Example
The weather is terrible and the ship is rolling.
The boiler level control is hunting so you would like to look at the level transmitter “Damping” settings and possibly
increase a little.
Remember:
Put the boiler level control into manual before connecting the SFC to the transmitter.
OR if there are 2 level transmitters fitted (usually one transmitter doing control/indication and the other doing
alarms/trips) – Force the other transmitter to do both functions, so that you can safely connect the SFC to the “out –
of – service” transmitter.
For this example the boiler level transmitter has a Tag number LT-86 and is a SMART type Yamatake DSTJ 3000
DP transmitter, Model JTD 920A.
The parameters used have been chosen to facilitate the simulation, and are not specific to any ship.
Connect the SFC to the transmitter – remember it is connected in parallel with the instrument, so you connect to
where the 2 wires are connected to the transmitter (red lead goes to +ve terminal).
Also remember to make a note of the original settings, so if required you can put everything back to as was.
(If you have a SFC with a printer – you can print the original settings).
For this exercise - only the buttons on the SFC that you require to use are active.
Y AMATAKE
On/Off s witch is
loca te d on le ft DE READ
ha nd s ide of S FC
A B C D
ID CONF DAMP UNITS
ON OFF
E F G H
LRV URV SET
0% 100% NEXT
FEED PRINT
After connecting to M
7
N
8
O
9
P
the transmitter - A DE
Switch On by clicking Q R S T
4 5 6
NON-VOL
CLR ENTER
ALPHA SHIFT (YES)
(NO)
Previous Slide
S -S FC
1
Y AMATAKE Ke yboa rd
LOOP IN MANUAL ?
For a brief des cription of the keyboard pre s s this key.
DE READ
A B C D
ID CONF DAMP UNITS
E F G H
LRV URV SET
0% 100% NEXT
Q R S T
4 5 6
F/S DIR
U V W X
STAT 1 2 3
URL A CT PR SCR P AD TIME
Y Z +
SPAN 0 _
NON-VOL
CLR ENTER
ALPHA SHIFT (YES)
Pre s s ENTER
(NO)
S -S FC
E F G H
LRV URV SET
0% 100% NEXT
FEED PRINT
M N O P
7 8 9
A DE
Q R S T
4 5 6
F/S DIR
U V W X
STAT 1 2 3
URL A CT PR SCR P AD TIME
Y Z +
SPAN 0 _
NON-VOL
CLR ENTER
ALPHA SHIFT (YES)
(NO)
S -S FC
2
Y AMATAKE
TAG No.
WORKING …
DE READ
A B C D
ID CONF DAMP UNITS
E F G H
LRV URV SET
0% 100% NEXT
FEED PRINT
M N O P
7 8 9
A DE
Q R S T
4 5 6
F/S DIR
U V W X
STAT 1 2 3
URL A CT PR SCR P AD TIME
Y Z +
SPAN 0 _
NON-VOL
CLR ENTER
ALPHA SHIFT (YES)
(NO)
S -S FC
Y AMATAKE
DSTJ TAG No. The dis pla y is s howing tha t the instrument is a
LIN DP LT-86 DS TJ - Differe ntia l Pre s s ure Tra nsmitter.
Ta g No. LT-86 with it’s output mode s et to
DE READ Line a r.
A B C D
ID CONF DAMP UNITS
E F G H
LRV URV SET
0% 100% NEXT
FEED PRINT
M N O P
7 8 9
A DE
Q R S T
4 5 6
F/S DIR
U V W X
CLR (NO) ke y.
STAT 1 2 3 This cle a rs the dis pla y window a nd pla ce s the S -SFC
into “Input-Wa iting Mode ”
URL A CT PR SCR P AD TIME
Y Z +
SPAN 0 _
NON-VOL
CLR ENTER
ALPHA SHIFT
(NO) (YES) Pre s s the CLR key
S -S FC
3
Y AMATAKE
DSTJ LT-86
READY …
DE READ
A B C D
ID CONF DAMP UNITS Pre s s the DAMP key
This will dis pla y the curre nt da mping in s e conds.
E F G H
LRV URV SET
0% 100% NEXT
FEED PRINT
M N O P
7 8 9
A DE
Q R S T
4 5 6
F/S DIR
U V W X
STAT 1 2 3
URL A CT PR SCR P AD TIME
Y Z +
SPAN 0 _
NON-VOL
CLR ENTER
ALPHA SHIFT (YES)
(NO)
S -S FC
Y AMATAKE
DAMP LT-86
0.48 s
DE READ
A B C D
ID CONF DAMP UNITS The s cre e n is dis pla ying the curre nt damping time of
0.48 s e conds .
E F G H We want to incre a s e the damping time so pre s s the
LRV
0%
URV
100%
SET
NEXT
NEXT key.
DE CONF INPUT RES ET
I J K L
MENU OUT- COR- (If a lowe r damping time was re quire d the n pre ss PREV ke y)
ITEM PUT RECT PREV
FEED PRINT
M N O P
7 8 9
A DE
Q R S T
4 5 6
F/S DIR
U V W X
STAT 1 2 3
URL A CT PR SCR P AD TIME
Y Z +
SPAN 0 _
NON-VOL
CLR ENTER
ALPHA SHIFT (YES)
(NO)
S -S FC
4
Y AMATAKE
DAMP LT-86
WORKING …
DE READ
A B C D
ID CONF DAMP UNITS
E F G H
LRV URV SET
0% 100% NEXT
FEED PRINT
M N O P
7 8 9
A DE
Q R S T
4 5 6
F/S DIR
U V W X
STAT 1 2 3
URL A CT PR SCR P AD TIME
Y Z +
SPAN 0 _
NON-VOL
CLR ENTER
ALPHA SHIFT (YES)
(NO)
S -S FC
Y AMATAKE
DAMP LT-86
1.0 s
DE READ
A B C D
ID CONF DAMP UNITS The s cre e n is dis pla ying the next availa ble da mping
time that ca n be us e d of 1.0 s econd.
E F G H We want to incre a s e the damping time so pre s s the
LRV
0%
URV
100%
SET
NEXT
NEXT key.
DE CONF INPUT RES ET
I J K L
MENU OUT- COR- (If a lowe r damping time was re quire d the n pre ss PREV ke y)
ITEM PUT RECT PREV
FEED PRINT
M N O P
7 8 9
A DE
Q R S T
4 5 6
F/S DIR
U V W X
STAT 1 2 3
URL A CT PR SCR P AD TIME
Y Z +
SPAN 0 _
NON-VOL
CLR ENTER
ALPHA SHIFT (YES)
(NO)
S -S FC
5
Y AMATAKE
DAMP LT-86
WORKING …
DE READ
A B C D
ID CONF DAMP UNITS
E F G H
LRV URV SET
0% 100% NEXT
FEED PRINT
M N O P
7 8 9
A DE
Q R S T
4 5 6
F/S DIR
U V W X
STAT 1 2 3
URL A CT PR SCR P AD TIME
Y Z +
SPAN 0 _
NON-VOL
CLR ENTER
ALPHA SHIFT (YES)
(NO)
S -S FC
Y AMATAKE The s cre en is dis pla ying the ne xt availa ble da mping
time that ca n be us e d of 2.0 s e conds .
DAMP LT-86
This is the time we re quire.
2.0 s
DE READ
A B C D
ID CONF DAMP UNITS
The 2 s e conds ha s be e n s ele cte d in the SFC.
The ne xt ste ps sta rt the proces s of cha nging the
E F G H da mping time in the tra nsmitter.
LRV URV SET
0% 100% NEXT
Pres s the CLR (NO) ke y to s top a nd ma ke no
DE CONF INPUT RES ET cha nges .
I J K L
MENU OUT- COR-
ITEM PUT RECT PREV
FEED PRINT
M N O P
7 8 9
A DE
Q R S T
4 5 6
F/S DIR
U V W X
STAT 1 2 3
URL A CT PR SCR P AD TIME
Y Z +
SPAN 0 _
NON-VOL
To continue a nd e nter the 2.0 s e conds into the
ENTER
tra ns mitte r:
CLR
ALPHA SHIFT
(NO) (YES) Pre s s the SHIFT ke y followe d by the ENTER key
S -S FC
6
Y AMATAKE
SHIFT -
Pre s s ing the SHIFT key followed by the ENTER
ke y, s e le cts NON-VOL.
DE READ NON-VOL - This write s da ta e ntere d by the S FC
ID
A
CONF
B
DAMP
C
UNITS
D into the non volatile me mory (EEPROM) of the
s ma rt fie ld ins trume nt.
E F G H
LRV URV SET
0% 100% NEXT
Q R S T
4 5 6
F/S DIR
U V W X
STAT 1 2 3
URL A CT PR SCR P AD TIME
Y Z +
SPAN 0 _
Y AMATAKE
DSTJ LT-86
WORKING …
DE READ
A B C D
ID CONF DAMP UNITS
E F G H
LRV URV SET
0% 100% NEXT
FEED PRINT
M N O P
7 8 9
A DE
Q R S T
4 5 6
F/S DIR
U V W X
STAT 1 2 3
URL A CT PR SCR P AD TIME
Y Z +
SPAN 0 _
NON-VOL
CLR ENTER
ALPHA SHIFT (YES)
(NO)
S -S FC
7
Y AMATAKE
DSTJ LT-86
DATA NON-VOLATILE
DE READ
A B C D
ID CONF DAMP UNITS
E F G H
LRV URV SET
0% 100% NEXT
FEED PRINT
M N O P
7 8 9
A DE
Q R S T
4 5 6
F/S DIR
U V W X
STAT 1 2 3
URL A CT PR SCR P AD TIME
Y Z +
SPAN 0 _
NON-VOL
CLR ENTER
ALPHA SHIFT (YES)
(NO)
S -S FC
Y AMATAKE
Back to Start
DSTJ LT-86 Press the Back to Start Key to Start Section 2 again.
READY …
DE READ
A B C D
ID CONF DAMP UNITS
E F G H
LRV URV SET
0% 100% NEXT
DE CONF
I
INPUT
J
RES ET
K L
Tha t is the da mping cha nge d in
the Tra ns mitte r to 2.0 s e conds .
MENU OUT- COR-
ITEM PUT RECT PREV
FEED PRINT
M N O P
7 8 9
A DE
Q R S T
4 5 6
F/S DIR
U V W X
STAT 1 2 3
URL A CT PR SCR P AD TIME
Y Z +
SPAN 0 _
NON-VOL
CLR ENTER
ALPHA SHIFT
(NO) (YES) Ba ck to the Me nu
S -S FC