FHC - Hydraulic Calculation Report

Submitted by FHC user number: Project: FIRST TEST


Project Ref 123/456
Area Ref: 10 HEADS
Inst. Number: 1

Tel:
Fax:

Project Data and Design Parameters


Project name : FIRST TEST
Area reference : 10 HEADS
Address / location : Leeds
Project number : 123/456
Installation number(s) : 1
Drawing number(s) : SKETCH 1
Issue no / date : ---
Designers reference : Canute LLP
Project Data File : test 2.FHC
Hazard classification : HIGH HAZARD
Design authority : EN 12845 Rules
Insurance company : Not known
Specified density of discharge : 10.00 mm/min (l/min/m2)
Assumed maximum area of operation : 54.00 m2
Number of operating sprinkler heads : 7
Maximum area covered per head : 9.00 m2
Highest head / nozzle above source : 5.00 m
Number of pipes in system : 15 from 25 to 100 mm
Pressure loss equation used : Hazen-Williams
Fluid : Water
Pipe Data Table : STD_PIPE.PDT
Maximum fluid velocity : 5.28 m/s in pipe 3 2
Volume of pipework and fittings : 0.61 m3
Elbows are welded for : 200 mm and above
Comment : -
Checked by & Date :

Source duty = 769.8 l/min @ 3.014 bar at node no 100

Canute FHC Ver: 1.8.4 Sunday, September 12, 2021 - 12:39


www.canutesoft.com Page: 1/3
FHC - Hydraulic Calculation Report
Submitted by user number: Project: FIRST TEST
Project Ref 123/456
Tel: Area Ref: 10 HEADS
Fax: Inst. Number: 1

Operating Sprinkler Heads, Nozzles and Hydrants


Head|Node| Size | 'K' |F l o w|A r e a|Density mm/min|Pressure bar|Heights|Pipe
no | no | mm | factor| l/min | m2 |Req.d Actual| Min Actual| m | no
1 7 15.0 80.00 118.6 9.000 10.00 13.18 0.50 2.199 5.000 6
2 13 15.0 80.00 117.8 9.000 10.00 13.09 0.50 2.167 5.000 9
3 14 15.0 80.00 116.5 9.000 10.00 12.95 0.50 2.122 5.000 10
4 8 15.0 80.00 114.0 9.000 10.00 12.67 0.50 2.032 5.000 11
5 4 15.0 80.00 117.2 0.000 0.00 0.00 0.50 2.145 5.000 13
6 2 15.0 80.00 95.6 9.000 10.00 10.62 0.50 1.429 5.000 14
7 1 15.0 80.00 90.0 9.000 10.00 10.00 0.50 1.266 5.000 15

0 heads are under the required density / minimum pressures

Canute FHC Ver: 1.8.4 Sunday, September 12, 2021 - 12:39


www.canutesoft.com Page: 2/3
FHC - Hydraulic Calculation Report
Submitted by user number: Project: FIRST TEST
Project Ref 123/456
Tel: Area Ref: 10 HEADS
Fax: Inst. Number: 1

Hydraulically Significant Pipes in System


NUMBERS | P I P E | F L O W |DIMENSIONS|ANGLE| VALUES |HEIGHT M|PRESSURES BARS
Pipe|Start|Size Type| L/min | Length VJ|Dir. | Eq.len | Start | Start Frict
no | End |Bore 'C'| Vel m/s |EL T VT|Slope| mbar/m | End | End Static
1 100 100mm MW 769.8 1.500 Up 2.31 0.000 3.014 -0.006
16 105.14 120 1.5 0 0 GV 90.0 2.7 1.500 2.861 -0.147
2 16 100mm MW 769.8 3.000 Up 8.07 1.500 2.861 -0.022
15 105.14 120 1.5 0 0 SV 90.0 2.7 4.500 2.545 -0.294
3 15 100mm MW 769.8 60.000 90 63.04 4.500 2.545 -0.169
10 105.14 120 1.5 1 0 0.0 2.7 4.500 2.376 +0.000
4 10 80mm MW 535.5 0.500 Up 5.25 4.500 2.376 -0.026
9 80.68 120 1.7 0 1 90.0 5.0 5.000 2.301 -0.049
5 9 80mm MW 535.5 1.500 0 3.87 5.000 2.301 -0.019
5 80.68 120 1.7 1 0 0.0 5.0 5.000 2.281 +0.000
6 5 32mm MW 232.7 1.500 0 1.50 5.000 2.281 -0.082
7 35.97 120 3.8 0 0 0.0 54.5 5.000 2.200 +0.000
7 10 100mm MW 234.3 3.000 90 3.00 4.500 2.376 -0.001
11 105.14 120 0.4 0 0 0.0 0.3 4.500 2.375 +0.000
8 11 40mm MW 234.3 0.500 Up 1.72 4.500 2.375 -0.045
12 41.86 120 2.8 1 0 90.0 26.4 5.000 2.281 -0.049
9 12 32mm MW 234.3 1.000 0 2.04 5.000 2.281 -0.113
13 35.97 120 3.8 1 0 0.0 55.2 5.000 2.168 +0.000
10 13 32mm MW 116.5 3.000 0 3.00 5.000 2.168 -0.045
14 35.97 120 1.9 0 0 0.0 15.2 5.000 2.122 +0.000
11 7 25mm MW 114.0 3.000 0 3.00 5.000 2.200 -0.167
8 27.31 120 3.2 0 0 0.0 55.7 5.000 2.032 +0.000
12 5 65mm MW 302.8 1.000 270 4.81 5.000 2.281 -0.018
3 68.67 120 1.4 0 1 0.0 3.8 5.000 2.263 +0.000
13 3 25mm MW 117.2 2.000 270 2.00 5.000 2.263 -0.117
4 27.31 120 3.3 0 0 0.0 58.5 5.000 2.146 +0.000
14 3 25mm MW 185.6 3.000 0 6.08 5.000 2.263 -0.834
2 27.31 120 5.3 0 1 ST 0.0 137.2 5.000 1.429 +0.000
15 2 25mm MW 90.0 3.000 0 4.54 5.000 1.429 -0.163
1 27.31 120 2.6 0 0 ST 0.0 35.9 5.000 1.266 +0.000
Maximum flow rate error at nodes : 0.00489 L/min
Maximum pressure drop error at nodes : 0.00089 bar
Maximum pressure drop error in loops : 0.00000 bar
Overall head flow balance error : 0.00220 %