOR SHALL BE INSTALLED NO LESS THAN 6" BELOW FROST DEPTH.
13. PLUMBING CONTRACTOR SHALL REFER TO THE SPECIFICATIONS FOR
N.O. NORMALLY OPEN DISTRIBUTION OF RESPONSIBILITY AMONGST CONTRACTORS FOR
PIPE GUIDE SPECIFIC PORTIONS OF CUTTING AND PATCHING WORK. PLUMBING
CONTRACTOR SHALL COORDINATE ALL CUTTING AND PATCHING WORK N. AT THE COMPLETION OF THE WORK AND PRIOR TO THE FINAL
N.C. NORMALLY CLOSED
PIPE SLEEVE WITH ALL OTHER CONTRACTORS INVOLVED AS DEFINED IN THE ACCEPTANCE, ALL PARTS OF THE WORK SHALL BE THOROUGHLY CLEANED.
SPECIFICATIONS.
PC PLUMBING CONTRACTOR
UNION
PRV PRESSURE REDUCING VALVE O. ALL PIPING SHALL BE CONCEALED IN WALLS AND BEHIND FIXED
FURNISHINGS UNLESS OTHERWISE INDICATED. EXPOSED PIPING IN FINISHED
PIPE CAP AREAS SHALL BE CHROME PLATED WITH A CHROME PLATED ESCUTCHEON
RD ROOF DRAIN
AT EACH FINISHED ENTRY/EXIT.
DIRECTION OF FLOW
RPBFP REDUCED PRESSURE BACKFLOW PREVENTER
P. ALL PIPING SHALL BE RUN PARALLEL TO BUILDING LINES AND BE
SLOPE PIPE DOWN IN DIRECTION OF ARROW SUPPORTED AND ANCHORED AS REQUIRED TO FACILITATE EXPANSION AND
RWC RAIN WATER CONDUCTOR
CONTRACTION. ALL PIPING SHALL BE CONCEALED EXCEPT IN UNFINISHED
CONCRETE THRUST BLOCK SPACES. INSTALL AS REQUIRED TO MEET ALL CONSTRUCTION CONDITIONS
SOG SAND/OIL/GAS WASTE AND TO ALLOW FOR INSTALLATION OF OTHER WORK INCLUDING DUCTS
SIGHT GLASS AND ELECTRICAL CONDUIT. ALL PIPING EXPOSED TO VIEW SHALL BE
SS SERVICE SINK ROUTED AS HIGH AS POSSIBLE AND TO THE UNDERSIDE OF STRUCTURE.
CONCENTRIC REDUCER
ST STORM SEWER
ECCENTRIC REDUCER Q. ELEVATIONS LISTED FOR ALL PLUMBING SYSTEM PIPING IN THE CONTRACT
TW TEMPERED WATER (TEPID WATER)
DOCUMENTS ARE TO BE VERIFIED PRIOR TO CONSTRUCTION AGAINST
CHECK VALVE W/ BALL DRIP EXISTING CONDITIONS, UTILITIES AND NEW CONSTRUCTION. ALL SLOPED
TYP. TYPICAL PLUMBING SYSTEMS SHALL HAVE RIGHT OF WAY OVER ALL OTHER

U URINAL CLEANOUT PLUG


BUILDING SYSTEM COMPONENTS. Keyplan
R. ALL EXISTING BUILDING AND SITE FEATURES NOT BEING ALTERED BY THIS
UG UN INTERRUPTABLE GAS FLOOR DRAIN PROJECT ARE TO BE PROTECTED FROM DAMAGE. CONTRACTOR SHALL
REPAIR ALL DAMAGE OCCURRING TO EXISTING CONSTRUCTION CAUSED BY
V VENT THE CONTRACTOR'S OPERATIONS AT HIS/HER EXPENSE TO THE COMPLETE
FLOOR SINK
SATISFACTION OF THE OWNER.
VTR VENT THROUGH ROOF
FLOOR OR GRADE CLEANOUT
S. THE PLUMBING CONTRACTOR IS RESPONSIBLE FOR COORDINATING ALL
W WASTE (SANITARY SEWER) WORK UNDER HIS/HER CONTRACT WITH ALL OTHER BUILDING TRADES.
VENT THRU ROOF NOTIFY THE ARCHITECT OF ALL DISCREPANCIES OR QUESTIONS PERTAINING
WC WATER CLOSET TO EXTENT OF WORK PRIOR TO BIDDING.

WCO WALL CLEANOUT HEAT TRACE


T. PROVIDE AND DOCUMENT CORRESPONDENCE TO THE GENERAL
CONTRACTOR AND ALL TRADES, REQUIREMENTS FOR INSTALLATION,
ROOF DRAIN / OVERFLOW DRAIN OPENINGS, CHASES AND UTILITY SERVICE CONNECTIONS. THIS INCLUDES
SUPPORTING DEVICES, POINT LOADS, ACCESS OPENINGS, SLEEVES AND
CUTOUTS.
GAS PRESSURE REGULATOR
U. PROVIDE STARTERS FOR MOTORS UNLESS SPECIFICALLY IDENTIFIED AS
BEING PROVIDED BY THE ELECTRICAL CONTRACTOR. PROVIDE ALL
SHOCK ABSORBER INTERNAL OVER CURRENT PROTECTION DEVICES AND INTERNAL
TRANSFORMERS FOR PACKAGED EQUIPMENT.

TERRACE / AREA DRAIN V.

LINE / EQUIPMENT TO BE DEMOLISHED # Date Change Description

DOWNSPOUT NOZZLE

EMERGENCY SHUT OFF VALVE (WITH FUSIBLE LINK)

RECESSED PENDANT MOUNTED SPRINKLER

RECESSED SIDEWALL SPRAY SPRINKLER APArchitects, LLC Reese Engineering


Associate Architect MEP Engineer
FIRE DEPARTMENT ALARM LIGHT AND HORN The EDGE Group CD+M Lighting Design Group
Landscape Architect Lighting Designer
REFERENCE SYMBOLS Sweetland Engineering Code Consultants, Inc
FIRE DEPARTMENT CONNECTION Civil Engineer Code Consultant
KORDA Engineering Rider Levett Bucknall
TAG EQUIPMENT DESIGNATION Structural Engineer Cost Estimator
ALARM CHECK VALVE

? REVISION DESIGNATION
IM BUILDING ADDITION AND RENOVATION
?? KEY NOTE DESIGNATION PHASE I
University Park, Pennsylvania 16802
?
ENLARGED PLAN DESIGNATION for
???
THE PENNSYLVANIA
C:\Users\bgoss\Documents\2010159_MEP_bgoss.rvt

STATE UNIVERSITY
NORTH ARROW
PSU# 09 12181.00 PSU Building # 0804 000

POINT OF CONNECTION OF NEW TO EXISTING

?
WATER RISER DIAGRAM REFERENCE
??? 300 Spruce Street Phone: (614) 461 4664
Suite 300 Fax: (614) 280 8881
PRINT DATE: 11/8/2012 4:41:19 PM

Columbus, Ohio 43215 www.moodynolan.com


?
???
CONDENSATE RISER DIAGRAM REFERENCE

DRAWN BY: CHECKED BY: APPROVED BY:


?
N.J.B. B.C.S. B.C.S. 11279.00
???
WASTE & VENT STACK DIAGRAM REFERENCE

Plumbing Legend And General P001


FILE INFO:

Notes
95% Construction Documents 11/9/2012
KEY NOTES
1 SEE 1/P111 FOR PLUMBING WORK IN THIS AREA.

2 6" ST UP TO LEVEL ABOVE.

3 12" ST EXTENDED TO 5' 0" FROM BUILDING AND TERMINATED WITH


GRADE CLEANOUT. SLEEVE THROUGH FOUNDATION WALL PER
STRUCTURAL ENGINEER'S REQUIREMENTS. CONNECT TO SITE STORM
SEWER EXTENDED UP TO BUILDING IN SITE UTILITIES PORTION OF WORK.
RE: CIVIL DOCUMENTS FOR CONTINUATION.

4 4" W UP TO LEVEL ABOVE.

5 2" W UP TO LEVEL ABOVE.

6 8" ST FROM LEVEL ABOVE. OFFSET BELOW STAIRS TO DOWNSPOUT


NOZZLE MOUNTED AT 12" AFG.

Keyplan

1 1

# Date Change Description

6" 10" 12"


GCO
ST ST 3
2 IE: 1172.1'

5 APArchitects, LLC Reese Engineering


DSN 1 Associate Architect MEP Engineer
The EDGE Group CD+M Lighting Design Group
4" 4"
Landscape Architect Lighting Designer
4 2 4 Sweetland Engineering Code Consultants, Inc
6 Civil Engineer Code Consultant
KORDA Engineering Rider Levett Bucknall
5
Structural Engineer Cost Estimator

IM BUILDING ADDITION AND RENOVATION


PHASE I
University Park, Pennsylvania 16802
for
THE PENNSYLVANIA
C:\Users\bgoss\Documents\2010159_MEP_bgoss.rvt

STATE UNIVERSITY
PSU# 09 12181.00 PSU Building # 0804 000

300 Spruce Street Phone: (614) 461 4664


Suite 300 Fax: (614) 280 8881
PRINT DATE: 11/8/2012 4:43:57 PM

Columbus, Ohio 43215 www.moodynolan.com

1 OVERALL BASEMENT LEVEL PLUMBING PLAN DRAWN BY: CHECKED BY: APPROVED BY:
P110 SCALE: 1/16" = 1' 0" FINISHED FLOOR = 1163.0' N.J.B. B.C.S. B.C.S. 11279.00

Overall Basement Level P110


FILE INFO:

Plumbing Plan
95% Construction Documents 11/9/2012
KEY NOTES
1 6" ST UP TO LEVEL ABOVE.

2 (N) 2" W DOWN IN (E) CHASE TO BFF. SAWCUT (E) FLOOR AND PATCH TO
MATCH EXISTING TO ACCOMMODATE NEW WASTE ROUTING.

3 8" ST UP TO LEVEL ABOVE.

4 3/4" CW UP TO LEVEL ABOVE.

5 1/2" CW AND 1"1/2" W UP TO LEVEL ABOVE.

6 CONNECT 2" HW TO (E) 1"1/2" HW. REDUCE TO 1" HW IN DEDUCT


ALTERNATE #6 EXTENDED BACK TO NEW MECHANICAL ROOM.

7 CONNECT (N) 4" W TO (E) 6" W BFF AND (N) 3" CW TO (E) 3" CW CAPPED
ABOVE CEILING. CAP (E) 3" NP FOR FUTURE USE.

8 CONNECT (N) 3/4" HWC TO (E) 3/4" HWC ABOVE CEILING. REDUCE NEW
3/4" HWC PIPING TO 1/2" AND PROVIDE (N) BALANCING VALVE IN
DEDUCT ALTERNATE #6. SET TO 1 GPM.

9 2" FORCED WASTE UP FROM PUMP IN ELEVATOR PIT AND OFFSET


ABOVE ADJACENT CEILING. RE: DETAIL 5/P801.

10 4" ST UP TO PLANTER DRAIN ABOVE.

11 4" F UP TO FIRE DEPARTMENT CONNECTION ABOVE.


DWH"1A 12
12 PROVIDE REPLACEMENT TUBE BUNDLE IN (E) STORAGE TANK FOR
CONNECTION TO BUILDING HEATING HOT WATER LOOP IN DEDUCT
ALTERNATE #6.

13 4" ST UP TO TERRACE DRAIN WITHIN COURTYARD DECK ABOVE. RE:


ARCHITECTURAL DETAILS.

14 4" ST FROM LEVEL ABOVE.

15 4" OD FROM LEVEL ABOVE COMBINED WITH 2" FORCED MAIN TO


DOWNSPOUT NOZZLE MOUNTED AT 12" AFG.

16 CONNECT (N) 2" W TO (E) 2" W CAPPED ABOVE CEILING.

17 CONNECT (N) 2" W TO (E) 2" W TO LEVEL ABOVE.

18 CONNECT (N) 1/2" CW TO (E) 1/2" CW ABOVE CEILING.

19 CONNECT (N) 1/2" CW TO (E) CW MAIN ABOVE CEILING.

20 CONNECT (N) 1" CW TO (E) CW MAIN ABOVE CEILING.

21 (N) 1/2" CW DOWN TO (E) SHOWERHEAD (E) CW SUPPLY STUBBED IN


WALL.

22 CONNECT (N) 1" CW AND (N) 3/4" HW TO (E) CW AND (E) HW CAPPED
ABOVE CEILING. CONNECT (N) 2" V TO (E) 3" V ABOVE CEILING. EXTEND
(N) 1/2" CW AND (N) 1/2" HW FROM NEW TAPS DOWN IN WALL TO (E)
SHOWER VALVE.

23 2" W FROM LEVEL ABOVE. COMBINE WITH 4" W IN WALL AND OFFSET TO
BFF. CONNECT TO (E) WASTE MAIN BFF. SAWCUT (E) FLOOR AND PATCH
TO MATCH EXISTING AS NECESSARY.

24 CONNECT (N) 3/4" CW TO (E) 3/4" CW CAPPED ABOVE CORRIDOR.

22

2" SH 1
1" 1/2"
WC 1
21
L 1 3/4"

Family Restroom WCO 1"


24
027 SA
21 Stair 1
23
1" Z003
6 2
2"
Adaptive PE
8
009

1/2" 7 20 19
17
Keyplan
2"
2"

1 1/2" 5 2
5
16
Storage 2"
1/2"
4" 5 18
NP

002 3"
3" (E) BASEMENT
2"
Lower Level Hall
Lower Level Hall 3/4" East
Storage West
F002
3 003 F001 2 BASEMENT
1

ST 1 1/4" ST ST ST
3/4"
8"
Lower Level Hall 10"
6" South
8"

ST
EWC 2 Q002 2"
NP

# Date Change Description


4"
2"
9 SP"1
Women's
3" 4"
Restroom
R006 10

4
APArchitects, LLC Reese Engineering
3
Associate Architect MEP Engineer
P501 Elevator The EDGE Group CD+M Lighting Design Group
Telecom Equipment 10 Landscape Architect Lighting Designer
ST

005 Sweetland Engineering Code Consultants, Inc


M007 Civil Engineer Code Consultant
KORDA Engineering Rider Levett Bucknall
1
4" Structural Engineer Cost Estimator
P501
Classroom
Multipurpose 008 IM BUILDING ADDITION AND RENOVATION
Storage Room PHASE I
2"
007A 007

ST
University Park, Pennsylvania 16802
for
3/4"
THE PENNSYLVANIA
C:\Users\bgoss\Documents\2010159_MEP_bgoss.rvt

4"
2" Mechanical 3/4"
4" 4" STATE UNIVERSITY
M004 PSU# 09 12181.00 PSU Building # 0804 000
4

2"
14

11 300 Spruce Street Phone: (614) 461 4664


Suite 300 Fax: (614) 280 8881
PRINT DATE: 11/8/2012 4:46:18 PM

Columbus, Ohio 43215 www.moodynolan.com


13 13
6"
4"
15 DSN"1
1 BASEMENT LEVEL PLUMBING PLAN DRAWN BY:
N.J.B.
CHECKED BY:
B.C.S.
APPROVED BY:
B.C.S. 11279.00
P111 SCALE: 1/8" = 1'"0" FINISHED FLOOR = 1163.0'

P111
FILE INFO:

Basement Level Plumbing Plan


95% Construction Documents 11/9/2012
KEY NOTES
1 8" ST FROM LEVEL ABOVE DOWN IN CHASE TO LEVEL BELOW.

2 3" V FROM LEVEL BELOW AND UP TO LEVEL ABOVE.

3 4" ST FROM ABOVE CEILING AND DOWN IN CHASE TO LEVEL BELOW.

4 4" RD UP TO ROOF DRAIN ABOVE.

5 6" ST UP TO LEVEL ABOVE.

6 6" ST DOWN IN CHASE TO LEVEL BELOW.

7 3/4" CW DOWN IN WALL/CHASE TO SILLCOCK MOUNTED AT 24" AFG.

8 2" W DOWN IN CHASE TO LEVEL BELOW.

9 4" OD UP TO OVERFLOW DRAIN ABOVE.

10 8" ST DOWN FROM LEVEL ABOVE, OFFSET BELOW STAIRS TO


DOWNSPOUT NOZZLE MOUNTED AT 12" AFG.

11 6" ST OFFSET DOWN TO ABOVE CEILING BELOW AND IN CHASE TO BFF.

12 DOWNSPOUT NOZZLE MOUNTED AT 12" AFG.

13 4" GALVANIZED PIPE UP IN CHASE FROM LEVEL BELOW TO FIRE


DEPARTMENT CONNECTION MOUNTED AT 36" AFG.

14 1" CW AND 2" W UP IN CHASE FROM LEVEL BELOW TO LEVEL ABOVE.

15 3/4" CW UP TO HOSE BIBB ON LEVEL ABOVE.

16 4" W UP TO FLOOR DRAIN ON LEVEL ABOVE AND 2" V UP TO LEVEL


ABOVE.

17 4" W DOWN ON COLUMN TO LEVEL BELOW.

18 3/4" CW UP FROM LEVEL BELOW TO SILLCOCK MOUNTED AT 24" AFF.

19 4" RD UP TO TERRACE DRAIN ON LEVEL ABOVE.

20 EXTEND 1/2" CW IN WALL FROM SINK TO ICEMAKER BOX MOUNTED IN


LOCATION RECOMMENDED BY REFERIGERATOR MANUFACTURER.

21 (N) 1&1/2" W AND (N) 1/2" CW UP FROM LEVEL BELOW TO WATER


COOLER. EXTEND (N) 2" V UP IN CHASE TO LEVEL ABOVE.

22 (N) 2" W AND (N) 1/2" CW UP FROM LEVEL BELOW TO WATER COOLER.
EXTEND (N) 2" V UP IN CHASE TO LEVEL ABOVE.

23 (N) 2" W AND (N) 1/2" CW UP IN CHASE FROM LEVEL BELO TO LEVEL
ABOVE.

A B

Stair 3
Z107 Equipment
Checkout
121

21 EWC 1

Day Lockers 22 Daylockers Daylockers


120 203E 203F

1 Main Level Hall


Q101

Stair 8
3/4" 5 15 Daylockers
Z109 Men's Restroom
203G
R128 8 EWC 2 EWC 2
SC&1 7

3/4" 3/4"
4" Storage Janitor
6 Elevator
125A J127
2" Electric V101 Keyplan
16 16 14
Storage 16 Storage 1/2" Vending
P102
124A 4" 123 Women's 2
102
4"
Storage Restroom Office
10
17 126 R127 101A

Workroom
17
101M Conference Room
Office
101L A
11 101B

4" 2
Offices
P501
101
RD

Multipurpose Multipurpose
Room Room
RD

124 125
4" 4"
20 IB 1 S 1 Director # Date Change Description
RD
3/4" 1/2" Office 101K
4 4
Office 101J
4 Office 19 Office
Break Room 101H
Office 101F 101G RD
9 101C 19 Office
101E 4"
101D RD

3/4" RD 4" 19 18 SC&1


APArchitects, LLC Reese Engineering
Associate Architect MEP Engineer
The EDGE Group CD+M Lighting Design Group
Landscape Architect Lighting Designer
4" Sweetland Engineering Code Consultants, Inc
A B Civil Engineer Code Consultant
12 13 KORDA Engineering Rider Levett Bucknall
Structural Engineer Cost Estimator
3
7 SC&1
IM BUILDING ADDITION AND RENOVATION
PHASE I
University Park, Pennsylvania 16802
for
THE PENNSYLVANIA
C:\Users\bgoss\Documents\2010159_MEP_bgoss.rvt

STATE UNIVERSITY
PSU# 09#12181.00 PSU Building # 0804#000

300 Spruce Street Phone: (614) 461#4664


Suite 300 Fax: (614) 280#8881
PRINT DATE: 11/8/2012 4:48:53 PM

Columbus, Ohio 43215 www.moodynolan.com

1 MAIN LEVEL PLUMBING PLAN AREA A DRAWN BY: CHECKED BY: APPROVED BY:
P121 SCALE: 1/8" = 1'&0" N.J.B. B.C.S. B.C.S. 11279.00

Main Level Plumbing Plan # P121


FILE INFO:

Area A
95% Construction Documents 11/9/2012
GENERAL NOTES (THIS SHEET ONLY)

A. REFER TO COLD WATER ISOMETRIC DIAGRAM 5/P601 FOR FITNESS (103)


WATER COOLER PIPING.

B. REFER TO WASTE AND VENT ISOMETRIC DIAGRM 6/P601 FOR FITNESS


(103) WATER COOLER PIPING.

KEY NOTES
1 6" ST DOWN IN CHASE FROM LEVEL ABOVE TO BFF.

2 3/4" CW UP IN STUD SPACE FROM LEVEL BELOW TO SILLCOCK MOUNTED


AT 30" AFF. LOCATE ON INTERIOR SIDE OF INSULATION.

3 EXTEND 3/4" CW DOWN IN WALL TO SILLCOCK MOUNTED AT 24" AFG.

4 8" ST DOWN ON WALL TO DOWNSPOUT NOZZLE MOUNTED AT 12" AFG.

5 (N) 2" W AND (N) 1/2" CW FROM BELOW AND UP IN CHASE TO LEVEL
ABOVE.

6 CONNECT (N) EWC&1 TO (E) 1/2" CW AND (E) 1&1/2" W.

7 2" W DOWN TO BFF.

8 8" OD DOWN IN CHASE FROM LEVEL ABOVE AND OFFSET ABOVE


CEILING AT 1/4" PER FOOT SLOPE MIN.

9 3/4" CW AND 2" V UP IN CHASE TO LEVEL ABOVE. 2" W DOWN IN CHASE


FROM LEVEL ABOVE TO BFF.

A B

Stair 1
Z103

Stair 2
Z104

Lounge
106
EWC 1 6

Daylockers
203F
5

1
Main Level Hall
Q101

Stair 4 Stair 5
Keyplan
9 4 DSN&1
PD 1 Z101 3/4" Z102
2"
OD
3 SC&1
2 SC&1 3/4" A/V/ Storage
8"
PD 1
Fitness Office 103B
103A
B

EWC 1 EWC 2
Vestibule
Fitness 7 Corridor
Lobby F101
103 Q105
F102

# Date Change Description


TD 1
TD 1
TD 1

APArchitects, LLC Reese Engineering


Associate Architect MEP Engineer
The EDGE Group CD+M Lighting Design Group
Landscape Architect Lighting Designer
Sweetland Engineering Code Consultants, Inc
A B Civil Engineer Code Consultant
KORDA Engineering Rider Levett Bucknall
Structural Engineer Cost Estimator

IM BUILDING ADDITION AND RENOVATION


PHASE I
University Park, Pennsylvania 16802
for
THE PENNSYLVANIA
C:\Users\bgoss\Documents\2010159_MEP_bgoss.rvt

STATE UNIVERSITY
PSU# 09 12181.00 PSU Building # 0804 000

300 Spruce Street Phone: (614) 461 4664


Suite 300 Fax: (614) 280 8881
PRINT DATE: 11/8/2012 4:51:02 PM

Columbus, Ohio 43215 www.moodynolan.com

1 MAIN LEVEL PLUMBING PLAN AREA B DRAWN BY: CHECKED BY: APPROVED BY:
P122 SCALE: 1/8" = 1'&0" N.J.B. B.C.S. B.C.S. 11279.00

Main Level Plumbing Plan P122


FILE INFO:

Area B
95% Construction Documents 11/9/2012
KEY NOTES
1 4" RD UP TO ROOF DRAIN ABOVE.

2 8" ST DOWN IN CHASE TO LEVEL BELOW.

3 3/4" CW FROM LEVEL BELOW TO HOSE BIBB MOUNTED AT 36" AFF.

4 6" ST DOWN ON WALL TO LEVEL BELOW.

5 3" V FROM LEVEL BELOW UP IN CHASE TO 3" VENT THROUGH ROOF.

6 1" CW AND 2" W FROM LEVEL BELOW OFFSET IN CHASE TO WATER


COOLER. CONNECT TO 2" V FROM WATER COOLER TO 3" V FROM
LEVEL BELOW AND EXTEND UP TO 3" VENT THROUGH ROOF. OFFSET 1"
CW ABOVE CEILING.

7 8" OD UP TO OVERFLOW DRAIN ABOVE.

8 8" OD DOWN TO LEVEL BELOW.

9 1/2" CW AND 2" W FROM LEVEL BELOW UP TO WATER COOLER. EXTEND


2" V UP IN CHASE TO 3" VENT THROUGH ROOF.

10 2" V UP FROM LEVEL BELOW, OFFSET ABOVE CEILING, AND CONNECTED


INTO (E) 2" V.

11 2" V UP DUCT FROM LEVEL BELOW AND OFFSET AS HIGH AS POSSIBLE.

12 INCREASE 2" V TO 3" V AT 40' OF TOTAL LENGTH.

13 3" V UP TO 3" VENT THROUGH ROOF.

A B

Stair 3
Z207

Stair 7
Z208

10
Mezzanine Hall
Landing West Stair EWC 2
C203
3" VTR 9

8" 6"

RD RD RD RD
7
1 4 1 1 4 3 HB(2 4" 1 6" 1 1 4" 4" 1 1"
1"
Mezzanine Hall
Landing Elevator
OD

201
8"
4" FD 2

4" FD 2 Stair 8 4" FD 2 Elevator Keyplan


2"
Mechanical
3" Z209 EWC 1 6
V201
M202
8

(E) 2"

12 12
3" VTR
13 3" VTR
11

Workroom
A
203A Fitness
11
203

5 3" VTR

# Date Change Description

RD 1 RD 1 RD 1
TD 1 TD 1

TD 1
Landscape
OD 2
43
APArchitects, LLC Reese Engineering
Associate Architect MEP Engineer
The EDGE Group CD+M Lighting Design Group
Landscape Architect Lighting Designer
Sweetland Engineering Code Consultants, Inc
A B Civil Engineer Code Consultant
KORDA Engineering Rider Levett Bucknall
Structural Engineer Cost Estimator

IM BUILDING ADDITION AND RENOVATION


PHASE I
University Park, Pennsylvania 16802
for
THE PENNSYLVANIA
C:\Users\bgoss\Documents\2010159_MEP_bgoss.rvt

STATE UNIVERSITY
PSU# 09 12181.00 PSU Building # 0804 000

300 Spruce Street Phone: (614) 461 4664


Suite 300 Fax: (614) 280 8881
PRINT DATE: 11/8/2012 4:53:40 PM

Columbus, Ohio 43215 www.moodynolan.com

1 MEZZANINE LEVEL PLUMBING PLAN AREA A DRAWN BY: CHECKED BY: APPROVED BY:
P131 SCALE: 1/8" = 1'(0" N.J.B. B.C.S. B.C.S. 11279.00

Mezzanine Level Plumbing P131


FILE INFO:

Plan Area A
95% Construction Documents 11/9/2012
GENERAL NOTES
A. REFER TO COLD WATER ISOMETRIC DIAGRAM 5/P601 FOR FITNESS (203)
WATER COOLER PIPING.

B. REFER TO WASTE AND VENT ISOMETRIC DIAGRAM 6/P601 FOR FITNESS (203)
WATER COOLER PIPING.

KEY NOTES
1 4" RD UP TO ROOF DRAIN ABOVE.

2 6" ST DOWN IN CHASE TO BFF.

3 6" ST, 3/4" CW AND 2" V TO LEVEL BELOW. EXTEND 2" V UP TO 3"
VENT THROUGH ROOF.

4 OFFSET 2" V FROM WATER COOLER ABOVE CEILING AND EXTEND UP


TO 3" VENT THROUGH ROOF.

5 1/2" CW AND 2" W UP IN CHASE FROM LEVEL BELOW TO EWC 1. 2"


VENT EXTENDED UP IN CHASE TO (E) 2" V.

6 8" OD UP TO OVERFLOW DRAIN ABOVE. SLOPE AT 1/4" PER FOOT


MIN.

7 8" ST DOWN IN CHASE TO LEVEL BELOW.

A B

Mezzanine Hall
Landing East Stair
201

5 EWC 2

1"

RD RD RD RD
8"
1 1" 1 6" 1 6" 1" 1 1 6" 1
6 2

OD
4
Stair 5
3" VTR
EWC 1 Z202
Keyplan
3

Telecom
203B

Fitness
203 Fitness
203
# Date Change Description

APArchitects, LLC Reese Engineering


Associate Architect MEP Engineer
The EDGE Group CD+M Lighting Design Group
Landscape Architect Lighting Designer
Sweetland Engineering Code Consultants, Inc
A B Civil Engineer Code Consultant
KORDA Engineering Rider Levett Bucknall
Structural Engineer Cost Estimator

IM BUILDING ADDITION AND RENOVATION


PHASE I
University Park, Pennsylvania 16802
for
THE PENNSYLVANIA
C:\Users\bgoss\Documents\2010159_MEP_bgoss.rvt

STATE UNIVERSITY
PSU# 09 12181.00 PSU Building # 0804 000

300 Spruce Street Phone: (614) 461 4664


Suite 300 Fax: (614) 280 8881
PRINT DATE: 11/8/2012 4:56:21 PM

Columbus, Ohio 43215 www.moodynolan.com

1 MEZZANINE LEVEL PLUMBING PLAN AREA B DRAWN BY: CHECKED BY: APPROVED BY:
P132 SCALE: 1/8" = 1' 0" N.J.B. B.C.S. B.C.S. 11279.00

Mezzanine Level Plumbing P132


FILE INFO:

Plan Area B
95% Construction Documents 11/9/2012
KEY NOTES
1 (E) 3" FLOOR DRAIN TO REMAIN.

2 CONNECT (N) 3" W TO (E) 3" W BELOW PENTHOUSE SLAB ABOVE CEILING
BELOW.

3"FD 2

3"FD 2
1
(E) 3"
3" CO
3"FD 2
CO
3" (E) 3"
3" 3"

2 1 2 Keyplan
3"FD 2
3"FD 2

# Date Change Description

APArchitects, LLC Reese Engineering


Associate Architect MEP Engineer
The EDGE Group CD+M Lighting Design Group
Landscape Architect Lighting Designer
Sweetland Engineering Code Consultants, Inc
Civil Engineer Code Consultant
KORDA Engineering Rider Levett Bucknall
Structural Engineer Cost Estimator

IM BUILDING ADDITION AND RENOVATION


PHASE I
University Park, Pennsylvania 16802
for
THE PENNSYLVANIA
C:\Users\bgoss\Documents\2010159_MEP_bgoss.rvt

STATE UNIVERSITY
PSU# 09 12181.00 PSU Building # 0804 000

300 Spruce Street Phone: (614) 461 4664


Suite 300 Fax: (614) 280 8881
PRINT DATE: 11/8/2012 4:59:13 PM

Columbus, Ohio 43215 www.moodynolan.com

1 MECHANICAL PENTHOUSE LEVEL PLUMBING PLAN DRAWN BY: CHECKED BY: APPROVED BY:
P140 SCALE: 1/16" = 1'$0" N.J.B. B.C.S. B.C.S. 11279.00

Mechanical Penthouse Level P140


FILE INFO:

Plumbing Plan
95% Construction Documents 11/9/2012
GENERAL NOTES (THIS SHEET ONLY)

A. ALL ROOF DRAINS AND VENTS THROUGH ROOF SHOWN WITHOUT LABELS ARE EXISTING TO REMAIN.

Keyplan

# Date Change Description

OD 1 8" 4" RD 1 4" RD 1 4" RD 1 RD 1 4" 4" RD 1 4" RD 1 4" RD 1 4" RD 1 4" RD 1 4" RD 1 4" RD 1 4" RD 1 RD 1 4" 8" OD 1

3" VTR
APArchitects, LLC Reese Engineering
Associate Architect MEP Engineer
3" VTR The EDGE Group CD+M Lighting Design Group
3" VTR
Landscape Architect Lighting Designer
Sweetland Engineering Code Consultants, Inc
Civil Engineer Code Consultant
KORDA Engineering Rider Levett Bucknall
3" VTR Structural Engineer Cost Estimator

IM BUILDING ADDITION AND RENOVATION


PHASE I
University Park, Pennsylvania 16802
for
THE PENNSYLVANIA
C:\Users\bgoss\Documents\2010159_MEP_bgoss.rvt

STATE UNIVERSITY
PSU# 09 12181.00 PSU Building # 0804 000

300 Spruce Street Phone: (614) 461 4664


Suite 300 Fax: (614) 280 8881
PRINT DATE: 11/8/2012 5:01:24 PM

Columbus, Ohio 43215 www.moodynolan.com

1 ROOF PLUMBING PLAN DRAWN BY: CHECKED BY: APPROVED BY:


P150 SCALE: 1/16" = 1' 0" N.J.B. B.C.S. B.C.S. 11279.00

P150
FILE INFO:

Roof Plumbing Plan


95% Construction Documents 11/9/2012
KEY NOTES
1 3/4" CW AND 3/4" HW DOWN IN CHASE.

2 HOSE BIBB MOUNTED AT 24" AFF BELOW COUNTER.

3 1" CW, 1" HW AND 4" W UP FROM LEVEL BELOW AND OFFSET IN CHASE.
EXTEND 1" CW AND 3/4" HW UP IN CHASE TO ABOVE CEILING.

4 2" NP UP IN CHASE TO ABOVE CEILING.

5 2" V AND 3" V COMBINED INTO SINGLE 3" V IN CHASE AND EXTENDED
UP TO LEVEL ABOVE.

6 1" CW, 2"W AND 3"V UP IN CHASE TO LEVEL ABOVE.

1 7 4" W UP TO LEVEL
3"
8 2" V UP IN CHASE TO ABOVE CEILING.

2"
3" 9 4" W TO BFF.
L 1 2" 1" 10 4" REUSE WATER EXTENDED INTO BUILDING, CAPPED AND VALVED FOR
FUTURE USE. SLEEVE THROUGH FOUNDATION WALL. REFER TO CIVIL
1"
HB 1 2
Women's DOCUMENTS FOR CONTINUATION.
Restroom

NP
11 2" W UP TO LEVEL ABOVE.
L 1 R006
12 1 1/4" CW, 1" HW AND 4" W UP TO LEVEL ABOVE.
6
13 2 1/2" NP UP TO LEVEL ABOVE.
2" 3" 2"
4
14 6" COMBINATION DOMESTIC WATER/FIRE SERVICE EXTENDED TO 5' 0"
FROM BUILDING EXCAVATION LINE. SLEEVE THROUGH FOUNDATION
ST WALL PER STRUCTURAL ENGINEER'S REQUIREMENTS. CONNECT TO SITE
WC 1 WATER SERVICE EXTENDED UP TO BUILDING IN SITE UTILITIES PORTION
8" OF WORK.
3" FD 1

NP
15 4" FIRE SERVICE DOUBLE CHECK BACKFLOW PREVENTER MOUNTED AT
24" AFF.
4" 2" WC 1
CO 16 2" HW(140), 2" CW AND 3/4" HWC DOWN TO WATER HEATERS. REFER
11 19 HB 2 TO DETAIL 1/P801. DELETE IN DEDUCT ALTERNATE #6 AND ALL
ASSOCIATED PIPING BACK TO MAINS. RE: DETAIL 1/P801.
1/2" 4" 3"
17 2" HW(140), 2" CW AND 3/4" HWC DOWN TO MIXING VALVES PIPED IN
WC 1
PARALLEL. DELETE IN DEDUCT ALTERNATE #6 AND ALL ASSOCIATED
2" 3/4" 3/4"
PIPING BACK TO MAINS.
1"

NP
1 1/4" 1 1/4" 3" FD 1
4" 1 1/4" 18 3/4" HWC TO AND FROM CIRC PUMPS PIPED IN PARALLEL. DELETE IN
DEDUCT ALTERNATE #6 AND ALL ASSOCIATED PIPING BACK TO MAINS.
WC 1 RE: DETAIL 2/P801.
2"
DHWP 1
18
DHWP 2 19 3/4" CW DOWN TO HOSE BIBB MOUNTED AT 36" AFF.

NP
2" 1"
3"
3" 20 (2) 4" DOUBLE CHECK BACKFLOW PREVENTERS (BFP DC 1&2;
4" FD 2 WC 1 CONBRACO 45 600 SERIES) PIPED SYMETRICALLY IN PARALLEL WITH
4" UPPER BACKFLOW PREVENTER AT 60" AFF. MAX. RE: DETAIL 4/P801.
CO 12 2"
4" 21 WATER SERVICE METER PROVIDED BY OWNER MOUNTED AT 24" AFF.
17 MV 1 WC 1 PROVIDE WITH METER STRAINER, ISOLATION VALVES AND BYPASS. RE:
4" FD 2 DETAIL 4/P801.
3/4"

140
22 1" CW DOWN ON WALL TO MAKE UP WATER ASSEMBLY (BFP RP 1;
4"
3" 2" CONBRACO 40 200). RE: DETAIL 3/P801.
2" 3" FD 1
25 4" 23 2" FORCED DISCHARGE AND 2" V UP ON WALL FROM BFF.
3"
1" 3/4" 24 SUMP PIT FOR CONNECTION TO UNDERSLAB GROUNDWATER DRAINAGE.
COORDINATE CONNECTION(S) IN THE FIELD WITH G.C.
WC 1 RE: DETAIL 6/P801.
4" FD 2 4" FD 2 2"
WCO
13 25 DOMESTIC HOT WATER SYSTEM EXPANSION TANK. RE: DETAIL 1/P801.
DELETE IN ALTERNATE #6.
4" SA
3"
26 CAPPED 3" NP FOR FUTURE CONNECTION TO CAMPUS RE USE LINE.
4"
27 2" V UP ON WALL FROM BFF.
16 DWH 1&2
NOTE: REFER TO DOMESTIC WATER ISOMETRIC DIAGRAM 1/P601 AND WASTE AND VENT
4" FD 2 ISOMETRIC DIAGRAM 2/P601.

4" FD 2 4" FD 2

ENLARGED BASEMENT LEVEL


4"
WOMEN'S RESTROOM R007
3"
3"
1 PLUMBING PLAN
P501 SCALE: 1/4" = 1' 0"
4" FD 2 3" 23
4" FD 2

4" 26
4" 2"

1"
2" 4"

HB 2 19
2" 2"
20 SP 2&3 24
4" FD 2
4" FD 2 22
4"

Women's
4" Mechanical
4" FD 2 4" 4" FD 2 Restroom Keyplan
M004 Janitor Men's Restroom
2" R127
R128
J127 3/4"
3
21 2" 4"
4"
7

4" FD 2 9 L 1
4" L 1
4" 1/2"
2" 2"
4" FD 2 HB 1 2 2 HB 1
4" SS 1
10 F
2"
2" L 1
4" L 1
SA 4
15 WC 1
2" L 1
2" 8 U 1
4 NP

2" 3" FD 1
2"
WC 1
14 27 WC 1
2" 3"
6" 2" U 1
NP

4"
3" FD 1 3" FD 1
2" # Date Change Description
4" WC 1 WC 1 2"
U 1
3"

NP
4" WC 1
WC 1
WC 1

3"
NP

4"
WC 1
3 ENLARGED BASEMENT LEVEL MECHANICAL ROOM PLUMBING PLAN 2"
3" FD 1
1/2" 1"
2" 3" FD 1
APArchitects, LLC Reese Engineering
P501 SCALE: 1/4" = 1' 0" WC 1 2" Associate Architect MEP Engineer
The EDGE Group CD+M Lighting Design Group
5 Landscape Architect Lighting Designer
3" FD 1 Sweetland Engineering Code Consultants, Inc
WC 1 WC 1
2" Civil Engineer Code Consultant
SA
3" 1" KORDA Engineering Rider Levett Bucknall
1" Structural Engineer Cost Estimator
WC 1 WCO
4"
WC 1 2" 4" IM BUILDING ADDITION AND RENOVATION
WCO
SA PHASE I
University Park, Pennsylvania 16802
for
THE PENNSYLVANIA
C:\Users\bgoss\Documents\2010159_MEP_bgoss.rvt

STATE UNIVERSITY
PSU# 09 12181.00 PSU Building # 0804 000
NOTE: REFER TO DOMESTIC WATER ISOMETRIC DIAGRAM 3/P601 AND WASTE AND VENT
ISOMETRIC DIAGRAM 4/P601.

2 ENLARGED MAIN LEVEL BATHROOM GROUP PLAN 300 Spruce Street Phone: (614) 461 4664
P501 SCALE: 1/4" = 1' 0"
Suite 300 Fax: (614) 280 8881
PRINT DATE: 11/8/2012 5:04:15 PM

Columbus, Ohio 43215 www.moodynolan.com

DRAWN BY: CHECKED BY: APPROVED BY:


N.J.B. B.C.S. B.C.S. 11279.00

P501
FILE INFO:

Enlarged Plumbing Plans


95% Construction Documents 11/9/2012
3/4"

1/2"

1" SA 1"
IB 1
2"
2"

S 1 WC 1
2" 1/2"
WC 1

1"

SA 3/4"
2"
1"
1/2" WC 1
SA WC 1
1" SA
1"
WC 1 3/4" 1" SS 1
WC 1 2"
2" WC 1
2" 1/2"
WC 1 1"
WC 1 3/4" WC 1
NP
3/4" 3/4"
U 1 WC 1 L 1 WC 1
EWC 1 3/4" 2" NP
WC 1

U 1 WC 1

2" 3/4" WC 1
1/2"
3/4"
WC 1
L 1
L 1
HB 1
HB 1
3/4" L 1

1 1/4"

EWC 2 1"

EWC 1

AREA B WATER COOLERS COLD BASEMENT LEVEL DOMESTIC


3 MAIN LEVEL DOMESTIC WATER ISOMETRIC DIAGRAM
5 WATER ISOMETRIC DIAGRAM P601 SCALE: NONE 1 WATER ISOMETRIC DIAGRAM
P601 SCALE: NONE
P601 SCALE: NONE

3" VTR

2"

4" 2"
2" WCO

WC 1 2"
S 1

2" WC 1
3" FD 1 2" 4"
3" 2"
2"
EWC 1 3" FD 1 WC 1
WC 1
2" 3" 3" 3" FD 1 2"
3" 4"
3" 3"
WC 1 3" SS 1
2"
2" 3" 2"
2"
4"
WCO
2" WC 1 4" 4"
3" FD 1 WCO 2"

4" 3" WC 1
2" 4" 3"
L 1 3"
WC 1 2" WC 1

WC 1 3" FD 1 WC 1 2"

U 1 2"
WC 1
3" FD 1 L 1 2"
WC 1
EWC 2
4"
3" FD 1 WC 1
Keyplan
EWC 1 4" WC 1
3" FD 1
2" 4"
3" FD 1 U 1
3"
L 1 L 1 2"
4"
2"
3"

3"

BASEMENT LEVEL WASTE &


AREA B WATER COOLERS WASTE & 2 VENT ISOMETRIC DIAGRAM
6 VENT ISOMETRIC DIAGRAM 4 MAIN LEVEL WASTE & VENT ISOMETRIC DIAGRAM P601 SCALE: NONE
# Date Change Description
P601 SCALE: NONE P601 SCALE: NONE

APArchitects, LLC Reese Engineering


Associate Architect MEP Engineer
The EDGE Group CD+M Lighting Design Group
Landscape Architect Lighting Designer
Sweetland Engineering Code Consultants, Inc
Civil Engineer Code Consultant
KORDA Engineering Rider Levett Bucknall
Structural Engineer Cost Estimator

IM BUILDING ADDITION AND RENOVATION


PHASE I
University Park, Pennsylvania 16802
for
THE PENNSYLVANIA
C:\Users\bgoss\Documents\2010159_MEP_bgoss.rvt

STATE UNIVERSITY
PSU# 09 12181.00 PSU Building # 0804 000

300 Spruce Street Phone: (614) 461 4664


Suite 300 Fax: (614) 280 8881
PRINT DATE: 11/8/2012 5:06:00 PM

Columbus, Ohio 43215 www.moodynolan.com

DRAWN BY: CHECKED BY: APPROVED BY:


N.J.B. B.C.S. B.C.S. 11279.00

P601
FILE INFO:

Plumbing Isometric Diagrams


95% Construction Documents 11/9/2012
PUMP SCHEDULE
NON ELECTRICAL
OVERLOADING IMPELLER OPERATING
DESIG. SERVICE TYPE GPM TDH (FT) RPM HP BHP VOLTS Ø HZ SIZE (IN) EFFIC. (%) WEIGHT MANUFACTURER MODEL NOTES
DHWP 1 INLINE PUMP DOMESTIC HOT 15 50 1750 2 2 480 3 60 7 31 BELL & GOSSETT SERIES 60 1, 2, 3
WATER
DHWP 2 INLINE PUMP DOMESTIC HOT 15 50 1750 2 2 480 3 60 7 31 BELL & GOSSETT SERIES 60 1, 2, 3
WATER
SP 1 SUMP PUMP SUMP PUMP 50 30 3450 1/2 0 115 1 60 0 0 ZOELLER OIL SMART SYSTEM #940 0014 4
SP 2&3 SUMP PIT SUMP PUMP 30 27 3540 1/2 0 115 1 60 0 0 ZOELLER 4161 5

1. ALL BRONZE CONSTRUCTION. MOTOR HP SHALL EXCEED NOL BHP.


2. FURNISH COMBINATION STARTER DISCONNECT.
3. DELETE IN ALTERNATE #6.
4. SYSTEM COMPONENTS SHALL INCLUDE BUT NOT BE LIMITTED TO: AUDIBLE LIGHT AND ALARM, 20 FT. PIGGYBACK ELECTRICAL SUPPLY CORD, 20 AMP RELAY, NEMA 312 ENCLOSURE AND UL508 APPROVED SWITCH.
5. PROVIDE ZOELLER #10 1039 DUPLEX CONTROLLER WITH HIGH WATER ALARM AND #39 0003 RAIL SYSTEM WITH LENGTH CORRESPONDING TO PIT DEPTH.

SINK SCHEDULE
ADA
PLAN CODE FIXTURE MANUFACTURER MODEL COMPLIANT CONSTRUCTION GAUGE HOLE DRILLINGS SIZE FAUCET DRAIN NOTES
S 1 SINK ELKAY LRAD 2222 Yes 302 ST/ST 18 3 @ 4" CENTERS 25" x 22" x 6 1/2" KOHLER K 15172 LK 35 1
SS 1 MOP SINK FIAT TSB 3010 No TERRAZZO 24" x 24" x 12" FIAT 830 AA 1453 BB 2, 3

1. PROVIDE 1/2" x 3/8" WHEEL HANDLE ANGLE VALVE VALVES WITH 20" RISERS, 1 1/2" CHROME BRASS TRAPS AND ONE PIECE CHROME ESCUTCHEONS.
2. PROVIDE WITH CHECK VALVES ON BOTH SUPPLIES. PROVIDE WITH 832 AA HOSE AND BRACKET AND 889 CC MOP HANGER.
3. PROVIDE AND INSTALL CHICAGO 952 HOSE BIBB ADJACENT TO FAUCET FOR CONNECTION TO SOAP DISPENSER.

WATER CLOSET SCHEDULE


ADA FLOOR TO RIM
PLAN CODE FIXTURE MANUFACTURER MODEL COMPLIANT COLOR HEIGHT SEAT CARRIER FLUSH VALVE NOTES
WC 1 FLUSH VALVE KOHLER K 4330 Yes WHITE 1' 3" BEMIS 95SSCT JOSAM 12000 6 SLOAN VALVE SOLIS 8111 1.6/1.1 1

1. REFER TO ARCHITECTURAL DRAWINGS FOR ADA COMPLIANT LOCATIONS AND MOUNTING HEIGHTS.

LAVATORY SCHEDULE
ADA
PLAN CODE FIXTURE MANUFACTURER MODEL COMPLIANT COLOR HOLE DRILLINGS SIZE FAUCET NOTES
L 1 UNDERMOUNT ELKAY ELU1511 Yes STAINLESS STEEL CENTERSET 17" x 13" SLOAN EAF 275 1, 2, 3, 4

1. PROVIDE 1/2" x 3/8" WHEEL HANDLE ANGLE VALVE VALVES WITH 12" RISERS, 1 1/4" CHROME BRASS TRAPS; ONE PIECE CHROME ESCUTCHEONS AND 0.5 GPM
AERATOR.
2. PROVIDE WITH TRUEBRO LAV SHIELD.
3. PROVIDE ELKAY LK 174 GRID STRAINER WITH OFFSET TAIILPIECE.
4. PROVIDE WITH SLOAN #MIX 135 A MIXING VALVE PROVIDED WITH LAVATORY AND LOCATED BEHIND SHIELD.

WATER HEATER SCHEDULE


STORAGE DOMESTIC WATER HEATING WATER SIZE (IN) OPERATING
VOLUME GPH EWT LWT EWT LWT WPD WEIGHT
PLAN CODE (GAL) (MAX) (˚F) (˚F) GPM (˚F) (˚F) (PSI) D H (LBS) MANUFACTURER MODEL NOTES
DWH 1&2 470 400 40 140 33 180 160 0.50 36" 120" 7062 CEMLINE #V470JST 1, 2, 3
DWH 1A 800 40 140 67 180 160 0.50 CEMLINE #860 4

1. CEMENT LINED. FIELD APPLIED INSULATION.


2. VERTICAL TANK WITH T & P RELIEF VALVE, 316 ST/ST TANK PENETRATIONS. ASME CERTIFIED.
3. PROVIDE PAIR OF WATER HEATERS WITH ONE AMTROL ST 80V C ASME RATED EXPANSION TANK.
4. EXISTING STORAGE TANK TO REMAIN IN ALTERNATE #6. REPLACE (E) STEAM TUBE BUNDLE WITH NEW HOT WATER BUNDLE.

URINAL SCHEDULE
ADA FLOOR TO RIM
PLAN CODE FIXTURE MANUFACTURER MODEL COMPLIANT COLOR HEIGHT CARRIER NOTES
U 1 FLUSH VALVE KOHLER K 4904 ET Yes WHITE 1' 5" JOSAM 17560 UR 10 1

1. PROVIDE WITH SLOAN VALVE SOLIS 8186 0.125 FLUSH VALVE.

WATER COOLER SCHEDULE


ADA FLOOR TO RIM ELECTRICAL
PLAN CODE MANUFACTURER MODEL COMPLIANT COLOR HEIGHT VOLTS Ø HZ AMPS NOTES
EWC 1 ELKAY EZWS SFGRN28K Yes STAINLESS STEEL 2' 7 1/2" 115 1 60 6 1, 2
EWC 2 ELKAY ENOBM28K Yes STAINLESS STEEL 2' 7 1/2" 115 1 60 4 1
1. PROVIDE 1/2" x 3/8" WHEEL HANDLE ANGLE VALVE WITH 12" CHROME RISER AND ONE PIECE CHROME ESCUTCHEON, 1 1/4" CHROME PLATED
BRASS TRAP.
2. PROVIDE WITH AND PLUMB TO BOTTLE FILLER.

SHOWER SCHEDULE
ADA SHOWER HEAD
PLAN CODE FIXTURE MANUFACTURER MODEL COMPLIANT COLOR SIZE AND VALVE NOTES

SH 1 BUILT IN FIELD Yes SYMMONS 1


25 500 B30 V

1. PROVIDE WITH JOSAM #30000 A 17 FLOOR DRAIN.


Keyplan

PLUMBING EQUIPMENT SCHEDULE


PLAN CODE TYPE MANUFACTURER MODEL NOTES
DSN 1 DOWNSPOUT NOZZLE JOSAM 25010
HB 1 HOSE BIBB WOODFORD B24
HB 2 HOSE BIBB WOODFORD 25
IB 1 ICE MAKER BOX OATEY 38689
MV 1 MIXING VALVE LAWLER 804 (73005) 1
SC 1 SILLCOCK WOODFORD B65
1. PACKAGED PRE PIPED MIXING VALVE STATION.

DRAIN SCHEDULE # Date Change Description


PLAN CODE FIXTURE MANUFACTURER MODEL NOTES
3" FD 1 FLOOR DRAIN JOSAM 30000 A VP 1
3"FD 2 FLOOR DRAIN JOSAM 32100 1
4" FD 2 FLOOR DRAIN JOSAM 32100 1
OD 1 OVERFLOW DRAIN JOSAM 21500 3 22
OD 2 OVERFLOW DRAIN JOSAM 23500 3
PD 1 PLANTER DRAIN JOSAM 39600
RD 1 ROOF DRAIN JOSAM 21500 3 22 APArchitects, LLC Reese Engineering
TD 1 ROOF DRAIN JOSAM 23500 3 Associate Architect MEP Engineer
The EDGE Group CD+M Lighting Design Group
1. PROVIDE WITH TRAP GUARD INSERT. Landscape Architect Lighting Designer
Sweetland Engineering Code Consultants, Inc
Civil Engineer Code Consultant
KORDA Engineering Rider Levett Bucknall
FIXTURE CONNECTION SCHEDULE Structural Engineer Cost Estimator

FIXTURE COLD WATER


HOT WATER
(120˚)
HOT WATER
(140˚) WASTE VENT
IM BUILDING ADDITION AND RENOVATION
2" FLOOR 2" 2" PHASE I
DRAIN
3" FLOOR 3" 2" University Park, Pennsylvania 16802
DRAIN for
4" FLOOR 4" 2" THE PENNSYLVANIA
C:\Users\bgoss\Documents\2010159_MEP_bgoss.rvt

DRAIN
4" FLOOR 4" 2" STATE UNIVERSITY
SINK
ELECTRIC 1/2" 2" 2" PSU# 09 12181.00 PSU Building # 0804 000
WATER
COOLER
F.V. WATER 1" 4" 2"
CLOSET
ICE MAKER 1/2"
BOX
300 Spruce Street Phone: (614) 461 4664
LAVATORY 1/2" 1/2"
Suite 300 Fax: (614) 280 8881
PRINT DATE: 11/8/2012 5:08:02 PM

MOP SINK 1/2" 1/2" 3" 2"


Columbus, Ohio 43215 www.moodynolan.com
SERVICE SINK 3/4" 1/2" 3" 2"
SHOWER 1/2" 1/2"
SINK 1/2" 1/2" 2" 2"
URINAL 3/4" 2" 2" DRAWN BY: CHECKED BY: APPROVED BY:
N.J.B. B.C.S. B.C.S. 11279.00

P701
FILE INFO:

Plumbing Schedules
95% Construction Documents 11/9/2012
3/4"

120°C

140°
2" 2"

2"
EQ EQ
3/4"
THERMOMETER (TYP.)
EQ EQ

T&P PRESSURE RELIEF


VALVE (TYP.)
2"

WATER HEATER

BALL UNION EXPANSION TANK

UNION

ALL PIPING AND CONTROLS


ON BOILER SIDE OF COIL
ARE PROVIDED AND
INSTALLED BY M.C.

D
D D

EXTEND TO ADJACENT
FLOOR DRAIN

6 SUMP PIT DETAIL 1 WATER HEATER DETAIL


P801 SCALE: 1/8" = 1' 0" P801 SCALE: NONE

SHUTOFF VALVE (TYP.)


THERMOMETER (TYP.)

UNION (TYP.)

T & P TEST PLUG (TYP.)

PROVIDE PUMP SUPPORT AT


INLET & DISCHARGE PIPING DO CHECK VALVE (TYP.)
NOT SUPPORT PUMP OR
MOTOR DIRECTLY.

Keyplan

4 WATER SERVICE DETAIL 2 IN LINE CIRCULATING PUMP DETAIL


P801 SCALE: NONE P801 SCALE: NONE

ALARM
SYSTEM
G.F.C.I. TO GRAVITY
DRAIN SYSTEM

PRESSURE GAUGE WITH


SNUBBER # Date Change Description
1 1/2" PRESSURE REDUCING
VALVE SET AT 20 PSI
NOTE:
REDUCED PRESSURE STRAINER
1. COORDINATE INSTALLATION OF SUMP GATE VALVE
BACKFLOW PREVENTER
PUMP COMPONENTS WITH ELEVATOR
MANUFACTURER PRIOR TO INSTALLATION. CHECK VALVE
1" 1"

APArchitects, LLC Reese Engineering


Associate Architect MEP Engineer
The EDGE Group CD+M Lighting Design Group
Landscape Architect Lighting Designer
EXTEND FULL SIZE FUNNEL Sweetland Engineering Code Consultants, Inc
DRAIN TO FLOOR DRAIN Civil Engineer Code Consultant
HIGH WATER ALARM KORDA Engineering Rider Levett Bucknall
FLOAT SWITCH AND DISCHARGE WITH AIR
GAP. Structural Engineer Cost Estimator
1 1/2"
50" MAX. IM BUILDING ADDITION AND RENOVATION
FINISHED SUMP COVER
FLOOR
PHASE I
University Park, Pennsylvania 16802
for
THE PENNSYLVANIA
C:\Users\bgoss\Documents\2010159_MEP_bgoss.rvt

SUMP
PUMP
STATE UNIVERSITY
PSU# 09 12181.00 PSU Building # 0804 000

24"

300 Spruce Street Phone: (614) 461 4664


Suite 300 Fax: (614) 280 8881
PRINT DATE: 11/8/2012 5:08:17 PM

Columbus, Ohio 43215 www.moodynolan.com

24"
3 MAKE UP WATER DETAIL DRAWN BY:
N.J.B.
CHECKED BY:
B.C.S.
APPROVED BY:
B.C.S. 11279.00
P801 SCALE: NONE

SUMP PUMP PIPING DETAIL


5
P801
FILE INFO:

P801 SCALE: NONE


Plumbing Details
95% Construction Documents 11/9/2012