Point of Application ● DI120-150 Detection ○ Speed CPU ● DI180-420 [Meaning] When the value obtained by computing floor table sum value in [Actions to take] NVRAM at one second interval is not identical with the SUM value memorized in NVRAM. 1. Try powering ON again. If any error exists in floor height Sum value in NVRAM [Diagram] when powering ON, EEPROM floor table is copied on to NVRAM NVRAM. Thus, TCD79 error should not occur after re-powering ON.
2. If TCD79 does not occur again after re-powering ON,
0x2000 the problem may have come from NVRAMFloor Height 1 data destruction owing to temporal mis-operation . (e.g. Noise, etc.), or . DOC-200 PCB Battery fault. . NVRAMFloor Height N 0x2108 Check the voltage of the battery fitted to BAT1 in NVRAM Unidentified Backup Area 0x2504 DOC-200 PCB. NVRAMFloor Height SUM 0x2508 Normally, battery voltage is DC +3.6[V]±0.2[V]~+2.5[V]. If a low voltage(+2.5[V] or less) is detected, replace the battery immediately. * Battery Housing Red Wire : “+”, NVRAMFloor Height 1~Floor Floor Height Table SUM B Black Wire : “-“(GND) Height N SUM A Recorded in NVRAM 3. If TCD 79 error exists even after re-powering ON, replace DOC-200 PCB since the error is coming from Are SUM A and No bad NVRAM. SUM B Identical?