OVERVIEW
Note: This document applies to ACS600 200V, 400 V, 500 V and 690 V
series, ACS611 series and ACF600 690V series only.
This paper gives instructions for converter parameter setting that must be
carried out when the NAMC-xx board is replaced.
There is also parameter settings for new and old ACS600 Single Drive
hardware. See Appendix 1.
Old ACF600 400V or 500V series inverters can be equipped with NAMC-
11 (or C) SP KIT STD or NAMC-11 (or C) SP KIT PFC.
ABB Industry Oy NAMC-xx Parameter 58946222
Drives Setting
Product AC, Helsinki 58946222.DOC
DEPT PREPARED BY DATE REVISION APPROVED BY PAGE
EJQ ACS600 Technical 20/05/1999 J KI 2(12)
Support
The NAMC-xx Application and Motor Control Board, used in all ACS600
models, requires no hardware configuration before or after installation.
However, after the board has been replaced, several parameters
concerning the technical specifications of the converter (Parameter
Groups 97, 112 and 190) units must be re-defined.
Gaining Access to Parameter Groups 97 (needed for 690 V units only), 112 and 190
Under normal conditions, the parameters in Groups 97, 112 and 190 have
to be set only once, and this is done at the manufacturing plant prior to
delivery. However, the parameters must be re-defined after a replacement
NAMC board has been installed. The parameters are not intended to be
changed by the user, and they are not dealt with in the ACS 600
Programming Manual. In order to gain access to Parameter Groups 112
and 190, code 564 must be entered at Parameter 16.3 (PASS CODE).
The passcode to parameter group 97 is 5600. The setting takes effect
only after the panel power is switched of and on. (See the ACS 600
Programming Manual for details on how to modify parameter values.)
After entering the parameters, the converter unit must be switched off
from the mains and then on again for the new settings to take effect. This
also disables changes to Parameter Groups 97, 112 and 190. The
Parameter Lock will be left in the OPEN position, allowing changes to
parameters in Groups 10 through 99. Setting the Parameter Lock in the
LOCKED position will disable all parameter alteration.
The required settings for Parameter Groups 112 and 190 for old type of
ACS600 Hardware (400 V, 500 V and 690V) are given in the Table 1.1.
for 400V and 500V units and for 690V units in the Table 1.2.
The required settings for Parameter Groups 112 and 190 for new type of
ACS600 Hardware (200V, 400 V, 500 V and 690V) are given in Table
2.1. for 400V, in Table 2.2. for 500V units, for 690V units in Table 2.3 and
200V units in Table 2.4.
The required settings for Parameter Groups 112 and 190 for ACX611
Hardware (500 V) are given in Table 2.5.
ABB Industry Oy NAMC-xx Parameter 58946222
Drives Setting
Product AC, Helsinki 58946222.DOC
DEPT PREPARED BY DATE REVISION APPROVED BY PAGE
EJQ ACS600 Technical 20/05/1999 J KI 4(12)
Support
Table 1.1 Parameters to be set after replacement of NAMC-03 or NAMC-11 in 400V and
500 V old type of units: ACS6XXXXXXXXXXXXXXXXX0 or
ACS6XXXXXXXXXXXXXXXXXC.
Parameter 112.1 112.2 112.3 112.4 190.1 190.2 190.4 190.15
Nominal Inverter Inverter ACS610 Maximum Maximum Nominal Minimum
inverter heavy duty Heavy duty measurable measurable inverter nominal
voltage current Power TRUE/ voltage current current line voltage
[V] [A] [kVA] FALSE [V] [A] [A] [V]
400V Series
ACS6xx-0005-3 415 6.2 4.4566 FALSE 900 22.134 7.6 380
ACS6xx-0006-3 415 7.6 5.4629 FALSE 900 27.132 11 380
ACS6xx-0009-3 415 11 7.9068 FALSE 900 39.27 15 380
ACS6xx-0011-3 415 15 10.7820 FALSE 900 53.55 18 380
ACS6xx-0016-3 415 18 12.9384 FALSE 900 64.26 24 380
ACS6xx-0020-3 415 24 17.2512 FALSE 900 85.68 32 380
ACS6xx-0025-3 415 32 23.0016 FALSE 900 114.24 41 380
ACS6xx-0030-3 415 41 29.4708 FALSE 900 146.37 47 380
ACS6xx-0040-3 415 47 33.7837 FALSE 900 167.79 62 380
ACS6xx-0050-3 415 62 44.5657 FALSE 900 221.34 76 380
ACS6xx-0060-3 415 76 54.6289 FALSE 900 271.32 89 380
ACS6xx-0070-3 415 89 63.9733 FALSE 900 317.73 112 380
ACS6xx-0100-3 415 112 80.5057 FALSE 900 399.84 147 380
ACS6xx-0120-3 415 147 105.6638 FALSE 900 524.79 178 380
ACS6xx-0140-3 415 178 127.9466 FALSE 900 635.46 216 380
ACS6xx-0170-3 415 216 155.2610 FALSE 900 771.12 260 380
ACS6xx-0210-3 415 260 186.8883 FALSE 900 928.2 316 380
ACS6xx-0260-3 415 316 227.1411 FALSE 900 1128.12 395 380
ACS6xx-0320-3 415 395 283.9264 FALSE 900 1410.15 480 380
500V Series
ACS6xx-0006-5 500 6.2 5.3694 FALSE 900 22.134 7.6 380
ACS6xx-0009-5 500 7.6 6.5818 FALSE 900 27.132 11 380
ACS6xx-0011-5 500 11 9.5263 FALSE 900 39.27 15 380
ACS6xx-0016-5 500 15 12.9904 FALSE 900 53.55 18 380
ACS6xx-0020-5 500 18 15.5885 FALSE 900 64.26 24 380
ACS6xx-0025-5 500 24 20.7846 FALSE 900 85.68 31 380
ACS6xx-0030-5 500 31 26.8468 FALSE 900 110.67 41 380
ACS6xx-0040-5 500 41 35.5070 FALSE 900 146.37 47 380
ACS6xx-0050-5 500 47 40.7032 FALSE 900 167.79 58 380
ACS6xx-0060-5 500 58 50.2295 FALSE 900 207.06 65 380
ACS6xx-0070-5 500 65 56.2917 FALSE 900 232.05 84 380
ACS6xx-0100-5 500 84 72.7461 FALSE 900 299.88 112 380
ACS6xx-0120-5 500 112 96.9948 FALSE 900 399.84 135 380
ACS6xx-0140-5 500 135 116.9134 FALSE 900 481.95 164 380
ACS6xx-0170-5 500 164 142.0282 FALSE 900 585.48 200 380
ACS6xx-0210-5 500 200 173.2051 FALSE 900 714 240 380
ACS6xx-0260-5 500 240 207.8461 FALSE 900 856.8 300 380
ACS6xx-0320-5 500 300 259.8076 FALSE 900 1071 365 380
ACS6xx-0400-5 500 365 316.0993 FALSE 900 1303.05 460 380
ABB Industry Oy NAMC-xx Parameter 58946222
Drives Setting
Product AC, Helsinki 58946222.DOC
DEPT PREPARED BY DATE REVISION APPROVED BY PAGE
EJQ ACS600 Technical 20/05/1999 J KI 5(12)
Support
Table 1.2. Parameters to be set after replacement of NAMC-03 or NAMC-11 in 690 V old
type of units: ACS6XXXXXX6XXXXXXXXXX0 or ACS6XXXXXX6XXXXXXXXXXC.
690V Series
ACS6xx-0009-6 690 6.2 7.4 NONE 1242 22.1 7.6 525.0
ACS6xx-0011-6 690 7.6 9.1 NONE 1242 27.1 11.0 525.0
ACS6xx-0016-6 690 11.0 13.1 NONE 1242 39.3 15.0 525.0
ACS6xx-0020-6 690 15.0 17.9 NONE 1242 53.6 20.0 525.0
ACS6xx-0025-6 690 20.0 23.9 NONE 1242 71.4 25.0 525.0
ACS6xx-0030-6 690 25.0 29.9 NONE 1242 89.3 28.0 525.0
ACS6xx-0040-6 690 28.0 33.5 NONE 1242 100.0 36.0 525.0
ACS6xx-0050-6 690 36.0 43.0 NONE 1242 128.5 44.0 525.0
ACS6xx-0060-6 690 44.0 52.6 NONE 1242 157.1 52.0 525.0
ACS6xx-0070-6 690 52.0 62.1 NONE 1242 185.6 65.0 525.0
ACS6xx-0100-6 690 65.0 77.7 NONE 1242 232.1 88.0 525.0
ACS6xx-0120-6 690 88.0 105.2 NONE 1242 314.2 105.0 525.0
ACS6xx-0140-6 690 105.0 125.5 NONE 1242 374.9 127.0 525.0
ACS6xx-0170-6 690 127.0 151.8 NONE 1242 453.4 150.0 525.0
ACS6xx-0210-6 690 150.0 179.3 NONE 1242 535.5 179.0 525.0
ACS6xx-0260-6 690 179.0 213.9 NONE 1242 639.0 225.0 525.0
ACS6xx-0320-6 690 225.0 268.9 NONE 1242 803.3 265.0 525.0
ACS6xx-0400-6 690 265.0 316.7 NONE 1242 946.1 351.0 525.0
NOTE!
Parameter 97.11 (Long Distance Mode) for 690 V units have to be set to “ON”.
ABB Industry Oy NAMC-xx Parameter 58946222
Drives Setting
Product AC, Helsinki 58946222.DOC
DEPT PREPARED BY DATE REVISION APPROVED BY PAGE
EJQ ACS600 Technical 20/05/1999 J KI 6(12)
Support
TABLE 2.1 Parameters to be set after replacement of NAMC-11 in 400 V a new type of
units: ACS6XXXXXX3XXXXXXXXXX1 or ACS6XXXXXX3XXXXXXXXXXD.
Parameter 112.1 112.2 112.3 112.4 190.1 190.2 190.4 190.15 190.08
Nominal Inverter Inverter Supply Ctrl Maximum Maximum Nominal Minimum
inverter heavy duty heavy duty Mode Measurable measurable Inverter nominal
voltage Current Power NONE/ Voltage current Current line
voltage
[V] [A] [kVA] LINE CONV [V] [A] [A] [V]
DEMO 415 1.6 1.1 NONE 900.0 5.6 2.1 380.0 2859753
400V Series
ACS6xx-0005-3 415 6.2 4.5 NONE 900.0 22.1 7.6 380.0 2570702
ACS6xx-0006-3 415 7.6 5.5 NONE 900.0 27.1 11 380.0 3035352
ACS6xx-0009-3 415 11 7.9 NONE 900.0 39.3 15 380.0 2859753
ACS6xx-0011-3 415 15 10.8 NONE 900.0 53.6 18 380.0 2516582
ACS6xx-0016-3 415 18 12.9 NONE 900.0 64.3 24 380.0 2796203
ACS6xx-0020-3 415 24 17.3 NONE 900.0 85.7 32 380.0 3582635
ACS6xx-0025-3 415 32 23.0 NONE 900.0 114.2 41 380.0 3080192
ACS6xx-0030-3 415 41 29.5 NONE 900.0 146.4 47 380.0 3171303
ACS6xx-0040-3 415 47 33.8 NONE 900.0 167.8 62 380.0 3391139
ACS6xx-0050-3 415 62 44.6 NONE 900.0 221.3 76 380.0 3010428
ACS6xx-0060-3 415 76 54.6 NONE 900.0 271.3 89 380.0 3090540
ACS6xx-0070-3 415 89 64.0 NONE 900.0 317.7 112 380.0 2921875
ACS6xx-0100-3 415 112 80.5 NONE 900.0 399.8 147 380.0 3332974
ACS6xx-0120-3 415 147 105.7 NONE 900.0 524.8 178 380.0 2853268
ACS6xx-0140-3 415 178 127.9 NONE 900.0 635.5 216 380.0 3063256
ACS6xx-0170-3 415 216 155.3 NONE 900.0 771.1 260 380.0 2912711
ACS6xx-0210-3 415 260 186.9 NONE 900.0 928.2 316 380.0 3024738
ACS6xx-0260-3 415 316 227.1 NONE 900.0 1128.1 395 380.0 3185547
ACS6xx-0320-3 415 395 283.9 NONE 900.0 1410.2 480 380.0 2707715
ABB Industry Oy NAMC-xx Parameter 58946222
Drives Setting
Product AC, Helsinki 58946222.DOC
DEPT PREPARED BY DATE REVISION APPROVED BY PAGE
EJQ ACS600 Technical 20/05/1999 J KI 7(12)
Support
TABLE 2.2 Parameters to be set after replacement of NAMC-11 in 500 V new type of
units: ACS6XXXXXX5XXXXXXXXXX1 or ACS6XXXXXX5XXXXXXXXXXD (Not ACS611
units) .
Parameter 112.1 112.2 112.3 112.4 190.1 190.2 190.4 190.15 190.08
Nominal Inverter Inverter Supply Ctrl Maximum Maximum Nominal Minimum
inverter heavy duty heavy duty Mode Measurable measurable inverter nominal
voltage Current power NONE/ Voltage current current line
voltage
[V] [A] [kVA] LINE [V] [A] [A] [V]
CONV
500V Series
ACS6xx-0006-5 500 6.2 5.4 NONE 900.0 22.1 7.6 380.0 2570702
ACS6xx-0009-5 500 7.6 6.6 NONE 900.0 27.1 11 380.0 3035352
ACS6xx-0011-5 500 11 9.5 NONE 900.0 39.3 15 380.0 2859753
ACS6xx-0016-5 500 15 13.0 NONE 900.0 53.6 18 380.0 2936013
ACS6xx-0020-5 500 18 15.6 NONE 900.0 64.3 24 380.0 3145728
ACS6xx-0025-5 500 24 20.8 NONE 900.0 85.7 31 380.0 3582635
ACS6xx-0030-5 500 31 26.8 NONE 900.0 110.7 41 380.0 3179553
ACS6xx-0040-5 500 41 35.5 NONE 900.0 146.4 47 380.0 2966703
ACS6xx-0050-5 500 47 40.7 NONE 900.0 167.8 58 380.0 2900317
ACS6xx-0060-5 500 58 50.2 NONE 900.0 207.1 65 380.0 3037255
ACS6xx-0070-5 500 65 56.3 NONE 900.0 232.1 84 380.0 3613554
ACS6xx-0100-5 500 84 72.7 NONE 900.0 299.9 112 380.0 3095796
ACS6xx-0120-5 500 112 97.0 NONE 900.0 399.8 135 380.0 3070830
ACS6xx-0140-5 500 135 116.9 NONE 900.0 482.0 164 380.0 2998151
ACS6xx-0170-5 500 164 142.0 NONE 900.0 585.5 200 380.0 3069003
ACS6xx-0210-5 500 200 173.2 NONE 900.0 714.0 240 380.0 2988442
ACS6xx-0260-5 500 240 207.8 NONE 900.0 856.8 300 380.0 3014656
ACS6xx-0320-5 500 300 259.8 NONE 900.0 1071.0 365 380.0 3215633
ACS6xx-0400-5 500 365 316.1 NONE 900.0 1303.1 460 380.0 2815355
ABB Industry Oy NAMC-xx Parameter 58946222
Drives Setting
Product AC, Helsinki 58946222.DOC
DEPT PREPARED BY DATE REVISION APPROVED BY PAGE
EJQ ACS600 Technical 20/05/1999 J KI 8(12)
Support
TABLE 2.3 Parameters to be set after replacement of NAMC-11 in 690 V new type of
units: ACS6XXXXX6XXXXXXXXXX1 or ACS6XXXXXX6XXXXXXXXXXD .
Parameter 112.1 112.2 112.3 112.4 190.1 190.2 190.4 190.15 190.08
Nominal Inverter Inverter Supply Ctrl Maximum Maximum Nominal Minimum
inverter heavy duty heavy duty Mode measurable measurable inverter nominal
690V Series
ACS6xx-0009-6 690 6.2 7.4 NONE 1242 22.1 7.6 525.0 2570702
ACS6xx-0011-6 690 7.6 9.1 NONE 1242 27.1 11 525.0 3035352
ACS6xx-0016-6 690 11 13.1 NONE 1242 39.3 15 525.0 2859753
ACS6xx-0020-6 690 15 17.9 NONE 1242 53.6 20 525.0 2796203
ACS6xx-0025-6 690 20 23.9 NONE 1242 71.4 25 525.0 2621440
ACS6xx-0030-6 690 25 29.9 NONE 1242 89.3 28 525.0 2348810
ACS6xx-0040-6 690 28 33.5 NONE 1242 100.0 36 525.0 2696338
ACS6xx-0050-6 690 36 43.0 NONE 1242 128.5 44 525.0 2563186
ACS6xx-0060-6 690 44 52.6 NONE 1242 157.1 52 525.0 2478452
ACS6xx-0070-6 690 52 62.1 NONE 1242 185.6 65 525.0 2621440
ACS6xx-0100-6 690 65 77.7 NONE 1242 232.1 88 525.0 2839221
ACS6xx-0120-6 690 88 105.2 NONE 1242 314.2 105 525.0 2502284
ACS6xx-0140-6 690 105 125.5 NONE 1242 374.9 127 525.0 2536555
ACS6xx-0170-6 690 127 151.8 NONE 1242 453.4 150 525.0 2476951
ACS6xx-0210-6 690 150 179.3 NONE 1242 535.5 179 525.0 2502601
ACS6xx-0260-6 690 179 213.9 NONE 1242 639.0 225 525.0 2636085
ACS6xx-0320-6 690 225 268.9 NONE 1242 803.3 265 525.0 2469979
ACS6xx-0400-6 690 265 316.7 NONE 1242 946.1 351 525.0 2777737
NOTE!
Parameter 97.11 (Long Distance Mode) for 690 V units have to be set to “ON”.
ABB Industry Oy NAMC-xx Parameter 58946222
Drives Setting
Product AC, Helsinki 58946222.DOC
DEPT PREPARED BY DATE REVISION APPROVED BY PAGE
EJQ ACS600 Technical 20/05/1999 J KI 9(12)
Support
TABLE 2.4 Parameters to be set after replacement of NAMC-11 in 200 V new type of
units:
Parameter 112.1 112.2 112.3 112.4 190.1 190.2 190.4 190.15 190.08
Nominal Inverter Inverter Supply Ctrl Maximum Maximum Nominal Minimum
inverter heavy duty heavy duty Mode measurable measurable inverter Nominal
voltage current power NONE/ voltage current current line
[V] [A] [kVA] LINE CONV [V] [A] [A] voltage [V]
200V Series
TABLE 2.5 Parameters to be set after replacement of NAMC-11 in ACX611 500 V units:
Appendix 1
Spare Part Kits for Software and different type of the ACS600 hardwares.