Features
Ordering information
KN-2 0 0 0 W
Size
W DIN W96×H48 mm
0 No option
1 Transmission output (4-20 mA)
Option output
4 RS485 communication output
Transmission output (4-20 mA)
5
+ RS485 communication output
0 No alarm output
Alarm output
2 2EA alarm output
4 4EA alarm output
Item
KN-2 Multi Indicator
Dimensions
(unit:mm)
48
96 10
108 90
● Panel cut-out
Min. 116
44.8
46 +0.6
0
Min. 52
92 +0.6
0
91
B-14
Multi Indicator
Connections A. Recorder
C. Converter
RTD/TC/mV/±1V
D. Controller
-1 to +10V
0 to 20mA
E. Thyristor
unit
F. Pressure
transmitter
F.G.
G. Temp.
transmitter
H. Accessories
Specifications
Series KN-2000W
B-15
KN-2000W Series
Input type and range
Part descriptions
①
① Display part(red)
● Run mode : Displays current measurement value.
● Parameter set mode : Displays parameter and SV.
②
③ ② Unit indicator : Displays the set unit.
③ Alarm output indicator : Turns ON when the alarm is ON.
⑤ ④ ( key: Used to enter parameter set mode, move to
parameters, save SV and return to RUN mode.
⑤ 1, 4, 3 key: Used to change parameter SV.
⑥ D.IN3 : Press the 4 and 3 keys keys for 3 sec. at the same
④ ⑥
time, it operates the set function (alarm clear, display
hold, zero-point adjustment) at [ DI-K ] at program
mode.
B-16
Multi Indicator
Functions A. Recorder
OFF H ON
AT! High limit alarm PV ≥ alarm temperature, alarm is ON H. Accessories
High limt alarm
PV
value: 800℃
ON H OFF
AT@ Low limit alarm Low limt alarm PV ≤ alarm temperature, alarm is ON
PV
value:200℃
It will be ON when it detects sensor disconnection.
SBa_ Sensor break alarm ㅡ
Sensor break alarm does not have alarm option.
※ H : Alarm output hysteresis
٧٧Alarm option
First alarm condition is ignored. From the second alarm condition, standard alarm operates.
AT .C Standby sequence When power is ON and it is an alarm condition, it is ignored. From the second alarm condition,
KN-2000W
standard alarm operates.
If it is an alarm condition, it operates both alarm latch and standby sequence.
Alarm latch and
AT .D When power is ON and it is an alarm condition, it is ignored. From the second alarm condition,
standby sequence
alarm latch operates.
B-17
KN-2000W Series
Parameter initialization Display scale [ Program mode : L-SC, H-SC ]
To initialize all parameter as factory default, supply the For analog input, this function is to set (-19999 to 19999)
power to the product with pressing the ( and 1 keys for particular high/low limit value in order to display high/
at the same time and it enters initialization parameter. low limit value of measurement input. If measurement
inputs are ‘a’ and ‘b’ and particular values are ‘A’ and ‘B’, it
Press the ( + 1 keys will display a=A, b=B as below graphs.
at the same time.
Display Display Display
Supply the power. value value B value
B B
CLR A A
a b
a b a b A
( Input Input Input
value value value
NO YES Display
value
Display
value
Display
value A
B a b
( a b
A
A
Completes initialization.
a b B
B
Temperature unit [ Program mode : UNIT ] Input Input Input
value value value
Temperature unit (℃/℉) is selectable. When changing Display scale function is able to change display value for
temperature unit, user input range, display scale, output max./min. measured input by setting high limit scale
scale, alarm SV are initialized. You should set the param- [ H-SC] and low limit scale [ L-SC] in program mode.
eters again for your purpose.
※Ex) Set high/low scale value (input range is 0 to 10V)
※ When selecting analog input, temperature unit [ UNIT ]
parameter is not displayed. • L-SC= )00
• H-SC= %00, 1)00, 1%00, `)00
Front display unit [ Program mode : dUNT ] Display value
1%00
When selecting analog input, select the unit (%, °C, °F, not
display) of display value. 1)00
※ When not displaying unit, set OFF and it turns OFF all %00
indicators. Input value
0 10V
※ When selecting temperature sensor input, this param-
eter [ dUNT ] is not displayed. `)00
User input range [ Program mode : L-RG, H-RG ] • L-SC=1)00, H-SC= `)00
Display value
When selecting analog input, you can set the input range
for your purpose. Set low limit input value [ L-RG ] and 1%00
high limit input value [ H-RG ] to limit the input range. 1)00
• Set conditions :
Low limit input value [ L-RG ]+20%F.S. < High limit Input value
input value [ H-RG ] 0 10V
`)00
※ This parameter is displayed only for transmission output ※ When changing input type, high/low scale is changed as
(4-20 mA) model. But it is not displayed when selecting factory default.
temperature sensor input.
B-18
Multi Indicator
scale, and transmission scale the scale as H-SC: 3000, dP: )000.
This unit displays for 4 mA input as -76)0, and for 20 G. Temp.
The below figure is the example for 4 to 20 mA. mA input as #000. transmitter
L-RG= 6 H-RG= 16
User
input range
B-19
KN-2000W Series
Digital input [ Program mode: DI-T, DI-K ] ٧٧RUN mode and error display color
[ Program mode: CLOR ]
By digital input terminal [ DI-T ] (no. 6, 7 terminals) or
digital input key [ DI-K ] (D.IN3 : 4+3 for 3 sec.), one of Parameter Display color
three functions executes as the below table. SV RUN Error
Transmission
Parameter SV output Alarm output
D1 D2 D3 D4 D5 D6 D7 D8 (4-20 mA)
This function is to change display color for occurring error, : Enable to check/set
operating alarm automatically. User can check the status : Enable to check, disable to set,
of this unit directly. : Disable to check
※ Color of monitoring mode, program mode is red. ※In LOC2, only LOCK parameter displays in program
mode.
B-20
Multi Indicator
Communications A. Recorder
KN-1000B
KN-2000W
B-21
KN-2000W Series
Monitoring mode
※ 1. S :Press any key among the 1, 3, 4.
RUN mode ※ 2. 1 : Moves digits / 4, 3: Changes SV.
※ 3. Press the MODE key after checking/changing SV in each parameter.
The value flashes twice and is saved. It moves to next parameter.
Press MODE key.
※ After entering setting group, press the MODE key for 3 sec. or there is no additional key
operation in 30 sec., it returns to RUN mode.
※ : This parameter may or may not appear, depending on the other parameter settings.
Alarm 4 value
S
AL4 00)1
MODE
Program mode
※ 1. S :Press any key among the 1, 3, 4.
RUN mode
※ 2. 1 : Moves digits / 4, 3: Changes SV.
※ 3. Press the MODE key after checking/changing SV in each parameter.
Press MODE key The value flashes twice and is saved. It moves to next parameter.
for 3 sec. ※ After entering setting group, press the MODE key for 3 sec. or there is no additional key
operation in 30 sec., it returns to RUN mode.
※ : This parameter may or may not appear, depending on the other parameter settings.
Input type ※1 ※2
S
IN-P aMA2 Select input type. (Refer to 「Input type and range」.)
MODE MODE ※3
B-22
Multi Indicator
Decimal point
S Select decimal point position of display scale value.
dP )0 B. Indicator
MODE )0 )00 )000 0
C. Converter
Low limit
scale value
S Set low limit scale value.
L-SC 00)0 • Set range : -19999 to 19999
D. Controller
MODE
E. Thyristor
High limit unit
scale value
S Set high limit scale value.
H-SC 10)0 • Set range : -19999 to 19999
F. Pressure
MODE transmitter
G. Temp.
4 mA output ※ Displayed only for transmission output model. transmitter
scale value
S Set output scale value for 4 mA.
lOUT 00)0 • Set range : Temperature sensor input → within temperature range, H. Accessories
MODE
Analog input → L-SC to H-SC
20 mA output
scale value Set output scale value for 20 mA.
S
hOUT 10)0 • Set range: Temperature sensor input → within temperature range,
MODE Analog input → L-SC to H-SC
Input and transmission ※Displayed only when selecting analog input type.
output extension
S Select extension range of 4-20 mA input and transmission output.
EX.I0 SP
MODE SP 10P 0P
MODE
<Alarm mode> <Alarm option>
Set AL1 to S
AL4 alarm AL-1 AT!A AT!A KN-2000W
AL2 mode mode and MODE
MODE
S option.
AL-2 AT!A AL-2
MODE
AT@A AT!B
MODE
AL-3
MODE SBa_ AT!C
AL3 mode
S AL-4
AL-3 AT@A MODE AT)_ AT!D
MODE
Next parameter
AL output hysteresis
S Set alarm output hysteresis.
A-HY 001
• Set range : 001 to 999
MODE
※ When alarm mode [ AL-1 to AL-4 ] in program mode is no alarm [ AT)_ ] or
sensor break alarm [ SBa_ ], this parameter is not displayed.
Input correction
S Set input correction value.
IN-B 0000 • Set range : -999 to 999
MODE
B-23
KN-2000W Series
Digital filter
S Set the number of moving average digital filters.
MAvF 04
MODE
• Set range : 01 to 16
Display color
S Select display part color for RUN mode and error.
CLOR RED ※ Refer to「Display color」.
MODE
RED GRN YELO R--G G--R
Communication speed
S Select communication speed (baud rate).
BAUD (6K
MODE (6K 1(2K !2K @4K $8K
Communication write
S Select enable/disable to communication write.
COmW EnA (EnA:enable to write, DIsA:disable to write)
EnA DIsA
MODE
Lock
S Select lock function.
LOCK OFF
MODE OFF LOC1 LOC2
B-24
Multi Indicator
Monitoring mode
B. Indicator
Parameter Default Parameter Default Parameter Default
AL1 09(9 AL3 00)1 hPEK ---- C. Converter
Proper usage
B-25