Project Ref 123/456 Area Ref: 10 HEADS Inst. Number: 1
Tel: Fax:
Project Data and Design Parameters
Project name : FIRST TEST Area reference : 10 HEADS Address / location : Leeds Project number : 123/456 Installation number(s) : 1 Drawing number(s) : SKETCH 1 Issue no / date : --- Designers reference : Canute LLP Project Data File : test 2.FHC Hazard classification : HIGH HAZARD Design authority : EN 12845 Rules Insurance company : Not known Specified density of discharge : 10.00 mm/min (l/min/m2) Assumed maximum area of operation : 54.00 m2 Number of operating sprinkler heads : 7 Maximum area covered per head : 9.00 m2 Highest head / nozzle above source : 5.00 m Number of pipes in system : 15 from 25 to 100 mm Pressure loss equation used : Hazen-Williams Fluid : Water Pipe Data Table : STD_PIPE.PDT Maximum fluid velocity : 5.28 m/s in pipe 3 2 Volume of pipework and fittings : 0.61 m3 Elbows are welded for : 200 mm and above Comment : - Checked by & Date :
Source duty = 769.8 l/min @ 3.014 bar at node no 100
Canute FHC Ver: 1.8.4 Sunday, September 12, 2021 - 12:39