You are on page 1of 23

Tem

mp R-tron Operation
O Manual
M ver 4.0U
4

OOPERATTION MANUAL
M L
Veersion 4.0U
100 May 20016

E-mail : salees@waterflam
me.co.th Page 1 10
1 May 20166
Temp R-tron Operation Manual ver 4.0U

Product Warranty & Limitation of Liability


The product warranty is in accordance with the following regulations:
 The manufacturer should take responsibility for below specific elements:
1. In domestic use (as calculated from the date of invoice)
- Invoice within one month should accept replacement and repair.
- Invoice within twelve months should accept repair.
2. Goods exported overseas (excluding Thailand) and invoice within fifteen months, the local seller is responsible for repair.
 All the distributors, agency or production place of Temp Control in whole Thailand can provide after-sales service for Temp Control product, their
conditions of service as follows:
2. We provide inspection service on the local selling place (including troubleshooting).
3. All services comply with the related after-sale service terms and conditions stated on the agency agreement between Siam Water Flame and
distributors.
4. Buyers can pay to any Temp Control agent if need any after-sales services (whether or not the warranty).
 The product’s warranty period is one year from the date of invoice. The product shall be free of defects in materials or workmanship and will conform to
technical specification.
 Siam Water Flame will not be responsible for any labor costs or expenses associated with repair and replacement of defective.
 In the case of the following causes of failure, even in the warranty period is also a paid repair:
3. Incorrect operation (depending on the use of manual), or misuse, alteration, neglect, improper, abuse, accident, or unauthorized maintenance or
repair.
4. The problems caused by using the control beyond its standard specifications requirement.
5. Damage caused by drop down or improper handling.
6. Controller components aged or failure caused by improper environment.
7. Due to an earthquake, fire, wind and water disasters, lightning strikes, abnormal voltage, electrical power surge, interruption of electricity,
electrical power surge or other natural disasters and disasters, accompanied by the damage caused.
8. The damage during transport (Note: The mode of transport designated by the customer, the company's help on behalf of the procedures for
handling the transfer of goods).
9. When the manufacture’s brand, trademark, serial number, nameplate and other damage or cannot be recognized.
10. If the buyer has not paid full money according to purchase agreement.
11. The installation, wiring, operation, maintenance or other use of objective reality cannot be described to the company's service office.
 Concerning replacement and repair services, goods shall be returned Temp Control to company, after confirmed the attribution of responsibility then
they are allowed to be returned or repaired.

The user should be aware and alert that something may fail beyond our control exists. Since farm condition and livestock environment may cause
controller damage, the user should provide adequate back up and alarm system. These are to operate critical system even in case of Temp Controller system failure.
Neglecting to provide such a backup will be regarded as the user’s willingness to accept the risk of loss, injury and financial damage. In no event will Siam Water
Flame be liable to user or any third party for any direct, indirect, special, consequential or incidental damages, including but not limited to any damage or injury to
business earnings, lost profits or goodwill, personal injury, costs of delay, any failure of delivery, costs of lost or damaged data or documentation, lost or damaged
products or goods, lost sales, lost orders, lost income. Except of the above express warranty, Siam Water Flame makes no other warranties, express or implied,
relating to the products. Siam Water Flame disclaims and excludes the implied warranties of merchantability and fitness for a particular purpose. No person is
authorized to make any other warranty or representation concerning the performance of the products other than as provided by Siam Water Flame.

E-mail : sales@waterflame.co.th Page 2 10 May 2016


Temp R-tron Operation Manual ver 4.0U

Technician Data
Circuit system Electricity pressure 220 (+/-10%) VAC
Frequency 5060 Hz
Electric power 18 VA
Fireproofing rate for relay 250VAC, 3A
Temperature for using -20 – 60 C
Measurement range temperature -10.0 – 70.0 C
Accurate value 0.1 C
Deviation value +/-1 %
Measurement range Humidity 0.0 – 99.9 %RH
Accurate value 0.1 %
Deviation value +/-5 %

INSTALLATION
1. Connect the Temp R-tron to the wall in a dry place approximately 1 meter away from the electrical cabinet.
2. Connect a 220VAC cable to the L, N connector. This is the unit power input.
3. The Temp R-tron has not breaker (fuse) inside for this relay output and it must be installed externally.
4. Connect a protective conductor (P.E.) to the G connector. The resistance of cable must be not over than 5
ohms. We suggest that, use an independent ground cable which is not shared with the one for electricity box.

E-mail : sales@waterflame.co.th Page 3 10 May 2016


Temp R-tron Operation Manual ver 4.0U

Analog Input Connections


1. Temperature sensors
T1 is used for indoor temperature sensor. Use a two wire cable.
Connect Brown wire to T1 and White/Black wire to the 0 V.
T2 is used for indoor temperature sensor. Use a two wire cable.
Connect Brown wire to T2 and White/Black wire to the 0 V.
T3 is used for outdoor temperature sensor. Use a two wire cable.
Connect Brown wire to T3 and White/Black wire to the 0 V.
T4 is used for indoor temperature sensor. Use a two wire cable.
Connect Brown wire to T4 and White/Black wire to the 0 V.
2. Humidity sensor
HUM is used for indoor humidity sensor. Use a three wire cable.
Connect Brown wire to 12V, White wire to HUM and Green wire to the 0 V.

Analog out Connections


A-OUT is used for the variable speed fan (inverter).

E-mail : sales@waterflame.co.th Page 4 10 May 2016


Temp R-tron Operation Manual ver 4.0U

Digital Input Connection


Input 1 is used for the water meter dry contact signal. Use a two wire cable.
Connect one wire to X1 terminal and the seconds wire to CM1 terminal.
The signal from the water meter should be wired in such a way that when the water meter sends a pulse
( 1 pulse per 10 Liters), the dry contact will be in a normally closed state (shorted).

E-mail : sales@waterflame.co.th Page 5 10 May 2016


Temp R-tron Operation Manual ver 4.0U

Relay Connections
Connect the relay outputs to the various systems. All outputs are dry contacts, maximum 4 A/220V
Relay list

Terminal Output
FAN 1, CMF 1 Fan group 1
FAN 2, CMF 2 Fan group 2
FAN 3, CMF 3 Fan group 3
FAN 4, CMF 4 Fan group 4
FAN 5, CMF 5 Fan group 5
FAN 6, CMF 6 Fan group 6
FAN 7, CMF 7 Fan group 7
FAN 8, CMF 8 Fan group 8
FAN 9, CMF 9 Fan group 9
FAN 10, CMF 10 Fan group 10
FAN 11, CMF 11 Fan group 11
FAN 12, CMF 12 Fan group 12
CP 1, CMP 1 Cooling system
CP 2, CMP 2 Cooling pump 2/ Heater / Feeding
LIGHT, CMLT Lighting system
S-FAN , CMSF Side Fan/ Heater
NO / COM / NC Alarm

Connect a 220VAC cable to the 220V IN connector near the ALARM connector. This is the unit power input.
Note that there is no breaker (fuse) inside the Temp R-tron for this relay output, and it must be installed
externally.

E-mail : sales@waterflame.co.th Page 6 10 May 2016


Temp R-tron Operation Manual ver 4.0U

E-mail : sales@waterflame.co.th Page 7 10 May 2016


Temp R-tron Operation Manual ver 4.0U

OPERATION
The Temp R-tron will display the average temperature of the connected temperature sensors. It is
possible to display each sensor separately.
The Temp R-tron will display the humidity of the connected humidity sensors. It is possible to display
each sensor separately. And display the operation of the relay and the fan speed.
Turn on power
1. Each time power is connected to the unit “4.0U” will appear on the display. This number is version number,
and is unique for this program version.
2. The left display indicates the indoor temperature. The center display shows the outdoor temperature. And the
right display shows the indoor humidity.
CHANGE OF DISPLAY
Push on button. For select the display.
 This is a reading of the current fan speed.
 This is a reading of the current indoor temperature 1.
 This is a reading of the current indoor temperature 2.
 This is a reading of the current outdoor temperature 3.
 This is a reading of the current indoor temperature 4.
 This is a reading of the current indoor humidity.
 Notification error (If no errors. Do not show this message.)
  Error from temperature sensor 1 alarm
  Error from temperature sensor 2 alarm
  Error from temperature sensor 3 alarm
  Error from temperature sensor 4 alarm
  Error of greater than or equal to the temperature 1 and 2 specified.
  Error of greater than or equal to the temperature specified.
  Error of less than or equal to the temperature specified.
  Error of greater than or equal to the humidity specified.
  Error of greater than or equal to the time heat stress index specified.
  Error of greater than or equal to the amount heat stress index specified.
  Error of greater than or equal to the CO2 specified.
Push On button. For select the display.
 Transfer current indoor temperature and outdoor temperature from Centigrade to Fahrenheit.

E-mail : sales@waterflame.co.th Page 8 10 May 2016


Temp R-tron Operation Manual ver 4.0U
CHANGE OF SET POINT
It is possible to change each set point.
1. Press “Select” Select button. For select the main functions.
2. Press “ ” or “ ” button to select the sub functions.
3 Press “Program” button. The lamp program will turn on.
4. Press “ ” or “ ” button. Enter the desired value. The new data will appear on the display.
5. Check the display to see if the desired value is correct. If correct, press the “Program” button to exit.
The lamp program will off. The new desired value has been stored into the unit’s memory.
SET POINTS
Functions
1. Temperature for Fan ON/OFF
1.1  Set ON
Enter here the temperature at fan1 turn on.
1.2  Set OFF
Enter here the temperature at fan1 turn off.
1.3  Set ON
Enter here the temperature at fan2 turn on.
1.4  Set OFF
Enter here the temperature at fan2 turn off.
1.5  Set ON
Enter here the temperature at fan3 turn on.
1.6  Set OFF
Enter here the temperature at fan3 turn off.
1.7  Set ON
Enter here the temperature at fan4 turn on.
1.8  Set OFF
Enter here the temperature at fan4 turn off.
1.9  Set ON
Enter here the temperature at fan5 turn on.
1.10  Set OFF
Enter here the temperature at fan5 turn off.
1.11  Set ON
Enter here the temperature at fan6 turn on.
1.12  Set OFF
Enter here the temperature at fan6 turn off.
1.13  Set ON
Enter here the temperature at fan7 turn on.

E-mail : sales@waterflame.co.th Page 9 10 May 2016


Temp R-tron Operation Manual ver 4.0U
1.14  Set OFF
Enter here the temperature at fan7 turn off.
1.15  Set ON
Enter here the temperature at fan8 turn on.
1.16  Set OFF
Enter here the temperature at fan8 turn off.
1.17  Set ON
Enter here the temperature at fan9 turn on.
1.18  Set OFF
Enter here the temperature at fan9 turn off.
1.19  Set ON
Enter here the temperature at fan10 turn on.
1.20  Set OFF
Enter here the temperature at fan10 turn off.
1.21  Set ON
Enter here the temperature at fan11 turn on.
1.22  Set OFF
Enter here the temperature at fan11 turn off.
1.23  Set ON
Enter here the temperature at fan12 turn on.
1.24  Set OFF
Enter here the temperature at fan12 turn off.
1.25  Set ON
Enter here the time period in minutes and seconds (x10) that the fan1 will run once the house temperature has
below the fan1 temperature (Function “”). The fan1 will run in an on-off cycle.
1.26  Set OFF
Enter here the time period in minutes and seconds (x10) that the fan1 will be off during the fan1 cycle.
Note: Enter “0.0” to disable this function.
1.27  Set ON
Enter here the time period in minutes and seconds (x10) that the fan2 will run once the house temperature below
the fan2 temperature (Function “”). The fan2 will run in an on-off cycle.
1.28  Set OFF
Enter here the time period in minutes and seconds (x10) that the fan2 will be off during the fan2 cycle.
Note: Enter “0.0” to disable this function.
1.29  Set ON
Enter here the time period in minutes and seconds (x10) that the fan3 will run once the house temperature below
the fan3 temperature (Function “”). The fan3 will run in an on-off cycle.
1.30  Set OFF
Enter here the time period in minutes and seconds (x10) that the fan3 will be off during the fan3 cycle.
Note: Enter “0.0” to disable this function.

E-mail : sales@waterflame.co.th Page 10 10 May 2016


Temp R-tron Operation Manual ver 4.0U
1.31  Set ON
Enter here the time period in minutes and seconds (x10) that the fan4 will run once the house temperature below
the fan4 temperature (Function “”). The fan4 will run in an on-off cycle.
1.32  Set OFF
Enter here the time period in minutes and seconds (x10) that the fan4 will be off during the fan4 cycle.
Note: Enter “0.0” to disable this function.
1.33  Set ON
Enter here the time period in minutes and seconds (x10) that the fan5 will run once the house temperature below
the fan5 temperature (Function “”). The fan5 will run in an on-off cycle.
1.34  Set OFF
Enter here the time period in minutes and seconds (x10) that the fan5 will be off during the fan5 cycle.
Note: Enter “0.0” to disable this function.
1.35  Set ON
Enter here the time period in minutes and seconds (x10) that the fan6 will run once the house temperature below
the fan6 temperature (Function “”). The fan6 will run in an on-off cycle.
1.36  Set OFF
Enter here the time period in minutes and seconds (x10) that the fan6 will be off during the fan6 cycle.
Note: Enter “0.0” to disable this function.
1.37  Set ON
Enter here the time period in minutes and seconds (x10) that the fan7 will run once the house temperature below
the fan7 temperature (Function “”). The fan7 will run in an on-off cycle.
1.38  Set OFF
Enter here the time period in minutes and seconds (x10) that the fan7 will be off during the fan7 cycle.
Note: Enter “0.0” to disable this function.
1.39  Set ON
Enter here the time period in minutes and seconds (x10) that the fan8 will run once the house temperature below
the fan8 temperature (Function “”). The fan8 will run in an on-off cycle.
1.40  Set OFF
Enter here the time period in minutes and seconds (x10) that the fan8 will be off during the fan8 cycle.
Note: Enter “0.0” to disable this function.
1.41  Set ON
Enter here the time period in minutes and seconds (x10) that the fan1 will run once the house temperature below
the fan9 temperature (Function “”). The fan9 will run in an on-off cycle.
1.42  Set OFF
Enter here the time period in minutes and seconds (x10) that the fan9 will be off during the fan9 cycle.
Note: Enter “0.0” to disable this function.
1.43  Set ON
Enter here the time period in minutes and seconds (x10) that the fan10 will run once the house temperature below
the fan10 temperature (Function “”). The fan10 will run in an on-off cycle.

E-mail : sales@waterflame.co.th Page 11 10 May 2016


Temp R-tron Operation Manual ver 4.0U
1.44  Set OFF
Enter here the time period in minutes and seconds (x10) that the fan10 will be off during the fan10 cycle.
Note: Enter “0.0” to disable this function.
1.45  Set ON
Enter here the time period in minutes and seconds (x10) that the fan11 will run once the house temperature below
the fan11 temperature (Function “”). The fan11 will run in an on-off cycle.
1.46  Set OFF
Enter here the time period in minutes and seconds (x10) that the fan11 will be off during the fan11 cycle.
Note: Enter “0.0” to disable this function.
1.47  Set ON
Enter here the time period in minutes and seconds (x10) that the fan12 will run once the house temperature below
the fan12 temperature (Function “”). The fan12 will run in an on-off cycle.
1.48  Set OFF
Enter here the time period in minutes and seconds (x10) that the fan12 will be off during the fan12 cycle.
Note: Enter “0.0” to disable this function.
Example:
 Set ON = 21.0C
 Set OFF = 20.0C
  Set ON = 5.0
 Set OFF = 10.0
As long as the indoor temperature is blow 20.0C . The fan1 will be turn on 5 minutes and turn off 10
minutes. When the temperature reaches 21.0C. The fan1 will be turn on continued.
1.49 
Enter here the minimum temperature setting to control the fan speed minimum.
1.50 
Enter here the medium temperature setting to control the fan speed minimum.
1.51 
Enter here the maximum temperature setting to control the fan speed maximum.
1.52 
Enter here the minimum speed set in percentage that the variable speed fan will run.
1.53 
Enter here the medium speed set in percentage that the variable speed fan will run.

E-mail : sales@waterflame.co.th Page 12 10 May 2016


Temp R-tron Operation Manual ver 4.0U

1.54 
Enter here the maximum speed set in percentage that the variable speed fan will run.
Example:
 = 10 %
 = 50 %
 = 100 %
 = 21.0C
 = 25.0C
 = 30.0C
As long as the indoor temperature is blow 23.0C the variable speed fan will be running at 30%. When
the temperature reaches 23.0C the variable speed fan will start to increase in speed. By the time the house
temperature has reaches 30.0C variable speed fan will be running at 100%.
2. Temperature for Cooling / Heater ON/OFF
2.1  Set ON
Enter here the temperature at heater turn on.
2.2  Set OFF
Enter here the temperature at heater turn off.
Example:
 Set ON = 29.0C
 Set OFF = 30.0C
When the temperature is lower than or equal to 29.0C, heater will turn on. And temperature greater than
or equal to 30.0C, heater will turn off.
Cooling Pump
When the indoor temperature is equal or over requested temperature for cooling system, a line (see line 1~4 at
table page14) can be active only when all the following conditions are fulfilled: time and temperature.
Cooling Table
Period From Time To Time Outdoor On (mm.s) Off (mm.s)
(_) (hh.m) (“_”) Temperature (“_”) (“_”)
(“_”) (“_”)
1 0:00 24:00 27.0 2:00 10:00
2 0:00 24:00 29.0 2:00 5:00
3 0:00 24.00 30.0 2:00 2:00
4 12:30 16:00 32.5 2:00 0:00

Example: When the outdoor temperature is below 27◦C, under the assumption that the range of both time, the
cooling system will not operate when the outdoor temperature reaches or rises over 27◦C. The cooling system
operates according to the first line when the temperature rises over 29.0◦C, the cooling system will operate
according to line 2 and so on.

E-mail : sales@waterflame.co.th Page 13 10 May 2016


Temp R-tron Operation Manual ver 4.0U

Cooling Pump
2.3  Set ON
Enter here the temperature at cooling pump1 turn on.
2.4  Set OFF
Enter here the temperature at cooling pump1 turn off.
2.5  Set ON
Enter here the temperature at cooling pump2 turn on.
2.6  Set OFF
Enter here the temperature at cooling pump2 turn off.
2.7  From Time Period 1
Enter here the cooling system on time for cooling table period 1. Use real time mode.
2.8  To Time Period 1
Enter here the cooling system off time for cooling table period 1. Use real time mode.
2.9  Outdoor Temperature Period 1
Enter here an outdoor temperature for cooling table period 1.
2.10  Time On Pump Period 1
Enter here the time period in minutes and seconds that the cooling system will run in an on-off cycle for cooling
table period 1.
2.11  Time Off Pump Period 1
Enter here the time period in minutes and seconds that the cooling system will be off during the cooling system
cycle for cooling table period 1.
2.12  From Time Period 2
Enter here the cooling system on time for cooling table period 2. Use a real time mode.
2.13  To Time Period 2
Enter here the cooling system off time for cooling table period 2. Use real time mode.
2.14  Outdoor Temperature Period 2
Enter here an outdoor temperature for cooling table period 2.
2.15  Time On Pump Period 2
Enter here the time period in minutes and seconds that the cooling system will run in an on-off cycle for cooling
table period 2.
2.16  Time Off Pump Period 2
Enter here the time period in minutes and seconds that the cooling system will be off during the cooling system
cycle for cooling table period 2.

E-mail : sales@waterflame.co.th Page 14 10 May 2016


Temp R-tron Operation Manual ver 4.0U

2.17  From Time Period 3


Enter here the cooling system on time for cooling table period 3. Use a real time mode.
2.18  To Time Period 3
Enter here the cooling system off time for cooling table period 3. Use real time mode.
2.19  Outdoor Temperature Period 3
Enter here an outdoor temperature for cooling table period 3.
2.20  Time On Pump Period 3
Enter here the time period in minutes and seconds that the cooling system will run in an on-off cycle for cooling
table period 3.
2.21  Time Off Pump Period 3
Enter here the time period in minutes and seconds that the cooling system will be off during the cooling system
cycle for cooling table period 3.
2.22  From Time Period 4
Enter here the cooling system on time for cooling table period 4. Use a real time mode.
2.23  To Time Period 4
Enter here the cooling system off time for cooling table period 4. Use real time mode.
2.24  Outdoor Temperature Period 4
Enter here an outdoor temperature for cooling table period 4.
2.25  Time On Pump Period 4
Enter here the time period in minutes and seconds that the cooling system will run in an on-off cycle for cooling
table period 4.
2.26  Time Off Pump Period 4
Enter here the time period in minutes and seconds that the cooling system will be off during the cooling system
cycle for cooling table period 4.
2.27  From Time Period 5
Enter here the cooling system on time for cooling table period 5. Use a real time mode.
2.28  To Time Period 5
Enter here the cooling system off time for cooling table period 5. Use real time mode.
2.29  Outdoor Temperature Period 5
Enter here an outdoor temperature for cooling table period 5.

E-mail : sales@waterflame.co.th Page 15 10 May 2016


Temp R-tron Operation Manual ver 4.0U
2.30  Time On Pump Period 5
Enter here the time period in minutes and seconds that the cooling system will run in an on-off cycle for period 5.
2.31  Time Off Pump Period 5
Enter here the time period in minutes and seconds that the cooling system will be off during the cooling system
cycle for cooling table period 5.
3. Humidity for Cooling OFF
3.1 
Enter here the humidity at pump turned off. The humidity at the turn on pump is calculated from the value of
 minus the value of . As set = 80.0% and =2.0%, pump will turn off at 80.0% and will turn on
again when humidity is less than or equal to 78.0%. (Factory - set value  = 2.0%. Users can edit it.)
3.2 
Enter here the time period in minutes and seconds (x10) that the cooling pump system will run once the indoor
temperature has reached the required temperature for cooling pump and indoor humidity rises above required
humidity. The cooling pump will run in an on-off cycle.
3.3 
Enter here the time period in minute and seconds (x10) that the cooling pump will be off during high humidity
cycle.
Note: Enter “0.0” to disable this function
3.4 
Enter here number X to turn on fan X. The humidity at the turn on fan from the value of .
Note: Enter “0” to disable this function
3.5 
Enter here the time period in minutes and seconds (x10) that the fan will run once the humidity reaches the 
value. The fan will run in an on-off cycle.
3.6 
Enter here the time period in minutes and seconds (x10) that the fan will be off during the fan cycle.
Note: Enter “0.0” to disable this function.
3.7 
Enter here the speed set in percentage that the variable speed fan will run. The humidity to turn on fan from the
value of.
Note: Enter “0” to disable this function
3.8 
Enter here the time period in minutes and seconds (x10) that the fan will run once the humidity reaches the 
value. The fan will run in an on-off cycle.
3.9 
Enter here the time period in minutes and seconds (x10) that the fan will be off during the fan cycle.
Note: Enter “0.0” to disable this function.

E-mail : sales@waterflame.co.th Page 16 10 May 2016


Temp R-tron Operation Manual ver 4.0U

4.Time Update
4.1 
This is a reading of the hour setting. It is possible here to adjust the hour reading.
4.2 
This is a reading of the minute setting. It is possible here to adjust the minute reading.
4.3 
This is a reading of the day setting. It is possible here to adjust the day reading.
4.4 
This is a reading of the date setting. It is possible here to adjust the date reading.
4.5 
This is a reading of the month setting. It is possible here to adjust the month reading.
4.7 
This is a reading of the year setting. It is possible here to adjust the year reading.
5. Set Times for Light ON/OFF and Feed ON/OFF
Light On /Off
5.1 Set ON
Enter here the time period 1 at light turn on.
5.2 Set OFF
Enter here the time period 1 at light turn off.
5.3 Set ON
Enter here the time period 2 at light turn on.
5.4 Set OFF
Enter here the time period 2 at light turn off.
5.5 Set ON
Enter here the time period 3 at light turn on.
5.6 Set OFF
Enter here the time period 3 at light turn off.
5.7 Set ON
Enter here the time period 4 at light turn on.
5.8 Set OFF
Enter here the time period 4 at light turn off.
5.9 Set ON
Enter here the time period 5 at light turn on.
5.10 Set OFF
Enter here the time period 5 at light turn off.

E-mail : sales@waterflame.co.th Page 17 10 May 2016


Temp R-tron Operation Manual ver 4.0U
Feed On/Off
For Feed On/Off control. It is possible to enable function before using. Please see parameter setup 8.13 
To enable select and Enter “ Program “ for confirm. For relay contact use terminal CP2 and CMP2
5.11 Set ON
Enter here the Feed time period 1 at CP2 turn on.
5.12 Set OFF
Enter here the Feed time period 1 at CP2 turn off.
5.13 Set ON
Enter here the Feed time period 2 at CP2 turn on.
5.14 Set OFF
Enter here the Feed time period 3 at CP2 turn off.
5.15 Set ON
Enter here the Feed time period 3 at CP2 turn on.
5.16 Set OFF
Enter here the Feed time period 3 at CP2 turn off.
5.15 Set ON
Enter here the Feed time period 4 at CP2 turn on.
5.16 Set OFF
Enter here the Feed time period 4 at CP2 turn off.
5.17 Set ON
Enter here the Feed time period 5 at CP2 turn on.
5.18 Set OFF
Enter here the Feed time period 5 at CP2 turn off.

6. Alarm
6.1 
Enter here the maximum temperature required notification. In case of the controller will activate the alarm relay
and high temperature alarm status will activate.
6.2 
Enter here the minimum temperature required notification. In case of the controller will activate the alarm relay
and low temperature alarm status will activate.
6.3 
Enter here the maximum humidity required notification. In case of the controller will activate the alarm relay and
high humidity alarm status will activate.
6.4   Indoor Temperature Sensor 1 Alarm
It is possible to enable temperature sensor 1 alarm
To disable an alarm enter the corresponding off.
To enable an alarm enter the corresponding on.
Note: If an alarm is disabled then the alarm relay will not be activated when there is a problem.

E-mail : sales@waterflame.co.th Page 18 10 May 2016


Temp R-tron Operation Manual ver 4.0U
6.5   Indoor Temperature Sensor 2 Alarm
It is possible to enable temperature sensor 2 alarm
To disable an alarm enter the corresponding off.
To enable an alarm enter the corresponding on.
Note: If an alarm is disabled then the alarm relay will not be activated when there is a problem.
6.6   Indoor Temperature Sensor 3 Alarm
It is possible to enable temperature sensor 3 alarm
To disable an alarm enter the corresponding off.
To enable an alarm enter the corresponding on.
Note: If an alarm is disabled then the alarm relay will not be activated when there is a problem.
6.7   Indoor Temperature Sensor 4 Alarm
It is possible to enable temperature sensor 4 alarm
To disable an alarm enter the corresponding off.
To enable an alarm enter the corresponding on.
Note: If an alarm is disabled then the alarm relay will not be activated when there is a problem.
6.8 
Enter here the different temperature required notification. In case of the controller will activate the alarm relay
and different temperature alarm status will activate.
6.9 
Enter here the number of the heat stress index. When the indoor temperature plus indoor humidity in the house is
above this value, the heat stress status will be activated.
6.10 
Enter here the number of amount time in the heat stress. When amount time in the heat stress is over this value,
the controller will activate the alarm relay and amount time heat stress alarm status will activate.
6.11 
Enter here the time in minutes of amount time in the heat stress.
6.12 
Enter here the time in minutes of time in the heat stress. When time period in the heat stress is above this value,
the controller will activate the alarm relay and the time heat stress alarm status will activate.
6.13  Set On
Enter here the time period in seconds that the alarm system will run. The alarm system will activate.

E-mail : sales@waterflame.co.th Page 19 10 May 2016


Temp R-tron Operation Manual ver 4.0U
6.14  Set Off
Enter here the time period in seconds that the alarm system will be off.
7. Max./Min. Values
7.1  Total Water Consumption
This is a reading of the total water consumption in the house.
7.2  Indoor High Temperature in today

This is a reading of Indoor high temperature in today. Press for time recording.
7.3  Low indoor Temperature in today

This is a reading of Indoor low temperature in today. Press for time recording.
7.4  High outdoor Temperature in today
This is a reading of Outdoor high temperature in today. Press for time recording.
7.5  Low outdoor Temperature in today
This is a reading of Outdoor low temperature in today. Press for time recording.
7.6  High Humidity in today
This is a reading of Indoor high humidity in today. Press for time recording.
7.7  Low Humidity in today
This is a reading of Indoor low humidity in today. Press for time recording.
7.8  Time Heat stress in today
This is a reading of total longest time period ( minute) when there is a heat stress index in today.

Press for time recording.


7.9  Heat stress in today
This is a reading of highest value of the heat stress index in today. Press for time recording.
7.10  Amount Heat stress in today
This is a reading of amount of events when there are the heat stress indexes in today.
Press for time recording.

E-mail : sales@waterflame.co.th Page 20 10 May 2016


Temp R-tron Operation Manual ver 4.0U
7.11  Water Consumption in today
This is a reading of water consumption in today.
7.12  High CO 2 in today
This is a reading of the high indoor CO2 in today. Press for time recording.
7.13 toThis is data recoding for yesterday.
7.14 toThis is data recoding for 2 Days ago.
8. Parameter Setup
8.1  (◦C) Indoor Temperature No. 1
This is a reading of the current indoor temperature 1. It is possible here to adjust the temperature reading.
8.2  (◦C) Indoor Temperature No. 2
This is a reading of the current indoor temperature 2. It is possible here to adjust the temperature reading.
8.3  (◦C) Outdoor Temperature
This is a reading of the current outdoor temperature. It is possible here to adjust the temperature reading.
8.4  (◦C) Indoor Temperature No. 3
This is a reading of the current indoor temperature 3. It is possible here to adjust the temperature reading.
8.5  (% RH) Indoor Humidity
This is a reading of the current indoor humidity. It is possible here to adjust the humidity reading.
8.6  House Number
It is possible to connect the unit to a PC computer with the help of the “TEMPVIEW” software package. It is
possible to manage up 99 units. Each controller needs a house number.
8.7  Formula Number
This is the formula number of the controller.
8.8  Indoor Temperature Sensor Control
It is possible to use partial or all indoor temperature sensors for control.
To use temperature sensor 1 enter the corresponding .
To use temperature sensor 2 enter the corresponding .
To use temperature sensor 4 enter the corresponding .
To use temperature sensor 1 and 2 enter the corresponding .
To use all temperature sensor enter the corresponding .

E-mail : sales@waterflame.co.th Page 21 10 May 2016


Temp R-tron Operation Manual ver 4.0U
8.9  Indoor Temperature Sensor Control Heater
It is possible to use indoor temperature sensor for control.
To use temperature sensor 1 enter the corresponding .
To use temperature sensor 2 enter the corresponding .
To use temperature sensor 4 enter the corresponding .
To use temperature sensor 1 and 2 enter the corresponding .
To use all temperature sensor enter the corresponding .
8.10  Indoor Humidity Sensor Control
It is possible to use indoor humidity sensor for control.
To use humidity sensor enter the corresponding .
To not use humidity sensor enter the corresponding .
8.11  Select Display Brooding Temperature
It is possible to select display brooding temperature for show. Press LED is light for select parameter.
Program

To show temperature control heater enter the corresponding . Press for confirm parameter.
Program

To show outdoor temperature enter the corresponding . Press for confirm parameter.
Program

To show CO2 enter the corresponding . Press Program for confirm parameter.
To show speed variable fan enter the corresponding . Press for confirm parameter.
Program

8.12  Select Use Relay Fan12


It is possible to use relay Fan12 for other functions. Press LED is light for select parameter.
Program

To use for Fan12 enter the corresponding . Press Program for confirm parameter.
To use for Feed enter the corresponding . Press Program for confirm parameter.
To use for heater enter the corresponding . Press Program for confirm parameter.
8.13  Select Use Relay CP2
It is possible to use relay CP2 for other functions. Press Program
LED is light for select parameter.
To use for Cooling Pump2 enter the corresponding . Press for confirm parameter.
Program

To use for heater enter the corresponding . Press Programfor confirm parameter.
To use for Feeding enter the corresponding . Press Program for confirm parameter.
8.14  Humidity Hysteresis
Enter here the number of percentage below the requested humidity for cooling system (function “”) that
cooling system will be turn on.

E-mail : sales@waterflame.co.th Page 22 10 May 2016


Temp R-tron Operation Manual ver 4.0U
8.15  Delay Turn on System
Enter here the time period in seconds that the controller will be delay turn on relay in case of power on.
8.16  Time Event Data Logger
Enter here the time interval in minutes (5, 15, 30, 60, 120 minute) that the data logger will get record.
8.17  Change Password
Enter here a change password.
8.18 
This is function for reset controller. To be used by technicians.
 1 = Load User Parameter
 2 = Clear Adjust Sensor
 3 = Clear Data Logger
 4 = Clear Max, Min Value
 5 = Load Factory Parameter
 8 = Save User Parameter
8.19 
This is function for test relay. To be used by technicians.
8.20 
This is function for test variable speed fan. To be used by technicians.
8.21 
This is function for test 7 segments. To be used by technicians.
8.22 
This is function for test digital input. To be used by technicians.

***************************

E-mail : sales@waterflame.co.th Page 23 10 May 2016

You might also like