5.1.7 Cable Tray Load Calculation
5.1.7 Cable Tray Load Calculation
Distance of
Column Span Effectrive Load on Moment on STAAD Load From
Span Left Elevation Eccentricity
Mark Right Span Column Column Beam Beam Start
Node
m m m kN m kNm
GY GX
A1 5 11 10.5 (+)6.805 50.4 1.15 57.96 254 0.805
A2 11 10.5 10.75 (+)6.805 51.6 1.15 59.34 134 0.805
A3 10.5 8 9.25 (+)6.805 44.4 1.15 51.06 135 0.805
A4 8 2.15 6.15 (+)6.805 29.52 1.15 33.948 267 2.105
5.1.8 Miscellaneous Loads
No of Fans
Col Staad
(Effectively Distance FY Eccentricity MZ
Mark Member
transferring load)
For 0.7 / 0.3 loads being transferred to each column A4 and B4 respectively
Eccentricity 2.52 m
Vertical Load 35 kN 15 kN
Moment 88.2 kN-m 37.8 kN-m
Dead Laod
Vertical Load 10 kN 10 kN
Moment 25.2 kN-m 25.2 kN-m
Live Load
Eccentricity 1.9 m
Vertical Load 90.25 kN 90.25 kN
Moment 171.475 kN-m 171.475 kN-m