Professional Documents
Culture Documents
023 N7491en
023 N7491en
The LMU34... and this Data Sheet are intended for use by OEMs which integrate
the BMUs in their products.
Use
The LMU34… provide all functions required for gas-fired heating boilers in intermittent
operation, burner capacity up to 70 kW.
Gas modulation takes place by fan speed variation.
The LMU34... are designed for residential applications only.
Key features Functions for central heating (CH), with or without weather compensation
Functions for domestic hot water (DHW), with instantaneous heater, etc.
(depending on the type of LMU34...)
Function condensate pump (depending on the type of LMU34...)
Integrated HMI with simple parameter settings / readout of installation data
Interchangeable L / N mains supply (depending on the type of LMU34...)
Options (depending on the type of LMU34...)
1. Auxiliary module AGU2.002... for digital room unit QAA73... (LMU34... parameter
settings via QAA73...) and additional output for central heating pump
2. PC software tool for trending / parameter settings (for laboratory and production)
3. YPLAN applications (for UK)
Note!
For more details, refer to LMU34... specification!
All activities (mounting, installation and service work, etc.) must be performed by
qualified staff
Before making any wiring changes in the connection area, completely isolate the
plant from mains supply (all-polar disconnection). Ensure that the plant cannot be
inadvertently switched on again and that it is indeed dead. If not disconnected,
there is a risk of electric shock hazard
Protection against electric shock hazard on the LMU34... and on all connected
electrical components must be ensured through adequate mounting
The following hazards must be considered and eliminated by fitting appropriate
covers and by using adequate constructions:
- Electrical shock hazard
- Injury when handling the unit
- Excessive heat spreading to cables, plastic parts or subassemblies
Before performing any wiring changes, completely isolate the unit from mains
supply and take measures to ensure that the plant cannot be inadvertently
switched on
Use a multipolar switch to isolate the LMU34... from mains supply
Each time work has been carried out (mounting, installation and service work, etc.),
check to ensure that wiring is in an orderly state and that parameters have been
correctly set and make the safety checks as described in «Commissioning notes».
Touch the LMU34... only on the transformer to prevent damage to electronic
components due to static charges
Check the required DHW temperature to prevent scalding. The installer is
responsible for fitting appropriate warning signs near the taps
Fall or shock can adversely affect the safety functions. Such units must not be put
into operation, even if they do not exhibit any damage
On the application, ensure that pollution degree 2 will not be exceeded
Ensure that the level of protection against electrical shock hazard will not be
reduced when installing or integrating the gas burner control into the equipment
Screws for securing / mounting the PCB must not be touchable or must be
separated from active parts by double or reinforced isolation
To ensure safe and reliable operation of the unit, the following points must also be
observed:
- Avoid condensation and damp environments!
If such conditions have occurred, make certain the LMU34... is completely dry again
before switching on power!
- Static charges must be avoided since they can damage the electronic components
when touched
Recommendation: Use ESD equipment!
2/29
Application notes
Notes on integrating the LMU34… (heating boiler for gaseous fuels type C, rated
capacity 70 kW):
The impact of continuous control of the ignition equipment caused by an internal
failure of one of the burner control components in connection with an earth fault of
one of the connecting wires of the ignition equipment must be assessed depending
on the application
High limit thermostat function
Signals from the potential-free contact at terminals X401: X401 pin 3 / X401 pin 4
will be further handled by the LMU34… in a safety-related manner. Functions
”Shutdown”, “Lockout” and “Reset” are implemented in the LMU34… and are in
compliance with EN 298 and DIN V ENV 14459 (class C)
Signals from the flue gas limiter (thermo fuse) fed to terminals X401: X401 pin 1 /
X401 pin 2 will be further handled in a non-safety-related manner (class A)
The LMU34... conforms to standard for gas boiler type C so DIN EN 483: 2000 (gas
boiler for central heating).
The LMU34.3… conforms to CSA / ANSI Z21.20b 2001 < 117 kW.
Note!
Prepurge, postpurge and interpurge times including all fan-related parameters (speed,
PWM) are non-safety-related.
The boiler must meet the requirements of 6.4.5 (according to EN 483:2000) through
other means (e.g. by a gas valve which must meet special requirements)
Mounting notes
The electrical wiring inside the boiler must conform to country-specific and local
regulations. The rated loads and the rating of the unit fuse must be taken into
account
Ensure that the relevant national safety regulations are complied with
Make certain that spliced individual wires cannot get into contact with neighboring
terminals
Electromagnetic emissions must be checked on an application-specific basis
The unit must be mounted within a closed housing
When mounted inside the boiler, the maximum permissible ambient temperature
must not be exceeded
On the boiler, fit the unit in a housing (degree of protection min. IP40 or IP54 for
outdoor use)
Resistor R114 can reach high temperatures in operation. This must be considered
when mounting and servicing the PCB
3/29
4/29
Ignition equipment Always run high-voltage ignition cables separately while observing the greatest
possible distance to the unit and to other cables. Always use suitable cable for the
ignition equipment. If not observed, unsuitable cable can cause electrical shock or
lead to plant failure
Electrical ignition sparks produce high-frequency energy that can adversely affect radio
and television reception. The high-voltage cable running to the ignition electrode acts
as a transmitter antenna. The ignition module connected to the LMU34…must be
equipped with suitable filters to prevent high-frequency energy from being passed from
the ignition cable to the other connection terminals.
Nevertheless, an application-specific test must be made to ensure that there is no
electrical interference. High-frequency energy is also of capacitive and inductive nature,
and not only wire-bound. This must be taken into consideration when laying the cables.
The ignition cable must meet the technical requirements of the ignition module
and must be run to the ignition electrode as directly as possible, without any
loops.
The ignition cable must never be run parallel or very close to other electrical cables.
To avoid poor EMC performance, run the functional earth of the ignition module to
burner ground as short as possible. This wire should not be routed via the LMU34…
Commissioning notes
There is no absolute protection against incorrect use of the connectors. For this
reason, prior to commissioning the plant, the correct assignment of the connection
terminals must be checked
5/29
ISO 9001:2008
ISO 14001:2004
OHSAS 18001:2007
Service notes
Each time a unit has been replaced, check all safety functions.
In the event of blown fuses external to the LMU34…, the unit must be
returned to Siemens AG (apply to safety checks)
Life cycle
LMU34... boiler management unit have a designed lifetime* of 250,000 burner startup
cycles which, under normal operating conditions in heating mode, correspond to
approx. 10 years of usage (starting from the production date given on the type field).
The designed lifetime is based on use of the BMUs according to the manufacturer’s
Data Sheet. After reaching the designed lifetime in terms of the number of burner
startup cycles, or the respective time of usage, the BMU is to be replaced by authorized
personnel.
* The designed lifetime is not the warranty time specified in the Terms of Delivery
Disposal notes
The unit contains electrical and electronic components and must not be disposed of
together with domestic waste.
Local and currently valid legislation must be observed.
Type summary
neutral conductor (N)
condensate pump
interchangeable
DHW relay as a
pump module)
(OpenTherm /
CSA approval
Mains voltage
AGU2.002...
Type Remark
Interface to
Phase (L) /
DHW relay
Integrated
LMU34.210... AC 230 V
LMU34.215... AC 230 V
LMU34.216... AC 230 V
LMU34.220... AC 230 V With software 02.12
LMU34.3... AC 120 V
6/29
Communication interface
- Interface for parameterization software ACS425 OCI425
- Interface for laboratory tool ACS420 OCI490...
PC software
- Software tool for laboratory ACS420
- Software tool for parameterization ACS425
7/29
7491z06/1204
Caution!
Condensation, formation of ice and ingress of water are not permitted!
8/29
AGU2.002… Connector X1
General unit data Type Siemens AG system-internal connection
cable is supplied together with
AGU2.002…, 5 poles, coded
Loads Connected to LMU34… (PELV)
Siemens AG system-internal connection
Function Interface for LMU34…
Connector X2
Type Stocko: MKS1852-6-0-202
2 poles, coded
AGU2.002… connections 7 and 8
interchangeable and short-circuit-proof
short-circuit might lead to activation of
special LMU34… functions
Lumberg: 2.5 MSF02(3114)
2 poles
Loads Connected to LMU34… PELV
Siemens AG system-internal connection
Function Interface (OpenTherm) for QAA73…
for more detailed information, refer to
OpenTherm specification and Basic
Documentation QAA73… (P2284)
Connector X3
Type Molex: 1008-5031
3 poles, coded
Loads AC 230 V
2 A, cos 0.8 Imax
fusing max. T3.15H250 to IEC127
Assignment Function AGU2.002…
pin 11: relay NC contact
pin 10: relay NO contact
pin 9: relay COM contact
Function Changeover contact for control of zone
pump / of zone valve
NO contact closed when there is a heat
request from QAA73…
NC contact closed when there is no heat
request from QAA73…
Caution!
The AGU2.002… has switching circuits operating on protective extra low-
voltage and switching circuits operating on mains voltage.
On the application, ensure that the required isolation will be observed (cabling,
etc.).
9/29
10/29
11/29
Ionization probe
(safety relevant) 120 / 230 RAC
Fault display
Note!
For more details, refer to LMU34... specification!
12/29
diagnostics
error code
display of
QAA73...
Internal
Meaning of QAA73... text display Cause
code
Error 10 Error outside sensor 1 Short-circuit of outside temperature sensor
Error 20 Error boiler temperature sensor 1 1 Short-circuit of boiler temperature sensor
Error 20 Error boiler temperature sensor 1 2 Open-circuit of boiler temperature sensor
Error 28 Error flue gas temperature sensor 1 Short-circuit of NTC flue gas sensor
Error 28 Error flue gas temperature sensor 2 Open-circuit of NTC flue gas sensor
Error DHW temperature sensor / thermostat
Error 50 1 Short-circuit of DHW sensor
1
Error DHW temperature sensor / thermostat
Error 50 2 Open-circuit of DHW sensor
1
Error 61 Error room unit 1 20 No telegram received within the timeout time
Error 110 Safety limit thermostat lockout 0 Opening of high limit thermostat
Error 119 Water pressure switch has cutout 0 --
Error 125 Maximum boiler temperature exceeded 20 Pump error due to no temperature gradient
Error 125 Maximum boiler temperature exceeded 21 Pump error due to high temperature check
Error 130 Maximum flue gas temperature exceeded 0 --
Pump error due to temperature check or
Error 131 Burner lockout 0
NTC flue gas sensor
Safety time for flame establishment
Error 133 0 --
exceeded
Error 151 BMU internal error 32 Not existing zeiko number
Error 151 BMU internal error 33-41 Time overrun in time slot detected
Error 151 BMU internal error 48 Not existing cycle number
Program counter was in undefined ROM
Error 151 BMU internal error 65
area
Error 151 BMU internal error 66 Not allowed interrupt vector
Error 151 BMU internal error 67 Stack overflow
Error 151 BMU internal error 68 Error in calculating the heating demand
Error 151 BMU internal error 82 Invalid init state
Error 152 Error parameter setting 20 Invalid parameter version number
Error 152 Error parameter setting 21 Invalid software type
Error 152 Error parameter setting 22 Invalid CRC parameter
Not displayed on the LMU34..., but on
Error 155 Remote lockout release blocked --
QAA73...
Low Voltage Fault (burner control start
Error 156 Error supply voltage 20
prevention)
Low Voltage Fault (indication, no start
Error 156 Error supply voltage 21
prevention)
Over Voltage Fault (indication, no start
Error 156 Error supply voltage 22
prevention)
Error 158 Error condensate 0 Condensate pump continuous operation
13/29
diagnostics
error code
display of
QAA73...
Internal
Meaning of QAA73... text display Cause
code
Under run of minimum fan speed threshold,
Error 160 Fan speed threshold not reached 20
wrong air supply, retry
5 times under run of minimum fan speed
Error 160 Fan speed threshold not reached 21
threshold, wrong air supply, retry after 2 hour
Fan speed on standstill in standby not
Error 160 Fan speed threshold not reached 22
reached
Fan speed threshold in ignition phase not
Error 160 Fan speed threshold not reached 23
reached
Fan speed threshold in ignition phase with
Error 160 Fan speed threshold not reached 24
delayed restart not reached
Error 160 Fan speed threshold not reached 25 Ignition fan speed threshold not reached
Error 161 Maximum fan speed exceeded 20 Exceeding of maximum fan speed NoGmax
Pump OFF, but flow / pressure switch does
Error 164 Error heating circuit flow / pressure switch 1
not open
Pump ON, but flow / pressure switch does not
Error 164 Error heating circuit flow / pressure switch 2
close
Exceeding maximum heat capacity in
Error 167 Heating power limit exceeded / under run 20
operating mode
Under run minimum heat capacity in
Error 167 Heating power limit exceeded / under run 21
operating mode
Error 168 Lockout of device active 0 Burner control communication timeout
Error 180 Chimney sweep function active 0 --
Error 181 Regulator stop function active 0 --
Error 183 Remote reset test mode active 20 Remote reset test mode 1 active
Error 183 Remote reset test mode active 21 Remote reset test mode 2 active
Error 193 Flatness test 1 failed 20 Flatness test 1 failed
14/29
The LMU34... can be configured for different applications by setting parameters via the
QAA73. To make this procedure easy for the installer, 16 sets of parameters have been
defined, every set consisting of 9 parameters, and one set for each application. The
installer will only select the particular parameter set he needs. He cannot select single
parameters.
Only the manufacturer of the LMU34... can define these parameter fields.
The boiler manufacturer is able to set the parameters via OCI425 / ACS425.
15/29
Note!
Additional parameters via ACS425!
16/29
CH potentiometer in the 10 different values appear on the display, depending on the DHW potentiometer
«Display» position: position.
A0 DHW position 0: Actual DHW temperature
A1 DHW position 1: Outside temperature
A2 DHW position 2: Actual PWM value
A3 DHW position 3: Actual fan speed
A4 DHW position 4: Actual CH setpoint produced by the LMU34...
A5 DHW position 5: Flue gas NTC temperature
(not identical with the effective flue gas temperature)
A6 DHW position 6: Diagnostic code
A7 DHW position 7: Free
A8 DHW position 8: Boiler identification
A9 DHW position 9: Boiler parameter identification
This function stops when the starting sequence on the CH potentiometer is repeated
once again, or when there was no action within 3 minutes (timeout). When the function
ended by timeout and the CH potentiometer is in the «Display» position, a «d» will
appear alternating with the CH temperature (5 s) to remind the user to set the CH
setpoint again to a useful value. In this situation, the CH setpoint or room temperature
setpoint (depending on the outside sensor) is set to the minimum. The DHW setpoint
will then be taken from the actual DHW potentiometer position. This flashing sequence
will stop as soon as the CH potentiometer leaves the «Display» position.
A4 A5
A3 A6
A2 A7
min.
B min.
A1 A A8 Display
max. max.
A0 A0
*) Depending on parameterization
17/29
Room thermostat
Room thermostat
HC1
Heat circuit 1 HC1
Heat circuit 1
Room
LMU34... thermostat Room
LMU34... thermostat
Motor 3 way valve
Q1 DHW start Motor 3 way valve
Q1 DHW sensor
DHW
instantanous
DHW storage tank
p HC1
Heat circuit 1 HC1
DHW sensor Heat circuit 1
Boiler 1
Boiler 1
DHW
Primary CH DHW
heat Primary CH
exchanger M heat
Q1 exchanger M
CH pump Q1
CH pump
7491a01e/0107 7491a02e/0107
Single heating zone, controlled via 2-positiion room Single heating zone, controlled via room thermostat,
thermostat: weather-dependent heating curve:
Motor Room
3 way valve thermostat Room thermostat
Room
External summer /
thermostat Room thermostat LMU34... winter changeover
Motor 3 way valve External summer / HC1
Q1 Heat circuit 1
LMU34... / winter changeover HC1 DHW start
Q1 DHW start Heat circuit 1
Outside
temperature
sensor
OTS
Outside
temperatures
sensor
DHW
instantanous DHW
instantanous
p HC1 p
Heat circuit 1 HC 1
Heat circuit 1
Boiler 1
Boiler 1
Primary DHW
Primary DHW
heat CH
heat CH
exchanger
H exchanger
Q1 H
CH pump Q1
CH pump
7491a03e/0107 7491a04e/0107
18/29
Heating zone with weather-compensated heating curve for CH setpoint, with or without room temperature influence:
CH + DHW
Potentiometers without
function QAA73
Remote Remote control
Motor 3 way valve control
20 °C CH setpoint
LMU34... DHW setpoint
Q1
DHW start CH timer
DHW timer
Outside
temperature
sensor
OpenTherm
AGU2.002A149
OTS
Outside
temperature
sensor
DHW
instantanous
p HC1
Heat circuit 1
Boiler 1
Primary DHW
heat CH
exchanger
H
Q1
CH pump
7491a09e/0107
DHW
instantanous
p
CH1 CH2 CHn
Boiler 1
Q2 Q1 Qn
CH pump CH pump CH pump
DHW
Primary
heat CH
exchanger
H
Q1
Boiler pump
7491a05e/0107
19/29
Gottak
Summer / Winter
DHW
instantanous
p
CH1 CH2 CHn
Boiler 1
Q2 Q1 Qn
DHW CH pump CH pump CH pump
Primary
CH
heat
exchanger H
Q1
Boiler pump
7491a06e/0107
Multizone system (room thermostat and / or QAA73), zones with weather-compensated CH setpoint, DHW setpoint
and DHW time program controlled by QAA73:
OTS
Outside
temperature
sensor
DHW
instantanous
p CH1
CH2 CHn
Boiler 1
Q3 Qn Q2
CH
CH CH
Primary DHW pump
pump pump
heat CH
exchanger
H
Q1
Boiler pump
7491a10e/0107
20/29
Summer
Winter Room thermostat
Summer / winter /
Fan supply OFF / reset
X3
Gas valve DHW pump
Heating circuit pump
Heating circuit pump
3 way valve 1)
Heating circuit / DHW
or condensate pump 1)
N Reset
L Room thermostat IN
X9
M Time switch heating circuit
X500 Function earth (has to be connected to burner ground independent from X900)
X501 Flame (ionization probe)
PELV
X401
Flue gas temperature limit thermostat (NTC or contact) not safety relevant
X400
DHW temperature sensor
Outside sensor
X300
X200
X403
Interface for parameterization IF (OCI425)
X900 Function earth (has to be connected to burner ground independent from X500)
1) Depending on the type of LMU34...
Caution!
Connection of X500 with X900 – in each case without separate connection to burner
ground and protective – with fault, there is a risk of electric shock hazard!
*) Applications L1 / L2 are only permitted in EC countries
**) Standard application with L / N for EC and U.S.
21/29
Stelvio
X2 HT: Cable length 1 m Cable length 1 m
CFM / 5 A
1 Functional earth (not for protection purposes)
Half wave rectified AC Half wave rectified AC
2 Ignition ¹) supply N
max. 3 VA max. 3 VA
3 PWM mains voltage operated fan supply L AC 230 V AC 230 V
4 PWM mains voltage operated fan supply N max. 160 VA max. 160 VA
Molex
X3 HT: Cable length 1 m Cable length 1 m
2599 9 poles
AC 40 V AC 40 V
50 Hz 60 Hz
8 Reset input N
< 5 mA < 5 mA
cable length 0.5 m cable length 0.5 m
5 mA (half wave rectified) 5 mA (half wave rectified)
9 Room thermostat input L Cp < 4000 pF Cp < 4000 pF
cable length 40 m cable length 40 m
The unit is supplied with the temperature setpoint potentiometer in the OFF position.
22/29
Molex
X9 HT: Cable length 1 m Cable length 1 m
2599 4 poles
< 5 mA AC < 5 mA AC
1 CH timer supply N
cos = 1 cos = 1
External voltage-free External voltage-free
2 CH timer contact OUT contact or bridge in series contact or bridge in series
to room thermostat input to room thermostat input
< 5 mA AC < 5 mA AC
3 CH timer supply L
cos = 1 cos = 1
External voltage-free External voltage-free
4 CH timer contact IN contact or bridge in series contact or bridge in series
to room thermostat input to room thermostat input
PCB edge
X200 PELV: PC tool interface (OCI490...) OCI490... / ACS420 OCI490... / ACS420
connector
1 Internal
2 Internal
3 Internal
4 Internal
5 Internal
Lumberg
X300 PELV: Auxiliary module (AGU2.002…) for 5 poles 5 poles
4)
Duomodul
remote control cable length <10 cm cable length <10 cm
5 poles
1 Internal
2 Internal
3 Internal
4 Internal
5 Internal
The unit is supplied with the temperature setpoint potentiometer in the OFF position.
23/29
Lumberg
X400 PELV: Cable length 1 m Cable length 1 m
MSF 9 poles
NTC 10 k at 25 °C NTC 10 k at 25 °C
1 DHW temperature sensor beta = 3977 beta = 3977
DC 5 V DC 5 V
NTC 1 k at 25 °C NTC 1 k at 25 °C
2 Outside temperature sensor beta = 3528 beta = 3528
cable length 40 m cable lengths 40 m
Open-circuit condition: Open-circuit condition:
Vout = DC 7.5 V Vout = DC 7.5 V
3 DHW Hall sensor / DHW flow switch IN Closed-circuit condition: Closed-circuit condition:
Iout < 1 mA Iout < 1 mA
Uin < 0.5 V Uin < 0.5 V
4 DHW temperature sensor NTC 10 k at 25 °C NTC 10 k at 25 °C
beta = 3977 beta = 3977
max. DC 5 V max. DC 5 V
5 Outside temperature sensor NTC 1 k at 25 °C NTC 1 k at 25 °C
beta = 3528 beta = 3528
cable length 40 m cable length 40 m
6 DHW Hall sensor / DHW flow switch GND GND GND
DHW Hall sensor / CH primary flow switch DC 7.5 V DC 7.5 V
7
supply (max. 24 mA) (max. 24 mA)
CH primary flow switch / water pressure DC 7.5 V DC 7.5 V
8
switch / bridge < 2 mA < 2 mA
CH primary flow switch / water pressure
9 GND GND
switch / bridge
The unit is supplied with the temperature setpoint potentiometer in the OFF position.
24/29
Lumberg
X401 PELV: Cable length 1 m Cable length 1 m
MSF 10 poles
NTC 20 K at 25 °C NTC 20 k at 25 °C
Flue gas temperature NTC ²) or thermostat beta = 3970 beta = 3970
1
contact DC 5 V DC 5 V
< 2 mA < 2 mA
NTC 20 K at 25 °C NTC 20 k at 25 °C
Flue gas temperature NTC ²) or thermostat beta = 3970 beta = 3970
2
contact DC 5 V DC 5 V
< 2 mA < 2 mA
Half wave rectified Half wave rectified
3 High limit thermostat (TB) AC 24 V AC 24 V
I = 2.5...5 mA I = 2.5...5 mA
Half wave rectified Half wave rectified
4 High limit thermostat (TB) AC 24 V AC 24 V
I = 2.5...5 mA I = 2.5...5 mA
5 PWM fan interface supply GND ¹) ³) GND GND
2 rectangular pulses per 2 rectangular pulses per
PWM hall sensor (fan speed) IN (non safety)
6 revolution revolution
¹) ³)
duty ratio 1:1 +/-5 % duty ratio 1:1 +/-5 %
7 PWM control output (non safety) ¹) ³) 4,800 Hz 4,800 Hz
8 PWM fan interface supply + ¹) ³) DC 30 V DC 30 V
NTC 10 k at 25 °C NTC 10 k at 25 °C
9 CH temperature sensor beta = 3977 beta = 3977
DC 5 V DC 5 V
NTC 10 k at 25 °C NTC 10 k at 25 °C
10 CH temperature sensor beta = 3977 beta = 3977
DC 5 V DC 5 V
Lumberg 3850
X403 PELV: PARA-IFC (OCI425) OCI425 / ACS425 OCI425 / ACS425
4 poles
1 Internal
2 Internal
3 Internal
4 Internal
X501 VT tabs HT: Flame (ionization probe) < AC 100 V < AC 100 V
4.8 mm cable length 1 m cable length 1 m
X900 Tabs 6.3 mm PELV: Functional earth (burner ground) (not Cable length 1 m Cable length 1 m
for protection purposes)
The unit is supplied with the temperature setpoint potentiometer in the OFF position.
25/29
LMU34...
34,5
7
1,55
90 52
75
11 40 24,95 21,52
X900
X300 *) X400 X401
X200
17,5
35
32,94 17,53
127
117
107,82
31 20
94
85,25
80,18
65
X501
4,
2
(6
X500
x)
5
5 87,5 62,5
160
AGU2.002…
(depending on the type of
16,6
LMU34...)
5 40
X1
X2
7
35
45
8
7491m01/0406
X3
11
10
9
5
25 20
51
26/29
15,9
X900
X400 X401
X300 *)
X200
45
6 51
60
X501
X500
27/29
Component side x)
9 (6
LMU34…
)
4x
6(
Inclined plane
45
from 27 up to 54
65
77
60
62
33
Total height max. 34
7491m03e/1006
Zero point 13
Total height (with AGU2.002... mounted) max. 27
6 51
7491m05e/1006
Zero point
28/29
50 55
Soldering side
52 56 34
LMU34…
3 (2 x)
3,5
9 (6
x)
39
39
3,5
4 (4 x)
44
Total height max. 5
28
14
7491m04e/1006
3,5
4 (2 x) Zero point
50 55
2015 Siemens AG Building Technologies Division, Berliner Ring 23, D-76437 Rastatt
Subject to change! 29/29