You are on page 1of 2

PACi Elite Inverter Three Phase

Product Code: U-125PE1E8A


Notes
»» Meeting all necessary safety approvals to ensure
quality and safety
»» Top-class SEER: & SCOP
»» Cooling operation is possible when outdoor
temperature as high as 46°C
»» DC inverter technology combined with R410A for
excellent efficiency
»» Cooling operation is possible when outdoor
temperature as low as -15°C
»» Heating operation is possible when outdoor
temperature as low as -20°C
»» Compact outdoor units
»» Auto restart from outdoor unit
MODEL NUMBER U-125PE1E8A
Nominal Cooling kW 12.5

Nominal Heating kW 14.0

Operating Range - Cooling (Outdoor Air) -15°C to 46°C

Operating Range - Heating (Outdoor Air) -20°C to 24°C

Height mm 1416

Width mm 940

Depth mm 340

Weight mm 98

Airflow Rate l/s 2167 - 1833 (Cool - Heat)

Sound Pressure Level dB(A) 53 - 53 (Cool - Heat)

Pipe Connection Size - Gas in 5/8”

Pipe Connection Size - Liquid in 3/8”

Maximum Pipe Run m 5 min - 75 max

Maximum Height Difference m 30

Refrigerant R410A

Precharged For m 30

Factory Charge kg 3.40

GWP (Tonnes CO2 Equivalent) 7.099

Additional Charge g/m 50

Suitable For Replacement Technology Yes

Power Supply V- Ph - Hz 400 - 3 - 50

Interconnecting Cables 2 core

Suggested Fuse Size A 16

* exact cooling and heating capacities will depend on connected indoor unit(s)

ampair.co.uk | 01707 378 670 | sales@ampair.co.uk

AMP Air Conditioning, Blenheim House, Blenheim Court, Brownfields, Welwyn Garden City, Hertfordshire AL7 1AD
Wiring
As standard on the Big PACi, Std &Elite PACi they have a separate power supply to indoor and out-
door.

However please note the following.

»» It is perfectly acceptable to run the power from the outdoor to indoor.


»» If you have a larger distance between indoor and outdoor, it is far more cost effective to simply
run the 2-core communication cables and have a separate supply.
»» All indoor units (apart from the ME or PE high static ducted), only require a 6A fused spur.
Therefore if you’re just running a split, it is possible to take the feed from a local lighting circuit or
similar. Be careful on twins, triples etc. and as always they need to be installed to local electrical
regulations.
»» Comms should always be screened both ends when connecting between indoor and outdoor
units.
»» We would never recommend running comms in the same cable as the power (EMI from power) it
should be shielded (0.75mm² min.).

ampair.co.uk | 01707 378 670 | sales@ampair.co.uk