Professional Documents
Culture Documents
D E F G H X2 X3 X4 X5 X6 X7 X8 X9 X10 X11 X12 X13 X14 X15 X16 X17 X18 X19 X20 C1
Y10
UP UP
STAIRCASE-19
ER-3
ER-1
STAIRCASE-21 Exp. Joint w=120
STAIRCASE 20
STAFF LOUNGE
MR-G-1 DS-PS MR-G-3
ER-2
Existing Wall
Y9
SHOP FOR STAFF
F-57a MR-G-2
TENANT STOCK
TENANT STOCK
Y8
Slope = 1%
Conc. Gutter W=400
Conc. Gutter W=400
F-57a
F - 53
Existing Wall
Drencher line
Y7
Slope = 1%
Void 2FL
F - 52b F - 52a F - 51
F - 53
Finishing line
Void 2FL
ZONE-2 F-57b
F - 61
F - 56
ESC-6 F - 54
Slope = 1.0%
Slope = 1.0%
VOID 1-3
Slope = 1.0%
1016
Slope = 1.0%
ER-4
STAIRCASE-23 MR-1-1a
ZONE-4
Drencher line
Drencher line
VOID ESC-5
Parapet wall Steel grid fence
t=220, h=1200 CENTER COURT
Drencher line
Y4
ZONE-3
Steel grid fence
Drencher line
Drencher line
Steel handrail
Ø42, h=1100
ANTE -ROOM 1-1
CAR PARKING
F- 63
Drencher line
Drencher line
Parapet wall
ZONE-1 Exp. Joint
Floor: w=120
Y3
Slope
F - 72
t=220, h=1200 Steel handrail Wall: w=170
Ø42, h=1100 F - 64
MR-1-1b
F - 71
F - 66
Existing Wall
F - 67 F - 68 F - 70
Bollard @650
EV - HALL
Y2
EV-15
EV-12 EV-11
CAR PARKING EV15-16 HALL
Bollard @650
EV-16
ER-7
STAIRCASE-16
Bollard @650
DS.PS
STAIRCASE 17 ER-6 DS
STAIRCASE 17 STAIRCASE - 15 DS PS STAIRCASE 14
STAIRCASE-18 DSØ200
Parapet wall UP UP UP
t=220, h=900 ER-5
Y1
VOID
Steel grid fence
DSØ200 DSØ200 DSØ200 DSØ200 DSØ200 DSØ200
Exp. Joint, DSØ200
Canopy - 7A Canopy - 6B DSØ200 Canopy - 6A
Wall : w=250
Y1
Steel grid fence
CAR PARKING
Y0
Slope = 1.0%
STAIRCASE-24
Upright and Pendent sprinkler (K = 5.6 & K = 11.2, Temp. rate = 68°C) DN40 DN40
DN65 DN50 DN50 DN40 DN40
Upright and Pendent sprinkler for tenant (K = 5.6 & K = 11.2, Temp. rate = 68°C)
Pendent sprinkler for tenant is "C" work
Pendent sprinkler (K = 5.6, Temp. rate = 68°C) DN50 DN50 DN40 DN40 DN40
TYPICAL INSTALLATION UPRIGHT & PENDENT SPRINKLER HEAD ( TENANT AREA ) NOTE 1.Coverage area per sprinkler is 12m2
TYPICAL INSTALLATION ONLY UPRIGHT SPRINKLER HEAD ( BACK YARD MALL AREA ) TYPICAL INSTALLATION UPRIGHT & PENDENT SPRINKLER HEAD (CEILING AREA )
TYPICAL INSTALLATION PENDENT SPRINKLER HEAD 2.Maximum distance between sprinkler shall be 4m
ADDITION SPRINKLER HEAD UNDER DUCTING PIPE WIDTH >=750MM
3.Minimum distance between sprinkler shall be 1.5m