You are on page 1of 8

i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 4 1 ( 2 0 1 4 ) 3 7 e4 4

Available online at www.sciencedirect.com

w w w . i i fi i r . o r g

journal homepage: www.elsevier.com/locate/ijrefrig

Mapping the energy consumption of household


refrigerators by varying the refrigerant charge and
the expansion restriction

Joel Boeng a,1, Cláudio Melo b,*


a
Whirlpool Latin America S.A., Dona Francisca St., 7.200, 89219-600 Joinville, SC, Brazil
b
POLO Research Laboratories for Emerging Technologies in Cooling and Thermophysics,
Department of Mechanical Engineering, Federal University of Santa Catarina, 88040-900 Florianópolis, SC, Brazil

article info abstract

Article history: In this work the thermodynamic behavior of a household refrigerator was experimentally
Received 21 December 2012 studied by simultaneously varying the refrigerant charge and the expansion restriction. A
Received in revised form special charging device was designed and constructed for this purpose comprised of a
13 May 2013 cylinder, a load cell and two solenoid valves. In addition, the original capillary tube was
Accepted 12 June 2013 replaced with a larger-diameter capillary tube and installed in series with a metering valve.
Available online 21 June 2013 The expansion restriction was varied by adjusting the capillary tubeemetering valve pair to
settings higher and lower than that of the original system. A total of 95 energy con-
Keywords: sumption measurements were recorded with different combinations of refrigerant charge
Household refrigerator and expansion restriction. A minimum energy consumption region comprised of several
Expansion combinations of refrigerant charge and expansion restriction was clearly identified. It was
Capillary also observed that an improper combination of expansion restriction and refrigerant
Refrigerant charge charge may increase the energy consumption by up to 30%.
Energy consumption ª 2013 Elsevier Ltd and IIR. All rights reserved.

Cartographie de la consommation énergétique des


réfrigérateurs domestiques grâce à la variation de la charge
frigorifique et la restriction de la détente
Mots clés : Réfrigérateurs domestiques ; Détente ; Capillaire ; Charge en frigorigène ; Consommation énergétique

* Corresponding author. Tel.: þ55 48 3234 5691; fax: þ55 48 3234 5166.
E-mail addresses: joel_boeng@whirlpool.com (J. Boeng), melo@polo.ufsc.br (C. Melo).
1
Tel.: þ55 47 3803 4062; fax: þ55 47 3803 4800.
0140-7007/$ e see front matter ª 2013 Elsevier Ltd and IIR. All rights reserved.
http://dx.doi.org/10.1016/j.ijrefrig.2013.06.005
38 i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 4 1 ( 2 0 1 4 ) 3 7 e4 4

Nomenclature Greek
s compressor duty cycle, dimensionless
Roman DT temperature difference, K
COP coefficient of performance, dimensionless
Subscripts
EC energy consumption, kWh month1
a ambient
Qe thermal load, W
e evaporation
Qt cooling capacity, W
coil evaporator surface
ton time of compressor on, s
comp compressor
toff time of compressor off, s
fan evaporator fan
T temperature, K
ff fresh food compartment
UA overall thermal conductance, WK1
fz freezer compartment
VP valve position, dimensionless
k compressor
W power, W
sup superheating
syst system

1. Introduction data points they concluded that the energy consumption had
a minimum for certain combinations of expansion restriction
In Brazil, household refrigeration is responsible for 30% of the and refrigerant charge and that this minimum was flat and
average household electricity consumption and this account wide. To the contrary of Dmitriyev and Pisarenko (1984, 1982)
for approximately 6% of the national electricity production. they also found that the optimum charge increases with lower
This relatively high fraction is due to the large number of units ambient temperatures.
in operation and also to the inherent low thermodynamic ef- This study follows very closely the research work of Björk
ficiencies of such products. and Palm (2006), but with some differences: i) the test sam-
It is well known that household refrigerators have highest ple is a top-mount refrigerator with a no-frost evaporator and
efficiency when operating with certain combinations of without a low side accumulator; ii) the energy consumption is
expansion restriction and refrigeration charge (Gonçalves and measured under steady-state conditions; and iii) the expan-
Melo, 2004; Vjacheslav et al., 2001). Such parameters are nor- sion restriction is substantially decreased in respect to that
mally determined at a late stage in the development process imposed by the original capillary tube.
after all other system components have been designed or
selected. The common procedure is to use a trial-and-error
approach, with the energy consumption measured according
2. Experimental apparatus
to the ISO 15502 (2007) standard. However, such a procedure is
time consuming e an energy consumption test may last more
The experimental apparatus is basically comprised of a
than 48 h e and does not always produce the expected results.
charging device connected to the suction and discharge lines,
Dmitriyev and Pisarenko (1982) suggested a method to
through which refrigerant is added to or removed from the
calculate the optimum refrigerant charge for household re-
system in a controllable way. In addition, the original internal
frigerators based only on the evaporator and condenser internal
heat exchanger, also known as the capillary tube-suction line
volumes. The authors concluded that regardless of the ambient
heat exchanger, was modified by replacing the original capillary
temperature, there was always a particular refrigerant charge
tube with another of the same length but with a larger internal
that provided the maximum coefficient of performance (COP).
diameter. A metering valve was also installed in series with the
Jakobsen (1995) simulated the effect of varying the expan-
capillary tube in order to vary the expansion restriction. This
sion restriction and the refrigerant charge on the COP of a
arrangement, which provides mass flow rates higher and lower
particular household refrigerator. He found that the COP was
than that provided by the original system, is shown in Fig. 1.
more sensitive to a deficit of charge and to an excess of
The experiments were carried out with a 403 L top-mount
expansion restriction than the opposite scenario.
refrigerator, originally charged with 47 g of HC-600a and
Vjacheslav et al. (2001) presented a model to estimate the
comprised of a 9.66 cm3 reciprocating-type compressor, a nat-
optimum refrigerant charge for refrigeration systems. The
ural draft wire and tube condenser, a tube-fin forced-draft no-
authors modeled each component separately, exploring the
frost evaporator, a concentric internal heat exchanger (2.05 m
effect of refrigerant charge on each of them and consequently
length) and a capillary tube (3.32 m length, 0.70 mm I.D.).
on the system performance. Similarly to Dmitriyev and
The charging device consisted essentially of a cylinder
Pisarenko (1984, 1982), they found that the system perfor-
suspended in a load cell from which refrigerant enters and
mance was strongly affected by the refrigerant charge.
exits under the control of two solenoid valves connected to
Björk and Palm (2006) conducted a series of experiments
the discharge and suction lines through two 0.9 mm I.D.
with a household refrigerator working under cyclic conditions
capillary tubes. The refrigerant pressure inside the cylinder,
in an attempt to identify the ideal combination of expansion
which corresponds to the saturation pressure at ambient
restriction and refrigerant charge. Based on a database of 600
temperature, always lies between the suction and discharge
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 4 1 ( 2 0 1 4 ) 3 7 e4 4 39

Fig. 1 e Schematic of the experimental apparatus.

pressures. Thus, refrigerant exits to feed the system through to manage both the charging device and the metering valve
the opening of the solenoid valve connected to the suction line was developed using the LabVIEW platform.
and returns from the system through the opening of the so- All experiments were carried out in a climate-controlled
lenoid valve connected to the discharge line. Refrigerant was chamber, constructed in accordance with the recommen-
added to and removed from the system several times in a row, dations of the ISO 15502 (2007) standard. Such a chamber is
when it was found that the amount of oil collected inside the capable of maintaining the air temperature at any value
cylinder was negligible. ranging from 18  C to 50  C, with a maximum uncertainty of
The expansion restriction was varied by a 3.25 mm I.D. 0.2  C. The relative humidity is also maintained at any
metering valve installed in series with a capillary tube. To this value within the range of 30e95%, with a maximum un-
end, the original capillary tube was replaced with a 0.83 mm certainty of 2% and 3% within a range of 0e90% and
I.D. capillary tube. This allowed higher or lower restrictions 90e100%, respectively. The air velocity at any point inside
with respect to that imposed by the original capillary tube. the chamber does not exceed 0.25 m s1, as required by the
The opening of the metering valve was controlled by a step standard.
motor in steps of 1.8 .
The air temperatures in the refrigerated compartments
and the room air temperature were measured by T-type 3. Experimental procedure
thermocouples embedded in standard-sized copper cylinders,
with a maximum uncertainty of 0.2  C. The refrigerant The experimental procedure consisted of measuring the en-
temperatures along with the refrigeration loop were also ergy consumption for different pairs of expansion restriction
measured by T-type thermocouples, attached to the pipe wall and refrigerant charge. The experiments started with the
with plastic straps and dielectric adhesive tape. Thermal paste metering valve fully open and with a refrigerant charge large
was used to decrease the contact resistance between the enough to establish the reference temperatures of 5  C and
thermocouples and the pipe wall. The suction and discharge 18  C in the fresh food and freezer compartments, respec-
pressures were measured by absolute pressure transducers, tively. Next the metering valve was gradually closed until the
with a maximum uncertainty of 0.04 bar. The refrigerant reference temperatures could no longer be attained. The valve
mass flow rate was measured by a Coriolis-type mass flow was then reset to the fully open position, a small amount of
meter installed in the discharge line, with a maximum un- refrigerant e around 3 g e was added to the system and the
certainty of 0.06 kg h1. The compressor, evaporator fan and test was restarted. The experiments ended when the refrig-
the electric heaters power was measured by a power trans- erant charge reached a limit, above which liquid droplets
ducer, with a maximum uncertainty of 1.5 W. The refrig- appear in the evaporator outlet and are ingested into the
erant mass contained in the charge cylinder was measured by compressor cylinder. The valve position increments were not
a 1 kg maximum capacity load cell, with a maximum uncer- constant, since the refrigerant mass flow rate is almost un-
tainty of 0.3 g. The transducer readings were acquired by a affected by the valve position at the beginning of the closing
computerized data acquisition system. A computer program cycle and strongly affected at the end.
40 i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 4 1 ( 2 0 1 4 ) 3 7 e4 4

3.1. Measurement of the energy consumption Finally, the coefficient of performance was expressed as:

The cooling capacity of a household refrigerator is higher than its Q_ e Q þ Wfan ðs  1Þ


COP ¼ ¼ t (6)
_
Wsyst EC
thermal load, usually to reduce the pull-down time e the length
of time needed to reach the reference temperatures after the first As shown by Hermes et al. (2013) this methodology provides
compressor start-up. After the initial transient period, the sys- results within 5% of those provided by the ISO 15502 (2007)
tem then normally works under oneoff cyclic conditions due to standard. More importantly the applied methodology follows
the excess of cooling capacity provided by the compressor. closely the experimental trends observed with the ISO cyclic
The energy consumption of any household refrigerator test procedure.
sold in the Brazilian market must be measured according to
the recommendations of the ISO 15502 (2007) standard. Ac-
cording to this standard two tests are performed, one above
and another below the reference temperatures, each of them 4. Results
lasting at least 24 h after steady-state periodic conditions are
reached. In order to avoid such a time consuming procedure The experiments were carried out according to the previously
an alternative steady-state methodology (Hermes et al., 2013) described methodology. In total, 95 experimental data points
was adopted in this work. were gathered. The minimum and maximum refrigerant
To this end the excess of cooling capacity was balanced by charges were 36.7 g and 64.7 g, respectively. The metering
PID-driven electric heaters installed in the refrigerated com- valve opening was varied between the fully open position (9.75
partments, while the thermostat was turned off and the turns) and the opening corresponding to 0.425 turns.
damper was maintained at the maximum position. The cabi-
net thermal load, Q_ t ; was then calculated from the fresh food 4.1. Effect of the expansion restriction
and freezer temperatures, Tff, Tfz, the ambient temperature,
Ta, and the overall thermal conductances of each compart- The expansion restriction was varied through the opening
ment, UAff, UAfz. The thermal conductances were obtained of the metering valve. The valve opening was related to the
beforehand from the so-called reverse heat leakage tests (Sim remaining number of turns required for total closure. The
and Ha, 2011). Under steady-state conditions the cabinet fully-open position corresponds to the 9.75 opening, while
thermal load was then expressed simply as: the fully-closed position corresponds to the zero opening.
  As the refrigerant mass flow rate does not vary linearly
Q_ t ¼ UAff Ta  Tff þ UAfz Ta  Tfz þ W
_ fan (1)
with the valve opening, the number of turns was correlated
where W _ fan is the evaporator fan power. with a position scale, varying between 0 and 11. The
The cooling capacity, Q_ e , was obtained by adding the opening-position relationship, obtained applying variations
thermal load and the electrical power released by the electric in the mass flow rate of around 0.04 kg h1, is shown in
heaters, W _ fz :
_ ff ; W Table 1.
The restriction data used in this work, expressed in
Q_ e ¼ Q_ t þ W
_ ff þ W
_ fz (2) numbers of turns or position, were converted into an equiv-
The times of compressor on (ton) and off (toff), were calcu- alent capillary tube, i.e., a capillary tube which supplies the
lated considering that all energy transferred into the refrig- same mass flow rate as the pair metering valveecapillary
erated compartments during an entire cycle is removed by the tube. This rather complex issue was addressed in another
compressor action (Hermes et al., 2009). article by Boeng and Melo (2012), and produced inner capillary
tube diameters ranging from 0.62 mm to 0.83 mm.

Q e $ton ¼ Q t $ton þ Q t  Wfan $toff (3) Fig. 2 shows the compression work and the refrigerant
mass flow rate as a function of valve position when the
Rearranging the previous equation for the compressor duty-
refrigerator was charged with 46.9 g of HC-600a. It is shown
cycle, s, yields:
that the compression work increases while the refrigerant
ton Q  Wfan mass flow rate decreases with increasing expansion restric-
sh y t (4) tion. This is so because with greater restriction the refrigerant
ton þ toff Q e  Wfan
tends to build-up in the condenser, which starves the evapo-
The energy consumption (EC) was then obtained by multi- rator. The evaporation pressure then decreases, the evapo-
plying the compressor duty-cycle and the system average rator superheating increases, the specific volume at the inlet
power consumption (Wsyst ¼ Wk þ Wfan ), as follows: of the compressor increases and consequently the mass flow
EC ¼ 0:72s$Wsyst (5) rate decreases. Moreover, the system pressure ratio increases,
thereby increasing the compression work and decreasing the
where 0.72 is the conversion factor from [W] to [kWh month1]. volumetric efficiency and mass flow rate.

Table 1 e Metering valve opening vs. position.


Opening [turns] 9.75 1.750 1.000 0.750 0.650 0.600 0.550 0.525 0.500 0.475 0.450 0.425
Position [e] 11 10 9 8 7 6 5 4 3 2 1 0
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 4 1 ( 2 0 1 4 ) 3 7 e4 4 41

143 1.5 2.3


VP=11
VP=9
VP=7
Compression work [kJ.kg ]

1.4
2.0
-1

141

Mass flow rate [kg.h ]


VP=5

Mass flow rate [kg.h ]

-1
-1
VP=3
VP=1
1.8
139 1.3

1.5
137 1.2

1.3

135 1.1
0 2 4 6 8 10 12
1.0
Valve position [-] 35 40 45 50 55 60 65

Fig. 2 e Compression work and mass flow rate vs. valve Refrigerant charge [g]
position. Fig. 4 e Mass flow rate vs. refrigerant charge.

The compression power, W _ k , results from the compression


Fig. 6 shows the cooling capacity, compression power and
work multiplied by the mass flow rate. Due to the contrasting
coefficient of performance as a function of refrigerant charge
response of these two parameters to the restriction variation,
at the maximum valve opening position (VP ¼ 11). It may be
the compression power tends to a maximum as illustrated in
noted that the minimum refrigerant charge at which the
Fig. 3. The cooling capacity, Q_ e , and the coefficient of perfor-
system is still able to reach the reference temperatures is
mance (COP) are also shown in Fig. 3 as a function of the
36.7 g. At this charge the cooling capacity is quite small since a
expansion restriction.
considerable fraction of the evaporator is occupied by vapor
refrigerant. As more refrigerant is added to the system the
4.2. Effect of the refrigerant charge evaporator is more properly filled with refrigerant and
consequently the cooling capacity increases. However, after a
The refrigerant charge was varied using a specially designed certain limit, the amount of refrigerant in the condenser also
and constructed charging device as previously mentioned. increases, thereby increasing the system pressure ratio and
Fig. 4 shows the mass flow rate as a function of refrigerant the compression power and decreasing the cooling capacity.
charge and valve position (VP). As more refrigerant is added to In short, at a fixed restriction, as more refrigerant is gradually
the system, more refrigerant is accumulated in the heat ex- added to the system the coefficient of performance passes
changers, thereby increasing the condensing and evaporating through a maximum, as shown in Fig. 6.
pressures and decreasing the evaporator superheating.
These combined effects decrease the specific volume at the 4.3. Combined effect of the refrigerant charge and
compressor inlet, thereby increasing the refrigerant mass flow expansion restriction
rate. It should be noted that this behavior is more pronounced
at lower restrictions when the evaporator overflows and liquid The cooling capacity is driven by the air temperature at the
refrigerant is carried to the suction line, reducing its temper- inlet of the evaporator and by the mean evaporator temper-
ature and the specific volume at the inlet of the compressor, as ature. The latter varies with the evaporation temperature and
shown in Fig. 5.

50
110 1.06

Qe
Suction line temperature [°C]

40
Capacity and power [W]

106 1.04

30
COP [-]

102 1.02
Wk
COP 20

98 1.00

10 VP=11
VP=7
VP=1
94 0.98
0 2 4 6 8 10 12
0
Valve position [-] 35 40 45 50 55 60 65
Refrigerant charge [g]
Fig. 3 e Cooling capacity, compression work and COP vs.
valve position. Fig. 5 e Suction line temperature vs. refrigerant charge.
42 i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 4 1 ( 2 0 1 4 ) 3 7 e4 4

120 1.1 112

COP VP=11
VP=5
107
Capacity and power [W]

1.0 VP=3

Cooling capacity [W]


110 Wk

COP [-]
102
0.9

100 Qe 97
0.8

92

90 0.7
35 40 45 50 55 60
87
Refrigerant charge [g] 35 40 45 50 55 60 65

Fig. 6 e Cooling capacity, compression power and COP vs. Refrigerant charge [g]
refrigerant charge. Fig. 8 e Cooling capacity vs. refrigerant charge.

superheating, while the former is held constant. Thus, it can


be concluded that the lower the evaporation temperature and minimum. Thereafter, an increase in the refrigerant charge
superheating the lower the evaporator mean temperature and increases the evaporation pressure and decreases the cooling
the higher the cooling capacity. Fig. 7 shows the mean evap- capacity. Thus, when more refrigerant is added to the system
orator temperature, Tcoil, and the evaporation temperature, Te, the expansion restriction must be increased in order to reduce
as a function of refrigerant charge. It can be observed that as the evaporation pressure and keep the cooling capacity at its
more refrigerant is added to the system, liquid builds-up in maximum value.
the evaporator, reducing the superheating and increasing the Fig. 10 shows the coefficient of performance for several
cooling capacity up to a maximum point. From this point on refrigerant charges and expansion restrictions. As also shown
the evaporator remains fully activated, but with a higher in Fig. 6, the coefficient of performance passes through a
mean temperature, which reduces the cooling capacity. maximum as more refrigerant is added to the system. As the
Fig. 8 shows the cooling capacity against the refrigerant expansion restriction increases, the maximum COP point is
charge and valve restriction. It is worth noting that at the shifted to the right, i.e., toward higher refrigerant charges.
lowest restriction (VP ¼ 11) the maximum cooling capacity is Fig. 11 illustrates the valve position at the maximum COP
reached with a charge of approximately 48 g. It can also be against the refrigerant charge. It can be seen that the expan-
noted that the maximum point is shifted to the right, i.e., to- sion restriction must be increased in order to keep the COP at
ward higher refrigerant charges, as the expansion restriction its maximum value when more refrigerant is added to the
increases. system. This behavior is similar to that shown in Fig. 8. It can
Fig. 9 shows the valve position at the maximum cooling also be seen that the COP again passes through a maximum.
capacity against the refrigerant charge. It can be observed that This occurs because a higher restriction decreases the mass
the optimum restriction decreases continuously with flow rate, which has two contrasting effects on the COP: (i) it
increasing refrigerant charge. When the charge increases the decreases the compression ratio; and (ii) it decreases the
refrigerant tends to accumulate in the evaporator, increasing cooling capacity. Until the maximum point, the effect of
the cooling capacity until the superheating reaches a lowering the compression ratio prevails over the effect of the

12 112
Cooling capacity [W]

10
108
Cooling capacity [W]
Valve position [-]

8
104

100
4

96
2

0 92
35 40 45 50 55 60 65
Refrigerant charge [g] Refrigerant charge [g]

Fig. 7 e Mean evaporator temperature and cooling capacity Fig. 9 e Valve position at maximum cooling capacity vs.
vs. refrigerant charge. refrigerant charge.
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 4 1 ( 2 0 1 4 ) 3 7 e4 4 43

1.1 12

10
1.0 Qe

Valve position [-]


8
COP
COP [-]

0.9 6

4
0.8 VP=11
VP=9
VP=7 2
VP=5

0.7 0
35 40 45 50 55 60 65 35 40 45 50 55 60 65
Refrigerant charge [g] Refrigerant charge [g]
Fig. 10 e COP vs. refrigerant charge. Fig. 12 e Valve position at maximum COP and maximum
cooling capacity vs. refrigerant charge.

reducing the cooling capacity, and after this point the opposite
behavior is observed. central part of the figure, correspond to regions of low energy
Fig. 12 shows the valve position at the maximum COP and consumption. The successive contour lines correspond to re-
maximum cooling capacity against the refrigerant charge. It is gions of higher energy consumption which increase with the
worth noting that the charge-restriction pairs which provide distance from the central region.
the maximum capacity and the maximum COP do not match. It is worth noting that the minimum energy consumption
For a given refrigerant charge, the restriction that maximizes region (50e52 kWh month1) is quite wide. It can also be noted
the COP is always less than that which maximizes the cooling that at the lowest restrictions, between positions 4 and 11, the
capacity. Likewise, for the same restriction the charge that optimum energy consumption is almost unaffected by the
maximizes the COP is always less than that which maximizes expansion restriction. It can also be seen that at the highest
the cooling capacity. This is because the refrigerant charge restrictions, between positions 0 and 4, there is a nearly linear
affects both the cooling capacity and the compression power, relationship between the optimum restriction and the refrig-
parameters which have contrasting effects on the coefficient erant charge. Such behavior is quite similar to that observed
of performance. by Björk and Palm (2006), despite the dissimilarities of the
Fig. 13 shows a contour map of energy consumption refrigerator models.
plotted using the valve position and the refrigerant charge as Below position 4, any additional restriction causes an
the graph coordinates. This map is composed of contour lines accumulation of refrigerant in the condenser and a lack of
e lines which delimit regions of equal energy consumption e refrigerant in the evaporator, thereby increasing the super-
obtained by the Multi-quadric Radial Basis Function Interpo- heating and decreasing the evaporation pressure and the
lation Method (Wright, 2003).
Each contour line, represented by a color scale ranging
from blue to red, corresponds to a range of energy consump-
tion values. The blue regions, which are predominant in the

12 1.08

10
Maximum COP [-]
Valve position [-]

8 1.04

4 1.00

0 0.96
35 40 45 50 55 60 65
Refrigerant charge [g]

Fig. 11 e Valve position at maximum COP vs. refrigerant Fig. 13 e Energy consumption vs. refrigerant charge and
charge. valve position.
44 i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 4 1 ( 2 0 1 4 ) 3 7 e4 4

system performance. This effect is compensated for by adding which suggests a common behavior for most household
more refrigerant to the system. From another perspective, an refrigerators;
increased refrigerant charge results in evaporator overflow  A methodology to find the optimum operation point in
and decreases the suction line temperature, with a negative terms of refrigerant charge and expansion restriction based
effect on the system performance. To compensate for this on a small amount of experimental data was also developed,
effect the restriction of the expansion device is increased. but it is out of the scope of this paper.
At the lowest restrictions the system is less sensitive to the
refrigerant charge. Björk and Palm (2006) explained this
behavior focusing on the low-side accumulator that would
prevent both superheating and the suction line being too cold, Acknowledgments
both having negative effects on the system performance.
However, it should be emphasized that the refrigerator used This study was carried out at the POLO Laboratories under
in this study does not have a low-side accumulator, and so National Grant No. 573581/2008-8 (National Institute of Sci-
another explanation is needed. ence and Technology in Cooling and Thermophysics) funded
The distinct behavior above and below position 4 can be by the Brazilian Government Agency CNPq. The authors thank
explained by the refrigerant state at the entrance of the Embraco S.A for financial support.
capillary tube. At higher restrictions there is a liquid seal at
the entrance of the capillary, and therefore this component
references
effectively rules the refrigerant mass flow rate and the system
performance (active action). In this region the system
really runs in steady-state regime, which means that the
Boeng, J., 2012. A Methodology to Select the Optimum Pair
compressor and the capillary tube mass flow rates are equal.
Capillary TubeeRefrigerant Charge for Household
At lower restrictions, the liquid seal is broken and the mass Refrigerators. M.Sc. Dissertation. Federal University of Santa
flow rate and system performance are now ruled by the Catarina.
amount of vapor allowed to enter the tube along with the Boeng, J., Melo, C., 2012. A capillary tubeerefrigerant charge
liquid (passive action). In this region the compressor and the design methodology for household refrigerators e part II:
capillary tube mass flow rates vary within a cycle period of equivalent diameter and test procedure. In: Proceedings of the
approximately 4 s in an attempt to match each other. This 14th International Refrigeration and Air Conditioning
Conference at Purdue, West Lafayette, USA.
creates an intermittent flow at the entrance of the capillary
Björk, E., Palm, B., 2006. Performance of a domestic refrigerator
tube, giving a macroscopic and false impression that the under influence of varied expansion device capacity,
system is in steady-state conditions (Boeng, 2012). refrigerant charge and ambient temperature. Int. J.
Refrigeration 29 (5), 789e798.
Dmitriyev, V.I., Pisarenko, V.E., 1982. Determination of optimum
5. Concluding remarks refrigerant charge for domestic refrigerator units. Int. J.
Refrigeration 7 (3), 178e180.
Gonçalves, J.M., Melo, C., 2004. Experimental and numerical
This research provided insights related to the household
steady-state analysis of a top-mount refrigerator. In:
refrigeration sector. Some of them are listed below: Proceedings of the 10th International Refrigeration and Air
Conditioning Conference at Purdue, West Lafayette, USA.
 A minimum energy consumption region, comprised of Hermes, C.J.L., Melo, C., Knabben, F.T., 2013. Alternative test
several combinations of refrigerant charge and expansion method to assess the energy consumption of frost-free
restriction, was identified. It was also observed that an household refrigerating appliances. Appl. Therm. Eng. 50,
1029e1034.
inappropriate combination of expansion restriction and
Hermes, C.J.L., Melo, C., Knabben, F.T., Gonçalves, J.M., 2009.
refrigerant charge may increase the energy consumption by
Prediction of the energy consumption of household
up to 30%; refrigerators and freezers via steady-state simulation. Appl.
 A deficit of charge or an excess of restriction increases the Energ. 86, 1311e1319.
evaporator superheating. On the other hand, an excess of ISO/FDIS 15502, 2007. Household Refrigerating Appliances e
charge or a small restriction leads to evaporator overflow Characteristics and Test Methods. International Organization
and decreases the suction line temperature. In both cases for Standardization, Genebra, Switzerland.
Jakobsen, A., 1995. Energy Optimization of Refrigeration Systems.
the cooling capacity and the energy consumption are
The Domestic Refrigerator e a Case Study. Ph.D. thesis. The
penalized; Technical University of Denmark.
 The product energy consumption was completely mapped Sim, J.S., Ha, J.S., 2011. Experimental study of heat transfer
since the replacement of the capillary tube resulted in mass characteristics for a refrigerator by using reverse heat loss
flow rates considerable higher than those supplied by method. Int. Commun. Heat Mass Transf. 38, 572e576.
the original system. This was a limitation of the work of Vjacheslav, N., Rozhentsev, A., Wang, C., 2001. Rationally based
model for evaluating the optimal refrigerant mass charge in
Björk and Palm (2006), who were unable to substantially
refrigerating machines. Energ. Convers. Manage. 42 (18),
decrease the expansion restriction;
2083e2095.
 Despite the dissimilarities between the refrigerator used in Wright, G.B., 2003. Radial Basis Function Interpolation: Numerical
this study and that used by Björk and Palm (2006), there and Analytical Developments. Ph.D. thesis. University of
is clearly a similarity in the energy consumption maps, Colorado, USA.

You might also like